Power Transformer Abb Energy Efficiency Ecodesign Regulation
This document provides specifications for various power transformers ranging in size from 12.5 to 100 MVA. It lists key details like frequency, phase number, rated power, voltages, impedances, losses, core and conductor materials and masses. The transformers can be customized based on specific project requirements.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
97 views1 page
Power Transformer Abb Energy Efficiency Ecodesign Regulation
This document provides specifications for various power transformers ranging in size from 12.5 to 100 MVA. It lists key details like frequency, phase number, rated power, voltages, impedances, losses, core and conductor materials and masses. The transformers can be customized based on specific project requirements.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Power transformers
Sr (MVA) Units 12,5 20 31,5 40 50 63 85 100 Notes
Frequency (Hz) 50 50 50 50 50 50 50 50 60 Hz frequency can also be provided on request Phase number 3 3 3 3 3 3 3 3 Single phase can also be provided on request Typical rating presented here, however any rating (MVA) 12,5 20 31,5 40 50 63 85 100 Rated power as per requirement can be provided Tertiary winding can be provided based on (MVA) - - - - - - 85 Rated power of tertiary requirement Power absorbed by that portion of the For ONAN rating power absorbed by cooling cooling system which is permanently on (kW) 0 0 0 0 0 0 0 0 system is 0. other cooling types can be provided (normally first stage) based on requirement. Typical voltages inlcuded here, however other (kV) 33 66 110 110 110 110 145 27 Rated voltage HV winding voltages based on requirement can be provided Typical impedances are inlcuded here, however (%) 8 10 12,5 14 14 14 8/17 9 other impedances based on requirement can be Short-circuit impedance on the rated tap provided PEI (%) 99,62 99,66 99,69 99,70 99,72 99,72 99,76 99,74 values to 2 decimal places Power at which PEI occurs (MVA) 5 7 12 14 17 23 85 100 kPEI x rated power Typical no load losses are presented here, (kW) 9 12 18 21 24 32 40 46 however any losses meeting the PEI requirements No-load loss at rated voltage can be provided Typical load losses are presented here, however Load Loss on the main tapping at rated (kW) 62 96 135 175 200 240 238 357 any losses meeting PEI requirements can be power provided Core Material Hi-B Hi-B Hi-B Hi-B Hi-B Hi-B Hi-B CGO Weights are based typical rating data and IEC (t) 6,5 9 12,5 17 19 23 42 32 Core mass requirements May also be provided with Al, while fullfilling the Cu Cu Cu Cu Cu Cu Cu Cu Conductor material PEI requirements Weights are based typical rating data and IEC (t) 3 4 7 8 9 9,5 19,5 12,5 requirements Conductor mass