Daikin-Applied-Agz-E Da 05062015 LR

Download as pdf or txt
Download as pdf or txt
You are on page 1of 96

Installation, Operation, IOM 1206-3

and Maintenance Manual Group: Chiller


Part Number: IOM1206-3
Date: May 2015

Trailblazer™
Air-Cooled Scroll Chillers
Model AGZ, E Vintage
30 to 180 Tons (100 to 630 kW)
HFC-410a Refrigerant
50/60 Hz
Table of Contents
Table of Contents

Table of Contents

Installation and Application Information . . . . . . . . . . 3 Circuit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59


Dimensions and Weights - Packaged Units . . . . . . 14 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Using the Controller . . . . . . . . . . . . . . . . . . . . . . . . . 69
Isolator Information . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Optional Low Ambient Fan VFD . . . . . . . . . . . . . . . . 72
Presure Drop Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Startup and Shut-down Procedures . . . . . . . . . . . . 78
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Component Operation . . . . . . . . . . . . . . . . . . . . . . . . 80
Unit Controller Operation . . . . . . . . . . . . . . . . . . . . . 33 Unit Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . 42 Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . 88
Unit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Warranty Registration Form (Scroll) . . . . . . . . . . . . 90

Manufactured in an ISO 9001 & ISO 14001 certified facility

©2015 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 2 www.DaikinApplied.com


Pre-Start Checklist – Scroll Compressor Chillers
Must be completed, signed and provided to Daikin Applied at least 2 weeks prior to requested start date.
Job Name
Installation Location
Customer Order Number
Model Number(s)
G.O. Number(s)
Chilled Water Yes No N/A Initials
Piping Complete
Water strainer installed on evaporator entering chilled water piping per IM
Water System filled, flushed and vented
Pumps installed and operational (rotation checked, strainers cleaned)
Controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)
Water system operated and tested; flow meets unit design requirements
Flow switch installed and wired
Vent installed on evaporator
Glycol at design %
Electrical Yes No N/A Initials
Building controls operational
*Power leads connected to power block or optional disconnect
Power leads have been checked for proper phasing and voltage
All interlock wiring complete and compliant with Daikin specifications
Power applied at least 24 hours before startup
Oil heaters energized at least 24 hours before startup
Chiller components (EXV Sensors Transducers) installed and wired properly.
*Wiring complies with National Electrical Code and local codes (See Notes)
Remote EXV wired with shielded cable
Miscellaneous Yes No N/A Initials
Unit control switches all off
Remote Evaporator /Condenser Piping factory reviewed
All refrigerant components/piping leak tested, evacuated and charged
Thermometers, wells, gauges, control, etc., installed
Minimum system load of 80% capacity available for testing/adjusting controls
Document Attached: Technical Breakdown from Selection Software
Document Attached: Final Order Acknowledgement
Document Attached: Remote piping approval
Cut Here 

WGZ Units Cooling tower filled, wired and test operated


WGZ Units Water strainer installed on condenser water inlet piping per IM
Notes: The most common problems delaying start-up and affecting unit reliability are:
1. Field installed compressor motor power supply leads too small. Questions: Contact the local Daikin sales representative*. State size, number and
type of conductors and conduits installed:
a. From Power supply to chiller
* Refer to NEC Article 430-22 (a)
2. Remote Evaporator piping incomplete or incorrect. Provide approved piping diagrams.
3. Items on this list incorrectly acknowledged may result in delayed start and extra expenses incurred for return trips.
Contractor Representative Daikin Applied Sales Representative
Signed: Signed:
Name: Name:
Company: Company:
Date: Date:
Phone/Email: Phone/Email:

©2014 Daikin Applied Form P/N 10OCT2014


Installation and Application Information

General Description Installation and Application Information

Daikin Trailblazer™ air-cooled water chillers are complete, The electrical control center includes all equipment protection
self-contained, automatic chiller units designed for outdoor and operating controls necessary for dependable automatic
installation. Packaged units are completely assembled, factory operation.
wired, charged, and tested.

NOMENCLATURE

A G Z XXX E H
Air-Cooled Application
H = Standard Packaged
Global Design
Scroll Compressor Design Vintage

Nominal Tons

WARNING Figure 1: Suggested Pushing Arrangment


Blocking is required
Installation is to be performed by qualified personnel who are across full width
familiar with local codes and regulations.

CAUTION
Sharp edges on unit and coil surfaces are a potential hazard
to personal safety. Avoid contact with them.

Additional Manual
This manual covers the installation, of dual circuit, AGZ-EH
packaged, scroll compressor chillers using R-410A.
Information for units with either the pump package or remote
evaporator options can be found at www.DaikinApplied.com. Figure 2: Required Lifting Arrangement

Inspection Number of fans may


vary from this diagram.
Check all items carefully against the bill of lading. Inspect SPREADER BARS The lifting method will
REQUIRED remain the same.
all units for damage upon arrival. Report shipping damage (USE CAUTION)
and file a claim with the carrier. Check the unit nameplate
before unloading, making certain it agrees with the power
supply available. Daikin Applied is not responsible for physical
damage after the unit leaves the factory.

Handling
Be careful to avoid rough handling of the unit. Do not push
or pull the unit from anything other than the base. Block the
pushing vehicle away from the unit to prevent damage to the
sheet metal cabinet and end frame (see Figure 1).
To lift the unit, 2-1/2” (64mm) diameter lifting eyes are provided
MUST USE THESE
on the base of the unit. Arrange spreader bars and cables to RIGGING HOLES
(BE AWARE OF
prevent damage to the condenser coils or cabinet (see Figure CONTROL BOX
2). LOCATION)

CAUTION DANGER
All lifting locations must be used to prevent damage to unit. Do not stand beneath the unit while it is being lifted or
installed.

www.DaikinApplied.com 3 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Installation and Application Information

Operating and Standby Limits


Table 1: Operating Limits

Maximum standby ambient temperature 131°F (55°C)


Maximum operating ambient temperature 105°F (41°C)
-with optional high ambient package (see information under High Ambient Operation) 125°F (52°C)
Minimum operating ambient temperature (standard control) 32°F (0°C)
Minimum operating ambient temperature (with optional low-ambient control) -10°F (-23°C)
Leaving chilled water temperature 40°F to 65°F (2°C to 18°C)
Leaving chilled fluid temperatures (with anti-freeze) - Note that in cases of high ambient
temperature, the lowest leaving water temperature settings may be outside of the chiller 15°F to 65°F (-9°C to 18°C)
operating envelope; consult Daikin Tools to ensure chiller is capable of the required lift.
Operating chilled water delta-T range 6°F to 16°F (3.3°C to 8.9°C)
Maximum evaporator operating inlet fluid temperature 81°F (27°C)
Maximum evaporator non-operating inlet fluid temperature 100°F (38°C)

Figure 3: Service Clearance


Unit Placement
Trailblazer™ units are for outdoor applications and can be
mounted either on a roof or at ground level. For roof mounted Minimum = 4 ft (1.2 m)
applications, install the unit on a steel channel or I-beam 75-180 Ton Models: 8ft (2.4 m) recommended on one side

frame to support the unit above the roof. For ground level
applications, install the unit on a substantial base that will not Minimum = 7.5 ft (2.3 m)
settle. Use a one-piece concrete slab with footings extended for models 030-070 Minimum = 4 ft
with Microchannel Coils

Control Panel
below the frost line. Be sure the foundation is level within 0.5” (1.2 m)

(13 mm) over its length and width. The foundation must be
Minimum = 4 ft (1.2 m)
strong enough to support the unit weight - see “Dimensions for all other models
and Weights - Packaged Units” on page 14.

Service Clearance Minimum = 4 ft (1.2 m)

Sides
• 30-70 Ton Models: Minimum of 4 feet (1.2 meters)
• 75-180 Ton Models: It is highly recommended to Spacing Requirements
provide a minimum of 8 feet (2.4 meters) on one side to Sufficient clearance must be maintained between the unit
allow for coil replacement. Coils can be removed from and adjacent walls or other units to allow the required unit
the top, allowing a minimum of 4 feet (1.2 meters) of air flow to reach the coils. Failure to do so will result in a
side clearance; however, the unit performance may be capacity reduction and an increase in power consumption. No
derated. obstructions are allowed above the unit at any height.
Control Panel End Graphs on the following pages give the minimum clearance for
• All Models: Minimum of 4 feet (1.2 meters) different types of installations and also capacity reduction and
Opposite Control Panel End power increase if closer spacing is used.

• 30-70 Ton Models with Microchannel Coils: Minimum


of 7.5 feet (2.3 meters)
• 75-180 Ton Models: Minimum of 4 feet (1.2 meters)

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 4 www.DaikinApplied.com


Installation and Application Information

Case 1: Building or Wall on One Side of Unit Case 2: Two Units, Side-by-Side
For models AGZ030-100E, maintain a 4 feet minimum from a For all models, there must be a minimum of 4 feet between
wall of any height. two units placed side-by-side; however, performance may be
affected at this distance. The Case 2 figures show performance
For models AGZ110-180E, maintain a 6 feet minimum from a
adjustments as the distance between two units increases.
wall of any height.

Figure 5: Two Units, Side-by-Side


Figure 4: Building or Wall on One Side of Unit

Height Distance
of Between
Wall Wall
and
Unit
Figure 6: Case 2 - Full Load Capacity Reduction
Full Load Capacity Reduction
3.0

2.5
% Capacity Reduction

2.0

1.5

1.0

0.5

0.0
4 5 6 8
Distance Between Units (ft)

AGZ030-070E AGZ075-100E AGZ110-130E AGZ140-180E

Figure 7: Case 2 - Power Increase


Power Increase
4.0

3.5

3.0
% Power Increase

2.5

2.0

1.5

1.0

0.5

0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-070E AGZ075-100E AGZ110-130E AGZ140-180E

www.DaikinApplied.com 5 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Installation and Application Information

Case 3: Three or More Units, Side-by-Side Case 4: Open Screening Walls


For all models, there must be a minimum of 4 feet between any Decorative screening walls are often used to help conceal a
two units placed side-by-side; however, performance may be unit either on grade or on a rooftop. When possible, design
affected at this distance. Figure 9 and Figure 10 depict Case these walls such that the combination of their open area and
3 performance adjustments as the distance between two units distance from the unit do not require performance adjustment.
increases. It is assumed that the wall height is equal to or less than the
NOTE: Data in Figure 9 and Figure 10 is for the middle unit unit height when mounted on its base support. If the wall height
with a unit on each side. See Case 2 adjustment is greater than the unit height, see Case 5: Pit Installation.
factors for the two outside units. The distance from the sides of the unit to the side walls must
be sufficient for service, such as opening control panel doors.
Figure 8: Three or More Units, Side-by-Side For uneven wall spacing, the distance from the unit to each
wall can be averaged providing no distance is less than 4 feet.
Values are based on walls on all four-sides.

Figure 11: Case 4 Adjustment Factor


Wall Free Area vs. Distance
8.0

Distance from Wall to Unit (ft)


7.0

6.0

5.0

Figure 9: Case 3 - Full Load Capacity Reduction 4.0

Full Load Capacity Reduction


6.0 3.0
0 10 20 30 40 50
% Open Wall Area
5.0
AGZ030-070E AGZ075-100E AGZ110-130E AGZ140-180E
% Capacity Reduction

4.0

3.0

2.0
Case 5: Pit Installation
Pit installations can cause operating problems resulting from
1.0 air recirculation and restriction and require care that sufficient
air clearance is provided, safety requirements are met and
0.0
4 5 6 8 service access is provided. Pit covers must have abundant
Distance Between Units open area at least equal to the chiller footprint. A solid wall
AGZ030-035E AGZ040-070E AGZ075-100E surrounding a unit is substantially a pit and this data should be
AGZ0110-130E AGZ140-180E
used.
Steel grating is sometimes used to cover a pit to prevent
Figure 10: Case 3 - Power Increase accidental falls or trips into the pit. The grating material
and installation design must be strong enough to prevent
Power Increase such accidents, yet provide abundant open area to avoid
8.0
recirculation problems. Have any pit installation reviewed by
7.0 the Daikin Applied sales representative prior to installation to
% Power Increase

6.0 ensure it has sufficient air-flow characteristics and approved by


5.0 the installation design engineer to avoid risk of accident.
4.0

3.0

2.0

1.0

0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-035E AGZ040-070E AGZ075-100E
AGZ0110-130E AGZ140-180E

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 6 www.DaikinApplied.com


Installation and Application Information

Figure 12: Case 5 - Pit Installation Models AGZ075-130E:


The Case 5 figures for models AGZ075-130E show adjustment
factors for pit/wall heights of 5 feet, 6 feet, and 8 feet.

Figure 15: Case 5 - Full Load Capacity Reduction


(AGZ075-130E)

Full Load Capacity Reduction (AGZ075-130E)


6.0

5.0

% Capacity Reduction
4.0

3.0

2.0

1.0
Models AGZ030-070E:
0.0
The Case 5 figures for models AGZ030-070E show adjustment 0 8 10 12 13 14
factors for pit/wall heights of 4 feet, 5 feet, and 6 feet. Depth of Pit / Wall Height ft)
Distance = 5 f t Distance = 6 f t Distance = 8 f t

Figure 13: Case 5 - Full Load Capacity Reduction


(AGZ030E-070E) Figure 16: Case 5 - Power Increase (AGZ075-130E)
Full Load Capacity Reduction (AGZ030-070E) Power Increase (AGZ075-130E)
6.0 9.0

8.0
5.0
7.0
% Capacity Reduction

% Power Increase

4.0
6.0

3.0 5.0

4.0
2.0
3.0
1.0
2.0

0.0 1.0
0 8 10 12 13 14
0.0
Depth of Pit / Wall Height (ft) 0 8 10 12 13 14
Distance = 4 f t Distance = 5 f t Distance = 6 f t Depth of Pit / Wall Height (ft)
Distance = 5 f t Distance = 6 f t Distance = 8 f t

Figure 14: Case 5 - Power Increase (AGZ030-070E)


Power Increase (AGZ030-070E)
9.0

8.0

7.0

6.0
% Power Increase

5.0

4.0

3.0

2.0

1.0

0.0
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Distance = 4 f t Distance = 5 f t Distance = 6 f t

www.DaikinApplied.com 7 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Installation and Application Information

Models AGZ140-180E: Chilled Water Piping


The Case 5 figures for models AGZ140-180E show adjustment
factors for pit/wall heights of 6 feet, 8 feet, and 10 feet. CAUTION
To prevent damage to the evaporator and potential chiller
Figure 17: Case 5 - Full Load Capacity Reduction failure, a supply strainer is required in the inlet water piping
(AGZ140-180E) which connects to this evaporator. This strainer must be
installed prior to operation of the chilled liquid pumps.
Full Load Capacity Reduction (AGZ140-180E)
6.0 Field installed water piping to the chiller must include:

5.0
• A cleanable strainer installed at the water inlet to the
evaporator to remove debris and impurities before they
% Capacity Reduction

4.0 reach the evaporator. Install cleanable strainer within


5 feet (1500 mm) of pipe length from the evaporator
3.0
inlet connection and downstream of any welded
2.0 connections (no welded connections between strainer
and evaporator).
1.0
• AGZ-E models 030-180 require a strainer with
0.0 perforations no larger than 0.062” diameter. See the Inlet
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Strainer Guidelines on page 9 for more information.
Distance = 6 f t Distance = 8 f t Distance = 10 f t
• A water flow switch must be installed in the horizontal
piping of the supply (evaporator outlet) water line to avoid
evaporator freeze-up under low or no flow conditions. The
Figure 18: Case 5 - Power Increase (AGZ140-180E) flow switch may be ordered as a factory-installed option,
a field-installed kit, or may be supplied and installed in the
Power Increase (AGZ140-180E) field. See page 11 for more information.
9.0

8.0
• Piping for units with brazed-plate evaporators must have
a drain and vent connection provided in the bottom of
7.0
the lower connection pipe and to the top of the upper
% Power Increase

6.0 connection pipe respectively, see Figure 19. These


5.0 evaporators do not have drain or vent connections due to
4.0 their construction.
3.0 • Purge air from water system before unit start-up to
2.0 provide adequate flow through the evaporator.
1.0 • Adequate piping support, independent from the unit,
0.0
to eliminate weight and strain on the fittings and
0 8 10 12 13 14 connections.
Depth of Pit / Wall Height (ft)
It is recommended that the field installed water piping to the
Distance = 6 f t Distance = 8 f t Distance = 10 f t
chiller include:
• Thermometers at inlet and outlet evaporator connections.
• Water pressure gauge connection taps and gauges at
the inlet and outlet connections of the evaporator for
measuring water pressure drop.
• Shutoff valves are necessary to isolate the unit from the
piping during unit servicing.
• Minimum bends and changes in elevation to minimize
pressure drop.
• An expansion tank or regulating valve to maintain
adequate water pressure.
• Vibration eliminators in both the supply and return water
lines to reduce transmissions to the building.
• Flush the system water piping thoroughly before making
connections to the unit evaporator.
• Piping insulation, including a vapor barrier, helps prevent
condensation and reduces heat loss.
• Regular water analysis and chemical water treatment
for the evaporator loop is recommended immediately at

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 8 www.DaikinApplied.com


Installation and Application Information

equipment start-up.

Figure 19: Typical Piping, Brazed-Plate Evaporator Air


Vent
Strainer

Inlet
Isolation
P Vibration
Valves
Eliminators

Outlet
Flow
Switch
Drain

Inlet Strainer Guidelines Figure 20: Factory Installed Strainer


An inlet water strainer kit must be installed in the chilled water
piping before the evaporator inlet. Several paths are available
to meet this requirement:
1. A factory installed option is available for model sizes 030
to 180.
2. A field-installed kit shipped-loose with the unit is available
for all unit sizes and consists of:
• Y-type area strainer with 304 stainless steel perforated
basket, Victaulic pipe connections and strainer cap
(a strainer with perforations no larger than 0.062”
diameter for AGZ-E models 030-180).
• Extension pipe with two Schrader fittings that can be
used for a pressure gauge and thermal dispersion flow Table 2: Strainer Data
switch. The pipe provides sufficient clearance from the
evaporator for strainer basket removal. Trailblazer™ Model Strainer Size Strainer Weight
in (mm) lbs (kg)
• ½-inch blowdown valve
030-070E 2.5 (64) 18 (8.2)
• Two grooved clamps
075-130E 3.0 (76) 23 (10.4)
Both are sized per Table 2 and with the pressure drop shown in
140-180E 4.0 (102) 42 (19.1)
the Strainer Pressure Drop graph. Connection sizes are given
in the Dimensions and Weights section beginning on page
14. Figure 21: Strainer Pressure Drop
100.0
3. A field-supplied strainer that meets specification and
installation requirements of this manual.
Pressure Drop ( ft)

10.0

1.0

0.1
10.0 100.0 1000.0

Flow Rate (gpm)


2.5 in 3.0 in 4.0 in

www.DaikinApplied.com 9 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Installation and Application Information

Water Flow Limitations helps protect the evaporator down to -20°F (-29°C) ambient
air temperature. The evaporator heater cable is factory wired
Constant Evaporator Flow to the 115 volt control circuit transformer in the control box.
A 115V power source for the heater and controls may also
The evaporator flow rates and pressure drops shown on page be supplied from a separate power feed to maximize unit
24 are for full load design purposes. The maximum flow protection if desired. Refer to the field wiring diagram on page
rate and pressure drop are based on a 6°F temperature drop. 26 for additional information on supplying a separate 115V
Avoid higher flow rates with lower temperature drops to prevent power feed.
potential control problems resulting from a very small control
band and limited start up/shut off temperature changes. Flow Operation of the heaters is automatic through the ambient
rates above the maximum values will result in unacceptable sensing thermostat that energizes the evaporator heaters for
pressure drops and can cause excessive erosion, potentially protection against freeze-up. Unless the evaporator is drained
leading to failure. in the winter or contains an adequate concentration of anti-
freeze, the disconnect switch to the evaporator heater must not
The minimum flow and pressure drop is based on a full load be open.
evaporator temperature drop of 16°F. Evaporator flow rates
below the minimum values can result in laminar flow causing Although the evaporator is equipped with freeze protection,
freeze-up problems, scaling and poor control. it does not protect water piping external to the unit or the
evaporator itself if there is a power failure or heater burnout, or
Variable Evaporator Flow if the chiller is unable to control the chilled water pumps. Use
one of the following recommendations for additional freeze
Reducing evaporator flow in proportion to load can reduce protection:
system power consumption. The rate of flow change should be
a maximum of 10 percent of the flow per minute. For example, 1. If the unit will not be operated during the winter, drain the
if the maximum design flow is 200 gpm and it will be reduced to evaporator and chilled water piping and flush with glycol.
a flow of 140 gpm, the change in flow is 60 gpm. Ten percent of 2. Add a glycol solution to the chilled water system. Burst
200 gpm equals 20 gpm change per minute, or a minimum of protection should be approximately 10°F below minimum
three minutes to go from maximum to desired flow. The water design ambient temperature.
flow through the evaporator must remain between the minimum
3. Insulate the exposed piping.
and maximum values listed in Table 11 on page 24. If flow
drops below the minimum allowable, large reductions in heat 4. Add thermostatically controlled heat by wrapping the
transfer can occur. If the flow exceeds the maximum rate, lines with heat tape.
excessive pressure drop and tube erosion can occur. 5. When glycol is added to the water system for freeze
protection, the refrigerant suction pressure will be lower,
System Water Volume Considerations cooling performance less, and water side pressure drop
All chilled water systems need adequate time to recognize greater. If the percentage of glycol is high, or if propylene
a load change, respond to the change and stabilize to avoid is used instead of ethylene glycol, the added pressure
undesirable short cycling of the compressors or loss of drop and loss of performance could be substantial. When
temperature control. In air conditioning systems, the potential Glycol or Ice are selected as Unit Mode, the MicroTech III
for short cycling usually exists when the building load falls control will automatically reset the available range for the
below the minimum chiller plant capacity or on close-coupled Leaving Water Temperature, Freezestat and Evaporator
systems with very small water volumes. Some of the things Pressure settings.
the designer should consider when looking at water volume
are the minimum cooling load, the minimum chiller plant Chilled Water Pump
capacity during the low load period and the desired cycle time It is important that the chilled water pumps be wired to, and
for the compressors. Assuming that there are no sudden load controlled by, the chiller’s microprocessor. When equipped
changes and that the chiller plant has reasonable turndown, with optional dual pump output, the chiller controller has the
a rule of thumb of “gallons of water volume equal to two to capability to selectively send the signal to a pump relay (by
three times the chilled water gpm flow rate” is often used. A others) to start pump A or B or automatically alternate pump
storage tank may have to be added to the system to reach the selection and also has standby operation capability. The
recommended system volume. controller will energize the pump whenever at least one circuit
BAS should enable chiller only when there is a cooling on the chiller is enabled to run, whether there is a call for
demand. cooling or not. This helps ensure proper unit start-up sequence.
he pump will also be turned on when the water temperature
Evaporator Freeze Protection goes below the Freeze Setpoint for longer than a specified time
to help prevent evaporator freeze-up. Connection points are
Evaporator freeze-up can be a concern in the application of shown in the Field Wiring Diagram beginning on page 26.
air-cooled water chillers in areas experiencing below freezing
temperatures. To protect against freeze-up, insulation and an
electric heater are furnished with the evaporator. Models 030
through 180 have an external plate heater and thermostat. This

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 10 www.DaikinApplied.com


Installation and Application Information

CAUTION Glycol Solutions


Adding glycol or draining the system is the recommended The use of a glycol/water mixture in the evaporator to prevent
method of freeze protection. If the chiller does not have freezing will reduce system capacity and efficiency, as well
the ability to control the pumps and the water system is as increase pressure drop. The system capacity, required
not drained in temperatures below freezing, catastrophic glycol solution flow rate, and pressure drop with glycol may be
evaporator failure may occur. calculated using the following formulas and tables.
Glycol Flow Rate = Capacity Tons X Flow Correction Factor
(gpm) 0.00429 x ΔT
Failure to allow pump control by the chiller may cause the
following problems: 1. Capacity - Multiply the capacity based on water by the
Capacity correction factor from Table 3 or Table 4.
1. If any device other than the chiller attempts to start the
chiller without first starting the pump, the chiller will lock 2. Flow - Multiply the water evaporator flow by the Flow
out on the No Flow alarm and require manual reset. correction factor from Table 3 or Table 4 to determine
the increased evaporator flow due to glycol. If the flow
2. If the chiller evaporator water temperature drops below
is unknown, it can be calculated from the following
the “Freeze setpoint” the chiller will attempt to start the
equation:
water pumps to avoid evaporator freeze. If the chiller
does not have the ability to start the pumps, the chiller 3. Pressure drop - Multiply the water pressure drop from
will alarm due to lack of water flow. Table 11 by Pressure Drop correction factor from Table
3 or Table 4. High concentrations of propylene glycol at
3. If the chiller does not have the ability to control the
low temperatures may cause unacceptably high pressure
pumps and the water system is not to be drained in
drops.
temperatures below freezing, the chiller may be subject
to catastrophic evaporator failure due to freezing. The 4. Power - Multiply the water system power by Power
freeze rating of the evaporator is based on the plate correction factor from Table 3 or Table 4.
heater and pump operation. The plate heater itself Test coolant with a clean, accurate glycol solution hydrometer
may not be able to properly protect the evaporator from (similar to that found in service stations) or refractto determine
freezing without circulation of water. the freezing point. Obtain percent glycol from the freezing
point table below. It is recommended that a minimum of 25%
Flow Switch solution by weight be used for protection against corrosion or
All chillers require a chilled water flow switch to check that that additional compatible inhibitors be added. Concentrations
there is adequate water flow through the evaporator ant to shut above 35% do not provide any additional burst protection and
the unit down if there isn’t. There are two options for meeting should be carefully considered before using.
this requirement. Reset the freezestat setting to 6 degrees F (3.3 degrees C)
1. A factory-mounted thermal dispersion flow switch. below the leaving chilled water setpoint temperature after the
glycol percentage is verified safe for the application.
2. A “paddle” type flow switch is available from Daikin
Applied for field mounting and wiring. Wire from switch
terminals Y and R to the unit control panel terminals
CAUTION
shown on the field wiring diagrams, page 26 and page
27. Mount the flow switch in the leaving water line to Do not use an automotive-grade antifreeze. Industrial
shut down the unit when water flow is interrupted. A flow grade glycols must be used. Automotive antifreeze contains
switch is an equipment protection control and should inhibitors which will cause plating on the copper tubes within
never be used to cycle a unit. the chiller evaporator. The type and handling of glycol used
must be consistent with local codes.
Installation should be per manufacturer’s instructions included
with the switch. Flow switches should be calibrated to shut off
the unit when operated below the minimum listed flow rate for
the unit as listed on page 18.
There is also a set of normally closed contacts on the switch
that can be used for an indicator light or an alarm to indicate
when a “no flow” condition exists. Freeze protect any flow
switch that is installed outdoors. Differential pressure switches
are not recommended for outdoor installation. They can freeze
and not indicate a no-flow conditions.

www.DaikinApplied.com 11 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Installation and Application Information

Table 3: Ethylene Glycol Factors Condenser Coil Options and Coating


E.G. Freeze Point Considerations
Cap Power Flow PD
% °F °C The standard coils on the Trailblazer™ chiller are an all
10 26 -3.3 0.998 0.998 1.036 1.097 aluminum alloy microchannel design with a series of flat
tubes containing multiple, parallel flow microchannels layered
20 18 -7.8 0.993 0.997 1.060 1.226 between the refrigerant manifolds. The microchannel coils are
30 7 -13.9 0.987 0.995 1.092 1.369 designed to withstand 1000+ hour acidified synthetic sea water
40 -7 -21.7 0.980 0.992 1.132 1.557 fog (SWAAT) test (ASTM G85-02) at 120°F (49°C) with 0% fin
loss and develop no leaks.
50 -28 -33.3 0.973 0.991 1.182 1.791
Should the standard microchannel coil not meet the corrosion
requirements for the application, additional coil options are
available.
Table 4: Propylene Glycol Factors
Aluminum fin/copper tube coils consist of 3/8 inch (10 mm)
P.G. Freeze Point seamless copper tubes mechanically bonded into plate-type
Cap Power Flow PD aluminum fins. The fins have full drawn collars to completely
% °F °C
cover the tubes. The aluminum fin/copper tube option is best
10 26 -3.3 0.995 0.997 1.016 1.100 suited for non-corrosive environments, and can be repaired
20 19 -7.2 0.987 0.995 1.032 1.211 onsite. This option is only available for models AGZ030-070E.
30 9 -12.8 0.978 0.992 1.057 1.380
Figure 22: Aluminum Fin/Copper Tube Coils
40 -5 -20.6 0.964 0.987 1.092 1.703
50 -27 -32.8 0.952 0.983 1.140 2.251

Low Ambient Operation


Compressor staging is adaptively determined by system load,
ambient air temperature, and other inputs to the MicroTech® III
control. The standard minimum ambient temperature is 32°F
(0°C). A low ambient option with fan VFD allows operation
down to -10°F (-23°C). The minimum ambient temperature
is based on still conditions where the wind is not greater
than 5 mph. Greater wind velocities will result in reduced
discharge pressure, increasing the minimum operating
ambient temperature. Field installed louvers are available and
recommended to help allow the chiller to operate effectively
down to the ambient temperature for which it was designed.

High Ambient Operation


Trailblazer™ units for high ambient operation (105°F to 125°F,
40°C to 52°C) require the addition of the optional high ambient
package that includes a small fan with a filter in the air intake
to cool the control panel.
All units with the optional VFD low ambient fan control
automatically include the high ambient option.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 12 www.DaikinApplied.com


Installation and Application Information

BlackFin™ coils include aluminum fins pre-coated with a option is not well suited for industrial or chemical atmospheric
durable phenolic epoxy coating. In addition to providing a contamination. This option is only available for models
durable coating on the fin material, the BlackFin™ coils provide AGZ030-070E.
and epoxy barrier between the aluminum fin stock and the ElectroFin® coil coating is a water-based extremely flexible
copper tube, to prevent the galvanic corrosion that can occur and durable epoxy polymer coating uniformly applied to all
between the dissimilar metals. This option will provide a 1000+ coil surfaces through a multi-step, submerged electrostatic
hour salt spray rating per ASTM B117-90. The BlackFin™ coating process. ElectroFin® condenser coils provide a 5000+
option provides enhanced protection in mildly corrosive hour salt spray resistance per ASTM B117-90, applied to both
environments. This option is only available for models AGZ030- the coil and the coil frames. The ElectroFin® coated coils also
070E. receive a UV-resistant urethane top-coat to provide superior
Copper-fin coils consist of 3/8 inch (10 mm) seamless copper resistance to degradation from direct sunlight. This coil coating
tubes mechanically bonded into plate-type copper fins. The fins option provides the best overall protection against corrosive
have full drawn collars to completely cover the tubes. Since marine, industrial or combined atmospheric contamination.
the fin and the tube materials are similar, the opportunity for This coating option may be applied to any of the untreated coil
galvanic corrosion is eliminated. The copper fin/copper tube options offered, to provide excellent longevity and resistance to
option may be used in marine environments; however this corrosion.

Table 5: Coil/Coating Selection Matrix


Coil Option Non-Corrosive1 Unpolluted Marine2 Industrial3 Combined Marine-Industrial4
Standard Microchannel +++ - - -
Aluminum Fin/Copper Tube5 +++ - - -
Copper Fin/Copper Tube5 +++ +++ - -
BlackFin™5 +++ + + -
ElectroFin® +++ +++ +++ ++

NOTE:
1. Non-corrosive environments may be estimated by the appearance of existing equipment in the immediate area where the
chiller is to be placed.
2. Marine environments should take into consideration proximity to the shore as well as prevailing wind direction.
3. Industrial contaminants may be general or localized, based on the immediate source of contamination (i.e. diesel fumes due
to proximity to a loading dock).
4. Combined marine-industrial are influenced by proximity to shore, prevailing winds, general and local sources of
contamination.
5. Available for models AGZ030-070E only.

www.DaikinApplied.com 13 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE
M3 M1 334547101 0B
337 1721 337 AGZ-E, 4 FANS
13.3 L3 67.8 L1 13.3

NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.


MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
52 SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
COMPRESSORS 2.0
CIRCUIT #2 COMPRESSORS
CIRCUIT #1
PACKAGE UNITS WITH MICROCHANNEL COILS
TOP VIEW WITH CG LOCATION, IN (MM)
COILS AND UNIT MODEL
X Y Z
FANS REMOVED
AGZ030E 38.9 (988) 44.5 (1130) 40.9 (1039)
AGZ035E 39.7 (1008) 45.5 (1156) 38.1 (968)
Figure 23: AGZ030E - AGZ035E

EVAP. DIMENSIONS IN (MM) CONNECTION SIZE


UNIT MODEL
A B (VICTAULIC)
19
AGZ030E 24.2 (615) 2.9 (74) 2.5 (64)
.750 52 AGZ035E 23.5 (597) 2.2 (56) 2.5 (64)
QTY. 4 2.0

209
L4 L2 1822
8.2
M4 M2 71.8
REF.
BLANK PANELS ARE
USED ON UNIT SIDES. CONTROL

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


SLOPED 50" COILS BOX
USED ON INSIDE.

51 497
2.0 19.6 64
[22] 22 2X 2.5
Ø.875 KNOCKOUTS 80 127 .875 KNOCKOUTS
POWER ENTRY KNOCKOUTS 165 370
3.2 5.0 FIELD CONTROL
ARE ON THE OPPOSITE 6.5 14.6 2546
CONNECTIONS
SIDE OF CONTROL BOX QTY. 3 100.2

[22] 2389
152 A Ø.875
EVAP. 94.1
WATER 6.0 B POWER ENTRY
INLET KNOCKOUTS
FRONT OR
1094 RIGHT SIDE Y
43.1 153
635 6.0 EVAP.
L1 - L4, 25.0
LIFTING 266
LOCATIONS 10.5
L3 L1
506 L4 EVAP. L2 506 WYE-STRAINER
19.9 WATER 19.9 FRONT LEFT REQUIRED X
OUTLET 797 CORNER POST (FACTORY OR FIELD
PURPOSELY INSTALLED OPTION) 2235
31.4 HIDDEN
Z 88.0
2396 DIMENSION DOES NOT INCLUDE
94.3 LIFTING BRACKETS

PACKAGE UNITS WITH MICROCHANNEL COILS


OPERATING
SHIPPING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER LBS (KG) MOUNTING (OPERATING) WEIGHT LBS (KG)
UNIT MODEL WEIGHT
LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4
AGZ030E 2947 (1337) 2960 (1343) 1011 (459) 799 (362) 635 (288) 502 (228) 980 (445) 775 (352) 673 (305) 532 (241)

14 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Dimensions and Weights - Packaged Units

AGZ035E 2873 (1303) 2887 (1310) 1051 (477) 861 (391) 528 (240) 433 (196) 1005 (456) 824 (374) 581 (264) 476 (216)
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE PACKAGE UNITS WITH MICROCHANNEL COILS
M3 M1 CG LOCATION, IN (MM)
337 1721 337 UNIT MODEL
13.3 67.8 13.3 X Y Z
L3 L1
AGZ040E 39.8 (1011) 45.9 (1166) 38.4 (975)
52 AGZ045E 38.9 (988) 44.5 (1130) 41.2 (1047)
2.0 AGZ050E 39.1 (993) 44.9 (1141) 41.2 (1047)
COMPRESSORS
CIRCUIT #2 AGZ055E 39.1 (993) 44.8 (1138) 41.2 (1047)
COMPRESSORS
CIRCUIT #1 AGZ060E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ065E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ070E 36.8 (935) 41.8 (1062) 42.6 (1082)
TOP VIEW WITH
COILS AND
FANS REMOVED EVAP. DIMENSIONS IN (MM) CONNECTION SIZE
UNIT MODEL
A B (VICTAULIC)
AGZ040E 22.8 (579) 1.5 (38) 2.5 (64)
AGZ045E 21.4 (544) 0.11 (3) 2.5 (64)
AGZ050E 20 (508) 2.7 (69) 2.5 (64)
Figure 24: AGZ040E - AGZ070E

AGZ055E 19.3 (490) 2.0 (51) 2.5 (64)


19 AGZ060E 17.6 (447) 0.3 (8) 2.5 (64)
.750
QTY. 4 52 AGZ065E 17.6 (447) 0.3 (8) 2.5 (64)
2.0 AGZ070E 17.6 (447) 0.3 (8) 2.5 (64)

L4 L2 208
1822
8.2
M4 M2 71.8
REF.
CONTROL
BOX

497
19.6
51
2.0 64
22 2X 2.5
[22]
.875 KNOCKOUTS

www.DaikinApplied.com 15
Ø.875 KNOCKOUTS 80 127
POWER ENTRY KNOCKOUTS FIELD CONTROL 165 370
3.2 5.0 CONNECTIONS 6.5 14.6
ARE ON THE OPPOSITE 2546
SIDE OF CONTROL BOX QTY. 3 100.2

152 [22] 2389


A Ø.875
EVAP. 6.0 94.0
WATER POWER ENTRY
B KNOCKOUTS
INLET
FRONT OR
1094 RIGHT SIDE Y
43.1 153
635 6.0 EVAP.
25.0
L1 - L4, 266
LIFTING 10.5
LOCATIONS
L3 EVAP. L1
506 L4 WATER L2 506
19.9 OUTLET 19.9 WYE-STRAINER X
FRONT LEFT REQUIRED 334547101 0B
797 CORNER POST (FACTORY OR FIELD
31.4 PURPOSELY INSTALLED OPTION) 2235
AGZ-E, 4 FANS
Z HIDDEN
88.0
2396 DIMENSION DOES NOT INCLUDE
94.3 LIFTING BRACKETS
PACKAGE UNITS WITH MICROCHANNEL COILS
OPERATING
SHIPPING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER LBS (KG) MOUNTING (OPERATING) WEIGHT LBS (KG)
UNIT MODEL WEIGHT
LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4
AGZ040E 2948 (1337) 2964 (1345) 1067 (484) 881 (400) 548 (249) 453 (206) 1022 (464) 844 (383) 601 (273) 496 (225)
AGZ045E 3094 (1403) 3112 (1412) 1051 (477) 832 (377) 676 (307) 535 (243) 1021 (463) 809 (367) 715 (324) 567 (257)
AGZ050E 3093 (1403) 3114 (1413) 1049 (476) 837 (380) 671 (304) 536 (243) 1020 (463) 814 (369) 712 (323) 568 (258)
AGZ055E 3106 (1409) 3128 (1419) 1052 (477) 840 (381) 675 (306) 539 (245) 1023 (464) 817 (371) 716 (325) 572 (260)
AGZ060E 3130 (1420) 3155 (1431) 1059 (480) 851 (386) 676 (307) 543 (246) 1031 (468) 828 (376) 718 (326) 577 (262)
AGZ065E 3130 (1420) 3155 (1431) 1059 (480) 851 (386) 676 (307) 543 (246) 1031 (468) 828 (376) 718 (326) 577 (262)
AGZ070E 3472 (1575) 3497 (1586) 1180 (535) 847 (384) 842 (382) 604 (274) 1157 (525) 830 (377) 880 (399) 631 (286)

NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.


MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Dimensions and Weights - Packaged Units
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.

M1
M3
984 2433 315
38.7 95.8 12.4
L3 L1
UNIT CG LOCATION, IN (MM)
52 MODEL X Y Z
2.0 AGZ075E 45.3 (1151) 38.6 (980) 56.2 (1427)
AGZ080E 44.2 (1122) 39.2 (995) 56.5 (1435)
TOP VIEW WITH AGZ090E 44.2 (1122) 39.2 (995) 55.0 (1397)
COILS AND FANS COMPR.
REMOVED CIRCUIT 2 AGZ100E 43.6 (1108) 38.9 (988) 55.7 (1415)

EVAP. DIMENSIONS
UNIT CONNECTION
IN (MM)
MODEL SIZE, IN.
A B
Figure 25: AGZ075E - AGZ100E

COMPR. AGZ075E 55.6 (1412) 27.1 (688)


1118 CIRCUIT 1 AGZ080E 54.4 (1382) 25.9 (658)
44.0 3.0 (76)
AGZ090E 54.4 (1382) 25.9 (658)
52 AGZ100E 51.6 (1311) 23.1 (587)
2.0

L4 L2 M2
M4 19
B .750
QTY. 4
A

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


CONTROL
BOX X 2506
WYE-STRAINER
REQUIRED 98.6
(FACTORY OR FIELD
INSTALLED OPTION) 22
.875 KNOCKOUTS 2355
FIELD CONTROL 92.7
CONNECTIONS
51 QTY. 3
2.0
127 64
80 5.0 2.5
153 Y
3.1
858 6.0 64
2.5 213
33.8 8.4
290 305
11.4 12.0
L3 L1
L4 EVAP. L2 22 [22]
L1 - L4, 916 EVAP. 609 292 165
WATER .875 KNOCKOUTS .875 POWER ENTRY
LIFTING 36.1 WATER INLET 24.0 11.5 6.5
POWER ENTRY KNOCKOUTS KNOCKOUTS
LOCATIONS OUTLET 175
ARE ON THE OPPOSITE SIDE FRONT OR RIGHT SIDE
Z 2235 6.9
OF THE CONTROL BOX
3733 37 88.0
147.0 1.5 DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS 334547111 00
AGZ-E, 6 FANS

SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
UNIT MODEL
LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4
AGZ075E 4388 (1990) 4451 (2019) 1341 (608) 1420 (644) 790 (358) 837 (380) 1173 (532) 1242 (563) 989 (449) 1047 (475)
AGZ080E 4510 (2046) 4579 (2077) 1407 (638) 1418 (643) 840 (381) 846 (384) 1232 (559) 1241 (563) 1049 (476) 1057 (479)
AGZ090E 4540 (2059) 4609 (2091) 1456 (660) 1466 (665) 806 (366) 812 (368) 1276 (579) 1285 (583) 1020 (463) 1028 (466)
AGZ100E 4696 (2130) 4780 (2168) 1505 (683) 1480 (671) 863 (391) 848 (385) 1322 (600) 1299 (589) 1089 (494) 1070 (485)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.

16 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
M1 - M6, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.

M5 M3 M1
630 1499 2433 315
24.8 L3 59.0 95.8 L1 12.4

52
2.0

TOP VIEW WITH COMPR.


COILS AND FANS CIR. 2 UNIT CG LOCATION, IN (MM)
REMOVED. MODEL X Y Z
AGZ110E 44.1 (1120) 42.1 (1069) 69.0 (1753)
AGZ120E 44.1 (1120) 43.3 (1100) 66.4 (1687)
AGZ130E 43.1 (1095) 41.0 (1041) 68.3 (1735)
Figure 26: AGZ110E - AGZ130E

UNIT EVAP. DIMENSIONS, IN (MM) CONNECTION


1118 COMPR.
44.0 CIR. 1 MODEL A B SIZE, IN.
AGZ110E 95.5 (2426) 69.1 (1755)
52 AGZ120E 93.9 (2385) 67.5 (1715) 3.0 (76)
2.0 AGZ130E 92.0 (2337) 65.5 (1664)
M6 L4 M4 L2 M2
19
.750 B
QTY. 6
A

www.DaikinApplied.com 17
CONTROL
BOX 2506
98.6
WYE-STRAINER
REQUIRED 22 X
(FACTORY OR .875 KNOCKOUTS 2355
FIELD INSTALLED FIELD CONTROL 92.7
OPTION) CONNECTIONS
51 QTY. 3
2.0 64
80 2.5
153 127 213
3.1 5.0 64 Y
858 6.0 8.4
33.8 2.5
290 305
11.4 12.0

L3 L1
996 L4 EVAP. EVAP. L2 609 292 165 [22]
L1 - L4, 39.2 WATER WATER 24.0 11.5 6.5 .875 POWER ENTRY
LIFTING OUTLET INLET KNOCKOUTS
Z 37 175
LOCATIONS FRONT OR RIGHT SIDE
4879 1.5 2235 6.9
192.1 88.0
22
DIMENSION DOES NOT INCLUDE
.875 KNOCKOUTS LIFTING BRACKETS
POWER ENTRY KNOCKOUTS
ARE ONTHE OPPOSITE SIDE 334547121
OF THE CONTROL BOX AGZ-E 8 FANS

UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ110E 5437 (2466) 5528 (2508) 1762 (799) 1769 (802) 951 (431) 955 (433) 1424 (646) 1430 (649) 845 (383) 849 (385) 489 (222) 491 (223)
AGZ120E 5696 (2584) 5796 (2629) 1907 (865) 1915 (869) 935 (424) 939 (426) 1548 (702) 1555 (705) 878 (398) 882 (400) 465 (211) 467 (212)
AGZ130E 5792 (2627) 5903 (2678) 1941 (880) 1863 (845) 1015 (460) 974 (442) 1575 (714) 1511 (685) 920 (417) 883 (401) 517 (235) 496 (225)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Dimensions and Weights - Packaged Units
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.

M1
M5 M3
1711 1564 2433 315
67.4 61.6 95.8 12.4
L3 L1 334547131
AGZ-E 10FANS
52
2.0

TOP VIEW WITH UNIT CG LOCATION, IN (MM) EVAP. DIMENSIONS, IN (MM) CONNECTION
COILS AND FANS COMPR. MODEL X Y Z A B SIZE, IN.
REMOVED CIR. 2 AGZ140E 44.1 (1120) 42.6 (1083) 83.3 (2117) 122.1 (3102) 67.51 (1715)
4.0 (102)
AGZ150E 43.9 (1116) 42.4 (1077) 83.3 (2115) 120.5 (3062) 65.9 (1674)
Figure 27: AGZ140E - AGZ150E

COMPR.
1118 CIR. 1
44.0
52
2.0

M6 L4 M4 L2 M2
19
B
.750
QTY. 6

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


A

2506
98.6

CONTROL
BOX X 2355
92.7

51
2.0 64
2.5 Y
80 127
210 3.1 64 213
858 5.0
8.3 2.5 8.4
33.8
290 305 22
11.4 12.0 .875 KNOCKOUTS
FIELD CONTROL
L3 L1
1919 L2 CONNECTIONS [22]
L4 EVAP. EVAP. 609 22 292 165
75.5 QTY. 3 .875
WATER WATER 24.0 .875 KNOCKOUTS 11.5 6.5 175
L1 - L4 INLET 2235 POWER ENTRY
LIFTING WYE-STRAINER OUTLET POWER ENTRY KNOCKOUTS 6.9 KNOCKOUTS FRONT
37 88.0
LOCATIONS REQUIRED ARE ON THE OPPOSITE SIDE OR RIGHT SIDE
(FACTORY OR FIELD 1.5 OF THE CONTROL BOX DIMENSION DOES NOT INCLUDE
Z LIFTING BRACKETS
INSTALLED OPTION)
6025
237.2

UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ140E 6555 (2973) 6674 (3027) 1862 (845) 1868 (847) 1410 (640) 1415 (642) 1411 (640) 1416 (642) 1070 (485) 1074 (487) 850 (386) 853 (387)
AGZ150E 6617 (3001) 6745 (3059) 1888 (856) 1881 (853) 1426 (647) 1421 (645) 1433 (650) 1428 (648) 1085 (492) 1081 (490) 861 (391) 858 (389)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.

18 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.

M1
M5 M3
1711 1564 2433 315
67.4 61.6 95.8 12.4
L3 L1
52
2.0

334547131
TOP VIEW WITH COMPR. AGZ-E 10FANS
COILS AND FANS CIR. 2
REMOVED
Figure 28: AGZ160E - AGZ180E

CG LOCATION, IN (MM) EVAP. DIMENSIONS, IN (MM) CONNECTION


UNIT MODEL
X Y Z A B SIZE, IN.
AGZ160E 44.1 (1119) 41.4 (1051) 84.5 (2147) 120.5 (3062) 65.9 (1674)
AGZ170E 43.2 (1096) 40.4 (1025) 83.6 (2123) 119 (3022) 64.3 (1634) 4.0 (102)
AGZ180E 44.1 (1119) 39.4 (1000) 82.8 (2103) 117 (2971) 62.4 (1584)
COMPR.
1118 CIR. 1
44.0
52
2.0

M6 L4 M4 L2 M2
19
B .750
QTY. 6
A

www.DaikinApplied.com 19
2506
98.6

CONTROL 2355
BOX X 92.7

51
2.0 64
2.5 Y
80 127
210 3.1 5.0 64 213
858
8.3 2.5 8.4
33.8
290 305 22
11.4 12.0 .875 KNOCKOUTS
FIELD CONTROL
L3 L1
1919 L4 L2 CONNECTIONS 165 [22]
EVAP. EVAP. 609 22 QTY. 3 292
75.5 6.5 175 .875
L1 - L4 WATER WATER 24.0 .875 KNOCKOUTS 11.5 POWER ENTRY
WYE-STRAINER OUTLET INLET 37 POWER ENTRY KNOCKOUTS 6.9
LIFTING REQUIRED 2235 KNOCKOUTS FRONT
LOCATIONS 1.5 ARE ON THE OPPOSITE SIDE OR RIGHT SIDE
(FACTORY OR FIELD 88.0
INSTALLED OPTION) Z OF THE CONTROL BOX
DIMENSION DOES NOT INCLUDE
6025 LIFTING BRACKETS
237.2

UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ160E 6937 (3147) 7065 (3205) 1941 (880) 1947 (883) 1522 (690) 1527 (693) 1466 (665) 1471 (667) 1136 (515) 1140 (517) 924 (419) 927 (420)
AGZ170E 7170 (3252) 7307 (3314) 2072 (940) 1995 (905) 1581 (717) 1522 (690) 1571 (713) 1512 (686) 1197 (543) 1152 (523) 956 (434) 920 (417)
AGZ180E 7412 (3362) 7560 (3429) 2121 (962) 2127 (965) 1580 (717) 1584 (718) 1613 (732) 1617 (733) 1210 (549) 1214 (551) 951 (431) 954 (433)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Dimensions and Weights - Packaged Units
Refrigerant Charge

Refrigerant Charge

Table 6: Refrigerant Charge


Unit Operating Charge - lbs (kg)
Unit Models Replaceable Core Filter Drier Sealed Filter Drier
Circuit 1 Circuit 2 Circuit 1 Circuit 2
030E 17 (7.7) 17 (7.7) 15 (16.8) 15 (16.8)
035E 16 (7.3) 16 (7.3) 14 (6.4) 14 (6.4)
040E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
045E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
050E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
055E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
060E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
065E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
070E 23 (10.5) 23 (10.5) 21 (9.5) 21 (9.5)
075E 46 (20.9) 46 (20.9)
080E 46 (20.9) 46 (20.9)
090E 48 (21.8) 48 (21.8)
100E 49 (22.3) 49 (22.3)
110E 64 (29.1) 64 (29.1)
120E 65 (29.5) 65 (29.5)
130E 65 (29.5) 65 (29.5)
140E 76 (34.5) 76 (34.5)
150E 76 (34.5) 76 (34.5)
160E 78 (35.4) 78 (35.4)
170E 80 (36.3) 80 (36.3)
180E 80 (36.3) 80 (36.3)

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 20 www.DaikinApplied.com


Isolator Information

Isolator Information

Figure 29: Spring Isolator In all cases, set the unit in place and level. When spring
ELASTOMERIC isolators are required, install springs running under the main
SNUBBER
unit supports.
Installation of spring isolators requires flexible piping
3
[76.2]
.62 [15.8] connections and at least three feet of flexible electrical conduit
to avoid straining the piping and transmitting vibration and
noise.
9.25 [235.0]
Mounting locations for each model can be found in the
10.5 [266.7]
“Dimensions and Weights - Packaged Units” section of this
7.75 [196.9] document, starting on page 14.
.625 .5 [12.7] DIA.
[15.9] POSITIONING
.25 TO .5 GAP Optional seismic isolator information begins on page 23
PIN
[6.4 to 12.7]
Contact a Daikin Applied sales representative for isolator
ADJ. BOLT information related to units with other fin materials.
6.25
[127.0]
FREE HT. Table 7: Isolator Kits
5\X [127.0]
OPER. HT.
AGZ-E Microchannel - Packaged Units
Model Spring Isolators RIS Isolators
.56 [14.3]
030 332320102 332325101
.25 [6.4]
ELASTOMERIC PAD 035 332320102 332325101
040 332320102 332325101
045 332320132 332325101
Figure 30: Rubber-in-Shear (RIS) Isolator
050 332320132 332325101
055 332320132 332325101
060 332320132 332325101
065 332320132 332325101
070 332320132 332325101
075 332320117 332325101
080 332320117 332325101
090 332320117 332325101
100 332320117 332325101
110 332320123 332325113
120 332320124 332325113
130 332320124 332325113
140 332320106 332325113
150 332320106 332325113
160 332320111 332325113
170 332320111 332325113
180 332320111 332325113

www.DaikinApplied.com 21 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Isolator Information

Table 8: Microchannel Isolator Information


AGZ-E Rubber-In-Shear (RIS) Mounts Spring Isolator Mountings
Model M1 M2 M3 M4 M5 M6 M7 M8 M1 M2 M3 M4 M5 M6 M7 M8
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
030
Brown Brown Brown Brown Dark Grn Dk Purple Black Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
035
Brown Brown Brown Brown Dark Grn Dk Purple Black Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
040
Brown Brown Brown Brown Dark Grn Dk Purple Black Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
045
Brown Brown Brown Brown Dark Grn Dk Purple Dk Purple Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
050
Brown Brown Brown Brown Dark Grn Dk Purple Dk Purple Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
055
Brown Brown Brown Brown Dark Grn Dk Purple Dk Purple Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
060
Brown Brown Brown Brown Dark Grn Dk Purple Dk Purple Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
065
Brown Brown Brown Brown Dark Grn Dk Purple Dk Purple Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
070
Brown Brown Brown Brown Dark Grn Dk Purple Dk Purple Black
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
075
Brown Brown Brown Brown Dark Grn Dark Grn Dark Grn Dark Grn
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
080
Brown Brown Brown Brown Dark Grn Dark Grn Dark Grn Dark Grn
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
090
Brown Brown Brown Brown Dark Grn Dark Grn Dark Grn Dark Grn
RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2
100
Brown Brown Brown Brown Dark Grn Dark Grn Dark Grn Dark Grn
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
110
Red Red Brown Brown Brown Brown Dark Grn Dark Grn Dk Purple Dk Purple Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
120
Red Red Brown Brown Brown Brown Gray Gray Dk Purple Dk Purple Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
130
Red Red Brown Brown Brown Brown Gray Gray Dk Purple Dk Purple Red Red
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
140
Red Red Brown Brown Brown Brown Dark Grn Dark Grn Dark Grn Dark Grn Dk Purple Dk Purple
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
150
Red Red Brown Brown Brown Brown Dark Grn Dark Grn Dark Grn Dark Grn Dk Purple Dk Purple
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
160
Red Red Brown Brown Brown Brown Gray Gray Dark Grn Dark Grn Dark Grn Dark Grn
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
170
Red Red Brown Brown Brown Brown Gray Gray Dark Grn Dark Grn Dark Grn Dark Grn
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4 CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
180
Red Red Brown Brown Brown Brown Gray Gray Dark Grn Dark Grn Dark Grn Dark Grn

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 22 www.DaikinApplied.com


Isolator Information

Figure 31: Seismic Spring Isolators


1 1/8 8
[29] [203]
13/16 [21] DIA HOLE FOR
ATTACHMENT TO
CONCRETE (6 TYP)

(BASE PLATE)
3/4 [19] DIA HOLE FOR
ATTACHMENT TO
2 1/4 [57]
STEEL (4 TYP)
6 1/4 [159] (VIEW CUT AWAY FOR CLARITY)

2 7/8 [73]

2 7/8 [73]

7/8 [22]
5 1/8
[130]
1 1/2 7 1/4
[38] [184]
5 3/4
3/4 [19] REMOVABLE [146]
ADJUSTING BOLT
STEEL SHIM
(REMOVE AFTER
SPRING ADJUSTMENT)
3/4 [19] STD.WASHER
(BY OTHERS)
3/8 [10] GAP
1/2 [13]

1/4 - 3/8 [6 - 10]

6 1/8 [156]
ELASTOMERIC
FREE &
SNUBBER LIMIT STOPS
OPERATING
HEIGHT SHIPPING SPACER (NOT SHOWN
ASSY STRAP IN TOP VIEW
(NOT SHOWN FOR CLARITY)
IN OTHER VIEWS
FOR CLARITY) 3/8 [10]

10 1/4 8
[260] [203]

Figure 32: Seismic Neoprene Isolation Pads Table 9: Seismic Isolator Kit Numbers
8.00 AGZ-E Packaged Unit - Aluminum Fins
203.2 Model Neoprene Pads Spring Isolators
030 334549001 334548801
035 334549001 334548801

4.00 040 334549001 334548801


101.6 045 334549001 334548801
2.00
50.8 050 334549001 334548801
055 334549001 334548801

.875 060 334549001 334548801


4.00
101.6
22.2 065 334549001 334548801
THRU
ALL 070 334549001 334548802

Table 10: Seismic Isolator Information


Neoprene Pads Spring Isolators
AGZ-E
Model M1 M2 M3 M4 M5 M6 M7 M8 M1 M2 M3 M4 M5 M6 M7 M8
030 Brown Brown Brown Brown Pink Pink Tan Tan
035 Brown Brown Brown Brown Pink Pink Tan Tan
040 Brown Brown Brown Brown Pink Pink Tan Tan
045 Brown Brown Brown Brown Pink Pink Tan Tan
050 Brown Brown Brown Brown Pink Pink Tan Tan
055 Brown Brown Brown Brown Pink Pink Tan Tan
060 Brown Brown Brown Brown Pink Pink Tan Tan
065 Brown Brown Brown Brown Pink Pink Tan Tan
070 Brown Brown Brown Brown Pink Pink Pink Tan

www.DaikinApplied.com 23 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Presure Drop Data

Presure Drop Data

Figure 33: Pressure Drop Curves


100
A
B
C
D
E
I
F E
G BCD FG
H
U
H
ST
I A Q
OP
J L MN

Differential Pressure (ft)


K JK
L I
E
M C FH
D
N B G
10 O
A
P
Q U
J O
R
N T
S LM
T K S
U Q
P

I
E
BC H
D FG U
ST
A Q
L NOP
M
JK
1
10 100 1000
Flow Rate (gpm)

Table 11: Pressure Drop Data


Variable Flow System Only Fixed Flow System Only Fixed and Variable Flow Systems
Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve IP SI IP SI IP SI IP SI
Model
Ref.
GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa
A 030E 27.0 1.7 1.7 5.1 42.2 4.0 2.7 12.0 67.4 9.8 4.3 29.4 112.4 26.0 7.1 77.7
B 035E 33.5 2.4 2.1 7.1 52.4 5.6 3.3 16.7 83.8 13.7 5.3 40.9 139.6 36.4 8.8 108.7
C 040E 37.1 2.5 2.3 7.4 57.9 5.8 3.7 17.3 92.6 14.2 5.8 42.5 154.4 37.7 9.7 112.6
D 045E 40.9 2.3 2.6 6.8 63.9 5.3 4.0 15.8 102.2 13.2 6.5 39.4 170.4 34.4 10.8 102.7
E 050E 46.4 2.7 2.9 7.9 72.5 6.2 4.6 18.5 115.9 15.2 7.3 45.3 193.2 40.0 12.2 119.6
F 055E 49.7 2.3 3.1 7.0 77.7 5.5 4.9 16.3 124.3 13.4 7.8 40.0 207.2 35.6 13.1 106.2
G 060E 54.0 2.3 3.4 6.9 84.3 5.4 5.3 16.1 134.9 13.1 8.5 39.3 224.8 34.7 14.2 103.6
H 065E 55.5 2.4 3.5 7.3 86.7 5.7 5.5 17.0 138.7 13.9 8.8 41.4 231.2 36.6 14.6 109.3
I 070E 61.5 3.0 3.9 8.8 96.1 6.9 6.1 20.6 153.8 16.9 9.7 50.4 256.4 44.5 16.2 133.0
J 075E 69.8 1.2 4.4 3.6 109.1 2.8 6.9 8.4 174.5 6.9 11.0 20.5 290.8 18.2 18.3 54.3
K 080E 73.8 1.2 4.7 3.7 115.4 2.9 7.3 8.6 184.6 7.1 11.6 21.3 307.6 18.9 19.4 56.6
L 090E 80.1 1.4 5.1 4.3 125.1 3.4 7.9 10.1 200.2 8.3 12.6 24.8 333.6 22.1 21.0 66.1
M 100E 92.4 1.3 5.8 4.0 144.3 3.2 9.1 9.5 230.9 7.8 14.6 23.3 384.8 20.8 24.3 62.2
N 110E 102.0 1.4 6.4 4.2 159.5 3.3 10.1 9.9 255.1 8.2 16.1 24.4 425.2 21.6 26.8 64.6
O 120E 113.1 1.5 7.1 4.5 176.7 3.6 11.1 10.7 282.7 8.8 17.8 26.4 471.2 23.5 29.7 70.3
P 130E 119.5 1.5 7.5 4.4 186.8 3.5 11.8 10.4 298.8 8.6 18.9 25.7 498.0 22.9 31.4 68.3
Q 140E 128.9 1.7 8.1 5.1 201.5 4.0 12.7 12.1 322.3 9.9 20.3 29.7 537.2 26.4 33.9 79.0
R 150E 143.6 1.8 9.1 5.5 224.4 4.4 14.2 13.0 359.0 10.8 22.7 32.4 598.4 29.1 37.8 87.0
S 160E 143.6 1.8 9.1 5.5 224.4 4.4 14.2 13.0 359.0 10.8 22.7 32.4 598.4 29.1 37.8 87.0
T 170E 154.1 1.9 9.7 5.6 240.8 4.5 15.2 13.4 385.2 11.2 24.3 33.4 642.0 30.2 40.5 90.2
U 180E 164.8 2.3 10.4 6.9 257.6 5.3 16.2 15.9 412.1 12.8 26.0 38.3 686.8 33.5 43.3 99.9

IOM 1206-3 • TRAILBLAZER® MODEL AGZ CHILLERS 24 www.DaikinApplied.com


Electrical Data
Electrical Data

Electrical Data Notes per NEMA MG-1, 2009 Standard Rev. 1-2010.

Electrical Data Single and Multi-Point Table 12: Standard and HSCCR Panel Ratings
1. Unit wire size ampacity (MCA) is equal to 125% of the Panel Type 208V / 230V 380V / 400V / 460V 575V
largest compressor-motor RLA plus 100% of RLA of all Standard 5kA 5kA 5kA
other loads in the circuit.
HSCCR 65kA 65kA 25kA
2. The control transformer is furnished and no separate
115V power is required. For both single and multi-point Electrical Control Center
power connections, the control transformer is in circuit
Operating and equipment protection controls and motor
#1 with control power wired from there to circuit #2. In
starting components are separately housed in a centrally
multi-point power, disconnecting power to circuit #1
located, weather resistant control panel with hinged and
disconnects control power to the unit.
tool-locked doors. In addition to the MicroTech® III controller
3. Wire sizing amps is 15 amps if a separate 115V power described in the next sections, the following components are
supply is used for the control circuit. housed in the panel:
4. Recommended power lead wire sizes for 3 conductors • Power terminal blocks, multi-point connection standard
per conduit are based on 100% conductor ampacity • Control, input, and output terminal block
in accordance with NEC. Voltage drop has not been
included. It is recommended that power leads be kept • Control transformer
short. All terminal block connections must be made with • Optional disconnect switch (through-the-door handle)
copper (type THW) wire or aluminum wire. • Compressor motor inherent thermal and overload
5. Recommended Fuse Sizes are selected at approximately protection is standard
175% of the largest compressor RLA, plus 100% of all • Optional phase voltage monitor with under/over voltage
other loads in the circuit. and phase reversal protection
6. Maximum Fuse or breaker size is equal to 225% of the • Fan contactors with short circuit protective devices.
largest compressor RLA, plus 100% of all other loads. • Optional ground fault protection
7. The recommended power wire sizes are based on an • FanTrol™ fan staging head pressure control system
ambient temperature of 86°F (30°C). Ampacity correction • Power connections are per Table 13
factors must be applied for other ambient temperatures.
Refer to the NEC Handbook. Power Connections
8. Must be electrically grounded according to national and
local electrical codes. Table 13: Power Connection Availability
Comp. Panel High
Power Disc.
Wiring Data Power Connection Block Swt. Circuit Short Circuit
Breakers Current Rating
1. Single-point power supply requires a single disconnect Optional Single Point Std. Opt. Std. Opt.
to supply electrical power to the unit. This power supply
Standard Multi-Point Std. Opt. Not Avail. Opt.
must either be fused or use a circuit breaker.
2. Power wiring connections to the chiller may be done with Definitions:
either copper or aluminum wiring. Wire should be sized
1. Power Block: An electrical device to directly accept field
per NEC and/or local codes. Wire sizing and wire count
wiring without any disconnecting means.
must fit in the power connection lug sizing shown in the
Electrical Data tables starting on page 28. 2. Disconnect Switch: A molded case switch that accepts
field wiring and disconnects main power to the entire
3. All field wire size values given in the Electrical Data
unit or each main power supply if the multi-point power
tables starting on page 28 apply to 75°C rated wire per
supply option is selected. This option does not provide
NEC.
overcurrent protection.
Circuit Breakers 3. Compressor Circuit Breakers: A manually reset circuit
breaker for each compressor, providing compressor
Factory installed compressor circuit breakers are standard on
only short circuit protection and located ahead of the
units with single point power supply only. This option provides
contactor.
compressor short circuit protection and makes servicing easier
4. Control Panel High Short Circuit Current Rating:
Voltage Limitations: (Previously known as “withstand rating”). The entire
control panel is designed for short circuit current rating
1. Within 10 percent of nameplate rating.
as shown in Table 12. In the event of a short circuit, the
2. Voltage unbalance not to exceed 2% with a resultant damage is contained within the control panel enclosure.
current unbalance of 6 to 10 times the voltage unbalance

www.DaikinApplied.com 25 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Electrical Data

Figure 34: Typical Field Wiring Diagram (Single-Point Connection)


FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER

PANEL

CIRCUIT BREAKER DISCONNECT SWITCH


(BY OTHERS) OR
POWER BLOCK

L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3

EARTH
FU4 FU5
GROUND
T1

TB1
35 120 VAC
CHWR1
FU6 301 120 299
PUMP NO.1 RELAY DISCONNECT
CONTROL CIRCUIT VAC
(BY OTHERS) (BY OTHERS)
FUSE
120VAC @ 1.0AMP MAX
TB1 SEE NOTE 2 TB1 22 N
33 N OPTIONAL
(626) / 301A FIELD SUPPLIED
TB1 FU
TB1 CONTROL POWER
1A 120 VAC
P2+ 120 VAC 15A for 1.5 KVA
CHWR2 30A for 3.0KVA
PUMP NO.2 RELAY (BY OTHERS)
(BY OTHERS)
120VAC @ 1.0AMP MAX
TB1
31 N
(714) /

TB1
34 120 VAC

ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX TB1
32A
(235)
/ ABR GND
(630) OFF
(317)
** TIME CLOCK TB2
52
AUTO IF REMOTE STOP
REMOTE CONTROL IS USED
STOP SWITCH 585 REMOVE LEAD 585
(BY OTHERS) ON FROM TERM
TB2 TB2-52 TO TB2-72
72
(655) / MANUAL **

** TIME OFF
CLOCK TB2
54 ALARM BELL **
AUTO RELAY
TB2 /(542)
DOUBLE SET POINT/MODE
SWITCH 24 VAC 43
ON COM NO
(BY OTHERS) ABR
TB2
UNIT ALARM
74
(652) / MANUAL ** BELL
TB2 1 2
N 83
/(225)
** NOR. OPEN PUMP 24VAC @ 0.4AMP MAX.
AUX. CONTACTS
(OPTIONAL) TB2
CHW FLOW SWITCH 44
-MANDATORY-
** TB2 TB2
(BY OTHERS)
61 IF EXTERNAL 45
(649) / ALARM/EVENT
EXTERNAL
IS USED 555A ALARM/
REMOVE LEAD 555A
EVENT
FROM TERM TB2 **
TB2-45 TO TB2-67 67
/(645)

TB2 Notes:
+ 68
4-20MA FOR
1.) ALL FIELD WIRING TO BE INSTALLED AS
EVAP. - LWT RESET
TB2 NEC CLASS 1 WIRING SYSTEM WITH
(BY OTHERS) _
69 CONDUCTOR RATED 600 VOLTS.
(637) / 2.) IF FIELD SUPPLIED, CONTROL POWER USER
TB2 MUST REMOVE FU6, AND WIRE NUMBERS
+ 70 299, 301A INSIDE CONTROL PANEL
4-20MA FOR
3.) ** = USE 'DRY CONTACTS' ONLY
DEMAND LIMIT
TB2 4.) DO NOT SUPPLY FIELD POWER TO
(BY OTHERS) _
71 24VAC OR 120VAC CONTROL CIRCUITS.
(629) /

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 26 www.DaikinApplied.com


Electrical Data

Figure 35: Typical Field Wiring Diagram (Multi-Point Connection)


FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER

PANEL

CIRCUIT BREAKER 1 DISCONNECT SWITCH


(BY OTHERS) OR
POWER BLOCK

L1 T1
3 PHASE TO CIRCUIT 1
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3

FU4 FU5

T1

EARTH
GROUND
FU6 301 120 299
DISCONNECT
CONTROL CIRCUIT VAC (BY OTHERS)
FUSE
SEE NOTE 2 TB1 22 N
OPTIONAL
301A FIELD SUPPLIED
TB1 FU
DISCONNECT SWITCH CONTROL POWER
CIRCUIT BREAKER 2 1A 120 VAC
(BY OTHERS) OR
15A for 1.5 KVA
POWER BLOCK
30A for 3.0KVA
(BY OTHERS)
L1 T1
3 PHASE TO CIRCUIT 2
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
TB1
35 120 VAC
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
TB1
33 N
(626) /
TB1
P2+ 120 VAC
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
TB1
31 N
(714) /

TB1
34 120 VAC

ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX TB1
32A
(240)
/ ABR GND
(630) OFF (317)
** TIME CLOCK TB2
52
AUTO IF REMOTE STOP
REMOTE CONTROL IS USED
STOP SWITCH 585 REMOVE LEAD 585
(BY OTHERS) ON FROM TERM
TB2 TB2-52 TO TB2-72
72
(655) / MANUAL **
OFF ALARM BELL**
** TIME
TB2 RELAY
CLOCK TB2 /(540)
54 24 VAC 43
AUTO COM NO
DOUBLE SET POINT/MODE ABR
ALARM BELL
SWITCH OPTION
(BY OTHERS) ON BELL
TB2 1 2
TB2
N 83
74 /(231)
(652) / MANUAL** 24VAC @ 0.4AMP MAX.
** NOR. OPEN PUMP
AUX. CONTACTS
(OPTIONAL) TB2
CHW FLOW SWITCH 44 TB2
-MANDATORY- 45
** TB2 IF EXTERNAL
(BY OTHERS)
ALARM/EVENT
61 EXTERNAL
(649) / IS USED 555A ALARM/
REMOVE LEAD 555A
** EVENT
FROM TERM TB2
TB2-45 TO TB2-67 67
/(645)

Notes:
TB2
1.) ALL FIELD WIRING TO BE INSTALLED AS
+ 68 NEC CLASS 1 WIRING SYSTEM WITH
4-20MA FOR
EVAP. - LWT RESET CONDUCTOR RATED 600 VOLTS.
TB2 2.) IF FIELD SUPPLIED, CONTROL POWER USER
(BY OTHERS) _
69 MUST REMOVE FU6, AND WIRE NUMBERS
(637) / 299, 301A INSIDE CONTROL PANEL
TB2 3.) ** = USE 'DRY CONTACTS' ONLY
+ 70 4.) DO NOT SUPPLY FIELD POWER TO
4-20MA FOR 24VAC OR 120VAC CONTROL CIRCUITS.
DEMAND LIMIT
TB2
(BY OTHERS) _
71
(629) /

www.DaikinApplied.com 27 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Electrical Data

Table 14: Electrical Data - Single Point (60/50Hz) Table 14 continued: Electrical Data - Single Point (60/50Hz)
Single Point Field Data Single Point Field Data
Model Voltage / Ratings Lug Range Model Voltage / Ratings Lug Range
Size Freq. Size Freq.
Disconnect Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 149 175 175 (1) 2-600MCM (1) 6-350MCM 208V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
230V/60 149 175 175 (1) 2-600MCM (1) 6-350MCM 230V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
380V/60 87 100 100 (1) 2-600MCM (1) 12-1/0 380V/60 161 175 175 (1) 2-600MCM (1) 6-350MCM
030E 065E
460V/60 74 80 80 (1) 14-2/0 (1) 12-1/0 460V/60 129 150 150 (1) 2-600MCM (1) 4-300MCM
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0 575V/60 113 125 125 (1) 2-600MCM (1) 4-300MCM
400V/50 77 90 90 (1) 14-2/0 (1) 12-1/0 400V/50 129 150 150 (1) 2-600MCM (1) 4-300MCM
208V/60 163 175 175 (1) 2-600MCM (1) 6-350MCM 208V/60 306 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 163 175 175 (1) 2-600MCM (1) 6-350MCM 230V/60 306 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 96 110 110 (1) 2-600MCM (1) 4-300MCM 380V/60 164 200 200 (1) 2-600MCM (1) 6-350MCM
035E 070E
460V/60 77 90 90 (1) 14-2/0 (1) 12-1/0 460V/60 138 150 150 (1) 2-600MCM (1) 4-300MCM
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0 575V/60 117 125 125 (1) 2-600MCM (1) 4-300MCM
400V/50 80 90 90 (1) 14-2/0 (1) 12-1/0 400V/50 138 150 150 (1) 2-600MCM (1) 4-300MCM
208V/60 168 200 200 (1) 2-600MCM (1) 6-350MCM 208V/60 338 400 400 (1) 2-600MCM (2) 3/0-500MCM
230V/60 168 200 200 (1) 2-600MCM (1) 6-350MCM 230V/60 338 400 400 (1) 2-600MCM (2) 3/0-500MCM
380V/60 107 125 125 (1) 2-600MCM (1) 4-300MCM 380V/60 173 200 200 (1) 14-2/0 (1) 6-350MCM
040E 075E
460V/60 80 90 90 (1) 14-2/0 (1) 12-1/0 460V/60 149 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 67 80 80 (1) 14-2/0 (1) 12-1/0 575V/60 125 150 150 (1) 14-2/0 (1) 4-300MCM
400V/50 83 100 100 (1) 14-2/0 (1) 12-1/0 400V/50 149 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 228 250 250 (1) 2-600MCM (1) 6-350MCM 208V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
230V/60 228 250 250 (1) 2-600MCM (1) 6-350MCM 230V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
380V/60 117 125 125 (1) 2-600MCM (1) 4-300MCM 380V/60 187 225 225 (1) 2-600MCM (1) 6-350MCM
045E 080E
460V/60 90 100 100 (1) 2-600MCM (1) 12-1/0 460V/60 153 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 75 90 90 (1) 14-2/0 (1) 12-1/0 575V/60 126 150 150 (1) 14-2/0 (1) 4-300MCM
400V/50 94 110 110 (1) 2-600MCM (1) 4-300MCM 400V/50 153 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 241 250 250 (1) 2-600MCM (2) 3/0-500MCM 208V/60 384 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 241 250 250 (1) 2-600MCM (2) 3/0-500MCM 230V/60 384 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 131 150 150 (1) 2-600MCM (1) 4-300MCM 380V/60 218 250 250 (1) 2-600MCM (1) 6-350MCM
050E 090E
460V/60 109 125 125 (1) 2-600MCM (1) 4-300MCM 460V/60 168 200 200 (1) 14-2/0 (1) 6-350MCM
575V/60 97 110 110 (1) 2-600MCM (1) 4-300MCM 575V/60 147 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 107 125 125 (1) 2-600MCM (1) 4-300MCM 400V/50 168 200 200 (1) 14-2/0 (1) 6-350MCM
208V/60 251 300 300 (1) 2-600MCM (2) 3/0-500MCM 208V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
230V/60 251 300 300 (1) 2-600MCM (2) 3/0-500MCM 230V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
380V/60 147 175 175 (1) 2-600MCM (1) 6-350MCM 380V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
055E 100E
460V/60 118 125 125 (1) 2-600MCM (1) 4-300MCM 460V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM
575V/60 105 125 125 (1) 2-600MCM (1) 4-300MCM 575V/60 184 225 225 (1) 2-600MCM (1) 6-350MCM
400V/50 119 125 125 (1) 2-600MCM (1) 4-300MCM 400V/50 203 250 250 (1) 2-600MCM (1) 6-350MCM
208V/60 260 300 300 (1) 2-600MCM (2) 3/0-500MCM 208V/60 490 600 600 (2) 6-500MCM (2) 3/0-500MCM
230V/60 260 300 300 (1) 2-600MCM (2) 3/0-500MCM 230V/60 490 600 600 (2) 6-500MCM (2) 3/0-500MCM
380V/60 161 175 175 (1) 2-600MCM (1) 6-350MCM 380V/60 294 350 350 (1) 2-600MCM (2) 3/0-500MCM
060E 110E
460V/60 126 150 150 (1) 2-600MCM (1) 4-300MCM 460V/60 227 250 250 (1) 2-600MCM (1) 6-350MCM
575V/60 113 125 125 (1) 2-600MCM (1) 4-300MCM 575V/60 204 250 250 (1) 2-600MCM (1) 6-350MCM
400V/50 129 150 150 (1) 2-600MCM (1) 4-300MCM 400V/50 227 250 250 (1) 2-600MCM (1) 6-350MCM

NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 28 www.DaikinApplied.com


Electrical Data

Table 14 continued: Electrical Data - Single Point (60/50Hz)


Single Point Field Data
Model Voltage / Ratings Lug Range
Size Freq.
Disconnect
MCA RFS MFS Power Block Switch
208V/60 534 600 600 (2) 6-500MCM (2) 3/0-500MCM
230V/60 534 600 600 (2) 6-500MCM (2) 3/0-500MCM
380V/60 330 400 400 (1) 2-600MCM (2) 3/0-500MCM
120E
460V/60 261 300 300 (1) 2-600MCM (2) 3/0-500MCM
575V/60 234 250 250 (1) 2-600MCM (2) 3/0-500MCM
400V/50 261 300 300 (1) 2-600MCM (2) 3/0-500MCM
208V/60 569 700 700 (2) 6-500MCM (3) 2/0-400MCM
230V/60 569 700 700 (2) 6-500MCM (3) 2/0-400MCM
380V/60 358 400 450 (1) 2-600MCM (2) 3/0-500MCM
130E
460V/60 284 350 350 (1) 2-600MCM (2) 3/0-500MCM
575V/60 239 250 250 (1) 2-600MCM (2) 3/0-500MCM
400V/50 284 350 350 (1) 2-600MCM (2) 3/0-500MCM
208V/60 612 700 700 (2) 6-500MCM (3) 2/0-400MCM
230V/60 612 700 700 (2) 6-500MCM (3) 2/0-400MCM
380V/60 388 450 450 (1) 2-600MCM (2) 3/0-500MCM
140E
460V/60 309 350 350 (1) 2-600MCM (2) 3/0-500MCM
575V/60 248 300 300 (1) 2-600MCM (2) 3/0-500MCM
400V/50 309 350 350 (1) 2-600MCM (2) 3/0-500MCM
208V/60 640 700 700 (2) 6-500MCM (3) 2/0-400MCM
230V/60 640 700 700 (2) 6-500MCM (3) 2/0-400MCM
380V/60 410 500 500 (1) 2-600MCM (2) 3/0-500MCM
150E
460V/60 328 400 400 (1) 2-600MCM (2) 3/0-500MCM
575V/60 252 300 300 (1) 2-600MCM (2) 3/0-500MCM
400V/50 328 400 400 (1) 2-600MCM (2) 3/0-500MCM
208V/60 688 800 800 (2) 6-500MCM (3) 2/0-400MCM
230V/60 688 800 800 (2) 6-500MCM (3) 2/0-400MCM
380V/60 406 450 450 (1) 2-600MCM (2) 3/0-500MCM
160E
460V/60 316 350 350 (1) 2-600MCM (2) 3/0-500MCM
575V/60 280 300 300 (1) 2-600MCM (2) 3/0-500MCM
400V/50 316 350 350 (1) 2-600MCM (2) 3/0-500MCM
208V/60 734 800 800 (2) 6-500MCM (4) 4/0-500MCM
230V/60 734 800 800 (2) 6-500MCM (4) 4/0-500MCM
380V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
170E
460V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
575V/60 309 350 350 (1) 2-600MCM (2) 3/0-500MCM
400V/50 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
208V/60 875 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
230V/60 875 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
380V/60 479 500 500 (2) 6-500MCM (2) 3/0-500MCM
180E
460V/60 394 450 450 (1) 2-600MCM (2) 3/0-500MCM
575V/60 339 350 350 (1) 2-600MCM (2) 3/0-500MCM
400V/50 394 450 450 (1) 2-600MCM (2) 3/0-500MCM

NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.

www.DaikinApplied.com 29 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Electrical Data

Table 15: Electrical Data - Multiple Point (60/50 Hz)


Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Model Voltage / Ratings Lug Range Ratings Lug Range
Size Frequency
Disconnect Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 78 100 100 (1) 14-2/0 (1) 12-1/0 78 100 100 (1) 14-2/0 (1) 4-300MCM
230V/60 78 100 100 (1) 14-2/0 (1) 12-1/0 78 100 100 (1) 14-2/0 (1) 4-300MCM
380V/60 46 60 60 (1) 14-2/0 (1) 12-1/0 46 60 60 (1) 14-2/0 (1) 12-1/0
030E
460V/60 39 50 50 (1) 14-2/0 (1) 12-1/0 39 50 50 (1) 14-2/0 (1) 12-1/0
575V/60 34 40 45 (1) 14-2/0 (1) 12-1/0 34 40 45 (1) 14-2/0 (1) 12-1/0
400V/50 40 50 50 (1) 14-2/0 (1) 12-1/0 40 50 50 (1) 14-2/0 (1) 12-1/0
208V/60 82 100 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
230V/60 82 100 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
380V/60 44 60 60 (1) 14-2/0 (1) 12-1/0 56 70 70 (1) 14-2/0 (1) 12-1/0
035E
460V/60 39 50 50 (1) 14-2/0 (1) 12-1/0 42 50 50 (1) 14-2/0 (1) 12-1/0
575V/60 32 40 40 (1) 14-2/0 (1) 12-1/0 35 45 45 (1) 14-2/0 (1) 12-1/0
400V/50 40 50 50 (1) 14-2/0 (1) 12-1/0 44 60 60 (1) 14-2/0 (1) 12-1/0
208V/60 88 110 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
230V/60 88 110 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
380V/60 56 70 70 (1) 14-2/0 (1) 12-1/0 56 70 70 (1) 14-2/0 (1) 12-1/0
040E
460V/60 42 50 50 (1) 14-2/0 (1) 12-1/0 42 50 50 (1) 14-2/0 (1) 12-1/0
575V/60 35 45 45 (1) 14-2/0 (1) 12-1/0 35 45 45 (1) 14-2/0 (1) 12-1/0
400V/50 44 60 60 (1) 14-2/0 (1) 12-1/0 44 60 60 (1) 14-2/0 (1) 12-1/0
208V/60 120 150 150 (1) 14-2/0 (1) 4-300MCM 120 150 150 (1) 14-2/0 (1) 6-350MCM
230V/60 120 150 150 (1) 14-2/0 (1) 4-300MCM 120 150 150 (1) 14-2/0 (1) 6-350MCM
380V/60 62 80 80 (1) 14-2/0 (1) 12-1/0 62 80 80 (1) 14-2/0 (1) 12-1/0
045E
460V/60 48 60 60 (1) 14-2/0 (1) 12-1/0 48 60 60 (1) 14-2/0 (1) 12-1/0
575V/60 39 50 50 (1) 14-2/0 (1) 12-1/0 39 50 50 (1) 14-2/0 (1) 12-1/0
400V/50 49 60 60 (1) 14-2/0 (1) 12-1/0 49 60 60 (1) 14-2/0 (1) 12-1/0
208V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 127 150 175 (1) 14-2/0 (1) 6-350MCM
230V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 127 150 175 (1) 14-2/0 (1) 6-350MCM
380V/60 69 90 90 (1) 14-2/0 (1) 12-1/0 69 90 90 (1) 14-2/0 (1) 12-1/0
050E
460V/60 58 70 80 (1) 14-2/0 (1) 12-1/0 58 70 80 (1) 14-2/0 (1) 12-1/0
575V/60 51 60 70 (1) 14-2/0 (1) 12-1/0 51 60 70 (1) 14-2/0 (1) 12-1/0
400V/50 56 70 70 (1) 14-2/0 (1) 12-1/0 56 70 70 (1) 14-2/0 (1) 12-1/0
208V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
230V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
380V/60 69 90 90 (1) 14-2/0 (1) 12-1/0 85 110 110 (1) 14-2/0 (1) 4-300MCM
055E
460V/60 58 70 80 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 12-1/0
575V/60 51 60 70 (1) 14-2/0 (1) 12-1/0 59 70 80 (1) 14-2/0 (1) 12-1/0
400V/50 56 70 70 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0
208V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
230V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
380V/60 85 110 110 (1) 14-2/0 (1) 4-300MCM 85 110 110 (1) 14-2/0 (1) 4-300MCM
060E
460V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 12-1/0
575V/60 59 70 80 (1) 14-2/0 (1) 12-1/0 59 70 80 (1) 14-2/0 (1) 12-1/0
400V/50 68 80 90 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0

NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 30 www.DaikinApplied.com


Electrical Data

Table 15 continued: Electrical Data - Multiple Point (60/50 Hz)


Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Model Voltage / Ratings Lug Range Ratings Lug Range
Size Frequency
Disconnect Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 141 175 175 (1) 14-2/0 (1) 6-350MCM 141 175 175 (1) 14-2/0 (1) 6-350MCM
230V/60 141 175 175 (1) 14-2/0 (1) 6-350MCM 141 175 175 (1) 14-2/0 (1) 6-350MCM
380V/60 85 110 110 (1) 14-2/0 (1) 4-300MCM 85 110 110 (1) 14-2/0 (1) 4-300MCM
065E
460V/60 68 80 90 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0
575V/60 59 70 80 (1) 14-2/0 (1) 12-1/0 59 70 80 (1) 14-2/0 (1) 12-1/0
400V/50 68 80 90 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0
208V/60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM
230V/60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM
380V/60 86 110 110 (1) 14-2/0 (1) 4-300MCM 86 110 110 (1) 14-2/0 (1) 4-300MCM
070E
460V/60 73 90 100 (1) 14-2/0 (1) 12-1/0 73 90 100 (1) 14-2/0 (1) 4-300MCM
575V/60 62 80 80 (1) 14-2/0 (1) 12-1/0 62 80 80 (1) 14-2/0 (1) 12-1/0
400V/50 73 90 100 (1) 14-2/0 (1) 12-1/0 73 90 100 (1) 14-2/0 (1) 4-300MCM
208V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 170 225 225 (1) 14-2/0 (1) 6-350MCM
230V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 170 225 225 (1) 14-2/0 (1) 6-350MCM
380V/60 92 110 125 (1) 14-2/0 (1) 4-300MCM 91 110 125 (1) 14-2/0 (1) 4-300MCM
075E
460V/60 80 100 110 (1) 14-2/0 (1) 4-300MCM 76 100 100 (1) 14-2/0 (1) 4-300MCM
575V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 65 80 90 (1) 14-2/0 (1) 12-1/0
400V/50 80 100 110 (1) 14-2/0 (1) 4-300MCM 76 100 100 (1) 14-2/0 (1) 4-300MCM
208V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 3/0-500MCM
230V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 3/0-500MCM
380V/60 98 125 125 (1) 14-2/0 (1) 4-300MCM 98 125 125 (1) 14-2/0 (1) 6-350MCM
080E
460V/60 80 100 110 (1) 14-2/0 (1) 4-300MCM 80 100 110 (1) 14-2/0 (1) 4-300MCM
575V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 4-300MCM
400V/50 80 100 110 (1) 14-2/0 (1) 4-300MCM 80 100 110 (1) 14-2/0 (1) 4-300MCM
208V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 3/0-500MCM
230V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 3/0-500MCM
380V/60 115 150 150 (1) 14-2/0 (1) 4-300MCM 115 150 150 (1) 14-2/0 (1) 6-350MCM
090E
460V/60 89 110 125 (1) 14-2/0 (1) 4-300MCM 89 110 125 (1) 14-2/0 (1) 4-300MCM
575V/60 78 100 110 (1) 14-2/0 (1) 4-300MCM 78 100 110 (1) 14-2/0 (1) 4-300MCM
400V/50 89 110 125 (1) 14-2/0 (1) 4-300MCM 89 110 125 (1) 14-2/0 (1) 4-300MCM
208V/60 215 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 215 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 129 175 175 (1) 14-2/0 (1) 6-350MCM 152 200 200 (1) 14-2/0 (2) 3/0-500MCM
100E
460V/60 96 125 125 (1) 14-2/0 (1) 4-300MCM 117 150 150 (1) 14-2/0 (1) 6-350MCM
575V/60 87 110 110 (1) 14-2/0 (1) 4-300MCM 105 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 96 125 125 (1) 14-2/0 (1) 4-300MCM 117 150 150 (1) 14-2/0 (1) 6-350MCM
208V/60 259 350 350 (1) 2-600MCM (2) 3/0-500MCM 259 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 259 350 350 (1) 2-600MCM (2) 3/0-500MCM 259 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 156 200 225 (1) 14-2/0 (1) 6-350MCM 156 200 225 (1) 14-2/0 (2) 3/0-500MCM
110E
460V/60 120 150 175 (1) 14-2/0 (1) 6-350MCM 120 150 175 (1) 14-2/0 (1) 6-350MCM
575V/60 108 150 150 (1) 14-2/0 (1) 4-300MCM 108 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 120 150 175 (1) 14-2/0 (1) 6-350MCM 120 150 175 (1) 14-2/0 (1) 6-350MCM

NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.

www.DaikinApplied.com 31 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Electrical Data

Table 15 continued: Electrical Data - Multiple Point (60/50Hz)


Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Model Voltage / Ratings Lug Range Ratings Lug Range
Size Frequency
Disconnect Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 281 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 281 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 174 225 225 (1) 14-2/0 (1) 6-350MCM 174 225 225 (1) 14-2/0 (2) 3/0-500MCM
120E
460V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 123 150 150 (1) 14-2/0 (1) 4-300MCM 123 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 316 400 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 316 400 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 174 225 225 (1) 14-2/0 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 3/0-500MCM
130E
460V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 160 200 225 (1) 14-2/0 (2) 3/0-500MCM
575V/60 123 150 150 (1) 14-2/0 (1) 4-300MCM 128 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 137 175 175 (1) 14-2/0 (1) 6-350MCM 160 200 225 (1) 14-2/0 (2) 3/0-500MCM
208V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 324 400 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 324 400 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 3/0-500MCM
140E
460V/60 164 200 225 (1) 14-2/0 (1) 6-350MCM 164 200 225 (1) 14-2/0 (2) 3/0-500MCM
575V/60 131 175 175 (1) 14-2/0 (1) 6-350MCM 131 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 164 200 225 (1) 14-2/0 (1) 6-350MCM 164 200 225 (1) 14-2/0 (2) 3/0-500MCM
208V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 351 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 351 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 3/0-500MCM
150E
460V/60 164 200 225 (1) 14-2/0 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 3/0-500MCM
575V/60 131 175 175 (1) 14-2/0 (1) 6-350MCM 134 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 164 200 225 (1) 14-2/0 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 3/0-500MCM
208V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 358 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 358 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 3/0-500MCM
160E
460V/60 165 200 200 (1) 14-2/0 (1) 6-350MCM 165 200 200 (1) 14-2/0 (2) 3/0-500MCM
575V/60 146 175 175 (1) 14-2/0 (1) 6-350MCM 146 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 165 200 200 (1) 14-2/0 (1) 6-350MCM 165 200 200 (1) 14-2/0 (2) 3/0-500MCM
208V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 405 500 500 (1) 2-600MCM (2) 3/0-500MCM
230V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 405 500 500 (1) 2-600MCM (2) 3/0-500MCM
380V/60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 3/0-500MCM
170E
460V/60 165 200 200 (1) 14-2/0 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM
575V/60 146 175 175 (1) 14-2/0 (1) 6-350MCM 176 200 225 (1) 2-600MCM (1) 6-350MCM
400V/50 165 200 200 (1) 14-2/0 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM
208V/60 453 500 500 (2) 6-500MCM (2) 3/0-500MCM 453 500 500 (2) 6-500MCM (2) 3/0-500MCM
230V/60 453 500 500 (2) 6-500MCM (2) 3/0-500MCM 453 500 500 (2) 6-500MCM (2) 3/0-500MCM
380V/60 248 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 300 (1) 2-600MCM (2) 3/0-500MCM
180E
460V/60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM
575V/60 176 200 225 (1) 2-600MCM (1) 6-350MCM 176 200 225 (1) 2-600MCM (2) 3/0-500MCM
400V/50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM

NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 32 www.DaikinApplied.com


Unit Controller Operation

Unit Controller Operation

General Description
The MicroTech® III controller’s design not only permits Security protection prevents unauthorized changing of the
the chiller to run more efficiently, but also can simplify setpoints and control parameters.
troubleshooting if a system failure occurs. Every MicroTech® MicroTech® III control continuously performs self-diagnostic
IIII controller is programmed and tested prior to shipment to checks, monitoring system temperatures, pressures and
facilitate start-up. protection devices, and will automatically shut down a
The controller menu structure is separated into three distinct compressor or the entire unit should a fault occur. The cause
categories that provide the operator or service technician with of the shutdown will be retained in memory and can be easily
a full description of: displayed in plain English for operator review. The MicroTech®
III chiller controller will also retain and display the date/time the
1. current unit status
fault occurred. In addition to displaying alarm diagnostics, the
2. control parameters MicroTech® III chiller controller also provides the operator with
3. alarms a warning of limit (pre-alarm) conditions.

System Architecture
The overall controls architecture uses the following:
• One MicroTech® III unit controller
• I/O extension modules as needed depending on the
configuration of the unit
• Communications interface(s) as needed based on
installed options
Communication interface modules will connect directly to the
left side of the unit controller. I/O extensions will connect
via peripheral bus using the connection on the right side of
the controller. All of the I/O extension modules can connect
directly or using a wiring harness.

Figure 36: System Architecture

BAS Interface BAS Interface BAS Interface


(Bacnet, Lon, (Bacnet, Lon, (Bacnet, Lon, MicroTech® III Controller - UC
Modbus) Modbus) Modbus)

Peripheral Bus

I/O Extension
I/O Extension
EEXV1
CC1

I/O Extension I/O Extension I/O Extension


CC2 EEXV 2 RapidRestore®

www.DaikinApplied.com 33 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Controller Operation

Controller Inputs and Outputs Table 21: Digital Inputs

Description Signal Off Signal On


Main Controller X6 Circuit 1 Switch Circuit Disable Circuit Enable
X7 Circuit 1 MHP Switch Fault No fault
Table 16: Analog Inputs
Circuit 1 Motor
X8 Fault No fault
# Description Signal Type Expected Range Protection
AI1 Evaporator EWT NTC 10k 340 to 300k Ω Circuit 1 (or Unit) PVM/
DI1 Fault No fault
AI2 Evaporator LWT NTC 10k 340 to 300k Ω GFP
AI3 Ambient Temp NTC 10k 340 to 300k Ω NOTE: The Motor Protection and MHP input signal are wired
X1 Demand Limit 4-20 mA 1 to 23 mA
in series. If Motor Protection input is open, MHP
Switch input will also be open.
X4 LWT Reset 4-20 mA 1 to 23 mA

Table 22: Digital Outputs


Table 17: Analog Outputs
Description Output Off Output On
# Description Signal Type Range
DO1 Compressor #1 Compressor Off Compressor On
X5 Circuit 1 Fan VFD Speed Voltage 0 to 10 volts
DO2 Compressor #3 Compressor Off Compressor On
X6 Circuit 2 Fan VFD Speed Voltage 0 to 10 volts
DO3 Compressor #5 Compressor Off Compressor On
Evaporator Water
Table 18: Digital Inputs DO4 Pump Off Pump On
Pump 2
Description Signal Off Signal On Circuit 1 Hot Gas
DO5 Solenoid Closed Solenoid Open
DI1 External Alarm/Event Ext. Fault No Ext. Fault Bypass SV

DI2 Evaporator Flow Switch No Flow Flow Circuit 1 Liquid


DO6 Solenoid Closed Solenoid Open
Line SV
Double Set Point/ Mode See sections on Unit Mode
DI3
Switch Selection and LWT Target
DI4 Remote Switch Remote Disable Remote Enable
Compressor Module 2
DI5 Unit Switch Unit Disable Unit Enable Table 23: Analog Inputs

Expected
Table 19: Digital Outputs Description Signal Type
Range
Description Output Off Output On Circuit 2 Suction
X1 NTC 10k 340 to 300k Ω
DO1 Evaporator Water Pump 1 Pump Off Pump On Temperature
DO2 Alarm Indicator Alarm Not Active Alarm Active Circuit 2 Evaporator
X2 Voltage 0.4 to 4.6 volts
Pressure
DO3 Circuit 1 Fan Output 1 Fan(s) Off Fan(s) On
Circuit 2 Condenser
DO4 Circuit 1 Fan Output 2 Fan(s) Off Fan(s) On X4 Voltage 0.4 to 4.6 volts
Pressure
DO5 Circuit 1 Fan Output 3 Fan(s) Off Fan(s) On
DO6 Circuit 1 Fan Output 4 Fan(s) Off Fan(s) On Table 24: Digital Inputs
DO7 Circuit 2 Fan Output 1 Fan(s) Off Fan(s) On
Description Signal Off Signal On
DO8 Circuit 2 Fan Output 2 Fan(s) Off Fan(s) On
X6 Circuit 2 Switch Circuit Disable Circuit Enable
DO9 Circuit 2 Fan Output 3 Fan(s) Off Fan(s) On
X7 Circuit 2 MHP Switch Fault No fault
DO10 Circuit 2 Fan Output 4 Fan(s) Off Fan(s) On
Circuit 2 Motor
X7 Circuit 1 Condenser SV 1 Solenoid Closed Solenoid Open X8 Fault No fault
Protection
X8 Circuit 2 Condenser SV 1 Solenoid Closed Solenoid Open
DI1 Circuit 2 PVM/GFP Fault No fault
NOTE: The Motor Protection and MHP input signal are wired
Compressor Module 1 in series. If Motor Protection input is open, MHP
Table 20: Analog Inputs Switch input will also be open.

Description Signal Type Expected Range


Circuit 1 Suction
X1 NTC 10k 340 to 300k Ω
Temperature
Circuit 1 Evaporator
X2 Voltage 0.4 to 4.6 volts
Pressure
Circuit 1 Condenser
X4 Voltage 0.4 to 4.6 volts
Pressure

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 34 www.DaikinApplied.com


Unit Controller Operation

Table 25: Digital Outputs RapidRestore®


Description Output Off Output On This module will be used only when the unit is equipped with
DO1 Compressor #2 Compressor Off Compressor On the RapidRestore® option.
DO2 Compressor #4 Compressor Off Compressor On
DO3 Compressor #6 Compressor Off Compressor On Table 28: Digital Inputs
Circuit 2 Hot Gas Description Signal Off Signal On
DO5 Solenoid Closed Solenoid Open
Bypass SV
RapidRestore Disable Allow RapidRestore
DO6 Circuit 2 Liquid Line SV Solenoid Closed Solenoid Open DI1
Enable RapidRestore Enabling
Backup Chiller Not Backup
EXV Module 1 and 2 DI2
Designation Chiller
Backup Chiller

These modules will be used only when the expansion valve


type is electronic.
Sensor Information
Table 26: Digital Outputs

Description Output Off Output On Pressure


DO1 Circuit 1 Fan Output 5 Fan(s) Off Fan(s) On Pressure inputs will be read using 0 to 5 volt ratiometric
sensors. Nominal voltage range will be 0.5 to 4.5 volts.
Table 27: Stepper Motor Output

Description
M1+, M1- EXV Stepper Coil 1
M2+, M2- EXV Stepper Coil 2

www.DaikinApplied.com 35 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Controller Operation

Set Points
Set points are initially set to the values in the Default column, not be needed and therefore not be visible.
and can be adjusted to any value in the Range column. Set Basic unit configuration set points will require the unit to be
points are stored in permanent memory. If an option is not off in order to make a change and then require rebooting the
available on a specific model size, the respective set point will controller in order to apply a change.
Table 29: Unit Level Set Point Defaults and Ranges
Description Default Range
Basic Unit Configuration
Unit Model AGZ000??? See Unit Model Configuration Section
Condenser Type Not Set Not Set Tube and Fin, Microchannel
Expansion Valve Type Not Set Not Set., Thermal, Electronic
Condenser Fan VFD Disable Disable, Enable
Power Connection Configuration Single Point Single Point, Multi Point
Mode/Enabling
Unit Enable Enable Disable, Enable
Control source Local Local, Network
Available Modes Cool Cool, Cool w/Glycol, Cool/Ice w/Glycol, Ice, Test
Staging and Capacity Control
Cool LWT 1 7°C (44.6°F) See Dynamic Set Point Ranges
Cool LWT 2 7°C (44.6°F) See Dynamic Set Point Ranges
Ice LWT 4.4°C (39.9°F) -9.5 to 4.4 °C (14.9 to 39.9 °F)
Startup Delta T 5.6°C (10.1°F) 0.6 to 8.3 °C (1.1 to 14.9 °F)
Shut Down Delta T 0.3°C (0.5°F) 0.3 to 1.7 °C (0.5 to 3.1 °F)
Stage Up Delay 240 sec 120 to 480 sec
Stage Down Delay 30 sec 20 to 60 sec
Stage Delay Clear No No, Yes
Max Pulldown Rate 0.6°C/min (1.1°F/min) 0.1 to 2.7°C/min (0.2 to 4.9°F/min)
Full Capacity Evap Delta T 8.9 °C (16°F) 3.3 to 8.9 °C (5.9 to 16 °F)
Variable Evaporator Flow No No, Yes
Ice TimCycle Delay 12 1-23 hours
Clear Ice Timer No No,Yes
RapidRestore Disable Disable, Enable
Rapid Restore Max Power Off 15 seconds 15 ro 180 seconds
Evaporator Pump Control
Evap Pump Control Configuration #1 Only #1 Only, #2 Only, Auto, #1 Primary, #2 Primary
Evap Recirc Timer 30 15 to 300 seconds
Evap Pump 1 Run Hours 0 0 to 999999 hours
Evap Pump 2 Run Hours 0 0 to 999999 hours
Power Conservation and Limits
LWT Reset Enable Disable Disable, Enable
Demand Limit Enable Disable Disable, Enable
High IPLV Mode Disable Disable, Enable
IPLV Condensiong Target 23.89°C (75°F) 21.11 to 32.22°C (70 to 90°F)
Unit Sensor Offsets
Evap LWT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Evap EWT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
OAT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Circuit Configuration Timers
Start to start Time Delay 15 min 10-60 minutes
Stop to start Time Delay 5 min 3-20 minutes
Clear Cycle Timers No No, yes
Alarm and Limit Settings - Units
Evaporator Water Freeze 2.2°C (36°F) See Dynamic Set Point Ranges
Evaporator Flow Proof 5 sec 5 to 15 sec
Evaporator Recirculate Timeout 3 min 1 to 10 min
External Fault Configuration Event Event, Alarm
Low Ambient Lockout 1.7°C (35.1°F) See Dynamic Set Point Ranges
Low Ambient Lockout BAS Alert Off Off, On

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 36 www.DaikinApplied.com


Unit Controller Operation

Alarm and Limit Settings - Circuits


Low Evap Pressure Unload 689.5 KPA (100 PSI) See Dynamic Set Point Ranges
Low Evap Pressure Hold 696.4 KPA (101 PSI) See Dynamic Set Point Ranges
High Condenser Pressure 4240 KPA (615 PSI) 3310 to 4275 KPA (480 to 620 PSI)
High Condenser Pressure Unload 4137 KPA (600 PSI) 3241 to 4137 KPA (470 to 600 PSI)
Low OAT Start Time 165 sec 150 to 240 sec
BAS Control Inputs
Network Unit Enable Disable Disable, Enable
Network Mode Command Cool Cool, Ice
Network Cool Set Point 7°C (44.6°F) See Dynamic Set Point Ranges
Network Ice Set Point 4.4°C (39.9°F) -9.5 to 4.4 °C (14.9 to 39.9 °F)
Network Capacity Limit 100% 0 to 100%
Network Alarm Clear Command Normal Normal, Clear Alarm

Dynamic Set Point Ranges


The following settings have different ranges of adjustment based on other settings.

Table 30: Cool LWT 1 and Cool LWT2 Set Point Ranges
Available Mode Selection Unit Vintage/Amp Rating Range
Without Glycol E vintage 4.4 to 18.34°C (39.9 to 65°F)
With Glycol E vintage -9.5 to 18.34°C (14.9 to 65°F)

Table 31: Evaporator Water Freeze


Available Mode Selection Range
Without Glycol 2.2 to 5.6°C (36 to 42.1°F)
With Glycol -10.8 to 5.6°C (12.6 to 42.1°F)

Table 32: Low Ambient Lockout


Fan VFD Range
Disable 0 to 15.6°C (32 to 60.1°F)
Enable -23.3 to 15.6°C (-9.9 to 60.1°F)

Table 33: Low Evaporator Pressure


Available Mode Selection Range
Hold - Without Glycol 669 to 793 KPA (97 to 115 PSI)
Hold - With Glycol 317 to 793 KPA (46 to 115 PSI)
Unhold - Without Glycol 669 to 793 KPA (97 to 115 PSI)
Unhold - With Glycol 317 to 793 KPA (46 to 115 PSI)

Table 34: Design Conditions

Description Default Range


Design Evaporator EWT 0°C (32°F) -64°C to 64°C (-83.2°F to 147.2°F)
Design Evaporator LWT 0°C (32°F) -64°C to 64°C (-83.2°F to 147.2°F)
Design Evaporator Water Flow 0 lph 0 to 600000 lph
Design Evaporator Approach Circuit 1/2 0°C (32°F) -64°C to 64°C (-115.2°F to 115.2°F)
Design Ambient Temperature 0°C (32°F) -64°C to 64°C (-115.2°F to 115.2°F)
Design Condenser Approach Circuit 1/2 0 0°C (32°F) -64°C to 64°C (-115.2°F to 115.2°F)
Design Full Load Efficiency 0% 0 to 100%
Design IPLV 0 -64 to 64
Design Rated Capacity 0 tons 0 to 10000 tons

www.DaikinApplied.com 37 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Controller Operation

Table 35: Administration and Service Support

Description Default Range


Unit G.O. Number “Enter Data” Alphanumeric string of up to 16 characters
Unit Serial Number “Enter Data” Alphanumeric string of up to 20 characters
Next Maintenance Month January January through December
Next Maintenance Year 2009 2009 - 2100
Service Support Reference 999-999-9999 Any 10 digit phone number
Controller Time From Controller Timeclock 00:00:00 to 23:59:59
Controller Date From Controller Timeclock 1/1/2000 to 12/31/2050
UTC Difference -60 minutes -3276 to 32767 minutes
Daylight Savings Time Enable Yes No, Yes
Daylight Savings Time Start Month March January through December
Daylight Savings Time Start Week 2nd Week 1st through 5th Week
Daylight Savings Time End Month November January through December
Daylight Savings Time End Week 1st Week 1st through 5th Week
Operator Password Disable Off Off, On
Apply Changes No No, Yes
Active Alarm Clear Off Off, On
Alarm Log Clear No No, Yes
Power Restore Event Log - Day Selection Current Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
Display Units English English, Metric

Table 36: Unit Test Mode Set Points

Description Default Range


Test Unit Alarm Output Off Off, On
Test Evaporator Pump Output 1 Off Off, On
Test Evaporator Pump Output 2 Off Off, On
NOTE: Unit test mode set points can be changed only when the unit mode is in Test. When the unit mode is no longer Test, all
unit test mode set points will be changed back to the ‘off’ values.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 38 www.DaikinApplied.com


Unit Controller Operation

Table 37: Commincation Configuration

Description Default Range


Controller IP DHCP On Off, On
Controller IP Network Address 192.168.001.042 000.000.000.000 to 255.255.255.255
Controller IP Network Mask 255.255.255.000 000.000.000.000 to 255.255.255.255
Controller IP Network Gateway 192.168.001.001 000.000.000.000 to 255.255.255.255
Lon Module Maximum Send Time 0 seconds 0 to 6553.4 seconds
Lon Module Minimum Send Time 0 seconds 0 to 6553.4 seconds
Lon Module Receive Heartbeat 0 seconds 0 to 6553.4 seconds
BACnet Module Name Alphanumeric string up to 15 characters long
BACnet Module Dev Instance 0 0 to 4194302
BACnet Module Unit Support English Metric, English
BACnet Module NC Dev 1 0 0 to 42949672
BACnet Module NC Dev 2 0 0 to 42949672
BACnet Module Reset Out of Service Done Done, False, True
BACnet IP Module UDP Port 0 0 to 65535
BACnet IP Module DHCP Off Off, On
BACnet IP Module Network Address 000.000.000.000 to 999.999.999.999
BACnet IP Module Network Mask 000.000.000.000 to 999.999.999.999
BACnet IP Module Network Gateway 000.000.000.000 to 999.999.999.999
BACnet MSTP Module Address 0 0 to 127
BACnet MSTP Module Baud Rate 38400 9600, 19200, 38400, 76800
BACnet MSTP Module Max Master 0 0 to 127
BACnet MSTP Module Max Info Frm 0 0 to 255
Modbus Module Address 1 1 to 247
Modbus Module Baud Rate 19200 4800, 9600, 19200, 38400
Modbus Module Parity Even Even, Odd, None
Modbus Module Two Stop Bits No No, Yes
Modbus Module Response Delay 0 milliseconds 0 to 30000 milliseconds
Modbus Module Comm LED Time Out 0 seconds 0 to 3600 seconds
AWM DHCP Off Off, On
AWM Network Address 000.000.000.000 to 999.999.999.999
AWM Network Mask 000.000.000.000 to 999.999.999.999
AWM Network Gateway 000.000.000.000 to 999.999.999.999

www.DaikinApplied.com 39 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Controller Operation

Circuit Level Set Points


The settings in this section all exist for each individual circuit.

Table 38: Set Points for Individual Circuits

Description Default Range


Mode/Enabling
Circuit mode Enable Disable, Enable, Test
Compressor 1 Enable Auto Auto, off
Compressor 2 Enable Auto Auto, off
Compressor 3 Enable Auto Auto, off
EXV Settings
EXV control Auto Auto, manual
EXV position See Special Setpoints 0% to 100%
Suction SH Target 5.56°C (10°F) 4.44 to 6.67 °C (8 to 12 °F)
Max Evap Pressure 1076 KPA(156.1 PSI) 979 to 1172 KPA (142 to 170 PSI)
Condenser Control
Condenser Target 100% 37.8°C (100°F) 37.88 to 46.1°C (100 to 115°F)
Condenser Target 67% (2) 32.2°C (90°F) See Dynamic Set Point Ranges
Condenser Target 50% (1) See Dynamic Set Point Ranges See Dynamic Set Point Ranges
Condenser Target 33% (2) See Dynamic Set Point Ranges See Dynamic Set Point Ranges
VFD Max Speed 100% 90 to 110%
VFD Min Speed 25% 25 to 60%
Fan Stage Up Deadband 1 See Dynamic Set Point Ranges 11.1 to 13.9°C (15 to 25°F)
Fan Stage Up Deadband 2 See Dynamic Set Point Ranges See Dynamic Set Point Ranges
Fan Stage Up Deadband 3 5.56°C (10°F) 5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Up Deadband 4 5.56°C (10°F) 5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Down Deadband 1 11.11°C (20°F) 8.33 to11.11 °C (15 to 20 °F)
Fan Stage Down Deadband 2 5.56°C (10°F) 5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Down Deadband 3 5.56°C (10°F) 3.33 to 5.56 °C (6 to 10 °F)
Fan Stage Down Deadband 4 5.56 °C (10 °F) 3.33 to 5.56 °C (6 to 10 °F)
Sensor Offsets
Evap pressure offset 0 KPA (0 PSI) -100 to 100 KPA (-14.5 to 14.5 PSI)
Cond pressure offset 0 KPA (0 PSI) -100 to 100 KPA (-14.5 to 14.5 PSI)
Suction temp offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
BAS Control Inputs
Network Compressor 1 Enable Enable Enable, Disable
Network Compressor 2 Enable Enable Enable, Disable
Network Compressor 3 Enable Enable Enable, Disable
NOTE: 1. Condenser Target 50% will be available only when the unit has 4 compressors..
2. Condenser Targets 33 and 67% will be available only when the unit has 6 compressors.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 40 www.DaikinApplied.com


Unit Controller Operation

Dynamic Set Point Ranges and Defaults Special Set Point Operation
Some settings have different ranges of adjustment based on The EXV position set point is not changeable unless the unit
other parameters. switch is off.
Table 39: Condenser Target 33% EXV Position set point on each circuit follows the actual EXV
Unit Model Default Range position while EXV Control = Auto. When EXV Control =
Manual, the position set point should be changeable.
Models 30 to 70 32.2°C (90°F) 32.2 to 40.56 °C (90 to 105 °F)
Models 75 to 180 29.4°C (85°F) 29.4 to 40.56 °C (85 to 105 °F)
Security
Table 40: Condenser Target 50% All set points are protected using passwords. A four-digit
password provides operator access to changeable parameters.
Unit Model Default Range
Service level passwords are reserved for authorized service
Models 30 to 70 32.2°C (90°F) 32.2 to 40.56 °C (90 to 105 °F) personnel.
Models 75 to 180 29.4°C (85°F) 29.4 to 40.56 °C (85 to 105 °F)
Operator password: 2526

Table 41: Condenser Target 67% Entering Passwords


Unit Model Range Passwords are entered on the first screen on the unit
Models 30 to 70 32.2 to 46.1°C (90 to 115 °F) controller,
Models 75 to 180 32.2 to 43.3°C (90 to 110 °F) If the wrong password is entered, a message will temporarily
appear stating this. If no valid password is active the active
Table 42: Fan Stage Down Deadband 1 password level displays “none.”

Unit Model Default


Editing Setpoints
Models 30 to 70 11.1°C (20°F)
After a valid password has been entered at the unit controller,
Models 75 to 180 8.3°C (15°F)
set points may be changed. If the operator attempts to edit a
set point for which the necessary password level is not active,
Table 43: an Stage Down Deadband 2 no action will be taken.
Unit Model Default Range Once a password has been entered, it remains valid for 10
Models 30 to 70 5.6°C (10°F) 5.6 to 8.3°C (10 to 15°F) minutes after the last key-press on the unit controller.
Models 75 to 180 8.3°C (15°F) 8.3 to 11.1°C (15 to 20°F)

www.DaikinApplied.com 41 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Sequence of Operation

Sequence of Operation

Figure 37: Unit Sequence of Operation - Cool Mode

Unit power up

Unit in Off state


The chiller may be disabled via the unit switch, the remote switch, the keypad
enable setting, or the BAS network. In addition, the chiller will be disabled if all
No circuits are disabled, or if there is a unit alarm. If the chiller is disabled, the unit
status display will reflect this and also show why it is disabled.

Is unit enabled? If the unit switch is off, the unit status will be Off:Unit Switch. If the chiller is
Yes disabled due to network command, the unit status will be Off:BAS Disable. When
the remote switch is open, the unit status will be Off:Remote Switch. When a unit
alarm is active, the unit status will be Off:Unit Alarm. In cases where no circuits
Yes are enabled, the unit status will be Off:All Cir Disabled. If the unit is disabled via
the Chiller Enable set point, the unit status will be Off:Keypad Disable.

Low ambient lockout will prevent the chiller from starting even if it is otherwise
Is low ambient lockout
enabled. When this lockout is disabling the chiller, the unit status will be Off:Low
active?
OAT Lock.

No

If the chiller is enabled, then the unit will be in the Auto state and the evaporator
Evaporator pump output on
water pump output will be activated.

No

The chiller will then wait for the flow switch to close, during which time the unit
Is flow present? status will be Auto:Wait for flow.

Yes

After establishing flow, the chiller will wait some time to allow the chilled water
Wait for chilled water loop to
recirculate loop to recirculate for an accurate reading of the leaving water temperature.
The unit status during this time is Auto:Evap Recirculate.

Pump output remains on


while chiller is enabled

Is Motor Protection If the chiller is waiting on the motor protection delay after powering up, the unit
delay active? status will be Off: Motor Protection Delay.

Yes

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 42 www.DaikinApplied.com


Sequence of Operation

Figure 37: Unit Sequence of Operation - Cool Mode (continued)

Keep pump output on while


chiller is enabled and either
running or ready to run.

No
The chiller is now ready to start if enough load is present. If the LWT is not higher
than the start up temperature, the unit status will be Auto:Wait for load.
Is there enough load to
start chiller?
If the LWT is higher than the start up temperature, the unit status will become
Auto. A circuit can start at this time.

Yes

The first circuit to start is generally the available circuit with the least number of
Start first circuit.
starts. This circuit will go through its start sequence at this point.

Maintain unit capacity.

No

Additional capacity The unit capacity can be increased if the LWT is above the stage up temperature.
needed to satisfy load?
No

Yes No

Has the stage up time


delay expired?
A minimum time must pass between the starting of circuits.

Yes
If the second circuit is not running, it will be started now. The unit will try to keep
the load balanced between circuits as the unit capacity is increased.
Increase unit capacity.
If both circuits are running, then additional compressors will start based on the
sequencing logic.

Unit at full capacity?

Yes

www.DaikinApplied.com 43 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Sequence of Operation

Figure 37: Unit Sequence of Operation - Cool Mode (continued)

Yes

Maintain unit capacity.

No

Can less circuits handle


The unit capacitycan be decreasedif the LWTis below the stage down
the load? temperature.
No

Yes

Has the stage down


A minimum time must pass between decreases in unit capacity.
time delay expired?

Yes

Decrease unit capacity Compressors will shut off as needed in the order determined by sequencing logic.

Is unit running at
minimum capacity?

Yes

Maintain unit capacity

No

When only one compressor is running, the load may drop off to the point where even
Is load satisfied? minimum unit capacity is too much. The load has been satisfied when the LWT
drops below the shutdown temperature. At this time the only running circuit can
shut down.

Yes

Shut down last circuit. The last circuit running now shuts down.

When last circuit has completed pumpdown, the unit will go back to waiting for
All circuits off.
enough load to start.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 44 www.DaikinApplied.com


Sequence of Operation

Figure 38: Unit Sequence of Operation - Ice Mode

Unit power up

Unit in Off state


The chiller may be disabled via the unit switch, the remote switch, the keypad
enable setting, or the BAS network. In addition, the chiller will be disabled if all
No circuits are disabled, or if there is a unit alarm. If the chiller is disabled, the unit
status display will reflect this and also show why it is disabled.

Is unit enabled? If the unit switch is off, the unit status will be Off:Unit Switch. If the chiller is
Yes disabled due to network command, the unit status will be Off:BAS Disable. When
the remote switch is open, the unit status will be Off:Remote Switch. When a unit
alarm is active, the unit status will be Off:Unit Alarm. In cases where no circuits
Yes are enabled, the unit status will be Off:All Cir Disabled. If the unit is disabled via
the Chiller Enable set point, the unit status will be Off:Keypad Disable.
No

Low ambient lockout will prevent the chiller from starting even if it is otherwise
Is low ambient lockout enabled. When this lockout is disabling the chiller, the unit status will be Off:Low
active?
OAT Lock.

No

Is Ice Mode Start Delay A delay is required between Ice cycles.


expired?

Yes

If the chiller is enabled, then the unit will be in the Auto state and the evaporator
Evaporator pump output on
water pump output will be activated.

No

The chiller will then wait for the flow switch to close, during which time the unit
Is flow present? status will be Auto:Wait for flow.

Yes

After establishing flow, the chiller will wait some time to allow the chilled water loop
Wait for chilled water loop to
recirculate. to recirculate for an accurate reading of the leaving water temperature. The unit
status during this time is Auto:Evap Recirc.

www.DaikinApplied.com 45 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Sequence of Operation

Figure 38: Unit Sequence of Operation - Ice Mode (continued)

Pump output remains on


while chiller is enabled.

Yes

Is Motor Protection If the chiller is waiting on the motor protection delay after powering up, the unit
delay active? status will be Off:Motor Protection Delay.

No

Keep pump output on while


chiller is enabled and either
running or ready to run.

No

The chiller is now ready to start if enough load is present. If the LWT is not higher
than the startup temperature, the unit status will be Auto:Wait for load.
Is fluid temp high
enough to start?
If the LWT is higher than the startup temperature, the unit status will be Auto.
A circuit can start at this time.

Yes

Start first circuit.

The first circuit to start is generally the circuit which contains the compressor with
the least number of starts. This circuit will go through it’s start sequence at this
Maintain unit capacity. point.

No

Has the stage up time A minimum time must pass between the starting of circuits.
delay expired?

No

Yes

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 46 www.DaikinApplied.com


Sequence of Operation

Figure 38: Unit Sequence of Operation - Ice Mode (continued)

No
Yes
If the second circuit is not running, it will be started now. The unit will try to keep
the load balanced between circuits as the unit capacity is increased.
Increase unit capacity.
If both circuits are running, then additional compressors will start based on the
sequencing logic.

Unit at full capacity?

Yes

Maintain unit capacity.

No

Is the ice cycle


Ice building is complete when LWT is less than the Active Setpoint.
complete?

Yes

Begin normal shut down of


All circuits begin the shut down sequence simultaneously.
all circuits.

When all circuits have completed shutdown, the unit will remain in the off state until
All circuits off.
the start conditions are satisfied again.

www.DaikinApplied.com 47 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Sequence of Operation

Figure 39: Circuit Sequence of Operation

Unit power up

When the circuit is in the Off state the EXV is in the closed position, compressors are
Circuit is in Off state off, solenoid valves are closed, and all condenser fans are off.

No
The circuit must be enabled before it can run. It might be disabled for several
reasons. When the circuit switch is off, the status will be Off:Circuit Switch.
Is circuit is enabled to If the circuit has an active stop alarm then the status will be Off:Alarm. If the circuit
start?
has been disabled via the circuit mode set point, the status will be Off:Keypad
Yes
Disable. If all compressors are disabled via the settings, the circuit status will be
Off:All Comp Disable.
Yes

A minimum time must pass between the previous start and stop of a compressor
and the next start. If this time has not passed, a cycle timer will be active. If all
Are all compressor cycle
timers active? compressors on the circuit have active cycle timers the circuit status will be
Off:Cycle Timers.

No

Circuit is ready to start If the circuit is ready to start when needed, the circuit status will be
Off:Ready.

No

Capacity control logic at the unit level will determine when a circuit needs to start
Is circuit commanded to
start? and issue a start command to the next circuit to start based on sequencing rules.

Yes

Yes

No Before the first compressor on a circuit can start, the EXV performs a brief preopen.
Preopen EXV
The circuit status during this time will be Preopen.

The first compressor will be started and the fans, solenoid valves, and other
Run circuit
devices will be controlled as needed. The normal circuit status at this time will be
Run:Normal. Additional compressors will be started as needed per the unit level
capacity control.
No

Is last compressor Capacity control logic at the unit level will determine when a compressor needs to
commanded to shut down and issue a stop command to the next compressor to stop based on
shut down? sequencing rules. If this compressor is the last one on the circuit, the circuit will
need to shut down.

Yes

When the circuit needs to shut down, a pumpdown of the circuit will NOT be
Is condenser type performed if the condenser coil is Microchannel type. When the circuit needs to
tube and fin? shut down and the condenser is Microchannel type, everything will turn off on the
circuit at approximately the same time.

Yes

When the circuit needs to shut down, a pumpdown of the circuit will be performed
Pumpdown circuit if the condenser coil is tube and fin type. The circuit status during this time will be
Run:Pumpdown.

No

Pumpdown is complete when the evaporator pressure drops to a certain point or


Is pumpdown
complete?
the circuit has been pumping down for longer than the pumpdown time limit.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 48 www.DaikinApplied.com


Unit Functions

Unit Functions

The calculations in this section are used in unit level control means the flow that is needed for a 5.56°C (10°F) delta T at full
logic or in control logic across all circuits. unit capacity.

Evaporator Delta T Table 44: Minimum Flows and Corresponding Maximum


The evaporator water delta T is calculated as entering water Effective Full Capacity Delta T
temperature minus leaving water temperature. Number of Unit Minimum Flow Max Effective Full
Compressors Capacity (nominal %) Capacity DT
LWT Slope 100% 62.5% 8.9 °C (16 °F)
LWT slope is calculated such that the slope represents the 75% 55% 10.1 °C (18.2 °F)
estimated change in LWT over a time frame of one minute. 4
50% 47.5% 11.7 °C (21.1 °F)

Pulldown Rate 25% 40% 13.9 °C (25 °F)


100% 62.5% 8.9 °C (16 °F)
The slope value calculated above will be a negative value
as the water temperature is dropping. A pulldown rate is 83.3% 58% 9.59 °C (17.3 °F)
calculated by inverting the slope value and limiting to a 66.7% 53.5% 10.39 °C (18.7 °F)
minimum value of 0°C/min. 6
50% 49% 11.35 °C (20.4 °F)
33.3% 44.5% 12.49 °C (22.5 °F)
LWT Error
16.7% 40% 13.9 °C (25 °F)
LWT error is calculated as LWT – LWT target.
For variable evaporator flow, the Control Band is calculated as
follows:
Unit Capacity
1. Effective Full Capacity Delta T = (Full Capacity Evap
For applying unit capacity limits, an estimate of total unit
Delta T* 100) /Unit Capacity
capacity is needed. Unit capacity will be based on the
estimated circuit capacities. 2. If above value is more than the Max Effective
Full Capacity dT listed in the table above for the
The unit capacity is the number of compressors running (on
corresponding unit capacity, it is set equal to the value in
circuits that are not pumping down) divided by the number of
the table.
compressors on the unit.
3. Effective Full Capacity Delta T with the limit applied is
Control Band then multiplied by 0.35 for units with four compressors
and by 0.25 for units with six compressors. This gives
The Control Band defines the band in which unit capacity will the total control band for the unit configuration and actual
not be increased or decreased. unit capacity.

Constant Evaporator Flow Staging Temperatures


The Control Band is calculated as follows for constant
If the unit is configured for use without glycol:
evaporator flow:
When the LWT target is more than half the Control Band above
• Four compressor units: Control Band = Full Capacity
3.9°C (39.0°F)
Evap Delta T Set Point * 0.35
• Six compressor units: Control Band = Full Capacity Evap • Stage Up Temperature = LWT target + (Control Band/2)
Delta T Set Point * 0.25 • Stage Down Temperature = LWT target – (Control
Band/2)
Variable Evaporator Flow If the LWT target is less than half the Control Band above
When Variable Evaporator Flow is required, the control band 3.9°C (39.0°F)
increases as capacity decreases to account for the decrease • Stage Down Temperature = LWT target – (LWT target -
in flow. It is assumed that the flow will vary to maintain the full 3.9°C)
capacity evaporator temperature delta at part load conditions.
• Stage Up temperature = LWT target + Control Band –
The control band is limited at each capacity step to a maximum
(LWT target – 3.9°C)
value that corresponds to the minimum flow for that capacity
step. If the unit is configured for use with glycol, the compressor
staging temperatures are calculated as shown below:
Since evaporator flow is represented by the set point Full
Capacity Evaporator Delta T, the calculations of the control • Stage Up Temperature = LWT target + (Control Band/2)
band for variable flow applications are explained in terms of • Stage Down Temperature = LWT target – (Control
delta T also. The term ‘Effective Full Capacity Delta T’ means Band/2)
the approximate temperature delta that would be observed with The Start up and Shutdown temperatures are referenced from
the unit running at full capacity for the given flow. ‘Nominal flow’

www.DaikinApplied.com 49 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Functions

the Control Band: Table 45: Unit Mode Settings


• Start Up Temperature = Stage Up Temperature + Start Up Control Available
Delta set point BAS
Source Set Mode Input Modes Set Unit Mode
Request
• Shutdown Temperature = Stage Down Temperature – Point Point
Shutdown Delta set point Cool Cool
Cool w/
Cool
Glycol
Unit Enable Cool/Ice w/
Local Off Cool
Enabling and disabling the chiller is accomplished using set Glycol
points and inputs to the chiller. The unit switch, remote switch Cool/Ice w/
Local On Ice
input, and Unit Enable Set Point all are required to be ‘on’ for Glycol
the unit to be enabled when the control source is set to ‘local.’ Cool/Ice w/
The same is true if the control source is set to ‘network,’ with Network Cool Cool
Glycol
the additional requirement that the building automation system Cool/Ice w/
(BAS) Enable set point must be ‘on’. The BAS should enable Network Ice Ice
Glycol
the chiller only when there is a demand for cooling. Ice w/Glycol Ice
Unit is enabled according to the following table: Test Test

Unit Control Remote Unit BAS Unit


Switch Source Switch Enable Enable Enable
Glycol Configuration
Set Input Set Set If the Available Modes Set Point is set to an option ‘w/Glycol,’
Point Point Point then glycol operation should be enabled for the unit. Glycol
Off Off operation should only be disabled when the Available Modes
Set Point is set to ‘Cool.’
Off Off
Off Off
On Local On On On Unit States
Network Off Off The unit will always be in one of three states:
On Network On On On On Off – Unit is not enabled to run
Auto – Unit is enabled to run

Unit Mode Selection Pumpdown – Unit is doing a normal shutdown (tube and fin
condenser coils only). If a unit has microchannel coils, the
The operating mode of the unit is determined by setpoints and individual refrigerant circuits will never do a pumpdown. So
inputs to the chiller. The Available Modes Set Point determines if the conditions for the Auto to Pumpdown transition occur,
what modes of operation can be used. This set point also the unit state will transition from Auto to Pumpdown and
determines whether the unit is configured for glycol use. The then immediately to Off.
Control Source Set Point determines where a command
to change modes will come from. A digital input switches Transitions between these states are shown in the following
between cool mode and ice mode if they are available and diagram.
the control source is set to ‘local.’ The BAS mode request
switches between cool mode and ice mode if they are both
available and the control source is set to ‘network.’
The Available Modes Set Point should only be changeable
when the unit switch is off. This is to avoid changing modes of
operation inadvertently while the chiller is running.
3

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 50 www.DaikinApplied.com


Unit Functions

T1 - Off to Auto Power Up Start Delay


All of the following are required: After powering up the unit, the motor protectors may not be
• Unit Enable = On engaged for up to 150 seconds. Therefore, after the control
• No Unit Alarm active is powered up, no compressor can start for 150 seconds. In
addition, the motor protect inputs are ignored during this time
• A circuit is enabled to start so as to avoid tripping a false alarm.
• If Unit Mode = Ice then Ice Delay not active
• Low Ambient Lockout is not active
• Unit configuration settings are valid Ice Mode Start Delay
An adjustable start to start ice delay timer will limit the
T2 - Auto to Pumpdown frequency with which the chiller may start in Ice mode. The
Any of the following are required: timer starts when the first compressor starts while the unit is in
ice mode. While this timer is active, the chiller cannot restart in
• Unit Enable = Off and Unit Switch is closed
Ice mode. The time delay is adjustable via the Ice Time Delay
• Unit Mode = Ice AND LWT target is reached set point.
• Unit Pumpdown Alarm active
The ice delay timer may be manually cleared to force a
• Low Ambient Lockout is active restart in ice mode. A set point specifically for clearing the ice
mode delay is available. In addition, cycling the power to the
T3 - Pumpdown to Off controller should clear the ice delay timer.
Any of the following are required:
• Unit rapid stop alarm active
• All circuits complete pumpdown
Low Ambient Lockout
• Unit Switch open When the OAT drops below the low ambient lockout set point
and the OAT sensor fault is not active, low ambient lockout is
T4 - Auto to Off triggered. The unit should go into the pumpdown state if any
circuits are running. If no circuits are running the unit should go
Any of the following are required: into the off state. This condition should clear when OAT rises to
• Unit rapid stop alarm active the lockout set point plus 2.5°C (4.5°F).
• No circuit enabled and no compressors running
• Unit Switch open

www.DaikinApplied.com 51 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Functions

Unit Status Evaporator Pump Control


The displayed unit status should be determined by the For control of the evaporator pumps, three evaporator pump
conditions in the following table: control states should be used:
# Status Conditions
Off - No pump on.
1 Auto Unit State = Auto
Unit State = Auto and MP start Start – Pump is on, water loop is being recirculated.
2 Off: Motor Prot Delay
up delay is active Run – Pump is on, water loop has been recirculated and
Unit State = Off, circuits can start if needed.
3 Off: Ice Mode Timer Unit Mode = Ice, and
Transitions between these states are shown in the following
Ice Delay = Active
diagram.
Unit State = Off and Low OAT
4 Off: Low OAT Lockout
Lockout is active
Unit State = Off and both
5 Off: All Cir Disabled
circuits unavailable
Unit State = Off and Unit Alarm
6 Off: Unit Alarm
active
Unit State = Off and Unit
7 Off: Keypad Disable
Enable Set Point = Disable
Unit State = Off and Remote

3
8 Off: Remote Switch
Switch is open
Unit State = Off, Control
9 Off: BAS Disable Source = Network, and BAS
Enable = false
Unit State = Off and Unit RUN START
10 Off: Unit Switch
Switch = Disable
Unit State = Off and Unit Mode
11 Off: Test Mode
= Test
Unit State = Auto, no circuits
running, and LWT is less than
T1 – Off to Start
12 Auto: Wait for load
the active set point + startup Requires any of the following
delta
• Unit state = Auto
Unit State = Auto and
13 Auto: Evap Recirc • Freeze protection started
Evaporator State = Start
Unit State = Auto, Evaporator T2 – Start to Run
14 Auto: Wait for flow State = Start, and Flow Switch
is open Requires the following
15 Auto: Pumpdown Unit State = Pumpdown • Flow ok for time longer than evaporator recirculate time
Unit State = Auto, max set point
16 Auto: Max Pulldown pulldown rate has been met or
exceeded T3 – Run to Off
Unit State = Auto, unit Requires all of the following
17 Auto: Unit Cap Limit capacity limit has been met or
exceeded
• Unit state is Off
Unit State = Auto and high • Freeze protection not active
18 Auto: High Ambient Limit
ambient capacity limit is active
Unit State = Auto and unit is
T4 – Start to Off
19 Auto:Rapid Restore performing Rapid Restore Requires all of the following
operation
• Unit state is Off
Condenser type setting is set
20 Off:Cond Type Not Set • Freeze protection not active
to ‘Not Set’
Expansion valve type setting is T5 – Run to Start
21 Off:ExVlv Type Not Set
set to ‘Not Set’
22 Off:Invalid Config Unit model selected not valid Flow switch input is low for longer than the flow proof set
A configuration change
point.
Config Changed, Reboot requiring a reboot has
23
Required occurred but controller has not
been rebooted yet.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 52 www.DaikinApplied.com


Unit Functions

Freeze Protection LWT Target


To protect the evaporator from freezing, the evaporator pump The LWT Target varies based on settings and inputs.
will start if all of the following are true:
The base LWT Target is selected as follows:
• LWT equal to or less than the Evap Freeze set point for at
least three seconds Control Available
BAS Base LWT
Source Set Mode Input Modes Set
• LWT sensor fault isn’t active Point
Request
Point
Target
• manual reset flow loss alarm is not active Cool Set
Local OFF COOL
Freeze protection will end when any of the following are true: Point 1
• [LWT is at least 1.11°C (2°F) above the Evap Freeze set Cool Set
Local ON COOL
point OR LWT sensor fault is active] and pump has been Point 2
in run state for at least 15 minutes BAS Cool
Network COOL
Set Point
• manual reset flow loss alarm is active
COOL w/ Cool Set
Local OFF
Pump Selection Glycol Point 1
COOL w/ Cool Set
The pump output used will be determined by the Evap Local ON
Glycol Point 2
Pump Control set point. This setting allows the following
COOL w/ BAS Cool
configurations: Network
Glycol Set Point
• #1 only – Pump 1 will always be used COOL/ICE Cool Set
Local OFF
• #2 only – Pump 2 will always be used w/Glycol Point 1
• Auto – The primary pump is the one with the least run COOL/ICE Ice Set
Local ON
hours, the other is used as a backup w/Glycol Point

• #1 Primary – Pump 1 is used normally, with pump 2 as a COOL/ICE BAS Cool


Network COOL
w/Glycol Set Point
ackup
COOL/ICE BAS Ice Set
• #2 Primary – Pump 2 is used normally, with pump 1 as a Network ICE
w/Glycol Point
backup
ICE w/ Ice Set
Local
Primary/Standby Pump Staging Glycol Point
ICE w/ BAS Ice Set
The pump designated as primary will start first. If the Network
Glycol Point
evaporator state is start for a time greater than the recirculate
timeout set point and there is no flow, then the primary pump
will shut off and the standby pump will start. When the
Leaving Water Temperature (LWT) Reset
evaporator is in the run state, if flow is lost for more than half The base LWT target may be reset if the unit is in Cool mode
of the flow proof set point value, the primary pump will shut and LWT reset is enabled via the set point.
off and the standby pump will start. Once the standby pump The reset amount is adjusted based on the 4 to 20 mA reset
is started, the flow loss alarm logic will apply if flow cannot be input. Reset is 0° if the reset signal is less than or equal to
established in the evaporator start state, or if flow is lost in the 4 mA. Reset is 5.56°C (10.0°F) if the reset signal equals or
evaporator run state. exceeds 20 mA. The amount of reset will vary linearly between
these extremes if the reset signal is between 4 mA and 20 mA.
Auto Control When the reset amount increases, the Active LWT Target is
If auto pump control is selected, the primary/standby logic changed at a rate of 0.1°C every 10 seconds. When the active
above is still used. When the evaporator is not in the run state, reset decreases, the Active LWT Target is changed all at once.
the run hours of the pumps will be compared. The pump with
After the reset is applied, the LWT target can never exceed a
the least hours will be designated as the primary at this time.
value of 18.33°C (65°F).

www.DaikinApplied.com 53 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Functions

Unit Capacity Control only one compressor running.

Unit capacity control will be performed as described in this Next To Start


section. All unit capacity limits described in following sections
must be applied as described. If both circuits have an equal number of compressors running
or a circuit has no compressors available to start:
Compressor Staging in Cool Mode • the available compressor with the least starts will be next
to start
The first compressor on the unit should be started when
evaporator LWT is higher than the Startup Temperature. • if starts are equal, the one with the least run hours will be
next to start
Additional compressors can be started when Evaporator LWT
• if run hours are equal, the lowest numbered one will be
is higher than the Stage Up Temperature and the Stage Up
next to start
Delay is not active.
If the circuits have an unequal number of compressors running,
When multiple compressors are running, one should shut down the next compressor to start will be on the circuit with the least
if evaporator LWT is lower than the Stage Down Temperature compressors running if it has at least one compressor available
and the Stage Down Delay is not active. to start. Within that circuit:
All running compressors should shut down when the • the available compressor with the least starts will be next
evaporator LWT is lower than the Shut Down Temperature. to start
• if starts are equal, the one with the least run hours will be
Stage Up Delay
next to start
A minimum amount of time, defined by the Stage Up Delay set • if run hours are equal, the lowest numbered one will be
point, should pass between increases in the capacity stage. next to start
This delay should only apply when at least one compressor
is running. If the first compressor starts and quickly shuts off Next to Stop
for some reason, another compressor may start without this
If both circuits have an equal number of compressors running:
minimum time passing.
• the running compressor with the most run hours will be
Stage Down Delay next to stop
A minimum amount of time, defined by the Stage Down Delay • if run hours are equal, the one with the least starts will be
set point, should pass between decreases in the capacity next to stop
stage. This delay should not apply when the LWT drops below • if starts are equal, the lowest numbered one will be next
the Shut Down Temperature (unit should immediately shut to stop
down). If the circuits have an unequal number of compressors running,
the next compressor to stop will be on the circuit with the most
Compressor Staging in Ice Mode compressors running. Within that circuit:
The first compressor on the unit should be started when • the running compressor with the most run hours will be
evaporator LWT is higher than the Startup Temperature. next to stop
Additional compressors should be started as quickly as • if run hours are equal, the one with the least starts will be
possible with respect to the Stage Up Delay. next to stop
The unit should shut down when evaporator LWT is less than • if starts are equal, the lowest numbered one will be next
the LWT target. to stop

Stage Up Delay
Unit Capacity Overrides
A fixed stage up delay of one minute between compressor
Unit capacity limits can be used to limit total unit capacity in
starts should be used in this mode.
Cool mode only. Multiple limits may be active at any time, and
the lowest limit is always used in the unit capacity control.
Staging Sequence
This section defines which compressor is the next one to Demand Limit
start or stop. In general, compressors with fewer starts will
The maximum unit capacity can be limited by a 4 to 20 mA
normally start first, and compressors with more run hours will
signal on the Demand Limit analog input. This function is
normally stop first.
only enabled if the Demand Limit set point is set to ON. The
If possible circuits will be balanced in stage. If a circuit is maximum unit capacity stage is determined as shown in the
unavailable for any reason, the other circuit shall be allowed following tables:
to stage all compressors on. When staging down, one
compressor on each circuit shall be left on until each circuit has

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 54 www.DaikinApplied.com


Unit Functions

Table 46: Stage Limits - Four Compressors High Ambient Limit


Demand Limit Signal Demand Limit Range (mA) Stage On units configured with single point power connections, the
(%) maximum load amps could be exceeded at high ambient
Limit ≥ 75% Limit ≥ 16 mA 1 temperatures. If the power connection is single point, and the
75% > Limit ≥ 50% 16 mA > Limit ≥ 12 mA 2 outdoor air temperature OAT is greater than 46.6°C (115.9°F),
the high ambient limit becomes active. This limit will be
50% > Limit ≥ 25% 12 mA > Limit ≥ 8 mA 3 removed when the OAT drops back down to 45.45°C (114°F).
25% > Limit 8 mA > Limit 4 The max operating ambient temperature is 51.6°C (125°F).
When the limit is active, the unit is allowed to run all but one
Table 47: Stage Limits - Six Compressors compressor. So it will inhibit the unit from loading if all but one
Demand Limit Signal Demand Limit Range Stage compressor is on, and it will shut down a compressor if all
(%) (mA) compressors are running.
Limit ≥ 83.3% Limit ≥ 17.3 mA 1
83.3% > Limit ≥ 66.7% 17.3 mA > Limit ≥ 14.7 mA 2 RapidRestore® Option
66.7% > Limit ≥ 50% 14.7 mA > Limit ≥ 12 mA 3 RapidRestore® is an option that can be added to Trailblazer™
50% > Limit ≥ 33.3% 12 mA > Limit ≥ 9.3 mA 4 chillers. The general purpose of the option is to allow the
33.3% > Limit ≥ 16.7% 9.3 mA > Limit ≥ 6.7 mA 5 capability to restart more quickly and to load faster than normal
operation.
16.7% > Limit 6.7 mA > Limit 6
Enabling
Network Limit
The RapidRestore® option shall be enabled via the
The maximum unit capacity can be limited by a network signal. RapidRestore® set point. Doing so will require the following to
This function is only enabled if the control source is set to be true:
network. The maximum unit capacity stage is based on the
network limit value received from the BAS and is determined • RapidRestore® module is present at address 22
as shown in the following tables: • DI1 on the RapidRestore® module has a signal
If the DI1 input loses the signal or the RapidRestore® module
Table 48: Stage Limits - Four Compressors is no longer communicating, then the option will be disabled in
Network Limit Stage the chiller.

Limit ≥ 100% 4
Operation Following Power Cycle
100% > Limit ≥ 75% 3
The chiller will enter RapidRestore® upon powering up when
75% > Limit ≥ 50% 2 the following conditions are met:
50% > Limit 1 • RapidRestore® is enabled
• Power failure lasts less than the value of the Max Power
Table 49: Stage Limits - Six Compressors Failure Time set point
Network Limit Stage • Power failure lasts at least one second (shorter power
Limit ≥ 100% 6 loss may result in unpredictable operation)
100% > Limit ≥ 83.3% 5 • Unit is enabled
83.3% > Limit ≥ 66.7% 4 When RapidRestore® is triggered, the time value used for the
evaporator recirculation time will be limited to 110 seconds
66.7% > Limit ≥ 50% 3 or less. The evaporator recirculation time set point will not be
50% > Limit ≥ 33.3% 2 changed. Only the value used in the evaporator state logic will
33.3% > Limit 1 be limited, and only if the set point exceeds the 110 second
limit.
Maximum LWT Pulldown Rate This action will ensure that the chiller is ready to start after the
The maximum drop rate for the leaving water temperature shall motor protection module delay has expired.
be limited by the Maximum Pulldown Rate set point only when
the unit mode is Cool.
If the rate exceeds the set point, no more compressors can
be started until the pulldown rate is less than the set point.
Running compressors will not be stopped as a result of
exceeding the maximum pulldown rate.

www.DaikinApplied.com 55 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Functions

Time to Start Backup Chiller Operation


The compressor manufacturer requires a minimum two minute If DI2 on the RapidRestore® module has a signal and the unit
delay after power on until a compressor should be started, has RapidRestore® enabled, then the chiller is considered a
which is to ensure proper operation of the motor protection ‘backup chiller’. When a ‘backup chiller’ is enabled, it will use
modules. Unit controller boot time is about 10 seconds, so a an evaporator recirculation time of 13 seconds regardless
delay of 110 seconds will start upon completing boot up. After of what the evaporator recirculation time set point is. Then,
this delay, the two minute manufacturer requirement will be fast loading will be used as outlined above in the fast loading
satisfied. section.
After the 110 second delay, the first circuit to start will enter the This backup chiller sequence is safe for the unit if it has had
preopen state, which takes five seconds. The end result is that power applied for the minimum time stated in the operation
the first compressor should start approximately 125 seconds manual. Since this sequence does not have to wait on the
after power is restored to the chiller. compressor motor protection module delay, the unit can
achieve full capacity even faster than during a power loss
Current software has a delay of 150 seconds after bootup is
scenario.
complete before the first circuit can start. The software will be
changed to use the 110 second delay discussed above only
when the chiller is performing the RapidRestore operation. Compressor Starts Per Hour
Since the compressor cycle timers are not maintained through
Fast Loading power cycling, a limitation on the number of starts per hour
will be added. Each compressor will be allowed six starts in an
Fast loading will be performed when the following conditions
hour.
are met after the unit power up:
If a compressor start is being delayed due to this limitation,
• Chiller enters RapidRestore® operation
it can be cleared by using the existing Clear Cycle Timers
• Current LWT > Start Up Temperature setting.
For reference, Start Up Temperature is Stage Up Temperature
The following charts show the approximate best case scenario
+ Start Up Delta T. Stage Up Temperature is calculated based
for start time and loading time with the RapidRestore®
on the Full Capacity Evaporator Delta T set point and the
operation.
number of compressors on the chiller.
Fast loading should end if any of the following conditions occur:
• LWT < Stage Up Temperature
• Unit capacity = 100%
• All circuits become disabled for any reason
• Unit becomes disabled for any reason
• 10 minutes have passed since unit powered up
When fast loading ends, the RapidRestore® operation is
considered complete.

Capacity Changes
Normally the delay between compressors staging on is
determined by the Stage Up Delay setting. That setting
defaults to 240 seconds and has a range of 120 to 480
seconds. During fast loading, a delay of 60 seconds between
compressor starts within a circuit should be used. In addition,
a delay of 30 seconds between compressor starts on different
circuits should be used.
This change during RapidRestore® operation will allow for a
faster time to full capacity while maintaining stable operation
within each circuit. Assuming both circuits are able to run, the
effective unit stage up delay will be 30 to 35 seconds, so it will
load about four times faster during RapidRestore® than the
fastest it possibly can during normal operation.

Max Pulldown Rate


Max pulldown rate will be ignored during fast loading so the
chiller can reach full capacity as soon as possible.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 56 www.DaikinApplied.com


Unit Functions

Figure 40: RapidRestore® Mode - Four Compressor Units – Power Lost and Restored

Figure 41: RapidRestore® Mode - Six Compressor Units - Power Lost and Restored

www.DaikinApplied.com 57 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Functions

Figure 42: RapidRestore® Mode - Four Compressor Units - Backup Chiller, Constant Power

Figure 43: RapidRestore® Mode - Six Compressor Units - Backup Chiller Constant Power

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 58 www.DaikinApplied.com


Circuit Functions

Circuit Functions

Calculations
Circuit States
Refrigerant Saturated Temperature The circuit will always be in one of four states:
Refrigerant saturated temperature shall be calculated from the Off – Circuit is not running
pressure sensor readings for each circuit.
Preopen – Circuit is preparing to start
Evaporator Approach Run – Circuit is running
The evaporator approach shall be calculated for each circuit. Pumpdown – Circuit is doing a normal shutdown
The equation is as follows:
Transitions between these states are shown in the following
Evaporator Approach = LWT – Evaporator Saturated diagram.
Temperature
T1
Condenser Approach POWER
ON
OFF
T6
PREOPEN

The condenser approach shall be calculated for each circuit.


The equation is as follows:
Condenser Approach = Condenser Saturated Temperature

T4
T2

T5
- OAT

Suction Superheat
Suction superheat shall be calculated for each circuit using the PUMPDOWN T3 RUN
following equation:
Suction superheat = Suction Temperature – Evaporator
Saturated Temperature
T1 – Off to Preopen
Pumpdown Pressure • No compressors are running and any compressor on
The pressure to which a circuit will pumpdown is based on the circuit is commanded to start (see unit capacity control)
Low Evaporator Pressure Unload set point. The equation is as
follows: T2 – Preopen to Run
Pumpdown pressure = Low Evap Pressure Unload set point • 5 seconds in Preopen state has passed
– 103KPA (15 PSI)
T3 – Run to Pumpdown
Circuit Control Logic Any of the following are required:
• Last compressor on circuit is commanded to stop
Circuit Enabling • Unit State = Pumpdown
A circuit should be enabled to start if the following conditions • Circuit switch is open
are true: • Circuit mode is disable
• Circuit switch is closed • Circuit Pumpdown alarm is active
• No circuit alarms are active
T4 – Pumpdown to Off
• Circuit Mode set point is set to Enable
Any of the following are required:
• At least one compressor is enabled to start (according to
enable setpoints) • Evaporator Pressure < Pumpdown Pressure Value
• Unit State = Off
Compressor Availability • Circuit Rapid Stop alarm is active
A compressor is considered available to start if all the following
are true: T5 – Run to Off
• The corresponding circuit is enabled Any of the following are required:
• The corresponding circuit is not in pumpdown • Unit State = Off
• No cycle timers are active for the compressor • Circuit Rapid Stop alarm is active
• No limit events are active for the corresponding circuit • A low ambient start attempt failed
• The compressor is enabled via the enable setpoints
• The compressor is not already running

www.DaikinApplied.com 59 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Circuit Functions

T6 – Preopen to Off Circuit Status


Any of the following are required: The displayed circuit status should be determined by the
• Unit State = Off conditions in the following table:If more than one status is
• Unit State = Pumpdown enabled at the same time, the hightest numbered status
overrides the others and is displayed.
• Circuit switch is open
• Circuit mode is disable # Status Conditions
• Circuit Rapid Stop alarm is active 1 Off:Ready Circuit is ready to start when
• Circuit Pumpdown alarm is active needed.
2 Off:Cycle Timers Circuit is off and cannot start
due to active cycle timer on all
Pumpdown Procedure compressors.
Pumpdown is performed as follows: 3 Off:All Comp Circuit is off and cannot start
• If multiple compressors are running, shut off the Disable due to all compressors being
appropriate compressors based on sequencing logic and disabled.
leave only one running 4 Off:Keypad Circuit is off and cannot start due
• Turn off hot gas output and liquid line output Disable to circuit enable set point.
• Keep running until evaporator pressure reaches the 5 Off:Circuit Switch Circuit is off and circuit switch is
pumpdown pressure, then stop compressor off.
• If evaporator pressure does not reach pumpdown 6 Off:Alarm Circuit is off and cannot start due
pressure within two minutes, stop compressor to active circuit alarm.
7 Off:Test Mode Circuit is in test mode.
Low Ambient Starts 8 Preopen Circuit is in preopen state.
A low OAT start is initiated if the condenser refrigerant 9 Run:Pumpdown Circuit is in pumpdown state.
saturated temperature is less than 29.5°C (85.1° F) when the 10 Run:Normal Circuit is in run state and running
first compressor starts. Once the compressor starts the circuit normally.
is in a low OAT start state for a time equal to the Low OAT 11 Run:Evap Press Circuit is running and cannot load
Start Time set point. During Low OAT Starts, the freezestat Low due to low evaporator pressure.
logic for the low evaporator pressure alarm as well as the low
evaporator pressure hold and unload alarms are disabled. The 12 Run:Cond Press Circuit is running and cannot load
absolute limit for low evaporator pressure is enforced and the High due to high condenser pressure.
low evaporator pressure alarm should trigger if the evaporator 13 Run:High OAT Circuit is running and cannot
pressure drops below that limit. In addition if the evaporator Limit add more compressors due to
pressure is less than the Low Evap Pressure Unload set point the high ambient limit on unit
during the low POAT start, no addition al compressors can capacity. Applies only to circuit 2.
start on that circuit even though the hold and unlaod events are
disabled at this time.
When the Low OAT Start Timer has expired, if the evaporator Compressor Control
pressure is greater than or equal to the Low Evaporator Compressors should run only when the circuit is in a run or
Pressure Unload set point, the start is considered successful pumpdown state. They should not be running when the circuit
and normal alarm and event logic is reinstated. If the is in any other state.
evaporator pressure is less than the Low Evaporator Pressure
Unload set point when the Low OAT Start Timer expires, the Starting a Compressor
start is unsuccessful and the compressor will shutdown.
A compressor should start if it receives a start command from
Multiple Low Ambient Start attempts are allowed. On the third the unit capacity control logic.
failed Low Ambient Start attempt, the Restart Alarm is triggered
and the circuit will not attempt to restart until the Restart alarm
has been cleared.
Stopping a Compressor
A compressor should be turned off if any of the following occur:
The restart counter should be reset when either a startup is
successful, the Low OAT Restart alarm is triggered, or the unit • Unit capacity control logic commands it off
time clock shows that a new day has started. • An unload alarm occurs and the sequencing requires this
compressor to be next off
• Circuit state is pumpdown and sequencing requires this
compressor to be next off

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 60 www.DaikinApplied.com


Circuit Functions

Cycle Timers Table 53: 5 Fans Without VFD


Condenser Fans Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 SV 1
A minimum time between starts of the compressor and a
Stage Running D.O. D.O. D.O. D.O. D.O. D.O.
minimum time between shutdown and start of the compressor
0 0
shall be enforced. The time values are determined by the
1 1 On
Start-start Timer and Stop-start Timer setpoints.
2 2 On On
These cycle timers should not be enforced through cycling of
power to the chiller. This means that if power is cycled, the 3 3 On On On
cycle timers should not be active. 4 4 On On On On
These timers may be cleared via a setting on the controller. 5 5 On On On On On On

Condenser Fan Control Table 54: 2 Fans With Fan VFD


Fan
Condenser fan control should stage fans as needed any time Condenser Fans Fan 2 Fan 3 Fan 4 Fan 5 SV 1
Speed
compressors are running on the circuit. All fans and solenoid Stage Running D.O. D.O. D.O. D.O. D.O.
A.O.
valves will be off when the circuit is in the off/preopen states.
0 0
1 1 On
Fan Staging 2 2 On On
Fan staging will use up to 5 digital outputs for control of
condenser fans and a digital output for control of a condenser
Table 55: 3 Fans With Fan VFD
solenoid valve. When equipped with a condenser fan VFD, the
speed signal also starts and stops the fan that is connected Fan
Condenser Fans Fan 2 Fan 3 Fan 4 Fan 5 SV 1
to the VFD. The total number of fans on shall be adjusted Speed
Stage Running D.O. D.O. D.O. D.O. D.O.
with changes of one fan at a time. The tables below show the A.O.
outputs energized for each stage. 0 0
1 1 On
Table 50: 2 Fans Without VFD 2 2 On On
Condenser Fans Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 SV 1 3 3 On On On On
Stage Running D.O. D.O. D.O. D.O. D.O. D.O.
0 0 Table 56: 4 Fans With Fan VFD
1 1 On
Fan
2 2 On On Condenser Fans Fan 2 Fan 3 Fan 4 Fan 5 SV 1
Speed
Stage Running D.O. D.O. D.O. D.O. D.O.
A.O.
Table 51: 3 Fans Without VFD 0 0
Condenser Fans Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 SV 1 1 2 On
Stage Running D.O. D.O. D.O. D.O. D.O. D.O. 2 2 On On
0 0
3 3 On On On
1 1 On
2 2 On On 4 4 On On On On

3 3 On On On On
Table 57: 5 Fans With Fan VFD
Fan
Table 52: 4 Fans Without VFD Condenser Fans Fan 2 Fan 3 Fan 4 Fan 5 SV 1
Speed
Condenser Fans Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 SV 1 Stage Running D.O. D.O. D.O. D.O. D.O.
A.O.
Stage Running D.O. D.O. D.O. D.O. D.O. D.O.
0 0
0 0
1 2 On
1 1 On
2 3 On On
2 2 On On On
3 4 On On On
3 3 On On On On
4 5 On On On On On
4 4 On On On On On

www.DaikinApplied.com 61 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Circuit Functions

Condenser Target below the target – the active deadband, a stage down error is
accumulated.
The condenser target is selected based on circuit capacity
using the condenser target set points. There are set points Stage Down Error Step = (Target - Stage Down dead band)
that establish the condenser target for 33%, 50%, 67%, and - Saturated Condenser Temperature
100% capacity. If the circuit has two compressors the set The Stage Down Error Step is added to Stage Down
points for 50% and 100% will be used. If the circuit has three Accumulator once every 5 seconds. When the Stage Down
compressors then the set points for 33%, 67%, and 100% will Error Accumulator is greater than 2.8°C (5°F) another stage of
used. condenser fans is removed.
A minimum condenser target should be enforced. This When a stage down occurs or the saturated temperature rises
minimum will be calculated based on the evaporator LWT. back above the target minus the Stage Down dead band, the
As the LWT varies from 7.2°C (45°F) to 32.2°C (90°F), the Stage Down Error Accumulator is reset to zero.
minimum condenser target will vary from 23.9°C (75°F) to
48.9°C (120°F). VFD
Condenser pressure trim control is accomplished using an
Staging Up optional VFD on the first fan. This VFD control will vary the fan
The first fan will not start until the evaporator pressure drop speed to drive the saturated condenser temperature to a target
or condenser pressure rise requirement for the No Pressure value. The target value is normally the same as the saturated
Change After Start alarm is satisfied. Once that requirement condenser temperature target.
is met, if there is no fan VFD then the first condenser stage
The speed should be controlled between the minimum and
should start when the saturated condenser temperature
maximum speed set points.
exceeds the condenser target. If there is a fan VFD, then
the first stage should start when the saturated condenser
temperature exceeds the condenser target less 5.56°C (10°F).
VFD State
The VFD speed signal should always be 0 when the fan stage
After this, the four stage up dead band settings will be used:
is 0.
Stage Up Deadband 1 – used when active condenser stage is 1
When the fan stage is greater than 0, the VFD speed signal
Stage Up Deadband 2 – used when active condenser stage is 2 should be enabled and control the speed as needed.
Stage Up Deadband 3 – used when active condenser stage is 3
Stage Up Compensation
Stage Up Deadband 4 – used when active condenser stage is 4, 5,
or 6 In order to create a smoother transition when another fan is
staged on, the VFD compensates by slowing down initially.
When the saturated condenser temperature is above the target This is accomplished by adding the new fan stage up
plus the active deadband, stage up error is deadband to the VFD target. The higher target causes the
accumulated. VFD logic to decrease fan speed. Then, every 2 seconds,
0.1°C (0.18°F) is subtracted from the VFD target until it is
Stage Up Error Step = Saturated Condenser Temperature –
equal to the saturated condenser temperature target set point.
(Target + Stage Up dead band)
The Stage Up Error Step is added to Stage Up Accumulator High IPLV Mode
once every 5 seconds, only if the Saturated Condenser
Refrigerant Temperature is not falling. When Stage Up Error When the High IPLV Mode setting is ‘On’ and one compressor
Accumulator is greater than 11°C (19.8°F) another stage is is running on the unit, the condenser target setting for the
added. running circuit may be overridden. In this case, rather than use
the condenser target setting for 33% or 50% (depending on
When a stage up occurs or the saturated condenser number of compressors), the condenser target will be forced to
temperature falls back within the stage up dead band the Stage the value of the IPLV Condenser Target set point.
Up Accumulator is reset to zero.
In addition, when high IPLV mode is active the calculation for
the minimum allowed condenser target (based on LWT) will
Staging Down be changed. The minimum value will be changed from 23.9°C
Four stage down dead bands shall be used. (75°F) to the value of the IPLV Condenser Target set point.
Stage Down Deadband 1 – used when active condenser stage is 1 No other changes to the operation are made when High IPLV
mode is on.
Stage Down Deadband 2 – used when active condenser stage is 2
Stage Down Deadband 3 – used when active condenser stage is 3 Additional Conditions For MicroChannel
Stage Down Deadband 4 – used when active condenser stage is 4, Coils
5, or 6
For units configured with MicroChannel condenser coils, the
When the saturated condenser refrigerant temperature is fan staging is the same as for a standard coil except there are

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 62 www.DaikinApplied.com


Circuit Functions

two additional conditions which may cause the fan stage to Position Commands
increase:
In order to improve the reliability of the EXV positioning, the
• If circuit has two compressors, the second compressor position commands that are issued to the stepper driver are
on a circuit starts, the circuit is not already at the limited in two ways:
maximum condenser stage, and the condenser saturated
1. Position commands are filtered so that the minimum change
temperature is higher than 37.78°C (100°F), then a
in position is 0.3%. Changes of less than this are ignored. This
condenser stage will be added immediately.
avoids unnecessary movement of the EXV and lowers the
• If the condenser stage is not already at the maximum, chances of losing steps as a result.
the saturated condenser temperature exceeds 56.67°C
(134°F), it has been at least 5 seconds since adding 2. The position commands are issued once per program cycle
a condenser stage, and the saturated condenser with a maximum change of 0.7% each time. This allows the
temperature is not dropping, then a condenser stage will stepper to move the valve to the commanded position before
be added immediately. the next position command is issued. Issuing commands in this
way may also lower the chances of losing steps.
In addition, if the circuit has 4 fans, or it has 6 fans and no
fan VFD’s, then the first condenser stage may be skipped at
startup. This happens if the OAT is at least 21.11°C (70°F) EXV Position Range
when the first condenser stage would normally be started, in The minimum EXV position while the circuit is running will
which case it will go directly to the second stage. always be 8%. The maximum position will change as the
Both of these additions are in place to deal with spikes in number of compressors running on the circuit changes. These
condenser pressure resulting from the lower volume of the values are shown for each unit model in the table below.
MicroChannel coils.
Table 58: Maximum Position Range

EXV Control Model


1
# Compressors Running
2 3
AGZ030E 50 100 n/a
Auto Control States AGZ035E 50 100 n/a
EXV control will operate in either the Closed state or the AGZ040E 50 100 n/a
Superheat Control state. AGZ045E 50 100 n/a
When the circuit is in the Off state or Pumpdown state, the AGZ050E 50 100 n/a
EXV will be in the Closed state and position will be 0. The EXV AGZ055E 50 100 n/a
control state display will show that the EXV state is closed AGZ060E 50 100 n/a
when this is the case. AGZ065E 50 100 n/a
AGZ070E 50 100 n/a
When the circuit is in the Preopen state or the Run state, the
AGZ075E 60 100 n/a
EXV will go into the Superheat Control state and the EXV
control state display will show this. While in superheat control, AGZ080E 60 100 n/a
the EXV controls suction superheat. AGZ090E 60 100 n/a
AGZ100E 60 100 n/a
A PID loop will be used to control the suction superheat to
AGZ110E 50 80 n/a
the target value. The EXV response is faster when the SSH
AGZ120E 50 80 n/a
is lower than 1.67°C (3°F) or higher than the SSH Target +
AGZ130E 50 80 n/a
1.67°C (3°F).
AGZ140E 60 100 n/a
The EXV should also prevent the evaporator pressure from AGZ150E 60 100 n/a
exceeding the Maximum Evaporator Pressure set point. This AGZ160E 50 80 100
is done by using another PID function to control evaporator AGZ170E 50 80 100
pressure to the maximum evaporator pressure. The EXV AGZ180E 50 80 100
position should be lesser position output from the two PID
functions. If the EXV position is being limited due to exceeding Operation Considerations
the maximum evaporator pressure, then the EXV control state
display will show ‘MaxEvapPr’. For units equipped with shell and tube evaporators, when
staging down a compressor the maximum position is reduced
Superheat Target by 10% for one minute to prevent liquid refrigerant from
getting to the compressors. After this initial one minute delay,
If the unit is E vintage and has 3 compressor on each circuit, the maximum valve position is allowed to return to its normal
then the suction superheat target is forced to 3.33°C (6°F) value at a rate of 0.1% every six seconds. This offset to the
when one compressor is running on the circuit. In all other manximum position should not occur if the stage down is due
cases, the superheat target is equal to the superheat target set to a low pressure unload.
point.
For all units - the expansion valve maximum position may

www.DaikinApplied.com 63 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Circuit Functions

be increased if both the suction superheat is higher than the


target and the expansion valve has been within 1% of its
current maximum position for a minute. The maximum should
increase at a rate of 0.1% every six seconds up to a total of an
additional 10%. This addition to the maximum position should
be reset when the EXV is no longer in the Superheat Control
state, or a compressor on the circuit stages.

Manual Control
The EXV position can be set manually. Manual control can only
be selected when the circuit is in the run state. At any other
time, the EXV control set point is forced to auto.
When EXV control is set to manual, the EXV position is equal
to the manual EXV position setting. If set to manual when the
circuit state transitions from run to another state, the control
setting is automatically set back to auto. When in manual
control, the EXV control state displayed should reflect that it is
manual control.

Liquid Line Solenoid Valve


The liquid line solenoid output should be on when the circuit
state is either Pre-open or Run. This output should be off at all
other times.

Hot Gas Bypass Solenoid Valve


This output will be on when circuit state is Run for at least 30
seconds and one compressor on the unit is running. The output
should be off at all other times.

Capacity Overrides – Limits of


Operation
The following conditions shall override automatic capacity
control as described. These overrides keep the circuit from
entering a condition in which it is not designed to run.

Low Evaporator Pressure


If the Low Evaporator Pressure Hold or Low Evaporator
Pressure Unload alarms are triggered, the circuit capacity
may be limited or reduced. See the Circuit Events section for
details on triggering, reset, and actions taken.

High Condenser Pressure


If the High Condenser Pressure Unload alarm is triggered,
the circuit capacity may be limited or reduced. See the Circuit
Events section for details on triggering, reset, and actions
taken.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 64 www.DaikinApplied.com


Alarms

Alarms

Situations may arise that require some action from the chiller always a manual reset alarm.
or that should be logged for future reference. Alarms are
classified in the following sections using the Fault/Problem/ Evaporator Water Freeze Protect
Warning scheme. Trigger: Evaporator LWT drops below evaporator freeze
When any Unit Fault Alarm is active, the alarm digital output protect set point and LWT sensor fault is not active for a time
should be turned on continuously. If both circuits have a Circuit longer than the evaporator recirculation time set point.
Fault Alarm active, the alarm digital output should be turned Action Taken: Rapid stop all circuits
on continuously. If no Unit Fault Alarm is active and only one
circuit has a Circuit Fault Alarm is active, the alarm digital Reset: This alarm can be cleared manually via the keypad,
output should alternate five seconds on and five seconds off but only if the alarm trigger conditions no longer exist.
continuously.
Evaporator LWT Sensor Fault
All alarms appear in the active alarm list while active. All alarms
are added to the alarm log when triggered and when cleared. Trigger: Sensor shorted or open for longer than one second
Entries in the log representing the occurrence of an alarm will Action Taken: Normal stop all circuits
be preceded by ‘+’ while entries representing the clearing of an
alarm will be preceded by ‘-‘. Reset: This alarm can be cleared manually via the keypad or
BAS command, but only if the sensor is back in range.

Unit Fault Alarms Outdoor Air Temperature Sensor Fault


Trigger: Sensor shorted or open for longer than one second
PVM/GFP Fault
Action Taken: Normal stop of all circuits.
Trigger: Power Configuration = Single Point and PVM/GFP
Input #1 is open for longer than one second. Reset: This alarm can be cleared manually via the keypad or
via BAS command if the sensor is back in range.
Action Taken: Rapid stop all circuits
Reset: Auto reset when input is closed for at least 5 seconds External Alarm
or if Power Configuration = Multi Point. Trigger: External Alarm/Event opens for at least 5 seconds
and external fault input is configured as an alarm.
Evaporator Flow Loss
Action Taken: Rapid stop of all circuits.
Trigger:
Reset: Auto clear when digital input is closed.
1: Evaporator Pump State = Run AND Evaporator Flow Digital
Input = No Flow for time > Flow Proof Set Point AND at least Compressor Module 1 Comm Failure
one compressor running
Trigger: Communication with the I/O extension module has
2: Evaporator Pump State = Start for time greater than failed.
Recirc Timeout Set Point and all pumps have been tried and
Evaporator Flow Digital Input = No Flow Action Taken: Rapid stop of circuit 1.
Action Taken: Rapid stop all circuits Reset: This alarm can be cleared manually via the keypad or
BAS command when communication between main controller
Reset: and the extension module is working for 5 seconds.
This alarm can be cleared at any time manually via the keypad
or via the BAS clear alarm command. Compressor Module 2 Comm Failure
If active via trigger condition 1: Trigger: Communication with I/O extension module failed.
When the alarm occurs due to this trigger, it can auto reset the Action Taken: Rapid stop of circuit 2.
first two times each day with the third occurrence being manual Reset: This alarm can be cleared manually via the keypad or
reset. BAS command when communication between main controller
For the auto reset occurrences, the alarm will reset and the extension module is working for 5 seconds.
automatically when the evaporator state is Run again. This
means the alarm stays active while the unit waits for flow, then EXV Module 1 Comm Failure
it goes through the recirculation process after flow is detected. Trigger: Expansion Valve Type = Electronic and
Once the recirculation is complete, the evaporator goes to the communication with the I/O extension module has failed.
Run state which will clear the alarm. After three occurrences,
the count of occurrences is reset and the cycle starts over if the Action Taken: Rapid stop of circuit 1.
manual reset flow loss alarm is cleared. Reset: This alarm can be cleared manually via the keypad or
If active via trigger condition 2: BAS command when communication between main controller
and the extension module is working for 5 seconds or
If the flow loss alarm has occurred due to this trigger, it is

www.DaikinApplied.com 65 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Alarms

Expansion Valve Type = Thermal. Reset: Auto clear when LWT reset is disabled or LWT reset
input back in range for 5 seconds.
EXV Module 2 Comm Failure
Trigger: Expansion Valve Type = Electronic and Evaporator EWT Sensor Fault
communication with the I/O extension module has failed. Trigger: Sensor shorted or open for longer than one second
Action Taken: Rapid stop of circuit 2. Action Taken: None.
Reset: This alarm can be cleared manually via the keypad or Reset: Auto clear when the sensor is back in range.
BAS command when communication between main controller
and the extension module is working for 5 seconds or
Expansion Valve Type = Thermal. Circuit Fault Alarms
PVM/GFP Fault
Unit Problem Alarms Trigger: Power Configuration = Multi Point and circuit PVM/
GFP input is open for longer than one second
Evaporator Pump #1 Failure
Action Taken: Rapid stop circuit.
Trigger: Unit is configured with primary and backup pumps,
pump #1 is running, and the pump control logic switches to Reset: Auto reset when input is closed for at least 5 seconds
pump #2. or if Power Configuration = Single Point.
Action Taken: Backup pump is used. Low Evaporator Pressure
Reset: This alarm can be cleared manually via the keypad or Trigger:
BAS command.
This alarm should trigger when Freeze time is exceeded, Low
Evaporator Pump #2 Failure Ambient Start is not active, and Circuit State = Run. It should
also trigger if Evaporator Press < 137.9 KPA (20 psi) and
Trigger: Unit is configured with primary and backup pumps, Circuit State = Run for longer than 1 second.
pump #2 is running, and the pump control logic switches to
pump #1. Freezestat logic allows the circuit to run for varying times at low
pressures. The lower the pressure, the shorter the time the
Action Taken: Backup pump is used. compressor can run. This time is calculated as follows:
Reset: This alarm can be cleared manually via the keypad or Freeze error = Low Evaporator Pressure Unload –
BAS command. Evaporator Pressure
Freeze time =
Unit Warning Alarms For units equipped with 10 or more condenser fans (shell
and tube type evaporator):
External Event
80 – (freeze error/6.895), limited to a range of 40 to 80
Trigger: External Alarm/Event input is open for at least 5 seconds
seconds and external fault is configured as an event.
For all other configurations (plate to plate type evaporator):
Action Taken: None.
60 – (freeze error/6.895), limited to a range of 20 to 60
Reset: Auto clear when digital input is closed. seconds
When the evaporator pressure goes below the Low Evaporator
Bad Demand Limit Input
Pressure Unload set point, a timer starts. If this timer exceeds
Trigger: Demand limit input out of range and demand limit the freeze time, then a freezestat trip occurs. If the evaporator
is enabled. For this alarm out of range is considered to be a pressure rises to the unload set point or higher, and the freeze
signal less than 3mA or more than 21mA. time has not been exceeded, the timer will reset.
Action Taken: Cannot use demand limit function. The alarm cannot trigger if the evaporator pressure sensor fault
Reset: Auto clear when demand limit disabled or demand limit is active.
input back in range for 5 seconds. Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the keypad if
Bad LWT Reset Input
the evaporator pressure is above 137.9 KPA (20 PSI).
Trigger: LWT reset input out of range and LWT reset is
enabled. For this alarm out of range is considered to be a High Condenser Pressure
signal less than 3mA or more than 21mA.
Trigger: Condenser Pressure > High Condenser Pressure set
Action Taken: Cannot use LWT reset function. point for longer than one second.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 66 www.DaikinApplied.com


Alarms

Action Taken: Rapid stop circuit. Suction Temperature Sensor Fault


Reset: This alarm can be cleared manually via the controller Trigger: Sensor shorted or open for longer than one second
keypad. and Expansion Valve Type = Electronic.
Action Taken: Normal shutdown of circuit.
Mechanical High Pressure Switch
Reset: This alarm can be cleared manually via the keypad or
Trigger: Mechanical High Pressure switch input is open and
BAS command, but only if the sensor is back in range.
Motor Protection input is closed for longer than one second,
and power up start delay is not active.
Action Taken: Rapid stop circuit. Circuit Warning Alarm
Reset: This alarm can be cleared manually via the controller
keypad if the MHP switch input is closed. Failed Pumpdown
Trigger: Circuit state = pumpdown for longer than 2 minutes.
Motor Protection Fault
Action Taken: Rapid stop circuit.
Trigger: Motor Protection input is open and power up start
Reset: N/A.
delay is not active for longer than one second.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the controller Alarm Logs
keypad if the input is closed. Press the alarm button on the controller to go to the alarm
section. Three alarm sub-sections will appear. Turn the
Low OAT Restart Fault navigating wheel to highlight among them and press the wheel
Trigger: Circuit has failed three low OAT start attempts. to select. Reference Figure 44 for controller components.
Action Taken: Rapid stop circuit.
Active Alarms
Reset: This alarm can be cleared manually via the keypad or
When an alarm or event occurs, it appears in the active alarm
via BAS command.
list. The active alarm list holds a record of all active alarms
not yet cleared and includes the date and time each occurred.
No Pressure Change After Start
When cleared, the alarm transfers to the Alarm Log that
Trigger: After start of compressor, at least a 7 KPA (1 PSI) contains an alarm history with time/date stamp. A (+) before an
drop in evaporator pressure OR 35 KPA (5.1 PSI) increase in alarm indicates that it is active, a (-) indicates a cleared alarm.
condenser pressure has not occurred after 30 seconds. The The Active Alarm list is only limited by the number of alarms
actual alarm will not be triggered until the second occurrence. since any given alarm cannot appear twice.
This counter should be reset every day at midnight.
Action Taken: Rapid stop circuit. Alarm Log
Reset: This alarm can be cleared manually via the keypad or An alarm log stores the last 50 occurrences or resets that
via BAS command. occur. When an alarm or event occurs, it is put into the first
slot in the alarm log and all others are moved down one,
Evaporator Pressure Sensor Fault dropping the last entry. The date and time the alarm occurred
are stored in the alarm log.
Trigger: Triggered when sensor is shorted or open for longer
than one second. However the fault should not be triggered
due to the input signal reading too high unless the circuit has Event Log
been running for longer than 90 seconds or the OAT is less An Event Log similar to the Alarm Log stores the last 50
than 40.56°C (105°F). event occurrences. Each Event Log entry includes an event
Action Taken: Rapid stop circuit. description and a time and date stamp for the event occurrence
plus the count of the event occurrences on the current day and
Reset: This alarm can be cleared manually via the keypad or for each of the last seven days. Events do not appear in the
BAS command, but only if the sensor is back in range. Active Alarm list.

Condenser Pressure Sensor Fault Clearing Alarms


Trigger: Sensor shorted or open for longer than one second.
Active alarms can be cleared through the keypad/display or a
Action Taken: Rapid stop circuit. BAS network. Alarms are automatically cleared when controller
Reset: This alarm can be cleared manually via the keypad or power is cycled. Alarms are cleared only if the conditions
BAS command, but only if the sensor is back in range. required to initiate the alarm no longer exist. All alarms and
groups of alarms can be cleared via the keypad or network
via LON using nviClearAlarms and via BACnet using the

www.DaikinApplied.com 67 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Alarms

ClearAlarms object. Reset: While still running, the event will reset if evaporator
pressure > Low Evaporator Pressure Hold SP + 90 KPA (13
To use the keypad, follow the Alarm links to the Alarms screen,
PSI). The event is also reset if the circuit is no longer in the run
which will show Active Alarms and Alarm Log. Select Active
state.
Alarm and press the wheel to view the Alarm List (list of current
active alarms). They are in order of occurrence with the most
recent on top. The second line on the screen shows Alm Cnt Low Evaporator Pressure - Unload
(number of alarms currently active) and the status of the alarm Trigger:
clear function. Off indicates that the Clear function is off and This event is triggered if all of the following are true:
the alarm is not cleared. Press the wheel to go to the edit
mode. The Alm Clr (alarm clear) parameter will be highlighted • circuit state = Run
with OFF showing. To clear all alarms, rotate the wheel to • more than one compressor is running on the circuit
select ON and enter it by pressing the wheel. • evaporator pressure <= Low Evaporator Pressure -
An active password is not necessary to clear alarms. Unload set point for a time greater than half of the
current freezestat time
If the problem(s) causing the alarm have been corrected, the
alarms will be cleared, disappear from the Active Alarm list • circuit is not currently in a low OAT start
and be posted in the Alarm Log. If not corrected, the On will • it has been at least 30 seconds since a compressor has
immediately change back to OFF and the unit will remain in the started on the circuit.
alarm condition. On units equipped with 6 compressors, electronic expansion
valves, and 10 or more fans, when each compressors

Events starts, there should be a 2 minute window during which the


evaporator pressure must drop an additional 27 KPA (3.9 PSI)
Situations may arise that require some action from the chiller to trigger the alarm. After this 2 minute window, the trigger
or that should be logged for future reference, but aren’t severe point should return to normal.
enough to track as alarms. These events are stored in a log Action Taken: Stage off one compressor on the circuit every
separate from alarms. This log shows the time and date of the 10 seconds while evaporator pressure is less than the unload
latest occurrence, the count of occurrences for the current day, set point, except the last one.
and the count of occurrences for each of the previous 7 days.
Reset: While still running, the event will be reset if evaporator
pressure > Low Evaporator Pressure Hold SP + 90 KPA(13
Unit Events PSI). The event is also reset if the circuit is no longer in the
run state.
Unit Power Restore
Trigger: Unit controller is powered up. High Condenser Pressure - Unload
Action Taken: None Trigger:

Reset: None This event is triggered if all of the following are true:
• circuit state = Run
• more than one compressor is running on the circuit
Circuit Events • condenser pressure > High Condenser Pressure –
Low Evaporator Pressure - Hold Unload set point
Trigger: Action Taken: Stage off one compressor on the circuit every
10 seconds while condenser pressure is higher than the
This event is triggered if all of the following are true: unload set point, except the last one. Inhibit staging more
• circuit state = Run compressors on until the condition resets.
• evaporator pressure <= Low Evaporator Pressure - Hold Reset: While still running, the event will be reset if condenser
set point pressure <= High Condenser Pressure Unload SP – 862
• circuit is not currently in a low OAT start KPA(125 PSI). The event is also reset if the circuit is no longer
in the run state.
• it has been at least 30 seconds since a compressor has
started on the circuit.
Action Taken: Inhibit starting of additional compressors on the
circuit.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 68 www.DaikinApplied.com


Using the Controller

Using the Controller

Figure 44: Schematic of Unit Controller

The keypad/display consists of a 5-line by 22-character include changeable data fields (setpoints).
display, three buttons (keys) and a “push and roll” navigation When the cursor is on a line the highlights will look like this:
wheel. There is an Alarm Button, Menu (Home) Button and a
Back Button. The wheel is used to navigate between lines on Evaporator Delta T= 10.0F
a screen (page) and to increase and decrease changeable If line contains a changeable value-
values when editing. Pushing the wheel acts as an Enter
Button and will jump from a link to the next set of parameters. Unit Status= Run
If the line contains status-only information-
Figure 45: Typical Screen Or a line in a menu may be a link to further menus. This
is often referred to as a jump line, meaning pushing the
•6 View/Set Unit 3
navigation wheel will cause a “jump” to a new menu. An arrow
Status/Settings > (>) is displayed to the far right of the line to indicate it is a
Set Up > “jump” line and the entire line is highlighted when the cursor is
on that line.
Temperature >
NOTE - Only menus and items that are applicable to the
Date/Time/Schedule >
specific unit configuration are displayed.
Generally, each line on the display contains a menu title, a
This manual includes information relative to the operator level
parameter (such as a value or a setpoint), or a link (which will
of parameters; data and setpoints necessary for the every
have an arrow in the right of the line) to a further menu.
day operation of the chiller. There are more extensive menus
The first line visible on each display includes the menu title and available for the use of service technicians.
the line number to which the cursor is currently “pointing.” In
the above screen, Temperature is highlighted. Navigating
The left most position of the title line includes an “up” arrow ▲ When power is applied to the control circuit, the controller
to indicate there are lines (parameters) “above” the currently screen will be active and display the Home screen, which can
displayed line; and/or a “down” arrow ▼ to indicate there are also be accessed by pressing the Menu Button The navigating
lines (parameters) “below” the currently displayed items or an wheel is the only navigating device necessary, although the
“up/down” arrow • to indicate there are lines “above and below” MENU, ALARM, and BACK buttons can provide shortcuts as
the currently displayed line. The selected line is highlighted. explained later.
Each line on a screen can contain status-only information or

www.DaikinApplied.com 69 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Using the Controller

Passwords When the Alarm Button is depressed, the Alarm Lists menu is
displayed.
Enter passwords from the Main Menu:
• Enter Password links to the Entry screen which is an Edit Mode
editable screen. So pressing the wheel goes to the edit
The Editing Mode is entered by pressing the navigation wheel
mode where the password (2526) can be entered. The
while the cursor is pointing to a line containing an editable field.
first (*) will be highlighted, rotate the wheel clockwise to
Once in the edit mode pressing the wheel again causes the
the first number and set it by pressing the wheel. Repeat
editable field to be highlighted. Turning the wheel clockwise
for the remaining three numbers. The password will time
while the editable field is highlighted causes the value to be
out after 10 minutes and is cancelled if a new password is
increased. Turning the wheel counter-clockwise while the
entered or the control powers down.
editable field is highlighted causes the value to be decreased.
• Not entering a password allows access to a limited The faster the wheel is turned the faster the value is increased
number of parameters as shown in Figure 49. or decreased. Pressing the wheel again cause the new value
to be saved and the keypad/display to leave the edit mode and
Figure 46: Password Menu return to the navigation mode.
Main Menu 1/3 A parameter with an “R” is read only; it is giving a value or
description of a condition. An “R/W“ indicates a read and/or
Enter Password >
write opportunity; a value can be read or changed (providing
Unit Status the proper password has been entered).
Off: Unit Sw Link and parameter access is indicated for the various
ACTIVE SETPT 44.6°F password levels with one column for each level. Column
headings for the password levels are as follows and shown in
Figure 47: Password Entry Page Figure 48:
N = No password
Enter Password 1/1
O = Operator level
Enter PW ****
T = Technician level
Entering an invalid password has the same effect as not D = Daikin Applied factory service technician level
entering a password.
Screen navigational links:
Once a valid password has been entered, the controller
allows further changes and access without requiring the user • For each link on a screen, the linked screen is indicated
to enter a password until either the password timer expires in the rightmost column.
or a different password is entered. The default value for this • For each screen, the screen(s) from which you can
password timer is 10 minutes. navigate to it is also shown in parentheses after the
screen identifier.
Navigation Mode • For most circuit or compressor level parameters, there
is a link to a screen that shows the values for all circuits/
When the navigation wheel is turned clockwise, the cursor
compressors which is indicated in the ‘Links to screen’
moves to the next line (down) on the page. When the wheel is
column as *.
turned counter-clockwise the cursor moves to the previous line
(up) on the page. The faster the wheel is turned the faster the For many of the circuit level screens, only one screen will be
cursor moves. Pushing the wheel acts as an “Enter” button. shown in this section. The same set of screens exists for each
circuit and compressor. These screens are the ones with ‘Cx’
Three types of lines exist: and Cmpx’ identifiers.
• Menu title, displayed in the first line as in Figure 46.
• Link (also called Jump) having an arrow ( > ) in the right Figure 48: Example of Screen Menu With Access Levels
of the line and used to link to the next menu.
• Parameters with a value or adjustable setpoint.
For example, “Time Until Restart” jumps from level 1 to level 2
and stops there.
When the Back Button is pressed the display reverts back to
the previously displayed page. If the Back button is repeatedly
pressed the display continues to revert one page back along
the current navigation path until the “main menu” is reached.
When the Menu (Home) Button is pressed the display reverts
to the “main page.”

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 70 www.DaikinApplied.com


Using the Controller

Figure 49: Controller Keypad Navigation

www.DaikinApplied.com 71 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Optional Low Ambient Fan VFD

Optional Low Ambient Fan VFD

The optional VFD fan control is used for unit operation below Inverter Output to the Motor
32°F (0°C) down to a minimum of -10°F (-23°C). The control
looks at the saturated discharge temperature and varies the WARNING
fan speed to hold the temperature (pressure) at the “target” Avoid swapping any 2 of the 3 motor lead connections which
temperature. will cause reversal of the motor direction. In applications
Low ambient air temperature control is accomplished by using where reversed rotation could cause equipment damage or
the Optional Low Ambient VFD to control the speed of the personnel injury, be sure to verify direction of rotation before
first fan on each circuit. This VFD control uses a proportional attempting full-speed operation. For safety to personnel,
integral function to drive the saturated condenser temperature the motor chassis ground must be connected to the ground
to a target value by changing the fan speed. The target value connection at the bottom of the inverter housing.
is normally the same as the saturated condenser temperature
target setpoint.
The AC motor must be connected only to the inverter’s
The fan VFD always starts when the saturated condenser
output terminals. The output terminals are uniquely labeled
temperature rises higher than the target.
(to differentiate them from the input terminals) with the
designations U/T1, V/T2, and W/T3.
What is an Inverter?
The term inverter and variable-frequency drive are related and
somewhat interchangeable. An electronic motor drive, for an
AC motor, controls the motor’s speed by varying the frequency
of the power sent to the motor.
In general, an inverter is a device that converts DC power to
AC power. The figure below shows how the variable-frequency
drive employs an internal inverter. The drive first converts
incoming AC power to DC through a rectifier bridge, creating
an internal DC bus voltage. Then the inverter circuit converts
the DC back to AC again to power the motor. The special
inverter can vary its output frequency and voltage according to
the desired motor speed.

This corresponds to typical motor lead connection designations


T1, T2, and T3. The consequence of swapping any two of the
three connections is the reversal of the motor direction. This
must not be done. In applications where reversed rotation
could cause equipment damage or personnel injury, be sure
to verify direction of rotation before attempting full-speed
operation. For safety to personnel, the motor chassis ground
must be connected to the ground connection at the bottom of
the inverter housing.
Notice the three connections to the motor do not include
one marked “Neutral” or “Return.” The motor represents a
balanced “Y” impedance to the inverter, so there is no need
for a separate return. In other words, each of the three “Hot”
connections serves also as a return for the other connections
because of their phase relationship.
Do not to switch off power to the inverter while the motor is
running (unless it is an emergency stop) to avoid equipment
damage. Also, do not install or use disconnect switches
in the wiring from the inverter to the motor (except thermal
disconnect).

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 72 www.DaikinApplied.com


Optional Low Ambient Fan VFD

VFD Interface
The VFD controller is located in the lower left-hand corner of
the unit control panel. It is used to view data including fault and
alarm information. No operator intervention on this control is
required for normal unit operation.

Table 59: Display Key Functions


No. Display Name Function
The functions assigned to F1 and F2 vary depending on the currently displayed menu. The name of each
1 Function Key (F1, F2)
function appears in the lower half of the display window.
• Returns to the previous display.
2, 3 ESC Key, RESET Key • Moves the cursor one space to the left
• Pressing and holding this button will return to the Frequency Reference display.
• Moves the cursor to the right.
3 RESET Key
• Resets the drive to clear a fault situation
4 RUN Key Starts the drive in LOCAL mode.
5 Up Arrow Key Scrolls up to display the next item, select parameter numbers, and increment setting values.
6 Down Arrow Key. Scrolls down to display the next item, select parameter numbers, and increment setting values
7 STOP Key Stops drive operation.
• Enters parameter values and settings.
8 ENTER Key
• Selects a menu item to move between displays
Switches drive control between the operator (LOCAL) and an external source (REMOTE)for the Run
9 LO/RE Selection Key
command and frequency reference.
10 RUN Light Lit while the drive is operating the motor.
11 LO/RE Ligh Lit while the operator is selected to run the drive (LOCAL mode).
12 ALM LED Light Refer to ALARM (ALM) LED Displays in Table 61

www.DaikinApplied.com 73 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Optional Low Ambient Fan VFD

Figure 50: LCD Display

Table 60: Display Data


No Name Display Content
MODE Displayed when in Mode Selection.
MONITR Displayed when in Monitor Mode.
Operation Mode VERIFY Indicates the Verify Menu
1
Menus PRMSET Displayed when in Parameter Setting Mode.
A.TUNE Displayed during Auto-Tuning.
SETUP Displayed when in Setup Mode.
DriveWorksEZ
2 DWEZ Displayed when DriveWorksEZ is set to enable. (A1-07 = 1 or 2)
Function Selection
DRV Displayed when in Drive Mode.
3 Mode Display Area
PRG Displayed when in Programming Mode
4 Ready Rdy Indicates the drive is ready to run.
5 Data Display — Displays specific data and operation data.
OPR Displayed when the frequency reference is assigned to the LCD Operator Option
Frequency AI Displayed when the frequency reference is assigned to the Analog Input of the drive
Reference Displayed when the frequency reference is assigned to the MEMOBUS/Modbus Communication
6 COM
Assignment Inputs of the drive
<1> OP Displayed when the frequency reference is assigned to an Option Unit of the drive.
RP Displayed when the frequency reference is assigned to the Pulse Train Input of the drive
RSEQ Displayed when the run command is supplied from a remote source.
LSEQ Displayed when the run command is supplied from the operator keypad.
7 LO/RE Display <2>
RREF Displayed when the run command is supplied from a remote source.
LREF Displayed when the run command is supplied from the operator keypad
JOG Pressing [F1} executes the Jog function.
HELP Pressing [F1] displays the Help menu.
8 Function Key 1(F1) ← Pressing [F1] scrolls the cursor to the left.
HOME Pressing [F1] returns to the top menu (Frequency Reference).
ESC Pressing [F1] returns to the previous display
FWD Indicates forward motor operation.
9 FWD/REV
REV Indicates reverse motor operation.
FWD/REV Pressing [F2] switches between forward and reverse
DATA Pressing [F2] scrolls to the next display
10 Function Key 2 (F2)
Pressing [F2] scrolls the cursor to the right
RESET Pressing [F2] resets the existing drive fault error

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 74 www.DaikinApplied.com


Optional Low Ambient Fan VFD

Table 61: Alarm Content

State Content
Illuminated When the drive detects an alarm or error
When an alarm occurs
Flashing When an oPE is detected
When a fault or error occurs during Auto-Tuning
Off Normal operation (no fault or alarm)

Table 62: LO/RE LED and RUN LED Indictors

Flashing
LED Lit Flashing Quickly Off
Slowly
When the operator When a device other than
is selected for Run the operator is selected for
LO/RE command and -- -- Run command and frequency
frequency reference reference control (REMOTE)
control (LOCAL)
While the drive was set to LOCAL, a Run
command was entered to the input terminals
then the drive was switched to REMOTE.
During
A Run command was entered via the input
deceleration
terminals while the drive was not in the Drive
to stop
Mode.
When a Run During deceleration when a Fast Stop
RUN During run command was entered. During stop
command
is input and The drive output is shut of by the Safe Disable
frequency function.
reference is
The STOP key was pressed while drive was
0 Hz
running in REMOTE.
The drive was powered up with b1-17 = 0
(default) while the Run command was active.

www.DaikinApplied.com 75 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Optional Low Ambient Fan VFD

Table 63: Types of Alarms, Faults, and Errors

Type Drive Response


When the drive detects a fault:
• The digital operator displays text indicating the specific fault and the ALM indicator LED remains lit until the
fault is reset.
Faults • The fault interrupts drive output and the motor coasts to a stop. • Some faults allow the user to select the
stopping method when the fault occurs.
• Fault output terminals MA-MC will close, and MB-MC will open.
The drive will remain inoperable until the fault is cleared.
When the drive detects an alarm or a minor fault:
• The digital operator displays text indicating the specific alarm or minor fault, and the ALM indicator LED
flashes.
• The drive continues running the motor, although some alarms allow the user to select a stopping method
Minor Faults when the alarm
and Alarms occurs.
• A multi-function contact output set to be tripped by a minor fault closes. If the output is set to be tripped by an
alarm, the contact will not close.
• The digital operator displays text indicating a specific alarm and the ALM indicator LED flashes.
Remove the cause of the problem to reset a minor fault or alarm.
An operation error occurs when parameter settings conflict or do not match hardware settings (such as with an
option card).When the drive detects an operation error:
Operation
• The digital operator displays text indicating the specific error. • Multi-function contact outputs do not operate.
Errors
The drive will not operate the motor until the error has been reset. Correct the settings that caused the
operation error to clear the error.
Tuning errors occur while performing Auto-Tuning. When the drive detects a tuning error:
• The digital operator displays text indicating the specific error. • Multi-function contact outputs do not operate.
Tuning Errors
• Motor coasts to stop.
Remove the cause of the error and repeat the Auto-Tuning process.
Copy Function Errors occur when using the digital operator or the USB Copy Unit to copy, read, or verify
parameter settings.
Copy Function • The digital operator displays text indicating the specific error.
Errors • Multi-function contact outputs do not operate.
Pressing any key on the digital operator will clear the fault. Investigate the cause of the problem (such as
model incompatibility)and try again.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 76 www.DaikinApplied.com


Optional Low Ambient Fan VFD

Table 64: Fault Reset Methods

After the Fault Occurs Procedure Table 65: Periodic Inspection Checklist
Press RESET on the controller. Inspection Area Inspection Points Corrective Action
Inspect equipment Replace damaged
including wiring, components.
Fix the cause of the fault,
terminals, resistors,
restart the drive, and reset
capacitors, diode and
the fault
General IGBT for discoloration
from overheating or
deterioration.

Close then open the fault signal Inspect for dirt or foreign Use dry air to clear
digital input via terminal S4. S4 is particles away.
set for “Fault Reset” as default Inspect contactors and Check for over or
Resetting via Fault Reset (H1-04 = 14) relays for excessive undervoltage
Digital Input S4 noise.
Relays and
Inspect for signs of Replace damaged
Contactors
overheating such as parts.
melted or cracked
insulation
Turn off the main power
supply if the above methods
do not reset the fault. Optional BAS Interface
Reapply power after the The AGZ chiller controller is configured for stand-alone
controller display has turned operation or integration with BAS through an optional
off. communication module.
NOTE: When a fault occurs, the cause of the fault must The following installation manuals for optional BAS interface
be removed and the drive must be restarted. The modules are shipped with the chiller. They can also be found
above table list the various ways to restart the drive. and downloaded from www.DaikinApplied.com.
Remove the Run command before attempting to clear
a fault. If the Run command is present, the control will • IM 966-1, BACnet® IP Communication Module
disregard any attempt to reset the fault. • IM 967-1, BACnet® Communication Module (MS/TP)
• IM 968-1, LONWORKS Communication Module
Recommended Periodic Inspection • IM 969-2, Modbus® Communication Module
WARNING • ED 15120, Protocol Information for MicroTech® III chiller,
Electrical Shock Hazard. Before servicing or inspecting BACnet and LONWORKS
the equipment, disconnect power to the unit.The internal • ED 15121, Protocol Information for MicroTech® III chiller,
capacitor remains charged after power is turned off. Wait Modbus
at least the amount of time specified on the drive before
touching any components.

www.DaikinApplied.com 77 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Startup and Shut-down Procedures

Startup and Shut-down Procedures

Pre Startup 3. Put System Switch (S1) to the Emergency Stop position.
Inspected the chiller to ensure no components became loose 4. Put both circuit #1 & #2 switches to the Pumpdown and
or damaged during shipping or installation including leak test Stop position.
and wiring check. 5. Apply power to the unit. The panel Alarm Light will stay
on until S1 is closed. Ignore the Alarm Light for the check
Pre-Startup Water Piping Checkout out period. If you have the optional Alarm Bell, you may
1. Check the pump operation and vent all air from the wish to disconnect it.
system. 6. Check at the power block or disconnect for the proper
2. Circulate evaporator water, checking for proper system voltage and proper voltage between phases. Check
pressure and evaporator pressure drop. Compare the power for proper phasing using a phase sequence meter
pressure drop to the evaporator water pressure drop before starting unit.
curve. 7. Check for 120 Vac at the optional control transformer and
3. Flush System and clean all water strainers before placing at TB-2 terminal #1 and the neutral block (NB).
the chiller into service. 8. Check between TB-2 terminal #7 and NB for 120 Vac
4. Check water treatment and proper glycol percent. supply for transformer #2.

5. Pre-Startup Refrigerant Piping Checkout 9. Check between TB-2 terminal #2 and NB for 120 Vac
control voltage. This supplies the compressor crank case
6. Check all exposed brazed joints for evidence of leaks. heaters.
Joints may have been damaged during shipping or when
the unit was installed. 10. Check between TB-3 terminal #17 and #27 for 24 Vac
control voltage.
7. Check that all refrigerant valves are either opened or
closed as required for proper operation of the chiller.
8. A thorough leak test must be done using an approved Startup
electronic leak detector. Check all valve stem packing for Refer to the MicroTech® III Controller information on page 24 to
leaks. Replace all refrigerant valve caps and tighten. become familiar with unit operation before starting the chiller.
9. Check all refrigerant lines to insure that they will not There should be adequate building load (at least 50 percent
vibrate against each other or against other chiller of the unit full load capacity) to properly check the operation of
components and are properly supported. the chiller refrigerant circuits.
10. Check all connections and all refrigerant threaded Be prepared to record all operating parameters required by
connectors. the “Compressorized Equipment Warranty Form”. Return
11. Look for any signs of refrigerant leaks around the this information within 10 working days to Daikin Applied as
condenser coils and for damage during shipping or instructed on the form to obtain full warranty benefits.
installation.
12. Connect refrigerant service gauges to each refrigerant Startup Steps
circuit before starting unit. • Verify chilled water flow.
• Verify remote start / stop or time clock (if installed) has
Pre-Startup Electrical Check Out requested the chiller to start.
• Set the chilled water setpoint to the required temperature.
WARNING
(The system water temperature must be greater than the
Electrical power must be applied to the compressor total of the leaving water temperature setpoint plus one-
crankcase heaters 8 hours before starting unit to eliminate half the control band plus the startup delta-T before the
refrigerant from the oil. MicroTech® III controller will stage on cooling.)
1. Open all electrical disconnects and check all power • Set the Evap Delta T based on a percent of unit nominal
wiring connections. Start at the power block and check flow indicated in Table 11 on page 24 and the Start
all connections through all components to and including Delta T as a starting point. Delta-T=Tons x 24 / gpm
the compressor terminals. These should be checked • Check the controller setpoints to be sure that factory
again after 3 months of operation and at least yearly defaults are appropriate.
thereafter. • Put both pumpdown switches (PS1 and PS2) to the ON
2. Check all control wiring by pulling on the wire at the position.
spade connections and tighten all screw connections. • Put system switch (S1) to ON position.
Check plug-in relays for proper seating and to insure
retaining clips are installed.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 78 www.DaikinApplied.com


Startup and Shut-down Procedures

Table 66: Pumpdown and System Switch Positions Shutdown


Switch Position
Switch
ON OFF
Temporary Shutdown
PS1, PS2, Circuits will operate Circuit will go 1. Put both circuit switches to the OFF position (Pumpdown
Pumpdown Switches in the normal, through the normal and Stop).
automatic mode pumpdown cycle and 2. After compressors have stopped, put System Switch (S1)
shut off. to OFF (emergency stop).
S1, System Switch Unit will operate in Unit will shut off 3. Turn off chilled water pump. Chilled water pump to
the normal automatic immediately without operate while compressors are pumping down.
mode pumping down
(emergency stop) 4. To start the chiller after a temporary shutdown, follow the
startup instructions.

Post Startup Extended Shutdown


After the chiller has been operating for a period of time and has 1. Front seat both condenser liquid line service valves.
become stable, check the following: 2. Put both circuit switches to the OFF position (Pumpdown
• Compressor oil level. (Some scroll compressors do not and Stop position).
have oil sight glasses). 3. After the compressors have stopped, put System Switch
• Refrigerant sight glass for flashing. (S1) to the OFF position (emergency stop).
• Rotation of condenser fans. 4. Front seat both refrigerant circuit discharge valves (if
• Complete the “Compressorized Equipment Warranty applicable).
Form.”
5. If chilled water system is not drained, maintain power to
the evaporator heater to prevent freezing. Maintain heat
tracing on the chilled water lines.
6. Drain evaporator and water piping to prevent freezing.
7. If electrical power to the unit is on, the compressor
crankcase heaters will keep the liquid refrigerant out of
the compressor oil. This will minimize startup time when
putting the unit back into service. The evaporator heater
will be able to function.
8. If electrical power is off, make provisions to power the
evaporator heater (if chilled water system is not drained
or is filled with suitable glycol). Tag all opened electrical
disconnect switches to warn against startup before the
refrigerant valves are in the correct operating position.
To start the chiller after an extended shutdown, follow the
prestartup and startup instructions.

www.DaikinApplied.com 79 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Component Operation

Component Operation

Hot Gas Bypass (Optional) Warnings and Alerts


This option allows the system to operate at lower loads without A solid green LED indicates the module is powered and
excessive on/off compressor cycling. The hot gas bypass operation is normal.
option is required to be on both refrigerant circuits because of A solid red LED indicates an internal problem with the module.
the lead / lag feature of the controller.
A flashing green LED communicates Warning codes. Warning
This option allows passage of discharge gas into the codes do not result in a trip or lockout condition.
evaporator inlet (between the TX valve and the evaporator)
which generates a false load to supplement the actual chilled A flashing red LED communicates Alert codes. Alert codes will
water or air handler load. result in a trip condition and possibly a lockout condition
NOTE: The hot gas bypass valve will not generate a 100%
false load. Warning Codes (Flashing Green LED )
The pressure regulating valve is factory set to begin opening Code 1 – Loss of Communication: The module will flash the
at 102 psig with R-410a and can be changed by changing the green Warning LED one time indicating the module has not
pressure setting. The adjustment range is 75 to 150 psig. To communicated with the master controller for longer than 5
raise the pressure setting, remove the cap on the bulb and minutes.
turn the adjustment screw clockwise. To lower the setting, Code 2 – Reserved For Future Use
turn the screw counterclockwise. Do not force the adjustment
Code 3 – Short Cycling: The module will flash the green
beyond the range it is designed for as this will damage the
Warning LED three times indicating the compressor has short
adjustment assembly. The regulating valve opening point
cycled more than 48 times in 24 hours.
can be determined by slowly reducing the system load while
observing the suction pressure. When the bypass valve starts Code 4 – Open/Shorted Scroll Thermistor: The module will
to open, the refrigerant line on the evaporator side of the valve flash the green Warning LED four times indicating an open/
will begin to feel warm to the touch. shorted
A solenoid valve is located ahead of the bypass valve and is
controlled by the MicroTech® III controller. It is active when the Alert/Lockout Codes (Flashing Red LED)
first stage of cooling on a circuit is active. Code 1 – Motor High Temperature: The module will flash the
red Alert LED one time indicating the motor is onerheating .
WARNING
A code 1 Alert will open the M2-M1 contacts. The Alert will
The hot gas line may become hot enough to cause injury. Be reset after 30 minutes. Five consecutive Code 1 Alerts will
careful during valve checkout. lockout the compressor. Once the module has locked out the
compressor, a power cycle or Modbus reset command will be
required for the lockout to be cleared.
VFD Low Ambient Control Code 2 – Open/Shorted Motor Thermistor: The module will
(Optional) flash the red Alert LED two times indicating the motor PTC
thermistor circuit has an open/shorted thermistor chain (see
The optional VFD fan control is used for unit operation below Table 2). A Code 2 Alert will open the M2-M1 contacts. The
32°F (0°C) down to a minimum of -10°F (-23.3°C). The control Alert will reset after 30 minutes and the M2-M1 contacts will
looks at the saturated discharge temperature and varies close if the resistance of the motor PTC circuit is back in the
(pressure) at the “target” temperature. This temperature is normal range. The module will lockout the compressor and a
established as an input to a setpoint screen labeled “Sat power cycle or Modbus reset command will be required to clear
Condenser Temp Target.” the lockout.
Code 3 – Short Cycling: The module will flash the red Alert
Compressor Communications LED three times indicating the compressor is locked out due to
short cycling. Once locked out the compressor, a power cycle
The communication module provides advanced diagnostics, or Modbus reset command will be required to clear the lockout.
protection, and communications that enhance compressor
Code 4 – Scroll High Temperature: The module will flash
performance and reliability.
the red Alert LED four times indicating the over-temperature
Features include motor temperature protection, scroll condition. A Code 4 Alert will open the M2-M1 contacts.The
temperature protection, missing phase protection, reverse Alert will reset after 30 minutes. Once the module has locked
phase protection, low control circuit voltage protection, short out the compressor, a power cycle or Modbus reset command
cycling detection and alert, modbus communication to system will be required to clear the lockout.
controller, operational and fault history storage, and LED status
Code 5 – Reserved for Future Use
display.
Code 6 – Missing Phase: The module will flash the red Alert
LED six times indicating a missing phase. The Alert will reset

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 80 www.DaikinApplied.com


Component Operation

after 5 minutes and the module will lockout the compressor


after 10 consecutive Code 6 Alerts. Once locked out, a power
Phase Voltage Monitor (Optional)
cycle or Modbus reset is required. Factory settings are as follows:
Code 7 – Reverse Phase: The module will flash the red Alert • Trip Delay Time: 2 seconds.
LED seven times indicating a reverse phase in two of the three • Voltage Setting: set at nameplate voltage.
compressor leads. The modules will lockout the compressor • Restart Delay Time: 60 seconds.
after one Code 7 Alert. A power cycle or Modbus reset
command will be required to clear the lockout.
Code 8 – Reserved For Future Use
Code 9 – Module Low Voltage: The module will flash the red
Alert LED nine times indicating low module voltage for more
than 5 seconds. The Alert will reset after 5 minutes and the M2-
M1 contacts will close if the T2-T1 voltage is above the reset
value.

NOTE: If a compressor with CoreSense Communications


fails in the field, the CoreSense module should
remain with the failed compressor so the
manufacturer’s technicians can download the
CoreSense data to assist with determining the root
cause of compressor failure.

Replaceable Core Filter-Driers


For units with replaceable core filter driers, the core assembly
of the replaceable core drier consists of a filter core held tightly
in the shell in a manner that allows full flow without bypass.
A condenser liquid line service valve is provided for isolating
the charge in the condenser, but also serves as the point from
which the liquid line can be pumped out. With the line free of
refrigerant, the filter-drier core(s) can be easily replaced.

Crankcase Heaters
The scroll compressors are equipped with externally mounted
band heaters located at the oil sump level. The function of
the heater is to keep the temperature in the crankcase high
enough to prevent refrigerant from migrating to the crankcase
and condensing in the oil during off-cycle.
Power must be supplied to the heaters 8 hours before starting
the compressors.

Evaporator
The evaporator is a compact, high efficiency, dual circuit,
brazed plate-to-plate type heat exchanger consisting of parallel
stainless steel plates. The evaporator is protected with an
electric resistance heater and insulated with 3/4” (19mm)
thick closed-cell polyurethane insulation. This combination
provides freeze protection down to -20°F (-29°C) ambient air
temperature. The water side working pressure of the brazed
plate type of evaporator is 653 psig (4502 kPa). Evaporators
are designed and constructed according to, and listed by,
Underwriters Laboratories (UL).

www.DaikinApplied.com 81 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Maintenance

General Figure 51: Micro-Channel Coil Cross Section


Unit Maintenance

On initial start-up and periodically during operation, it will


be necessary to perform certain routine service checks.
Among these are checking the liquid line sight glasses, taking
condensing and suction pressure readings, and checking
to see that the unit has normal superheat and subcooling
readings. A recommended maintenance schedule is located at
the end of this section.

Evaporator
The evaporators are brazed plate design. Other than cleaning
and testing, no service work should be required on the
evaporator.

Compressor Maintenance
The scroll compressors are fully hermetic and require no
maintenance other than checking oil level.

Lubrication
No routine lubrication is required on AGZ units. The fan motor
bearings are permanently lubricated and no further lubrication
is required. Excessive fan motor bearing noise is an indication
of a potential bearing failure.
Cleaning Micro-Channel Aluminum Coils
Maintenance consists primarily of the routine removal of dirt
POE type oil is used for compressor lubrication. Further details
and debris from the outside surface of the fins and repairing
are listed in the Unit Service section on page 86.
any fin damage.
WARNING
POE oil must be handled carefully using proper protective Cleaning ElectroFin® Coated Coils
equipment (gloves, eye protection, etc.) The oil must not The following cleaning procedures are recommended as part
come in contact with certain polymers (e.g. PVC), as it may of the routine maintenance activities for ElectroFin Coated
absorb moisture from this material. Also, do not use oil or Coils. Documented routine cleaning of ElectroFin Coated
refrigerant additives in the system. Coils is required to maintain warranty coverage. The cleaning
procedure can be downloaded from the ElectroFin web site
www.luvata.com/electrofin, click on Procedures for Cleaning.
All-Aluminum Condenser Coils WARNING
The condenser coils are an all-aluminum design including the
Prior to cleaning the unit, turn off and lock out the main
connections, micro-channels, fins (an oven brazing process
power switch to the unit and open all access panels.
brazes the fins to the micro-channel flat tube), and headers
(see “Micro-Channel Coil Cross Section”), which eliminates
the possibility of corrosion normally found between dissimilar Remove Surface Loaded Fibers
metals of standard coils. Surface loaded fibers or dirt should be removed prior to water
rinse to prevent further restriction of airflow. If unable to back
During the condensing process, refrigerant in the coil passes
wash the side of the coil opposite that of the coils entering air
through the micro-channel flat tubes, resulting in higher
side, then surface loaded fibers or dirt should be removed with
efficiency heat transfer from the refrigerant to the airstream. In
a vacuum cleaner. If a vacuum cleaner is not available, a soft
the unlikely occurence of a coil leak, contact Daikin Applied to
non-metallic bristle brush may be used. In either case, the tool
receive a replacement coil module.
should be applied in the direction of the fins. Coil surfaces can
be easily damaged (fin edges bent over) if the tool is applied
across the fins.
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and
dirt into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 82 www.DaikinApplied.com


Unit Maintenance

Periodic Clean Water Rinse application of this product. As in all surface preparation,
the best work yields the best results.
A monthly clean water rinse is recommended for coils that are
applied in coastal or industrial environments to help to remove 2. Apply CHLOR*RID DTS - Apply CHLOR*RID DTS
chlorides, dirt and debris. An elevated water temperature (not directly onto the substrate. Sufficient product must be
to exceed 130ºF) will reduce surface tension, increasing the applied uniformly across the substrate to thoroughly
ability to remove chlorides and dirt. Pressure washer PSI must wet out surface with no areas missed. This may
not exceed 900 psig and the nozzel should remain at least 1 be accomplished by use of a pump-up sprayer or
foot from the coil to avoid damaging fin edges. conventional spray gun. The method does not matter, as
long as the entire area to be cleaned is wetted. After the
Routine Quarterly Cleaning of ElectroFin substrate has been thoroughly wetted, the salts will be
Coated Coil Surfaces soluble and is now only necessary to rinse them off.

Quarterly cleaning is essential to extend the life of an 3. Rinse - It is highly recommended that a hose be used
ElectroFin Coated Coil and is required to maintain warranty as a pressure washer will damage the fins. The water to
coverage. Coil cleaning shall be part of the unit’s regularly be used for the rinse is recommended to be of potable
scheduled maintenance procedures. Failure to clean an quality, though a lesser quality of water may be used if a
ElectroFin Coated Coil will void the warranty and may result in small amount of CHLOR*RID DTS is added. Check with
reduced efficiency and durability in the environment. CHLOR*RID International, Inc. for recommendations on
lesser quality rinse water.
For routine quarterly cleaning, first clean the coil with an
approved coil cleaner (see approved products list in Table 67). Harsh Chemical and Acid Cleaners
After cleaning the coils with the approved cleaning agent, use
the approved chloride remover to remove soluble salts and Harsh chemicals, household bleach or acid cleaners should
revitalize the unit. not be used to clean outdoor or indoor ElectroFin Coated
Coils. These cleaners can be very difficult to rinse out of the
Recommended Coil Cleaner coil and can accelerate corrosion and attack the ElectroFin
coating. If there is dirt below the surface of the coil, use the
The following cleaning agent, assuming it is used in recommended coil cleaners as described above.
accordance with the manufacturer’s directions on the container
for proper mixing and cleaning, has been approved for use on High Velocity Water or Compressed Air
ElectroFin Coated Coils to remove mold, mildew, dust, soot,
greasy residue, lint and other particulate: High velocity water from a pressure washer or compressed air
should only be used at a very low pressure to prevent fin and/
or coil damages. The force of the water or air jet may bend the
Table 67: ElectroFin Coated Coil Recommended Cleaning
fin edges and increase airside pressure drop. Reduced unit
Agents
performance or nuisance unit shutdowns may occur.
Cleaning Agent Reseller Part Number
Coil to Copper Tubing Connections
Hydro-Balance Corp
Figure 52 shows the aluminum condenser coil connection
Enviro-Coil P.O. Box 730
H-EC01 to the copper tubing in the unit. Because of the low melting
Concentrate Prosper, TX 75078
point of aluminum (1220°F compared to 1984°F for copper),
800-527-5166
this brazed joint is performed with a low temperature brazing
Enviro-Coil process. If brazing the copper to copper connection near the
Home Depot H-EC01
Concentrate aluminum to copper connection, care should be taken to keep
Chlor*Rid Int’l, Inc. temperature at the copper aluminum joint cool to due the fact
Chloride P.O. Box 908 that low temperature brazed is used on that joint.
Chlor*Rid DTS
Remover Chandler, AZ 85244
800-422-3217 CAUTION
Potential equipment damage. If a standard copper brazing
process is performed at this joint, the process will damage
CHLOR*RID DTS™ should be used to remove soluble salts the aluminum connection. If a condenser coil ever needs
from the ElectroFin Coated Coil, but the directions must be to be replaced, the copper aluminum joint repair should
followed closely. This product is not intended for use as a be done with a ProBraze™ repair kit manufactured by
degreaser. Any grease or oil film should first be removed with OmniTechnologies Corporation. A non-corrosive flux must
the approved cleaning agent. also be used. The brazing temperature should be between
1. Remove Barrier - Soluble salts adhere themselves 850°F–900°F. If a coil needs replacing, contact Daikin
to the substrate. For the effective use of this product, Applied for a coil and copper connection assembly.
the product must be able to come in contact with the
salts. These salts may be beneath any soils, grease or
dirt; therefore, these barriers must be removed prior to

www.DaikinApplied.com 83 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Maintenance

Figure 52: Aluminum/Copper Connection any maintenance. The solenoids can, however, require
replacement of the solenoid coil or of the entire valve
assembly.

System Adjustment
To maintain peak performance at full load operation, the
system superheat and liquid subcooling may require
adjustment. Read the following subsections closely to
determine if adjustment is required.

Liquid Line Sight Glass and Subcooling


The refrigerant sight glasses should be observed periodically. A
clear glass of liquid indicates that there is subcooled refrigerant
charge in the system. Bubbling refrigerant in the sight glass,
during stable run conditions, may indicates that the system can
be short of refrigerant charge. However, it is not unusual to
see bubbles in the sight glass during changing load conditions.
Electrical Terminals Refrigerant gas flashing in the sight glass could also indicate
an excessive pressure drop in the liquid line, possibly due to a
DANGER
clogged filter-drier or a restriction elsewhere in the liquid line.
Electric shock hazard. Turn off all power before continuing
If the unit is at steady full load operation and bubbles are
with following service.
visible in the sight glass, then check liquid subcooling. The
AGZ units have a condenser coil design with approximately
High Ambient Control Panel 15% of the coil tubes located in a subcooler section of the coil
This option consists of an exhaust fan with rain hood, two inlet to achieve liquid cooling to within 5-10°F (2.8-5.6°C) of the
screens with filters, necessary controls and wiring to allow outdoor air temperature when all condenser fans are operating.
operation to 125°F (52°C). The components can be factory or Subcooling should be checked at full load with 70°F (21.1°C)
field installed as a kit. ambient temperature or higher, stable conditions, and all fans
running. Liquid line subcooling at the liquid shut-off valve
• It must be supplied on units operating at ambient should be between 15 and 20 degrees F at full load.
temperatures of 105°F (40.6°C) and above.
If subcooling is low, add charge to clear the sight glass. Once
• It is automatically included on units with fan VFD (low the subcooler is filled, extra charge will not lower the liquid
ambient option). temperature and does not help system capacity or efficiency.
• Check inlet filters periodically and clean as required.
If subcooling is normal (15 to 20 degrees F at full load) and
Verify that the fan is operational.
flashing is visible in the sight glass, check the pressure drop
across the filter-drier. See page 84 for maximum allowable
Filter-Driers pressure drops.
Replace the filter-drier any time excessive pressure drop is An element inside the sight glass indicates the moisture
read across the filter-drier and/or when bubbles occur in the condition corresponding to a given element color. Immediately
sight glass with normal subcooling. The filter-drier should also after the system has been opened for service, the element may
be changed if the moisture indicating liquid line sight glass indicate a wet condition. If the sight glass does not indicate
indicates excess moisture in the system. a dry condition after about 12 hours of operation, the circuit
Any residual particles from the condenser tubing, compressor should be pumped down and the filter-drier changed or verify
and miscellaneous components are swept by the refrigerant moisture content by performing an acid test on the compressor
into the liquid line and are caught by the filter-drier. oil.

Battery Expansion Valve


The controller has a battery located behind the clear The expansion valve’s function is to keep the evaporator
plastic bezel. It is a BR2032 with a minimum life of 2 years supplied with the proper amount of refrigerant to satisfy the
unpowered. It would be prudent to replace it on a 2-year cycle. load conditions.
There is no indication of an eminent failure. Before adjusting superheat, check that unit charge is correct
and liquid line sight glass is full with no bubbles and that the
circuit is operating under stable, full load conditions.
Liquid Line Solenoid Valve
The suction superheat for the suction leaving the evaporator is
The liquid line solenoid valves that shut off refrigerant flow set at the factory to 10 degrees F.
in the event of a power failure do not normally require

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 84 www.DaikinApplied.com


Unit Maintenance

Table 68: Planned Maintenance Schedule

Monthly Annual
Operation Weekly
(Note 1) (Note 2)
General
Complete unit log and review (Note 3) X
Visually inspect unit for loose or damaged components X
Inspect thermal insulation for integrity X
Clean and paint as required X
Electrical
Check terminals for tightness, tighten as necessary X
Clean control panel interior X
Visually inspect components for signs of overheating X
Verify compressor heater operation X
Test and calibrate equipment protection and operating controls X
Megger compressor motor (Note 4) X
Refrigeration
Leak test X
Check sight glasses for clear flow X
Check filter-drier pressure drop (see manual for spec) X
Perform compressor vibration test X
Acid test oil sample X
Condenser (air-cooled)
Clean condenser coils (Note 5) X
Check fan blades for tightness on shaft (Note 6) X
Check fans for loose rivets and cracks X
Check coil fins for damage X
Notes:
1. Monthly operations include all weekly operations.
2. Annual (or spring start-up) operations includes all weekly
and monthly operations.
3. Log readings can be taken daily for a higher level of unit
observation.
4. Never Megger motors while they are in a vacuum to
avoid damage to the motor.
5. Coil cleaning can be required more frequently in areas
with a high level of airborne particles.
6. Be sure fan motors are electrically locked out.

www.DaikinApplied.com 85 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Unit Maintenance

R-410A Refrigerant cardiac sensation effects.


• Evacuate systems and break vacuum (0 psig) with
Terminology nitrogen before welding or brazing.
• Always ventilate work areas before using open flames.
Bubble Point: The temperature/pressure where bubbles first
Exposure to open flames or glowing metal will form toxic
appear when heat is added to a liquid refrigerant. Used to
hydrofluoric acid & carbonyl fluoride. No smoking!
measure sub-cooling.
• Make sure all tools, equipment, and replacement
Dew Point: The temperature/pressure where droplets first components are rated for the refrigerant used.
appear when heat is removed from a refrigerant gas. Used to
measure superheat. POE Lubricants
Fractionalization: A change in refrigerant composition due
to the tendency of the higher pressure refrigerant to leak at a WARNING
faster rate, should a system have leakage from a static two- POE oil must be handled carefully using proper protective
phase region. equipment (gloves, eye protection, etc.) The oil must not
come in contact with certain polymers (e.g. PVC), as it may
Glide: The total difference of Dew and Bubble Point at a
absorb moisture from this material. Also, do not use oil or
specific condition. Mid-Point or Mean: Measurement half way
refrigerant additives in the system.
between Dew and Bubble Points.
Miscibility: The ability of a refrigerant and oil to mix and flow
together. POE type oil is used for compressor lubrication. This type of
oil is extremely hydroscopic which means it will quickly absorb
Solubility: The effect of refrigerant on the viscosity of a
moisture if exposed to air and may form acids that can be
lubricant.
harmful to the chiller. Avoid prolonged exposure of POE oil to
the atmosphere to prevent this problem.
Safety
It is important that only the manufacturer’s recommended oils
• ANSI/ASHRAE safety group A1. be used. Acceptable POE oil types are:
• Always carry and be familiar with MSDS information for
• CPI/Lubrizol Emkarate RL32-3 MAF
R-410a.
• Copeland Ultra 32-3 MAF
• Store refrigerant in clean, dry area out of direct sunlight.
• Parker Emkarate RL32-3MAF
• Never heat or store cylinders above 125° F. Note vehicle
precautions! • Virginia LE323MAF
• Never tamper with cylinder valves or pressure relief • Nu Calgon 4314-66
valves. (Typical relief for R-410A is 525 psig).
Procedure Notes
• Never refill disposable cylinders.
• Use only new sealed metal containers of oil to insure
• Verify cylinder hook-up.
quality.
• Verify cylinder label and color code match. R-410A is
• Buy smaller containers to prevent waste and
rose/light maroon. Must be DOT approved, R-410A with
contamination.
400 psig rating. Open cylinders slowly.
• Use only filter driers designed for POE and check
• Avoid rough handling of cylinders and secure as
pressure drops frequently.
appropriate. Cap when not in use.
• Test for acid and color at least annually. Change filter
• Do not overfill recovery cylinders or overcharge units.
driers if acid or high moisture (> 200 ppm) is indicated (<
• Check gauge calibration before every use and manifold 100 ppm typical).
set for leaks regularly.
• Evacuate to 500 microns and hold test to insure systems
• Be aware of pneumatic and possible hydrostatic pressure are dry.
potentials.
• Never pressurize systems with oxygen or ref/air mix. Control and Alarm Settings
R-410A, R-407C, R-134A, & R-22 are flammable with low
The software that controls the operation of the unit is factory-
air mix.
set for operation with R-410A taking into account that the
• Wear protective clothing. Impervious gloves and splash pressure/temperature relationship differs from R-22. The
goggles should be worn. software functionality is the same for either refrigerant.
• Avoid contact with liquid refrigerant (R-410A -60.8°F @
atms.) due to corrosion and freezing hazards. Refrigerant Charging
• Avoid exposure to vapors. 1000 ppm/8 hr.
If a unit is low on refrigerant, you must first determine the
• Evacuate areas in cases of large releases. R-410A is cause before attempting to recharge the unit. Locate and repair
heavier than air and can cause asphyxiation, narcotic and any refrigerant leaks. Soap works well to show bubbles at

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 86 www.DaikinApplied.com


Unit Maintenance

medium size leaks but electronic leak detectors are needed to POE oils and for the refrigerant pressure (R-410A 600psig
locate small leaks. typical).
Charging or check valves should always be used on charging R-410A compressor internal relief is 600-650 psid.
hoses to limit refrigerant loss and prevent frostbite. Ball valve Brazed connections only. No StayBrite or solder connections
type recommended. (solder should never be used with any refrigerant). K or L type
Charge to 80-85% of normal charge before starting the refrigeration tubing only. Use nitrogen purge. Higher R-410A
compressors. pressures and smaller molecule size make workmanship more
critical.
Charging procedure R-410A must be charged from cylinder as a liquid unless entire
The units are factory-charged with R-410A. Use the following cylinder is used. Use a Refrigerant flow restrictor if charging
procedure if recharging in the field is necessary: liquid to suction or to a system at pressure below a saturated
temperature of 32° F.
To prevent fractionalization, liquid must be charged from
the refrigerant cylinder, unless charging the entire cylinder EPA recovery and handling requirements for R-410A are the
contents. same as R-22.
The charge can be added at any load condition between Cooling the recovery cylinder will speed recovery and lessen
25 to 100 percent load per circuit, but at least two fans per stress on recovery equipment.
refrigerant circuit should be operating if possible.
WARNING
Start the system and observe operation.
Service on this equipment is to be performed by qualified
Trim the charge to the recommended liquid line sub-cooling refrigeration personnel familiar with equipment operation,
(approximately 15-20°F typical). maintenance, correct servicing procedures, and the safety
Verify the suction superheat (10 degrees F for EEVs and 10 – hazards inherent in this work. Causes for repeated tripping
12 degrees F for TXVs) at full load conditions. of equipment protection controls must be investigated and
corrected.
Use standard charging procedures (liquid only) to top off the
charge. Disconnect all power before doing any service inside the
unit.
Check the sight glass to be sure there is no refrigerant flashing.
Servicing this equipment must comply with the requirements
With outdoor temperatures above 60°F (15.6°C), all condenser set forth by the EPA in regards to refrigerant reclamation and
fans should be operating and the liquid line temperature venting.
should be within 5°F to 10°F (2.8°C to 5.6°C) of the outdoor
air temperature. At 25-50% load, the liquid line temperature
should be within 5°F (2.8°C) of outdoor air temperature with all
fans on. At 75-100% load the liquid line temperature should be
within 10°F (5.6°C) of outdoor air temperature with all fans on.
It may be necessary to add refrigerant through the compressor
suction. Because the refrigerant leaving the cylinder must be
a liquid, exercise care to avoid damage to the compressor by
using a flow restrictor. A sight glass can be connected between
the charging hose and the compressor. It can be adjusted to
have liquid leave the cylinder and vapor enter the compressor.
Overcharging of refrigerant will raise the compressor discharge
pressure due to filling of the condenser tubes with excess
refrigerant.

Service
With R-410A, fractionalization, if due to leaks and recharge has
a minimal effect on performance or operation.
Special tools will be required due to higher refrigerant
pressures with R-410A. Oil-less/hp recovery units, hp recovery
cylinders (DOT approved w/525# relief), gauge manifold 30”-
250 psi low/0-800 psi high, hoses w/800 psi working & 4,000
psi burst.
All filter driers and replacement components must be rated

www.DaikinApplied.com 87 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Troubleshooting Chart

Troubleshooting Chart

PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS


1. Main or compressor disconnect switch open. 1. Close switch.
2. Fuse blown. circuit breakers open 2. Check electrical circuits and motor windings for shorts or
grounds. Investigate for possible overloading. Check for loose or
corroded connections.Replace fuse or reset breakers after fault
cause is corrected.
3. Thermal overloads tripped 3. Overloads are auto-reset. Check voltages, cycle times and
mechanical operations. Allow time for auto-reset.
Compressor Will
Not Run 4. Defective contactor or coil. 4. Replace.
5. System shutdown by equipment protection devices 5. Determine type and cause of shutdown and correct it before
restarting equipment.
6. No cooling required 6. None. Wait until unit calls for cooling.
7. Liquid line solenoid will not open 7. Repair or replace solenoid. Check wiring.
8. Motor electrical trouble 8. Check motor for opens, shorts, or burnout.
9. Loose wiring 9. Check all wire junctions. Tighten all terminal screws.
1. Low lift, inverted start 1. Control issues or condenser fan VFDs needed.
2. Compressor running in reverse 2. Check unit and compressor for correct phasing.
Compressor Noisy
3. Improper piping or support on suction or discharge 3. Relocate, add, or remove hangers.
Or Vibrating
4. Worn compressor isolator bushing 4. Replace.
5. Compressor mechanical failure 5. Replace.
1. Noncondensables in system 1. Extract noncondensables with approved procedures or
replace charge.
2. Circuit overcharged with refrigerant 2. Remove excess, check liquid subcooling.

High Discharge 3. Optional discharge shutoff valve not open 3. Open valve.
Pressure 4. Condenser fan control wiring not correct 4. Correct wiring.
5. Fan not running 5. Check electrical circuit and fan motor.
6. Dirty condenser coil 6. Clean coil.
7. Air recirculation 7. Correct.
1. Rapid load swings 1. Stabilize load.
2. Lack of refrigerant 2. Check for leaks, repair, add charge. Check liquid sight glass.
3. Fouled liquid line filter drier 3. Check pressure drop across filter drier. Replace.
4. Expansion valve malfunctioning 4. Repair or replace and adjust for proper superheat.
Low Suction
5. Condensing temperature too low 5. Check means for regulating condenser temperature.
Pressure
6. Compressors not staging properly 6. See corrective steps - Compressor Staging Intervals Too Low.
7. Insufficient water flow 7. Correct flow.
8. Excess or wrong oil used 8. Recover or change oil
9. Evaporator dirty 9. Back flush or clean chemically.

IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 88 www.DaikinApplied.com


Troubleshooting Chart

PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS


1. Defective capacity control 1. Replace.
Compressor Will Not
2. Faulty sensor or wiring 2. Replace.
Stage Up
3. Stages not set for application 3. Adjust controller setting for application.
1. Thermostat control band not set properly 1. Adjust controller settings for application.
2. Faulty water temperature sensor 2. Replace.
3. Insufficient water flow 3. Correct flow.
Compressor Staging
4. Rapid temperature or flow swings 4. Stabilize load.
Intervals Too Short
5. Oversized equipment 5. Evaluate equipment selection
6. Chiller enabled with no load 6. Evaluate BAS sequence and settings
7. Light loads 7. Evaluate need for HGBP or thermal inertia
1. Oil hang-up in remote piping 1. Review refrigerant piping and correct.
2. Low oil level 2. Verify superheat, add oil.
3. Loose fitting on oil line 3. Repair.
4. Level too high with compressor operating 4. Confirm correct superheat, remove oil.

Compressor Oil 5. Insufficient water flow - Level too high 5. Correct flow, verify superheat.
Level Too High Or 6. Excessive liquid in crankcase - Level too high 6. Check crankcase heater. Check liquid line solenoid valve operation.
Too Low 7. Short cycling 7. Stabilize load or correct control settings for application.
8. HGBP valve oversize or improperly set-up 8. replace or adjust HGBP valve
9. Expansion valve operation or selection 9. Confirm superheat at minimum and maximum load conditions
10. Compressor mechanical issues 10. Replace compressor
11. Wrong oil for application 11. Verify
1. Voltage imbalance or out of range 1. Correct power supply.
Motor Overload
2. Defective or grounded wiring in motor 2. Replace compressor.
Relays or Circuit
3. Loose power wiring or burnt contactors 3. Check all connections and tighten, replace contactors.
Breakers Open
4. High condenser temperature 4. See corrective steps for High Discharge Pressure.
1. Operating beyond design conditions 1. Correct so conditions are within allowable limits.
2. Discharge valve not open 2. Open valve.
Compressor Thermal
3. Short cycling 3. Stabilize load or correct control settings for application
Protection Switch
4. Voltage range or imbalance 4. Check and correct.
Open
5. High superheat 5. Adjust to correct superheat.
6. Compressor mechanical failure 6. Replace compressor.

www.DaikinApplied.com 89 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS


Warranty Registration Form (Scroll)

Warranty Registration Form (Scroll) Warranty Registration Form (Scroll)

Warranty Registration Form (Scroll)

Attention: W arranty Department Scroll Compressor Equipment W arranty Registration Form


Daikin This f orm must be completely f illed out and returned to the
P.O Box 2510 Staunton Warranty Department w ithin te n (10) days of start-up in order to comply
Staunton, VA 24402-2510 w ith the terms of "Daikin Limited Product Warranty".

Check, Test and Commissioning for


Scroll Product (AGZ, ACZ, W GZ, TGZ)

Note : Us e OM and IM M or Late r M anuals

Job Nam e : Startup Date :

Daik in G.O. No.: Daik in S.O. No.:

Ins tallation Addre s s : City/State /Zip:

Purchas ing Contractor: Phone :

City/State /Zip: No. of units at s ite :

Unit M ode l No.: Se rial No.:

Com pre s s or # 1 Se rial #: Com pre s s or # 4 Se rial No.:

Com pre s s or # 2 Se rial. #: Com pre s s or # 5 Se rial No.:

Com pre s s or # 3 Se rial #: Com pre s s or # 6 Se rial No.:

Be ns haw /DRC Control Box M /M #: Be ns haw /DRC Control Box S/N #:

I. PRE START-UP PROCEDURE

II. Pre Start-Up Checklist

Pre Start-Up Checklist, All NO checks require an explanation under "Description". Please check yes or no.
YES NO
A. Is the unit free of visible shipping damage, corrosion or paint problems?

B. Is unit installed level?

C. Does the unit meet all location, installation and service clearances per IM Bulletin?

D. Has thermostat bulb been properly installed in the well?

E. Are all set screws on all pulleys, bearings, and fans tight?

F. Does electrical service correspond to unit nameplate?


Volts Hertz Phase
G. Has electrical service been checked for proper phasing at each circuit power terminal block?

H. Has unit been properly grounded?

I. Has a fused disconnect and fuses or breaker been sized per product manual and installed per local code?

J. Are all electrical power connections tight?

K. Have compressor heaters and oil separator heaters been


been operating for 24 hours prior to start-up?

L. Does all field wiring conform to unit electrical specifications?

74 Form # SF-99007 • Part #: 041541502-D


IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS 90 www.DaikinApplied.com
Warranty Registration Form (Scroll)

Warranty Registration Form (Scroll)

M. Are all service and liquid line valves open?

N. Have all shipping hold down plates been removed?

O. Has a flow switch been installed per the IM bulletin?

P. Has the chill water circuit been cleaned, flushed, and water treatment confirmed?

Q. Does the chiller and condenser water piping conform to the IM Bulletin?

R. Are fans properly aligned and turn freely?

S. Is wind impingement against the air cooled condenser a consideration?

T. Description of unit location with respect to building structures.

Description:

III. REFRIGERATION SYSTEM


YES NO
A. Has all field piping been leak tested at 100 psig (690 kPA)?
MicroTech Verification
C. Water Temperatures: Leaving Evaporator.............................................................................. °F (°C) °F (°C)
B. Has system been properly evacuated and charged?
Entering Evaporator ............................................................................. °F (°C) °F (°C)
Entering Condenser.............................................................................. °F (°C) °F (°C)
C. Refrigerant R- Circuit 1 lbs (kg) Circuit 2 lbs. (kg)
Leaving Condenser............................................................................... °F (°C) °F (°C)
D. Circuit #1Refrigerant Pressures:
D. Does piping to unit appear to be adequately
Evaporator _________sizedpsig and(kPa)installed ________according°F ( °C) to the IM bulletin? ________psig
Minimum Condenser Pressure ________ psig (kPa)
E. Is a liquid line filter-drier installed in each
Maximum circuit?Pressure ________ psig (kPa)
Condenser
E. Circuit #2 Refrigerant Pressures:
F. Is level of oil in sightglass visible butnot more
Evaporator ________ thanpsig 1/2(kPa)glass________
with compressors°F ( °C) running? psig
Minimum Condenser Pressure _______ psig (kPa)
G. Is a liquid line solenoid installed Maximum
in eachCondenser
circuit?Pressure _______ psig (kPa)
F. Circuit #1 Refrigerant Temperatures:
H. Is expansion valve bulb properly Saturated Evaporator
installed Temperature.......................................................
and insulated? °F (°C) °F (°C)
Suction Line Temperature.................................................................... °F (°C) °F (°C)
IV. DESIGN CONTROLS Suction Superheat................................................................................. °F (°C) °F (°C)
Saturated Condenser Temperature ....................................................... °F (°C) °F (°C)
A. CHILLER Condenser Approach ............................................................................ °F (°C) °F (°C)
Water Pressure Drop: Liquid Line
psig(kPa)Temperature .....................................................................
Ft. (kPa) gpm (lps) °F (°C) °F (°C)
Water Temperatures: Entering Subcooling ...........................................................................................
°F (°C) Leaving °F (°C) °F (°C) °F (°C)
G. Circuit #2 Refrigerant Temperatures:
B. CONDENSER Saturated Evaporator Temperature....................................................... ________°F (°C) °F (°C)
Water Pressure Drop: Suction Line
psig(kPa) Temperature....................................................................
Ft. (kPa) gpm (lps) ________°F (°C) °F (°C)
Water Temperatures: Entering Suction Superheat.................................................................................
°F (°C) Leaving °F (°C) ________°F (°C) °F (°C)
Saturated Condenser Temperature ....................................................... ________°F (°C) °F (°C)
V. START-UP Condenser Approach ............................................................................ ________°F (°C) °F (°C)
Liquid Line Temperature ..................................................................... ________°F (°C) °F (
YES NO
Subcooling ........................................................................................... ________°F (°C) °F (
A. Does unit start and perform per sequence of operation as stated in the IM bulletin?
H. Outdoor Air Temperature ............................................................................................................ ________°F (°C) °F (°C)
B. Does condenser fans rotate in the proper directions?

Form # SF-99007 • Part #: 041541502-D 75


www.DaikinApplied.com 91 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS
Warranty Registration Form (Scroll)

Warranty Registration Form (Scroll)

MICROTECH STATUS CHECK-Each Reading Must be Verified with Field Provided Instruments of Known Accuracy?

MicroTech Verification
C. Water Temperatures: Leaving Evaporator ……………………………… °F (°C) °F (°C)
Entering Evaporator ……………………………… °F (°C) °F (°C)
Entering Condenser ……………………………… °F (°C) °F (°C)
Leaving Condenser ……………………………… °F (°C) °F (°C)
D. Circuit #1 Refrigerant Pressures:
Evaporator psig (kPa) °F (°C) psig
Minimum Condensor Pressure psig (kPa)
Maximum Condenser Pressure psig (kPa)
E. Circuit #2 Refrigerant Pressures:
Evaporator psig (kPa) °F (°C) psig
Minimum Condensor Pressure psig (kPa)
Maximum Condenser Pressure psig (kPa)
F. Circuit #1 Refrigerant Temperatures:
Saturated Evaporator Temperature …………………… °F (°C) °F (°C)
Suction Line Temperature ………………………………. °F (°C) °F (°C)
Suction Superheat ………………………………………. °F (°C) °F (°C)
Saturated Condenser Temperature …………………… °F (°C) °F (°C)
Liquid Line Temperature ………………………………. °F (°C) °F (°C)
Subcooling ………………………………………………. °F (°C) °F (°C)
G. Circuit #2 Refrigerant Temperatures:
Saturated Evaporator Temperature …………………… °F (°C) °F (°C)
Suction Line Temperature ………………………………. °F (°C) °F (°C)
Suction Superheat …………………………………….... °F (°C) °F (°C)
Saturated Condenser Temperature …………………… °F (°C) °F (°C)
Liquid Line Temperature ………………………………. °F (°C) °F (°C)
Subcooling ………………………………………………. °F (°C) °F (°C)

H. Outdoor Air Temperature: ……………………………………………………….. °F (°C) °F (°C)

NON-MICROTECH READINGS

I. Does the system contain glycol? Yes No


Percentage by weight or by volume
J. If the chilled water system include glycol, have the freezstats been adjusted lower to meet acutal job requirements?
Yes No
Note: See operation manual for low temperature on ice bank applications.
K. Waterside Pressure Drop:
Chiller: psig (kPa) Ft. (kPa) gpm (lps)
Condenser: psig (kPa) Ft. (kPa) gpm (lps)
L. Unit Voltage Across Each Phase: V V V
M. Unit Current Per Phase: amps amps amps
N. Compressor Current Per Phase:
Comrpessor #1: Amps Amps Amps
Compressor #2: Amps Amps Amps
Compressor #3: Amps Amps Amps
Compressor #4: Amps Amps Amps
Compressor #5: Amps Amps Amps
Compressor #6: Amps Amps Amps

IOM
76 1206-3 • TRAILBLAZER MODEL AGZ CHILLERS
™ 92 www.DaikinApplied.com
Form # SF-99007 • Part #: 041541502-D
Warranty Registration Form (Scroll)

Warranty Registration Form (Scroll)

VI. CONTROL CHECK AND SETPOINT VERIFICATION/STANDARD UNIT SETPOINT


MICROTECH SETPOINTS MICROTECH STANDARD
A. Leaving Evaporator ………………………………………………………………….. °F (°C) °F (°C)
B. Reset Leaving ……………………………………………………………………… °F (°C) °F (°C)
C. Reset Signa ..………………………………………………………………………… ma
D. Reset Option………………………………………………………………………….
E. Maximum Chilled Water Reset …………………………………………………… °F (°C) °F (°C)
F. Return Setpoint ………………………………………………………………………. °F (°C)
G. Maximum Pulldown ………………………………………………………………. °F (°C)
H. Control Band………………………………………………………………………….. °F (°C) °F (°C)
I. Interstage Delay ………………………………………………………………………. sec. sec.
J. Start-to-Stop Delay ………………………………………………………………….. min.
K. Stop-to-Stop Delay …………………………………………………………………… min.
L. Stage Up Error ………………………………………………………………………. psig (kPa)
M. Stage Down Error ………………………………………………………………….. psig (kPa)

ALARM SETPOINTS MUST BE VERIFIED WITH INSTRUMENTS OF KNOWN ACCURACY

N. Low Pressure Hold ………………………………………………………………. psig (kPa) psig (kPa)


O. Low Pressure Unload……………………………………………………………. psig (kPa) psig (kPa)
P. Chilled Water Freezestat………………………………………………………… psig (kPa) psig (kPa)
Q. High Pressure Cut-Out………………………………………………………….. psig (kPa) psig (kPa)
R. Unit Type =
S. Number of Compressors =
T. Number of Stages =
U. Number of Fan Stages =
V. Software Version =

VII. FOR HEAT RECOVERY CHILLERS ONLY (Must Be Taken At Full Load)
A. Place Unit in heat recovery mode.
B. Waterside Pressure Drop: psig (kPa) Ft. (kPa) gpm (lps)
C. Waterside Temperatures: Inlet Outlet
D. Head Pressure: Circuit #1 psig (kPa) Circuit #2: psig (kPa)
E. Suction Pressure: Circuit #1 psig (kPa) Circuit #2: psig (kPa)
F. Compressor Current Per Phase
Compressor #1 AMPS AMPS AMPS
Compressor #2 AMPS AMPS AMPS
Compressor #3 AMPS AMPS AMPS
Compressor #4 AMPS AMPS AMPS

VIII. GENERAL
YES NO
A. Are all control lines secure to prevent excess vibration and wear? ……………………………………….
B. Are all gauges shut off, valve caps, and packings tight after startup? ……………………………………
Performed By: Title:

Company Name:

Address:
City/State/Zip Code: Telephone:

Modem Number:

Signature: Date:
Contractor's Signature

Form # SF-99007 • Part #: 041541502-D 77


www.DaikinApplied.com 93 IOM 1206-3 • TRAILBLAZER™ MODEL AGZ CHILLERS
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at
www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.

Aftermarket Services

To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.

Products manufactured in an ISO Certified Facility.

IOM 1206-3 (05/15) ©2015 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com

You might also like