Product data sheet

Specifications

Miniature circuit-breaker, Acti9 iC40,


1P+N, 6 A, B curve, 4500 A (IEC
60898-1), 6 kA (IEC 60947-2)
A9P42606

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Acti9

Product name Acti9 iC40

Product or component type Miniature circuit-breaker

Device short name iC40

Device application Distribution

Poles description 1P + N

Number of protected poles 1

Neutral position Left

[In] rated current 6 A

Network type AC

Trip unit technology Thermal-magnetic

Curve code B

Breaking capacity 6 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2


4500 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1

Suitability for isolation Yes conforming to EN/IEC 60947-2

Quality labels KEMA


IMQ

Complementary
Network frequency 50/60 Hz

[Ue] rated operational voltage 230 V AC 50/60 Hz

Magnetic tripping limit 3...5 x In conforming to EN/IEC 60898-1


4 x In +/- 20 % conforming to EN/IEC 60947-2

[Ics] rated service breaking 4500 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
capacity 4.5 kA 75 % x Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2

Limitation class 3 conforming to EN/IEC 60898-1

[Ui] rated insulation voltage 400 V AC 50/60 Hz conforming to EN/IEC 60947-2

[Uimp] rated impulse withstand 4 kV conforming to EN/IEC 60947-2


voltage

Contact position indicator Yes

Control type Toggle

Local signalling ON/OFF indication

Aug 13, 2022 1


Trip indicator

Mounting mode Clip-on

Mounting support DIN rail

9 mm pitches 2

Height 85 mm

Width 18 mm

Depth 74 mm

Net weight 120 g

Colour White

Mechanical durability 20000 cycles

Electrical durability 20000 cycles

Locking options description Padlocking device

Connections - terminals Tunnel type terminals top or bottom 1…10 mm² flexible


Tunnel type terminals top or bottom 1…16 mm² rigid

Wire stripping length 14 mm for top or bottom connection

Tightening torque 2 N.m top or bottom

Earth-leakage protection Separate block

Environment
Standards EN/IEC 60898-1
EN/IEC 60947-2

Product certifications CE
BV
RINA
DNV

IP degree of protection IP20 conforming to IEC 60529


IP40 (modular enclosure) conforming to IEC 60529

Pollution degree 3 conforming to EN/IEC 60947-2

Relative humidity 95 % at 55 °C

Operating altitude 2000 m

Ambient air temperature for -25…70 °C


operation

Ambient air temperature for -40…85 °C


storage

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Weight 117.0 g

Package 1 Height 1.8 cm

Package 1 width 7.4 cm

Package 1 Length 9.4 cm

Unit Type of Package 2 BB1

Number of Units in Package 2 12

Package 2 Weight 1.474 kg

Package 2 Height 8 cm

Package 2 width 9.8 cm

Package 2 Length 22.5 cm

2
Aug 13, 2022
Unit Type of Package 3 S03

Number of Units in Package 3 132

Package 3 Weight 16.492 kg

Package 3 Height 30 cm

Package 3 width 30 cm

Package 3 Length 40 cm

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

Halogen content performance Halogen free product

Aug 13, 2022 3

You might also like