EE Computation
EE Computation
CIRCUIT BREAKER
Load Description
Circuit No. VA Amperes VOLTAGE RATING Size of Conductor Size of Conduit
Load Qty AT P AF
2 - 3.5 mm2 THHN Cu. Wire1- 2.0
1 Lighting Outlets LED Type 8 800 3.48 230 15 2 100 mm2 THHN Cu. Wire(G)
15 mm Dia.PVC Conduit
Therefore Use : 2 - 30.0 mm2 THWN-2 Cu. Wire Therefore Use : 100 AT, CB
1- 8.0 mm2 TW Cu. Wire (G)
In 40 mm dia. RMC
Note:
Use GFCI type C.O. for outlets Located at Toilet and Barthroom, Laundry Area, and near kitchen sinks
Use Weather Proof type outlet for C.O. located at terrace and garrage and outdoor areas
Use 14 mm2 for the grounding and bonding conductor of the panel board
PP 1
CIRCUIT BREAKER
Load Description
Circuit No. VA Amperes VOLTAGE RATING Size of Conductor Size of Conduit
Load Qty AT P AF
2 - 3.5 mm2 THHN Cu. Wire1- 3.5
1 Convenience Outlets 5 900 3.91 230 20 2 100 mm2 THHN Cu. Wire(G)
20 mm Dia.PVC Conduit
Therefore Use : 2 - 125.0 mm2 THWN-2 Cu. Wire Therefore Use : 250 AT, CB
1- 22.0 mm2 TW Cu. Wire (G)
In 40 mm dia. RMC
Note:
Use GFCI type C.O. for outlets Located at Toilet and Barthroom, Laundry Area, and near kitchen sinks
Use Weather Proof type outlet for C.O. located at terrace and garrage and outdoor areas
Use 14 mm2 for the grounding and bonding conductor of the panel board
MDP
CIRCUIT BREAKER
Load Description
Circuit No. VA Amperes VOLTAGE RATING Size of Conductor Size of Conduit
Load Qty AT P AF
2 - 30.0 mm2 THHN Cu. Wire1- 8.0
1 LP 1 1 25,200.00 109.57 230 100 2 150 mm2 THHN Cu. Wire(G)
32 mm Dia.PVC Conduit
3 Spare 1,500.00
4 Spare 1,500.00
TOTAL 110,750.00 468.48
Therefore Use : 2 - 250.0 mm2 THW Cu. Wire Therefore Use : 350 AT, CB
1- 30.0 mm2 TW Cu. Wire (G)
In 65 mm dia. RMC