Transformer Equivalent Circuit
Transformer Equivalent Circuit
the transformer; that is, the resistance branch takes a current equal to
the core-loss current, and the reactance branch takes a current equal to
the true magnetising current. This method of treatment takes account
of the efficiency of the transformer, and the copper losses appear as
voltage drops. The phasor diagram corresponding to Figure A1.3 is
shown in Figure A1.4. E1 is the e.m.f. across the admittance Y0, and V1 E1
is the voltage drop (which is not measurable) that is assumed to occur
in the primary circuit if half the transformer reactance is allotted to the
primary side of the transformer.
Figure A1.4 Phasor diagram of equivalent circuit shown in FigureA1.3
D 0.211 A
D 17.4
Calculated secondary resistance D 0.00606
Actual secondary resistance R2 D 0.00606 ð 1.05
D 0.00637
R
D 13.4
and X0e
D 80.6
36 A
Rℓ
Rℓ0 D 0.624 ð 2110
D 1310
X
D 228 ð 0.6/292
D 0.468
D 987
ss °
D 6.51 A
Primary line current D 6.51 ð p3 D 11.3 A
⊳
ss
⊳
ss
Resistance drop to PP D
40.3 D 6800 V
V 10910 V
Percentage regulation
2%
i.e. V2 D 230 V
°
° °
1 D 38.6 C 1.3 D 39.9°
.
I0 D V1Z0 ⊲A1.3⊳
E1 D V2 C I02Z02
D IE1Ic C jIE1Im
D 5990 C j50500
Thus,
Z1 D 17.4 C j40.3
Z0 D 5990 C j50500
and .
Thus, substituting these values in equation (A1.1),
V
D 10540 n1.6° V
V2 D 10540/45.9 D 230 V
and the secondary terminal line voltage D 230p3 D 398 V.
I
D 6.45 n39.6° A
D 0.771
Power input
D 11000 ð 6.45 ð 0.771
D 54600 watts
I0 D 11000⊲5990 C j50500⊳ D
Thus it will be seen that the results obtained by the two methods of
calculation show close agreement.
13
Appendix 2
14