Intelligent Addressable Fire Alarm System: General
Intelligent Addressable Fire Alarm System: General
NFS2-3030
Intelligent Addressable Fire Alarm System
Intelligent Fire Alarm Control Panels
General
The NFS2-3030 is an intelligent Fire Alarm Control Panel designed for medium- to large-scale facilities. Fire emergency detection and evacuation are extremely critical to life safety, and the NFS2-3030 is ideally suited for these applications. The NFS2-3030 is part of the ONYX Series of products from NOTIFIER. The NFS2-3030 is ideal for virtually any application because it features a modular design that is configured per project requirements. With one to ten Signaling Line Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelligent addressable devices. Information is critical to fire evacuation personnel, and the NFS2-3030s large 640-character Liquid Crystal Display (LCD) presents vital information to operators concerning a fire situation, fire progression, and evacuation details.
The NFS2-3030 supports the FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD and permits monitoring of alarm signals over the Internet, saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line.
7070covg.jpg
A host of other options are available, including single- or multichannel voice; firefighters telephone; LED, LCD, or PC-based graphic annunciators; fire or integration networking; advanced detection products for challenging environments, and many additional options.
Features
Listed to UL Standard 864, 9th edition. One to ten isolated intelligent Signaling Line Circuits (SLC) Style 4, 6 or 7. Up to 159 detectors and 159 modules per SLC, 318 devices per loop/3,180 per FACP or network node. Detectors can be any mix of ion, photo, laser photo, thermal, or multi-sensor detectors; modules can be addressable pull stations, normally open contact devices, two-wire smoke, notification, or relay modules. Large 640-character LCD backlit display (16 lines x 40 characters) or display-less (a node on a network). Network options: High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, NCS, NFS-3030, NFS-640, and NCA). Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/ 400, AFP-1010, and AM2020). Up to 54 nodes when DVC is used in network paging. Built-in Alarm, Trouble, Security, and Supervisory relays. VeriFire Tools online/offline program option. Application code is saved in Flash memory. With built-in Degraded Mode operation, the system is capable of general alarm if a fire alarm condition is present even if the CPU fails.
Membrane Switch Controls: Acknowledge; Signal Silence; Drill; System Reset; Lamp Test. LCD Display: 640 characters (16 x 40) with long-life LED backlight.
...etc.
7070blok.wmf
NFS2-3030 Shown in CAB-C4 with display DVC audio in CA-1 in second tier PRN Series Printer
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD-80 in terminal mode, but not both at the same time.
self-restoring, and can be used to activate special control functions. Self-Optimizing Pre-Alarm. Each detector may be set for Self-Optimizing pre-alarm. In this special mode, the detector learns its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks. Cooperating Multi-Detector Sensing. A patented feature of ONYX Intelligent Sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one.
RELEASING FEATURES:
Ten independent hazards. Sophisticated cross-zone (three options). Delay timer and Discharge timers (adjustable). Abort (four options).
Ordering Information
Configuration Guidelines on page 3 Networking Options on page 4 Power Supplies on page 4 Audio Options on page 4 Compatible Devices, EIA-232 Ports on page 5 Compatible Devices, EIA-485 Ports on page 5 Compatible Intelligent Devices on page 5 Enclosures, Chassis & Dress Plates on page 6 Other Options on page 6
CONFIGURATION GUIDELINES
Stand-alone and network systems require a main display. On single-CPU systems (one NFS2-3030), the display option is the CPU2-3030D. On network systems (two or more networked fire panel nodes), at least one NCA-2, NCS, or ONYXWorks annunciation device is required. Options listed as follows. CPU2-3030D: NFS2-3030 Primary Display. CPU2-3030D ships with keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control keypad. CPU2-3030 is a central processing unit and requires an AMPS-24(E) power supply.
CPU2-3030ND: CPU2-3030 without display. VeriFire-TCD: VeriFire Tools CD-ROM. Contains programming software for ONYX series products, DVC, and XPIQ. Includes local panel connection cable. Programming PC requires a serial port connection. See DN-6871. LCM-320: Loop Control Module. Adds SLCs to 3030; 3030 supports up to 5 LCM-320s and 5 LEM-320s. See DN-6881. LEM-320: Loop Expander Module. Expands each LCM used on the 3030. See DN-6881. SAMPLE SYSTEM: Four-loop NFS2-3030 with display: CPU2-3030D, DP-DISP, two BMP-1s, CHS-M3, two LCM320s, two LEM-320s, AMPS-24, SBB-A4, DR-A4, BP2-4, BB100, batteries.
NFN Gateway (NFN-GW-PC-HNSF) and 19" color flat-screen LCD monitor. Each ONYXWorks consumes one of up to 200 network addresses. See DN-7048. ONYXWORKS-HNMF: UL-listed graphics PC workstation for multi-mode-fiber high-speed NOTIFIRENET. Includes HSNFN Gateway (NFN-GW-PC-HNMF) and 19" color flat-screen LCD monitor. Each ONYXWorks consumes one of up to 200 network addresses. See DN-7048.
POWER SUPPLIES
AMPS-24(E): One required for each NFS2-3030. Addressable power supply and battery charger with two 24 VDC outputs. Addressable by any FlashScan or CLIP mode FACP. Charges 7 to 200 AH batteries. Occupies up to four addresses on an SLC, depending on configuration. Primary input power for panel. See DN-6883. BAT Series Battery: AMPS-24 utilizes two 12 volt, 12 to 200 AH batteries. See DN-6933. BB-100: Backbox for batteries and power supplies. The BB100 is used to mount up to two 100-AH batteries and power supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x 7.5" (19.05 cm) deep; depth includes door. BB-200: Backbox for batteries and power supplies. Holds the AMPS-24(E) power supply when AMPS-24(E) is used as a charger for 200 AH batteries. Holds up to four 100 AH batteries and power supply. 30" (76.20 cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm) deep; depth includes door. NFS-LBB: Battery Box. The NFS-LBB is used to mount up to two 55-AH batteries. Dimensions: Box: 24" (610 mm) wide x 14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613 mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx. 1.6 mm) to depth. APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and transfer relay, and overcurrent protection. Mounts on two of four positions on a CHS-4L or CHS-4 chassis. See DN-5952. ACPS-610: 6.0 amp or 10 amp addressable charging power supply. See DN-60244. FCPS-24S6/-24S8: Remote six-amp and eight-amp power supplies with battery charger. See DN-6927.
NETWORKING OPTIONS
NCA-2: Network Control Annunciator, 640 characters. An alternate primary display for CPU2-3030 can be provided by the NCA-2, NCS, or ONYXWorks. Using NCA-2 as primary display enables non-English languages. On network systems (two or more networked fire panel nodes), one network display (either NCA-2, NCS, or ONYXWorks) is required for every system. On network systems, the NCA-2 connects (and requires) a standard Network Control Module or High-Speed Network Control Module. Mounts in a row of FACP node or in two annunciator positions. Mounting options include the DP-DISP, ADP-4B, or in an annunciator box, such as the ABS-2D. In CAB-4 top-row applications, a DP-DISP and two BMP-1 blank modules are required for mounting. See DN-6858. NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN6861. HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed network communications modules. Wire, single-mode fiber, multimode fiber, and media conversion models are available. See DN-60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT-WF). See DN-6971. NCS5-W-ONYX: Standard Network Control Station, Wire. ULListed graphics PC with mouse, 19" color flat-screen LCD monitor. Order as necessary for network systems. Each NCS consumes one of 103 network addresses. See DN-6868 (previous NCS-W), ONYX DN-6869. NCS5-F-ONYX: Standard Network Control Station, Fiber. ULListed graphics PC with mouse, 19" color flat-screen LCD monitor. Order as necessary for network systems. Each NCS consumes one of 103 network addresses. See DN-6868 (previous NCS-W), ONYX DN-6869. ONYXWorks-NW: UL-listed graphics PC workstation for standard NOTIFIRENET with wire media. Includes NFN Gateway wire version (NFN-GW-PC-W) and 19" color flat-screen LCD monitor. Each ONYXWorks workstation consumes one of 103 network addresses. See DN-7048. ONYXWORKS-HNW: UL-listed graphics PC workstation for wire high-speed NOTIFIRENET. Includes HS-NFN Gateway (NFN-GW-PC-HNW) and 19" color flat-screen LCD monitor. Each ONYXWorks consumes one of up to 200 network addresses. See DN-7048. ONYXWorks-NF: UL-listed graphics PC workstation for standard NOTIFIRENET with fiber media. Includes NFN Gateway wire version (NFN-GW-PC-F) and 19" color flat-screen LCD monitor. Each ONYXWorks workstation consumes one of 103 network addresses. See DN-7048. ONYXWORKS-HNSF: UL-listed graphics PC workstation for single-mode-fiber high-speed NOTIFIRENET. Includes HS-
AUDIO OPTIONS
DAA2-5025: 50W, 25 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556. DAA-5025: 50W, 25 Vrms Digital Audio Amplifier assembly with DAA-PS power supply board, shipped mounted to its chassis. See DN-7046. DAA2-5070: 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556. DAA-5070: 50W, 70.7 Vrms Digital Audio Amplifier assembly with DAA-PS power supply board, shipped mounted to its chassis. See DN-7046. DAA2-7525: 75W, 25 Vrms digital audio amplifier assembly with power supply; includes chassis. See DN-60556. DAA-7525: 75W, 25 Vrms digital audio amplifier assembly with DAA-PS power supply board, shipped mounted to its chassis. See DN-60257. DAX-3525: 35W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561. DAX-3570: 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5025: 50W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561. DAX-5070: 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561. DP-1B: Blank dress panel. Provides dead-front panel for unused tiers; covers DAA-series or AA-series amplifier. See DN-7046. CHS-BH1: Battery chassis; holds two 12.0 AH batteries. Mounts on the left side of DAA chassis. See DN-7046. DVC-EM: Digital Voice Command, digital audio processor with message storage for up to 32 minutes of standard quality (4 minutes at high quality) digital audio. See DN-7045. DVC-KD: Keypad for local annunciation and controls; status LEDs and 24 user-programmable buttons. See DN-7045. CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure. The left side accommodates one DVC and a DVC-KD (optional); and the right side houses a CMIC-1 microphone and its well (optional). See DN-7045. CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series enclosure. The left side accommodates one DVC mounted on a half-chassis and one NFS2-3030 or NCA-2 mounted on a half-chassis. The right side houses a microphone/handset well. The CA-2 assembly includes CMIC-1 microphone. ADDR Series doors with two-tier visibility are available for use with the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4 (below). TELH-1: Firefighters Telephone Handset for use with the DVC when mounted in the CA-2 chassis. See DN-7045. ADDR-B4: Two-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB4 Series DR doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-B4 backbox with the ADDR-B4. See DN-7045, DN-6857. ADDR-C4: Three-tier-sized door designed for use with the CA2 chassis configuration. ADDR Series doors are similar to CAB-4 Series DR doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-C4 backbox with the ADDR-C4. See DN-7045, DN-6857. ADDR-D4: Four-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB4 Series DR doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-D4 backbox with the ADDR-D4. See DN-7045, DN-6857. EQ Series Cabinets: EQ series cabinets will house amplifiers, power supplies, battery chargers and control modules. EQ cabinets are available in three sizes, B through D. See DN60229. DPA-1: Dress panel, used with the CA-1 chassis when configured with a DVC, DVC-KD, and CMIC-1. See DN-7045. DPA-2: Dress Panel used with the CA-2 chassis assembly. DPA-1A4: Dress panel, used with the CA-1 chassis when the CMIC-1 is not used. Provides mounting options on right two bays for two ACS annunciators, or for blank plates. See DN7045. CMIC-1: Microphone used with DVC/DVC-EM. Included with CA-2 chassis assembly. See DN-7045. FTM-1: Firephone Control Module connects a remote firefighter telephone to a centralized telephone console. Reports status to panel. Wiring to jacks and handsets is supervised. See DN-6989. RM-1/RM-1SA: Remote microphone assemblies, mount on ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) stand-alone cabinets. See DN-6728.
AA-30: Audio Amplifier, 30 watts. Switch-mode power. Includes amplifier and audio input supervision, backup input, and automatic switchover, power supply, cables. See DN3224. AA-120/AA-100: Audio Amplifier provides up to 120 watts of 25 Vrms audio power. The amplifier contains an integral chassis for mounting to a CAB-B4, -C4, or -D4 backbox (consumes one row). Switch-mode power. Includes audio input and amplified output supervision, backup input, and automatic switchover to backup tone. Order the AA-100 for 70.7 Vrms systems and 100 watts of power. See DN-3224.
BEAMMRK: Multi-mount kit, FSB-200(S) below. See DN-6985. BEAMSMK: Surface-mount kit, FSB-200(S) below. See DN6985. FSB-200: Intelligent beam smoke detector. See DN-6985. FSB-200S: Intelligent beam smoke detector with integral sensitivity test. See DN-6985. FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria Detector. See DN-60412. FSI-851: Low-profile FlashScan ionization detector. See DN6985. FSP-851: Low-profile FlashScan photoelectric detector. See DN-6935. FSP-851T: Low-profile FlashScan photoelectric detector with 135F (57C) thermal. See DN-6935. FST-851: FlashScan thermal detector 135F (57C). See DN-6936. FST-851R: FlashScan thermal detector 135F (57C) with rate-of-rise. See DN-6936. FST-851H: FlashScan 190F (88C) high-temperature thermal detector. See DN-6936. DNR: InnovairFlex low-flow non-relay duct-detector housing (order FSP-851 separately). Replaces FSD-751PL/FSD751RPL. See DN-60429. DNRW: Same as above with NEMA-4 rating, watertight. See DN-60429. FSP-851R: Low-profile intelligent photoelectric sensor, remote test capable. For use with DNR(W). FSP-851RA: Same as FSP-851R but with ULC listing. FAPT-851: FlashScan Acclimate Plus low-profile multisensor detector. See DN-6937. FSL-751: FlashScan VIEW laser photo detector. See DN6886. B224RB: Low-profile relay base. See DN-60054. B224BI: Isolator base for low-profile detectors. See DN-60054. B710LP: Low-profile base. Standard U.S. style. 60054.
See DN-
XP6-R: FlashScan six-relay (Form-C) control module. See DN-6926. XP10-M: FlashScan ten-input monitor module. See DN6923.
OTHER OPTIONS
411: Slave digital alarm communicator. See DN-6619. 411UDAC: Digital alarm communicator. See DN-6746.
IPDACT-2IPDACT Internet Monitoring Module: Mounts in IPENC enclosure. Connects to primary and secondary DACT telephone output ports for internet communications over customer-provided ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IP. See DN-60408.
FMM-1: FlashScan monitor module. See DN-6720. FDM-1: FlashScan dual monitor module. See DN-6720. FZM-1: FlashScan two-wire detector monitor module. See DN-6720. FMM-101: FlashScan miniature monitor module. See DN6720. FMM-4-20: FlashScan 4-20 mA protocol monitor module. See DN-60411. FCM-1-REL: FlashScan releasing control module. See DN60390. FCM-1: FlashScan NAC control module. See DN-6724. FRM-1: FlashScan relay module. See DN-6724.
NBG-12LX: Manual pull station, addressable. See DN-6726.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For mounting an IPDACT-2/2UD onto the panel chassis or CHS-4 series chassis. Use IPENC for external mounting applications. IPSPLT: Y-adaptor option allow connection of both panel dialer outputs to one IPDACT-2/2UD cable input. IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket; Red. For Black order IPENC-B. BB-UZC: Backbox for housing the UZC-256 for applications where the UZC will not fit in panel enclosure; Black. For Red, order BB-UZC-R. See DN-3404.
ISO-X: Isolator module. See DN-2243. XP6-C: FlashScan six-circuit supervised control module. See DN-6924. XP6-MA: FlashScan six-zone interface module; connects intelligent alarm system to two-wire conventional detection zone. See DN-6925.
Page 6 of 8 DN-7070:F 7/16/2010
SYSTEM SPECIFICATIONS
System Capacity
Intelligent Signaling Line Circuits ...........1 expandable to 10 Intelligent detectors .......................................... 159 per loop Addressable monitor/control modules .............. 159 per loop Programmable software zones ............................. over 2000 ACS annunciators per CPU2-3030 .......................32 address x 64 or 96 points
NOTE: The CPU2-3030 can support up to 96 annunciator address points per ACM-24/-48.
may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S635 ULC Listed: S635 MEA: 232-06-E FDNY: COA # 6058 CSFM: 7165-0028:0224 (Commercial) FM Approved FM6320 Approved. Class 6320 for Gas Detection City of Chicago City of Denver PSB Corporation Fire Services Department (Hong Kong)
Specifications
Primary input power: AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 Amps maximum. AMPS-24E: 240 VAC, 50/60 Hz, 2.25 Amps maximum. DC output: Main 24 VDC: Up to 5.0 A Aux 24 VDC: Up to 5.0 A 5 VDC: Up to 0.15 A.
NOTE: For details of DC output values, see manual 51907.
Standards
The NFS2-3030 complies with the following UL Standards and NFPA 72 Fire Alarm Systems requirements: UL 864 (Fire). UL 1076 (Burglary). LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). AUXILIARY (Automatic, Manual and Waterflow) (requires TM-4). REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires TM-4). PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler Supervisory). Not applicable for FM. EMERGENCY VOICE/ALARM. OT, PSDN (Other Technologies, Packet-switched Data Network)
Battery charger range: 7 AH 200 AH. Use separate cabinet for batteries over 26 AH. Float Rate: 27.6 V.
IntelliQuad and NOTIFIRENET are all trademarks; and Acclimate Plus, FlashScan, NION, NOTIFIER, ONYX, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. 2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com
Page 8 of 8 DN-7070:F 7/16/2010