Weidmuller Analog Signal Conditioners

Download as pdf or txt
Download as pdf or txt
You are on page 1of 65

SSB_J_manuelle_S_GB.xpr5 16.10.

2003 11:15 Uhr Seite 2

Analogue Signal Processing

Analogue Signal Processing

Analogue signal processing

Problems
The real environment can be measured in many different
forms, for example in terms of temperature, humidity or air
pressure. The values of these physical variables change con-
stantly. Elements which monitor the statuses and status
changes of a given environment and supply an indication of
this changed environment must be able to portray the continu-
ous change.

In industrial monitoring tasks, sensors are responsible for reg-


istering ambient statuses. Sensors provide signals which allow
detailed conclusions for downstream evaluation and monitor-
ing systems with detailed conclusions about the statuses or
status changes, for example in a production process. Sensor
signals monitor continuous changes in the monitored field.
They occur in digital and analogue form. As a rule, they supply
an electrical voltage or current value which corresponds pro-
portionally to the physical variables being monitored.

If automation processes are expected to reach certain status-


es or keep them Constant, then analogue signal processing is
required. It is also important in areas where this is has already
The product programme contains the following functions:
been part of long established practice, for example process
engineering or the chemicals industry. • dc/dc converters
• Current converters
In process engineering, standardised electrical signals are nor- • Voltage converters
mally used. Currents from 0… 20 mA, 4… 20 mA or voltages
from 0..10 V have become established as the output variable • Temperature transformers for resistance thermometers and
for sensors of various different physical parameters. thermoelements
• Frequency converters

Weidmüller takes account of the continuing trend to automate • Potentiometer transducers


– including and in particular with analogue signal processing – • ac transducers
and offers a wide range of products tailor-made to the require-
• Bridge transducers (strain gauges)
ments involved in handling sensor signals. Units for the com-
mon signals (0..20 mA, 4..20 mA, 0..10 V) generate an output • Threshold monitoring modules
J signal as proportional values of the variable input signal. • AD/DA converters
“Protective separation” e.g. of the sensor circuit from the eval-
uation circuit is also taken into account. “Protective separa-
tion” prevents mutual interference of several sensor circuits, for The stated products are available as pure signal conversion,
example as in the case of earth ground circuits in linked meas- 2-way isolation, 3-way isolation and passive disconnectors –
uring circuits. depending on the production functions in each case.

The wide range of products completely covers the functions


involved in signal conversion, signal separation and signal
monitoring. The products thus satisfy nearly all applications in
industrial measuring technology, and safeguard elementary
functions between field signals and further processing sys-
tems. The mechanical properties of the products are built up
around a continuous concept.

Signal converters can be used with other Weidmüller products


and combined with each other. They are designed from an
electrical and mechanical point of view so as to entail a mini-
mum wiring workload and maintenance.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 16.10.2003 11:16 Uhr Seite 3

Analogue Signal Processing


Analogue Signal Processing

Weidmüller interface units

2-way isolation separates the signals and decouples the measuring cir-
cuits. Potential differences, caused by long line leads and joint reference
points, are eliminated. Signal isolation also protects from destruction by
overvoltage together with inductive and capacitive gaps.

3-way isolation also separates the supply voltage to the input and out-
put circuit and allows for operation with only one operating voltage.

Passive isolators have another crucial advantage: they do not need any
additional power supply. The power supply for the module comes from the
input or output circuit and is transferred to the input/output. The outstand-
ing feature of this current loop feed is its very low own consumption.

There is a wide range of products for measuring temperature. PT100 sig-


nals are converted in 2, 3 and 4-conductor system to standardised signals
0-20 mA, 4-20 mA and 0-10 V.

The modules for connecting to commercially available thermocouples


have cold joint compensation as a standard feature. In addition, they
amplify and linearise the voltage signal issued by the thermocouple. This
guarantees exact conditioning of the analogue signal, eliminating interfer-
ence or fault sources.

Frequency converters convert frequency into analogue standard signals


so that subsequent controllers can directly process pulse sequences for
speed or velocity measurement.

No kind of automation is conceivable without AD or DA converters. To


bring together the analogue signals which portray the environment with
the digital processing of the process monitoring system, analogue signals
have to be converted into digital ones. Weidmüller also offers these mod- J
ules for the common input and output signals 0 … 20 mA, 4 … 20 mA
and 0 … 10 V, with 8 bit or 12 bit available on the digital side. All modules
have an additional input for freezing the current measured value.

Current monitoring modules control the current values up to 60 A for


dc or ac current. If the values fall below or above the setting, then the
switch output is triggered. Modules with analogue outputs monitor the
current flow continuously using subsequent controllers.

Voltage monitoring modules are used to monitor dc and ac voltage.


The freely adjustable switching threshold can be used to detect and report
fluctuations in voltage as a result of switching procedures or mains over-
load.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 16.10.2003 11:16 Uhr Seite 4

Analogue Signal Processing

Advantages of the WAVESERIES

The concept Replacement Cross connection

The modules in the WAVESERIES are The PCB can be removed from the Cross connectors are
ideal when users need analogue sep- enclosure without any tools. Simple used to connect up
arating transducers. Weidmüller’s press in the locking hook at the top sec- enclosures in the
WAVESEREIS combines the com- tion and pull out the upper part with same family to
pact, space-saving design of the connection level and PCB. bridge and
enclosure type (WAVEBOX) with transmit the
many different functions. The product power supply from
family offers a wide range of signal one module to the next.
transducers.
• Independent connection technolo-
gy – screw or spring with pluggable
socket connector
• Assembly without tools
• Fast commissioning – pluggable
spare boards
• Standardised current and voltage
signals
• Cross connectors for low wiring
workload
• Highly functional
• Clear type designations for simple
selection
• Ideal size – for more space in the
switchgear cabinet
• Cost-saving

Enclosure (WAVEBOX) Coding Safety

The WAVEBOX is an ideal combination The coding elements can be used to “Protective separation” has to be guar-
of technology, design and functionality. code the module for screw and also anteed as per EN 50178. WAVESERIES
The enclosure consists of recyclable tension clamp connections without loss complies with this requirement to the full
plastic and comes in four different of poles. In this way, it is not possible with analogue signal transmission with
widths. It needs practically no tools for to confuse the plugs. potential separation.
assembly and fulfils the EMC require- Connecting
ments. Ventilation slots allow good heat Screw connection BLZ and the tension
dissipation. clamp system BLZF offer the greatest
possible flexibility in the wiring stage (up
to 2.5 mm2).

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 16.10.2003 11:16 Uhr Seite 5

Analogue Signal Processing


Advantages of the MICROSERIES and MCZ SERIES

Connecting Cross connection Width

Screw connection BLZ and the tension The supply voltage can be MICROANALOGUE sets standards for ana-
clamp system BLZF offer the greatest bridged from one module logue signal processing. With a width of
possible flexibility in the wiring stage (up to the next. just 6 mm, MICROSERIES is highly
to 2.5 mm2). functional with a completely closed
enclosure.

Connecting Cross connection

Tension spring connection The power supply and another potential


can be cross connected

Width

Just 6 mm wide (without cover plate),


the MCZ SERIES offers enough space
for electronic circuits.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.6

DC/DC passive isolator

Input current loop-fed MCZ CCC


Signal converter

Passive isolator for electrical isolation of standard


0/4…20 mA signals. It is fed by the measuring
signal and does not need any auxiliary power
supply. Special features of this component are its
low power consumption and the operating current
of <100 µA.

4 2
- -

IN
OUT C C Z
Z
18V
5 18V 1
+ +

Technical data
Input
Input voltage/Input current /0(4)…20 mA current loop
Max. voltage/Max. current 15 V/50 mA
Operating current < 100 µA
Voltage drop 2.5….3 V at 20 mA
Output
Output voltage/Output current /0(4)…20 mA
Load resistance voltage/Current /< = 500 M
Accuracy < 0.1 % of final value
Temperature coefficient <50ppm/K of measurem. value at 0M load resist.
Influence of load impedance 0.05 % of measurement value/100 M load resistance
Residual ripple < 10 mVeff
Chopper frequency Approx. 200 kHz
General data
Operation temperature -25 °C…+60 °C
Storage temperature -40 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 60529, EN 61010-1
EMC standards EN 50081-1, EN 50082-2
Isolation voltage Input, output 510 Veff

Dimensions Tension clamp c.


Clamping range (rating- / min. / max.) mm2 1.50 / 0.50 / 1.50
Length x width x height mm 91.0 x 6.0 x 63.2
Information

Ordering data
Type of connection Type Qty. Order No.
Tension clamp c. MCZ CCC 0-20mA/0-20mA 10 8411190000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.7

DC/DC passive isolator

Input current loop-fed CCC LP CCC LP

Signal converter
• Galvanic isolation (1-channel) (2-channel)
• Very low power consumption
• Secure disconnection

14
12
10
U E [V]

8
6
4
2
0
0 100 200 300 400 500 600
RL

Technical data
Input
Input voltage/Input current /0(4)…20 mA current loop /0(4)…20 mA current loop
Max. voltage/Max. current 18 V/50 mA 18 V/50 mA
Operating current < 100 µA < 100 µA
Voltage drop approx. 3V at RL=0 M; approx. 13V at RL=500 M;(Iin=20mA) approx. 3V at RL=0 M; approx. 13V at RL=500 M;(Iin=20mA)
Output
Output voltage/Output current /0(4)…20 mA /0(4)…20 mA
Load resistance voltage/Current /< = 500 M /< = 500 M
Accuracy < 0.1 % of final value < 0.1 % of final value
Temperature coefficient < 50 ppm/K of final value < 50 ppm/K of final value
Influence of load impedance < 0.1 % of measurement value/100 M load resistance < 0.1 % of measurement value/100 M load resistance
Residual ripple < 20 mVeff < 20 mVeff
Chopper frequency approx. 170 kHz approx. 170 kHz
General data
Operation temperature -25 °C…+70 °C -25 °C…+70 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CSA / GL / UL/UR / CE / ESD CSA / GL / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 (safe separation) EN 50178 (safe separation)
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V
Impulse withstand voltage 6 kV 6 kV
Isolation voltage Input, output 4 kVeff / 1 s 4 kVeff / 1 s
Overvoltage category III III
Pollution severity 2 2 J
Clearance & creepage path >= 5.5 mm >= 5.5 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection WAS5 CCC LP 0-20/0-20mA 1 8444950000 WAS5 CCC LP 0-20/0-20mA 1 8463580000
Tension clamp c. WAZ5 CCC LP 0-20/0-20mA 1 8444960000 WAZ5 CCC LP 0-20/0-20mA 1 8463590000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.8

DC/DC passive isolator

Output current loop-fed OLP


Signal converter

• Galvanic isolation
• Very low power consumption
• Input range selected via DIP switch
• Calibration not necessary

Switch position/setting options


SW 1
Input 1 2 3 4
0…20 mA    
4…20 mA    
0…5 V    
0…10 V    
Transmission frequency
10 Hz    
100 Hz    

Technical data  = on
Input  = off
Input voltage 0…(5)10 V
Max. voltage 30 Vdc
Input resistance voltage/Current 0…5V: 210 kM; 0…10V: 430 kM/51 M
Input current 0(4)…20 mA
Max. current 40 mA
Output
Output current 4…20 mA (current loop)
Output signal limit approx. 24 mA
Load resistance voltage/Current /RL=(Ub-12V) / 20 mA e.g. 600 M at 24V
Accuracy 0.2 % of measuring range final value
Temperature coefficient <= 150 ppm/K
Residual ripple 50 mVeff at 500 M
Step response time < 10 Hz: 80 ms; 100 Hz: 50 ms
Cut-off freq. (-3dB) 10 Hz/ 100 Hz switchable
General data
Supply voltage min. 12 Vdc/ max. 30 Vdc
Operation temperature 0 °C…+55 °C (fitted)
Storage temperature -20 °C…+85 °C
Default settings 0…20mA, 10 Hz
Approvals CE / ESD / cURus
Insulation coordinates
Standards EN 50178
EMC standards EN 50082-2, EN 50081-1, -2, EN 55011
J Rated voltage 300 V
Impulse withstand voltage 4 kV
Isolation voltage Input, output 4 kVeff / 5s
Overvoltage category III
Pollution severity 2
Clearance & creepage path >= 5.5 mm

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS5 OLP 1 8543720000
Tension clamp c. WAZ5 OLP 1 8543730000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.9

DC/DC passive isolator

Loop splitter 2OLP

Signal converter
• Galvanic isolation
• Input and output current loop feed
• Very low power consumption
• Calibration not necessary

Technical data
Input
Input current 4…20 mA (current loop)
Max. current 40 mA
Voltage drop 3.8 V
Output
Output current/ 2 x 4…20 mA (current loop)/
Output signal limit approx. 31 mA
Load resistance voltage/Current /RL=(Ub-12V) / 20 mA e.g. 600 M at 24V
Accuracy typical 0.1%, max. 0.2%
Temperature coefficient <= 150 ppm/K
Step response time < 20 ms
Cut-off freq. (-3dB) 30 Hz
General data
Supply voltage min. 12 Vdc/ max. 30 Vdc 24Vd
Operation temperature 0 °C…+55 °C (fitted)
Storage temperature -20 °C…+85 °C Sensor
Approvals CE / ESD / cURus 230 Vac
Insulation coordinates ~
24 Vdc
Standards EN 50178
EMC standards EN 50082-2, EN 50081-1, -2, EN 55011
4 ... 20mA
Rated voltage 300 V
Impulse withstand voltage 4 kV
Isolation voltage Input, output/ 4 kVeff / 5s/
Overvoltage category III
Pollution severity 2
1
2
WAVEANALOG
2OLP
3 8581160000/8581170000
7
8
9
10
11
12 J
Clearance & creepage path >= 5.5 mm

4 ... 20mA
4 ... 20mA

RL2

SPS
RL1

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS5 CCC 2OLP 1 8581160000
Tension clamp c. WAZ5 CCC 2OLP 1 8581170000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.10

DC/DC 2-way isolator

Power supply on the 4…20mA/4…20mA 4…20mA/0…20mA 4…20mA/0…10V


output side
Signal converter

• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current /4…20 mA (current loop) /4…20 mA (current loop) /4…20 mA (current loop)
Max. voltage 7V 7V 7V
Max. current 25 mA 25 mA 25 mA
Output
Output voltage/Output current /4…20 mA /0…20 mA 0…10 V/
Load resistance voltage/Current /< = 500 M /< = 500 M >= 1 kM/
Accuracy +/- 0.2% of final value +/- 0.2% of final value +/- 0.2% of final value
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of final value <= 250 ppm/K of final value
Step response time <= 30 ms (typically 20 ms) <= 30 ms (typically 20 ms) <= 30 ms (typically 20 ms)
Cut-off freq. (-3dB) >= 15 Hz (typically 20 Hz) >= 15 Hz (typically 20 Hz) >= 15 Hz (typically 20 Hz)
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption < 32 mA at Iout = 20 mA < 32 mA at Iout = 20 mA < 20 mA at Iout = 10 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C (fitted) 0 °C…+55 °C (fitted) 0 °C…+55 °C (fitted)
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V 300 V
Impulse withstand voltage 4 kV 4 kV 4 kV
Isolation voltage Input, output/ 1.2 kVeff / 5s/ 1.2 kVeff / 5s/ 1.2 kVeff / 5s/
J Overvoltage category III III III
Pollution severity 2 2 2
Clearance & creepage path >= 3 mm >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c. Screw connection Tension clamp c.
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS4 CCC DC 4-20/4-20MA 8444980000 WAS4 CCC DC 4-20/0-20MA 8445010000 WAS4 CVC DC 4-20/0-10V 8445040000
Tension clamp c. WAZ4 CCC DC 4-20/4-20MA 8444990000 WAZ4 CCC DC 4-20/0-20MA 8445020000 WAZ4 CVC DC 4-20/0-10V 8445050000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.11

DC/DC 2-way isolator

Double sided power 0…20mA/0…20mA 0…20mA/4…20mA 0…20mA/0…10V


supply

Signal converter
• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current /0…20 mA /0…20 mA /0…20 mA
Max. voltage/Max. current /25 mA /25 mA /25 mA
Input resistance voltage/Current /50 M /50 M /50 M
Output
Output voltage/Output current /0…20 mA /4…20 mA 0…10 V/
Load resistance voltage/Current /< = 500 M /< = 500 M >= 1 kM/
Accuracy +/- 0.2% of final value +/- 0.2% of final value +/- 0.2% of final value
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of final value <= 250 ppm/K of final value
Step response time <= 30 ms (typically 16 ms) <= 30 ms (typically 16 ms) <= 30 ms (typically 16 ms)
Cut-off freq. (-3dB) >= 15 Hz (typically 25 Hz) >= 15 Hz (typically 25 Hz) >= 15 Hz (typically 25 Hz)
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption input < 11 mA at Iin = 20 mA < 11 mA at Iin = 20 mA < 11 mA at Iin = 20 mA
Current consumption output < 32 mA at Iout = 20 mA < 32 mA at Iout = 20 mA < 20 mA at Iout = 10 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C (fitted) 0 °C…+55 °C (fitted) 0 °C…+55 °C (fitted)
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V 300 V
Impulse withstand voltage 4 kV 4 kV 4 kV
Isolation voltage Input, output 1.2 kVeff / 5s 1.2 kVeff / 5s 1.2 kVeff / 5s J
Overvoltage category III III III
Pollution severity 2 2 2
Clearance & creepage path >= 3 mm >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c. Screw connection Tension clamp c.
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS4 CCC DC 0-20/0-20MA 8445070000 WAS4 CCC DC 0-20/4-20MA 8446970000 WAS4 CVC DC 0-20/0-10V 8447020000
Tension clamp c. WAZ4 CCC DC 0-20/0-20MA 8445080000 WAZ4 CCC DC 0-20/4-20MA 8446990000 WAZ4 CVC DC 0-20/0-10V 8447030000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.12

DC/DC 2-way isolator

Double sided power 0…10V/0…20mA 0…10V/4…20mA 0…10V/0…10V


supply
Signal converter

• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current 0…10 V/ 0…10 V/ 0…10 V/
Max. voltage/Max. current 15 V/ 15 V/ 15 V/
Input resistance voltage/Current 500 kM/ 500 kM/ 500 kM/
Output
Output voltage/Output current /0…20 mA /4…20 mA 0…10 V/
Load resistance voltage/Current /< = 500 M /< = 500 M >= 1 kM/
Accuracy +/- 0.2% of final value +/- 0.2% of final value +/- 0.2% of final value
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of final value <= 250 ppm/K of final value
Step response time <= 30 ms (typically 25 ms) <= 30 ms (typically 25 ms) <= 30 ms (typically 25 ms)
Cut-off freq. (-3dB) >= 13 Hz (typically 17 Hz) >= 13 Hz (typically 17 Hz) >= 13 Hz (typically 17 Hz)
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption input < 11 mA at Uin = 10 V < 11 mA at Uin = 10 V < 11 mA at Uin = 10 V
Current consumption output < 32 mA at Iout = 20 mA < 32 mA at Iout = 20 mA < 20 mA at Iout = 10 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C (fitted) 0 °C…+55 °C (fitted) 0 °C…+55 °C (fitted)
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V 300 V
Impulse withstand voltage 4 kV 4 kV 4 kV
J Isolation voltage Input, output 1.2 kVeff / 5s 1.2 kVeff / 5s 1.2 kVeff / 5s
Overvoltage category III III III
Pollution severity 2 2 2
Clearance & creepage path >= 3 mm >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c. Screw connection Tension clamp c.
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS4 VCC DC 0-10/0-20MA 8447050000 WAS4 VCC DC 0-10/4-20MA 8447100000 WAS4 VVC DC 0-10/0-10V 8447130000
Tension clamp c. WAZ4 VCC DC 0-10/0-20MA 8447080000 WAZ4 VCC DC 0-10/4-20MA 8447110000 WAZ4 VVC DC 0-10/0-10V 8447140000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.13

DC/DC 3-way isolator

10Hz Cut-off frequency 0…(4)20mA/0…(4)20mA 0…20mA/4…20mA 0…20mA/0…10V

Signal converter
• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current /0(4)…20 mA /0…20 mA /0…20 mA
Max. voltage
Max. current 25 mA 25 mA 25 mA
Output
Output voltage/Output current /0(4)…20 mA /4…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M /< = 600 M >= 1 kM/
Accuracy 0.2 % 0.2 % 0.2 %
Temperature coefficient +/- 250 ppm/K +/- 250 ppm/K +/- 250 ppm/K
Step response time <= 45 ms <= 45 ms <= 45 ms
Cut-off freq. (-3dB) 10 Hz 10 Hz 10 Hz
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.5 W at Iout = 20 mA < 1.5 W at Iout = 20 mA < 1.3 W at Iout = 5 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C (horiz. mounting) 0 °C…+55 °C (horiz. mounting) 0 °C…+55 °C (horiz. mounting)
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CE / cURus CE / cURus CE / cURus
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V 300 V
Impulse withstand voltage 4 kV 4 kV 4 kV
Isolation voltage Input, output/ 2 kVeff / 5s/ 2 kVeff / 5s/ 2 kVeff / 5s/
Overvoltage category III III III J
Pollution severity 2 2 2
Clearance & creepage path >= 3 mm >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c. Screw connection Tension clamp c.
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 CCC 0-20/0-20mA 8540180000 WAS5 CCC 0-20/4-20mA 8540250000 WAS5 CVC 0-20mA/0-10V 8540270000
Tension clamp c. WAZ5 CCC 0-20/0-20mA 8540190000 WAZ5 CCC 0-20/4-20mA 8540260000 WAZ5 CVC 0-20mA/0-10V 8540280000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.14

DC/DC 3-way isolator

10Hz Cut-off frequency 4…20mA/0…20mA 4…20mA/0…10V


Signal converter

• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current /4…20 mA /4…20 mA
Max. voltage
Max. current 25 mA 25 mA
Output
Output voltage/Output current /0…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M >= 1 kM/
Accuracy 0.2 % 0.2 %
Temperature coefficient +/- 250 ppm/K +/- 250 ppm/K
Step response time <= 45 ms <= 45 ms
Cut-off freq. (-3dB) 10 Hz 10 Hz
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.5 W at Iout = 20 mA < 1.3 W at Iout = 5 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C (horiz. mounting) 0 °C…+55 °C (horiz. mounting)
Storage temperature -20 °C…+85 °C -20 °C…+85 °C
Approvals CE / cURus CE / cURus
Insulation coordinates
Standards EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V
Impulse withstand voltage 4 kV 4 kV
Isolation voltage Input, output/ 2 kVeff / 5s/ 2 kVeff / 5s/
J Overvoltage category III III
Pollution severity 2 2
Clearance & creepage path >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 CCC 4-20/0-20MA 8540200000 WAS5 CVC 4-20mA/0-10V 8540230000
Tension clamp c. WAZ5 CCC 4-20/0-20MA 8540210000 WAZ5 CVC 4-20mA/0-10V 8540240000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.15

DC/DC 3-way isolator

10Hz Cut-off frequency 0…10V/0…20mA 0…10V/4…20mA 0…10V/0…10V

Signal converter
• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current 0…10 V/ 0…10 V/ 0…10 V/
Max. voltage 15 V 15 V 15 V
Max. current
Output
Output voltage/Output current /0…20 mA /4…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M /< = 600 M >= 1 kM/
Accuracy 0.2 % 0.2 % 0.2 %
Temperature coefficient +/- 250 ppm/K +/- 250 ppm/K +/- 250 ppm/K
Step response time <= 45 ms <= 45 ms <= 45 ms
Cut-off freq. (-3dB) 10 Hz 10 Hz 10 Hz
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.5 W at Iout = 20 mA < 1.5 W at Iout = 20 mA < 1.3 W at Iout = 5 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C (horiz. mounting) 0 °C…+55 °C (horiz. mounting) 0 °C…+55 °C (horiz. mounting)
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CE / cURus CE / cURus CE / cURus
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V 300 V
Impulse withstand voltage 4 kV 4 kV 4 kV
Isolation voltage Input, output/ 2 kVeff / 5s/ 2 kVeff / 5s/ 2 kVeff / 5s/
Overvoltage category III III III J
Pollution severity 2 2 2
Clearance & creepage path >= 3 mm >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c. Screw connection Tension clamp c.
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 VCC 0-10V/0-20MA 8540310000 WAS5 VCC 0-10V/4-20MA 8540290000 WAS5 VVC 0-10V/0-10V 8540330000
Tension clamp c. WAZ5 VCC 0-10V/0-20MA 8540320000 WAZ5 VCC 0-10V/4-20MA 8540300000 WAZ5 VVC 0-10V/0-10V 8540340000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.16

DC/DC 3-way isolator

20kHz Cut-off frequency 0(4)…20mA/0(4)…20mA 0…20mA/4…20mA 0…20mA/0…10V


Signal converter

• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current /0…20 mA /0…20 mA /0…20 mA
Max. voltage/Max. current /50 mA /50 mA /50 mA
Input resistance voltage/Current /50 M /50 M /50 M
Output
Output voltage/Output current /0…20 mA /4…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M /< = 600 M >= 2 kM/
Accuracy < 0.2 % of final value < 0.2 % of final value < 0.2 % of final value
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of final value <= 250 ppm/K of final value
Step response time <= 40 µs (type 30 µs) <= 40 µs (type 30 µs) <= 40 µs (type 30 µs)
Cut-off freq. (-3dB) >= 15 kHz (typ. 20 kHz) >= 15 kHz (typ. 20 kHz) >= 15 kHz (typ. 20 kHz)
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.5 W at Iout = 20 mA < 1.5 W at Iout = 20 mA < 1.3 W at Iout = 5 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C 0 °C…+55 °C 0 °C…+55 °C
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V 300 V
Impulse withstand voltage 4 kV 4 kV 4 kV
Isolation voltage Input, output 1.2 kVeff / 5s 1.2 kVeff / 5s 1.2 kVeff / 5s
J Coupling cap. in- resp. output/power supply 1 nF 1 nF 1 nF
Overvoltage category III III III
Pollution severity 2 2 2
Clearance & creepage path >= 3 mm >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c. Screw connection Tension clamp c.
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 CCC HF 0-20/0-20MA 8447160000 WAS5 CCC HF 0-20/4-20MA 8447190000 WAS5 CVC HF 0-20/0-10V 8447220000
Tension clamp c. WAZ5 CCC HF 0-20/0-20MA 8447170000 WAZ5 CCC HF 0-20/4-20MA 8447200000 WAZ5 CVC HF 0-20/0-10V 8447230000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.17

DC/DC 3-way isolator

20kHz Cut-off frequency 4…20mA/0…20mA 4…20mA/0…10V

Signal converter
• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current /4…20 mA /4…20 mA
Max. voltage/Max. current /50 mA /50 mA
Input resistance voltage/Current /50 M /50 M
Output
Output voltage/Output current /0…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M >= 2 kM/< = 600 M
Accuracy < 0.2 % of final value < 0.2 % of final value
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of final value
Step response time <= 40 µs (type 30 µs) <= 40 µs (type 30 µs)
Cut-off freq. (-3dB) >= 15 kHz (typ. 20 kHz) >= 15 kHz (typ. 20 kHz)
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.5 W at Iout = 20 mA < 1.3 W at Iout = 5 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C 0 °C…+55 °C
Storage temperature -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V
Impulse withstand voltage 4 kV 4 kV
Isolation voltage Input, output 1.2 kVeff / 5s 1.2 kVeff / 5s
Coupling cap. in- resp. output/power supply 1 nF 1 nF J
Overvoltage category III III
Pollution severity 2 2
Clearance & creepage path >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 CCC HF 4-20/0-20MA 8447250000 WAS5 CVC HF 4-20/0-10V 8447280000
Tension clamp c. WAZ5 CCC HF 4-20/0-20MA 8447260000 WAZ5 CVC HF 4-20/0-10V 8447290000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.18

DC/DC 3-way isolator

20kHz Cut-off frequency 0…10V/0…20mA 0…10V/4…20mA


Signal converter

• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current 0…10 V/ 0…10 V/
Max. voltage/Max. current 15 V/ 15 V/
Input resistance voltage/Current 500 kM/ 500 kM/
Output
Output voltage/Output current /0…20 mA /4…20 mA
Load resistance voltage/Current /< = 600 M /< = 600 M
Accuracy +/- 0.2% of final value +/- 0.2% of final value
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of final value
Step response time <= 40 µs (type 30 µs) <= 40 µs (type 30 µs)
Cut-off freq. (-3dB) >= 15 kHz (typ. 20 kHz) >= 15 kHz (typ. 20 kHz)
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.5 W at Iout = 20 mA < 1.5 W at Iout = 20 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C 0 °C…+55 °C
Storage temperature -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V
Impulse withstand voltage 4 kV 4 kV
Isolation voltage Input, output 1.2 kVeff / 5s 1.2 kVeff / 5s
J Coupling cap. in- resp. output/power supply 1 nF 1 nF
Overvoltage category III III
Pollution severity 2 2
Clearance & creepage path >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 VCC HF 0-10/0-20MA 8447310000 WAS5 VCC HF 0-10/4-20MA 8447340000
Tension clamp c. WAZ5 VCC HF 0-10/0-20MA 8447320000 WAZ5 VCC HF 0-10/4-20MA 8447350000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.19

DC/DC 3-way isolator

20kHz Cut-off frequency 0…10V/0…10V -10V…+10V/-10V…+10V

Signal converter
• Signal conversion
• Galvanic isolation between
input/output signal
• Power supply can be cross-
connected via plug-in jumpers

Technical data
Input
Input voltage/Input current 0…10 V/ -10…+10 V/
Max. voltage/Max. current 15 V/ +/- 15 V/
Input resistance voltage/Current 500 kM/ 500 kM/
Output
Output voltage/Output current 0…10 V/ -10…+10 V/
Load resistance voltage/Current >= 2 kM/ >= 2 kM/
Accuracy +/- 0.2% of final value +/- 0.2 % of measuring range
Temperature coefficient <= 250 ppm/K of final value <= 250 ppm/K of measuring range
Step response time <= 40 µs (type 30 µs) <= 40 µs (type 30 µs)
Cut-off freq. (-3dB) >= 15 kHz (typ. 20 kHz) >= 15 kHz (typ. 20 kHz)
General data
Supply voltage 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Power consumption < 1.3 W at Iout = 5 mA < 1.3 W at Iout = 5 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A
Operation temperature 0 °C…+55 °C 0 °C…+55 °C
Storage temperature -20 °C…+85 °C -20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CE / ESD / cURus
Insulation coordinates
Standards EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 300 V 300 V
Impulse withstand voltage 4 kV 4 kV
Isolation voltage Input, output 1.2 kVeff / 5s 1.2 kVeff / 5s
Coupling cap. in- resp. output/power supply 1 nF 1 nF J
Overvoltage category III III
Pollution severity 2 2
Clearance & creepage path >= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4

Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection WAS5 VVC HF 0-10/0-10V 8447370000 WAS5 VVC HF +-10V/+-10V 8561610000
Tension clamp c. WAZ5 VVC HF 0-10/0-10V 8447380000 WAZ5 VVC HF +-10V/+-10V 8587000000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.20

DC/DC 3-way isolator

Configurable PRO DC/DC


Signal converter

• Universal adjustable via DIP-switch


• Service tool WAVETOOL via internet
• Voltage supply 20…230 V ac/dc
• Low power loss
• Adjustable transmission frequency

Switch position/setting options


Switch
Input S1 S2
Input range 1 2 3 4 1 2 3 4
0 … ±60 mV        
0 … ±100 mV        
0 … ±150 mV        
0 … ±300 mV        
0 … ±500 mV        
0 … ±1 V        
0 … ±5 V        
Technical data
0 … ±10 V        
Input
0 … ±100 V        
Input voltage/Input current +/- 20 mV…+/- 200 V/+/-0.1mA…+/- 100 mA
0 … ± ~0.3 mA        
Input resistance voltage/Current ca. 1 MM/< 5 mA: ca. 100 M; >5 mA: ca. 5 M
0 … ±1 mA        
Max. current Iin < 5mA: < 100mA, Iin > 5mA < 300mA
0 … ±5 mA        
Output
0 … ±10 mA        
Output voltage/Output current 0…+/- 10 V/0…+/- 20 mA
0 … ±20 mA        
Load resistance voltage/Current >= 1 kM/< = 600 M
0 … ±50 mA        
Accuracy < 0.1 % of final value
4 … ±20 mA*        
Temperature coefficient < 60 ppm/K of end value
*Offset conversion not calibrated
Cut-off freq. (-3dB) > 10 kHz/ < 10 Hz
Offset 20 µA resp. 10 mV
Adjustment range, zero point +25 % of measuring range of the chosen output range
Switch S2 4
Adjustment range, amplification 0.33…3.30 x final value of the chosen output range
calibratet ranges 
Displacement -100%, -50%, 0%, 50%, 100% of measuring range
Span-pot. activated: input x 0.33 ... x 3.30
General data
Supply voltage 22…230 Vac/dc +10 %/ 48…62 Hz
Power consumption approx. 1 W
Operation temperature -10 °C…+70 °C Switch
Storage temperature -40 °C…+85 °C Output S1 S3
Default settings 0…10V / 0…10V / 10Hz Output range 5 6 7 1 2
0 … ±10 V     
Approvals GL / CE / cURus
2 … 10 V     
Insulation coordinates
0 … ±5 V     
Standards EN 50178
1…5V     
EMC standards DIN EN 61326. EN 61326/A1, EN 50081-2, EN 61000-6-2
J Rated voltage 600 V
0 … ±20 mA
4 … 20 mA










Impulse withstand voltage 5 kV, 1.2/50 µs (IEC 255-4)
Isolation voltage Input, output/ 4 kVeff/
Overvoltage category III
Pollution severity 2 Offset S1 S2
(in % of output voltage) 8 9 10 5
0%    
-100 %    
-50 %    
+50 %    
Dimensions Screw connection Tension clamp c. +100 %    
Clamping range (rating- / min. / max.) mm 2
2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 Zero pot. activated: additional ±25 %
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4
Information Tu=23°C, single module
Switch S3 3
Bandwidth 10 kHz 

Ordering data Bandwidth 10 Hz
Set range can be documented on side of housing.
Type of connection Type Qty. Order No.
Screw connection WAS4 PRO DC/DC 1 8560740000  = on
Tension clamp c. WAZ4 PRO DC/DC 1 8560750000 = off

Information

Accessories
Information Information accessories

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.21

DC/DC 3-way isolator

Configurable DC/DC select

Signal converter
• 3-way isolation
• DIP-switch
• Power supply can be cross connected
• Low power loss

Switch
S2
Input
    
20    
0 … 20 V       

20      
20 V     
Technical data 10       

Input 0 … 10    

Input voltage/Input current 0…10 V/0(4)…20 mA …    

Input resistance voltage/Current 100 kM/


Voltage drop < 0.1 V at Iin=20 mA (Current Input)
Output
Output voltage/Output current 0…10 V/0(4)…20 mA
Connection
Load resistance voltage/Current >= 10 kM/< = 600 M
Accuracy < 0.5% of final value
PS
Temperature coefficient < 150 ppm/K of final value
Cut-off freq. (-3dB) > 100 Hz - +
General data
Supply voltage 24 Vdc +/- 15 %
Power consumption approx. 0.6 W
Current-carrying cap. of cross-connect. <= 20 A
Operation temperature 0 °C…+55 °C - -
Storage temperature -20 °C…+85 °C V mA IN OUT mA V
Default settings 0…20mA / 0…20mA
Approvals CE / cURus
Insulation coordinates
Standards EN 50178
EMC standards DIN EN 61326
Rated voltage 50 V
Isolation voltage Input, output/ 500 Veff/
Overvoltage category II
Pollution severity 2 J

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 88.0 x 6.1 x 97.8 92.0 x 6.1 x 97.8
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection MAS DC/DC select 10 8594810000
Tension clamp c. MAZ DC/DC select 1 8594840000

Information

Accessories
Information Information accessoriesVoltage supply 24V and 0V with ZQV 4N/x
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.22

Supply isolator

Without HART MAS RPS


Signal converter

• 2-conductor technology
• 3-way isolation
• Voltage supply cross-connection

0V 0V
3 4
cc cc
2 5
PS
V
Out
Current
1 I Loop I 6
+ +

Technical data
Input
Input current 4…20 mA (sensor circuit)
Sensor 2-conductor
Feed voltage 16.5 V / constant for 3…22 mA
Output
Output current 4…20 mA
Output signal limit 22…25 mA
Load resistance voltage/Current /< = 600 M
Accuracy < 0.1 %
Offset current < 30 µA
Temperature coefficient <50 ppm/K
Residual ripple < 10 mVeff
General data
Supply voltage 24 Vdc +/- 15 %
Power consumption approx. 1 W
Current-carrying cap. of cross-connect. <= 20 A
Operation temperature 0 °C…+55 °C
Storage temperature -25 °C…+85 °C
Approvals CE / cURus
Insulation coordinates
Standards EN 50178
EMC standards DIN EN 61326 class B
Rated voltage 300 V
Isolation voltage Input, output 1.5 kVac
J Overvoltage category II
Pollution severity 2

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50
Length x width x height mm 88.0 x 6.1 x 97.8
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection MAS RPS 1 8721150000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 4N/x
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.23

Supply isolator

With HART MAS RPSH

Signal converter
• 2-conductor technology
• 3-way isolation
• With Hart transmission
• Output switchable

0V 0V
3 4
cc cc
2 5
PS
V
Out
Current
1 I Loop I 6
+ +

Technical data
Input
Input current 4…20 mA (sensor circuit)
Sensor 2-conductor
Feed voltage 16.5 V / constant for 3…22 mA
Output
Output current 0(4)…20 mA
Output voltage 0…10 V
Output signal limit 22…25 mA resp. 11…12.5 V
Load resistance voltage/Current >= 10 kM/< = 600 M
Accuracy Iout: < 0.1 % / Uout: < 0.2%
Offset current < 30 µA
Temperature coefficient <50 ppm/K
Residual ripple < 10 mVeff
General data
Supply voltage 24 Vdc +/- 15 %
Power consumption approx. 1 W
Communication according to HART Specification
Current-carrying cap. of cross-connect. <= 20 A
Operation temperature 0 °C…+55 °C
Storage temperature -25 °C…+85 °C
Approvals CE / cURus
Insulation coordinates
Standards EN 50178 (safe separation)
EMC standards DIN EN 61326 class B
Rated voltage 600 V J
Isolation voltage Input, output 2.5 kVac
Overvoltage category II
Pollution severity 2

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 1.50 / 0.50 / 2.50
Length x width x height mm 88.0 x 6.1 x 97.8
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection MAS RPSH 1 8721170000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 4N/x
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.24

PT100 / RTD - signal isolator/converter

PT100, 2-Conductor converter PT100/2 0(4)…20mA PT100/2 0…10V


Signal converter

• 2-conductor technology
• Adjustable temperature range
– 200 °C … + 800 °C
• Power supply can be cross connected via
plug-in jumper

Technical data
Input
Sensor PT100/2-conductor PT100/2-conductor
Feed current 1.45 mA 1.45 mA
Output
Output voltage/Output current /0(4)…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M >= 1 kM/
Accuracy +/-0.5% of measuring range +/-0.5% of measuring range
General data
Supply voltage/Current consumption 24 Vdc +/- 20 %/< 48 mA at Iout = 20 mA 24 Vdc +/- 20 %/< 38 mA at Iout = 20 mA
Operation temperature/Storage temperature 0 °C…+55 °C/-20 °C…+85 °C 0 °C…+55 °C/-20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Standards EN 50178, EN 60751, IEC751 EN 50178, EN 60751, IEC751
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Temperature input range Type of connection Type Qty. Order No. Type Qty. Order No.
Adjustable -200…+800 °C Screw connection WTS4 PT100/2 C 0/4-20mA 1 8432210000 WTS4 PT100/2 V 0-10V 1 8432180000
Adjustable -200…+800 °C Tension clamp c. WTZ4 PT100/2 C 0/4-20mA 1 8432220000 WTZ4 PT100/2 V 0-10V 1 8432190000
J Special adjusment Screw connection WTS4 PT100/2 C 0/4-20mA variable 1 8432219999 WTS4 PT100/2 V 0-10V variable 1 8432189999
Special adjusment Tension clamp connection WTZ4 PT100/2 C 0/4-20mA variable 1 8432229999 WTZ4 PT100/2 Vn 0-10V variable 1 8432199999
0…100 °C Screw connection WTS4 PT100/2 C 0-20mA 0…100C 1 8432210001 WTS4 PT100/2 V 0-10V 0…100C 1 8432180001
0…100 °C Tension clamp connection WTZ4 PT100/2 C 0-20mA 0…100C 1 8432220001 WTZ4 PT100/2 V 0-10V 0…100C 1 8432190001
0…100 °C Screw connection WTS4 PT100/2 C 4-20mA 0…100C 1 8432210011
0…100 °C Tension clamp connection WTZ4 PT100/2 C 4-20mA 0…100C 1 8432220011

Information
Specify temperature range by special calibrations. Specify temperature range by special calibrations.

Application

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.25

PT100 / RTD - signal isolator/converter

PT100, 3-Conductor converter PT100/3 0(4)…20mA PT100/3 0…10V

Signal converter
• 3-conductor technology
• Adjustable temperature range
– 200 °C …+ 800 °C
• Power supply can be cross connected via
plug-in jumper

Technical data
Input
Sensor PT100/3-conductor PT100/3-conductor
Feed current 1.45 mA 1.45 mA
Output
Output voltage/Output current /0(4)…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M >= 1 kM/
Accuracy +/-0.5% of measuring range +/-0.5% of measuring range
General data
Supply voltage/Current consumption 24 Vdc +/- 20 %/< 48 mA at Iout = 20 mA 24 Vdc +/- 20 %/< 38 mA at Iout = 20 mA
Operation temperature/Storage temperature 0 °C…+55 °C/-20 °C…+85 °C 0 °C…+55 °C/-20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Standards EN 50178, EN 60751, IEC751 EN 50178, EN 60751, IEC751
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Temperature input range Type of connection Type Qty. Order No. Type Qty. Order No.
Adjustable -200…+800 °C Screw connection WTS4 PT100/3 C 0/4-20mA 1 8432150000 WTS4 PT100/3 V 0-10V 1 8432090000
Adjustable -200…+800 °C Tension clamp c. WTZ4 PT100/3 C 0/4-20mA 1 8432160000 WTZ4 PT100/3 V 0-10V 1 8432130000
Special adjusment Screw connection WTS4 PT100/3 C 0/4-20mA variable 1 8432159999 WTS4 PT100/3 V 0-10V variabel 1 8432099999 J
Special adjusment Tension clamp connection WTZ4 PT100/3 C 0/4-20mA variable 1 8432169999 WTZ4 PT100/3 V 0-10V variabel 1 8432139999
0…100 °C Screw connection WTS4 PT100/3 C 0-20mA 0…100C 1 8432150001 WTS4 PT100/3 V 0-10V 0…100C 1 8432090001
0…100 °C Tension clamp connection WTZ4 PT100/3 C 0-20mA 0…100C 1 8432160001 WTZ4 PT100/3 V 0-10V 0…100C 1 8432130001
0…100 °C Screw connection WTS4 PT100/3 C 4-20mA 0…100C 1 8432150011
0…100 °C Tension clamp connection WTZ4 PT100/3 C 4-20mA 0…100C 1 8432160011

Information
Specify temperature range by special calibrations. Specify temperature range by special calibrations.

Application

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.26

PT100 / RTD - signal isolator/converter

PT100, 4-Conductor converter PT100/4 0(4)…20mA PT100/4 0…10V


Signal converter

• 4-conductor technology
• Adjustable temperature range
– 200 °C … + 800 °C
• Power supply can be cross connected via plug-
in jumper

Technical data
Input
Sensor PT100/4-conductor PT100/4-conductor
Feed current 1.45 mA 1.45 mA
Output
Output voltage/Output current /0(4)…20 mA 0…10 V/
Load resistance voltage/Current /< = 600 M >= 1 kM/
Accuracy 100K<=MR <600K: 0.1%;MR>=600K: 0.2% of MR 100K<=MR <600K: 0.1%;MR>=600K: 0.2% of MR
General data
Supply voltage/Current consumption 24 Vdc +/- 20 %/< 48 mA at Iout = 20 mA 24 Vdc +/- 20 %/< 38 mA at Iout = 20 mA
Operation temperature/Storage temperature 0 °C…+55 °C/-20 °C…+85 °C 0 °C…+55 °C/-20 °C…+85 °C
Approvals CSA / UL/UR / CE / ESD CSA / UL/UR / CE / ESD
Standards EN 50178, EN 60751, IEC751 EN 50178, EN 60751, IEC751
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Temperature input range Type of connection Type Qty. Order No. Type Qty. Order No.
Adjustable -200…+800 °C Screw connection WTS4 PT100/4 C 0/4-20mA 1 8432270000 WTS4 PT100/4 V 0-10V 1 8432240000
Adjustable -200…+800 °C Tension clamp c. WTZ4 PT100/4 C 0/4-20mA 1 8432280000 WTZ4 PT100/4 V 0-10V 1 8432250000
J Special adjusment Screw connection WTS4 PT100/4 C 0/4-20mA variable 1 8432279999 WTS4 PT100/4 V 0-10V variabel 1 8432249999
Special adjusment Tension clamp connection WTZ4 PT100/4 C 0/4-20mA variable 1 8432289999 WTZ4 PT100/4 V 0-10V variabel 1 8432259999
0…100 °C Screw connection WTS4 PT100/4 C 0…20mA 0…100C 1 8432270001 WTS4 PT100/4 V 0-10V 0…100C 1 8432240001
0…100 °C Tension clamp connection WTZ4 PT100/4 C 0…20mA 0…100C 1 8432280001 WTZ4 PT100/4 V 0-10V 0…100C 1 8432250001
0…100 °C Screw connection WTS4 PT100/4 C 4-20mA 0…100C 1 8432270011
0…100 °C Tension clamp connection WTZ4 PT100/4 C 4-20mA 0…100C 1 8432280011

Information
Specify temperature range by special calibrations Specify temperature range by special calibrations

Application

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.27

PT100 / RTD - signal isolator/converter

PT100, 2-/3-Conductor disconnector MCZ PT100/3 CLP


converter

Signal converter
• For 2- or 3-conductor PT100 sensors
• Loop-fed output current
• High accuracy and linearity

Technical data
Input
Sensor PT100/2-/3-conductor
Feed current 0.8 mA
Output
Output current 4…20 mA (current loop)
Load resistance voltage/Current /< = 600 M
Accuracy/Influence of cable resistance typical 0.2%, max. 0.5% of FSR/max. 06 K/M
Response time 10 ms
General data
Operation temperature/Storage temperature 0 °C…+50 °C/-20 °C…+85 °C
Approvals CSA;UL/UR;CE;ESD;
Standards EN 50178, EN 60751, IEC751
EMC standards EMVG, EN 50081-1, EN 50082-2

Dimensions Tension clamp c.


Clamping range (rating- / min. / max.) mm2 1.50 / 0.50 / 1.50
Length x width x height mm 91.0 x 6.0 x 63.2
Information Tu=23°C, single module

Ordering data
Temperature input range Type of connection Type Qty. Order No.
0…100 °C Tension clamp c. MCZ PT100/3 CLP 0…100C 10 8425720000
0…120 °C Tension clamp c. MCZ PT100/3 CLP 0…120C 10 8483680000
0…150 °C Tension clamp c. MCZ PT100/3 CLP 0…150C 10 8604420000 J
0…200 °C Tension clamp c. MCZ PT100/3 CLP 0…200C 10 8473010000
0…300 °C Tension clamp c. MCZ PT100/3 CLP 0…300C 10 8473020000
-50…+150 °C Tension clamp c. MCZ PT100/3 CLP -50C…+150C 10 8473000000
-40…+100 °C Tension clamp c. MCZ PT100/3 CLP -40C…100C 10 8604430000

Information

Application

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.28

PT100 / RTD - signal isolator/converter

PT100, 2-/3-Conductor disconnector PT100 Output select


converter
Signal converter

• 2-way isolation between input/output and


power supply
• PT100 2-/ 3-conductor
• Output can be switched calibrated via
DIP-switch

Switch
Output 1 2 3 4
0 … 10 V    
0 … 20 mA    
Technical data 4 … 20 mA    
Input
0…5V    
Sensor PT100/2-/3-conductor
Feed current 0.8 mA  = ein
Temperature input range 0…100 °C  = aus
Output
Output voltage/Output current 0…10V / 0…5V/0(4)…20 mA
Load resistance voltage/Current >= 10 kM/< = 600 M
Connection
Accuracy < 0.5 % out of measuring range
Temperature coefficient <= 250 ppm/K of final value
Step response time < 0.7 s PS
General data + -
Supply voltage 24 Vdc +/- 10 %
Power consumption approx. 0.6 W
Current-carrying cap. of cross-connect. <= 20 A
3 4
Operation temperature 0 °C…+55 °C
Storage temperature -20 °C…+85 °C 2 5 -
ϑ V/I
Default settings 0…20mA Pt100
1
ϑ 6
OUT mA V
Approvals CE / ESD / cURus
+
Insulation coordinates
Standards EN 50178, EN 60751, IEC751
EMC standards EN 50081, EN 50082, EN 55011, EN 61000-6-2, EN 61326
Rated voltage 100 V
Impulse withstand voltage 1.5 kV
Isolation voltage Input, output/ 500 Veff/
J Overvoltage category III
Pollution severity 2
Clearance & creepage path >= 1.5mm

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 88.0 x 6.1 x 97.8 92.0 x 6.1 x 97.8
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection MAS PT100 0…100C 1 8594820000
Tension clamp c. MAZ PT100 0…100C 1 8594850000

Information

Accessories
Information Information accessoriesVoltage supply 24V and 0V with ZQV 4N/x
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 21.10.2003 12:56 Uhr Seite J.29

PT100 / RTD - signal isolator/converter

RTD, signal disconnector converter PRO RTD PRO RTD 1000

Signal converter
• Universal adjustable via DIP-switch
• 3-way isolation
• Linearization
• Power supply can be cross connected via
plug-in jumper

Technical data
Input
Sensor PT100/2-/3-/4-cond.; Ni100/2-/3-/4-cond.; potentiometer: PT1000/2-/3-/4-cond.; Ni1000/2-/3-/4-cond.; potentiometer:
Temperature input range min. 0…100M, max. 0…100kM; resitance: 0…450M min. 0-1kM, max. 0-100kM; resitance: 0-4,5kM
Output configurable configurable
Output current/Output voltage
Offset current/Offset voltage 0(4)…20 mA/0…10 V 0(4)…20 mA/0…10 V
Load resistance voltage/Current max. 100 µA/max. 0.05 V max. 100 µA/max. 0.05 V
Step response time >= 1 kM/< = 600 M >= 1 kM/< = 600 M
Line resistance in measuring circuit fast: 1.2 s/ slow: 2.2 s fast/slow:2-/3-/4-cond.: 1.2s/2.3s; Poti: 0.5s/1.2s
Influence of cable resistance 50 M 50 M for 3- and 4-conductor
Wire break detection max. + 0.25°C at 50 M cond. resistance max. + 0.25°C at 50 M cond. resistance
Fine adjustment LED flashes (output value > 20mA, > 10V) LED flashes (output value > 20mA, > 10V)
Status indicator >=+/-5%, Version 1:>=12.5% / Poti:12.5%…25% >= +/- 12.5%; Poti: +/- 12.5% … +/-25%
General data active: LED on/cond. broken: LED flashing/Error: LED off active: LED on/cond. broken: LED flashing/Error: LED off
Supply voltage
Power consumption 24 Vdc +/- 25 % 24 Vdc +/- 25 %
Current-carrying cap. of cross-connect. 830…880…980mW at Iout=20mA 830…880…980mW at Iout=20mA
Operation temperature <= 2 A <= 2 A
Storage temperature 0 °C…+55 °C 0 °C…+55 °C
Default settings -20 °C…+85 °C -20 °C…+85 °C
Approvals PT100/3-cond./ 0…100°C / 4…20mA / man. adjustment: off / PT1000/3-cond./ 0…100°C / 4…20mA / man. adjustment: off
Insulation coordinates slow step response / slow step response
Standards GL / CE / cURus
EMC standards
Rated voltage EN 50178, EN 60751, IEC 751, DIN 43760 EN 50178, EN 60751, IEC 751, DIN 43760 J
Impulse withstand voltage EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Isolation voltage Input, output 300 V 300 V
Overvoltage category 4 kV 4 kV
Pollution severity 2 kVeff / 5s 2 kVeff / 5s
Clearance & creepage path III III
2 2
>= 3 mm >= 3 mm

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection WAS5 PRO RTD 1 8560700000 WAS5 PRO RTD 1000 1 8679490000
Tension clamp c. WAZ5 PRO RTD 1 8560710000 WAZ5 PRO RTD 1000 1 on demand

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 21.10.2003 13:00 Uhr Seite 30

DC/DC signal converter – configurable


WAVEANALOG PRO RTD WAVEANALOG PRO RTD 1000
Signal converter

Switch positions/possible settings Switch positions/possible settings

Selection of input  = on Selection of input  = on Selection of output Switching on the


Switch 1  = off Switch 1  = off Switch 2 manual adjustment
Input Input
1 2 3 1 2 3 Output 6 7 manual S.1
PT100 2-conductor    PT1000 2-conductor    0...10V   adjustment 8
PT100 3-conductor    PT1000 3-conductor    0...20mA   off 
PT100 4-conductor    PT1000 4-conductor    4...20mA   on 
R 2-conductor    R 2-conductor   
NI100 2-conductor    NI1000 2-conductor    Selection of the
NI100 3-conductor    NI1000 3-conductor    step response
NI100 4-conductor    NI1000 4-conductor    S.2
Potentiometer    Potentiometer    step response 8
slow 
fast 

Selection of minimum input size Selection of minimum input size Accuracy, slow/fast step response
Switch 1 Switch 1
min Rmin Potimin min Rmin Potimin
4 5 6 7 4 5 6 7 PT 100, Ni100: 0.3% of measuring range 0.8%
0°C 0Ω 0%     0°C 0Ω 0%     Measuring range:
-10°C 10 Ω 10%     -10°C 100 Ω 10%     Potentiometer: 0.2% of final value / 0.3%
-20°C 20 Ω 20%     -20°C 200 Ω 20%     Resistance: 0.2% of final value / 0.3%
-25°C 20 Ω 25%     -25°C 200 Ω 25%    
-30°C 30 Ω 30%     -30°C 300 Ω 30%    
-40°C 40 Ω 40%     -40°C 400 Ω 40%    
Temperature coefficient
-50°C 50 Ω 50%     -50°C 500 Ω 50%    
-60°C 60 Ω 60%     -60°C 600 Ω 60%    
Measuring range ≥ 200 K ≤ 200 ppm / °C
-70°C 70 Ω 70%     -70°C 700 Ω 70%    
100 K ≤ Measuring range < 200 K ≤ 250 ppm / °C
-80°C 80 Ω 80%     -80°C 800 Ω 80%    
40 K ≤ Measuring range < 100 K ≤ 400 ppm / °C
-90°C 90 Ω     -90°C 900 Ω    
-100°C 100 Ω     -100°C 1000 Ω    
-150°C 150 Ω     -150°C 1500 Ω    
-200°C 200 Ω     -200°C 2000 Ω    

Special range     Special range    

Choice of measuring range Choice of measuring range Examples for setting zero and range
Switch 2 Switch 2
T R Potentiometer T R Potentiometer
1 2 3 4 5 1 2 3 4 5 Temperature setting:
40K 20Ω 20%      40K 200Ω 20%      Output 4…20 mA
50K 25Ω 25%      50K 250Ω 25%      DIP switch -10 °C…+110 °C
60K 30Ω 30%      60K 300Ω 30%      Range 75…110 °C
70K 35Ω 35%      70K 350Ω 35%     
80K 40Ω 40%      80K 400Ω 40%      Range 120 °C
90K 45Ω 45%      90K 450Ω 45%      Range adjustment ± 12,5 %
J 100K
110K
50Ω
55Ω
50%
55%









v
100K
110K
500Ω
550Ω
50%
55%









v
120K 60Ω 60%      120K 600Ω 60%     
125K 62,5Ω 62,5%      125K 625Ω 62,5%      Zero
130K 65Ω 65%      130K 650Ω 65%     
140K 70Ω 70%      140K 700Ω 70%     
150K 75Ω 75%      150K 750Ω 75%      -25 ° C 95 ° C
-10 ° C 110 ° C
160K 80Ω 80%      160K 800Ω 80%      5° C 125 ° C
170K 85Ω 85%      170K 850Ω 85%     
180K 90Ω 90%      180K 900Ω 90%      Range
190K 95Ω 95%      190K 950Ω 95%     
200K 100Ω 100%      200K 1000Ω 100%     
110 ° C
5° C 125 ° C
250K 125Ω ---      250K 1250Ω ---      140 ° C
300K 150Ω ---      300K 1500Ω ---     
350K 175Ω ---      350K 1750Ω ---     
400K 200Ω ---      400K 2000Ω ---     
450K 225Ω ---      450K 2250Ω ---     
500K 250Ω ---      500K 2500Ω ---     
550K 275Ω ---      550K 2750Ω ---     
600K 300Ω ---      600K 3000Ω ---     
650K 325Ω ---      650K 3250Ω ---     
700K 350Ω ---      700K 3500Ω ---     
750K 375Ω ---      750K 3750Ω ---     
800K 400Ω ---      800K 4000Ω ---     
850K 425Ω ---      850K 4250Ω ---     
900K 450Ω ---      900K 4500Ω ---     

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.31

PT100 / RTD - signal isolator/converter

RTD, signal disconnector converter PRO RTD Cu

Signal converter
• Universally adjustable via DIP-switch Selection of connection Selection of senor
• 3-way isolation Switch 1 Switch 1
Type
Connection 1 2 3
• Linearization
3-wire  Cu 10  
• Power supply can be cross connected via plug- 4-wire  Cu 25  
in jumper Cu 50  
Cu 100  

Selection of minimun input values


Switch 1
min 4 5 6 7
- 0 °C    
-10 °C    
-20 °C    
-25 °C    
-30 °C    
-40 °C    
-50 °C    
-60 °C    
-70 °C    
-80 °C    
-90 °C    
-100 °C    
-150 °C    
Technical data -200 °C    
Input
Sensor Cu 10, Cu 25, Cu 50, Cu 100; 3-/4-cond. special range    
Temperature input range adjustable -200…+260 °C
Selection of the measurement range
Output
Switch 2
Output current/Output voltage 0(4)…20 mA/0…10 V Span 1 2 3 4 5
Offset current/Offset voltage max. 100 µA/max. 0.05 V
40 K     
Load resistance voltage/Current >= 1 kM/< = 600 M
50 K     
Step response time fast: 1.2 s/ slow: 2.2 s
60 K     
Line resistance in measuring circuit 5 M Cu 10; 15 M Cu 25; 25 M Cu 50; 50 M Cu 100
70 K     
Influence of cable resistance max. + 0.25°C at max. cond. resistance
80 K     
Wire break detection LED flashes (output value > 20mA, > 10V)
90 K     
Fine adjustment >= +/- 12.5 %
100 K     
Status indicator active: LED on/cond. broken: LED flashing/Error: LED off
110 K     
General data
120 K     
Supply voltage 24 Vdc +/- 25 %
125 K     
Power consumption 880…980…1030mW at Iout=20mA
130 K     
Current-carrying cap. of cross-connect. <= 2 A
140 K     
Operation temperature 0 °C…+55 °C
150 K     
Storage temperature -20 °C…+85 °C
160 K     
Default settings CU 10/3-cond.; 0…100°C; 4…20mA; no filter, manual adjust-
170 K     
Approvals ment off; slow step response
180 K     
Insulation coordinates GL / CE / ESD / cURus
190 K     
Standards
200 K     
EMC standards EN 50178
Rated voltage EN 50081, EN50082, EN55011
210 K
220 K










J
Impulse withstand voltage 300 V
230 K     
Isolation voltage Input, output 4 kV
240 K     
Overvoltage category 2 kVeff / 5s
250 K     
Pollution severity III
260 K     
Clearance & creepage path 2
270 K     
>= 3 mm
280 K     
290 K     
300 K     
350 K     
Dimensions Screw connection Tension clamp c.
400 K     
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
450 K     
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
460 K     
Information Tu=23°C, single module
Selection of Output Switching on the
Switch 2 manual fine adjustment
Output 6 7 Switch 1
Ordering data
0...10 V   man. adj. 8
Type of connection Type Qty. Order No.
0...20 mA   off 
Screw connection WAS5 PRO RTD Cu 1 8638950000
4...20 mA   on 
Tension clamp c. WAZ5 PRO RTD Cu 1 on demand

Selection of
Information step set time
Time of Schalter 2
step response 8
Accessories slow   = on
Information Voltage supply 24V and 0V with ZQV 2.5N/2 fast   = off
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.32

Thermo element, signal isolator/converter

Thermo disconnector converter Type: Thermo Select


K, J, T, E, N, R, S, B
Signal converter

• Calibration not necessary


• Cold-junction compensation
• Output signal selectable
• Power supply can be cross connected via plug-
in jumper

Switch position/setting options

SW 1 SW 2
Type 1 2 3 Span 1 2 3 4 5
K    100 C°     
J    150 C°     
T    200 C°     
E    250 C°     
N    300 C°     
R    350 C°     
S    400 C°     
B    450 C°     
Technical data 500 C°     
Input SW 1 550 C°     
Sensor thermo-elements (IEC 584) type: K,J,T,E,N,R,S,B 600 C°     
Tmin 4 5 6 7
Temperature input range -200…+1820 °C     
0 C°     650 C°
Output     
-10 C°     700 C°
Output voltage/Output current 0…10 V/0(4)…20 mA     
-20 C°     750 C°
Load resistance voltage/Current >= 1 kM/< = 600 M     
-30 C°     800 C°
Temperature coefficient +/- (200 ppm from span + 0.075 K)/K     
-40 C°     850 C°
Step response time with filter: 1.1 s; without filter: 6 s     
-50 C°     900 C°
Wire break detection LED flashes (output value > 20mA, > 10V)     
-100 C°     950 C°
General data     
-150 C°     1000 C°
Supply voltage 24 Vdc +/- 20 %     
-200 C°     1050 C°
Current consumption < 38 mA at Iout = 20 mA     
+50 C°     1100 C°
Current-carrying cap. of cross-connect. <= 2 A     
+100 C°     1150 C°
Operation temperature 0 °C…+55 °C     
+150 C°     1200 C°
Storage temperature -20 °C…+85 °C     
+200 C°     1250 C°
Approvals CSA / UL/UR / CE / ESD     
+250 C°     1300 C°
Insulation coordinates     
+500 C°     1350 C°
Standards EN 50178, EN 60584, IEC 584 1400 C°     
EMC standards EN 50081, EN50082, EN55011 SW 2 1450 C°     
Output 6 7 1500 C°     
0 - 10 V   1600 C°     
0 - 20 mA   1700 C°     
4 - 20 mA   1800 C°     

J Filter 8
off 
on 

 = on
 = off
Temperature coefficient
K -200°C ...-150°C ± (5K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
1200°C ...1372°C ± (4K + 0.1% of set range)
Dimensions Screw connection Tension clamp c.
J -200°C ...-150°C ± (4K + 0.1% of set range)
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
-150°C ...1200°C ± (3K + 0.1% of set range)
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4
T -200°C ...-150°C ± (5K + 0.1% of set range)
Information TU=23°C, single module
-150°C ...400°C ± (3K + 0.1% of set range)
E -200°C ...-150°C ± (4K + 0.1% of set range)
-150°C ...1000°C ± (3K + 0.1% of set range)
Ordering data N -200°C ...-150°C ± (6K + 0.1% of set range)
Type of connection Type Qty. Order No. -150°C ...1300°C ± (3K + 0.1% of set range)
Screw connection WTS4 THERMO 1 8432300000 R -50°C ...200°C ± (10K + 0.1% of set range)
Tension clamp c. WTZ4 THERMO 1 8432310000 200°C ...1760°C ± (6K + 0.1% of set range)
S -50°C ...200°C ± (10K + 0.1% of set range)
Information 200°C ...1760°C ± (6K + 0.1% of set range)
B 50°C ...250°C ± (25K + 0.1% of set rangeh)
250°C ...500°C ± (10K + 0.1% of set range)
Accessories 500°C ...1820°C ± (6K + 0.1% of set range)
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.33

Thermo element, signal isolator/converter

Thermo disconnector converter type: Thermo K Output Select


K

Signal converter
• 2-way isolation between input/output and
voltage supply
• Cold-junction compensation
• Linearization
• Output can be switched calib. via DIP-switch

Switch
Output 1 2 3 4
0 … 10 V    
0 … 20 mA    
4 … 20 mA    
0…5V    

 = on
 = off
Technical data
Input Connection
Sensor thermo-elements according IEC 584, type: K
Temperature input range 0…1000 °C
Output
Output voltage/Output current 0…10V / 0…5V/0(4)…20 mA
Load resistance voltage/Current >= 10 kM/< = 600 M PS
Accuracy < 0.6 % of measuring range - +
Temperature coefficient <= 250 ppm/K of final value
Step response time < 0.7 s
Wire break detection output value: > 20 mA, > 10 V
3 4
Residual ripple < 20 mVeff
General data - 2 V/I 5 -
Supply voltage 24 Vdc +/- 10 % IN ϑ OUT mA V
1 6
Power consumption approx. 0.6 W + +
Current-carrying cap. of cross-connect. <= 20 A
Operation temperature 0 °C…+55 °C
Storage temperature -20 °C…+85 °C
Default settings 0…20mA
Approvals CE / ESD / cURus
Insulation coordinates
Standards EN 50178, EN 60584, IEC 584
EMC standards EN 50081, EN 50082, EN 55011, EN 61000-6-2, EN 61326
Rated voltage 100 V
Impulse withstand voltage 1.5 kV
Isolation voltage Input, output/ 500 Veff/ J
Overvoltage category III
Pollution severity 2
Clearance & creepage path >= 1.5mm

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 88.0 x 6.1 x 97.8 92.0 x 6.1 x 97.8
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection MAS Thermo-K 0…1000°C Output select1 8594830000
Tension clamp c. MAZ Thermo-K 0…1000°C Output select1 8594860000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 4N/x
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.34

Thermo element, signal isolator/converter

Thermo disconnector converter type: Thermo J Output Select


J
Signal converter

• 2-way isolation between input/output and


voltage supply
• Cold-junction compensation
• Linearization
• Output can be switched calib. via DIP-switch

Switch
Output 1 2 3 4
0 … 10 V    
0 … 20 mA    
4 … 20 mA    
0…5V    

 = on
 = off
Technical data
Input Connection
Sensor thermo-elements according IEC 584, type: J
Temperature input range 0…700 °C
Output
Output voltage/Output current 0…10V / 0…5V/0(4)…20 mA
Load resistance voltage/Current >= 10 kM/< = 600 M PS
Accuracy < 0.7 % of measuring range - +
Temperature coefficient <= 250 ppm/K of final value
Step response time < 0.7 s
Wire break detection output value: > 20 mA, > 10 V
3 4
Residual ripple < 20 mVeff
General data - 2 V/I 5 -
Supply voltage 24 Vdc +/- 10 % IN ϑ OUT mA V
1 6
Power consumption approx. 0.6 W + +
Current-carrying cap. of cross-connect. <= 20 A
Operation temperature 0 °C…+55 °C
Storage temperature -20 °C…+85 °C
Default settings 0…20mA
Approvals CE / ESD / cURus
Insulation coordinates
Standards EN 50178, EN 60584, IEC 584
EMC standards EN 50081, EN 50082, EN 55011, EN 61000-6-2, EN 61326
Rated voltage 100 V
Impulse withstand voltage 1.5 kV
J Isolation voltage Input, output/ 500 Veff/
Overvoltage category III
Pollution severity 2
Clearance & creepage path >= 1.5mm

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 88.0 x 6.1 x 97.8 92.0 x 6.1 x 97.8
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection MAS Thermo-J 0…700°C Output select 1 8615210000
Tension clamp c. MAZ Thermo-J 0…700°C Output select 1 8615240000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 4N/x
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.35

Thermo element, signal isolator/converter

Thermo disconnector converter Type: PRO Thermo


K, J, T, E, N, R, S, B

Signal converter
Select of Selection of minimum
• 3-way isolation thermocoupler temperature
• Calibration not necessary SW1 SW1
Typ 1 2 3 min 4 5 6 7
• Cold-junction compensation K    0°C    
• Output signal selectable J    -10°C    
• Power sup. can be cross-conn. by jumper T    -20°C    
E    -30°C    
N    -40°C    
R    -50°C    
S    -100°C    
B    -150°C    
-200°C    
+50°C    
+100°C    
+150°C    
+200°C    
+250°C    
500°C    
Special range    

Selection of Selection of
temperature span output
SW2 SW2
Technical data Span 1 2 3 4 5 Output 6 7
Input
100°C      0...10V  
Sensor thermo-elements (IEC 584) type: K,J,T,E,N,R,S,B
150°C      0...20mA  
Temperature input range -200…+1820 °C
200°C      4...20mA  
Output
250°C     
Output voltage/Output current 0…10 V/0(4)…20 mA
300°C     
Load resistance voltage/Current >= 1 kM/< = 600 M
350°C      Switching on the
Offset current/Offset voltage max. 100 µA/max. 0.05 V
400°C      manual fine adjustment
Step response time max. 1.4 s; with filter: max. 7.5 ms
450°C      SW1
Line resistance in measuring circuit 50 M
500°C      man. adjust. 8
Wire break detection LED flashes (output value > 20mA, > 10V)
550°C      off 
Fine adjustment >= +/- 5 % (switchable)
600°C      on 
Status indicator active: LED on/cond. broken: LED flashing/Error: LED off
650°C     
General data
700°C     
Supply voltage 24 Vdc +/- 25 %
750°C     
Power consumption 800…850…950 mW at Iout= 20 mA
800°C      Switching on the
Current-carrying cap. of cross-connect. <= 2 A
850°C      filter function
Operation temperature 0 °C…+55 °C
900°C      SW2
Storage temperature -20 °C…+85 °C
950°C      Filter 8
Default settings type K; 0…1000°C; 4…20mA; filter: off; man. adjustment: off
1000°C      off 
Approvals GL / CE / cURus
1050°C      on 
Insulation coordinates
1100°C     
Standards EN 50178, EN 60584, IEC 584
1150°C     
EMC standards EN 50081, EN50082, EN55011
1200°C     
Rated voltage 300 V
Impulse withstand voltage 4 kV
1250°C    
1300°C    


J
Isolation voltage Input, output/ 2 kVeff / 5s/
1350°C     
Overvoltage category III
1400°C     
Pollution severity 2
1450°C     
Clearance & creepage path >= 3 mm
1500°C     
1600°C     
1700°C       = on
1800°C       = off

Temperature coefficient
Dimensions Screw connection Tension clamp c.
K -200°C ...-150°C ± (5K + 0,1% of set range)
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
-150°C...1200°C ± (3K + 0,1% of set range)
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
1200°C...1372°C ± (4K + 0,1% of set range)
Information TU=23°C, single module J -200°C ...-150°C ± (4K + 0,1% of set range)
-150°C...1200°C ± (3K + 0,1% of set range)
T -200°C ...-150°C ± (5K + 0,1% of set range)
Ordering data -150°C ...400°C ± (3K + 0,1% of set range)
Type of connection Type Qty. Order No. E -200°C ...-150°C ± (4K + 0,1% of set range)
Screw connection WAS5 PRO Thermo 1 8560720000 -150°C...1000°C ± (3K + 0,1% of set range)
Tension clamp c. WAZ5 PRO Thermo 1 8560730000 N -200°C ...-150°C ± (6K + 0,1% of set range)
-150°C...1300°C ± (3K + 0,1% of set range)
R -50°C ...200°C ± (10K + 0,1% of set range)
Information 200°C...1760°C ± (6K + 0,1% of set range)
S -50°C ...200°C ± (10K + 0,1% of set range)
200°C...1760°C ± (6K + 0,1% of set range)
Accessories B 50°C ...250°C ± (25K + 0,1% of set range)
Information Voltage supply 24V and 0V with ZQV 2.5N/2 250°C ...500°C ± (10K + 0,1% of set range)
cross-connection 500°C...1820°C ± (6K + 0,1% of set range)

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.36

Frequenzy signal isolator/converter

DC/f disconnector MCZ VFC MCZ CFC MCZ CFC


converter
Signal converter

By the conversion of analog signals


to frequency it is possible to read in
analog signals out of the array via
the counter-inputs of the controller.

Vcc Input
4 1 5 3 1
+24V 1
0...10V 0...20mA 4...20mA
Output OV OV OV
5 f
f 2 5 f 2 4 f
f 2
f
f f/2f/4f/16 U f f/2f/4f/16 f f/2f/4f/16 I
I
16kHz
3 GND 3 GND 5 GND

Technical data
Input
Input voltage/Input current 0…10 V/ /0…20 mA /4…20 mA (current loop)
Max. voltage/Max. current 30 V/ /50 mA /50 mA
Input resistance voltage/Current 100 kM/ /50 M /
Voltage drop 1 V at 20 mA 5.8…6.4 V at 20 mA
Output
Output frequency/ 0…1/ 4/ 8/ 16 kHz/ 0…1/ 4/ 8/ 16 kHz/ 0…1/ 4/ 8/ 16 kHz/
Output level PNP, Ub-0.7 V PNP, Ub-0.7 V PNP, Ub-0.7 V
Output current max. 20 mA max. 20 mA max. 20 mA
Fine adjustment +/- 10 %, internal +/- 10 %, internal +/- 10 %, internal
Accuracy 0.2% of FSR 0.2% of FSR 0.15 % of FSR
Temperature coefficient <= 250 ppm/K <= 250 ppm/K <= 250 ppm/K
Status indicator LED, pulsing LED, pulsing LED, pulsing
General data
Supply voltage 24 Vdc +/- 10 % 24 Vdc +/- 10 % 24 Vdc +/- 20 %
Current consumption 14 mA without load 14 mA without load 14 mA without load
Current-carrying cap. of cross-connect. <= 20 A
Operation temperature 0 °C…+50 °C 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -20 °C…+85 °C -20 °C…+85 °C -20 °C…+85 °C
Approvals CE / ESD CE / ESD CE / ESD
Insulation coordinates
Standards EN 50178 EN 50178 EN 50178
EMC standards EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011 EN 50081, EN50082, EN55011
Rated voltage 100 V 100 V 150 V
J Impulse withstand voltage 1.5 kV 1.5 kV 2.5 kV
Isolation voltage Input, output 1 kVdc 1 kVdc
Overvoltage category III III III
Pollution severity 2 2 2
Clearance & creepage path >= 1.5mm >= 1.5mm >= 2 mm

Dimensions Tension clamp c. Tension clamp c. Tension clamp c.


Clamping range (rating- / min. / max.) mm2 1.50 / 0.50 / 1.50 1.50 / 0.50 / 1.50 1.50 / 0.50 / 1.50
Length x width x height mm 91.0 x 6.0 x 63.2 91.0 x 6.0 x 63.2 91.0 x 6.0 x 63.2

Information Without DC/DC-converter input is current-loop-fed

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Tension clamp c. MCZ VFC 0-10V 8461470000 MCZ CFC 0-20MA 8461480000 MCZ CFC 4-20MA 8461490000

Information

Accessories
Information Voltage supply 24V,0V and GND with ZQV 4/x Voltage supply 24V,0V and GND with ZQV 4/x Voltage supply 24V,0V and GND with ZQV 4/x
cross-connection cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 14:13 Uhr Seite J.38

Frequenzy signal isolator/converter

f/DC disconnector converter PRO Frequency


Signal converter

• 3-way isolation
• Max. input frequency 100 kHz
• Input and output adjustable via DIP-switch
• Calibration not necessary
• Special partitions can be programmed

Selecting the
operting mode
Switch 2
Operating mode 3 4
0…fmax  
fmin…fmax  
saving
fmin  

f= (A+B) x C
Selecting Selecting
the frequency the frequency
Switch 1 Switch 1
Technical data A 1 2 3 4 B 5 6 7 8
Input 0     0    
Sensor/ 2-, 3-wire PNP/NPN, namur initiator, push-pull step/ 1     0,1    
Rated input level threshold / hysterese: namur: ca 1.7 mA/ca 0.2 mA; 2     0,2    
Resolution NPN: ca 6.5 V/ca 0.2V; PNP: ca 6.7V/ca 0.5V 3     0,3    
Output 0.1 mHz resp. 5 ppm of measurement value 4     0,4    
Output voltage/Output current 5     0,5    
Load resistance voltage/Current 0…10 V/0(4)…20 mA 6     0,6    
Offset current/Offset voltage >= 1 kM/< = 600 M 7     0,7    
Accuracy max. 100 µA/max. 0.05 V 8     0,8    
Temperature coefficient 0.2 % of output range 9     0,9    
Step response time max. 200 ppm/K of output range 10    
Selecting
Status indicator 360 ms + 2-fold period time of input frequency 11    
the frequency
General data LED green 12    
Switch 2
Supply voltage 13    
C 1 2
Power consumption 24 Vdc +/- 25 % 14    
x1  
Current-carrying cap. of cross-connect. max. 1.6 W at Iout= 20 mA 15    
x10  
Operation temperature <= 2 A
x100  
Storage temperature 0 °C…+55 °C
x1000  
Default settings -20 °C…+85 °C
Approvals 0…10kHz / 4…20mA
Insulation coordinates CE / ESD / cURus Selecting the output
Standards Switch 2
EMC standards EN 50178 (safe separation) Output 5 6 7 8
Rated voltage EN 50081, EN 50082, EN 55011, EN 61000-6-2, EN 61326 0...10 V    
J Impulse withstand voltage 300 V 0...20 mA    
Isolation voltage Input, output/ 6 kV 4...20 mA    
Overvoltage category 4 kVeff / 5s/ 0…5 V    
Pollution severity III
Special range (frequency generator is required)
Clearance & creepage path 2
Switch 2
>= 5.5 mm
Funktion 1 2 3 4
save min. frequency    
save max. frequency    
/
select special range    
Dimensions Screw connection Tension clamp c.  = ein
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50  = aus
Length x width x height mm 92.4 x 12.5 x 112.4 92.4 x 12.5 x 112.4
Information TU=23°C, single module Application

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS4 PRO Freq 1 8581180000
Tension clamp c. WAZ4 PRO Freq 1 8581190000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 16.10.2003 11:28 Uhr Seite 39

Frequency signal transformer

WAVEANALOGUE PRO Frequency

Signal converter
Connection configuration Setting help for any
of the sensors input and output values

3-wire initiator with PNP output Setting the input range using the DIP
3-wire initiator with PNP output and external supply
switches (no frequency generator
(1) +15V (1) +15V required):
(2) PNP (2) PNP
(3) NPN / Namur (3) NPN / Namur There are 2 different cases:
(4) GND (4) GND
1. Lower measuring frequency = 0 Hz
– Choose operating mode “= … fmax” S2.3 = 0
U=24V and S2.4 = 0
– Set the upper measuring frequency using DIP
3-wire initiator with NPN output switches S1 and S2.1, S2.2 (see table)
3-wire initiator with NPN output and external supply
– That's all
(1) +15V (1) +15V
(2) PNP (2) PNP
(3) NPN / Namur (3) NPN / Namur 2. Lower measuring frequency ≠ 0 Hz
(4) GND (4) GND
– First the lower measuring frequency
must be saved.
U=24V
Select mode “save fmin”.
S2.3 = 1 and S2.4 = 0.
Set the frequency using DIP switches S1 and
2-wire initiator Namur initiator S2.1, S2.2 (see table)

(1) +15V (1) +15V To save the frequency, briefly connect the mod-
N+ ule to the power supply.
(2) PNP (2) PNP
N-
(3) NPN / Namur (3) NPN / Namur – Select mode “fmin…fmax”
(4) GND (4) GND S2.3 = 0 and S2.4 = 1
(residual current < 1 mA)
– Set the upper measuring frequency using DIP
switches S1 and S2.1, S2.2 (see table).
– That's all.
Push pull output cascade

U=24V
(1) +15V
Adjusting the input range using
(2)
(3)
PNP
NPN / Namur
a frequency generator J
(4) GND – Select the switch setting for saving the frequency:
S2.1 = 0, S2.2 = 1, S2.3 = 1 and S2.4 = 1
– Apply min. frequency to the module
– Connect the module to the power supply
– The LED lights up when the input frequency is
being measured. If the LED goes off, the frequen-
cy has been saved and the module can be dis-
connected from the power supply again.
– Repeat with max. frequency:
S2.1 = 1, S2.2 = 0, S2.3 = 1 and S2.4 = 1
– Select special range:
S2.1 = 1, S2.2 = 1, S2.3 = 1 and S2.4 = 1

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.40

Bridge measuring converter

Configurable PRO BRIDGE


Switch position/setting options
Signal converter

• 3-way isolation
• Input and output selectable via DIP-switch SW 1
• Calibration not necessary Input voltage 1 2 3 4 5 6 7 8 9 10
• Inverse output signal 0…10 mV    
0…20 mV    
0...50 mV    
0...100 mV    
0...200 mV    
0...500 mV    
-10 mV...10 mV    
- 20 mV...20 mV    
- 50 mV...50 mV    
- 100 mV...100 mV    
- 200 mV...200 mV    
- 500 mV...500 mV    
Ausgang
0...+10 V  
0...+5 V  
0...20 mA  
4...20 mA  
Bridge supply voltage
+10V   
+5V   
Technical data
+4,8...+10,2V adjustable   
Input
+4,8...+10,2V adjustable
Input voltage/ -500mV…+500mV/
man. adjustment and
Input resistance voltage > 1 MM
offset possible   
Output
Transmission method
Output voltage/Output current 0…5 V, 5…0 V, 10…0 V, 0…10 V/
standard output signal 
Load resistance voltage/Current 0…20 mA, 20…0 mA, 4…20 mA, 20…4 mA
inverse output signal 
Offset current/Offset voltage >= 1 kM/< = 600 M
 = on
Accuracy max. 100 µA/max. 0.05 V
 = off
Temperature coefficient 0.3 % of output range
Step response time +/- 250 ppm/K of output range Status LED
Status indicator typ. < 200 ms LED on normal operating
Wire break detection LED green LED off Error
Bridge supply voltage output: 0 V resp. 0/4 mA LED blinks slow measurement range undershoot
General data +10 V, +5 V, 4.8…10.2 V; offset adjustable; max. 40mA Uin < Umax + 10%
Supply voltage LED blinks fast measurement range overshoot
Power consumption 24 Vdc +/- 25 % Uin < Umax - 10 %
Current-carrying cap. of cross-connect. max. 1.9 W at Iout= 20 mA
Operation temperature <= 2 A Application
Storage temperature 0 °C…+55 °C
230 Vac
Default settings -20 °C…+85 °C ~
24 Vdc
Approvals -500 mV…+500 mV / 0…10 V / + 10 V / standard 10 11 12
F Power supply +
Insulation coordinates CE / ESD / cURus PLC
7 8 9

R1 R3
Standards 0...5V
8581200000/8581210000

(DMS)
Bridge
WAVEANALOG
PRO Bridge

EMC standards EN 50178


J Rated voltage EN 61000-6-2, EN 50081-2
R2
U

R4
Bridge

Impulse withstand voltage 300 V 1 2 3

Isolation voltage Input, output/ 4 kV - 4 5 6

Power supply -
Overvoltage category 2 kVeff / 5s/ Measuring bridge
Pollution severity III
Clearance & creepage path 2
>= 3 mm Example for bridge supply voltage

Temperature adjustment:
Input voltage 0…10 mA
Dimensions Screw connection Tension clamp c.
Output 0…10 V
Clamping range (rating- / min. / max.) mm 2
2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Bridge supply voltage +4,8…10,2 V
Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4
Bridge excitation 1 mV/V
Information TU=23°C, single module (Declaration frommanufacturer)

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS5 PRO Bridge 1 8581200000 Exitation voltage
Tension clamp c. WAZ5 PRO Bridge 1 8581210000
+4,8V 10,2V
10V
Information Offset range 10%

Offset (Output)
Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection 0V 0V 1V 9V 10V 11V

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.42

Serial interface converter

RS232/RS485/422 RS232/RS485/422
Interface converter

• 3-way isolation
• RS232 connection via SUB-D 9
• RS485/422, TTY shield connection via KLBÜ
• DTE or DCE assignment selectable
• Bidirectional communication

5 T+ R+ 2
RS232 6 T- R- 3 TTY

2 R+ T+ 5
TTY RS232
3 R- T- 6

VCC SHLD VCC

WDS2 RS232/TTY WDS2 RS232/TTY

Technical data
RS232
Connection/Input current SUB-D9 (pin)/
Assignment DTE/DCE switchable via DIP-Switch
RS485/422
Terminating resistors pull down/ pull up via DIP-switch
Connection BLZ screw connection
Bit distortion < 1.5%
Bit delay <= 3µs
Control of data direction/ selfcontrolling or via RS232 RTS/CTS/
Shield connection KLBÜ 4-6/Z1
Status indicator LED green: supply voltage, TxD, RxD
Max. bit rate 115.2 kBit/s
Transmission channels half duplex (RS485-2 wire)
Transmission distance full duplex (RS485-4 wire and RS422)
General data max. 1200m twisted pair
Supply voltage
Power consumption 24 Vdc +/- 25 %
Operation temperature approx. 1.5 W
Storage temperature 0 °C…+55 °C (horiz. mounting)
Approvals -20 °C…+85 °C
Insulation coordinates CE / ESD / cURus
Standards
EMC standards EN 50178
Rated voltage EN 61000-6-2, EN 61000-6-4, EN 55011
J Impulse withstand voltage between adjacent electric circuits: 300 V
Pollution severity between electric circuits and PE: 150 V
Overvoltage category 4 kV
Clearance & creepage path 2
Isolation voltage Input, output III
between adjacent electric circuits: 3mm
between electric circuits and PE: 1.5mm
2 kVdc / 1 min.

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 22.5 x 112.4
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection WDS2 RS232/RS485/422 1 8615700000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.43

Serial interface converter

RS232/TTY RS232/TTY

Interface converter
• 3-way isolation
• RS232 connection via SUB-D 9
• RS485/422, TTY shield connection via KLBÜ
• DTE or DCE assignment selectable
• Bidirectional communication

5 T+ R+ 2
RS232 6 T- R- 3 TTY

2 R+ T+ 5
TTY RS232
3 R- T- 6

VCC SHLD VCC

WDS2 RS232/TTY WDS2 RS232/TTY

Technical data
RS232
Connection/Input current SUB-D9 (pin)/
Assignment DTE/DCE switchable via DIP-Switch
TTY
Connection BLZ screw terminal
Bit distortion < 1.5%
Bit delay <= 3 µs
Burden <= 500 M
Shield connection/ KLBÜ 4-6 Z/1/
Status indicator LED green: supply voltage, TxD, RxD
Max. bit rate 19.2 kBit/s
Transmission channels full duplex
Transmission distance max. 1000m twisted pair
General data
Supply voltage 24 Vdc +/- 25 %
Power consumption approx. 0.8 W
Operation temperature 0 °C…+55 °C (horiz. mounting)
Storage temperature -20 °C…+85 °C
Approvals CE / ESD / cURus
Insulation coordinates
Standards EN 50178
EMC standards EN 61000-6-2, EN 61000-6-4, EN 55011
Rated voltage between adjacent electric circuits: 300 V
Impulse withstand voltage between electric circuits and PE: 150 V
Pollution severity 4 kV J
Overvoltage category 2
Clearance & creepage path III
Isolation voltage Input, output between adjacent electric circuits: 3mm
between electric circuits and PE: 1.5mm
2 kVdc / 1 min.

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 22.5 x 112.4
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection WDS2 RS232/TTY 1 8615690000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.44

AD-/DA-Converter

AD-Converter 8-Bit RS I-D8 0…20mA RS I-D8 4…20mA


Interface converter

Terminal
Digital
PIN volue
MSB LSB Analog
E8 E7 E6 E5 E4 E3 E2 E1 voltage Ie 24V + Ie 24V +
0 0 0 0 0 0 0 0 0V A A
0 0 0 0 0 0 0 0 D D
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0V 0V 0V 0V
- - - -
- - - -
1 1 1 1 1 1 0 1
1 1 1 1 1 1 1 0 12345678 HE 12345678 HE
1 1 1 1 1 1 1 1 +10 V

Technical data
Input
Input voltage/Input current /0…20 mA /4…20 mA
Max. voltage/Max. current 3.5 V/25 mA 3.5 V/25 mA
Input resistance voltage/Current />= 51 M />= 51 M
Resolution 78 µA = 1 LSB 62.5 µA = 1 LSB
Output
Number of outputs 8Bit (1 Bit sign) 8Bit (1 Bit sign)
Output level 17 V = H, 0 V = L 17 V = H, 0 V = L
Signs
Output current <= 25 mA (as source) <= 25 mA (as source)
Accuracy +/- 1 LSB +/- 1 LSB
Cut-off freq. (-3dB) 5 kHz at full scale (sinus) 5 kHz at full scale (sinus)
Conversion time <= 4 µs <= 4 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption 35 mA (plus output current) 35 mA (plus output current)
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 35.0 x 72.0 70.0 x 35.0 x 72.0
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS I-D8 0…20MA 1 1160561001 RS I-D8 4…20MA 1 1168561001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.45

AD-/DA-Converter

AD-Converter 8-Bit RS U-D8 +/-10V RS U-D8 0…10V

Interface converter
Terminal Digital
PIN volue
LSB Analog
E8 E7 E6 E5 E4 E3 E2 E1 current Ue 24V + Ue 24V +
0V A A
0 0 D D
0V 0V 0V 0V
0
-
- - - -
1 1 1 1 1 1 0 1
12345678 HE 12345678 HE
1 1 +10 V

Technical data
Input
Input voltage/Input current -10…+10 V/ 0…10 V/
Max. voltage/Max. current /< = 55 µA /< = 25 µA
Input resistance voltage/Current >= 200 kM/ >= 400 kM/
Resolution 78 mV = 1 LSB 39 mV = 1 LSB
Output
Number of outputs 8Bit (1 Bit sign) 8Bit (1 Bit sign)
Output level 17 V = H, 0 V = L 17 V = H, 0 V = L
Signs MSB: H = positive; L = negative
Output current <= 25 mA (as source) <= 25 mA (as source)
Accuracy +/- 1 LSB +/- 1 LSB
Cut-off freq. (-3dB) 5 kHz at full scale (sinus) 5 kHz at full scale (sinus)
Conversion time <= 4 µs <= 4 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption 35 mA (plus output current) 35 mA (plus output current)
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 35.0 x 72.0 70.0 x 35.0 x 72.0
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS U-D8 +-10V 1 1122361001 RS U-D8 0…10V 1 1160361001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.46

AD-/DA-Converter

DA-Converter 8-Bit RS D8-I 0…20mA RS D8-I 4…20mA


Interface converter

12345678 H0V 12345678 H0V

+ 24V Ia + 24V Ia
D D
A A
- 0V 0V - 0V 0V

Technical data
Input
Input/Output 8 Bit / Analogue 8 Bit / Analogue
Max. voltage max. 30 V max. 30 V
Max. current
Input voltage/Input current 5…24 V/ 5…24 V/
Signs
Resolution 78 µA = 1 LSB 62.5 µA = 1 LSB
Output
Output voltage/Output current /0…20 mA (as source) /4…20 mA (as source)
Offset current/Offset voltage max. 0.08 mA/ 4 mA/
Load resistance voltage/Current /< = 600 M /< = 600 M
Accuracy +/- 1 LSB +/- 1 LSB
Conversion time <= 30 µs <= 30 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption 25 mA (plus output current) 25 mA (plus output current)
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 35.0 x 72.0 70.0 x 35.0 x 72.0
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS D8-I 0…20MA 1 1165861001 RS D8-I 4…20MA 1 1169261001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.47

AD-/DA-Converter

DA-Converter 8-Bit RS D8-U +/-10V RS D8-U 0…10V

Interface converter
12345678 H0V 12345678 H0V

+ 24V Ua + 24V Ua
D D
A A
- 0V 0V - 0V 0V

Technical data
Input
Input/Output 8 Bit / Analogue 8 Bit / Analogue
Max. voltage max. 30 V max. 30 V
Max. current 2.5 mA 2.5 mA
Input voltage/Input current 5…24 V/ 5…24 V/
Signs MSB: H = positive; L = negative
Resolution 78 mV = 1 LSB 39 mV = 1 LSB
Output
Output voltage/Output current -10…+10 V/<= 10 mA max. current 0…10 V/<= 10 mA max. current
Offset current/Offset voltage /<= 20 mV /<= 20 mV
Load resistance voltage/Current >= 1 kM/< = 600 M >= 1 kM/< = 600 M
Accuracy +/- 1 LSB +/- 1 LSB
Conversion time <= 30 µs <= 30 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption 25 mA (plus output current) 25 mA (plus output current)
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE CE / ESD
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 35.0 x 72.0 70.0 x 35.0 x 72.0
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS D8-U +-10V 1 1123361001 RS D8-U 0…10V 1 1160761001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.48

AD-/DA-Converter

AD-Converter 12-Bit RS I-D12 0…20mA RS I-D12 4…20mA


Interface converter

Terminal
Digital
PIN volue
MSB LSB Analog
12 11 10 9 8 7 6 5 4 3 2 1 current
0 0 0 0 0 0 0 0 0 0 0 0 4 mA
0 0 0 0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0 0 1 0
0 0 0 0 0 0 0 0 0 0 1 1

1 1 1 1 1 1 1 1 1 1 0 1
1 1 1 1 1 1 1 1 1 1 1 0
1 1 1 1 1 1 1 1 1 1 1 1 20 mA

Technical data
Input
Input voltage/Input current /0…20 mA /4…20 mA
Max. voltage/Max. current /30 mA /30 mA
Input resistance voltage/Current /500 M /500 M
Resolution 4.9 µA = 1 LSB 4 µA = 1 LSB
Output
Number of outputs 12Bit 12Bit
Output level 24 V = H, 0 V = L 24 V = H, 0 V = L
Signs
Output current <= 25 mA (as source) <= 25 mA (as source)
Accuracy +/- 1 LSB +/- 1 LSB
Conversion time <= 50 µs <= 50 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE / ESD
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 90.0 x 47.4 70.0 x 90.0 x 47.4
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS I-D12 0…20MA 1 1168461001 RS I-D12 4…20MA 1 1169161001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.49

AD-/DA-Converter

AD-Converter 12-Bit RS U-D12 +/-10V RS U-D12 0…10V

Interface converter
Terminal
Digital
PIN volue
MSB LSB Analog
12 11 10 9 8 7 6 5 4 3 2 1 current
0 0 0 0 0 0 0 0 0 0 0 0 4 mA
0 0 0 0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0 0 1 0
0 0 0 0 0 0 0 0 0 0 1 1

1 1 1 1 1 1 1 1 1 1 0 1
1 1 1 1 1 1 1 1 1 1 1 0
1 1 1 1 1 1 1 1 1 1 1 1 20 mA

Technical data
Input
Input voltage/Input current -10…+10 V/ 0…10 V/
Max. voltage/Max. current +/- 15 V/ 15 V/
Input resistance voltage/Current 100 kM/ 100 kM/
Resolution 4.88 mV = 1 LSB 2.44 mV = 1 LSB
Output
Number of outputs 12Bit 12Bit
Output level 24 V = H, 0 V = L 24 V = H, 0 V = L
Signs MSB: H = positive; L = negative
Output current <= 25 mA (as source) <= 25 mA (as source)
Accuracy +/- 1 LSB +/- 1 LSB
Conversion time <= 50 µs <= 50 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE / ESD
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 90.0 x 47.4 70.0 x 90.0 x 47.4
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS U-D12 +-10V 1 1168261001 RS U-D12 0…10V 1 1168361001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.50

AD-/DA-Converter

DA-Converter 12-Bit RS D12-I 0…20mA RS D12-I 4…20mA


Interface converter

HOV123456789101112 HOV123456789101112

+ 24V Ua + 24V Ua
D D
A A
- 0V 0V - 0V 0V

Technical data
Input
Input/Output 12 Bit / analogue 12 Bit / analogue
Max. voltage
Max. current
Input voltage/Input current 24 Vdc +/- 20 %/4.2 mA 24 Vdc +/- 20 %/4.2 mA
Signs
Resolution 4.9 µA = 1 LSB 4 µA = 1 LSB
Output
Output voltage/Output current /0…20 mA (as source) /4…20 mA (as source)
Offset current/Offset voltage / /
Load resistance voltage/Current /< = 600 M /< = 600 M
Accuracy +/- 1 LSB +/- 1 LSB
Conversion time <= 4 µs <= 4 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption 60 mA 60 mA
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE / ESD
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 90.0 x 47.4 70.0 x 90.0 x 47.4
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS D12-I 0..20MA 1 1166061001 RS D12-I 4..20MA 1 1165961001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.51

AD-/DA-Converter

DA-Converter 12-Bit RS D12-U +/-10V RS D12-U 0…10V

Interface converter
HOV123456789101112 HOV123456789101112

+ 24V Ua + 24V Ua
D D
A A
- 0V 0V - 0V 0V

Technical data
Input
Input/Output 12 Bit / analogue 12 Bit / analogue
Max. voltage
Max. current
Input voltage/Input current 24 Vdc +/- 20 %/4.2 mA 24 Vdc +/- 20 %/4.2 mA
Signs MSB: H = positive; L = negative
Resolution 4.88 mV = 1 LSB 2.44 mV = 1 LSB
Output
Output voltage/Output current -10…+10 V/<= 10 mA 0…10 V/<= 10 mA
Offset current/Offset voltage / /
Load resistance voltage/Current >= 1 kM/< = 600 M >= 1 kM/< = 600 M
Accuracy +/- 1 LSB +/- 1 LSB
Conversion time <= 4 µs <= 4 µs
General data
Supply voltage 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Current consumption 40 mA 40 mA
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -40 °C…+80 °C -40 °C…+80 °C
Approvals CE / ESD CE / ESD
Insulation coordinates
EMC standards EMVG, EN 50081-1, EN 50082-2 EMVG, EN 50081-1, EN 50082-2

Dimensions Screw connection Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4 4 / 0.50 / 4
Length x width x height mm 70.0 x 90.0 x 47.4 70.0 x 90.0 x 47.4
Information

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection RS D12-U +-10V 1 1160861001 RS D12-U 0…10V 1 1166161001

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 15:15 Uhr Seite J.52

Preprocessing logic

Preprocessing logic DKPL


• Logic function and time function can be combi-
Logic modules

ned
• Individually programmable (further functions on
request)

In Out
1 7
2 +24...30V
3
Out
4
6
5 8
OV

Technical data
Input
Rated input level/ 24 Vdc = high, 0 V = low/
Input current approx. 1.5 mA each input (24V)
Max. voltage 30 Vdc
Pulse duration/ > 1 ms/
Output
Output level/ PNP, Ub-1 V/
Output current/ max. 20 mA/
Switching thresholds/ high > 18 V, low < 7 V/
General data
Supply voltage 24 Vdc +/- 20 %
Current consumption < 10 mA
Operation temperature 0 °C…+50 °C
Storage temperature -40 °C…+60 °C
Approvals CE / ESD

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4
Length x width x height mm 65.0 x 6.0 x 57.0
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection DKPL 35 24VDC 5 8248340000

Information not programmed - functions see following page

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 21.10.2003 13:06 Uhr Seite 53

Remarks:
The module is programmed specifically to customer requirements. Up to 5 inputs can
be linked with various logic and time functions, e.g. AND, OR, EXOR, NAND, NOR,
EXNOR, delay links, etc.

Logic modules
The output is either low- or high-active.
824834 0001 DKPL 824834 0003 DKPL Frequency divider 824834 0006 DKPL
A = (E1 OR E2) AND (E3 OR E4) AND E5 Inputs 1 - 5 determine the division factor Input 1: FOUT = FIN
Status Input Output Input 1 = division factor 1: FOUT = FIN 1 Input 2: FOUT = FIN 10
5 4 3 2 1 6 Input 2 = division factor 2: FOUT = FIN 2
1 0 0 0 0 0 0 Input 5 = division factor 5: FOUT = FIN 5; FIN max. = 12 kHz
2 0 0 0 0 1 0 Input Output Input Output
3 0 0 0 1 0 0 6 6
4 0 0 0 1 1 0 1 fout = fin 1 fout = fin
5 0 0 1 0 0 0 2 fout = fin / 2 2 fout = fin / 10
6 0 0 1 0 1 0 3 fout = fin / 3 3 fout = fin / 50
7 0 0 1 1 0 0 4 fout = fin / 4 4 fout = fin / 100
8 0 0 1 1 1 0 5 fout = fin / 5 5 fout = fin / 1000
9 0 1 0 0 0 0 Remarks: a new division factor can only be Remarks: a new division factor can only be
10 0 1 0 0 1 0 used after the operating voltage has been used after the operating voltage has been
11 0 1 0 1 0 0 switched off. fin max. = 12 kHz switched off. fin max. = 3 kHz
12 0 1 0 1 1 0
13 0 1 1 0 0 0
14 0 1 1 0 1 0
15 0 1 1 1 0 0
16 0 1 1 1 1 0
17 1 0 0 0 0 0
18 1 0 0 0 1 0
19 1 0 0 1 0 0
20 1 0 0 1 1 0
21 1 0 1 0 0 0
22 1 0 1 0 1 1 824834 0004 DKPL 824834 007 DKPL
23 1 0 1 1 0 1 Input 1: signal A from an incremental transducer Input Output
24 1 0 1 1 1 1 Input 2: signal B90 offset 1 2 3 4 5 Out
25 1 1 0 0 0 0 Input 3: enable high active L L X X X no function
26 1 1 0 0 1 1 Input 4: output signal inverted high active H L X X X f = 1 Hz
27 1 1 0 1 0 1 Input 5: no function L H X X X f = 10 Hz
28 1 1 0 1 1 1 Output: the output is set for 20 – 30 Us at every edge H H X X X f = 1 Hz
29 1 1 1 0 0 0 of signal A or B L -> 0 V or connection open
30 1 1 1 0 1 1 (i.e.: FOUT = 4xFIN) H -> +24 …30 Vdc
31 1 1 1 1 0 1 FIN max. 1 kHz X -> no influence on the output function, L or H
32 1 1 1 1 1 1
Connection Descritpion
1 A Signal A 90 ° leading Fmax = 1 kHz
2 B Signal B 90 ° trailing Fmax = 1 kHz 824834 0008 DKPL
3 enable enable output Input Output
4 invert invert output signal 1 2
5 no function H H H
6 fout = 4 x fA/B (max. 4 kHz) L H L

J
824834 0002 DKPL 824834 0010 DKPL
Inputs 1 and 2 have the function of an RS FLIP-FLOP RS FLIP-FLOP with superimposed S-input (connection 2)
Inputs 3, 4 and 5 have no function Inputs connections 3, 4 and 5 must be at 0V
Input Output or remain open!
2 1 6 Connection1 logic Connection2 logic Connection6 logic
0 0 0 (is saved) R-input S-input Output
0 1 no change to the saved status 0 V or open L 0 V or open L previous
1 0 no change to the saved status status is
1 1 1 (is saved) saved
Inputs 3, no change to the saved status +24 Vdc H 0 V or open L 0V L
4 and 5 with- 0 V or open L +24 Vdc H +24 Vdc H
out function +24 Vdc H +24 Vdc H +24 Vdc H

824834 0005 DKPL 824834 0501 DKPL


Input pulse length between 80 and 100 ms The component allows for division of the input frequency at
Output pulse length 100 ms, only 2 pulses connection 1 (0 .. max. 50 kHz) with 2 fixed division factors.
Pulse/pause ratio 1:1. Depending on connection 2, the output frequency is issued at
The positive edge of the input signal must be evaluated. the output connection 6.
Only input E1 is used. Connections 3, 4 and 5 have no function
Connection2 logic Factor Input frequency Output frequency
Connection 1 Connection 2
0 V or open L 75 0…30 kHz 0…400 Hz
24 Vdc H 27 0…10.8 kHz 0…400 Hz

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 16.10.2003 11:30 Uhr Seite J.54

Preprocessing logic

Preprocessing logic AND


• Logic functions
Logic modules

• Compact design
• PLC load reduction

In Out
1 7
+ 24 ... 30 V
2
3 &

4 Out
6
5 8
0V

Technical data
Input
Rated input level/ 24 Vdc = high, 0 V = low/
Input current approx. 1.5 mA each input (24V)
Max. voltage 30 Vdc
Pulse duration/ > 50 µs/
Output
Output level/ PNP, Ub-1.8 V/
Output current/ max. 20 mA/
Switching thresholds/ high <15 V, low < 9 V/
General data
Supply voltage 24…30 Vdc
Current consumption < 5 mA
Operation temperature 0 °C…+50 °C
Storage temperature -40 °C…+60 °C
Approvals CE / ESD

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4
Length x width x height mm 65.0 x 6.0 x 57.0
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection DK AND 35 24VDC 5 8184040000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 16.10.2003 11:30 Uhr Seite J.55

Preprocessing logic

Preprocessing logic NAND


• Logic functions

Logic modules
• Compact design
• PLC load reduction

In Out
1 7
+ 24 ... 30 V
2
3 &

4 Out
6
5 8
0V

Technical data
Input
Rated input level/ 24 Vdc = high, 0 V = low/
Input current approx. 1.5 mA each input (24V)
Max. voltage 30 Vdc
Pulse duration/ > 50 µs/
Output
Output level/ PNP, Ub-1.8 V/
Output current/ max. 20 mA/
Switching thresholds/ high <15 V, low < 9 V/
General data
Supply voltage 24…30 Vdc
Current consumption < 5 mA
Operation temperature 0 °C…+50 °C
Storage temperature -40 °C…+60 °C
Approvals CE / ESD

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4
Length x width x height mm 65.0 x 6.0 x 57.0
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection DK NAND 35 24VDC 5 8248320000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 16.10.2003 11:30 Uhr Seite J.56

Preprocessing logic

Preprocessing logic OR
• Logic functions
Logic modules

• Compact design
• PLC load reduction

In Out
1 7
+ 24 ... 30 V
2
3 <
– 1
4 Out
6
5 8
0V

Technical data
Input
Rated input level/ 24 Vdc = high, 0 V = low/
Input current approx. 1.5 mA each input (24V)
Max. voltage 30 Vdc
Pulse duration/ > 50 µs/
Output
Output level/ PNP, Ub-1.8 V/
Output current/ max. 20 mA/
Switching thresholds/ high <15 V, low < 9 V/
General data
Supply voltage 24…30 Vdc
Current consumption < 5 mA
Operation temperature 0 °C…+50 °C
Storage temperature -40 °C…+60 °C
Approvals CE / ESD

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4
Length x width x height mm 65.0 x 6.0 x 57.0
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection DK OR 35 24VDC 5 8218440000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 16.10.2003 11:30 Uhr Seite J.57

Preprocessing logic

Preprocessing logic NOR


• Logic functions

Logic modules
• Compact design
• PLC load reduction

In Out
1 7
+ 24 ... 30 V
2
3 <
– 1
4 Out
6
5 8
0V

Technical data
Input
Rated input level/ 24 Vdc = high, 0 V = low/
Input current approx. 1.5 mA each input (24V)
Max. voltage 30 Vdc
Pulse duration/ > 50 µs/
Output
Output level/ PNP, Ub-1.8 V/
Output current/ max. 20 mA/
Switching thresholds/ high <15 V, low < 9 V/
General data
Supply voltage 24…30 Vdc
Current consumption < 5 mA
Operation temperature 0 °C…+50 °C
Storage temperature -40 °C…+60 °C
Approvals CE / ESD

Dimensions Screw connection


Clamping range (rating- / min. / max.) mm2 4 / 0.50 / 4
Length x width x height mm 65.0 x 6.0 x 57.0
Information

Ordering data
Type of connection Type Qty. Order No.
Screw connection DK NOR 35 24VDC 5 8248330000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 21.10.2003 13:53 Uhr Seite 59

Monitoring modules

Current and voltage monitoring

Monitoring modules
The monitoring of current and voltage allows constant control
of individual systems or installation parts. Deviations or inter-
ruptions occurring in the electric circuits can be evaluated as
Hall sensor
operation interruptions. Specific measures can be taken to
remedy the problem. internal

Products for monitoring current convert sinus or non-sinus ac


and dc current up to 60 A into analogue standard signals. The
measuring procedures are based on two principles. On the
one hand, ac current up to 10 A and 50/60 Hz are measured
using the transforming method. The module is looped
directly into the measuring circuit. From 10 A ac/dc, the Hall
sensor is used.

The conductor is pushed through the module free of potential


and allows current measurements up to 60 A ac/dc. Often
there are high-frequency signal parts on the line being meas-
ured. To take account of the signal parts, so-called TRMS
converters (true root mean square) are connected up in
series. They allow measurements up to 2 kHz regardless of 230 Vac

the curve shape. Available outputs are standard signals 0..20 ~


24 Vdc
mA, 4..20 mA, 4 ..20 mA current loop feed, 0..10 V or a 10 11 12 SPS
switch output.

0…20 mA
7 8 9

L1

WAVE CONTROL

8581220000/85811230000
L2

VMA Vac
Modules for voltage monitoring measure the mains voltage up L3
to max. 450 V ac. The unit provides isolated qualitative infor-
mation in the form of a standard signal (0..20 mA, 4..20 mA,
0..10 V). Extreme loads or load relief on the power supply can 1 2 3

cause short-term voltage fluctuations with a negative influence M U


4 5 6

on the process. The WAVECONTROL module VMA transmits the 3~


relevant information to the control so that suitable process
safety measures can be taken.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.60

Current monitoring

Relay output 1/5/10A ac 20/40/60A ac


Monitoring modules

• Current range adjustable via DIP-switch


• Switchable hysteresis
• Operating current or closed current principle

CC 7
1 CC
4 + 24V 2 10 ~
3 +24V 1 12 8
NC0V 11
5 2 10% 100% 11
CC 10% 100% 11 Setpoint
OV 3 K1 14
Setpoint ~ 9
IN 12
6 K1 12
CC

Technical data
Input
Input current 0…1 Aac/ 0…5 Aac/ 0…10 Aac 0…20 Aac/ 0…40 Aac/ 0…60 Aac
Input frequency 50…60 Hz 50…60 Hz
Max. current 100 A for 1s dependent on conductor cross-section
Max. voltage 250 Vac 400 Vac, > 400V ac depends on wire insulation
Sensor Transforming (internally) hall sensor (internal)
Diameter of bushing 8 mm
Output
Switching thresholds 10…100 % by front poten. 10…100 % by front poten.
Hysteresis 5 % or 10 % of threshold value 5 % or 10 % of threshold value
Switching voltage max./Switching voltage min. 60 Vdc/ 250 Vac/6 Vdc/ac 60 Vdc/ 250 Vac/6 Vdc/ac
Switching current max./Switching current min. 7 A/100 mA 7 A/100 mA
Step response time typ. 700 ms typ. 700 ms
Temperature coefficient <= 800 ppm/K <= 250 ppm/K
Status indicator LED green LED green
General data
Supply voltage 24 Vdc +/- 10 % 24 Vdc +/- 10 %
Current consumption 8.3 mA (Relay not triggered)/ 24 mA (Relay triggered) 23 mA (Relay not triggered)/ 47 mA (Relay triggered)
Current-carrying cap. of cross-connect. <= 2 A <= 2 A
Operation temperature 0 °C…+50 °C 0 °C…+50 °C
Storage temperature -20 °C…+70 °C -20 °C…+70 °C
Default settings 0…5A / 10% Hysteresis / current principle 0…40A / 10% Hysteresis / current principle
Approvals CE / ESD / cURus CE / ESD / cURus
Contact arrangement 1 changeover contact 1 changeover contact
J Insulation coordinates
Rated voltage 300 V 300 V
Impulse withstand voltage 4 kV 4 kV
Pollution severity 2 2
Overvoltage category III III
Clearance & creepage path >= 3 mm >= 3 mm
Isolation voltage Input, output 4 kVeff / 5s 4 kVeff / 5s

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection WAS2 CMR 1/5/10A ac 1 8516560000 WAS2 CMR 20/40/60A ac 1 8513340000
Tension clamp c. WAZ2 CMR 1/5/10A ac 1 8516570000 WAZ2 CMR 20/40/60A ac 1 8526600000

Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.61

Current monitoring

Analogue output 1/5/10A ac 1/5/10A ac 4…20mA

Monitoring modules
• Input and output adjustable via DIP-switch Current loop
• Calibration not necessary

1 1
+ 24V 7 Out + 7
NC NC
2 2
I CC Output 8 NC 8
IN I
IN
3 CC 0V 9 3
U/I I Out - 9

Technical data
Input
Input current 0…1 Aac/ 0…5 Aac/ 0…10 Aac 0…1 Aac/ 0…5 Aac/ 0…10 Aac
Input frequency 50…60 Hz 50…60 Hz
Max. current 100 A for 1s 100 A for 1s
Voltage of measuring circuit 250 Vac 250 Vac
Sensor Transforming (internally) Transforming (internally)
Diameter of bushing
Output
Output current/Output voltage 0(4)…20 mA/0…10 V 4…20 mA (current loop)/
Offset current max. 100 µA max. 100 µA
Output signal limit approx. 13 V resp. 24 mA approx. 24 mA
Load resistance voltage/Current >= 1 kM/< = 600 M /< = 600 M
Step response time typ. 700 ms typ. 700 ms
Accuracy 0.5% FSR 0.5 % FSR
Temperature coefficient <= 200 ppm/K <= 200 ppm/K
Status indicator LED ON: OK; FLASHING: signal out of range;OFF: Error LED ON: OK; FLASHING: signal out of range;OFF: Error
General data
Supply voltage 24 Vdc +/- 10 % 13…30 Vdc
Current consumption 40 mA at Iout=20 mA
Current-carrying cap. of cross-connect. <= 2 A
Operation temperature/Storage temperature 0 °C…+50 °C/-20 °C…+70 °C 0 °C…+50 °C/-20 °C…+70 °C
Default settings 0…5Aac, 4…20mA 0…5Aac, 4…20mA
Approvals CE / ESD / cURus CE / ESD / cURus
Insulation coordinates
Rated voltage 300 V 300 V J
Impulse withstand voltage 6 kV 6 kV
Pollution severity 2 2
Overvoltage category III III
Clearance & creepage path >= 5.5 mm >= 5.5 mm
Isolation voltage Input, output 4 kVeff / 5s 4 kVeff / 5s

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 72.0 x 22.5 x 92.4 72.0 x 22.5 x 92.4 72.0 x 22.5 x 92.4 72.0 x 22.5 x 92.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection WAS1 CMA 1/5/10A ac 1 8523400000 WAS1 CMA LP 1/5/10A ac 1 8528650000
Tension clamp c. WAZ1 CMA 1/5/10A ac 1 8523410000 WAZ1 CMA LP 1/5/10A ac 1 8528660000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.62

Current monitoring

Analogue output 5/10A ac/dc 20/25/30A ac/dc


Monitoring modules

• Input and output adjustable via DIP-switch


• Calibration not necessary

IN OUT IN OUT
WIRE WIRE
~
IN +
1 0...10V 7 ~
IN +
1 0...10V 7
2 CC I 0/4...20mA 8 2 CC I 0/4...20mA 8

- 3CC U/I OV 9 - 3CC U/I OV 9


OUT ~ OUT ~
OV OV

Technical data
Input
Input current 0…5 Aac/dc/ 0…10 Aac/dc 0…20 Aac/dc/0…25 Aac/dc / 0…30 Aac/dc
Input frequency 0…2 kHz (true RMS to DC converter) 0…2 kHz (true RMS to DC converter)
Max. current dependent on conductor cross-section dependent on conductor cross-section
Voltage of measuring circuit 400 Vac, >400V ac depends on conductor insulation 400 Vac, >400V ac depends on conductor insulation
Sensor hall sensor (internal) hall sensor (internal)
Diameter of bushing 8 mm 8 mm
Output
Output current/Output voltage 0(4)…20 mA/0…10 V 0(4)…20 mA/0…10 V
Offset current max. 150 µA max. 150 µA
Output signal limit approx. 13 V resp. 24 mA approx. 13 V resp. 24 mA
Load resistance voltage/Current >= 1 kM/< = 600 M >= 1 kM/< = 600 M
Step response time typ. 700 ms typ. 700 ms
Accuracy 0.5% FSR 0.5% FSR
Temperature coefficient <= 650 ppm/K <= 650 ppm/K
Status indicator LED ON: OK; FLASHING: signal out of range;OFF: Error LED ON: OK; FLASHING: signal out of range;OFF: Error
General data
Supply voltage 24 Vdc +/- 10 % 24 Vdc +/- 10 %
Current consumption 50 mA at Iout=20 mA 50 mA at Iout=20 mA
Current-carrying cap. of cross-connect. <= 2 A <= 2 A
Operation temperature/Storage temperature 0 °C…+50 °C/-20 °C…+70 °C 0 °C…+50 °C/-20 °C…+70 °C
Default settings 0…5A, 4…20mA 0…25A, 4…20mA
Approvals CE / ESD / cURus CE / ESD / cURus
Insulation coordinates
J Rated voltage 300 V 300 V
Impulse withstand voltage 6 kV 6 kV
Pollution severity 2 2
Overvoltage category III III
Clearance & creepage path >= 5.5 mm >= 5.5 mm
Isolation voltage Input, output 4 kVeff / 5s 4 kVeff / 5s

Dimensions Screw connection Tension clamp c. Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4
Information Tu=23°C, single module Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No. Type Qty. Order No.
Screw connection WAS2 CMA 5/10A uc 1 8526610000 WAS2 CMA 20/25/30A uc 1 8545830000
Tension clamp c. WAZ2 CMA 5/10A uc 1 8526620000 WAZ2 CMA 20/25/30A uc 1 8545840000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2 Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.63

Current monitoring

Analogue output 40/50/60A ac/dc

Monitoring modules
• Input and output adjustable via DIP-switch
• Calibration not necessary

IN OUT
WIRE
~
IN +
1 0...10V 7
2 CC I 0/4...20mA 8

- 3CC U/I OV 9
OUT ~
OV

Technical data
Input
Input current 0…40 Aac/dc/ 0…50 Aac/dc/ 0…60 Aac/dc
Input frequency 0…2 kHz (true RMS to DC converter)
Max. current dependent on conductor cross-section
Voltage of measuring circuit 400 Vac, >400V ac depends on conductor insulation
Sensor hall sensor (internal)
Diameter of bushing 8 mm
Output
Output current/Output voltage 0(4)…20 mA/0…10 V
Offset current max. 150 µA
Output signal limit approx. 13 V resp. 24 mA
Load resistance voltage/Current >= 1 kM/< = 600 M
Step response time typ. 700 ms
Accuracy 0.5% FSR
Temperature coefficient <= 650 ppm/K
Status indicator LED ON: OK; FLASHING: signal out of range;OFF: Error
General data
Supply voltage 24 Vdc +/- 10 %
Current consumption 50 mA at Iout=20 mA
Current-carrying cap. of cross-connect. <= 2 A
Operation temperature/Storage temperature 0 °C…+50 °C/-20 °C…+70 °C
Default settings 0…50A, 4…20mA
Approvals CE / ESD / cURus
Insulation coordinates
Rated voltage 300 V J
Impulse withstand voltage 6 kV
Pollution severity 2
Overvoltage category III
Clearance & creepage path >= 5.5 mm
Isolation voltage Input, output 4 kVeff / 5s

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS2 CMA 40/50/60A uc 1 8513330000
Tension clamp c. WAZ2 CMA 40/50/60A uc 1 8526590000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.64

Current monitoring

Analogue output CMA 100/5A CMA 250/5A CMA 500/5A


Monitoring modules

• Max. conductor diameter 35mm


• Can be added sidewise
• Mounting on mounting-rail TS35

Technical data
Input
Input current 100 Aac 250 Aac 500 Aac
Input frequency Class 1: 50…60Hz / Class 1.5: 16…400Hz Class 1: 50…60Hz / Class 1.5: 16…400Hz Class 1: 50…60 Hz / Class 1.5: 16…400 Hz
Max. current thermal current Ith >3 kA thermal current Ith >3 kA thermal current Ith >3 kA
Voltage of measuring circuit 600 V eff (unfinished conductor) 600 V eff (unfinished conductor) 600 V eff (unfinished conductor)
Diameter of bushing 35 mm 35 mm 35 mm
Output
Output current 5 Aac 5 Aac 5 Aac
Load resistance voltage/Current /< = 600 M /< = 600 M /< = 600 M
Accuracy class 1 / 1.5; residual current factor < 5 class 1 / 1.5; residual current factor < 5 class 1 / 1.5; residual current factor < 5
General data
Operation temperature/Storage temperature -5 °C…+40 °C/-40 °C…+85 °C -5 °C…+40 °C/-40 °C…+85 °C -5 °C…+40 °C/-40 °C…+85 °C
Approvals CE / cURus CE / cURus CE / cURus
Insulation coordinates
Isolation voltage Input, output 4 kVeff / 1 min. 4 kVeff / 1 min. 4 kVeff / 1 min.

Dimensions Screw connection (secondary) Screw connection (secondary) Screw connection (secondary)
Clamping range (rating- / min. / max.) mm2
Length x width x height mm 50.0 x 78.0 x 90.5 50.0 x 78.0 x 90.5 50.0 x 78.0 x 90.5

Information

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Screw connection (secondary) CMA 100/5A 8662140000 CMA 250/5A 8664570000 CMA 500/5A 8664580000

Information

Accessories
Information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.65

Voltage monitoring

Analogue output VMA Vac

Monitoring modules
• 3-way disconnection
• Max. measuring-voltage 450 Vaceff
• Output selectable via DIP-switch
• Calibration not necessary

Application

230 Vac
~
24 Vdc

10 11 12 SPS
7 8 9

0 20 mA
L1

WAVE CONTROL

8581220000/85811230000
L2

VMA Vac
L3

1 2 3

Technical data M U
4 5 6

3~
Input
Input voltage 0…30Vac/ 0…70Vac/ 0…130Vac/ 0…250Vac/ 0…450Vac
Input frequency 40…40 Hz sinus
Input voltage 0…30Vac/ 0…70Vac/ 0…130Vac/ 0…250Vac/ 0…450Vac
Max. voltage 45 Vac / 100 Vac / 180 Vac / 270 Vac / 475 Vac (short time)
Output
Output voltage/Output current 0…10 V/0(4)…20 mA
Offset voltage/Offset current max. 0.02 V/max. 40 µA
Load resistance voltage/Current >= 1 kM/< = 600 M
Accuracy 1.3 % (40…60 Hz) typ. 1 %/ 2 % (70…400 Hz) typ. 1.5 %
Temperature coefficient <= 250 ppm/K
Step response time 300 ms
Status indicator LED green
General data
Supply voltage 24 Vdc +/- 25 %
Current consumption 40…30…24 mA at Iout=20 mA
Current-carrying cap. of cross-connect. <= 2 A
Default settings 0…10V/0…20mA
Operation temperature 0 °C…+50 °C
Storage temperature -20 °C…+70 °C
Approvals CE / ESD / cURus
Insulation coordinates
Standards EN 50178
EMC standards EN 50081-1, EN 61000-2-6, EN 61326
Rated voltage supply/output: 300 V; input/output, supply/output: 600 V J
Impulse withstand voltage supply/output: 4 kV; input/output, supply/output: 6kV
Isolation voltage Input, output/ 4 kVeff / 5s/
Overvoltage category III
Pollution severity 2
Clearance & creepage path supply/output: 3mm; input/output, supply/output: 5.5mm

Dimensions Screw connection Tension clamp c.


Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50
Length x width x height mm 92.4 x 22.5 x 112.4 92.4 x 22.5 x 112.4
Information Tu=23°C, single module

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS2 VMA V ac 1 8581220000
Tension clamp c. WAZ2 VMA V ac 1 8581230000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.66

Threshold monitoring

Relay output DC/Alarm


Monitoring modules

• 3-way disconnection
• Low trip / high trip
• FAILSAFE / NON FAILSAFE
• 2 Relay outputs 250Vac/3A

Switch position/setting options


SW 1
function 1 2 3 4
Kanal A High Trip 
Kanal A Low Trip 
Kanal B High Trip 
Kanal B Low Trip 
FAILSAFE, Kanal 1 & 2  
NON FAILSAFE, Kanal 1 & 2  

 = on
 = off

NON FAILSAFE:The relay picks up when the arlarm is trige-


red
FAILSAFE: The relay drops out when the arlarm is trig-
gered. An alarm is also triggered in the
Technical data FAILSAFE mode, if for example, the opera-
Input ting voltage to the moduls fail
Input voltage 0…10 V Low Trip: Alarm is triggered if the signal is undershoot
Input current 0(4)…20 mA the threshold.
Input resistance voltage/Current >= 100 kM/< = 110 M High Trip: Alarm is triggered if the signal is overshoot
the threshold.
Output
Signal threshold:Adjustments of the signal threshold
Contact arrangement 2 change-over contacts (1...90)% are made for channel 1 with the
Contact material AgNi 90/10 potentiometer P1, and separately for chan-
Switching thresholds 1…90 % (independently for channel 1 and channel 2) nel 2 via potentiometer P2.
Hysterese: Adjustments of the hysteresis (1...10)% are
Hysteresis 1…90 % (independently for channel 1 and channel 2)
made for channel 1 with the potentiometer
Switching voltage max./Switching voltage min. 253 Vac/ P3, and separately for channel 2 via poten-
Continuous current 3A tiometer P3.
Function failsafe / non failsafe WAVEANALOG DC/Alarm
Temperature coefficient <= 500 ppm/K – Alarm indication
Status indicator LED green ON: OK, LED red ON: alarm (per channel)
General data Example 1
Supply voltage 24 Vdc +/- 25 %
100%
Power consumption typ. 1 W both relays picked up
Current-carrying cap. of cross-connect. <= 2 A Sc alSignal threshold
ll 2 / high
1 /trip
high trip
5% Hysteresis
Operation temperature 0 °C…+55 °C (fitted)
Storage temperature -20 °C…+85 °C SchalSignal threshold
chwelle 1 / high2trip
/ high trip
50%
Input range

Default settings channel A/B: low trip and FAILSAFE 10% Hysteresis

Approvals CE / ESD / cURus


Insulation coordinates
Standards EN 50178
J EMC standards EN 61000-4-2, -3, -4, -5, -6
1
Rated voltage 300 V Relay 2 NON FAILSAFE

Impulse withstand voltage 4 kV 0

Pollution severity 2 1 Relay 1 NON FAILSAFE


Overvoltage category III 0
Clearance & creepage path >= 3 mm Zeit

Isolation voltage Input, output 1.2 kVeff / 5s

Example 2
Dimensions Screw connection Tension clamp c. 100%
Signal threshold 1 / high trip
Clamping range (rating- / min. / max.) mm2 2.50 / 0.50 / 2.50 1.50 / 0.50 / 2.50 5% Hysteresis

Length x width x height mm 92.4 x 17.5 x 112.4 92.4 x 17.5 x 112.4


Information Tu=23°C, single module 10% Hysteresis
50%
Input range

Signal threshold 2 / low trip

Ordering data
Type of connection Type Qty. Order No.
Screw connection WAS5 DC/Alarm 1 8543820000
1
Tension clamp c. WAZ5 DC/Alarm 1 8543880000 Relay 2 FAILSAFE
0

Information 1 Relay 1 FAILSAFE


0
Time

Accessories
Information Voltage supply 24V and 0V with ZQV 2.5N/2
cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J006-J067_GB 23.10.2003 16:30 Uhr Seite J.67

Threshold monitoring

Transistor output MCZ SC 0…10V MCZ SC 0…20mA

Monitoring modules
• 2 digital outputs
• Monitoring of upper and lower le-
vel

4 3 Vcc 2
+24V OV
Output1 P1 Th1
max.50mA
Input
P2 Th2
0...20mA
5 Output2 S1 S2 Uth 1
off x 300mV...10V
max.50mA on off 30mV...1V
on off 10mV...100mV

Technical data
Input
Input voltage/Input current 0…10 V/ /0.5…20 mA
Input resistance voltage/Current 60 kM/ /50 M
Voltage drop 1V
Output
Contact arrangement/ double switch output PNP/ double switch output PNP/
Function Uin < Uth1: Output 1 active / Uin > Uth2: Iin < Ith 1: Output 1 active / Iin > Ith2: Output
Switching thresholds Output 2 active 2 active
Hysteresis via 2 potentiometers (12 turns) via 2 potentiometers (12 turns)
Switching current max. 1% of adjusted final value 1% of final value
Step response time 50 mA - per channel (voltage drop at output 50 mA - per channel (voltage drop at output
Cut-off freq. (-3dB) transistor: < 1.2 V at 50 mA) transistor: < 1.2 V at 50 mA)
Temperature coefficient < 250 µs (switch threshold at 90% of the < 250 µs (switch threshold at 90% of the
General data max. input signal; Rl<=1 kM) max. input signal; Rl<=1 kM)
Supply voltage 100 Hz 100 Hz
Current consumption 250 ppm/K (max. 500 ppm/K) max. 250 ppm/K
Operation temperature
Storage temperature 24 Vdc +/- 20 % 24 Vdc +/- 20 %
Approvals 15 mA 15 mA
0 °C…+50 °C 0 °C…+50 °C
-25 °C…+60 °C -25 °C…+60 °C

Dimensions Tension clamp c. Tension clamp c.


Clamping range (rating- / min. / max.) mm2 1.50 / 0.50 / 1.50 1.50 / 0.50 / 1.50
Length x width x height mm 91.0 x 6.0 x 63.2 91.0 x 6.0 x 63.2

Information

Ordering data
Type of connection Type (Qty.=1) Order No. Type (Qty.=1) Order No.
Tension clamp c. MCZ SC 0-10V 8260280000 MCZ SC 0-20MA 8227350000

Information

Accessories
Information Voltage supply 24V and 0V with ZQV 4/x Voltage supply 24V and 0V with ZQV 4/x
cross-connection cross-connection

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 23.10.2003 15:39 Uhr Seite 68

Accessories
MICROANALOG
Srew connection Tension clamp connection
Accessories

88 92

90

90
97,8

97,8
6,1

6,1

Accessories Type Order no. Qty


Cross connection, 2-poles, red ZQV 4N/2 rt 1793950000 60
Cross connection, 3-poles, red ZQV 4N/3 rt 1793980000 60
Cross connection, 4-poles, red ZQV 4N/4 rt 1794010000 60
Cross connection, 10-poles, red ZQV 4N/10 rt 1794040000 20
Cross connection, 41-poles, red ZQV 4N/41 rt 1794070000 10

Cross connection, 2-poles, blue ZQV 4N/2 bl 1793960000 60


Cross connection, 3-poles, blue ZQV 4N/3 bl 1793990000 60
Cross connection, 4-poles, blue ZQV 4N/4 bl 1794020000 60
Cross connection, 10-poles, blue ZQV 4N/10 bl 1794050000 20
Cross connection, 41-poles, blue ZQV 4N/41 bl 1794080000 10

Terminalmarker WS10/6 1060960000 200

MCZ

91

J
56
63,2

TS-Contact

Accessories Type Order no. Qty


Cross connection, 2-poles, yellow ZQV 4N/2 ge 1608950000 20
Cross connection, 3-poles, yellow ZQV 4N/3 ge 1608960000 20
Cross connection, 4-poles, yellow ZQV 4N/4 ge 1608970000 20
Cross connection, 5-poles, yellow ZQV 4N/5 ge 1608980000 20
Cross connection, 6-poles, yellow ZQV 4N/6 ge 1608990000 20
Cross connection, 7-poles, yellow ZQV 4N/7 ge 1609000000 20
Cross connection, 8-poles, yellow ZQV 4N/8 ge 1609010000 20
Cross connection, 9-poles, yellow ZQV 4N/9 ge 1609020000 20
Cross connection, 10-poles, yellow ZQV 4N/10 ge 1609030000 20

Terminalmarker WS10/6 1060960000 200

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]


SSB_J_manuelle_S_GB.xpr5 23.10.2003 15:39 Uhr Seite 69

Accessories
WAVEBOX S 22,5 WAVEBOX L 22,5

Accessories
WAVEBOX 12,5 WAVEBOX 17,5

Accessories Type Order no. Qty


Cross connection ZQV 2,5N/2 black ZQV 2,5N/2 sw 1718080000 60
Cross connection ZQV 2,5N/2 red ZQV 2,5N/2 rt 1717900000 60
Cross connection ZQV 2,5N/2 blue ZQV 2,5N/2 bl 1717990000 60
Cross connection ZQV 2,5N/2 yellow ZQV 2,5N/2 ge 1693800000 60

Terminalmarkers
WS 10/5 Multicard WS 10/5 1635010000 144
WS 10/5 Neutral WS 10/5 Neutral 1060860000 200

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

You might also like