PDF Helvar
PDF Helvar
PDF Helvar
Lamp Wattage No. of Ballast EEI Dimensions Connection Weight Circuit Mains Lamp
type lamps power current power
d
Dimensions 1 2 a
c
Length 'a' (mm) 280 360
Width 'b' (mm) 30 30 a
Height 'c' (mm) 21 21
'd' (mm) 270 350 b
Delivery information
Ballast Unit package Transportation package
Minimum Plastic One-way pallet Pallet Pallet
delivery binding 1200 x 820 weight height
amount strip (pcs.) (kg) (cm)
EL1 x s 10 2000 350 - 420 57
EL2 x s 10 1500 395 57
EL3/4 x s 10 1500 390 57
6 Data is subject to change without notice. More information at: www.helvar.com T07 103 1A 30.08.2010 1/2
EL-su
Electronic ballasts for T5 fluorescent lamps
14-80 W 220-240V 50-60Hz 1
• Only 21 mm high
• Optimal lamp operation
• Wide operational ambient temperature range
• Standard & sidemount possibilities
• With terminals for both manual and automatic
wiring (IDC & push-in)
• Low power losses EEI = A2
• Silent operation
• Stabilized flickerfree light
• High power factor
Lamp Wattage No. of Ballast EEI Dimensions Connection Weight Circuit Mains Lamp
type lamps power current power
Note: See pages 14-15 for connection diagrams and additional characteristics.
d
Dimensions 1 2 a
c
Length 'a' (mm) 280 360
Width 'b' (mm) 30 30 a
Height 'c' (mm) 21 21
'd' (mm) 270 350 b
Delivery information
Ballast Unit package Transportation package
Minimum Plastic One-way pallet Pallet Pallet
delivery binding 1200 x 820 weight height
amount strip (pcs.) (kg) (cm)
EL1 x s-u 10 2000 350 - 420 57
EL2 x s-u 10 1500 395 57
EL3/4 x s-u 10 1500 390 57
Data is subject to change without notice. More information at: www.helvar.com T07 103 1A 30.08.2010 2/2 7
EL-s, EL-su
Electronic ballasts for T8 fluorescent lamps
1 18-70 W 220-240V 50-60Hz
• Only 21 mm high
• Optimal lamp operation
• Wide operational ambient temperature range
• Standard & sidemount possibilities
• Optional terminals for automatic wiring
• Low power losses
• Silent operation EEI = A2
• Stabilized flickerfree light
• High power factor
Lamp Wattage No. of Ballast EEI Dimensions Connection Weight Circuit Mains Lamp
type lamps power current power
Note: See pages 14-15 for connection diagrams and additional characteristics.
**) With terminals for both manual and automatic wiring (IDC & push-in)
d
Dimensions 1 2 3 4 a
c
drawing a a b b
Length 'a' (mm) 280 360 280 360 a
Width 'b' (mm) 30 30 30 30
Height 'c' (mm) 21 21 21 21 b
'd' (mm) 270 350 270 350 d
d
Delivery information b
c
Ballast Unit package Transportation package
Minimum Plastic One-way pallet Pallet Pallet a
delivery binding 1200 x 820 weight height
amount strip b
(pcs.) (kg) (cm)
EL1 x s 10 2000 350 - 420 57 d
EL2 x s 10 1500 395 57
EL3/4 x s 10 1500 385 57
8 Data is subject to change without notice. More information at: www.helvar.com T07 104 1A 11.5.2011 1/2
EL-ngn
Electronic ballasts for T8 fluorescent lamps
18-58 W 220-240V 50-60Hz 1
• Energy saving
• Warm Start according to lamp standards
• Flickerless light
• Covers EMC requirements
• Low harmonics
• Low power losses
• Stabilized output EEI = A2
Lamp Wattage No. of Ballast EEI Dimensions Connection Weight Circuit Mains Lamp
type lamps power current power
Note: See pages 14-15 for connection diagrams and additional characteristics.
Dimensions 1 a c
Length 'a' (mm) 280
Width 'b' (mm) 30 a
Height 'c' (mm) 28
'd' (mm) 270 b
Delivery information
Ballast Unit package Transportation package
Minimum Plastic One-way pallet Pallet Pallet
delivery binding 1200 x 820 weight height
amount strip (pcs.) (kg) (cm)
EL1 x ngn 10 1600 330 60
EL2 x ngn 10 1600 320-360 60
EL4 x ngn 10 1600 370 60
Data is subject to change without notice. More information at: www.helvar.com T07 104 1A 11.5.2011 2/2 9
EL-s
Electronic ballasts for compact fluorescent lamps
1 18-80 W 220-240V 50-60Hz
• Only 21 mm high
• Optimal lamp operation
• Wide operational ambient temperature range
• Standard & sidemount possibilities
• Low power losses
• Silent operation
• Stabilized flickerfree light EEI = A2
• High power factor
Lamp Wattage No. of Ballast EEI Dimensions Connection Weight Circuit Mains Lamp
type lamps power current power
Note: See pages 14-15 for connection diagrams and additional characteristics.
1) With terminals for both manual and automatic wiring(IDC & push-in)
2) Tested and recommended by Helvar, not ENEC approved
d
Dimensions 1 2 3 4 a
c
drawing a a b b
Length 'a' (mm) 280 360 280 360 a
Width 'b' (mm) 30 30 30 30
Height 'c' (mm) 21 21 21 21 b
'd' (mm) 270 350 270 350 d
d
Delivery information b
c
Ballast Unit package Transportation package
Minimum Plastic One-way pallet Pallet Pallet a
delivery binding 1200 x 820 weight height
amount strip b
(pcs.) (kg) (cm)
EL1 x s 10 2000 350 - 420 57 d
EL2 x s 10 1500 395 57
EL3/4 x s 10 1500 390 57
10 Data is subject to change without notice. More information at: www.helvar.com T07 105 1B 28.11.2011 1/4
Connection diagrams
1
EL-s, EL-su, EL-ngn, EL-TCs
NOTE: All wiring to the connectors marked with a red dot (hot wires) should be as short as possible.
1 2 3
4 5 6
7 8 9
1
2
3
4
5
6
10 11 12
5
6
7
1
2 8
3 9
4 10
14 Data is subject to change without notice. More information at: www.helvar.com T07 106 1B 08.04.2011 1/2
Characteristics
1
EL-s / EL-su EL-ngn EL-TCs
Max.temperature at tc point 75°C 3) 4) 75 °C 75°C
Ambient temperature range -20…+50°C -20...+50°C -20…+50°C
Storage temperature range -40…+80°C -40...+80 °C -40…+80°C
Maximum relative humidity no condensation no condensation no condensation
Number of starts per lamp > 50 000 > 50 000 > 50 000
AC Range 198-264 VAC 5)6) 198-264 VAC 198-264 VAC
DC range (starting voltage >190VDC) 176-280 VDC 6) 176-280 VDC 176-280 VDC 1)
Over voltage duration 320 VAC, 1 h 320 VAC, 1 h 320 V / 1 h
Power factor (at maximum), typical 0.98 0.98 > 0.95
Earth leakage current < 0.4 mA < 0.4 mA < 0.4 mA
Maximum working voltage (Uout) 400 V 350 V 250 V 2)
50 000 h, 50 000 h, 50 000 h,
Lifetime (90% survival)
at tc at tc at tc
Max length of ballast to lamp wiring 2m 1.5 m 1 m/2 m (hot/cold)
Ignition time, typical ~1.0 s <1s ~1 s
Standards
EL-s / EL-su EL-ngn EL-TCs
General and safety requirements EN61347-2-3
Additional safety requirements for AC/DC supplied
ballasts acc. to EN61347-2-3 Annex J
Performance requirements EN60929
Lamp life acc. to EN60081 / EN60901 *)
Mains current harmonics, acc. to EN61000-3-2
Radio Frequency Interference, acc. to EN55015
Immunity standard, acc.to EN61547
Vibration test EN60068-2-64 test Fh
Bump test EN60068-2-29 test Eb
Thermal protection class EN61347, C5e
* EN 60081 for T5 & T8 fluorescent lamps, EN 60901 for compact fluorescent lamps
Data is subject to change without notice. More information at: www.helvar.com T07 106 1B 08.04.2011 2/2 15