Ducts and Diffusers Design
Ducts and Diffusers Design
Ducts and Diffusers Design
What is Air Distribution in HVAC? Why Does One Need to Study it?
Air Distribution in HVAC: Distribution of Conditioned Air in Buildings and Rooms in Order to Hold Temperatures, Humidities and Air Velocities within Occupied Space at Acceptable Conditions
Distribution and Movement of Air within Conditioned Space Selection and Location of Optimum Air Outlets Delivering Proper Amount of Air:
To Provide Comfort within Occupied Zone To Provide Suitable Indoor Quality within Occupied Zone To Meet Required Total Pressure To Produce acceptable Noise Level within Occupied Zone
Reaction Complaints About Stagnant Air Complaints About Stagnant Air Probably Favorable but 50 FPM is Approaching Maximum Tolerable Velocity for Seated People Probably Favorable but 50 FPM is Approaching Maximum Tolerable Velocity for Seated People Upper Limit For People Moving About SlowlyFavorable Some Factory Air Conditioning Installations-Favorable None
Recommended Application
Retail and Department Store Factory Air Conditioning Higher Velocities for Spot Cooling
Diffuser
Ceiling diffuser very popular in commercial applications Linear or T-bar diffusers favored in VAV applications due to their better flow characteristics at reduced flow
Jet and Room Air Velocities and Temperature for Vo = 1000 ft/min and t = - 20 F
Sound in HVAC
Sound becomes noise when:
Too load Unexpected Uncontrolled Happens at wrong time Contains pure tones Contains unwanted information Unpleasant
Sound in HVAC
Audible frequency range for humans extends from 20 Hz to 20000 Hz Sound power and sound pressure Sound measured in decibel (dB):
10 Log10 ( W/10-12 ) dB relative to 1 pW 10 Log10 ( P/2X10-5 ) dB relative to 1 Pa
All air outlets generate noise Noise can be annoying to occupants Noise level can be related to velocity of air through outlet:
Lower air velocity produces low level of noise Higher air velocity makes air outlet noisy
Noise criterion (NC) curves widely used to describe noise level of air outlets
Level below NC of 30 considered quiet Level above NC of 50 considered noisy
NC Curves
Linear Diffuser
Zero-Bar Diffuser
Round Diffuser
Perforated Diffuser
Grille
Square Diffuser
Slot-Bar Diffuser
Diffuser Type
Characteristic Length L
Example
Room part of single-story office Building Building located in Riyadh Dimensions of room shown in sketch Ceiling height =10 ft Air quantity = 250 cfm Select Ceiling Diffuser
Example
Solution
Noise level from above table, for office, NC < 35 Flow rate, Q = 250 cfm Room almost square
From above table, Characteristic length, L = 14/2 = 7 ft Throw = L = 7 ft
One essential component of HVAC - FANS Fan used to move air through ducts and air outlets Two type of fans used in HVAC:
Centrifugal fan (Blower)
Forward-tip fan Backward-tip fan
Axial fan
Vane-axial fan Tube-axial fan
Axial Fans
Fans laws
Relationships between fan capacity, pressure, speed, and power: First three fan laws (most useful)
Capacity proportional to fan speed (rpm) Pressure proportional to square of fan speed Power proportional to cube of fan speed
Performance of fans
Manufacturers present their fan performance data in form of:
Graphs of pressure, efficiency, and power as functions of flow rate Example: Centrifugal fan operating at point 1, estimate capacity, pressure, and power at speed 1050 rpm, initial bhp = 2 hp
Q2/Q1= rpm2/rpm1 Q2=5000 (1050/900)=5830CFM P2/P1= (rpm2/rpm1)2 P2=1.5(1050/900)2 =2.04 IWG W2/W1= (rpm2/rpm1)3 W2=2 (1050/900)3 = 3.2 hp
Pressure-Capacity Table
Selection of Fans
System and fan characteristics combined on one plot Intersecting of system and fan characteristics is point of operation Range of Optimum matching of system and fan shown Slope of system and fan characteristics must be of opposite sign for stable operation
Fan Installation
Point B is specific operation point Test may show point A as actual operation point
System Effect
Duct Design
General considerations Low-velocity duct system
Pressure loss per 100 ft of duct range between 0.08 to 0.15 Pressure loss of 0.1 per 100 ft of duct is ok Pressure loss of 0.05 per 100 ft of duct used in most projects in KSA
Simple Duct Systems with Outdoor Air Intake and Relief Shown Pressure Gradient Diagrams
Simple Duct Systems with Outdoor Air Intake and Relief Cont.
Total Pressure Profile for Typical Unitary System Shown Pressure Gradient Diagram
Tables give coefficients Co for different fittings Equivalent-length method used for fitting losses in lowvelocity duct (table gives equivalent length)
Equal-friction method Balanced-capacity method Constant-velocity method Reduced-velocity method Static-regain method T-method (optimization procedure)
Will cover only equal-friction method in detail and briefly cover balanced-capacity method
Equal-friction method
Principle of equal-friction method to make pressure loss per foot of duct length same for entire system Produce good balanced design for symmetrical duct layout Most duct systems have variety of duct runs ranging from long to short Dampers may be used for short runs (may cause considerable noise) in order to balance system Equal-friction method reduces air velocity in direction of flow
20 ft 1
80 ft 300 CFM 2 25 ft 15 ft 5 3
60 ft
300 CFM
6 7 30 ft
4 60 ft
300 CFM
300 CFM
Using this velocity with flow rate, one can establish duct size of that section and pressure loss per 100 ft Using this pressure loss per 100 ft for all sections, one continue to find their diameters
Balanced-capacity method
Principle of Balanced-capacity method, one makes loss in total pressure equal for all duct runs from fan to outlets Each run may have different equivalent length Pressure loss per 100 ft may be different for each run This may result in high air velocity (noisy duct) Limit air velocity and use damper for balancing
20 ft 1
80 ft 300 CFM 2 15 ft 25 ft 5 3
60 ft
300 CFM
6 7 30 ft
4 60 ft
300 CFM
300 CFM
Longest run form fan to outlets must be determine Pressure drop (loss) per 100 ft will be same for sections of longest run (same as equal-friction method) Establish pressure loss for branch by equating its pressure loss to pressure loss of branch of longest run Find pressure loss per 100 ft by divide pressure loss over equivalent length of that section
From name of constant-velocity method, velocity selected and kept fixed for all duct runs
Used for exhaust (kitchen exhaust, grease, industrial ventilation)
Static-Regain method
Static-regain method reduces air velocity in direction of flow in such a way that increase (regain) in static pressure in transition just balances pressure loss in following section Used in high-velocity systems Method require iterations
Examples
Several example will be solved using mainly method of equal friction Each example will be solved using computer software Ductlator will be used for designing some sections Examples done using single line duct work
Example # 1
300 CFM 55 ft
2
400 CFM 45 ft
30 ft
a 1
25 ft
3
25 ft
5 6
85 ft
600 CFM
60 ft
500 CFM
Example # 2
80 ft 2 20 ft 1 25 ft 3
300 CFM
60 ft
6
15 ft 5
300 CFM
4
60 ft 300 CFM
30 ft
300 CFM
Example # 3
90 ELBOW
400 CFM
90 ELBOW
diff
SHARP INLET
P = 0.04 IWG 10 ft
300 CFM
10 ft
10 ft 10 ft 5 ft
20 ft
diff
P = 0.04 IWG
PLENUM
20 ft
diff
200 CFM
90 ELBOW
P = 0.04 IWG
Example # 4
20 ft 1
80 ft 300 CFM 2 25 ft 15 ft 5 3
60 ft
300 CFM
6 7 30 ft
4 60 ft
300 CFM
300 CFM
Example # 5
80 ft
2
20 ft 1 25 ft 3
300 CFM
60 ft
300 CFM
15 ft 5
4
60 ft
30 ft
300 CFM
300 CFM
Example # 6
Fan produce 0.7 IWG and 0.35 IWG lost pressure in coil, filter and
furnace, divide remaining pressure 65% for supply duct and 35% for return duct
Duct layout
Actual duct work of some projects shown using double line duct with sizes shown Different diffuser types shown Air conditioning equipment shown
Roof-Top Packaged Unit With Duct Work (25 tons, Side view)