Daikin-Applied-Agz-E Da 05062015 LR
Daikin-Applied-Agz-E Da 05062015 LR
Daikin-Applied-Agz-E Da 05062015 LR
Trailblazer™
Air-Cooled Scroll Chillers
Model AGZ, E Vintage
30 to 180 Tons (100 to 630 kW)
HFC-410a Refrigerant
50/60 Hz
Table of Contents
Table of Contents
Table of Contents
©2015 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.
Daikin Trailblazer™ air-cooled water chillers are complete, The electrical control center includes all equipment protection
self-contained, automatic chiller units designed for outdoor and operating controls necessary for dependable automatic
installation. Packaged units are completely assembled, factory operation.
wired, charged, and tested.
NOMENCLATURE
A G Z XXX E H
Air-Cooled Application
H = Standard Packaged
Global Design
Scroll Compressor Design Vintage
Nominal Tons
CAUTION
Sharp edges on unit and coil surfaces are a potential hazard
to personal safety. Avoid contact with them.
Additional Manual
This manual covers the installation, of dual circuit, AGZ-EH
packaged, scroll compressor chillers using R-410A.
Information for units with either the pump package or remote
evaporator options can be found at www.DaikinApplied.com. Figure 2: Required Lifting Arrangement
Handling
Be careful to avoid rough handling of the unit. Do not push
or pull the unit from anything other than the base. Block the
pushing vehicle away from the unit to prevent damage to the
sheet metal cabinet and end frame (see Figure 1).
To lift the unit, 2-1/2” (64mm) diameter lifting eyes are provided
MUST USE THESE
on the base of the unit. Arrange spreader bars and cables to RIGGING HOLES
(BE AWARE OF
prevent damage to the condenser coils or cabinet (see Figure CONTROL BOX
2). LOCATION)
CAUTION DANGER
All lifting locations must be used to prevent damage to unit. Do not stand beneath the unit while it is being lifted or
installed.
frame to support the unit above the roof. For ground level
applications, install the unit on a substantial base that will not Minimum = 7.5 ft (2.3 m)
settle. Use a one-piece concrete slab with footings extended for models 030-070 Minimum = 4 ft
with Microchannel Coils
Control Panel
below the frost line. Be sure the foundation is level within 0.5” (1.2 m)
(13 mm) over its length and width. The foundation must be
Minimum = 4 ft (1.2 m)
strong enough to support the unit weight - see “Dimensions for all other models
and Weights - Packaged Units” on page 14.
Sides
• 30-70 Ton Models: Minimum of 4 feet (1.2 meters)
• 75-180 Ton Models: It is highly recommended to Spacing Requirements
provide a minimum of 8 feet (2.4 meters) on one side to Sufficient clearance must be maintained between the unit
allow for coil replacement. Coils can be removed from and adjacent walls or other units to allow the required unit
the top, allowing a minimum of 4 feet (1.2 meters) of air flow to reach the coils. Failure to do so will result in a
side clearance; however, the unit performance may be capacity reduction and an increase in power consumption. No
derated. obstructions are allowed above the unit at any height.
Control Panel End Graphs on the following pages give the minimum clearance for
• All Models: Minimum of 4 feet (1.2 meters) different types of installations and also capacity reduction and
Opposite Control Panel End power increase if closer spacing is used.
Case 1: Building or Wall on One Side of Unit Case 2: Two Units, Side-by-Side
For models AGZ030-100E, maintain a 4 feet minimum from a For all models, there must be a minimum of 4 feet between
wall of any height. two units placed side-by-side; however, performance may be
affected at this distance. The Case 2 figures show performance
For models AGZ110-180E, maintain a 6 feet minimum from a
adjustments as the distance between two units increases.
wall of any height.
Height Distance
of Between
Wall Wall
and
Unit
Figure 6: Case 2 - Full Load Capacity Reduction
Full Load Capacity Reduction
3.0
2.5
% Capacity Reduction
2.0
1.5
1.0
0.5
0.0
4 5 6 8
Distance Between Units (ft)
3.5
3.0
% Power Increase
2.5
2.0
1.5
1.0
0.5
0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-070E AGZ075-100E AGZ110-130E AGZ140-180E
6.0
5.0
4.0
3.0
2.0
Case 5: Pit Installation
Pit installations can cause operating problems resulting from
1.0 air recirculation and restriction and require care that sufficient
air clearance is provided, safety requirements are met and
0.0
4 5 6 8 service access is provided. Pit covers must have abundant
Distance Between Units open area at least equal to the chiller footprint. A solid wall
AGZ030-035E AGZ040-070E AGZ075-100E surrounding a unit is substantially a pit and this data should be
AGZ0110-130E AGZ140-180E
used.
Steel grating is sometimes used to cover a pit to prevent
Figure 10: Case 3 - Power Increase accidental falls or trips into the pit. The grating material
and installation design must be strong enough to prevent
Power Increase such accidents, yet provide abundant open area to avoid
8.0
recirculation problems. Have any pit installation reviewed by
7.0 the Daikin Applied sales representative prior to installation to
% Power Increase
3.0
2.0
1.0
0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-035E AGZ040-070E AGZ075-100E
AGZ0110-130E AGZ140-180E
5.0
% Capacity Reduction
4.0
3.0
2.0
1.0
Models AGZ030-070E:
0.0
The Case 5 figures for models AGZ030-070E show adjustment 0 8 10 12 13 14
factors for pit/wall heights of 4 feet, 5 feet, and 6 feet. Depth of Pit / Wall Height ft)
Distance = 5 f t Distance = 6 f t Distance = 8 f t
8.0
5.0
7.0
% Capacity Reduction
% Power Increase
4.0
6.0
3.0 5.0
4.0
2.0
3.0
1.0
2.0
0.0 1.0
0 8 10 12 13 14
0.0
Depth of Pit / Wall Height (ft) 0 8 10 12 13 14
Distance = 4 f t Distance = 5 f t Distance = 6 f t Depth of Pit / Wall Height (ft)
Distance = 5 f t Distance = 6 f t Distance = 8 f t
8.0
7.0
6.0
% Power Increase
5.0
4.0
3.0
2.0
1.0
0.0
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Distance = 4 f t Distance = 5 f t Distance = 6 f t
5.0
• A cleanable strainer installed at the water inlet to the
evaporator to remove debris and impurities before they
% Capacity Reduction
8.0
• Piping for units with brazed-plate evaporators must have
a drain and vent connection provided in the bottom of
7.0
the lower connection pipe and to the top of the upper
% Power Increase
equipment start-up.
Inlet
Isolation
P Vibration
Valves
Eliminators
Outlet
Flow
Switch
Drain
10.0
1.0
0.1
10.0 100.0 1000.0
Water Flow Limitations helps protect the evaporator down to -20°F (-29°C) ambient
air temperature. The evaporator heater cable is factory wired
Constant Evaporator Flow to the 115 volt control circuit transformer in the control box.
A 115V power source for the heater and controls may also
The evaporator flow rates and pressure drops shown on page be supplied from a separate power feed to maximize unit
24 are for full load design purposes. The maximum flow protection if desired. Refer to the field wiring diagram on page
rate and pressure drop are based on a 6°F temperature drop. 26 for additional information on supplying a separate 115V
Avoid higher flow rates with lower temperature drops to prevent power feed.
potential control problems resulting from a very small control
band and limited start up/shut off temperature changes. Flow Operation of the heaters is automatic through the ambient
rates above the maximum values will result in unacceptable sensing thermostat that energizes the evaporator heaters for
pressure drops and can cause excessive erosion, potentially protection against freeze-up. Unless the evaporator is drained
leading to failure. in the winter or contains an adequate concentration of anti-
freeze, the disconnect switch to the evaporator heater must not
The minimum flow and pressure drop is based on a full load be open.
evaporator temperature drop of 16°F. Evaporator flow rates
below the minimum values can result in laminar flow causing Although the evaporator is equipped with freeze protection,
freeze-up problems, scaling and poor control. it does not protect water piping external to the unit or the
evaporator itself if there is a power failure or heater burnout, or
Variable Evaporator Flow if the chiller is unable to control the chilled water pumps. Use
one of the following recommendations for additional freeze
Reducing evaporator flow in proportion to load can reduce protection:
system power consumption. The rate of flow change should be
a maximum of 10 percent of the flow per minute. For example, 1. If the unit will not be operated during the winter, drain the
if the maximum design flow is 200 gpm and it will be reduced to evaporator and chilled water piping and flush with glycol.
a flow of 140 gpm, the change in flow is 60 gpm. Ten percent of 2. Add a glycol solution to the chilled water system. Burst
200 gpm equals 20 gpm change per minute, or a minimum of protection should be approximately 10°F below minimum
three minutes to go from maximum to desired flow. The water design ambient temperature.
flow through the evaporator must remain between the minimum
3. Insulate the exposed piping.
and maximum values listed in Table 11 on page 24. If flow
drops below the minimum allowable, large reductions in heat 4. Add thermostatically controlled heat by wrapping the
transfer can occur. If the flow exceeds the maximum rate, lines with heat tape.
excessive pressure drop and tube erosion can occur. 5. When glycol is added to the water system for freeze
protection, the refrigerant suction pressure will be lower,
System Water Volume Considerations cooling performance less, and water side pressure drop
All chilled water systems need adequate time to recognize greater. If the percentage of glycol is high, or if propylene
a load change, respond to the change and stabilize to avoid is used instead of ethylene glycol, the added pressure
undesirable short cycling of the compressors or loss of drop and loss of performance could be substantial. When
temperature control. In air conditioning systems, the potential Glycol or Ice are selected as Unit Mode, the MicroTech III
for short cycling usually exists when the building load falls control will automatically reset the available range for the
below the minimum chiller plant capacity or on close-coupled Leaving Water Temperature, Freezestat and Evaporator
systems with very small water volumes. Some of the things Pressure settings.
the designer should consider when looking at water volume
are the minimum cooling load, the minimum chiller plant Chilled Water Pump
capacity during the low load period and the desired cycle time It is important that the chilled water pumps be wired to, and
for the compressors. Assuming that there are no sudden load controlled by, the chiller’s microprocessor. When equipped
changes and that the chiller plant has reasonable turndown, with optional dual pump output, the chiller controller has the
a rule of thumb of “gallons of water volume equal to two to capability to selectively send the signal to a pump relay (by
three times the chilled water gpm flow rate” is often used. A others) to start pump A or B or automatically alternate pump
storage tank may have to be added to the system to reach the selection and also has standby operation capability. The
recommended system volume. controller will energize the pump whenever at least one circuit
BAS should enable chiller only when there is a cooling on the chiller is enabled to run, whether there is a call for
demand. cooling or not. This helps ensure proper unit start-up sequence.
he pump will also be turned on when the water temperature
Evaporator Freeze Protection goes below the Freeze Setpoint for longer than a specified time
to help prevent evaporator freeze-up. Connection points are
Evaporator freeze-up can be a concern in the application of shown in the Field Wiring Diagram beginning on page 26.
air-cooled water chillers in areas experiencing below freezing
temperatures. To protect against freeze-up, insulation and an
electric heater are furnished with the evaporator. Models 030
through 180 have an external plate heater and thermostat. This
BlackFin™ coils include aluminum fins pre-coated with a option is not well suited for industrial or chemical atmospheric
durable phenolic epoxy coating. In addition to providing a contamination. This option is only available for models
durable coating on the fin material, the BlackFin™ coils provide AGZ030-070E.
and epoxy barrier between the aluminum fin stock and the ElectroFin® coil coating is a water-based extremely flexible
copper tube, to prevent the galvanic corrosion that can occur and durable epoxy polymer coating uniformly applied to all
between the dissimilar metals. This option will provide a 1000+ coil surfaces through a multi-step, submerged electrostatic
hour salt spray rating per ASTM B117-90. The BlackFin™ coating process. ElectroFin® condenser coils provide a 5000+
option provides enhanced protection in mildly corrosive hour salt spray resistance per ASTM B117-90, applied to both
environments. This option is only available for models AGZ030- the coil and the coil frames. The ElectroFin® coated coils also
070E. receive a UV-resistant urethane top-coat to provide superior
Copper-fin coils consist of 3/8 inch (10 mm) seamless copper resistance to degradation from direct sunlight. This coil coating
tubes mechanically bonded into plate-type copper fins. The fins option provides the best overall protection against corrosive
have full drawn collars to completely cover the tubes. Since marine, industrial or combined atmospheric contamination.
the fin and the tube materials are similar, the opportunity for This coating option may be applied to any of the untreated coil
galvanic corrosion is eliminated. The copper fin/copper tube options offered, to provide excellent longevity and resistance to
option may be used in marine environments; however this corrosion.
NOTE:
1. Non-corrosive environments may be estimated by the appearance of existing equipment in the immediate area where the
chiller is to be placed.
2. Marine environments should take into consideration proximity to the shore as well as prevailing wind direction.
3. Industrial contaminants may be general or localized, based on the immediate source of contamination (i.e. diesel fumes due
to proximity to a loading dock).
4. Combined marine-industrial are influenced by proximity to shore, prevailing winds, general and local sources of
contamination.
5. Available for models AGZ030-070E only.
209
L4 L2 1822
8.2
M4 M2 71.8
REF.
BLANK PANELS ARE
USED ON UNIT SIDES. CONTROL
51 497
2.0 19.6 64
[22] 22 2X 2.5
Ø.875 KNOCKOUTS 80 127 .875 KNOCKOUTS
POWER ENTRY KNOCKOUTS 165 370
3.2 5.0 FIELD CONTROL
ARE ON THE OPPOSITE 6.5 14.6 2546
CONNECTIONS
SIDE OF CONTROL BOX QTY. 3 100.2
[22] 2389
152 A Ø.875
EVAP. 94.1
WATER 6.0 B POWER ENTRY
INLET KNOCKOUTS
FRONT OR
1094 RIGHT SIDE Y
43.1 153
635 6.0 EVAP.
L1 - L4, 25.0
LIFTING 266
LOCATIONS 10.5
L3 L1
506 L4 EVAP. L2 506 WYE-STRAINER
19.9 WATER 19.9 FRONT LEFT REQUIRED X
OUTLET 797 CORNER POST (FACTORY OR FIELD
PURPOSELY INSTALLED OPTION) 2235
31.4 HIDDEN
Z 88.0
2396 DIMENSION DOES NOT INCLUDE
94.3 LIFTING BRACKETS
14 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Dimensions and Weights - Packaged Units
AGZ035E 2873 (1303) 2887 (1310) 1051 (477) 861 (391) 528 (240) 433 (196) 1005 (456) 824 (374) 581 (264) 476 (216)
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE PACKAGE UNITS WITH MICROCHANNEL COILS
M3 M1 CG LOCATION, IN (MM)
337 1721 337 UNIT MODEL
13.3 67.8 13.3 X Y Z
L3 L1
AGZ040E 39.8 (1011) 45.9 (1166) 38.4 (975)
52 AGZ045E 38.9 (988) 44.5 (1130) 41.2 (1047)
2.0 AGZ050E 39.1 (993) 44.9 (1141) 41.2 (1047)
COMPRESSORS
CIRCUIT #2 AGZ055E 39.1 (993) 44.8 (1138) 41.2 (1047)
COMPRESSORS
CIRCUIT #1 AGZ060E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ065E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ070E 36.8 (935) 41.8 (1062) 42.6 (1082)
TOP VIEW WITH
COILS AND
FANS REMOVED EVAP. DIMENSIONS IN (MM) CONNECTION SIZE
UNIT MODEL
A B (VICTAULIC)
AGZ040E 22.8 (579) 1.5 (38) 2.5 (64)
AGZ045E 21.4 (544) 0.11 (3) 2.5 (64)
AGZ050E 20 (508) 2.7 (69) 2.5 (64)
Figure 24: AGZ040E - AGZ070E
L4 L2 208
1822
8.2
M4 M2 71.8
REF.
CONTROL
BOX
497
19.6
51
2.0 64
22 2X 2.5
[22]
.875 KNOCKOUTS
www.DaikinApplied.com 15
Ø.875 KNOCKOUTS 80 127
POWER ENTRY KNOCKOUTS FIELD CONTROL 165 370
3.2 5.0 CONNECTIONS 6.5 14.6
ARE ON THE OPPOSITE 2546
SIDE OF CONTROL BOX QTY. 3 100.2
M1
M3
984 2433 315
38.7 95.8 12.4
L3 L1
UNIT CG LOCATION, IN (MM)
52 MODEL X Y Z
2.0 AGZ075E 45.3 (1151) 38.6 (980) 56.2 (1427)
AGZ080E 44.2 (1122) 39.2 (995) 56.5 (1435)
TOP VIEW WITH AGZ090E 44.2 (1122) 39.2 (995) 55.0 (1397)
COILS AND FANS COMPR.
REMOVED CIRCUIT 2 AGZ100E 43.6 (1108) 38.9 (988) 55.7 (1415)
EVAP. DIMENSIONS
UNIT CONNECTION
IN (MM)
MODEL SIZE, IN.
A B
Figure 25: AGZ075E - AGZ100E
L4 L2 M2
M4 19
B .750
QTY. 4
A
SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
UNIT MODEL
LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4
AGZ075E 4388 (1990) 4451 (2019) 1341 (608) 1420 (644) 790 (358) 837 (380) 1173 (532) 1242 (563) 989 (449) 1047 (475)
AGZ080E 4510 (2046) 4579 (2077) 1407 (638) 1418 (643) 840 (381) 846 (384) 1232 (559) 1241 (563) 1049 (476) 1057 (479)
AGZ090E 4540 (2059) 4609 (2091) 1456 (660) 1466 (665) 806 (366) 812 (368) 1276 (579) 1285 (583) 1020 (463) 1028 (466)
AGZ100E 4696 (2130) 4780 (2168) 1505 (683) 1480 (671) 863 (391) 848 (385) 1322 (600) 1299 (589) 1089 (494) 1070 (485)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
16 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
M1 - M6, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M5 M3 M1
630 1499 2433 315
24.8 L3 59.0 95.8 L1 12.4
52
2.0
www.DaikinApplied.com 17
CONTROL
BOX 2506
98.6
WYE-STRAINER
REQUIRED 22 X
(FACTORY OR .875 KNOCKOUTS 2355
FIELD INSTALLED FIELD CONTROL 92.7
OPTION) CONNECTIONS
51 QTY. 3
2.0 64
80 2.5
153 127 213
3.1 5.0 64 Y
858 6.0 8.4
33.8 2.5
290 305
11.4 12.0
L3 L1
996 L4 EVAP. EVAP. L2 609 292 165 [22]
L1 - L4, 39.2 WATER WATER 24.0 11.5 6.5 .875 POWER ENTRY
LIFTING OUTLET INLET KNOCKOUTS
Z 37 175
LOCATIONS FRONT OR RIGHT SIDE
4879 1.5 2235 6.9
192.1 88.0
22
DIMENSION DOES NOT INCLUDE
.875 KNOCKOUTS LIFTING BRACKETS
POWER ENTRY KNOCKOUTS
ARE ONTHE OPPOSITE SIDE 334547121
OF THE CONTROL BOX AGZ-E 8 FANS
UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ110E 5437 (2466) 5528 (2508) 1762 (799) 1769 (802) 951 (431) 955 (433) 1424 (646) 1430 (649) 845 (383) 849 (385) 489 (222) 491 (223)
AGZ120E 5696 (2584) 5796 (2629) 1907 (865) 1915 (869) 935 (424) 939 (426) 1548 (702) 1555 (705) 878 (398) 882 (400) 465 (211) 467 (212)
AGZ130E 5792 (2627) 5903 (2678) 1941 (880) 1863 (845) 1015 (460) 974 (442) 1575 (714) 1511 (685) 920 (417) 883 (401) 517 (235) 496 (225)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
M1
M5 M3
1711 1564 2433 315
67.4 61.6 95.8 12.4
L3 L1 334547131
AGZ-E 10FANS
52
2.0
TOP VIEW WITH UNIT CG LOCATION, IN (MM) EVAP. DIMENSIONS, IN (MM) CONNECTION
COILS AND FANS COMPR. MODEL X Y Z A B SIZE, IN.
REMOVED CIR. 2 AGZ140E 44.1 (1120) 42.6 (1083) 83.3 (2117) 122.1 (3102) 67.51 (1715)
4.0 (102)
AGZ150E 43.9 (1116) 42.4 (1077) 83.3 (2115) 120.5 (3062) 65.9 (1674)
Figure 27: AGZ140E - AGZ150E
COMPR.
1118 CIR. 1
44.0
52
2.0
M6 L4 M4 L2 M2
19
B
.750
QTY. 6
2506
98.6
CONTROL
BOX X 2355
92.7
51
2.0 64
2.5 Y
80 127
210 3.1 64 213
858 5.0
8.3 2.5 8.4
33.8
290 305 22
11.4 12.0 .875 KNOCKOUTS
FIELD CONTROL
L3 L1
1919 L2 CONNECTIONS [22]
L4 EVAP. EVAP. 609 22 292 165
75.5 QTY. 3 .875
WATER WATER 24.0 .875 KNOCKOUTS 11.5 6.5 175
L1 - L4 INLET 2235 POWER ENTRY
LIFTING WYE-STRAINER OUTLET POWER ENTRY KNOCKOUTS 6.9 KNOCKOUTS FRONT
37 88.0
LOCATIONS REQUIRED ARE ON THE OPPOSITE SIDE OR RIGHT SIDE
(FACTORY OR FIELD 1.5 OF THE CONTROL BOX DIMENSION DOES NOT INCLUDE
Z LIFTING BRACKETS
INSTALLED OPTION)
6025
237.2
UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ140E 6555 (2973) 6674 (3027) 1862 (845) 1868 (847) 1410 (640) 1415 (642) 1411 (640) 1416 (642) 1070 (485) 1074 (487) 850 (386) 853 (387)
AGZ150E 6617 (3001) 6745 (3059) 1888 (856) 1881 (853) 1426 (647) 1421 (645) 1433 (650) 1428 (648) 1085 (492) 1081 (490) 861 (391) 858 (389)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
18 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
M5 M3
1711 1564 2433 315
67.4 61.6 95.8 12.4
L3 L1
52
2.0
334547131
TOP VIEW WITH COMPR. AGZ-E 10FANS
COILS AND FANS CIR. 2
REMOVED
Figure 28: AGZ160E - AGZ180E
M6 L4 M4 L2 M2
19
B .750
QTY. 6
A
www.DaikinApplied.com 19
2506
98.6
CONTROL 2355
BOX X 92.7
51
2.0 64
2.5 Y
80 127
210 3.1 5.0 64 213
858
8.3 2.5 8.4
33.8
290 305 22
11.4 12.0 .875 KNOCKOUTS
FIELD CONTROL
L3 L1
1919 L4 L2 CONNECTIONS 165 [22]
EVAP. EVAP. 609 22 QTY. 3 292
75.5 6.5 175 .875
L1 - L4 WATER WATER 24.0 .875 KNOCKOUTS 11.5 POWER ENTRY
WYE-STRAINER OUTLET INLET 37 POWER ENTRY KNOCKOUTS 6.9
LIFTING REQUIRED 2235 KNOCKOUTS FRONT
LOCATIONS 1.5 ARE ON THE OPPOSITE SIDE OR RIGHT SIDE
(FACTORY OR FIELD 88.0
INSTALLED OPTION) Z OF THE CONTROL BOX
DIMENSION DOES NOT INCLUDE
6025 LIFTING BRACKETS
237.2
UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ160E 6937 (3147) 7065 (3205) 1941 (880) 1947 (883) 1522 (690) 1527 (693) 1466 (665) 1471 (667) 1136 (515) 1140 (517) 924 (419) 927 (420)
AGZ170E 7170 (3252) 7307 (3314) 2072 (940) 1995 (905) 1581 (717) 1522 (690) 1571 (713) 1512 (686) 1197 (543) 1152 (523) 956 (434) 920 (417)
AGZ180E 7412 (3362) 7560 (3429) 2121 (962) 2127 (965) 1580 (717) 1584 (718) 1613 (732) 1617 (733) 1210 (549) 1214 (551) 951 (431) 954 (433)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
Refrigerant Charge
Isolator Information
Figure 29: Spring Isolator In all cases, set the unit in place and level. When spring
ELASTOMERIC isolators are required, install springs running under the main
SNUBBER
unit supports.
Installation of spring isolators requires flexible piping
3
[76.2]
.62 [15.8] connections and at least three feet of flexible electrical conduit
to avoid straining the piping and transmitting vibration and
noise.
9.25 [235.0]
Mounting locations for each model can be found in the
10.5 [266.7]
“Dimensions and Weights - Packaged Units” section of this
7.75 [196.9] document, starting on page 14.
.625 .5 [12.7] DIA.
[15.9] POSITIONING
.25 TO .5 GAP Optional seismic isolator information begins on page 23
PIN
[6.4 to 12.7]
Contact a Daikin Applied sales representative for isolator
ADJ. BOLT information related to units with other fin materials.
6.25
[127.0]
FREE HT. Table 7: Isolator Kits
5\X [127.0]
OPER. HT.
AGZ-E Microchannel - Packaged Units
Model Spring Isolators RIS Isolators
.56 [14.3]
030 332320102 332325101
.25 [6.4]
ELASTOMERIC PAD 035 332320102 332325101
040 332320102 332325101
045 332320132 332325101
Figure 30: Rubber-in-Shear (RIS) Isolator
050 332320132 332325101
055 332320132 332325101
060 332320132 332325101
065 332320132 332325101
070 332320132 332325101
075 332320117 332325101
080 332320117 332325101
090 332320117 332325101
100 332320117 332325101
110 332320123 332325113
120 332320124 332325113
130 332320124 332325113
140 332320106 332325113
150 332320106 332325113
160 332320111 332325113
170 332320111 332325113
180 332320111 332325113
(BASE PLATE)
3/4 [19] DIA HOLE FOR
ATTACHMENT TO
2 1/4 [57]
STEEL (4 TYP)
6 1/4 [159] (VIEW CUT AWAY FOR CLARITY)
2 7/8 [73]
2 7/8 [73]
7/8 [22]
5 1/8
[130]
1 1/2 7 1/4
[38] [184]
5 3/4
3/4 [19] REMOVABLE [146]
ADJUSTING BOLT
STEEL SHIM
(REMOVE AFTER
SPRING ADJUSTMENT)
3/4 [19] STD.WASHER
(BY OTHERS)
3/8 [10] GAP
1/2 [13]
6 1/8 [156]
ELASTOMERIC
FREE &
SNUBBER LIMIT STOPS
OPERATING
HEIGHT SHIPPING SPACER (NOT SHOWN
ASSY STRAP IN TOP VIEW
(NOT SHOWN FOR CLARITY)
IN OTHER VIEWS
FOR CLARITY) 3/8 [10]
10 1/4 8
[260] [203]
Figure 32: Seismic Neoprene Isolation Pads Table 9: Seismic Isolator Kit Numbers
8.00 AGZ-E Packaged Unit - Aluminum Fins
203.2 Model Neoprene Pads Spring Isolators
030 334549001 334548801
035 334549001 334548801
I
E
BC H
D FG U
ST
A Q
L NOP
M
JK
1
10 100 1000
Flow Rate (gpm)
Curve IP SI IP SI IP SI IP SI
Model
Ref.
GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa
A 030E 27.0 1.7 1.7 5.1 42.2 4.0 2.7 12.0 67.4 9.8 4.3 29.4 112.4 26.0 7.1 77.7
B 035E 33.5 2.4 2.1 7.1 52.4 5.6 3.3 16.7 83.8 13.7 5.3 40.9 139.6 36.4 8.8 108.7
C 040E 37.1 2.5 2.3 7.4 57.9 5.8 3.7 17.3 92.6 14.2 5.8 42.5 154.4 37.7 9.7 112.6
D 045E 40.9 2.3 2.6 6.8 63.9 5.3 4.0 15.8 102.2 13.2 6.5 39.4 170.4 34.4 10.8 102.7
E 050E 46.4 2.7 2.9 7.9 72.5 6.2 4.6 18.5 115.9 15.2 7.3 45.3 193.2 40.0 12.2 119.6
F 055E 49.7 2.3 3.1 7.0 77.7 5.5 4.9 16.3 124.3 13.4 7.8 40.0 207.2 35.6 13.1 106.2
G 060E 54.0 2.3 3.4 6.9 84.3 5.4 5.3 16.1 134.9 13.1 8.5 39.3 224.8 34.7 14.2 103.6
H 065E 55.5 2.4 3.5 7.3 86.7 5.7 5.5 17.0 138.7 13.9 8.8 41.4 231.2 36.6 14.6 109.3
I 070E 61.5 3.0 3.9 8.8 96.1 6.9 6.1 20.6 153.8 16.9 9.7 50.4 256.4 44.5 16.2 133.0
J 075E 69.8 1.2 4.4 3.6 109.1 2.8 6.9 8.4 174.5 6.9 11.0 20.5 290.8 18.2 18.3 54.3
K 080E 73.8 1.2 4.7 3.7 115.4 2.9 7.3 8.6 184.6 7.1 11.6 21.3 307.6 18.9 19.4 56.6
L 090E 80.1 1.4 5.1 4.3 125.1 3.4 7.9 10.1 200.2 8.3 12.6 24.8 333.6 22.1 21.0 66.1
M 100E 92.4 1.3 5.8 4.0 144.3 3.2 9.1 9.5 230.9 7.8 14.6 23.3 384.8 20.8 24.3 62.2
N 110E 102.0 1.4 6.4 4.2 159.5 3.3 10.1 9.9 255.1 8.2 16.1 24.4 425.2 21.6 26.8 64.6
O 120E 113.1 1.5 7.1 4.5 176.7 3.6 11.1 10.7 282.7 8.8 17.8 26.4 471.2 23.5 29.7 70.3
P 130E 119.5 1.5 7.5 4.4 186.8 3.5 11.8 10.4 298.8 8.6 18.9 25.7 498.0 22.9 31.4 68.3
Q 140E 128.9 1.7 8.1 5.1 201.5 4.0 12.7 12.1 322.3 9.9 20.3 29.7 537.2 26.4 33.9 79.0
R 150E 143.6 1.8 9.1 5.5 224.4 4.4 14.2 13.0 359.0 10.8 22.7 32.4 598.4 29.1 37.8 87.0
S 160E 143.6 1.8 9.1 5.5 224.4 4.4 14.2 13.0 359.0 10.8 22.7 32.4 598.4 29.1 37.8 87.0
T 170E 154.1 1.9 9.7 5.6 240.8 4.5 15.2 13.4 385.2 11.2 24.3 33.4 642.0 30.2 40.5 90.2
U 180E 164.8 2.3 10.4 6.9 257.6 5.3 16.2 15.9 412.1 12.8 26.0 38.3 686.8 33.5 43.3 99.9
Electrical Data Notes per NEMA MG-1, 2009 Standard Rev. 1-2010.
Electrical Data Single and Multi-Point Table 12: Standard and HSCCR Panel Ratings
1. Unit wire size ampacity (MCA) is equal to 125% of the Panel Type 208V / 230V 380V / 400V / 460V 575V
largest compressor-motor RLA plus 100% of RLA of all Standard 5kA 5kA 5kA
other loads in the circuit.
HSCCR 65kA 65kA 25kA
2. The control transformer is furnished and no separate
115V power is required. For both single and multi-point Electrical Control Center
power connections, the control transformer is in circuit
Operating and equipment protection controls and motor
#1 with control power wired from there to circuit #2. In
starting components are separately housed in a centrally
multi-point power, disconnecting power to circuit #1
located, weather resistant control panel with hinged and
disconnects control power to the unit.
tool-locked doors. In addition to the MicroTech® III controller
3. Wire sizing amps is 15 amps if a separate 115V power described in the next sections, the following components are
supply is used for the control circuit. housed in the panel:
4. Recommended power lead wire sizes for 3 conductors • Power terminal blocks, multi-point connection standard
per conduit are based on 100% conductor ampacity • Control, input, and output terminal block
in accordance with NEC. Voltage drop has not been
included. It is recommended that power leads be kept • Control transformer
short. All terminal block connections must be made with • Optional disconnect switch (through-the-door handle)
copper (type THW) wire or aluminum wire. • Compressor motor inherent thermal and overload
5. Recommended Fuse Sizes are selected at approximately protection is standard
175% of the largest compressor RLA, plus 100% of all • Optional phase voltage monitor with under/over voltage
other loads in the circuit. and phase reversal protection
6. Maximum Fuse or breaker size is equal to 225% of the • Fan contactors with short circuit protective devices.
largest compressor RLA, plus 100% of all other loads. • Optional ground fault protection
7. The recommended power wire sizes are based on an • FanTrol™ fan staging head pressure control system
ambient temperature of 86°F (30°C). Ampacity correction • Power connections are per Table 13
factors must be applied for other ambient temperatures.
Refer to the NEC Handbook. Power Connections
8. Must be electrically grounded according to national and
local electrical codes. Table 13: Power Connection Availability
Comp. Panel High
Power Disc.
Wiring Data Power Connection Block Swt. Circuit Short Circuit
Breakers Current Rating
1. Single-point power supply requires a single disconnect Optional Single Point Std. Opt. Std. Opt.
to supply electrical power to the unit. This power supply
Standard Multi-Point Std. Opt. Not Avail. Opt.
must either be fused or use a circuit breaker.
2. Power wiring connections to the chiller may be done with Definitions:
either copper or aluminum wiring. Wire should be sized
1. Power Block: An electrical device to directly accept field
per NEC and/or local codes. Wire sizing and wire count
wiring without any disconnecting means.
must fit in the power connection lug sizing shown in the
Electrical Data tables starting on page 28. 2. Disconnect Switch: A molded case switch that accepts
field wiring and disconnects main power to the entire
3. All field wire size values given in the Electrical Data
unit or each main power supply if the multi-point power
tables starting on page 28 apply to 75°C rated wire per
supply option is selected. This option does not provide
NEC.
overcurrent protection.
Circuit Breakers 3. Compressor Circuit Breakers: A manually reset circuit
breaker for each compressor, providing compressor
Factory installed compressor circuit breakers are standard on
only short circuit protection and located ahead of the
units with single point power supply only. This option provides
contactor.
compressor short circuit protection and makes servicing easier
4. Control Panel High Short Circuit Current Rating:
Voltage Limitations: (Previously known as “withstand rating”). The entire
control panel is designed for short circuit current rating
1. Within 10 percent of nameplate rating.
as shown in Table 12. In the event of a short circuit, the
2. Voltage unbalance not to exceed 2% with a resultant damage is contained within the control panel enclosure.
current unbalance of 6 to 10 times the voltage unbalance
PANEL
L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
EARTH
FU4 FU5
GROUND
T1
TB1
35 120 VAC
CHWR1
FU6 301 120 299
PUMP NO.1 RELAY DISCONNECT
CONTROL CIRCUIT VAC
(BY OTHERS) (BY OTHERS)
FUSE
120VAC @ 1.0AMP MAX
TB1 SEE NOTE 2 TB1 22 N
33 N OPTIONAL
(626) / 301A FIELD SUPPLIED
TB1 FU
TB1 CONTROL POWER
1A 120 VAC
P2+ 120 VAC 15A for 1.5 KVA
CHWR2 30A for 3.0KVA
PUMP NO.2 RELAY (BY OTHERS)
(BY OTHERS)
120VAC @ 1.0AMP MAX
TB1
31 N
(714) /
TB1
34 120 VAC
ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX TB1
32A
(235)
/ ABR GND
(630) OFF
(317)
** TIME CLOCK TB2
52
AUTO IF REMOTE STOP
REMOTE CONTROL IS USED
STOP SWITCH 585 REMOVE LEAD 585
(BY OTHERS) ON FROM TERM
TB2 TB2-52 TO TB2-72
72
(655) / MANUAL **
** TIME OFF
CLOCK TB2
54 ALARM BELL **
AUTO RELAY
TB2 /(542)
DOUBLE SET POINT/MODE
SWITCH 24 VAC 43
ON COM NO
(BY OTHERS) ABR
TB2
UNIT ALARM
74
(652) / MANUAL ** BELL
TB2 1 2
N 83
/(225)
** NOR. OPEN PUMP 24VAC @ 0.4AMP MAX.
AUX. CONTACTS
(OPTIONAL) TB2
CHW FLOW SWITCH 44
-MANDATORY-
** TB2 TB2
(BY OTHERS)
61 IF EXTERNAL 45
(649) / ALARM/EVENT
EXTERNAL
IS USED 555A ALARM/
REMOVE LEAD 555A
EVENT
FROM TERM TB2 **
TB2-45 TO TB2-67 67
/(645)
TB2 Notes:
+ 68
4-20MA FOR
1.) ALL FIELD WIRING TO BE INSTALLED AS
EVAP. - LWT RESET
TB2 NEC CLASS 1 WIRING SYSTEM WITH
(BY OTHERS) _
69 CONDUCTOR RATED 600 VOLTS.
(637) / 2.) IF FIELD SUPPLIED, CONTROL POWER USER
TB2 MUST REMOVE FU6, AND WIRE NUMBERS
+ 70 299, 301A INSIDE CONTROL PANEL
4-20MA FOR
3.) ** = USE 'DRY CONTACTS' ONLY
DEMAND LIMIT
TB2 4.) DO NOT SUPPLY FIELD POWER TO
(BY OTHERS) _
71 24VAC OR 120VAC CONTROL CIRCUITS.
(629) /
PANEL
L1 T1
3 PHASE TO CIRCUIT 1
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
FU4 FU5
T1
EARTH
GROUND
FU6 301 120 299
DISCONNECT
CONTROL CIRCUIT VAC (BY OTHERS)
FUSE
SEE NOTE 2 TB1 22 N
OPTIONAL
301A FIELD SUPPLIED
TB1 FU
DISCONNECT SWITCH CONTROL POWER
CIRCUIT BREAKER 2 1A 120 VAC
(BY OTHERS) OR
15A for 1.5 KVA
POWER BLOCK
30A for 3.0KVA
(BY OTHERS)
L1 T1
3 PHASE TO CIRCUIT 2
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
TB1
35 120 VAC
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
TB1
33 N
(626) /
TB1
P2+ 120 VAC
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
TB1
31 N
(714) /
TB1
34 120 VAC
ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX TB1
32A
(240)
/ ABR GND
(630) OFF (317)
** TIME CLOCK TB2
52
AUTO IF REMOTE STOP
REMOTE CONTROL IS USED
STOP SWITCH 585 REMOVE LEAD 585
(BY OTHERS) ON FROM TERM
TB2 TB2-52 TO TB2-72
72
(655) / MANUAL **
OFF ALARM BELL**
** TIME
TB2 RELAY
CLOCK TB2 /(540)
54 24 VAC 43
AUTO COM NO
DOUBLE SET POINT/MODE ABR
ALARM BELL
SWITCH OPTION
(BY OTHERS) ON BELL
TB2 1 2
TB2
N 83
74 /(231)
(652) / MANUAL** 24VAC @ 0.4AMP MAX.
** NOR. OPEN PUMP
AUX. CONTACTS
(OPTIONAL) TB2
CHW FLOW SWITCH 44 TB2
-MANDATORY- 45
** TB2 IF EXTERNAL
(BY OTHERS)
ALARM/EVENT
61 EXTERNAL
(649) / IS USED 555A ALARM/
REMOVE LEAD 555A
** EVENT
FROM TERM TB2
TB2-45 TO TB2-67 67
/(645)
Notes:
TB2
1.) ALL FIELD WIRING TO BE INSTALLED AS
+ 68 NEC CLASS 1 WIRING SYSTEM WITH
4-20MA FOR
EVAP. - LWT RESET CONDUCTOR RATED 600 VOLTS.
TB2 2.) IF FIELD SUPPLIED, CONTROL POWER USER
(BY OTHERS) _
69 MUST REMOVE FU6, AND WIRE NUMBERS
(637) / 299, 301A INSIDE CONTROL PANEL
TB2 3.) ** = USE 'DRY CONTACTS' ONLY
+ 70 4.) DO NOT SUPPLY FIELD POWER TO
4-20MA FOR 24VAC OR 120VAC CONTROL CIRCUITS.
DEMAND LIMIT
TB2
(BY OTHERS) _
71
(629) /
Table 14: Electrical Data - Single Point (60/50Hz) Table 14 continued: Electrical Data - Single Point (60/50Hz)
Single Point Field Data Single Point Field Data
Model Voltage / Ratings Lug Range Model Voltage / Ratings Lug Range
Size Freq. Size Freq.
Disconnect Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 149 175 175 (1) 2-600MCM (1) 6-350MCM 208V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
230V/60 149 175 175 (1) 2-600MCM (1) 6-350MCM 230V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
380V/60 87 100 100 (1) 2-600MCM (1) 12-1/0 380V/60 161 175 175 (1) 2-600MCM (1) 6-350MCM
030E 065E
460V/60 74 80 80 (1) 14-2/0 (1) 12-1/0 460V/60 129 150 150 (1) 2-600MCM (1) 4-300MCM
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0 575V/60 113 125 125 (1) 2-600MCM (1) 4-300MCM
400V/50 77 90 90 (1) 14-2/0 (1) 12-1/0 400V/50 129 150 150 (1) 2-600MCM (1) 4-300MCM
208V/60 163 175 175 (1) 2-600MCM (1) 6-350MCM 208V/60 306 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 163 175 175 (1) 2-600MCM (1) 6-350MCM 230V/60 306 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 96 110 110 (1) 2-600MCM (1) 4-300MCM 380V/60 164 200 200 (1) 2-600MCM (1) 6-350MCM
035E 070E
460V/60 77 90 90 (1) 14-2/0 (1) 12-1/0 460V/60 138 150 150 (1) 2-600MCM (1) 4-300MCM
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0 575V/60 117 125 125 (1) 2-600MCM (1) 4-300MCM
400V/50 80 90 90 (1) 14-2/0 (1) 12-1/0 400V/50 138 150 150 (1) 2-600MCM (1) 4-300MCM
208V/60 168 200 200 (1) 2-600MCM (1) 6-350MCM 208V/60 338 400 400 (1) 2-600MCM (2) 3/0-500MCM
230V/60 168 200 200 (1) 2-600MCM (1) 6-350MCM 230V/60 338 400 400 (1) 2-600MCM (2) 3/0-500MCM
380V/60 107 125 125 (1) 2-600MCM (1) 4-300MCM 380V/60 173 200 200 (1) 14-2/0 (1) 6-350MCM
040E 075E
460V/60 80 90 90 (1) 14-2/0 (1) 12-1/0 460V/60 149 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 67 80 80 (1) 14-2/0 (1) 12-1/0 575V/60 125 150 150 (1) 14-2/0 (1) 4-300MCM
400V/50 83 100 100 (1) 14-2/0 (1) 12-1/0 400V/50 149 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 228 250 250 (1) 2-600MCM (1) 6-350MCM 208V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
230V/60 228 250 250 (1) 2-600MCM (1) 6-350MCM 230V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
380V/60 117 125 125 (1) 2-600MCM (1) 4-300MCM 380V/60 187 225 225 (1) 2-600MCM (1) 6-350MCM
045E 080E
460V/60 90 100 100 (1) 2-600MCM (1) 12-1/0 460V/60 153 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 75 90 90 (1) 14-2/0 (1) 12-1/0 575V/60 126 150 150 (1) 14-2/0 (1) 4-300MCM
400V/50 94 110 110 (1) 2-600MCM (1) 4-300MCM 400V/50 153 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 241 250 250 (1) 2-600MCM (2) 3/0-500MCM 208V/60 384 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 241 250 250 (1) 2-600MCM (2) 3/0-500MCM 230V/60 384 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 131 150 150 (1) 2-600MCM (1) 4-300MCM 380V/60 218 250 250 (1) 2-600MCM (1) 6-350MCM
050E 090E
460V/60 109 125 125 (1) 2-600MCM (1) 4-300MCM 460V/60 168 200 200 (1) 14-2/0 (1) 6-350MCM
575V/60 97 110 110 (1) 2-600MCM (1) 4-300MCM 575V/60 147 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 107 125 125 (1) 2-600MCM (1) 4-300MCM 400V/50 168 200 200 (1) 14-2/0 (1) 6-350MCM
208V/60 251 300 300 (1) 2-600MCM (2) 3/0-500MCM 208V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
230V/60 251 300 300 (1) 2-600MCM (2) 3/0-500MCM 230V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
380V/60 147 175 175 (1) 2-600MCM (1) 6-350MCM 380V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
055E 100E
460V/60 118 125 125 (1) 2-600MCM (1) 4-300MCM 460V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM
575V/60 105 125 125 (1) 2-600MCM (1) 4-300MCM 575V/60 184 225 225 (1) 2-600MCM (1) 6-350MCM
400V/50 119 125 125 (1) 2-600MCM (1) 4-300MCM 400V/50 203 250 250 (1) 2-600MCM (1) 6-350MCM
208V/60 260 300 300 (1) 2-600MCM (2) 3/0-500MCM 208V/60 490 600 600 (2) 6-500MCM (2) 3/0-500MCM
230V/60 260 300 300 (1) 2-600MCM (2) 3/0-500MCM 230V/60 490 600 600 (2) 6-500MCM (2) 3/0-500MCM
380V/60 161 175 175 (1) 2-600MCM (1) 6-350MCM 380V/60 294 350 350 (1) 2-600MCM (2) 3/0-500MCM
060E 110E
460V/60 126 150 150 (1) 2-600MCM (1) 4-300MCM 460V/60 227 250 250 (1) 2-600MCM (1) 6-350MCM
575V/60 113 125 125 (1) 2-600MCM (1) 4-300MCM 575V/60 204 250 250 (1) 2-600MCM (1) 6-350MCM
400V/50 129 150 150 (1) 2-600MCM (1) 4-300MCM 400V/50 227 250 250 (1) 2-600MCM (1) 6-350MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
General Description
The MicroTech® III controller’s design not only permits Security protection prevents unauthorized changing of the
the chiller to run more efficiently, but also can simplify setpoints and control parameters.
troubleshooting if a system failure occurs. Every MicroTech® MicroTech® III control continuously performs self-diagnostic
IIII controller is programmed and tested prior to shipment to checks, monitoring system temperatures, pressures and
facilitate start-up. protection devices, and will automatically shut down a
The controller menu structure is separated into three distinct compressor or the entire unit should a fault occur. The cause
categories that provide the operator or service technician with of the shutdown will be retained in memory and can be easily
a full description of: displayed in plain English for operator review. The MicroTech®
III chiller controller will also retain and display the date/time the
1. current unit status
fault occurred. In addition to displaying alarm diagnostics, the
2. control parameters MicroTech® III chiller controller also provides the operator with
3. alarms a warning of limit (pre-alarm) conditions.
System Architecture
The overall controls architecture uses the following:
• One MicroTech® III unit controller
• I/O extension modules as needed depending on the
configuration of the unit
• Communications interface(s) as needed based on
installed options
Communication interface modules will connect directly to the
left side of the unit controller. I/O extensions will connect
via peripheral bus using the connection on the right side of
the controller. All of the I/O extension modules can connect
directly or using a wiring harness.
Peripheral Bus
I/O Extension
I/O Extension
EEXV1
CC1
Expected
Table 19: Digital Outputs Description Signal Type
Range
Description Output Off Output On Circuit 2 Suction
X1 NTC 10k 340 to 300k Ω
DO1 Evaporator Water Pump 1 Pump Off Pump On Temperature
DO2 Alarm Indicator Alarm Not Active Alarm Active Circuit 2 Evaporator
X2 Voltage 0.4 to 4.6 volts
Pressure
DO3 Circuit 1 Fan Output 1 Fan(s) Off Fan(s) On
Circuit 2 Condenser
DO4 Circuit 1 Fan Output 2 Fan(s) Off Fan(s) On X4 Voltage 0.4 to 4.6 volts
Pressure
DO5 Circuit 1 Fan Output 3 Fan(s) Off Fan(s) On
DO6 Circuit 1 Fan Output 4 Fan(s) Off Fan(s) On Table 24: Digital Inputs
DO7 Circuit 2 Fan Output 1 Fan(s) Off Fan(s) On
Description Signal Off Signal On
DO8 Circuit 2 Fan Output 2 Fan(s) Off Fan(s) On
X6 Circuit 2 Switch Circuit Disable Circuit Enable
DO9 Circuit 2 Fan Output 3 Fan(s) Off Fan(s) On
X7 Circuit 2 MHP Switch Fault No fault
DO10 Circuit 2 Fan Output 4 Fan(s) Off Fan(s) On
Circuit 2 Motor
X7 Circuit 1 Condenser SV 1 Solenoid Closed Solenoid Open X8 Fault No fault
Protection
X8 Circuit 2 Condenser SV 1 Solenoid Closed Solenoid Open
DI1 Circuit 2 PVM/GFP Fault No fault
NOTE: The Motor Protection and MHP input signal are wired
Compressor Module 1 in series. If Motor Protection input is open, MHP
Table 20: Analog Inputs Switch input will also be open.
Description
M1+, M1- EXV Stepper Coil 1
M2+, M2- EXV Stepper Coil 2
Set Points
Set points are initially set to the values in the Default column, not be needed and therefore not be visible.
and can be adjusted to any value in the Range column. Set Basic unit configuration set points will require the unit to be
points are stored in permanent memory. If an option is not off in order to make a change and then require rebooting the
available on a specific model size, the respective set point will controller in order to apply a change.
Table 29: Unit Level Set Point Defaults and Ranges
Description Default Range
Basic Unit Configuration
Unit Model AGZ000??? See Unit Model Configuration Section
Condenser Type Not Set Not Set Tube and Fin, Microchannel
Expansion Valve Type Not Set Not Set., Thermal, Electronic
Condenser Fan VFD Disable Disable, Enable
Power Connection Configuration Single Point Single Point, Multi Point
Mode/Enabling
Unit Enable Enable Disable, Enable
Control source Local Local, Network
Available Modes Cool Cool, Cool w/Glycol, Cool/Ice w/Glycol, Ice, Test
Staging and Capacity Control
Cool LWT 1 7°C (44.6°F) See Dynamic Set Point Ranges
Cool LWT 2 7°C (44.6°F) See Dynamic Set Point Ranges
Ice LWT 4.4°C (39.9°F) -9.5 to 4.4 °C (14.9 to 39.9 °F)
Startup Delta T 5.6°C (10.1°F) 0.6 to 8.3 °C (1.1 to 14.9 °F)
Shut Down Delta T 0.3°C (0.5°F) 0.3 to 1.7 °C (0.5 to 3.1 °F)
Stage Up Delay 240 sec 120 to 480 sec
Stage Down Delay 30 sec 20 to 60 sec
Stage Delay Clear No No, Yes
Max Pulldown Rate 0.6°C/min (1.1°F/min) 0.1 to 2.7°C/min (0.2 to 4.9°F/min)
Full Capacity Evap Delta T 8.9 °C (16°F) 3.3 to 8.9 °C (5.9 to 16 °F)
Variable Evaporator Flow No No, Yes
Ice TimCycle Delay 12 1-23 hours
Clear Ice Timer No No,Yes
RapidRestore Disable Disable, Enable
Rapid Restore Max Power Off 15 seconds 15 ro 180 seconds
Evaporator Pump Control
Evap Pump Control Configuration #1 Only #1 Only, #2 Only, Auto, #1 Primary, #2 Primary
Evap Recirc Timer 30 15 to 300 seconds
Evap Pump 1 Run Hours 0 0 to 999999 hours
Evap Pump 2 Run Hours 0 0 to 999999 hours
Power Conservation and Limits
LWT Reset Enable Disable Disable, Enable
Demand Limit Enable Disable Disable, Enable
High IPLV Mode Disable Disable, Enable
IPLV Condensiong Target 23.89°C (75°F) 21.11 to 32.22°C (70 to 90°F)
Unit Sensor Offsets
Evap LWT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Evap EWT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
OAT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Circuit Configuration Timers
Start to start Time Delay 15 min 10-60 minutes
Stop to start Time Delay 5 min 3-20 minutes
Clear Cycle Timers No No, yes
Alarm and Limit Settings - Units
Evaporator Water Freeze 2.2°C (36°F) See Dynamic Set Point Ranges
Evaporator Flow Proof 5 sec 5 to 15 sec
Evaporator Recirculate Timeout 3 min 1 to 10 min
External Fault Configuration Event Event, Alarm
Low Ambient Lockout 1.7°C (35.1°F) See Dynamic Set Point Ranges
Low Ambient Lockout BAS Alert Off Off, On
Table 30: Cool LWT 1 and Cool LWT2 Set Point Ranges
Available Mode Selection Unit Vintage/Amp Rating Range
Without Glycol E vintage 4.4 to 18.34°C (39.9 to 65°F)
With Glycol E vintage -9.5 to 18.34°C (14.9 to 65°F)
Dynamic Set Point Ranges and Defaults Special Set Point Operation
Some settings have different ranges of adjustment based on The EXV position set point is not changeable unless the unit
other parameters. switch is off.
Table 39: Condenser Target 33% EXV Position set point on each circuit follows the actual EXV
Unit Model Default Range position while EXV Control = Auto. When EXV Control =
Manual, the position set point should be changeable.
Models 30 to 70 32.2°C (90°F) 32.2 to 40.56 °C (90 to 105 °F)
Models 75 to 180 29.4°C (85°F) 29.4 to 40.56 °C (85 to 105 °F)
Security
Table 40: Condenser Target 50% All set points are protected using passwords. A four-digit
password provides operator access to changeable parameters.
Unit Model Default Range
Service level passwords are reserved for authorized service
Models 30 to 70 32.2°C (90°F) 32.2 to 40.56 °C (90 to 105 °F) personnel.
Models 75 to 180 29.4°C (85°F) 29.4 to 40.56 °C (85 to 105 °F)
Operator password: 2526
Sequence of Operation
Unit power up
Is unit enabled? If the unit switch is off, the unit status will be Off:Unit Switch. If the chiller is
Yes disabled due to network command, the unit status will be Off:BAS Disable. When
the remote switch is open, the unit status will be Off:Remote Switch. When a unit
alarm is active, the unit status will be Off:Unit Alarm. In cases where no circuits
Yes are enabled, the unit status will be Off:All Cir Disabled. If the unit is disabled via
the Chiller Enable set point, the unit status will be Off:Keypad Disable.
Low ambient lockout will prevent the chiller from starting even if it is otherwise
Is low ambient lockout
enabled. When this lockout is disabling the chiller, the unit status will be Off:Low
active?
OAT Lock.
No
If the chiller is enabled, then the unit will be in the Auto state and the evaporator
Evaporator pump output on
water pump output will be activated.
No
The chiller will then wait for the flow switch to close, during which time the unit
Is flow present? status will be Auto:Wait for flow.
Yes
After establishing flow, the chiller will wait some time to allow the chilled water
Wait for chilled water loop to
recirculate loop to recirculate for an accurate reading of the leaving water temperature.
The unit status during this time is Auto:Evap Recirculate.
Is Motor Protection If the chiller is waiting on the motor protection delay after powering up, the unit
delay active? status will be Off: Motor Protection Delay.
Yes
No
The chiller is now ready to start if enough load is present. If the LWT is not higher
than the start up temperature, the unit status will be Auto:Wait for load.
Is there enough load to
start chiller?
If the LWT is higher than the start up temperature, the unit status will become
Auto. A circuit can start at this time.
Yes
The first circuit to start is generally the available circuit with the least number of
Start first circuit.
starts. This circuit will go through its start sequence at this point.
No
Additional capacity The unit capacity can be increased if the LWT is above the stage up temperature.
needed to satisfy load?
No
Yes No
Yes
If the second circuit is not running, it will be started now. The unit will try to keep
the load balanced between circuits as the unit capacity is increased.
Increase unit capacity.
If both circuits are running, then additional compressors will start based on the
sequencing logic.
Yes
Yes
No
Yes
Yes
Decrease unit capacity Compressors will shut off as needed in the order determined by sequencing logic.
Is unit running at
minimum capacity?
Yes
No
When only one compressor is running, the load may drop off to the point where even
Is load satisfied? minimum unit capacity is too much. The load has been satisfied when the LWT
drops below the shutdown temperature. At this time the only running circuit can
shut down.
Yes
Shut down last circuit. The last circuit running now shuts down.
When last circuit has completed pumpdown, the unit will go back to waiting for
All circuits off.
enough load to start.
Unit power up
Is unit enabled? If the unit switch is off, the unit status will be Off:Unit Switch. If the chiller is
Yes disabled due to network command, the unit status will be Off:BAS Disable. When
the remote switch is open, the unit status will be Off:Remote Switch. When a unit
alarm is active, the unit status will be Off:Unit Alarm. In cases where no circuits
Yes are enabled, the unit status will be Off:All Cir Disabled. If the unit is disabled via
the Chiller Enable set point, the unit status will be Off:Keypad Disable.
No
Low ambient lockout will prevent the chiller from starting even if it is otherwise
Is low ambient lockout enabled. When this lockout is disabling the chiller, the unit status will be Off:Low
active?
OAT Lock.
No
Yes
If the chiller is enabled, then the unit will be in the Auto state and the evaporator
Evaporator pump output on
water pump output will be activated.
No
The chiller will then wait for the flow switch to close, during which time the unit
Is flow present? status will be Auto:Wait for flow.
Yes
After establishing flow, the chiller will wait some time to allow the chilled water loop
Wait for chilled water loop to
recirculate. to recirculate for an accurate reading of the leaving water temperature. The unit
status during this time is Auto:Evap Recirc.
Yes
Is Motor Protection If the chiller is waiting on the motor protection delay after powering up, the unit
delay active? status will be Off:Motor Protection Delay.
No
No
The chiller is now ready to start if enough load is present. If the LWT is not higher
than the startup temperature, the unit status will be Auto:Wait for load.
Is fluid temp high
enough to start?
If the LWT is higher than the startup temperature, the unit status will be Auto.
A circuit can start at this time.
Yes
The first circuit to start is generally the circuit which contains the compressor with
the least number of starts. This circuit will go through it’s start sequence at this
Maintain unit capacity. point.
No
Has the stage up time A minimum time must pass between the starting of circuits.
delay expired?
No
Yes
No
Yes
If the second circuit is not running, it will be started now. The unit will try to keep
the load balanced between circuits as the unit capacity is increased.
Increase unit capacity.
If both circuits are running, then additional compressors will start based on the
sequencing logic.
Yes
No
Yes
When all circuits have completed shutdown, the unit will remain in the off state until
All circuits off.
the start conditions are satisfied again.
Unit power up
When the circuit is in the Off state the EXV is in the closed position, compressors are
Circuit is in Off state off, solenoid valves are closed, and all condenser fans are off.
No
The circuit must be enabled before it can run. It might be disabled for several
reasons. When the circuit switch is off, the status will be Off:Circuit Switch.
Is circuit is enabled to If the circuit has an active stop alarm then the status will be Off:Alarm. If the circuit
start?
has been disabled via the circuit mode set point, the status will be Off:Keypad
Yes
Disable. If all compressors are disabled via the settings, the circuit status will be
Off:All Comp Disable.
Yes
A minimum time must pass between the previous start and stop of a compressor
and the next start. If this time has not passed, a cycle timer will be active. If all
Are all compressor cycle
timers active? compressors on the circuit have active cycle timers the circuit status will be
Off:Cycle Timers.
No
Circuit is ready to start If the circuit is ready to start when needed, the circuit status will be
Off:Ready.
No
Capacity control logic at the unit level will determine when a circuit needs to start
Is circuit commanded to
start? and issue a start command to the next circuit to start based on sequencing rules.
Yes
Yes
No Before the first compressor on a circuit can start, the EXV performs a brief preopen.
Preopen EXV
The circuit status during this time will be Preopen.
The first compressor will be started and the fans, solenoid valves, and other
Run circuit
devices will be controlled as needed. The normal circuit status at this time will be
Run:Normal. Additional compressors will be started as needed per the unit level
capacity control.
No
Is last compressor Capacity control logic at the unit level will determine when a compressor needs to
commanded to shut down and issue a stop command to the next compressor to stop based on
shut down? sequencing rules. If this compressor is the last one on the circuit, the circuit will
need to shut down.
Yes
When the circuit needs to shut down, a pumpdown of the circuit will NOT be
Is condenser type performed if the condenser coil is Microchannel type. When the circuit needs to
tube and fin? shut down and the condenser is Microchannel type, everything will turn off on the
circuit at approximately the same time.
Yes
When the circuit needs to shut down, a pumpdown of the circuit will be performed
Pumpdown circuit if the condenser coil is tube and fin type. The circuit status during this time will be
Run:Pumpdown.
No
Unit Functions
The calculations in this section are used in unit level control means the flow that is needed for a 5.56°C (10°F) delta T at full
logic or in control logic across all circuits. unit capacity.
Unit Mode Selection Pumpdown – Unit is doing a normal shutdown (tube and fin
condenser coils only). If a unit has microchannel coils, the
The operating mode of the unit is determined by setpoints and individual refrigerant circuits will never do a pumpdown. So
inputs to the chiller. The Available Modes Set Point determines if the conditions for the Auto to Pumpdown transition occur,
what modes of operation can be used. This set point also the unit state will transition from Auto to Pumpdown and
determines whether the unit is configured for glycol use. The then immediately to Off.
Control Source Set Point determines where a command
to change modes will come from. A digital input switches Transitions between these states are shown in the following
between cool mode and ice mode if they are available and diagram.
the control source is set to ‘local.’ The BAS mode request
switches between cool mode and ice mode if they are both
available and the control source is set to ‘network.’
The Available Modes Set Point should only be changeable
when the unit switch is off. This is to avoid changing modes of
operation inadvertently while the chiller is running.
3
3
8 Off: Remote Switch
Switch is open
Unit State = Off, Control
9 Off: BAS Disable Source = Network, and BAS
Enable = false
Unit State = Off and Unit RUN START
10 Off: Unit Switch
Switch = Disable
Unit State = Off and Unit Mode
11 Off: Test Mode
= Test
Unit State = Auto, no circuits
running, and LWT is less than
T1 – Off to Start
12 Auto: Wait for load
the active set point + startup Requires any of the following
delta
• Unit state = Auto
Unit State = Auto and
13 Auto: Evap Recirc • Freeze protection started
Evaporator State = Start
Unit State = Auto, Evaporator T2 – Start to Run
14 Auto: Wait for flow State = Start, and Flow Switch
is open Requires the following
15 Auto: Pumpdown Unit State = Pumpdown • Flow ok for time longer than evaporator recirculate time
Unit State = Auto, max set point
16 Auto: Max Pulldown pulldown rate has been met or
exceeded T3 – Run to Off
Unit State = Auto, unit Requires all of the following
17 Auto: Unit Cap Limit capacity limit has been met or
exceeded
• Unit state is Off
Unit State = Auto and high • Freeze protection not active
18 Auto: High Ambient Limit
ambient capacity limit is active
Unit State = Auto and unit is
T4 – Start to Off
19 Auto:Rapid Restore performing Rapid Restore Requires all of the following
operation
• Unit state is Off
Condenser type setting is set
20 Off:Cond Type Not Set • Freeze protection not active
to ‘Not Set’
Expansion valve type setting is T5 – Run to Start
21 Off:ExVlv Type Not Set
set to ‘Not Set’
22 Off:Invalid Config Unit model selected not valid Flow switch input is low for longer than the flow proof set
A configuration change
point.
Config Changed, Reboot requiring a reboot has
23
Required occurred but controller has not
been rebooted yet.
Stage Up Delay
Unit Capacity Overrides
A fixed stage up delay of one minute between compressor
Unit capacity limits can be used to limit total unit capacity in
starts should be used in this mode.
Cool mode only. Multiple limits may be active at any time, and
the lowest limit is always used in the unit capacity control.
Staging Sequence
This section defines which compressor is the next one to Demand Limit
start or stop. In general, compressors with fewer starts will
The maximum unit capacity can be limited by a 4 to 20 mA
normally start first, and compressors with more run hours will
signal on the Demand Limit analog input. This function is
normally stop first.
only enabled if the Demand Limit set point is set to ON. The
If possible circuits will be balanced in stage. If a circuit is maximum unit capacity stage is determined as shown in the
unavailable for any reason, the other circuit shall be allowed following tables:
to stage all compressors on. When staging down, one
compressor on each circuit shall be left on until each circuit has
Limit ≥ 100% 4
Operation Following Power Cycle
100% > Limit ≥ 75% 3
The chiller will enter RapidRestore® upon powering up when
75% > Limit ≥ 50% 2 the following conditions are met:
50% > Limit 1 • RapidRestore® is enabled
• Power failure lasts less than the value of the Max Power
Table 49: Stage Limits - Six Compressors Failure Time set point
Network Limit Stage • Power failure lasts at least one second (shorter power
Limit ≥ 100% 6 loss may result in unpredictable operation)
100% > Limit ≥ 83.3% 5 • Unit is enabled
83.3% > Limit ≥ 66.7% 4 When RapidRestore® is triggered, the time value used for the
evaporator recirculation time will be limited to 110 seconds
66.7% > Limit ≥ 50% 3 or less. The evaporator recirculation time set point will not be
50% > Limit ≥ 33.3% 2 changed. Only the value used in the evaporator state logic will
33.3% > Limit 1 be limited, and only if the set point exceeds the 110 second
limit.
Maximum LWT Pulldown Rate This action will ensure that the chiller is ready to start after the
The maximum drop rate for the leaving water temperature shall motor protection module delay has expired.
be limited by the Maximum Pulldown Rate set point only when
the unit mode is Cool.
If the rate exceeds the set point, no more compressors can
be started until the pulldown rate is less than the set point.
Running compressors will not be stopped as a result of
exceeding the maximum pulldown rate.
Capacity Changes
Normally the delay between compressors staging on is
determined by the Stage Up Delay setting. That setting
defaults to 240 seconds and has a range of 120 to 480
seconds. During fast loading, a delay of 60 seconds between
compressor starts within a circuit should be used. In addition,
a delay of 30 seconds between compressor starts on different
circuits should be used.
This change during RapidRestore® operation will allow for a
faster time to full capacity while maintaining stable operation
within each circuit. Assuming both circuits are able to run, the
effective unit stage up delay will be 30 to 35 seconds, so it will
load about four times faster during RapidRestore® than the
fastest it possibly can during normal operation.
Figure 40: RapidRestore® Mode - Four Compressor Units – Power Lost and Restored
Figure 41: RapidRestore® Mode - Six Compressor Units - Power Lost and Restored
Figure 42: RapidRestore® Mode - Four Compressor Units - Backup Chiller, Constant Power
Figure 43: RapidRestore® Mode - Six Compressor Units - Backup Chiller Constant Power
Circuit Functions
Calculations
Circuit States
Refrigerant Saturated Temperature The circuit will always be in one of four states:
Refrigerant saturated temperature shall be calculated from the Off – Circuit is not running
pressure sensor readings for each circuit.
Preopen – Circuit is preparing to start
Evaporator Approach Run – Circuit is running
The evaporator approach shall be calculated for each circuit. Pumpdown – Circuit is doing a normal shutdown
The equation is as follows:
Transitions between these states are shown in the following
Evaporator Approach = LWT – Evaporator Saturated diagram.
Temperature
T1
Condenser Approach POWER
ON
OFF
T6
PREOPEN
T4
T2
T5
- OAT
Suction Superheat
Suction superheat shall be calculated for each circuit using the PUMPDOWN T3 RUN
following equation:
Suction superheat = Suction Temperature – Evaporator
Saturated Temperature
T1 – Off to Preopen
Pumpdown Pressure • No compressors are running and any compressor on
The pressure to which a circuit will pumpdown is based on the circuit is commanded to start (see unit capacity control)
Low Evaporator Pressure Unload set point. The equation is as
follows: T2 – Preopen to Run
Pumpdown pressure = Low Evap Pressure Unload set point • 5 seconds in Preopen state has passed
– 103KPA (15 PSI)
T3 – Run to Pumpdown
Circuit Control Logic Any of the following are required:
• Last compressor on circuit is commanded to stop
Circuit Enabling • Unit State = Pumpdown
A circuit should be enabled to start if the following conditions • Circuit switch is open
are true: • Circuit mode is disable
• Circuit switch is closed • Circuit Pumpdown alarm is active
• No circuit alarms are active
T4 – Pumpdown to Off
• Circuit Mode set point is set to Enable
Any of the following are required:
• At least one compressor is enabled to start (according to
enable setpoints) • Evaporator Pressure < Pumpdown Pressure Value
• Unit State = Off
Compressor Availability • Circuit Rapid Stop alarm is active
A compressor is considered available to start if all the following
are true: T5 – Run to Off
• The corresponding circuit is enabled Any of the following are required:
• The corresponding circuit is not in pumpdown • Unit State = Off
• No cycle timers are active for the compressor • Circuit Rapid Stop alarm is active
• No limit events are active for the corresponding circuit • A low ambient start attempt failed
• The compressor is enabled via the enable setpoints
• The compressor is not already running
3 3 On On On On
Table 57: 5 Fans With Fan VFD
Fan
Table 52: 4 Fans Without VFD Condenser Fans Fan 2 Fan 3 Fan 4 Fan 5 SV 1
Speed
Condenser Fans Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 SV 1 Stage Running D.O. D.O. D.O. D.O. D.O.
A.O.
Stage Running D.O. D.O. D.O. D.O. D.O. D.O.
0 0
0 0
1 2 On
1 1 On
2 3 On On
2 2 On On On
3 4 On On On
3 3 On On On On
4 5 On On On On On
4 4 On On On On On
Condenser Target below the target – the active deadband, a stage down error is
accumulated.
The condenser target is selected based on circuit capacity
using the condenser target set points. There are set points Stage Down Error Step = (Target - Stage Down dead band)
that establish the condenser target for 33%, 50%, 67%, and - Saturated Condenser Temperature
100% capacity. If the circuit has two compressors the set The Stage Down Error Step is added to Stage Down
points for 50% and 100% will be used. If the circuit has three Accumulator once every 5 seconds. When the Stage Down
compressors then the set points for 33%, 67%, and 100% will Error Accumulator is greater than 2.8°C (5°F) another stage of
used. condenser fans is removed.
A minimum condenser target should be enforced. This When a stage down occurs or the saturated temperature rises
minimum will be calculated based on the evaporator LWT. back above the target minus the Stage Down dead band, the
As the LWT varies from 7.2°C (45°F) to 32.2°C (90°F), the Stage Down Error Accumulator is reset to zero.
minimum condenser target will vary from 23.9°C (75°F) to
48.9°C (120°F). VFD
Condenser pressure trim control is accomplished using an
Staging Up optional VFD on the first fan. This VFD control will vary the fan
The first fan will not start until the evaporator pressure drop speed to drive the saturated condenser temperature to a target
or condenser pressure rise requirement for the No Pressure value. The target value is normally the same as the saturated
Change After Start alarm is satisfied. Once that requirement condenser temperature target.
is met, if there is no fan VFD then the first condenser stage
The speed should be controlled between the minimum and
should start when the saturated condenser temperature
maximum speed set points.
exceeds the condenser target. If there is a fan VFD, then
the first stage should start when the saturated condenser
temperature exceeds the condenser target less 5.56°C (10°F).
VFD State
The VFD speed signal should always be 0 when the fan stage
After this, the four stage up dead band settings will be used:
is 0.
Stage Up Deadband 1 – used when active condenser stage is 1
When the fan stage is greater than 0, the VFD speed signal
Stage Up Deadband 2 – used when active condenser stage is 2 should be enabled and control the speed as needed.
Stage Up Deadband 3 – used when active condenser stage is 3
Stage Up Compensation
Stage Up Deadband 4 – used when active condenser stage is 4, 5,
or 6 In order to create a smoother transition when another fan is
staged on, the VFD compensates by slowing down initially.
When the saturated condenser temperature is above the target This is accomplished by adding the new fan stage up
plus the active deadband, stage up error is deadband to the VFD target. The higher target causes the
accumulated. VFD logic to decrease fan speed. Then, every 2 seconds,
0.1°C (0.18°F) is subtracted from the VFD target until it is
Stage Up Error Step = Saturated Condenser Temperature –
equal to the saturated condenser temperature target set point.
(Target + Stage Up dead band)
The Stage Up Error Step is added to Stage Up Accumulator High IPLV Mode
once every 5 seconds, only if the Saturated Condenser
Refrigerant Temperature is not falling. When Stage Up Error When the High IPLV Mode setting is ‘On’ and one compressor
Accumulator is greater than 11°C (19.8°F) another stage is is running on the unit, the condenser target setting for the
added. running circuit may be overridden. In this case, rather than use
the condenser target setting for 33% or 50% (depending on
When a stage up occurs or the saturated condenser number of compressors), the condenser target will be forced to
temperature falls back within the stage up dead band the Stage the value of the IPLV Condenser Target set point.
Up Accumulator is reset to zero.
In addition, when high IPLV mode is active the calculation for
the minimum allowed condenser target (based on LWT) will
Staging Down be changed. The minimum value will be changed from 23.9°C
Four stage down dead bands shall be used. (75°F) to the value of the IPLV Condenser Target set point.
Stage Down Deadband 1 – used when active condenser stage is 1 No other changes to the operation are made when High IPLV
mode is on.
Stage Down Deadband 2 – used when active condenser stage is 2
Stage Down Deadband 3 – used when active condenser stage is 3 Additional Conditions For MicroChannel
Stage Down Deadband 4 – used when active condenser stage is 4, Coils
5, or 6
For units configured with MicroChannel condenser coils, the
When the saturated condenser refrigerant temperature is fan staging is the same as for a standard coil except there are
two additional conditions which may cause the fan stage to Position Commands
increase:
In order to improve the reliability of the EXV positioning, the
• If circuit has two compressors, the second compressor position commands that are issued to the stepper driver are
on a circuit starts, the circuit is not already at the limited in two ways:
maximum condenser stage, and the condenser saturated
1. Position commands are filtered so that the minimum change
temperature is higher than 37.78°C (100°F), then a
in position is 0.3%. Changes of less than this are ignored. This
condenser stage will be added immediately.
avoids unnecessary movement of the EXV and lowers the
• If the condenser stage is not already at the maximum, chances of losing steps as a result.
the saturated condenser temperature exceeds 56.67°C
(134°F), it has been at least 5 seconds since adding 2. The position commands are issued once per program cycle
a condenser stage, and the saturated condenser with a maximum change of 0.7% each time. This allows the
temperature is not dropping, then a condenser stage will stepper to move the valve to the commanded position before
be added immediately. the next position command is issued. Issuing commands in this
way may also lower the chances of losing steps.
In addition, if the circuit has 4 fans, or it has 6 fans and no
fan VFD’s, then the first condenser stage may be skipped at
startup. This happens if the OAT is at least 21.11°C (70°F) EXV Position Range
when the first condenser stage would normally be started, in The minimum EXV position while the circuit is running will
which case it will go directly to the second stage. always be 8%. The maximum position will change as the
Both of these additions are in place to deal with spikes in number of compressors running on the circuit changes. These
condenser pressure resulting from the lower volume of the values are shown for each unit model in the table below.
MicroChannel coils.
Table 58: Maximum Position Range
Manual Control
The EXV position can be set manually. Manual control can only
be selected when the circuit is in the run state. At any other
time, the EXV control set point is forced to auto.
When EXV control is set to manual, the EXV position is equal
to the manual EXV position setting. If set to manual when the
circuit state transitions from run to another state, the control
setting is automatically set back to auto. When in manual
control, the EXV control state displayed should reflect that it is
manual control.
Alarms
Situations may arise that require some action from the chiller always a manual reset alarm.
or that should be logged for future reference. Alarms are
classified in the following sections using the Fault/Problem/ Evaporator Water Freeze Protect
Warning scheme. Trigger: Evaporator LWT drops below evaporator freeze
When any Unit Fault Alarm is active, the alarm digital output protect set point and LWT sensor fault is not active for a time
should be turned on continuously. If both circuits have a Circuit longer than the evaporator recirculation time set point.
Fault Alarm active, the alarm digital output should be turned Action Taken: Rapid stop all circuits
on continuously. If no Unit Fault Alarm is active and only one
circuit has a Circuit Fault Alarm is active, the alarm digital Reset: This alarm can be cleared manually via the keypad,
output should alternate five seconds on and five seconds off but only if the alarm trigger conditions no longer exist.
continuously.
Evaporator LWT Sensor Fault
All alarms appear in the active alarm list while active. All alarms
are added to the alarm log when triggered and when cleared. Trigger: Sensor shorted or open for longer than one second
Entries in the log representing the occurrence of an alarm will Action Taken: Normal stop all circuits
be preceded by ‘+’ while entries representing the clearing of an
alarm will be preceded by ‘-‘. Reset: This alarm can be cleared manually via the keypad or
BAS command, but only if the sensor is back in range.
Expansion Valve Type = Thermal. Reset: Auto clear when LWT reset is disabled or LWT reset
input back in range for 5 seconds.
EXV Module 2 Comm Failure
Trigger: Expansion Valve Type = Electronic and Evaporator EWT Sensor Fault
communication with the I/O extension module has failed. Trigger: Sensor shorted or open for longer than one second
Action Taken: Rapid stop of circuit 2. Action Taken: None.
Reset: This alarm can be cleared manually via the keypad or Reset: Auto clear when the sensor is back in range.
BAS command when communication between main controller
and the extension module is working for 5 seconds or
Expansion Valve Type = Thermal. Circuit Fault Alarms
PVM/GFP Fault
Unit Problem Alarms Trigger: Power Configuration = Multi Point and circuit PVM/
GFP input is open for longer than one second
Evaporator Pump #1 Failure
Action Taken: Rapid stop circuit.
Trigger: Unit is configured with primary and backup pumps,
pump #1 is running, and the pump control logic switches to Reset: Auto reset when input is closed for at least 5 seconds
pump #2. or if Power Configuration = Single Point.
Action Taken: Backup pump is used. Low Evaporator Pressure
Reset: This alarm can be cleared manually via the keypad or Trigger:
BAS command.
This alarm should trigger when Freeze time is exceeded, Low
Evaporator Pump #2 Failure Ambient Start is not active, and Circuit State = Run. It should
also trigger if Evaporator Press < 137.9 KPA (20 psi) and
Trigger: Unit is configured with primary and backup pumps, Circuit State = Run for longer than 1 second.
pump #2 is running, and the pump control logic switches to
pump #1. Freezestat logic allows the circuit to run for varying times at low
pressures. The lower the pressure, the shorter the time the
Action Taken: Backup pump is used. compressor can run. This time is calculated as follows:
Reset: This alarm can be cleared manually via the keypad or Freeze error = Low Evaporator Pressure Unload –
BAS command. Evaporator Pressure
Freeze time =
Unit Warning Alarms For units equipped with 10 or more condenser fans (shell
and tube type evaporator):
External Event
80 – (freeze error/6.895), limited to a range of 40 to 80
Trigger: External Alarm/Event input is open for at least 5 seconds
seconds and external fault is configured as an event.
For all other configurations (plate to plate type evaporator):
Action Taken: None.
60 – (freeze error/6.895), limited to a range of 20 to 60
Reset: Auto clear when digital input is closed. seconds
When the evaporator pressure goes below the Low Evaporator
Bad Demand Limit Input
Pressure Unload set point, a timer starts. If this timer exceeds
Trigger: Demand limit input out of range and demand limit the freeze time, then a freezestat trip occurs. If the evaporator
is enabled. For this alarm out of range is considered to be a pressure rises to the unload set point or higher, and the freeze
signal less than 3mA or more than 21mA. time has not been exceeded, the timer will reset.
Action Taken: Cannot use demand limit function. The alarm cannot trigger if the evaporator pressure sensor fault
Reset: Auto clear when demand limit disabled or demand limit is active.
input back in range for 5 seconds. Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the keypad if
Bad LWT Reset Input
the evaporator pressure is above 137.9 KPA (20 PSI).
Trigger: LWT reset input out of range and LWT reset is
enabled. For this alarm out of range is considered to be a High Condenser Pressure
signal less than 3mA or more than 21mA.
Trigger: Condenser Pressure > High Condenser Pressure set
Action Taken: Cannot use LWT reset function. point for longer than one second.
ClearAlarms object. Reset: While still running, the event will reset if evaporator
pressure > Low Evaporator Pressure Hold SP + 90 KPA (13
To use the keypad, follow the Alarm links to the Alarms screen,
PSI). The event is also reset if the circuit is no longer in the run
which will show Active Alarms and Alarm Log. Select Active
state.
Alarm and press the wheel to view the Alarm List (list of current
active alarms). They are in order of occurrence with the most
recent on top. The second line on the screen shows Alm Cnt Low Evaporator Pressure - Unload
(number of alarms currently active) and the status of the alarm Trigger:
clear function. Off indicates that the Clear function is off and This event is triggered if all of the following are true:
the alarm is not cleared. Press the wheel to go to the edit
mode. The Alm Clr (alarm clear) parameter will be highlighted • circuit state = Run
with OFF showing. To clear all alarms, rotate the wheel to • more than one compressor is running on the circuit
select ON and enter it by pressing the wheel. • evaporator pressure <= Low Evaporator Pressure -
An active password is not necessary to clear alarms. Unload set point for a time greater than half of the
current freezestat time
If the problem(s) causing the alarm have been corrected, the
alarms will be cleared, disappear from the Active Alarm list • circuit is not currently in a low OAT start
and be posted in the Alarm Log. If not corrected, the On will • it has been at least 30 seconds since a compressor has
immediately change back to OFF and the unit will remain in the started on the circuit.
alarm condition. On units equipped with 6 compressors, electronic expansion
valves, and 10 or more fans, when each compressors
Reset: None This event is triggered if all of the following are true:
• circuit state = Run
• more than one compressor is running on the circuit
Circuit Events • condenser pressure > High Condenser Pressure –
Low Evaporator Pressure - Hold Unload set point
Trigger: Action Taken: Stage off one compressor on the circuit every
10 seconds while condenser pressure is higher than the
This event is triggered if all of the following are true: unload set point, except the last one. Inhibit staging more
• circuit state = Run compressors on until the condition resets.
• evaporator pressure <= Low Evaporator Pressure - Hold Reset: While still running, the event will be reset if condenser
set point pressure <= High Condenser Pressure Unload SP – 862
• circuit is not currently in a low OAT start KPA(125 PSI). The event is also reset if the circuit is no longer
in the run state.
• it has been at least 30 seconds since a compressor has
started on the circuit.
Action Taken: Inhibit starting of additional compressors on the
circuit.
The keypad/display consists of a 5-line by 22-character include changeable data fields (setpoints).
display, three buttons (keys) and a “push and roll” navigation When the cursor is on a line the highlights will look like this:
wheel. There is an Alarm Button, Menu (Home) Button and a
Back Button. The wheel is used to navigate between lines on Evaporator Delta T= 10.0F
a screen (page) and to increase and decrease changeable If line contains a changeable value-
values when editing. Pushing the wheel acts as an Enter
Button and will jump from a link to the next set of parameters. Unit Status= Run
If the line contains status-only information-
Figure 45: Typical Screen Or a line in a menu may be a link to further menus. This
is often referred to as a jump line, meaning pushing the
•6 View/Set Unit 3
navigation wheel will cause a “jump” to a new menu. An arrow
Status/Settings > (>) is displayed to the far right of the line to indicate it is a
Set Up > “jump” line and the entire line is highlighted when the cursor is
on that line.
Temperature >
NOTE - Only menus and items that are applicable to the
Date/Time/Schedule >
specific unit configuration are displayed.
Generally, each line on the display contains a menu title, a
This manual includes information relative to the operator level
parameter (such as a value or a setpoint), or a link (which will
of parameters; data and setpoints necessary for the every
have an arrow in the right of the line) to a further menu.
day operation of the chiller. There are more extensive menus
The first line visible on each display includes the menu title and available for the use of service technicians.
the line number to which the cursor is currently “pointing.” In
the above screen, Temperature is highlighted. Navigating
The left most position of the title line includes an “up” arrow ▲ When power is applied to the control circuit, the controller
to indicate there are lines (parameters) “above” the currently screen will be active and display the Home screen, which can
displayed line; and/or a “down” arrow ▼ to indicate there are also be accessed by pressing the Menu Button The navigating
lines (parameters) “below” the currently displayed items or an wheel is the only navigating device necessary, although the
“up/down” arrow • to indicate there are lines “above and below” MENU, ALARM, and BACK buttons can provide shortcuts as
the currently displayed line. The selected line is highlighted. explained later.
Each line on a screen can contain status-only information or
Passwords When the Alarm Button is depressed, the Alarm Lists menu is
displayed.
Enter passwords from the Main Menu:
• Enter Password links to the Entry screen which is an Edit Mode
editable screen. So pressing the wheel goes to the edit
The Editing Mode is entered by pressing the navigation wheel
mode where the password (2526) can be entered. The
while the cursor is pointing to a line containing an editable field.
first (*) will be highlighted, rotate the wheel clockwise to
Once in the edit mode pressing the wheel again causes the
the first number and set it by pressing the wheel. Repeat
editable field to be highlighted. Turning the wheel clockwise
for the remaining three numbers. The password will time
while the editable field is highlighted causes the value to be
out after 10 minutes and is cancelled if a new password is
increased. Turning the wheel counter-clockwise while the
entered or the control powers down.
editable field is highlighted causes the value to be decreased.
• Not entering a password allows access to a limited The faster the wheel is turned the faster the value is increased
number of parameters as shown in Figure 49. or decreased. Pressing the wheel again cause the new value
to be saved and the keypad/display to leave the edit mode and
Figure 46: Password Menu return to the navigation mode.
Main Menu 1/3 A parameter with an “R” is read only; it is giving a value or
description of a condition. An “R/W“ indicates a read and/or
Enter Password >
write opportunity; a value can be read or changed (providing
Unit Status the proper password has been entered).
Off: Unit Sw Link and parameter access is indicated for the various
ACTIVE SETPT 44.6°F password levels with one column for each level. Column
headings for the password levels are as follows and shown in
Figure 47: Password Entry Page Figure 48:
N = No password
Enter Password 1/1
O = Operator level
Enter PW ****
T = Technician level
Entering an invalid password has the same effect as not D = Daikin Applied factory service technician level
entering a password.
Screen navigational links:
Once a valid password has been entered, the controller
allows further changes and access without requiring the user • For each link on a screen, the linked screen is indicated
to enter a password until either the password timer expires in the rightmost column.
or a different password is entered. The default value for this • For each screen, the screen(s) from which you can
password timer is 10 minutes. navigate to it is also shown in parentheses after the
screen identifier.
Navigation Mode • For most circuit or compressor level parameters, there
is a link to a screen that shows the values for all circuits/
When the navigation wheel is turned clockwise, the cursor
compressors which is indicated in the ‘Links to screen’
moves to the next line (down) on the page. When the wheel is
column as *.
turned counter-clockwise the cursor moves to the previous line
(up) on the page. The faster the wheel is turned the faster the For many of the circuit level screens, only one screen will be
cursor moves. Pushing the wheel acts as an “Enter” button. shown in this section. The same set of screens exists for each
circuit and compressor. These screens are the ones with ‘Cx’
Three types of lines exist: and Cmpx’ identifiers.
• Menu title, displayed in the first line as in Figure 46.
• Link (also called Jump) having an arrow ( > ) in the right Figure 48: Example of Screen Menu With Access Levels
of the line and used to link to the next menu.
• Parameters with a value or adjustable setpoint.
For example, “Time Until Restart” jumps from level 1 to level 2
and stops there.
When the Back Button is pressed the display reverts back to
the previously displayed page. If the Back button is repeatedly
pressed the display continues to revert one page back along
the current navigation path until the “main menu” is reached.
When the Menu (Home) Button is pressed the display reverts
to the “main page.”
The optional VFD fan control is used for unit operation below Inverter Output to the Motor
32°F (0°C) down to a minimum of -10°F (-23°C). The control
looks at the saturated discharge temperature and varies the WARNING
fan speed to hold the temperature (pressure) at the “target” Avoid swapping any 2 of the 3 motor lead connections which
temperature. will cause reversal of the motor direction. In applications
Low ambient air temperature control is accomplished by using where reversed rotation could cause equipment damage or
the Optional Low Ambient VFD to control the speed of the personnel injury, be sure to verify direction of rotation before
first fan on each circuit. This VFD control uses a proportional attempting full-speed operation. For safety to personnel,
integral function to drive the saturated condenser temperature the motor chassis ground must be connected to the ground
to a target value by changing the fan speed. The target value connection at the bottom of the inverter housing.
is normally the same as the saturated condenser temperature
target setpoint.
The AC motor must be connected only to the inverter’s
The fan VFD always starts when the saturated condenser
output terminals. The output terminals are uniquely labeled
temperature rises higher than the target.
(to differentiate them from the input terminals) with the
designations U/T1, V/T2, and W/T3.
What is an Inverter?
The term inverter and variable-frequency drive are related and
somewhat interchangeable. An electronic motor drive, for an
AC motor, controls the motor’s speed by varying the frequency
of the power sent to the motor.
In general, an inverter is a device that converts DC power to
AC power. The figure below shows how the variable-frequency
drive employs an internal inverter. The drive first converts
incoming AC power to DC through a rectifier bridge, creating
an internal DC bus voltage. Then the inverter circuit converts
the DC back to AC again to power the motor. The special
inverter can vary its output frequency and voltage according to
the desired motor speed.
VFD Interface
The VFD controller is located in the lower left-hand corner of
the unit control panel. It is used to view data including fault and
alarm information. No operator intervention on this control is
required for normal unit operation.
State Content
Illuminated When the drive detects an alarm or error
When an alarm occurs
Flashing When an oPE is detected
When a fault or error occurs during Auto-Tuning
Off Normal operation (no fault or alarm)
Flashing
LED Lit Flashing Quickly Off
Slowly
When the operator When a device other than
is selected for Run the operator is selected for
LO/RE command and -- -- Run command and frequency
frequency reference reference control (REMOTE)
control (LOCAL)
While the drive was set to LOCAL, a Run
command was entered to the input terminals
then the drive was switched to REMOTE.
During
A Run command was entered via the input
deceleration
terminals while the drive was not in the Drive
to stop
Mode.
When a Run During deceleration when a Fast Stop
RUN During run command was entered. During stop
command
is input and The drive output is shut of by the Safe Disable
frequency function.
reference is
The STOP key was pressed while drive was
0 Hz
running in REMOTE.
The drive was powered up with b1-17 = 0
(default) while the Run command was active.
After the Fault Occurs Procedure Table 65: Periodic Inspection Checklist
Press RESET on the controller. Inspection Area Inspection Points Corrective Action
Inspect equipment Replace damaged
including wiring, components.
Fix the cause of the fault,
terminals, resistors,
restart the drive, and reset
capacitors, diode and
the fault
General IGBT for discoloration
from overheating or
deterioration.
Close then open the fault signal Inspect for dirt or foreign Use dry air to clear
digital input via terminal S4. S4 is particles away.
set for “Fault Reset” as default Inspect contactors and Check for over or
Resetting via Fault Reset (H1-04 = 14) relays for excessive undervoltage
Digital Input S4 noise.
Relays and
Inspect for signs of Replace damaged
Contactors
overheating such as parts.
melted or cracked
insulation
Turn off the main power
supply if the above methods
do not reset the fault. Optional BAS Interface
Reapply power after the The AGZ chiller controller is configured for stand-alone
controller display has turned operation or integration with BAS through an optional
off. communication module.
NOTE: When a fault occurs, the cause of the fault must The following installation manuals for optional BAS interface
be removed and the drive must be restarted. The modules are shipped with the chiller. They can also be found
above table list the various ways to restart the drive. and downloaded from www.DaikinApplied.com.
Remove the Run command before attempting to clear
a fault. If the Run command is present, the control will • IM 966-1, BACnet® IP Communication Module
disregard any attempt to reset the fault. • IM 967-1, BACnet® Communication Module (MS/TP)
• IM 968-1, LONWORKS Communication Module
Recommended Periodic Inspection • IM 969-2, Modbus® Communication Module
WARNING • ED 15120, Protocol Information for MicroTech® III chiller,
Electrical Shock Hazard. Before servicing or inspecting BACnet and LONWORKS
the equipment, disconnect power to the unit.The internal • ED 15121, Protocol Information for MicroTech® III chiller,
capacitor remains charged after power is turned off. Wait Modbus
at least the amount of time specified on the drive before
touching any components.
Pre Startup 3. Put System Switch (S1) to the Emergency Stop position.
Inspected the chiller to ensure no components became loose 4. Put both circuit #1 & #2 switches to the Pumpdown and
or damaged during shipping or installation including leak test Stop position.
and wiring check. 5. Apply power to the unit. The panel Alarm Light will stay
on until S1 is closed. Ignore the Alarm Light for the check
Pre-Startup Water Piping Checkout out period. If you have the optional Alarm Bell, you may
1. Check the pump operation and vent all air from the wish to disconnect it.
system. 6. Check at the power block or disconnect for the proper
2. Circulate evaporator water, checking for proper system voltage and proper voltage between phases. Check
pressure and evaporator pressure drop. Compare the power for proper phasing using a phase sequence meter
pressure drop to the evaporator water pressure drop before starting unit.
curve. 7. Check for 120 Vac at the optional control transformer and
3. Flush System and clean all water strainers before placing at TB-2 terminal #1 and the neutral block (NB).
the chiller into service. 8. Check between TB-2 terminal #7 and NB for 120 Vac
4. Check water treatment and proper glycol percent. supply for transformer #2.
5. Pre-Startup Refrigerant Piping Checkout 9. Check between TB-2 terminal #2 and NB for 120 Vac
control voltage. This supplies the compressor crank case
6. Check all exposed brazed joints for evidence of leaks. heaters.
Joints may have been damaged during shipping or when
the unit was installed. 10. Check between TB-3 terminal #17 and #27 for 24 Vac
control voltage.
7. Check that all refrigerant valves are either opened or
closed as required for proper operation of the chiller.
8. A thorough leak test must be done using an approved Startup
electronic leak detector. Check all valve stem packing for Refer to the MicroTech® III Controller information on page 24 to
leaks. Replace all refrigerant valve caps and tighten. become familiar with unit operation before starting the chiller.
9. Check all refrigerant lines to insure that they will not There should be adequate building load (at least 50 percent
vibrate against each other or against other chiller of the unit full load capacity) to properly check the operation of
components and are properly supported. the chiller refrigerant circuits.
10. Check all connections and all refrigerant threaded Be prepared to record all operating parameters required by
connectors. the “Compressorized Equipment Warranty Form”. Return
11. Look for any signs of refrigerant leaks around the this information within 10 working days to Daikin Applied as
condenser coils and for damage during shipping or instructed on the form to obtain full warranty benefits.
installation.
12. Connect refrigerant service gauges to each refrigerant Startup Steps
circuit before starting unit. • Verify chilled water flow.
• Verify remote start / stop or time clock (if installed) has
Pre-Startup Electrical Check Out requested the chiller to start.
• Set the chilled water setpoint to the required temperature.
WARNING
(The system water temperature must be greater than the
Electrical power must be applied to the compressor total of the leaving water temperature setpoint plus one-
crankcase heaters 8 hours before starting unit to eliminate half the control band plus the startup delta-T before the
refrigerant from the oil. MicroTech® III controller will stage on cooling.)
1. Open all electrical disconnects and check all power • Set the Evap Delta T based on a percent of unit nominal
wiring connections. Start at the power block and check flow indicated in Table 11 on page 24 and the Start
all connections through all components to and including Delta T as a starting point. Delta-T=Tons x 24 / gpm
the compressor terminals. These should be checked • Check the controller setpoints to be sure that factory
again after 3 months of operation and at least yearly defaults are appropriate.
thereafter. • Put both pumpdown switches (PS1 and PS2) to the ON
2. Check all control wiring by pulling on the wire at the position.
spade connections and tighten all screw connections. • Put system switch (S1) to ON position.
Check plug-in relays for proper seating and to insure
retaining clips are installed.
Component Operation
Crankcase Heaters
The scroll compressors are equipped with externally mounted
band heaters located at the oil sump level. The function of
the heater is to keep the temperature in the crankcase high
enough to prevent refrigerant from migrating to the crankcase
and condensing in the oil during off-cycle.
Power must be supplied to the heaters 8 hours before starting
the compressors.
Evaporator
The evaporator is a compact, high efficiency, dual circuit,
brazed plate-to-plate type heat exchanger consisting of parallel
stainless steel plates. The evaporator is protected with an
electric resistance heater and insulated with 3/4” (19mm)
thick closed-cell polyurethane insulation. This combination
provides freeze protection down to -20°F (-29°C) ambient air
temperature. The water side working pressure of the brazed
plate type of evaporator is 653 psig (4502 kPa). Evaporators
are designed and constructed according to, and listed by,
Underwriters Laboratories (UL).
Evaporator
The evaporators are brazed plate design. Other than cleaning
and testing, no service work should be required on the
evaporator.
Compressor Maintenance
The scroll compressors are fully hermetic and require no
maintenance other than checking oil level.
Lubrication
No routine lubrication is required on AGZ units. The fan motor
bearings are permanently lubricated and no further lubrication
is required. Excessive fan motor bearing noise is an indication
of a potential bearing failure.
Cleaning Micro-Channel Aluminum Coils
Maintenance consists primarily of the routine removal of dirt
POE type oil is used for compressor lubrication. Further details
and debris from the outside surface of the fins and repairing
are listed in the Unit Service section on page 86.
any fin damage.
WARNING
POE oil must be handled carefully using proper protective Cleaning ElectroFin® Coated Coils
equipment (gloves, eye protection, etc.) The oil must not The following cleaning procedures are recommended as part
come in contact with certain polymers (e.g. PVC), as it may of the routine maintenance activities for ElectroFin Coated
absorb moisture from this material. Also, do not use oil or Coils. Documented routine cleaning of ElectroFin Coated
refrigerant additives in the system. Coils is required to maintain warranty coverage. The cleaning
procedure can be downloaded from the ElectroFin web site
www.luvata.com/electrofin, click on Procedures for Cleaning.
All-Aluminum Condenser Coils WARNING
The condenser coils are an all-aluminum design including the
Prior to cleaning the unit, turn off and lock out the main
connections, micro-channels, fins (an oven brazing process
power switch to the unit and open all access panels.
brazes the fins to the micro-channel flat tube), and headers
(see “Micro-Channel Coil Cross Section”), which eliminates
the possibility of corrosion normally found between dissimilar Remove Surface Loaded Fibers
metals of standard coils. Surface loaded fibers or dirt should be removed prior to water
rinse to prevent further restriction of airflow. If unable to back
During the condensing process, refrigerant in the coil passes
wash the side of the coil opposite that of the coils entering air
through the micro-channel flat tubes, resulting in higher
side, then surface loaded fibers or dirt should be removed with
efficiency heat transfer from the refrigerant to the airstream. In
a vacuum cleaner. If a vacuum cleaner is not available, a soft
the unlikely occurence of a coil leak, contact Daikin Applied to
non-metallic bristle brush may be used. In either case, the tool
receive a replacement coil module.
should be applied in the direction of the fins. Coil surfaces can
be easily damaged (fin edges bent over) if the tool is applied
across the fins.
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and
dirt into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water Rinse application of this product. As in all surface preparation,
the best work yields the best results.
A monthly clean water rinse is recommended for coils that are
applied in coastal or industrial environments to help to remove 2. Apply CHLOR*RID DTS - Apply CHLOR*RID DTS
chlorides, dirt and debris. An elevated water temperature (not directly onto the substrate. Sufficient product must be
to exceed 130ºF) will reduce surface tension, increasing the applied uniformly across the substrate to thoroughly
ability to remove chlorides and dirt. Pressure washer PSI must wet out surface with no areas missed. This may
not exceed 900 psig and the nozzel should remain at least 1 be accomplished by use of a pump-up sprayer or
foot from the coil to avoid damaging fin edges. conventional spray gun. The method does not matter, as
long as the entire area to be cleaned is wetted. After the
Routine Quarterly Cleaning of ElectroFin substrate has been thoroughly wetted, the salts will be
Coated Coil Surfaces soluble and is now only necessary to rinse them off.
Quarterly cleaning is essential to extend the life of an 3. Rinse - It is highly recommended that a hose be used
ElectroFin Coated Coil and is required to maintain warranty as a pressure washer will damage the fins. The water to
coverage. Coil cleaning shall be part of the unit’s regularly be used for the rinse is recommended to be of potable
scheduled maintenance procedures. Failure to clean an quality, though a lesser quality of water may be used if a
ElectroFin Coated Coil will void the warranty and may result in small amount of CHLOR*RID DTS is added. Check with
reduced efficiency and durability in the environment. CHLOR*RID International, Inc. for recommendations on
lesser quality rinse water.
For routine quarterly cleaning, first clean the coil with an
approved coil cleaner (see approved products list in Table 67). Harsh Chemical and Acid Cleaners
After cleaning the coils with the approved cleaning agent, use
the approved chloride remover to remove soluble salts and Harsh chemicals, household bleach or acid cleaners should
revitalize the unit. not be used to clean outdoor or indoor ElectroFin Coated
Coils. These cleaners can be very difficult to rinse out of the
Recommended Coil Cleaner coil and can accelerate corrosion and attack the ElectroFin
coating. If there is dirt below the surface of the coil, use the
The following cleaning agent, assuming it is used in recommended coil cleaners as described above.
accordance with the manufacturer’s directions on the container
for proper mixing and cleaning, has been approved for use on High Velocity Water or Compressed Air
ElectroFin Coated Coils to remove mold, mildew, dust, soot,
greasy residue, lint and other particulate: High velocity water from a pressure washer or compressed air
should only be used at a very low pressure to prevent fin and/
or coil damages. The force of the water or air jet may bend the
Table 67: ElectroFin Coated Coil Recommended Cleaning
fin edges and increase airside pressure drop. Reduced unit
Agents
performance or nuisance unit shutdowns may occur.
Cleaning Agent Reseller Part Number
Coil to Copper Tubing Connections
Hydro-Balance Corp
Figure 52 shows the aluminum condenser coil connection
Enviro-Coil P.O. Box 730
H-EC01 to the copper tubing in the unit. Because of the low melting
Concentrate Prosper, TX 75078
point of aluminum (1220°F compared to 1984°F for copper),
800-527-5166
this brazed joint is performed with a low temperature brazing
Enviro-Coil process. If brazing the copper to copper connection near the
Home Depot H-EC01
Concentrate aluminum to copper connection, care should be taken to keep
Chlor*Rid Int’l, Inc. temperature at the copper aluminum joint cool to due the fact
Chloride P.O. Box 908 that low temperature brazed is used on that joint.
Chlor*Rid DTS
Remover Chandler, AZ 85244
800-422-3217 CAUTION
Potential equipment damage. If a standard copper brazing
process is performed at this joint, the process will damage
CHLOR*RID DTS™ should be used to remove soluble salts the aluminum connection. If a condenser coil ever needs
from the ElectroFin Coated Coil, but the directions must be to be replaced, the copper aluminum joint repair should
followed closely. This product is not intended for use as a be done with a ProBraze™ repair kit manufactured by
degreaser. Any grease or oil film should first be removed with OmniTechnologies Corporation. A non-corrosive flux must
the approved cleaning agent. also be used. The brazing temperature should be between
1. Remove Barrier - Soluble salts adhere themselves 850°F–900°F. If a coil needs replacing, contact Daikin
to the substrate. For the effective use of this product, Applied for a coil and copper connection assembly.
the product must be able to come in contact with the
salts. These salts may be beneath any soils, grease or
dirt; therefore, these barriers must be removed prior to
Figure 52: Aluminum/Copper Connection any maintenance. The solenoids can, however, require
replacement of the solenoid coil or of the entire valve
assembly.
System Adjustment
To maintain peak performance at full load operation, the
system superheat and liquid subcooling may require
adjustment. Read the following subsections closely to
determine if adjustment is required.
Monthly Annual
Operation Weekly
(Note 1) (Note 2)
General
Complete unit log and review (Note 3) X
Visually inspect unit for loose or damaged components X
Inspect thermal insulation for integrity X
Clean and paint as required X
Electrical
Check terminals for tightness, tighten as necessary X
Clean control panel interior X
Visually inspect components for signs of overheating X
Verify compressor heater operation X
Test and calibrate equipment protection and operating controls X
Megger compressor motor (Note 4) X
Refrigeration
Leak test X
Check sight glasses for clear flow X
Check filter-drier pressure drop (see manual for spec) X
Perform compressor vibration test X
Acid test oil sample X
Condenser (air-cooled)
Clean condenser coils (Note 5) X
Check fan blades for tightness on shaft (Note 6) X
Check fans for loose rivets and cracks X
Check coil fins for damage X
Notes:
1. Monthly operations include all weekly operations.
2. Annual (or spring start-up) operations includes all weekly
and monthly operations.
3. Log readings can be taken daily for a higher level of unit
observation.
4. Never Megger motors while they are in a vacuum to
avoid damage to the motor.
5. Coil cleaning can be required more frequently in areas
with a high level of airborne particles.
6. Be sure fan motors are electrically locked out.
medium size leaks but electronic leak detectors are needed to POE oils and for the refrigerant pressure (R-410A 600psig
locate small leaks. typical).
Charging or check valves should always be used on charging R-410A compressor internal relief is 600-650 psid.
hoses to limit refrigerant loss and prevent frostbite. Ball valve Brazed connections only. No StayBrite or solder connections
type recommended. (solder should never be used with any refrigerant). K or L type
Charge to 80-85% of normal charge before starting the refrigeration tubing only. Use nitrogen purge. Higher R-410A
compressors. pressures and smaller molecule size make workmanship more
critical.
Charging procedure R-410A must be charged from cylinder as a liquid unless entire
The units are factory-charged with R-410A. Use the following cylinder is used. Use a Refrigerant flow restrictor if charging
procedure if recharging in the field is necessary: liquid to suction or to a system at pressure below a saturated
temperature of 32° F.
To prevent fractionalization, liquid must be charged from
the refrigerant cylinder, unless charging the entire cylinder EPA recovery and handling requirements for R-410A are the
contents. same as R-22.
The charge can be added at any load condition between Cooling the recovery cylinder will speed recovery and lessen
25 to 100 percent load per circuit, but at least two fans per stress on recovery equipment.
refrigerant circuit should be operating if possible.
WARNING
Start the system and observe operation.
Service on this equipment is to be performed by qualified
Trim the charge to the recommended liquid line sub-cooling refrigeration personnel familiar with equipment operation,
(approximately 15-20°F typical). maintenance, correct servicing procedures, and the safety
Verify the suction superheat (10 degrees F for EEVs and 10 – hazards inherent in this work. Causes for repeated tripping
12 degrees F for TXVs) at full load conditions. of equipment protection controls must be investigated and
corrected.
Use standard charging procedures (liquid only) to top off the
charge. Disconnect all power before doing any service inside the
unit.
Check the sight glass to be sure there is no refrigerant flashing.
Servicing this equipment must comply with the requirements
With outdoor temperatures above 60°F (15.6°C), all condenser set forth by the EPA in regards to refrigerant reclamation and
fans should be operating and the liquid line temperature venting.
should be within 5°F to 10°F (2.8°C to 5.6°C) of the outdoor
air temperature. At 25-50% load, the liquid line temperature
should be within 5°F (2.8°C) of outdoor air temperature with all
fans on. At 75-100% load the liquid line temperature should be
within 10°F (5.6°C) of outdoor air temperature with all fans on.
It may be necessary to add refrigerant through the compressor
suction. Because the refrigerant leaving the cylinder must be
a liquid, exercise care to avoid damage to the compressor by
using a flow restrictor. A sight glass can be connected between
the charging hose and the compressor. It can be adjusted to
have liquid leave the cylinder and vapor enter the compressor.
Overcharging of refrigerant will raise the compressor discharge
pressure due to filling of the condenser tubes with excess
refrigerant.
Service
With R-410A, fractionalization, if due to leaks and recharge has
a minimal effect on performance or operation.
Special tools will be required due to higher refrigerant
pressures with R-410A. Oil-less/hp recovery units, hp recovery
cylinders (DOT approved w/525# relief), gauge manifold 30”-
250 psi low/0-800 psi high, hoses w/800 psi working & 4,000
psi burst.
All filter driers and replacement components must be rated
Troubleshooting Chart
High Discharge 3. Optional discharge shutoff valve not open 3. Open valve.
Pressure 4. Condenser fan control wiring not correct 4. Correct wiring.
5. Fan not running 5. Check electrical circuit and fan motor.
6. Dirty condenser coil 6. Clean coil.
7. Air recirculation 7. Correct.
1. Rapid load swings 1. Stabilize load.
2. Lack of refrigerant 2. Check for leaks, repair, add charge. Check liquid sight glass.
3. Fouled liquid line filter drier 3. Check pressure drop across filter drier. Replace.
4. Expansion valve malfunctioning 4. Repair or replace and adjust for proper superheat.
Low Suction
5. Condensing temperature too low 5. Check means for regulating condenser temperature.
Pressure
6. Compressors not staging properly 6. See corrective steps - Compressor Staging Intervals Too Low.
7. Insufficient water flow 7. Correct flow.
8. Excess or wrong oil used 8. Recover or change oil
9. Evaporator dirty 9. Back flush or clean chemically.
Compressor Oil 5. Insufficient water flow - Level too high 5. Correct flow, verify superheat.
Level Too High Or 6. Excessive liquid in crankcase - Level too high 6. Check crankcase heater. Check liquid line solenoid valve operation.
Too Low 7. Short cycling 7. Stabilize load or correct control settings for application.
8. HGBP valve oversize or improperly set-up 8. replace or adjust HGBP valve
9. Expansion valve operation or selection 9. Confirm superheat at minimum and maximum load conditions
10. Compressor mechanical issues 10. Replace compressor
11. Wrong oil for application 11. Verify
1. Voltage imbalance or out of range 1. Correct power supply.
Motor Overload
2. Defective or grounded wiring in motor 2. Replace compressor.
Relays or Circuit
3. Loose power wiring or burnt contactors 3. Check all connections and tighten, replace contactors.
Breakers Open
4. High condenser temperature 4. See corrective steps for High Discharge Pressure.
1. Operating beyond design conditions 1. Correct so conditions are within allowable limits.
2. Discharge valve not open 2. Open valve.
Compressor Thermal
3. Short cycling 3. Stabilize load or correct control settings for application
Protection Switch
4. Voltage range or imbalance 4. Check and correct.
Open
5. High superheat 5. Adjust to correct superheat.
6. Compressor mechanical failure 6. Replace compressor.
Pre Start-Up Checklist, All NO checks require an explanation under "Description". Please check yes or no.
YES NO
A. Is the unit free of visible shipping damage, corrosion or paint problems?
C. Does the unit meet all location, installation and service clearances per IM Bulletin?
E. Are all set screws on all pulleys, bearings, and fans tight?
I. Has a fused disconnect and fuses or breaker been sized per product manual and installed per local code?
P. Has the chill water circuit been cleaned, flushed, and water treatment confirmed?
Q. Does the chiller and condenser water piping conform to the IM Bulletin?
Description:
MICROTECH STATUS CHECK-Each Reading Must be Verified with Field Provided Instruments of Known Accuracy?
MicroTech Verification
C. Water Temperatures: Leaving Evaporator ……………………………… °F (°C) °F (°C)
Entering Evaporator ……………………………… °F (°C) °F (°C)
Entering Condenser ……………………………… °F (°C) °F (°C)
Leaving Condenser ……………………………… °F (°C) °F (°C)
D. Circuit #1 Refrigerant Pressures:
Evaporator psig (kPa) °F (°C) psig
Minimum Condensor Pressure psig (kPa)
Maximum Condenser Pressure psig (kPa)
E. Circuit #2 Refrigerant Pressures:
Evaporator psig (kPa) °F (°C) psig
Minimum Condensor Pressure psig (kPa)
Maximum Condenser Pressure psig (kPa)
F. Circuit #1 Refrigerant Temperatures:
Saturated Evaporator Temperature …………………… °F (°C) °F (°C)
Suction Line Temperature ………………………………. °F (°C) °F (°C)
Suction Superheat ………………………………………. °F (°C) °F (°C)
Saturated Condenser Temperature …………………… °F (°C) °F (°C)
Liquid Line Temperature ………………………………. °F (°C) °F (°C)
Subcooling ………………………………………………. °F (°C) °F (°C)
G. Circuit #2 Refrigerant Temperatures:
Saturated Evaporator Temperature …………………… °F (°C) °F (°C)
Suction Line Temperature ………………………………. °F (°C) °F (°C)
Suction Superheat …………………………………….... °F (°C) °F (°C)
Saturated Condenser Temperature …………………… °F (°C) °F (°C)
Liquid Line Temperature ………………………………. °F (°C) °F (°C)
Subcooling ………………………………………………. °F (°C) °F (°C)
NON-MICROTECH READINGS
IOM
76 1206-3 • TRAILBLAZER MODEL AGZ CHILLERS
™ 92 www.DaikinApplied.com
Form # SF-99007 • Part #: 041541502-D
Warranty Registration Form (Scroll)
VII. FOR HEAT RECOVERY CHILLERS ONLY (Must Be Taken At Full Load)
A. Place Unit in heat recovery mode.
B. Waterside Pressure Drop: psig (kPa) Ft. (kPa) gpm (lps)
C. Waterside Temperatures: Inlet Outlet
D. Head Pressure: Circuit #1 psig (kPa) Circuit #2: psig (kPa)
E. Suction Pressure: Circuit #1 psig (kPa) Circuit #2: psig (kPa)
F. Compressor Current Per Phase
Compressor #1 AMPS AMPS AMPS
Compressor #2 AMPS AMPS AMPS
Compressor #3 AMPS AMPS AMPS
Compressor #4 AMPS AMPS AMPS
VIII. GENERAL
YES NO
A. Are all control lines secure to prevent excess vibration and wear? ……………………………………….
B. Are all gauges shut off, valve caps, and packings tight after startup? ……………………………………
Performed By: Title:
Company Name:
Address:
City/State/Zip Code: Telephone:
Modem Number:
Signature: Date:
Contractor's Signature
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.