Capacitance Type Level
Capacitance Type Level
LMC
®
Capacitance Type Level
Switch for Liquids & Solids sensing matters
Product Overview
Trumen capacitance type point level switch model LMC is suitable for
conductive and nonconductive liquid, solid and powder & use in all
process industries like food, beverages, chemical, pharma, oil & gas,
water treatment plant, cement, and many more. Trumen LMC is fully,
partially PTFE & ceramic insulated and available in rigid rod probe &
flexible rope probe for point level detection of bulk solids and liquids.
LMC is available for various service temperatures from regular 80 °C to
600 °C.
Operating Principle
Capacitance type limit switch
is a static level sensor, Its
sensing parts are:-
Performance Specifications
Features
Parameter Description
General
Min. Dielectric Constant 1.6 (non-hygroscopic)
Reproducability 0.1 %
Accuracy 0.3 %
Influence of medium Max +2 to -3 mm (-20 to +150 °C)
temperature
Sensor Cable Remote electronics require special interconnection cable from probe to controller 5 meter standard length
Process
Ambient Temperature -20°C ... 70°C (-4°F ... 158 °F)
Process Temperature -20°C ... 100°C (-4°F ... 212 °F)
Extended Process Temperature PTFE Insulation: -30°C ... 250°C (-22 °F ... 482 °F), *Ceramic Insulation: -30°C ... 600°C (-22°F ... 1,112°F),
(extensions & heat sinks required)
(*Note- Ceramic part insulation probe suitable for non-conductive or low dielectric material only)
Process Pressure Absolute / max. 20 bar
Physical Specifications
Wetted Parts SS 316, SS 316L, PTFE, Part ceramic
Process Connections NPT / BSP 1", 1-1⁄4", 1-1⁄2", 2" & Triclover 1-1/2", 2" and Flanged ANSI / JIS / DIN / ASA / custom
Probe Insertion Length Rigid Rod Probe: 50mm to 3,000mm, Flexible Rope Probe: 100mm to 20,000mm
Typical Installation
2/3 Core ordinary cable
for interconnection
between probe and
remote controller
Performance Specifications
Features Specifications
Parameter Description Electrical Connection
Electrical
EIUDD / ERUDD Integral / Remote Electronics LMC-UD
turn-on 2pF
turn-on
LMC-UD
2pF
to set 500pF to set 500pF
Supply Universal Power Supply 15 to 80 VDC & 15 to 260 VAC 50/60Hz process bar
8pF
1800pF process bar
8pF
1800pF
calibrate
calibrate
5-sec 5-sec
min failsafe min failsafe
1 2 3 4 5 6 wet delay / high cal wet delay / high cal
U 15... 80V DC dry delay / low cal U 15... 80V DC dry delay / low cal
15... 260V AC 15... 260V AC
alarm alarm
L1 N L1 N
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
Live
Relay Rating 5 A each @ 24VDC or 220VAC Neutral
output
relay 1
output
relay 2
DC output
relay 1
output
relay 2
15 to 260 VAC 15 to 80 VDC
50/60 Hz
LMC-U2S LMC-U2S
EIUSI / ERUSI Integral / Remote Electronics turn-on
to set
!
turn-on
to set
!
fs min
fs min
fs min
fs min
delay
delay
delay
delay
calib
calib
calib
calib
ch1 ch2 ch1 ch2
15... 80 VDC ch1 ch2 15... 80 VDC ch1 ch2
Output 2 SPDT relay contact output for 2 single point independent sensing U 15... 260 VAC
L1 N
ch1-relay ch2-relay power
U 15... 260 VAC
L1 N
ch1-relay ch2-relay power
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
LMC-U2CP LMC-U2CP
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
Live output output output output
DC
Relay Rating 6 A each @ 24VDC or 230VAC Neutral relay 1 relay 2 relay 1 relay 2
15 to 260 VAC 15 to 80 VDC
50/60 Hz
LMC-DP
2pF
EIDPD / ERDPD Integral / Remote Electronics process bar
turn-on
to set 500pF
8pF
1800pF
calibrate
5-sec
Supply 12 to 60 VDC 1 2 3 4 5 6
min failsafe
wet delay / high cal
dry delay / low cal
U 12 to 60V DC PNP (alarm=float) alarm
12 to 60 VDC
LMC-UD-1S-1P LMC-UD-1S-1P
LMC-NL
turn-on 2pF
LMC-DL
turn-on 2pF
to set
Auto calib
1 2 3 4 5 6
min failsafe
8 / 16 mA mA
Not used
Supply
Output Limit 8mA (-1mA max) / 16mA (+1mA max) 15 to 60 VDC
Meter/Indicator/PLC/SCADA
EIFDS/ERFDS Integral /Remote Electronics Specially designed with special output Electrical connection depends on selected model code
../qrd/lmc-qrd-p3-190721.svg
LMC: Capacitance Level Switch for Liquids & Solids sensing matters
®
Ordering Information
Features