The UG series inductive voltage transformers use oil-paper insulation for models up to 420 kV. They have a compact design with a primary winding running from the terminal through an SF6 insulated bushing to the magnetic core, around which secondary windings are also wound. They provide very high accuracy over their 30+ year lifespan and are designed to withstand high voltages and temperatures while being transportable and environmentally friendly. The range of models goes from 123 kV up to 420 kV.

Uploaded by

Carlos Fernandez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
274 views4 pages

Arteche CT Ug en

The UG series inductive voltage transformers use oil-paper insulation for models up to 420 kV. They have a compact design with a primary winding running from the terminal through an SF6 insulated bushing to the magnetic core, around which secondary windings are also wound. They provide very high accuracy over their 30+ year lifespan and are designed to withstand high voltages and temperatures while being transportable and environmentally friendly. The range of models goes from 123 kV up to 420 kV.

Uploaded by

Carlos Fernandez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

INDUCTIVE VOLTAGE TRANSFORMERS > UG Series

UG SERIES
Oil-paper insulation:
model UG up to 420 kV.
1. Primary terminal
2. Pressure relief device
3. HV Electrode
4. Insulator
5. LV Electrode
6. Manometer
7. Primary windings
8. Secondary windings
9. Core
10. Secondary terminal box
11. Gas filling valve

1
2

9 8

10

11

28 Instrument transformers | High voltage


INDUCTIVE VOLTAGE TRANSFORMERS > UG Series

DESIGN AND MANUFACTURING


The voltage transformer primary conductor The windings have an antiresonant design,
runs from the primary terminal through an SF6 which makes the transformer work properly
insulated bushing with electrodes for proper both at power frequency and during temporary
electrical field distribution. Then it is wounded high frequency transients. Layers of plastic
thousands of times around the magnetic with a high dielectric resistance and excellent
core. The secondary winding(s) are wounded thermal and mechanical performance and the
around the same core, which is loaded with SF6 form the electrical insulation.
their combined burden, and located in the
bottom part of the transformers within a
metallic external enclosure.

CHARACTERISTICS
› Very high and invariable accuracy (up to › Reduced size due to a compact design that
0.1%) steady for the operational life of the is easy to transport, store and install, and
equipment, with maximum reliability. which reduces visual impact.
› Up to 4 secondary windings with or › May be transported and stored horizontally
without taps, with metering, protection, or or vertically.
dual function.
› Anti-resonant winding design.
OPTIONS:
› Internal arc test compliant as per IEC 61869
and other standards. › Sealable secondary terminals.
› Designed to withstand rated voltage with › Different cable glands and accessories.
internal atmospheric gas pressure. › Wide range of primary and secondary
› Robust mechanical strength. terminals.
› Silicone rubber insulator. › Secondary protection devices inside the
› Excellent response under extreme terminal box (fuses or MCB).
environmental conditions: Temperatures › Ferroresonance suppressing devices.
from -50°C up to +60°C, high altitudes,
seismic hazard areas, violent winds, etc.
› Maintenance-free throughout their
complete lifespan of more than 30 years.
Only periodic monitoring is recommended.
› Temperature compensated densimeter with
two levels of alarm that can be wired to the
control equipment for remote monitoring.
› Designed to minimize gas volume, pressure
and leaks, with a leakage rate <0.5%/year
(lower values available upon request), thus
reducing its environmental impact. Each
unit is tested individually.
› Tanks and insulators are designed,
manufactured and tested according to
international pressure vessel standards.
› Officially homologated in-house testing
facilities.
› Quality management system certifications:
ISO9001, ISO14001 and OHSAS 18001.
› Each unit is routine tested following
applicable standards.
› Complete type tests reports following
international standards.
› Compliance to any international or
domestic standards.
› Environmentally friendly. The materials used
for construction are recyclable and resistant
to the elements. Its advanced design
adheres to environmental regulations.

Instrument transformers | High voltage 29


INDUCTIVE VOLTAGE TRANSFORMERS > UG Series

RANGE
This series is named with the letters UG
followed by 3 numbers indicating the
maximum service voltage for which they have
been designed.
The table on the next page shows the range
currently manufactured by ARTECHE.
These characteristics are merely indicative.
ARTECHE can manufacture these transformers
to comply with any domestic or international
standard.
Secondary windings for:
› Protection: all possible types.
› Metering: accuracy classes for any meter- H

ing/billing need (including high accuracy


class 0.1 / 0.15 with extended range in cur-
rent).
Number of secondary windings: up to 4
secondary windings are possible in a single
device.

30 Instrument transformers | High voltage


INDUCTIVE VOLTAGE TRANSFORMERS > UG Series

Gas insulation > Model UG

Rated insulation level Dimensions


Standard
Highest Thermal
creepage Weight
Model voltage Lightning burden
Power Switching distance (kg)
(kV) impulse (VA) AxB H
frequency impulse (mm)
(BIL) (mm) (mm)
(kV) (kVp)
(kVp)

UG-123 123 230 550 - 1000 3813 315x315 2400 450

UG-145 145 275 650 - 1000 4495 315x315 2400 450

UG-170 170 325 750 - 1000 5270 315x315 2600 470

UG-245 245 460 1050 - 1000 7595 450x450 3200 650

UG-300 300 460 1050 850 1000 9300 450x450 3550 700

UG-362 362 510 1175 950 1000 11222 600x600 3900 1100

UG-420 420 630 1425 1050 1000 13020 600x600 4600 1200

These dimensions and weights are approximate based on standard requirements.


For detailed values please consult with Arteche.

Instrument transformers | High voltage 31