Lighting Calc

This document provides lighting calculations for external areas of new MedGulf facilities under construction at RLIC in Qatar. It details the design parameters, methodology, analysis and results of lighting calculations performed using Dialux software. Calculations were conducted for roadways, parking areas, and open spaces to ensure illuminance levels meet recommended CISBE/BSEN standards. The results indicate the proposed lighting layout and selected luminaires will provide adequate illuminance across external areas in line with design requirements.

Uploaded by

Nagoor Meeran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
427 views28 pages

Lighting Calc

This document provides lighting calculations for external areas of new MedGulf facilities under construction at RLIC in Qatar. It details the design parameters, methodology, analysis and results of lighting calculations performed using Dialux software. Calculations were conducted for roadways, parking areas, and open spaces to ensure illuminance levels meet recommended CISBE/BSEN standards. The results indicate the proposed lighting layout and selected luminaires will provide adequate illuminance across external areas in line with design requirements.

Uploaded by

Nagoor Meeran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

CONTRACT NO.

: MJ-1901/20892

CONTRACT TITLE: DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF


FACILITIES IN RLIC

DOCUMENT TITLE:

LIGHTING CALCULATION - EXTERNAL

DESIGN CONSULTANT:

10/11/2022 0 ISSUED FOR RLIC APPROVAL NM VP BT RLIC

Date Rev Description Prepared Checked Approved Approved

Document No. 1901-EL-CAL-002 Page: 01 of 28


Document Title: Doc No. 1901-EL-CAL-002
LIGHTING CALCULATION - EXTERNAL Rev.: 0
Date : 10/11/2022

Page: 2 of 28

Contents

1. INTRODUCTION: ........................................................................................................................................... 3
2. OBJECTIVE: ................................................................................................................................................... 3
3. DESIGN PARAMETERS .............................................................................................................................. 3
4. DESIGN REFERENCE .................................................................................................................................. 3
5. ANALYSIS....................................................................................................................................................... 3
5.1 Methodology .............................................................................................................................................. 3
5.2 Calculation Results .................................................................................................................................. 4
5.3 Conclusion ................................................................................................................................................. 4
5.4 Reference Drawings ................................................................................................................................ 4
6. ATTACHMENT ............................................................................................................................................... 4
6.1 External Lighting calculation Result ................................................................................................... 4
Document Title: Doc No. 1901-EL-CAL-002
LIGHTING CALCULATION - EXTERNAL Rev.: 0
Date : 10/11/2022

Page: 3 of 28

1. INTRODUCTION:

Design and Engineering works for New Med Gulf facilities (such as Office Building, Fabrication
workshop building, Store, security room etc.) will be constructed by M/s. Med Gulf at RLIC and
the design works was awarded to M/s.QDC. In line with this new development, lighting design
for Outdoor application (for Road Lighting, Car parking and Open field area) has to be provided.

2. OBJECTIVE:

To calculate and check the lighting illuminance levels for Outdoor areas based on the proposed
lighting layout drawings with the selected type of luminaires. This is also to check adequacy of
the lighting lux level calculated which is in line to the recommended standards using Dialux
software 4.13 Version.

3. DESIGN PARAMETERS

The following are average illumination levels as per the Recommended CISBE / BS EN lighting
Standards.

External Lighting

Area Lux Reference standards


Road Lighting - Driveway 0.75 cd / sq.m BS EN 13201-2
Road Intersections 15 CIBSE
Car Parking 20 CIBSE
Open field area 50 ES.2.03.0001RB
Main Entrance 50 ES.2.03.0001RB
Building perimeter 10-20 CIBSE

4. DESIGN REFERENCE

 Chartered Institute for Building Services Engineers (CIBSE) Lighting Guide


 BS 5489 – Code of practice for the Design of road lighting Part :1 Lighting of roads
and public amenity areas
 Qatar Highway Design Manual
 ES.2.03.0001RB - Electrical Engineering Philosophy
 CE 140 / EN 13201 Part 2: Road Lighting – Performance Requirements

5. ANALYSIS

5.1 Methodology

For Outdoor area & road lighting process starts with inserting the area dimensions (width and
length of the plot) and inserting the buildings with their heights, width and length in meters. The
selected outdoor luminaires are then inserted in the design work area in the proposed location
and elevation.
Document Title: Doc No. 1901-EL-CAL-002
LIGHTING CALCULATION - EXTERNAL Rev.: 0
Date : 10/11/2022

Page: 4 of 28

The selection of luminaires type is taken from manufacturers on line plug-in where the light
data are inputs to the Dialux software Program Version 4.13. The input from the plug in are the
rated lumens of the lamps. The angle of rotation to check light direction for optimum light
distribution can be done. Adjustment can be done to add or reduce the luminaires until the
required level is achieved.

The selected luminaire shall be also compatible with the task, lighting requirement and location.
A multiplying Factor of 0.8 (Maintenance Factor) shall be used in the calculations.

5.2 Calculation Results

Summary of calculation results for external lighting is attached in Item 6.1 showing the required
and achieved average illumination lux levels. Dialux calculation shows the External lighting
calculation results.

5.3 Conclusion

As per the above satisfactory calculation results shown in the attached calculation results
summary, the proposed design and layout of External Lighting layout and for the new facilities
are adequate and meets the lighting level requirement. Hence, acceptable.

5.4 Reference Drawings

1901-EL-B0-002 – Site plan - External Lighting Layout

6. ATTACHMENT

6.1 External Lighting calculation Result


DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN
RLIC WEST SIDE

External Lighting

Rev-0

Partner for Contact:


Order No.:
Company:
Customer No.:

Date: 08.03.2022
Operator:
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

Table of contents

DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WES...
Project Cover 1
Table of contents 2
External Lighting
Planning data 3
Luminaires (layout plan) 4
Luminaires (coordinates list) 5
Calculation surfaces (results overview) 11
3D Rendering 13
False Color Rendering 14
8.0 Meter wide road
Planning data 15
Photometric Results 16
Valuation Fields
Valuation Field Roadway 1
Value Chart (E) 17
Observer
Observer 1
Value Chart (L) 18
Observer 2
Value Chart (L) 19
6.0 Meter wide road
Planning data 20
Photometric Results 21
Valuation Fields
Valuation Field Roadway 1
Value Chart (E) 22
Observer
Observer 1
Value Chart (L) 23
Observer 2
Value Chart (L) 24

Page 2
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Planning data

Light loss factor: 0.80, ULR (Upward Light Ratio): 2.0% Scale 1:2211
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
NORTHCLIFFE Auva LED1x16950 E937
1 42 16423 16423 135.3
T730 LSM1 (1.000)
NORTHCLIFFE Boreas MB LED1x24200
2 82 23312 23312 211.6
D355 T740 LS60 (1.000)
NORTHCLIFFE Nord LED1x5700 G474 T840
3 10 5665 5665 34.4
PCPC OP LT80 ta-40+50C (1.000)
Total: 2658000 Total: 2658000 23377.8

Page 3
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (layout plan)

Scale 1 : 1613

Luminaire Parts List

No. Pieces Designation


1 42 NORTHCLIFFE Auva LED1x16950 E937 T730 LSM1
2 82 NORTHCLIFFE Boreas MB LED1x24200 D355 T740 LS60
3 10 NORTHCLIFFE Nord LED1x5700 G474 T840 PCPC OP LT80 ta-40+50C

Page 4
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (coordinates list)

NORTHCLIFFE Auva LED1x16950 E937 T730 LSM1


16423 lm, 135.3 W, 1 x 1 x LED1x16950 T730 (Correction Factor 1.000).

No. Position [m] Rotation [°]


X Y Z X Y Z
1 26.288 197.271 8.000 0.0 0.0 -90.0
2 32.093 197.271 8.000 0.0 0.0 90.0
3 32.700 179.800 8.000 0.0 0.0 90.0
4 104.178 188.767 8.000 0.0 0.0 133.2
5 45.681 167.202 8.000 0.0 0.0 180.0
6 67.681 167.202 8.000 0.0 0.0 180.0
7 89.681 167.202 8.000 0.0 0.0 180.0
8 106.873 164.985 8.000 0.0 0.0 90.0
9 106.873 141.319 8.000 0.0 0.0 90.0
10 106.873 117.654 8.000 0.0 0.0 90.0
11 106.873 93.988 8.000 0.0 0.0 90.0
12 106.873 70.322 8.000 0.0 0.0 90.0
13 106.873 46.656 8.000 0.0 0.0 90.0
14 106.873 22.991 8.000 0.0 0.0 90.0
15 99.054 177.664 8.000 0.0 0.0 -89.6
16 102.050 5.949 8.000 0.0 0.0 48.2
17 -5.300 11.700 8.000 0.0 0.0 -58.1
18 29.036 48.810 8.000 0.0 0.0 58.2
19 83.657 1.613 8.000 0.0 0.0 0.0
20 58.711 1.613 8.000 0.0 0.0 0.0
21 33.765 1.613 8.000 0.0 0.0 0.0
22 8.819 1.613 8.000 0.0 0.0 0.0
23 -42.100 182.546 8.000 0.0 0.0 -155.0
24 -20.108 183.159 8.000 0.0 0.0 -180.0
25 32.446 155.468 8.000 0.0 0.0 90.0
26 32.446 133.791 8.000 0.0 0.0 90.0
27 32.446 112.114 8.000 0.0 0.0 90.0
28 32.446 90.437 8.000 0.0 0.0 90.0

Page 5
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (coordinates list)

No. Position [m] Rotation [°]


X Y Z X Y Z
29 32.446 68.761 8.000 0.0 0.0 90.0
30 13.982 37.608 8.000 0.0 0.0 32.2
31 -19.474 34.662 8.000 0.0 0.0 -58.1
32 -31.882 54.620 8.000 0.0 0.0 -58.1
33 -44.290 74.577 8.000 0.0 0.0 -58.1
34 -56.698 94.534 8.000 0.0 0.0 -58.1
35 -69.105 114.491 8.000 0.0 0.0 -58.1
36 -1.705 25.226 8.000 0.0 0.0 63.2
37 -7.600 33.700 8.000 0.0 0.0 163.2
38 -69.563 130.391 8.000 0.0 0.0 -89.6
39 -69.704 152.390 8.000 0.0 0.0 -89.6
40 -56.698 168.938 8.000 0.0 0.0 -135.0
41 -4.304 176.567 8.000 0.0 0.0 180.0
42 17.696 176.567 8.000 0.0 0.0 180.0

Page 6
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (coordinates list)

NORTHCLIFFE Boreas MB LED1x24200 D355 T740 LS60


23312 lm, 211.6 W, 1 x 1 x LED (Correction Factor 1.000).

No. Position [m] Rotation [°]


X Y Z X Y Z
1 52.669 183.978 9.500 0.0 -25.0 90.0
2 83.743 183.978 9.500 0.0 -25.0 90.0
3 69.019 184.972 9.500 0.0 -25.0 90.0
4 18.874 186.260 5.200 0.0 -15.0 0.0
5 -6.344 182.435 5.200 0.0 -20.0 180.0
6 -6.344 192.179 5.200 0.0 -20.0 180.0
7 14.271 200.360 8.000 60.0 0.0 0.0
8 -5.307 200.360 8.000 60.0 0.0 0.0
9 96.061 200.674 8.000 60.0 0.0 0.0
10 70.944 200.674 8.000 60.0 0.0 0.0
11 45.827 200.674 8.000 60.0 0.0 0.0
12 62.218 150.844 12.000 0.0 -15.0 90.0
13 82.418 150.844 12.000 0.0 -15.0 90.0
14 88.785 50.104 12.000 0.0 -40.0 -90.0
15 82.118 50.104 12.000 0.0 -40.0 -90.0
16 75.451 50.104 12.000 0.0 -40.0 -90.0
17 68.785 50.104 12.000 0.0 -40.0 -90.0
18 62.118 50.104 12.000 0.0 -40.0 -90.0
19 55.451 50.104 12.000 0.0 -40.0 -90.0
20 51.648 58.735 10.000 0.0 -15.0 180.0
21 51.648 75.435 10.000 0.0 -15.0 180.0
22 51.648 92.135 10.000 0.0 -15.0 180.0
23 51.648 108.835 10.000 0.0 -15.0 180.0
24 51.649 125.535 10.000 0.0 -15.0 180.0
25 51.649 142.235 10.000 0.0 -15.0 180.0
26 -24.100 104.300 16.000 0.0 -30.0 0.0
27 -24.393 105.007 16.000 0.0 -30.0 45.0
28 -25.100 105.300 16.000 0.0 -30.0 90.0

Page 7
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (coordinates list)

No. Position [m] Rotation [°]


X Y Z X Y Z
29 -25.807 105.007 16.000 0.0 -30.0 135.0
30 -26.100 104.300 16.000 0.0 -30.0 180.0
31 -25.807 103.593 16.000 0.0 -30.0 -135.0
32 -25.100 103.300 16.000 0.0 -30.0 -90.0
33 -24.393 103.593 16.000 0.0 -30.0 -45.0
34 4.600 148.900 16.000 0.0 -30.0 0.0
35 4.307 149.607 16.000 0.0 -30.0 45.0
36 3.600 149.900 16.000 0.0 -30.0 90.0
37 2.893 149.607 16.000 0.0 -30.0 135.0
38 2.600 148.900 16.000 0.0 -30.0 180.0
39 2.893 148.193 16.000 0.0 -30.0 -135.0
40 3.600 147.900 16.000 0.0 -30.0 -90.0
41 4.307 148.193 16.000 0.0 -30.0 -45.0
42 -28.600 143.900 16.000 0.0 -30.0 0.0
43 -28.893 144.607 16.000 0.0 -30.0 45.0
44 -29.600 144.900 16.000 0.0 -30.0 90.0
45 -30.307 144.607 16.000 0.0 -30.0 135.0
46 -30.600 143.900 16.000 0.0 -30.0 180.0
47 -30.307 143.193 16.000 0.0 -30.0 -135.0
48 -29.600 142.900 16.000 0.0 -30.0 -90.0
49 -28.893 143.193 16.000 0.0 -30.0 -45.0
50 -0.500 66.000 16.000 0.0 -30.0 0.0
51 -0.793 66.707 16.000 0.0 -30.0 45.0
52 -1.500 67.000 16.000 0.0 -30.0 90.0
53 -2.207 66.707 16.000 0.0 -30.0 135.0
54 -2.500 66.000 16.000 0.0 -30.0 180.0
55 -2.207 65.293 16.000 0.0 -30.0 -135.0
56 -1.500 65.000 16.000 0.0 -30.0 -90.0
57 -0.793 65.293 16.000 0.0 -30.0 -45.0
58 34.055 27.742 16.000 0.0 -30.0 0.0
59 33.763 28.449 16.000 0.0 -30.0 45.0
60 33.055 28.742 16.000 0.0 -30.0 90.0
61 32.348 28.449 16.000 0.0 -30.0 135.0
62 32.055 27.742 16.000 0.0 -30.0 180.0
63 32.348 27.035 16.000 0.0 -30.0 -135.0
64 33.055 26.742 16.000 0.0 -30.0 -90.0
65 33.763 27.035 16.000 0.0 -30.0 -45.0
66 10.015 105.852 16.000 0.0 -30.0 0.0

Page 8
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (coordinates list)

No. Position [m] Rotation [°]


X Y Z X Y Z
67 9.722 106.559 16.000 0.0 -30.0 45.0
68 9.015 106.852 16.000 0.0 -30.0 90.0
69 8.308 106.559 16.000 0.0 -30.0 135.0
70 8.015 105.852 16.000 0.0 -30.0 180.0
71 8.308 105.144 16.000 0.0 -30.0 -135.0
72 9.015 104.852 16.000 0.0 -30.0 -90.0
73 9.722 105.144 16.000 0.0 -30.0 -45.0
74 -5.271 199.771 8.000 60.0 0.0 180.0
75 -70.530 152.352 8.000 60.0 0.0 90.0
76 -70.530 130.422 8.000 60.0 0.0 90.0
77 -69.862 114.057 8.000 60.0 0.0 114.6
78 -57.219 94.196 8.000 60.0 0.0 121.9
79 -44.806 74.239 8.000 60.0 0.0 121.9
80 -32.393 54.281 8.000 60.0 0.0 121.9
81 -19.979 34.324 8.000 60.0 0.0 121.9
82 -5.796 11.374 8.000 60.0 0.0 119.2

Page 9
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Luminaires (coordinates list)

NORTHCLIFFE Nord LED1x5700 G474 T840 PCPC OP LT80 ta-40+50C


5665 lm, 34.4 W, 1 x 1 x LED1x5700 (Correction Factor 1.000).

No. Position [m] Rotation [°]


X Y Z X Y Z
1 43.262 196.415 2.500 0.0 0.0 0.0
2 49.305 196.415 2.500 0.0 0.0 0.0
3 55.348 196.415 2.500 0.0 0.0 0.0
4 61.391 196.415 2.500 0.0 0.0 0.0
5 67.434 196.415 2.500 0.0 0.0 0.0
6 73.477 196.415 2.500 0.0 0.0 0.0
7 79.520 196.415 2.500 0.0 0.0 0.0
8 85.563 196.415 2.500 0.0 0.0 0.0
9 15.844 196.985 2.400 0.0 0.0 0.0
10 105.646 194.774 2.400 0.0 0.0 0.0

Page 10
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Calculation surfaces (results overview)

Scale 1 : 2714

Calculation Surface List

No. Designation Type Grid Eav Emin Emax u0 Emin /


[lx] [lx] [lx] Emax
1 Main Entrance perpendicular 16 x 32 80 30 135 0.376 0.222
2 Car parking Area perpendicular 128 x 32 116 31 272 0.265 0.113
3 Driveway-1 perpendicular 32 x 128 66 36 113 0.551 0.322
4 Driveway-2 perpendicular 128 x 32 73 12 169 0.160 0.069
5 Driveway-3 perpendicular 128 x 32 56 27 84 0.481 0.321
6 Driveway-4 perpendicular 32 x 16 78 49 96 0.625 0.506
7 Driveway-5 perpendicular 16 x 128 50 22 98 0.430 0.219
Package
8 perpendicular 64 x 32 186 2.31 688 0.012 0.003
substation
9 Driveway-6 perpendicular 32 x 16 62 42 85 0.683 0.499

Page 11
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / Calculation surfaces (results overview)

Calculation Surface List

No. Designation Type Grid Eav Emin Emax u0 Emin /


[lx] [lx] [lx] Emax
10 Driveway-7 perpendicular 128 x 16 53 24 88 0.456 0.275
11 Driveway-8 perpendicular 128 x 32 72 32 107 0.444 0.297
12 Driveway-9 perpendicular 128 x 64 61 25 124 0.407 0.199
13 Driveway-10 perpendicular 64 x 16 58 29 84 0.499 0.347
14 Driveway-11 perpendicular 128 x 64 54 34 80 0.619 0.419
15 Driveway-12 perpendicular 128 x 64 68 36 180 0.532 0.200
RLIC Road - Entrance
16 perpendicular 128 x 32 25 3.56 112 0.140 0.032
side
17 Open workshop-Crane perpendicular 64 x 64 75 11 163 0.153 0.071
Open Area - Fabrication
18 perpendicular 64 x 128 54 14 168 0.252 0.081
workshop
19 Paint workshop area perpendicular 128 x 128 78 7.86 221 0.101 0.036
20 Radiography area-1 perpendicular 16 x 16 46 11 140 0.238 0.079
21 Radiography area-2 perpendicular 16 x 16 51 13 146 0.252 0.088
RLIC Road - Right side
22 perpendicular 64 x 64 29 7.32 123 0.251 0.059
road
RLIC Road - Back side
23 perpendicular 128 x 64 26 4.98 129 0.189 0.039
entrance road

Summary of Results

Type Quantity Average [lx] Min [lx] Max [lx] u0 Emin / Emax
perpendicular 23 51 2.31 688 0.05 0.00

Page 12
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / 3D Rendering

Page 13
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

External Lighting / False Color Rendering

Page 14
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

8.0 Meter wide road / Planning data

Street Profile

Roadway 1 (Width: 8.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)

Light loss factor: 0.80


Luminaire Arrangements

Luminaire: NORTHCLIFFE Auva LED1x16950 E937 T730 LSM1


Luminous flux (Luminaire): 16423 lm Maximum luminous intensities
Luminous flux (Lamps): 16423 lm at 70°: 655 cd/klm
Luminaire Wattage: 135.3 W at 80°: 47 cd/klm
Arrangement: Single row, bottom at 90°: 0.00 cd/klm
Pole Distance: 24.000 m Any direction forming the specified angle from the downward vertical, with the
Mounting Height (1): 8.000 m luminaire installed for use.
Height: 7.898 m No luminous intensities above 90°.
Overhang (2): 0.900 m Arrangement complies with luminous intensity class G3.
Boom Angle (3): 0.0 ° Arrangement complies with glare index class D.4.
Boom Length (4): 1.000 m

Page 15
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

8.0 Meter wide road / Photometric Results

Light loss factor: 0.80 Scale 1:215


Calculation Field List

1 Valuation Field Roadway 1


Length: 24.000 m, Width: 8.000 m
Grid: 10 x 6 Points
Accompanying Street Elements: Roadway 1.
tarmac: R3, q0: 0.070
Selected Lighting Class: ME4a

Lav [cd/m²] U0 Ul TI [%] SR


2.64 0.55 0.77 13 0.42

Page 16
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

8.0 Meter wide road / Valuation Field Roadway 1 / Value Chart (E)

Values in Lux, Scale 1 : 215

Grid: 10 x 6 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax


41 20 70 0.489 0.288

Page 17
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

8.0 Meter wide road / Valuation Field Roadway 1 / Observer 1 / Value Chart (L)

Values in Candela/m², Scale 1 : 215

Grid: 10 x 6 Points
Observer Position: (-60.000 m, 2.000 m, 1.500 m)
tarmac: R3, q0: 0.070

Lav [cd/m²] U0 Ul TI [%]


Calculated values: 2.64 0.55 0.77 13

Required values according to class ME4a: ≥ 0.75 ≥ 0.40 ≥ 0.60 ≤ 15

Fulfilled/Not fulfilled:

Page 18
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

8.0 Meter wide road / Valuation Field Roadway 1 / Observer 2 / Value Chart (L)

Values in Candela/m², Scale 1 : 215

Grid: 10 x 6 Points
Observer Position: (-60.000 m, 6.000 m, 1.500 m)
tarmac: R3, q0: 0.070

Lav [cd/m²] U0 Ul TI [%]


Calculated values: 2.84 0.56 0.87 10

Required values according to class ME4a: ≥ 0.75 ≥ 0.40 ≥ 0.60 ≤ 15

Fulfilled/Not fulfilled:

Page 19
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

6.0 Meter wide road / Planning data

Street Profile

Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)

Light loss factor: 0.80


Luminaire Arrangements

Luminaire: NORTHCLIFFE Auva LED1x16950 E937 T730 LSM1


Luminous flux (Luminaire): 16423 lm Maximum luminous intensities
Luminous flux (Lamps): 16423 lm at 70°: 655 cd/klm
Luminaire Wattage: 135.3 W at 80°: 47 cd/klm
Arrangement: Single row, bottom at 90°: 0.00 cd/klm
Pole Distance: 24.000 m Any direction forming the specified angle from the downward vertical, with the
Mounting Height (1): 8.000 m luminaire installed for use.
Height: 7.898 m No luminous intensities above 90°.
Overhang (2): 0.900 m Arrangement complies with luminous intensity class G3.
Boom Angle (3): 0.0 ° Arrangement complies with glare index class D.4.
Boom Length (4): 1.000 m

Page 20
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

6.0 Meter wide road / Photometric Results

Light loss factor: 0.80 Scale 1:215


Calculation Field List

1 Valuation Field Roadway 1


Length: 24.000 m, Width: 6.000 m
Grid: 10 x 6 Points
Accompanying Street Elements: Roadway 1.
tarmac: R3, q0: 0.070
Selected Lighting Class: ME4a

Lav [cd/m²] U0 Ul TI [%] SR


2.92 0.68 0.75 11 0.53

Page 21
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

6.0 Meter wide road / Valuation Field Roadway 1 / Value Chart (E)

Values in Lux, Scale 1 : 215

Grid: 10 x 6 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax


43 19 71 0.444 0.271

Page 22
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

6.0 Meter wide road / Valuation Field Roadway 1 / Observer 1 / Value Chart (L)

Values in Candela/m², Scale 1 : 215

Grid: 10 x 6 Points
Observer Position: (-60.000 m, 1.500 m, 1.500 m)
tarmac: R3, q0: 0.070
Lav [cd/m²] U0 Ul TI [%]
Calculated values: 2.92 0.68 0.75 11
Required values according to class ME4a: ≥ 0.75 ≥ 0.40 ≥ 0.60 ≤ 15

Fulfilled/Not fulfilled:

Page 23
DESIGN AND ENGINEERING WORKS FOR NEW MEDGULF FACILITIES IN RLIC WEST SIDE
08.03.2022

Operator
Telephone
Fax
e-Mail

6.0 Meter wide road / Valuation Field Roadway 1 / Observer 2 / Value Chart (L)

Values in Candela/m², Scale 1 : 215

Grid: 10 x 6 Points
Observer Position: (-60.000 m, 4.500 m, 1.500 m)
tarmac: R3, q0: 0.070
Lav [cd/m²] U0 Ul TI [%]
Calculated values: 3.11 0.70 0.83 11
Required values according to class ME4a: ≥ 0.75 ≥ 0.40 ≥ 0.60 ≤ 15

Fulfilled/Not fulfilled:

Page 24