100% found this document useful (1 vote)
107 views

Capacitance Type Level

We are an ISO 9001:2015 certified manufacturer & exporter of level sensing, measurement, indication and control instruments. Trumen came into existence in 2009 and initially started with manufacturing of Tuning Fork Level Switches for liquid and solid applications. With time, the manufacturing range increased with addition of Capacitance Level Transmitter & Capacitance Level Switches, RF Admittance Level Switches, Rotating Paddle Level Switches, Conductivity Type Level Switches.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
100% found this document useful (1 vote)
107 views

Capacitance Type Level

We are an ISO 9001:2015 certified manufacturer & exporter of level sensing, measurement, indication and control instruments. Trumen came into existence in 2009 and initially started with manufacturing of Tuning Fork Level Switches for liquid and solid applications. With time, the manufacturing range increased with addition of Capacitance Level Transmitter & Capacitance Level Switches, RF Admittance Level Switches, Rotating Paddle Level Switches, Conductivity Type Level Switches.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
You are on page 1/ 4

Technical Specification

LMC
®
Capacitance Type Level
Switch for Liquids & Solids sensing matters

Product Overview
Trumen capacitance type point level switch model LMC is suitable for
conductive and nonconductive liquid, solid and powder & use in all
process industries like food, beverages, chemical, pharma, oil & gas,
water treatment plant, cement, and many more. Trumen LMC is fully,
partially PTFE & ceramic insulated and available in rigid rod probe &
flexible rope probe for point level detection of bulk solids and liquids.
LMC is available for various service temperatures from regular 80 °C to
600 °C.

Operating Principle
Capacitance type limit switch
is a static level sensor, Its
sensing parts are:-

Earth Extension (body)


Sensing Rod (or Rope as per application)

The capacitance is formed by


the sense rod and earth extension.
C(air)
When material is absent,
the capacitance is analogically
a multiple of probe dimension
and dielectric constant of air
{ε(air) ≈ 1}.

C(material) When material is present, the


capacitance gets multiplied by
dielectric constant of the material.

This variation in capacitance, which


is due to the dielectric property of
C(material) > C(air)
material, is then translated into
Applications switching output by the device.
Capacitance level switch probe is used in different With two point independent type switches,
applications like two different values are mapped to two
- Water - Chemical different outputs and thus only one level
- Paints - Cement switch can provide two different level
- Animal feed - Food & Beverages outputs.
- Rice plants - Diesel
- Soya plants - Pharma liquids
- Dye powder - Resins
- Edible oil - Gypsum
- Milk powder - Corrosive liquid
Features
Compact size
Fast switching response
Static Charge Safe Low power consumption
Durable construction
Easy calibration via DIP switch
Single sensor allows pump-control & multi-point switching
Electronics is designed to endure High temperature endurable probes
heavy static charges without using External indication LED available
any external discharging devices Ingress protection : IP 67/68 (as per IS/IEC 60529:2001)
Electronic inserts support all requirements
High Temperature Probes Process temperature max 600°C
Process pressure max. 20 bar
Rigid rod / flexible rope probe version
../qrd/lmc-qrd-p1-190721.svg

600° Threaded / flanged / customized process connections


Remote electronics with as standard 10 meters cable length

ceramic insulated probe


for 600°C applications
LMC: Capacitance Level Switch for Liquids & Solids sensing matters
®

Performance Specifications
Features
Parameter Description
General
Min. Dielectric Constant 1.6 (non-hygroscopic)
Reproducability 0.1 %
Accuracy 0.3 %
Influence of medium Max +2 to -3 mm (-20 to +150 °C)
temperature
Sensor Cable Remote electronics require special interconnection cable from probe to controller 5 meter standard length

Process
Ambient Temperature -20°C ... 70°C (-4°F ... 158 °F)
Process Temperature -20°C ... 100°C (-4°F ... 212 °F)
Extended Process Temperature PTFE Insulation: -30°C ... 250°C (-22 °F ... 482 °F), *Ceramic Insulation: -30°C ... 600°C (-22°F ... 1,112°F),
(extensions & heat sinks required)
(*Note- Ceramic part insulation probe suitable for non-conductive or low dielectric material only)
Process Pressure Absolute / max. 20 bar

Physical Specifications
Wetted Parts SS 316, SS 316L, PTFE, Part ceramic
Process Connections NPT / BSP 1", 1-1⁄4", 1-1⁄2", 2" & Triclover 1-1/2", 2" and Flanged ANSI / JIS / DIN / ASA / custom
Probe Insertion Length Rigid Rod Probe: 50mm to 3,000mm, Flexible Rope Probe: 100mm to 20,000mm

Approvals & Certifications


ISO Certification ISO 9001:2015
CE certification All product comply as per directives 2014/35/EU Low Voltage Directive & 2014/30/EU
Electromagnetic Compatibility Directive
RoHS Certification RoHS Compliance as per RoHS Directive (2011/65/EU); Certificate No. RoHS-TTPL-2021-0305
Ingress Protection IP67/68 as per IS/IEC 60529:2001
Ex-proof (Ex d T6 IIC) Flameproof as per IS/IEC 60079-1:2014, Ingress Protection (IP-67) as per IS/IEC 60529:2001
Suitable for Gas Group: IIC, Suitable for Zone 1 & 2 atmospheres and Dust hazardous area Zone 21 & 22
Ex-ia Approval Intrinsically safe according to the requirement of IS/IEC 60079-0:2011, IS/IEC 60079-11:2006 & IS/IEC 60529: 2001
EMC Certification EMC Certified as per Standard IEC 61000-4-3, IEC 61000-4-2, IEC 61000-4-6, IEC 61000-4-29, IEC 61000-4-4,
IEC 61000-4-5, CISPR 11
Vibration Test Certificate Vibration complied as per IEC 60068 part 2-6 sinusoidal, 10-55Hz, 0.15mm

Specifications are subject to change without prior notice

Typical Installation
2/3 Core ordinary cable
for interconnection
between probe and
remote controller

Trumen Technologies Pvt.Ltd. ../qrd/lmc-qrd-p2-190721.svg


LMC: Capacitance Level Switch for Liquids & Solids sensing matters
®

Performance Specifications
Features Specifications
Parameter Description Electrical Connection
Electrical
EIUDD / ERUDD Integral / Remote Electronics LMC-UD

turn-on 2pF
turn-on
LMC-UD
2pF
to set 500pF to set 500pF

Supply Universal Power Supply 15 to 80 VDC & 15 to 260 VAC 50/60Hz process bar
8pF
1800pF process bar
8pF
1800pF

calibrate

calibrate
5-sec 5-sec
min failsafe min failsafe
1 2 3 4 5 6 wet delay / high cal wet delay / high cal

Output 1 DPDT potential free relay contact output


1 2 3 4 5 6

U 15... 80V DC dry delay / low cal U 15... 80V DC dry delay / low cal
15... 260V AC 15... 260V AC
alarm alarm
L1 N L1 N

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

Live
Relay Rating 5 A each @ 24VDC or 220VAC Neutral
output
relay 1
output
relay 2
DC output
relay 1
output
relay 2
15 to 260 VAC 15 to 80 VDC
50/60 Hz

LMC-U2S LMC-U2S
EIUSI / ERUSI Integral / Remote Electronics turn-on
to set
!
turn-on
to set
!

Supply Universal Power Supply 15 to 80 VDC & 15 to 260 VAC 50/60Hz

fs min

fs min
fs min

fs min

delay

delay
delay

delay

calib

calib
calib

calib
ch1 ch2 ch1 ch2
15... 80 VDC ch1 ch2 15... 80 VDC ch1 ch2

Output 2 SPDT relay contact output for 2 single point independent sensing U 15... 260 VAC
L1 N
ch1-relay ch2-relay power
U 15... 260 VAC
L1 N
ch1-relay ch2-relay power

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

Live output output output output


DC
Relay Rating 6 A each @ 24VDC or 230VAC Neutral relay 1 relay 2 relay 1 relay 2
15 to 260 VAC 15 to 80 VDC
50/60 Hz

LMC-U2CP LMC-U2CP

EIUSP/ERUSP Integral / Remote Electronics turn-on


to set
2pF
500pF
turn-on
to set
2pF
500pF
8pF 8pF

Supply Universal Power Supply 15 to 80 VDC & 15 to 260 VAC 50/60Hz


alarm alarm
1800pF 1800pF
cal-hi-rly1 cal-hi-rly1
rly1 rly2 rly1 rly2
cal-lo-rly1 cal-lo-rly1
15... 80 VDC cal-hi-rly2 15... 80 VDC cal-hi-rly2
U 15... 260 VAC cal-lo-rly2 U 15... 260 VAC cal-lo-rly2

Output 2 SPDT relay output for 2 individual pump control switching L1 N


rly-1 rly-2 power
L1 N
rly-1 rly-2 power

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
Live output output output output
DC
Relay Rating 6 A each @ 24VDC or 230VAC Neutral relay 1 relay 2 relay 1 relay 2
15 to 260 VAC 15 to 80 VDC
50/60 Hz

LMC-DP
2pF
EIDPD / ERDPD Integral / Remote Electronics process bar
turn-on
to set 500pF
8pF
1800pF

calibrate
5-sec

Supply 12 to 60 VDC 1 2 3 4 5 6
min failsafe
wet delay / high cal
dry delay / low cal
U 12 to 60V DC PNP (alarm=float) alarm

Output PNP output 1 single / 1 pump control field settable


1 2 3 4 5 6 7 8 9
Output Limit 250mA max. Short Circuit Safe output unused terminals
DC

12 to 60 VDC

LMC-UD-1S-1P LMC-UD-1S-1P

turn-on 2pF 2pF


turn-on

EIUSH / ERUSH Integral / Remote Electronics alarm


to set 500pF
8pF
1800pF alarm
to set 500pF
8pF
1800pF
calib-rly1 calib-rly1
rly1 rly2 rly1 rly2
5sec dly rly1

Supply Universal Power Supply 15 to 80 VDC & 15 to 260 VAC 50/60Hz U


15... 80 VDC
15... 260 VAC
cal-hi-rly2
cal-lo-rly2
rly1-FSL rly2-FSH power
U
15... 80 VDC
15... 260 VAC
5sec dly rly1
cal-hi-rly2
cal-lo-rly2
rly1-FSL rly2-FSH power
L1 N L1 N
Output 2 SPDT relay output for 1 single point and 1 pump control 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
Live output output DC output output
Neutral relay 1 relay 2 relay 1 relay 2
Relay Rating 6 A each @ 24VDC or 230VAC 15 to 260 VAC 15 to 80 VDC
50/60 Hz

LMC-NL

turn-on 2pF

EINL NAMUR (L-H / H-L) as per IEC-60947-5-6 alarm


to set 500pF
8pF
1800pF
calibrate 5 sec

Supply 8.2 VDC Barrier or


NAMUR Output
(⩽1.2mA & ⩾2.1mA)
8.2V DC
dry delay
wet delay
low alarm

⩽1.2mA & ⩾2.1mA NAMUR output, 1KΩ series resistance


U
Amplifier X X X X X X
Output Supply
NAMUR 1 2 3 4 5 6 7 8 9
24V DC 8.2V
DC unused terminals
Barrier or
Amplifier

LMC-DL
turn-on 2pF
to set

EIDLD Integral Electronics process bar


5-sec
8pF
calibrate

Auto calib
1 2 3 4 5 6
min failsafe

Supply 15 to 60 VDC Loop Powered 8mA ±1mA (Alarm)


U
15... 60 VDC
16mA ±1mA (Normal)
wet dly / high cal
dry dly / low cal
alarm
!

Output 4-20mA loop powered single / pump settable two wire DC 1 2 3 4 5 6 7 8 9

8 / 16 mA mA
Not used

Supply
Output Limit 8mA (-1mA max) / 16mA (+1mA max) 15 to 60 VDC

Meter/Indicator/PLC/SCADA

ER2SR/ER3SR Remote Electronics Electrical connection depends on selected model code


Supply 80-270VAC, 50/60Hz
Output Dual / Three SPDT relay output, normal shielded cable

Relay Rating 5 A each @ 24VDC or 220VAC

EIFDS/ERFDS Integral /Remote Electronics Specially designed with special output Electrical connection depends on selected model code
../qrd/lmc-qrd-p3-190721.svg
LMC: Capacitance Level Switch for Liquids & Solids sensing matters
®

Ordering Information
Features

LMC Hxx Tx Rx Sx Ix Gx Wx Px Cx Exxx Lxxxx


Insertion Length
Rigid Rod Probe:
Enclosure
50mm to 3,000mm
HAN: Aluminum Non-Hazardous IP-67/68
Flexible Rope Probe:
HAX: Aluminum Flameproof IIa, IIb and IIc
100mm to 20,000mm
HSN: Stainless steel
HPN: Polycarbonate (Plastic) Electronics (Refer page 3 for detail description)
HES: Specially designed as per customer EIUDD: 1 DPDT relay O/P
requirement EIUSI: 2 SPDT relay O/P for 2 single point
EIUSP: 2 SPDT relay O/P for for 2 individual
pump control switching
Material Temperature EIUSH: 2 SPDT relay O/P for 1 single point
T1: max 80°C and 1 pump control
T2: max 200°C EIDPD: PNP O/P for 1 single / 1 pump control
T3: max 250°C EINL: ⩽1.2mA NAMUR (L-H) &
T4: max 600°C ⩾2.1mA NAMUR (H-L) O/P
TS: Customer Specified Special designed EIDLD: 4-20mA loop powered O/P
EIFDS: Special O/P
ERUDD: Remote Electronics with 1 DPDT
relay O/P
Sensor rigid / flexible type ERUSI: Remote Electronics with 2 SPDT relay O/P
RD1: Single Rigid Rod Probe ERUSP: Remote Electronics with 2 SPDT
RD2: 2 in 1 Rod Probe relay O/P
RL1: Single Flexible Rope Probe for Liquids (5mm) ERUSH: Remote Electronics with 2 SPDT
RL2: 2 in 1 Rope Probe relay O/P
RPS: Flexible Rope Probe for Solids (6mm) ERDPD: Remote Electronics with PNP O/P
RPT: Flexible Rope Probe for Solids (12mm) ERFDS: Remote Electronics with special O/P
RS: Specially designed probe ER2SR: Remote Electronics with Dual SPDT O/P
ER3SR: Remote Electronics with Three SPDT O/P

Sensing Rod/Rope Material Process Connection Material


S4: SS 304 C4: SS 304
S6: SS 316 C6: SS 316
SL: SS 316L CL: SS 316L
SS: Special Surface CS: Special Material

Process Connection Type


PB1: 1" BSP
Insulation type PB2: 1-1/2" BSP
I0: None PB3: 3/4"BSP
IP: Partly PTFE insulated PB4: 1-1/4" BSP
IT: Full PTFE insulated PB5: 2" BSP
IC: Partly ceramic insulated PB6: 1/2"BSP
PN1: 1" NPT
PN2: 1-1/2" NPT
PN3: 3/4" NPT
PN4: 1-1/4" NPT
Inactive Length or Sensor PN5: 2" NPT
Extension Material PN6: 1/2"NPT
G0: None PT1: 1-1⁄2" Triclover/Triclamp
G4: SS 304 PT2: 2" Triclover/Triclamp
G6: SS 316 PFL: Flanged Type (Fxxx)
GL: SS 316L F001: 1/2" B16.5 ANSI/ASA 150#RF
GS: Special material F002: 3/4" B16.5 ANSI/ASA 150#RF
F003: 1" B16.5 ANSI/ASA 150#RF
F004: 1-1/4" B16.5 ANSI/ASA 150#RF
F005: 1-1/2 " B16.5 ANSI/ASA 150#RF
Stilling Well Material F006: 2" B16.5 ANSI/ASA 150#RF
W0: None F007: 2-1/2" B16.5 ANSI/ASA 150#RF
W4: SS 304 F008: 3" B16.5 ANSI/ASA 150#RF
W6: SS 316 F009: 4" B16.5 ANSI/ASA 150#RF
WL: SS 316L F010: 5" B16.5 ANSI/ASA 150#RF
WS: Special material F011: 6" B16.5 ANSI/ASA 150#RF
PCS: Special Process Connection

Trumen Technologies Pvt. Ltd.


../qrd/lmc-qrd-p4-190721.svg

(an ISO 9001:2015 company)


® 39 Mangal Nagar, B/H Sai Ram Plaza, Nr. Rajiv Gandhi
Circle, AB Road, Indore, MP, 452 001, India
sensing matters
Phone: +91-731-497 2065, 8109062425
email: [email protected] web:www.trumen.in

You might also like