MaRweb.
sk
www.marweb.sk
KD6 - screen recorder
• Up to 60 logical channels (max. up to 8 analog channels).
• Input:
• measuring programmable (0,4 or 8),
• binary (2 or 6),
• digital Modbus RTU Master (10 devices up to 10 registers).
• Outputs:
• relays (2, 6 or 8),
• analog 0/4...20mA (0, 4 or 8),
• supplying output 24V d.c. / 30mA,
• digital RS-485 Modbus.
• Graphical color display: LCD TFT 3.5’’, 320 x 240 pixels, fully configurable by a user.
• Archiving of measured parameters in the internal file system memory
with a capacity of 8GB.
• Data logging in the form of CSV.
• Extensive alarm, math and scaling functions.
tri
cal Sa • Data presentation in digital form, in form of analog indicators, line charts, bargraphs.
V V V • Independent recording for each group of logical channels (interval, registration trigger mode.
Elec
fe t
• Built-in USB HOST 2.0.
y
CAT III • Modern and user-friendly Ethernet interface 10/100 BASE-T:
• protocol: MODBUS TCP/IP, HTTP, FTP,
• services: www server, ftp server, DHCP client.
• Programming of parameters using free eCon software.
• NTP client for synchronization with a time server.
• Overall dimensions: 96 x 96 x 77 mm.
Example of application
PLc
4-20 mA
max. 8 outputs
max. 14
max. 8 inputs
global
encoder
0-10V KD6 Monitoring
.csv
4-20mA
vibration Ethernet www/ ftp
sensor global
Monitoring
bearing Pt100
temp. Ethernet TCP IP
sensor
winding Pt1000 RS-485
temp. global
sensor Monitoring
local
Monitoring
P43 usb host
10 devices x 10 registers
KD6 RS-485
Monitoring of engine operating parameters.
current, voltage, power, thd measurement
Distributor Slovakia: MaRweb.sk mob. +421 908 170 313 web. www.marweb.sk
KD6 - screen recorder
features inputs outputs galvanic isolation
RS 0/4..20
IP65
DC 485 mA
Ochrona
hasłem
A f(x) RS 485 RS
NTP MASTER Ethernet Zasilanie 485
Technical data
inputs
Sensor type / Input signal Standard Range Basic error
PT100 -200...850 °C -328...1562 °F
RTD
PT500 EN 60751:2009 -200...850 °C -328...1562 °F
PT1000 -200...850 °C -328...1562 °F
Fe-CuNi (J) -100...1200 °C -148...2192 °F
Cu-CuNi (T) -100...400 °C -148...752 °F
NiCr-NiAl (K) -100...1370 °C -148...2498 °F
PtRh10-Pt (S) -5...1760 °C 23...3200 °F
EN 60584-1:2014
PtRh13-Pt (R) -5...1760 °C 23...3200 °F 0.2%
PtRh30-PtRh6 (B) 200...1820 °C 392...3200 °F
NiCr-CuNi (E) -100...1000 °C -148...1832 °F
NiCrSi-NiSi (N) -100 ...1300 °C -148...2372 °F
±10 V, ±300 mV, ±75 mV,
Voltage 10 V, 300 mV, 75 mV,
Current ±40 mA, 40 mA
Resistance R 0...4000 Ω
additional inputs
2 or 6 inputs; 0 V d.c. – inactive binary input,
Binary inputs
5...24 V d.c. – active binary input
Outputs
Output type Properties
Analog current: 0/4 .. 20 mA programable, load resistance ≤ 400 Ω
Relays 2, 6, 8 relays, NOC, load 250V / 0,5A a.c. or 30V / 5A d.c.
Suplying output 1x output 24V d.c. /30 mA
Digital interface
Interface type Properties
1x Modbus Master/Slave interface Transmission mode Modbus RTU: 8N2, 8E1, 8O1
RS-485 1x Modbus Slave interface Bauderate: 9.6, 19.2, 38.4, 57.6, 115.2 kbit/s
Address:1...247
Modbus TCP/IP, NTP protocoll WWW server, FTP server, DHCP client
Ethernet
10/100 Base-T RJ45 socket
USB HOST 2.0
external features
Readout field graphical color display: LCD TFT 3.5’’, 320 x 240 pixels
Overall dimensions 96 x 96 x 77 mm panel cut-out dimensions: 92.5 x 92.5 mm
Weight 0.3 kg
Protection grade fron frontal side: IP65 from terminal side: IP20
2
KD6 - screen recorder
rated operating conditions
85...253 V a.c. (40...50...60 ... 400 Hz), 90...300 V d.c.
Supply voltage power consumption ≤ 12 VA
or 20...60 V d.c.
Preheating time 30 min.
Ambient temperature -10…23…55°C, K55 class acc. to EN61557-12
Humidity 0...40...60…95% without condensation
Operating position any
Additional error (in % of the basic error) from ambient temperature change: < 50% / 10°C
Safety and compability requirements
noise immunity acc. to EN 61000-6-2
Electromagnetic compatibility
noise emissions acc. to EN 61000-6-4
Isolation between circuits basic acc. to EN 61010-1
Polution level 2 acc. to EN 61010-1
Installation category III acc. to EN 61010-1
• for supply circuit and relay outputs 300 V
Maximal phase-to-earth voltage • for measuring input 50 V acc. to EN 61010-1
• for circuits of RS-485, Ethernet, analog outputs: 50 V
Altitude a.s.l. < 2000 m
data visualisation
Various forms of data presentation:
• line charts
• digital indicators
• analog view
• bargraphs
up to 10 programmable screens
(6 parameters per page);
ability to change color for all screens
Available colors for digital indications:
Easy to use and intuitive menu;
information bar with status of:
logical group archiving, USB port status,
status of used memory storage,
Ethernet and RS-485 interface,
time and data.
3
KD6 - screen recorder
recordeR configuration with FREE eCon Software
ability to configure and update of KD6
with free eCon software
(via RS-485 or Ethernet interface)
Saving the configuration to a file
and loading to many of the same recorders
or creating a backup copy.
remote readout of parameters throug Ethernet: WWW server, FTP
www server for remote reading
of current measurement data;
FTP server for downloading
archived data in CSV files
4
MaRweb.sk
www.marweb.sk
KD6 - screen recorder
ordering code
KD6 X X X XX X X
I/O module – slot X*:
4 x programmable measuring inputs 4
I/O module – slot Y:
without module 0
6 x relay outputs 1
4 x relay outputs + 4 x binary inputs separated from each other 2
4 x analog outputs + 4 x binary inputs with common ground 3
4 x programmable measuring inputs 4
Supply voltage:
85...253 V a.c., 90...300 V d.c. 1
20...60 V d.c. 2
Version:
standard 00
custom-made** XX
Language:
Polish/English M
other* X
Acceptance tests:
with test certificate 0
with calibration certificate 2
acc.to customer’s request** X
* all possible variants for slot X are described in the user manual in chapter 11
** only after agreeing with the manufacturer
Distributor Slovakia: MaRweb.sk mob. +421 908 170 313 web. www.marweb.sk