Module 9 of Geotech
Module 9 of Geotech
Unit 9
Lateral Earth Pressure
Reference:
Das, B. M., & Sobhan, K. (2014). Principles of geotechnical engineering (8th ed.).
Stamford, Connecticut: Cengage Learning.
10 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Now, three possible cases may arise concerning the retaining wall; they are
described as follows:
Case 1 If the wall AB is static—that is, if it does not move either to the right or to the
left of its initial position—the soil mass will be in a state of static equilibrium. In that
case, σ’h is referred to as the at-rest earth pressure, or
Case 2 If the frictionless wall rotates sufficiently about its bottom to a position of
A’B (Figure 13.1b), then a triangular soil mass ABC’ adjacent to the wall will reach a
state of plastic equilibrium and will fail sliding down the plane BC9. At this time, the
horizontal effective stress, σ’h = σ’a, will be referred to as active pressure. Now,
11 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Case 3 If the frictionless wall rotates sufficiently about its bottom to a position A’’B
(Figure 13.1c), then a triangular soil mass ABC0 will reach a state of plastic
equilibrium and will fail sliding upward along the plane BC0. The horizontal effective
stress at this time will be σ’h = σ’p, the so-called passive pressure. In this case,
For coarse-grained soils, the coefcient of earth pressure at rest can be estimated by
using the empirical relationship
Figure 13.4 shows the distribution of lateral earth pressure at rest on a wall of height
H retaining a dry soil having a unit weight of γ. The total force per unit length of the
wall, Po, is equal to the area of the pressure diagram, so
12 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
The force per unit length of the wall for partially submerged soil, as shown in Figure
13.5, can be calculated using the following formula
13 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Example 1
Figure 13.6a shows a 4.5-m-high retaining wall. The wall is restrained from yielding.
Calculate the lateral force Po per unit length of the wall. Also, determine the location
of the resultant force. Assume that for sand OCR = 1.5.
Solution
14 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
The location of the resultant, measured from the bottom of the wall is
Or
z=
(
( 38.01 ) 1.5+
3
3) ( )
+ ( 38.01 )
1.5
2 ( )
+ ( 10.94 )
1.5
3
+(11.04)(
1.5
3
)
=1.76 m
98
Figure 13.10a shows a soil mass that is bounded by a frictionless wall, AB, that
extends to an infinite depth. The vertical and horizontal effective principal stresses
on a soil element at a depth z are σ’o and σ’h, respectively. If the wall AB is not
allowed to move, then σ’h = Ko σ’o. The stress condition in the soil element can be
represented by the Mohr’s circle a in Figure 13.10b. However, if the wall AB is
allowed to move away from the soil mass gradually, the horizontal principal stress
will decrease.
15 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Ultimately a state will be reached when the stress condition in the soil element can
be represented by the Mohr’s circle b, the state of plastic equilibrium and failure of
the soil will occur. This situation represents Rankine’s active state, and the effective
pressure σ’a on the vertical plane (which is a principal plane) is Rankine’s active
earth pressure.
16 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
17 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Active case Figure 13.19a shows a frictionless retaining wall with a cohesive soil
backfill. The active pressure against the wall at any depth below the ground surface
can be expressed as
The depth zo at which the active pressure becomes equal to 0 can be found from Eq.
(13.31) as
18 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
So, with time, tensile cracks at the soil–wall interface will develop up to a depth z o.
Passive case Figure 13.20a shows the same retaining wall with backfill similar to
that considered in Figure 13.19a. Rankine’s passive pressure against the wall at
depth z can be given by
19 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Example 2
An 6-m-high retaining wall is shown in Figure 13.21a. Determine:
a. Rankine active force per unit length of the wall and the location of the resultant
b. Rankine passive force per unit length of the wall and the location of the resultant
Solution
Part a
Because c’ = 0, to determine the active force
σ ' a=K a σ ' o=K a γz
1−sinφ ' 1−sin 36
Ka= = =0.26
1+ sinφ' 1+sin 36
At z = 0, σ’a = 0; at z = 6m,
σ’a = (0.26)(16)(6) = 24.96 kN/m2
The pressure-distribution diagram is shown in Figure 13.21b. The active force per
unit length of the wall
1
Pa= ( 6 )( 24.96 )=74.88 kN /m
2
Also,
z=2 m
Part b
To determine the passive force, we are given that c’ = 0. So,
σ ' p=K p σ ' o=K p γz
1+ sinφ' 1+ sin 36
K p= = =3.85
1−sinφ' 1−sin 36
At z = 0, σ’p = 0; at z = 6m,
σ’p = (3.85)(16)(6) = 369.6 kN/m2
20 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
The pressure-distribution diagram is shown in Figure 13.21c. The passive force per
unit length of the wall is
1
P p= ( 6 )( 369.6 )=1108.8 kN /m
2
Also,
6
z= =2 m
3
21 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Example 3
Refer to Figure 13.25. Given: α = 10°; θ = 5°; H = 4m; unit weight of soil, γ = 15
kN/m3; soil friction angle, Ø’ = 30°; and δ’ = 15°. Estimate the active force, Pa, per
unit length of the wall. Also, state the direction and location of the resultant force, P a.
Solution:
1 2
Pa= γ H K a
2
For Ø’ = 30°; δ’ = 15° - that is, δ’/φ’ = 15/30 = ½; α = 10°; and θ = 5°, the magnitude
of Ka using the formula is 0.3872.
22 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
2
cos (30−5)
Ka=
[ √ ]
2
2 sin ( 15+30 ) sin ( 30−10 )
cos 5 cos (15+ 5 ) 1+
cos ( 15+5 ) cos ( 5−10 )
¿
1 2
Pa= ( 15 )( 4 ) ( 0.3872 )=46.46 kN /m
2
The resultant will act at a vertical distance equal to H/3 = 4/3 = 1.33 m above the
bottom of the wall and will be inclined at an angle of 15° (= δ’) to the back face of the
wall.
23 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
Self-assessment
1. The figure below shows a non-yielding vertical wall retaining a sandy backfill
underlain by clay. Determine the magnitude of the resultant at-rest force per unit
length on the wall, Po. Ans. 267.93 kN/m.
24 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
2. For the retaining wall shown in Example 2, determine the force per unit length of
the wall for Rankine’s active state. Also find the location of the resultant. Ans. P o =
117.15 kN/m ; z = 1.78m.
Activity
1. The figure below shows a retaining wall that is restrained from yielding. Determine
the magnitude of the lateral earth force per length of the wall. Also, find the location
of the resultant, z, measured from the bottom of the wall. Given: H = 7.5m; Ø’ = 31°;
γ = 19.2 kN/m3; OCR = 2.2.
25 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
2. Assume that the retaining wall shown in Figure 13.39 is frictionless. Determine the
Rankine passive force per unit length of the wall, the variation of active earth
pressure with depth, and the location of the resultant. Given: H = 18ft; Ø’ = 23°; γ =
99 lb/ft3.
3. Assume that the retaining wall shown in Figure 13.39 is frictionless. Determine the
Rankine active force per unit length of the wall, the variation of active earth pressure
with depth, and the location of the resultant. Given: H = 29ft; Ø’ = 34°; γ = 119 lb/ft 3.
4. Consider the retaining wall shown in Figure 13.42. The height of the wall is 8 m,
and the unit weight of the sand backll is 21.1 kN/m3. Using Coulomb’s equation,
calculate the active force, Pa, on the wall for the following values of the angle of wall
friction. Also, comment on the direction and location of the resultant. Consider the
following two cases of wall friction:
a. δ’ = 25°
b. δ’ = 19°
26 | P a g e CE 8 – Geotechnical Engineering 1
MODULE 8
27 | P a g e CE 8 – Geotechnical Engineering 1