Development of An Improved Earthing Method For Power and Distribution Transformers Substations
Development of An Improved Earthing Method For Power and Distribution Transformers Substations
2, DEPT. OF ELECTRICAL & ELECTRONIC ENGINEERING, UNIVERSITY OF LAGOS, AKOKA, LAGOS STATE, NIGERIA
ABSTRACT
Engineers and planners have realized that equipment grounding is a necessary part of installation process in
Electrical power substations. Over years, grounding or earthing has been carried out primarily through preparation of
Earth Mat which is interconnected with several Earth-rods buried around the equipment under consideration. This
approach takes several efforts to have an acceptable and reliable result. However, this paper presents a more flexible,
economical and results oriented approach. A flow chart which describes the procedures of carrying out the proposed
method of earthing is developed. This was applied to two case studies: a proposed Power transformer substation and
distribution Transformer substation located within the same geographical domain. On the two cases, the measured
earth resistances are presented and discussed. The results from the case study indicates that the earth resistance
values obtained from this new approach are reliable and in compliance with IEEE Standards 80,142, 81 and 1100.
Keywords: Equipment, Grounding, Earthing, Earth-rod, Flowchart, Earth Mat, Flow Process, Injection Substation,
Distribution Substation, Earth Resistance, IEEE Standard.
be less than 1.0 Ohm especially for Power • Prevent or at least minimize damage to equipment
Transformers of ratings 7.5 MVA, 33/11 KV and above. because of heavy fault current (short circuit
But for cases of Distribution Transformer either current) and Lightning and thus improve the
33/0.415kV or 11/0.415kV having capacity ranging reliability of Equipment.
from 100 KVA to 2 MVA [7], it is often difficult to • Provides stable platform for operation of sensitive
achieve this earth resistance values. electronic equipment i.e. maintaining the voltage at
It worth noting that the old conventional ways of doing any part of an electrical system at a known value to
Power Transformer substation earthing was to dig a prevent overcurrent or excessive voltage on the
large pit and bury all the earth rods and just brought appliance or equipment.
out about two leads which will be extended to all the
power transformers and substation equipment. 2.2 Overvoltage Protection
Factors influencing resistance of grounding (Earthing) Lightning, Line surges or Unintentional Contact with
electrode systems include, [7-9] higher voltage lines can cause dangerously high
• The resistance of the electrode is a function of the voltages to the electrical distribution system. Earthing
material of the rod and the surface area of the rod. provide an alternative path around the electrical
The surface area of the rod is a function of the rod system to minimize damages in the system.
diameter.
• Difference in ground rod sizes and materials make 2.3 Voltage Stabilization
little appreciable difference in the resistance of the In power system network, there are various sources of
electrode. system electricity supply. For example, every
The contact resistance between the rod and the Transformer in the system can be considered a
surrounding soil also varies depending on the separate source. If there were not a common reference
compatibility of the soil. For example, if the rod is point for all these voltage sources, it would be
driven into well compacted soil, then the resistance extremely difficult to establish relationships with each
between the rod and the surrounding soil is not a other.
significant factor.
Thus, in a properly installed grounding electrode 2.4 Protection of system
system, soil resistance is the key factor that determines The reliability of the power supply is generally
what the resistance of a grounding electrode will be improved.
and to what depth a rod must be driven to obtain low
ground resistance. This imply that the resistivity of 3. PARALLEL CONNECTION OF EARTH PIT
soils varies with the depth from the surface and the RESISTANCES IN SYSTEM GROUNDING.
electrolyte in the soil (the type of concentration of A Parallel circuit is one with several different paths for
soluble chemical in the soil, the moisture content and the electricity to travel [8, 9]. It is like a river that has
soil temperature). been divided up into smaller streams, however, all the
streams come back to the same point to form the river
2. IMPORTANCE OF EQUIPMENT GROUNDING IN once again.
POWER SYSTEM Resistors in parallel, on the other hand, result in an
Equipment grounding in power system is of significant equivalent resistance that is always lower than every
importance to the life of Equipment as well as human individual resistor [9, 13]. If voltage is applied across a
operating them. Some of them are discussed as follows resistor, certain amount of current flows. If another
[10-12]. resistor is added in parallel with the first one, one
would have essentially opened a new channel through
2.1. Safety of Human life / Building / Equipment which more current can flow. No matter how large the
• Save human life from danger of electrical shock or second resistor is, the total current flowing from the
death by blowing a fuse i.e. to provide an alternative power supply will be at least slightly higher than the
path for the fault current to flow so that it will not current through the single resistor. And if the total
endanger the user current is higher, the overall resistance must be lower.
• Protect buildings, machinery and appliances under Consider a 15 MVA 33/11 kV power Injection
fault conditions Substation where the resistance of six number earth pit
• Ensure that all exposed conductive parts do not are R1, R2, R3, R4, R5 and R6 and are connected in
reach a dangerous potential
parallel. The resultant resistance RT1 , is shown in 7. Use copper conductor to bond the two earth rods
equation (1) [2,14]; in each pit and connect the two ends to the grid via
soldering.
8. Measure the resistance (R) of each of these pits
Where, conductor to 15 m around the earth pit with
; another conductor dip on earth at least 0.6m deep.
; Each of these resistances should be maintained at a
; value less than one ohm.
In the same way, for a 500 KVA, 33/0.415 KV 9. Obtain the equivalent resistance (RT1) for R1, R2, R3,
Distribution Transformer Substation, the equivalent R4, R5 and R6. The RT1 value should be closer to zero
resistance (RT2) of 4 No Earth pit required is also ohm as much as possible for an injection substation
shown in equation (2) [2,14]; and less than 5 Ω for the Distribution transformer
substation.
10. Check voltage between earth pit conductor to
Where, neutral of mains supply 220 A.C, 50 Hz. The result
; ; ; should be less than 2.0 Volts.
4. PROPOSED WORK SPECIFICATION FOR STANDARD 4.2 Procedure of Standard Grounding in Distribution
GROUNDING OF POWER SYSTEM SUBSTATION AND Transformer Substations.
DEVELOPMENT OF FLOWCHARTS 1. Specify 0.1 x 1.8m Earth rod, 70mm2 x 1 copper
The general procedures of carrying out Grounding or earth conductor, 1.5 x 1.5 x 2 m Earth pit
Earthing in typical Injection and Distribution dimension and Earth Grid of l x b x 0.6m. Where, l
Transformer Substations are as shown below including and b are respectively length and breadth of the
the flowchart shown in figure 1. This flowchart space occupied by the equipment to be protected.
illustrates the flow process in obtaining a very good 2. Excavate Earth Grid and the desire number of
grounding results. Earth Pits. If unable to achieve wet soil after
excavation depth of 2m, increase excavation depth
4.1 Procedure of Standard Grounding in Power till the desired results is achieved.
Transformer Substations 3. The Earthing Material i.e wood coal, Animal dung,
1. Specify 1.5 x 1.5 x 2.0m earth pit, 150mm2 x 1 water & sand are poured into the earth pit in layers
copper earth conductor, 0.1 x 2.4m copper earth shown in figure 4. Wood coal used as good
rod and Earth Grid of l x b x 0.6m. Where, l and b conductor of electricity while Sand is used to form
are respectively length and breadth of the space porosity to cycle water and humidity around the
occupied by the equipment to be protected. mixture.
2. Excavate earth grid and the desire number of earth 4. Put Copper or Galvanize earth rod of size 0.1
pits. If unable to achieve wet soil after excavation x1.8m in the mid of mixture.
depth of 2m, increase excavation depth till the 5. Insert/bury 2 No Earth rod per pit (copper or
desired results is achieved. galvanized earth rod type) as shown in figure 5.
3. The Earthing Material i.e wood coal, Animal dung, 6. Lay Copper Conductor round the Earth grid and
water & sand are poured into the earth pit in layers terminate by soldering at the two ends.
shown in figure 2. Wood coal used as good 7. Use copper conductor to bond the two earth rods
conductor of electricity while Sand is used to form in each pit and connect the two ends to the grid via
porosity to cycle water and humidity around the soldering.
mixture. 8. Measure the resistance (R) of each of these pits
4. Put copper earth rod of size 0.1 x 2.4m in the mid conductor to 15 m around the earth pit with
of mixture. another conductor dip on earth at least 0.6m deep.
5. Insert/bury 4No. Copper earth rod per pit as Each of these resistances should be maintained at a
shown figure 3 value less than one Ohm.
6. Lay Copper Conductor round the Earth grid and 9. Obtain the equivalent resistance (RT2) for R1, R2, R3
terminate by soldering or mechanical joining at the and R4. The RT2 value should be less than 5 Ω for the
two ends. Distribution transformer substation.
5. DESCRIPTION OF CASE STUDY 1.5x1.5x2m well treated and two earth rods is buried
Oke Ira 2X15MVA, 33/11KV Injection Station that takes and well connected. The lead is then being brought out
source from Ajah Transmission in Eko Electricity by clamp and each earth pit is connected to already laid
Distribution Company, Lagos State, Nigeria is used as a grid wire in parallel. The resistance of the earth pit R1,
case study. At the completion of the project, the result R2, R3, R4, R5 and R6 were measured and recorded as
of the conventional formal earthing system of the shown in Table 1. Substituting the above resistance
injection substation was obtained to be 3.5 Ω due to the values in equation (1), the equivalent resistance is
swampy nature of the land. The procedural steps calculated as RT1 0.47 Ω. Consequently, the newly
described in subsection 4.1 and flow process of Figure developed earthing standard has really made it
1 were applied to the installation shown in Figure 6. possible to get values of our earthing within the
In Figure 6, the earth wire called grid wire is laid prescribed international value of < 1 Ohm.
without connected to any wire and soldered at the Further application of the procedures in subsection 4.2
meeting point. Then, the Six earth pit is being dug and the flow process in Figure 1 to 500 KVA 33/0.415
Earth Pit
Transformer
shortening the lives of the equipment, thereby putting Electrical Engineering Department, Faculty of
the utility customers in darkness and loss of revenue to Engineering, Jazan University, pp.1-64, 2014.
utility company. [2] Fink, G. D. and Beaty, W. H. Standard Handbook
The new approach to equipment grounding has for Electrical Engineers, McGraw-Hill, USA, 2000.
therefore eliminated the problems being faced in
[3] Beltz, R., Peacock, L. and William, V.P.E;
convectional approach. For example, “Application Considerations for high Resistance
The connection of each power equipment in the ground retrofits in pulp and paper Mills”;
substation to Earth pit is dual from the earth grid. http://www.eaton.us/ecm/groups/public/@pub
More than one Earth pits are used in each case /@electrical/documents/pu0 70 00 e.pdf” 2nd
study. February, 2018.
The problem of repeated process before getting [4] Shah, S. G. and Bhasme, N. R. “Design of Earthing
reliable result in the conventional method of system for HV/EHV AC Substation”, International
earthing is eliminated. This is because the result in Journal of Advance in Engineering & Technology,
Volume 6, Issue 6, pp.2597-2605, 2014.
this method is obtained at once.
Period required for the for the commissioning of the [5] Adelian, M. A. “Improvement of Substation
Transformer substation ( i.e connection to Grid) is Earthing”, International Journal of Engineering
.and Advanced Technology, Volume 3, Issue 4, pp
drastically reduced
100-104, April 2014.
Effects of copper conductor vandalism is minimized.
Loss of power utility equipment and revenue would [6] IEEE Standard 80 -: IEEE guide for safety in
Alternating current in substation grounding,
be drastically reduced.
2000.
Thus, the reliability of this newly improved power
equipment grounding method is high. [7] IEEE Standard 142-2007: Recommended Practice
for Grounding of Industrial and commercial
power systems. Chapter 4 page 164.
7. CONCLUSION
Grounding of power system equipment in substations [8] IEEE Standard 81: Guide for measuring Earth
Resistivity, Ground Impedance and Earth Surface
is a phenomenon that engineers must attach great
Potentials of a ground system.
concern with. This became necessary to save the lives
of the equipment as well as personnel handling the [9] IEEE 1100 –: Powering and Grounding Electronics
equipment. It enhances security of personnel and Equipment. 2005
minimizes installation maintenance cost. The paper has [10] Bakkabulindi, G. “Planning Models for Single Wire
presented the importance of Grounding of Power Earth Return Power Distribution Networks”,
System equipment in substations. A flexible approach Licentiate Thesis, Royal Institute of Technology,
Stockholm, Sweden, December, pp.9 – 71. 2012.
to this Earthing contrary to the old approach that
involves creating Earth Mat without even achieving [11] Obeta, C. N. and Nnadi, D. B. N. “Performance
results in time is introduced. A flow process to achieve Assessment of Substation Site Earthing using
this new approach was developed and presented. The Fluke 6 5 Ground Tester”, Nigerian Journal of
Technology, Vol. 32, No. 1, March, pp.49-53, 2013..
Developed flow process was applied to two case study;
a 15 MVA, 33/11 kV PT substation and a 500 kV, [12] Oluseyi, P. O., Akinbulire, T. O. and Amahian, O.
33/0.415 kV DT substation. The results obtained in the “Investigation of the Lightning Arrester Operation
in Electric Power Distribution Network”, Nigerian
two - case studied are presented and discussed. These
Journal of Technology, Vol. 37, No. 2, April 2018,
results are satisfactory, reliable and obviously in pp.490 – 497.
compliance with IEEE Standards. Thus, the new
[13] Engineer Educators (2007 – 008 ; “Grounding
approach is highly recommended to power utility
and Bonding Electrical Systems”,
companies. http://www.engineereducators.com/docs/groun
dingandbonding2-2.pdf, pp.1-34, 2007 – 2008.
8. REFERENCES
[14] Theraja, B. L. and Theraja, A. K. A Textbook of
[1] Al. Nami A., Al. Qarni K., Al. Shahrani S. and Al. Electrical Technology, S. Chand Company Ltd,
Juhani M.; “Design of Substation grounding grids”, Hardback, India, 2005