5063-E-EPC-PTR-DE-D-V-001 - Data Sheet Cat A2
5063-E-EPC-PTR-DE-D-V-001 - Data Sheet Cat A2
5063-E-EPC-PTR-DE-D-V-001 - Data Sheet Cat A2
APPROVAL STATUS:
SS RP MMK
01 21.11.22 SS RP MMK Revised as per comments
SS RP MMK
00 04.11.22 SS RP MMK For Approval
Categories:
Reviewer
Cat-II Approved. Released for Manufacturing/fabrication/construction
subjected to incorporation of comments. Modification as
Noted. Resubmission is required.
Amit
Digitally
signed by Cat-III Not Approved
Amit
Asha Asharfilal
Date:
2022.11.28
Cat-IV For Information & Records
rfilal 17:54:49
Approver
+05'30' Note: “Approval of this document does not absolve the Contractor/ Supplier/
Fabricator from fulfilling Contractual obligations in any way”
SECTION-3: TECHNICAL DATA SHEETS & SCHEDULES
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 2 of 28
Cluster, Mundra
TABLE OF CONTENTS
SUBSECTION – 3.1 : TECHNICAL DATA SHEET FOR POWER TRANSFORMER AND REACTOR.....................
.............................................................................................................................................................
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 3 of 28
Cluster, Mundra
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 4 of 28
Cluster, Mundra
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 5 of 28
Cluster, Mundra
2.No external or internal Transformers/ Reactors are to be used to achieve the specified HV/IV, HV/LV and IV/LV
impedances.
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 6 of 28
Cluster, Mundra
GUARANTEED AND OTHER TECHNICAL PARTICULARS FOR POWER TRANSFORMERS (To be filled in for each type of
transformer by the manufacturer)
Sl.No. Description Unit Specified Offered by
by Buyer manufacturer
1. General Information i) Indo tech
Transformer
i) Supplier
ii) Indo tech
ii) Name of Manufacturer
Transformer
iii) Place of Manufacture (Country & City) iii) India &
iv) Type of transformer (Core/Shell) Kancheepuram
iv) Core Type
2. Applications
i) Indoor/Outdoor i) Outdoor
ii) 2wdg/3wdg/Auto ii) 2 Wdg
iii) GT/Step-down/ICT/Station Start-up/ Auxiliary/ Rail Trackside iii) Step – down
Supply
3. Corrosion Level at Site
i) Light ii) Medium iii) Heavy iv) Very Heavy Very Heavy Very Heavy
5. Seismic zone and ground acceleration at site (both in horizontal & As per Zone V
verticaldirection)
6. Maximum and minimum ambient temperature at site 47.8 Deg °C &
-1.1Deg °C
7. Applicable Standards Applicable
Standards
i) IEC: 60076
IEC: 60076 /
ii) IS : 2026
IS: 2026
iii) Any other, please specify
ii) Guaranteed I2R Loss at rated current & frequency (at 750C) kW 105kW max
at principal tap
Tolerance (to be considered for loss evaluation) % Nil
iii) Eddy current and stray loss at rated current & frequency (at kW ≤ 20.0 kW
750C) atprincipal tap
iv) Load Loss (I2R+Eddy and Stray) at rated current & frequency kW ≤ 125 kW Max
(at 750C)at principal tap
v) Guaranteed Auxiliary loss at rated voltage and frequency kW 3
Tolerance (to be considered for loss evaluation) % Nil
vi) Calculated Fan Loss kW 3
vii) Calculated Pump Loss kW NA
viii) Air core reactance of HV winding % >20%
ix) Guaranteed Impedance (at Highest MVA base) %
(a) HV-IV (at Principal tap) NA
(b) HV-LV (at Principal tap) 12.5%
(c) IV-LV (at Principal tap) NA
a) upf 1.03%
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 9 of 28
Cluster, Mundra
21. Guaranteed maximum Magnetizing Current at rated Voltage % <1% of full load
rated current
22. Efficiency: %
At 100% load upf
0.8 lead 99.70%
0.8 lag 99.63%
At 75% load upf
0.8 lead 99.75%
0.8 lag 99.68%
At 50% load upf
0.8 lead 99.78%
0.8 lag 99.72%
23. Load at Maximum efficiency % 44.72%
24. Any limitations in carrying out the required test? Short Circuit test
not considered.
If Yes, State limitations
25. Fault level of system (in kA) and its duration (in sec) kA (sec) 40kA (3 sec) for HV
& LV
26. Calculated short Circuit current (in kA) withstand capability for 2 kA HV Wdg – 3.5 kA
seconds (3 seconds for generator transformers) without exceeding
LV Wdg – 20.08 kA
temperature limit(i.e. Thermal ability to withstand SC current)
Approx
27. Test current (in kA) and duration (in ms) for short Circuit current kA As per IEC-60076-5
test (i.e.Dynamic ability to withstand SC)
(Dynamic short
circuit test is not
considered)
28. Over fluxing withstand time (due to combined voltage & msec
frequencyfluctuations):
110 %
110% continuously
125% 125 % for 1 minute
140% 140 % for 5
seconds
150%
150 % for 1
170%
seconds approx.
170 % for 0.25
seconds approx..
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 10 of 28
Cluster, Mundra
A. MAGNETIC SYSTEM
Sl. Description Unit Specifiedby Offered by
Buyer manufacturer
No.
1. Core Type:
i) 3 Phase 3 Limb (3 wound limbs)
ii) 3 Phase 5 Limb (3 wound limbs) 3 Phase 3 Limb (3
wound limbs)
iii) 1 Phase 2 Limb (2 wound limbs
iv) 1 Phase 3 Limb (1 wound limb)
v) 1 Phase 4 Limb (2 wound limbs)
vi) 1 Phase 5 Limb (3 wound Limbs)
2. Type of Core Joint:
i) Mitred Yes
ii) Step Lap Yes
3. CRGO: Posco/Nippon/JF
E/Equi. Country:
i) Make & Country of Origin
Korea/Japan/Equi
ii) Thickness, mm 0.23mm
iii) Max. Specific loss at 1.7 T, 50Hz, in Watts/kg 0.923
iv) Grade of core as per BIS MOH-0.23
v) Insulation between core laminations Carlite
vi) BIS certified (Yes/No) Yes
4. Minimum Gross & Net Area of: cm2
i) Core Core: 3177.76
Approx.
ii) Limb
Limb: 3177.76
iii) Yoke Approx.
iv) Unwound limb Yoke: 3177.76
(May be verified during manufacturing stage – at the discretion Approx.
of buyer) Unwound limb:
NA
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 11 of 28
Cluster, Mundra
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 12 of 28
Cluster, Mundra
B. CONDUCTING SYSTEM
Sl. Description Unit Offered
No. by manufacturer
HV IV LV Regulatin
g
1. Type of Winding Helical/Disc/Layer/inter wound Disc NA Helical Disc
2. Type of Conductor PICC/CTC/CTCE/CTCEN/BPICC BPICC NA CTC PICC
3. Minimum Yield Strength of Conductor for0.2% elongation N/mm2 80-140 NA 140 80 Approx.
Approx. Approx.
4. Maximum Current density at CMR and conductor area at any A/mm2 3.5 NA 3.5 3.5 A/Sqmm
tap: A/Sqmm A/Sqmm
&sq. 72.15 Sqmm
mm 72.15 717.2 min
i) HV Sqmm min Sqmm Min
ii) IV
iii) LV
5. Maximum current density under short circuit: A/mm2 28 NA 28 28
i) HV
ii) IV
iii) LV
6. Bare Weight of copper without paper insulation and lead Kg 6290 NA 4060 1530
(Minimum) R1
Approx. Approx. Approx.
7. Per Phase Maximum resistance of winding at rated tap at 75 ohm 0.2209 NA 0.00271 0.0603
OC
(Approx.) (Approx.) (Approx.)
8. Number of Turns/Phase 472 NA 56 111
9. Insulating material used for HV/IV/LV winding Kraft Paper NA Kraft Paper Kraft Paper
iv) Regulating winding and adjacent winding/core PCB Cylinder as Phase Barriers
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 13 of 28
Cluster, Mundra
14. Noise level when energized at normal voltage and frequency dB 70db
without load
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 14 of 28
Cluster, Mundra
C. COOLING SYSTEM
Sl.No. Description Unit Specified Offered by
by Buyer manufacturer
1. Type of Cooling
[ONAN (or) ONAN/ONAF (or) ONAN / ONAF / OFAF (or) ONAN / ONAN/ONAF
ONAF/ODAF (or) ONAN / ONAF1 / ONAF2 etc.]
2. Percentage Rating Corresponding to Cooling Stages (HV/IV/LV) 80/100%
3. No. of Cooler banks (2x50% / 2x100% / 1x100% etc.) 1 X 100%
4. Temperature gradient between windings and oil < 18 Deg C Approx
5. Time in minutes for which the transformer can run at full min 10minutes
load withoutexceeding maximum permissible temperature at without hotspot
reference ambient temperature when supply to fans and / or temperature
pumps is cut off exceeding
140degC
6. Guaranteed Maximum Temperature rise at 1000 mts. altitude 0C
and at actual altitude at site at ambient temperature at cooling
specified at sl. No.1:
45
i) Top Oil by thermometer
50
ii) Average Winding by resistance
61+ 32 Deg Avg.
iii) Winding hot spot Ambient Temp
7. Type of Cooler:
i) Radiator Bank Yes
ii) Oil to Air Heat Exchanger (Unit Cooler) NA
iii) Oil to Water Cooler (Single Tube) NA
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 15 of 28
Cluster, Mundra
9. Oil Pumps:
i) Type
ii) Size
iii) Rating (lpm and kW)
iv) Supply voltage NA
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 16 of 28
Cluster, Mundra
iv) Numbers 7
13. Cooler loss at rated output, normal ratio, rated voltage, rated kW 3kW for fans
frequency atambient temperature of 50oC
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 17 of 28
Cluster, Mundra
D. DIELECTRIC SYSTEM
Sl.No. Description Unit Offered by
manufacturer
2. Regulating Winding:
i) Body Tap NO
ii) Separate YES
3. HV Line Exit point in winding:
i) Top Yes
ii) Center No
4. Varistors used across WindingsIf yes, Details Yes/No No
5. Insulation Levels of windings HV IV LV HV-N LV-
N
i) Lightning Impulse withstand voltage (1.2/50µs) kVp 325 NA 75 NA 75
ii) Chopped wave Lightning Impulse withstand voltage kVp NA NA NA NA NA
iii) Switching Impulse withstand voltage (250/2500µs) kVp NA NA NA NA NA
iv) Power frequency withstand voltage (one minute / 5 minutes) kVrms 140 NA 28 NA 28
6. Tan delta of windings at ambient temperature % 0.5%
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 18 of 28
Cluster, Mundra
E. ACCESSORIES
Sl.No. Description Unit Specifiedby Offeredby
Buyer manufacturer
1. Tap Changers
i) Control
a-Manual b-Automatic Yes
c-Remote d-Local
ii) Voltage Class and Current Rating of Tap Changers 72.5kV 350A
iii) Make and Model Easun MR VIII model
iv) Make and Type of Automatic Voltage Regulator EMCO/Pradeep sales
(AVR) Microprocessor based
v) Tie-in resistor requirement (to limit the recovery Not applicable
voltage to a safevalue) and its value
vi) OLTC control and monitoring to be carried out Y/N Yes
through SubstationAutomation System
vii) Power Supply for control motor
(No. of Phases/Voltage/Frequency) 3 / 415V / 50hz
viii) Rated Voltage for control circuit V
(No. of Phases/Voltage/Frequency) 1 / 230V / 50hz
2. Tank
i) Tank Cover: Conventional/Bell/Bottom Plate Conventional
ii) Material of plate for tank Mild Steel
iii) Plate thickness: side, bottom, cover mm 12/20/16
iv) Rail Gauge mm 1676
v) Minimum Clearance height from rail for lifting Mm 8500
Active Part
vi) Wheels: Numbers/Plane/Flanged/Uni- 4/Flanged/Bi-
Directional/Bi- Directional
Directional/Locking Details
vii) Vacuum withstand Capability mm of Hg
(a) Tank 760mm
(b) Radiators/Conservator/Accessories As per CBIP
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 19 of 28
Cluster, Mundra
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 20 of 28
Cluster, Mundra
i) Voltage class kV
ii) No. of cores
iii) Ratio
iv) Accuracy class VA Refer Drawing 5964/C-
03 for complete details
v) Burden
vi) Accuracy limit factor ΩV
A
vii) Maximum resistance of secondary winding
viii) Knee point voltage
ix) Current rating of secondaries
16. Neutral CTs:
i) Voltage class kV
ii) No. of cores Refer Drawing 5964/C-
03 for complete details
iii) Ratio
iv) Accuracy class VA
v) Burden
vi) Accuracy limit factor Ω
VA
vii) Maximum resistance of secondary winding
viii) Knee point voltage
ix) Current rating of secondaries
17. Transformer Oil As per Annexure-L &
i) IS 335 / IEC60296 / as per specification IEC 60296
ii) Inhibited/ un-inhibited Uninhibited
iii) Mineral / Natural Ester / Synthetic Ester Mineral
vi) Quantity of oil (before filling and before R1 18145 Lit – Approx.
commissioning) IEC 60296
vii) Moisture content (mg/L or ppm)
IEC 60296
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 22 of 28
Cluster, Mundra
20. Provision for fire protection system (as per spec), if yes, Y/N Yes, NIFPS considered.
provide details CTR make
21. Insulation of core bolts, washers, end plates etc. NA
22. Weights and Dimensions: Approx. weights
i) Weights:
a. Core 43600
b. Windings (CCA Weight)
c. Tank 13000
d. Fittings 7000
R1 16150
e. Oil
79750
f. Total weights of complete transformers with oil
R1
and fittings
ii) Dimensions:
a. Overall height above track 6000
b. Overall length 8000
R1
c. Overall breadth 6100
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 23 of 28
Cluster, Mundra
iii) Minimum bay width required for installation of LxW 8500 x 6100
the transformer
R1
iv) Weight of the heaviest package of the transformer 69500
arranged fortransportation
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 24 of 28
Cluster, Mundra
HV HV NeutralSide LV LV NeutralSide
Side Side
Ratio
CORE 3 800V, PX / PS - - -
CORE 3 1.5Ohm - - -
Application
CORE 3 Differential - - -
CORE 1 100 mA - 25 mA 25 mA
CORE 2 - - 25 mA 25 mA
CORE 3 100 mA - - -
a. Notes:
i. Parameters of WTI CT for each winding shall be provided by the manufacturer / contractor.
ii. The CTs used for REF protection must have the identical parameters in order to limit the
circulating current under normal condition for stability ofprotection.
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 25 of 28
Cluster, Mundra
TECHNICAL SCHEDULES of HVIC/RTV Coating (Data to be furnished along with the Bid)
S.NO. Specification Requirement Supplier’s Compliance
in Y/N
1 Product Silicon based Yes
(Note- Other materials such as Fluorourethanes do not
have the long-term UV resistance or adhesion of properly
formulated Silicon, hence not accepted)
2 Product type RTV Type I or RTV II silicon. Yes RTV - I
(Note:-RTV Type I (also written as RTV-I or RTV-1) silicon
refers to a silicone that is 1-component and does not
require the addition of catalyst or other chemicals during
the application process in order to cure the product.
RTV II refers to multiple component materials and these
components are to be mixed by operators in the field
before application.)
3 Product must contain Alumina Tri-Hydrate (ATH), Yes ATH
in the formulation-
Size = _____
(Note:-larger grain
size ATH is preferred
and vendor should
indicate the grain size
of ATH).
4 Method Application Spray/Brush Spray/Brush
5 Product must not Peel, chalk, crack, craze, blister or bubble. Yes
6 Product must have porcelain, glass or nonceramic Yes
strong adhesion to
insulators
7 Product must NOT use of primers in order to Yes
require
achieve adhesion
8 Product must never Develop tracking marks longer than 100 millimeters. Yes
9 Product must never Erode in areas greater than 500 sq millimeters. Yes
10 Product must retain Equal to or better than Class Yes
hydrophobic
HC3 as per the STRI Guide
performance
92/1.
11 The coating should be Salt, fog, coastal and desert condition, water, UV, Yes
resistant to chemicals and other atmospheric conditions.
12 Product must eliminate appreciable leakage current over the long term resulting in the elimination of surface
discharge, visible discharge at nightfall and hotspots (as indicated through infrared thermal imaging).
13 Coating Material
properties in liquid
form
Basic Components RTV silicone coating containing optimally sized ATH Yes
(alumina tri hydrate) present in optimal concentration.
ATH (alumina tri Between 10 and 20 microns, 13 to 15 microns preferred Yes
hydrate) Grain Size
Percent of Solids by > or =70% Yes
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 26 of 28
Cluster, Mundra
Dissipation Factor 0.03 (max.) (at 50 Hz)/0.0292 (max) & 100 Hz 0.0864 Yes
(max.) (at 100 Hz)/ 0.0788 (max.)(at 100 kHz)
Dry Arc Resistance > 115 seconds (for Track) > 420 seconds (for burn Yes
Out)
Volume resistivity Yes
2.4 x 1015 ohm cm (minimum)
at 25°
Water repellency Yes
Angle > 110 °
15 Copy of following Type Test Certificates issued by any Government approved lab like CPRI, etc., to be
submitted along with quotation.
a Accelerated Yes
· Minimum 5,000 hours testing clause 5.3 Annex C of the
Weathering Test as
IEC 61109 test standard;
per IEC 61109.
· Maximum allowable leakage current pulses during 5,000
hours 1.10 mA
· Maximum allowable 100 data point moving average
during 5,000 hours 0.75mA
b Tests as per IEC – · Artificial Pollution test by Yes
60507 Salt-Fog method.
· Hydrophobic recovery by corona test
c Test as per IEC Yes
60587 Tracking & Erosion Resistance Test.
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 27 of 28
Cluster, Mundra
A guarantee starting
from the date of the
final taking over
certificate shall be
given by the Coating
Manufacturer and
contractor for the
silicon coating of the
insulator confirming
that no flash over &
no arcing will occur
on the coated
insulator within the
guarantee period.
Only oil communicating type porcelain bushing shall be provided with RTV coating.
For RIP bushing RTV coating is not applicable.
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 28 of 28
Cluster, Mundra
Note: The loss figures indicated shall be as a maximum and inclusive of IS/IEC tolerances.
SIGNATURE OF ___________________________
BIDDER
NAME ________________________________
DESIGNATION_____________________________
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY