National Standard Plumbing Code 2009
National Standard Plumbing Code 2009
National Standard Plumbing Code 2009
NATIONAL STANDARD
PLUMBING CODE
ILLUSTRATED
Published By
PLUMBING-HEATING-COOLING CONTRACTORS—
NATIONAL ASSOCIATION
All inquiries or questions relating to interpretation should be forwarded to
Code Secretary
180 S. Washington St., P.O. Box 6808
Falls Church, VA 22046-1148
1-800-813-7061
Scope:
The development of a recommended code of plumbing practice, design, and installation,
including the establishment of performance criteria predicated on the need for protection of
health and safety through proper design, installation, and maintenance of plumbing systems.
This scope excludes the development of specific standards related to the composition,
dimensions, and/or mechanical and physical properties of materials, fixtures, devices, and
equipment used or installed in plumbing systems.
Purpose:
To provide practices and performance criteria for the protection of health and safety through
proper design and installation of plumbing systems.
Exceptions:
In case of practical difficulty, unnecessary hardship or new developments, exceptions
to the literal requirements may be granted by the authority having jurisdiction to permit
the use of other devices or methods, but only when it is clearly evident that equivalent
protection is thereby secured.
Disclaimer:
PHCC is not responsible or liable for any personal injury, property, or other damages of any nature whatsoever directly or indirectly
resulting from the publication, use of, or reliance on the National Standard Plumbing Code or its Supplements. PHCC also makes no guar-
antee or warranty as to the accuracy or completeness of any information published herein.
i
ii
FOREWORD
Since its founding as the National Association of Master Plumbers in 1883, the National Association of Plumbing-
Heating-Cooling Contractors has maintained a serious interest in plumbing standards, codes and good plumbing
design practices.
The Association published the NAMP “Standard Plumbing Code” in 1933 and furnished revised editions until
1942. NAPHCC participated in the development of special standards for war-time plumbing and later was repre-
sented on the National Plumbing Code Coordinating Committee, whose work ultimately resulted in the adoption
of A40.8 as a standard or model plumbing code in 1955.
NAPHCC served as a sponsor in the early 1960’s of the project which attempted to update the 1955 document.
This project was operated through the procedures of the American National Standards Institute. However, the
A40.8 revision project was not completed because consensus could not be achieved.
In order to provide local and state governments, code administrative bodies and industry with a modern, updated
code, NAPHCC published the “National Standard Plumbing Code,” in 1971, following the format and sequence
of the A40.8 to provide for maximum convenience of users.
With the June 1973 revision, the American Society of Plumbing Engineers joined this effort by co-sponsoring
the National Standard Plumbing Code. ASPE maintained its co-sponsorship status until September, 1980. Upon
ASPE’s withdrawal of co-sponsorship, the Code Committee composition was changed to include not only mem-
bers of the contracting and engineering communities but also members of the inspection community. Contractors,
engineers and inspectors now comprise the National Standard Plumbing Code Committee.
The National Standard Plumbing Code Committee has worked closely with the plumbing industry to maintain a
document of minimum requirements for plumbing systems that reflect current practices, materials, and techniques,
consistent with public health and safety.
However, the written requirements of a Code can sometimes be interpreted differently by different individuals.
For this reason, the NSPC Committee developed the NSPC Illustrated, which includes explanatory comments and
illustrations to demonstrate the intent of the various Code Sections.
The Committee also realizes that despite the countless hours of preparation and review, perfection may not have
been achieved in this document. For this reason, please send any questions, comments, suggestions, or prob-
lems to the Code Secretary, Plumbing-Heating-Cooling Contractors - National Association, P.O. Box 6808, Falls
Church, VA 22046-1148.
The comments following the various Sections of the Code text are intended to explain the intent of that Section
of the Code. The comments themselves are not Code requirements but are intended to supplement the Code and
provide guidance toward its interpretation.
iii
Figures and Figure Notes
The illustrations (figures) are intended to graphically demonstrate the intent or provide an example of the refer-
enced definition or Code Section. The figures are based only on the referenced definition or Code Section and do
not necessarily include all details of the complete installation, such as pipe sizes, specific pipe fittings, required
pipe supports, required cleanouts, and other details that are not part of the definition or Code Section being illus-
trated. The figures must not be used to justify work that does not comply with all requirements of the Code.
The figures are not intended to restrict installations to the arrangement shown. In many cases, the figures show
only one example or a typical example of an acceptable arrangement. Any arrangement that meets the intent of
the referenced Code Section is acceptable.
This Edition
This edition of the National Standard Plumbing Code includes changes from the 2007 and 2008 Supplements and
the changes that were approved at the August 21, 2008 Public Hearing.
iv
INTRODUCTORY NOTES
The material presented in this Code does not have legal standing unless it is adopted by
reference, or by inclusion, in an act of state, county, or municipal government. Therefore,
administration of the provisions of this Code must be preceded by suitable legislation at the
level of government where it is desired to use this Code.
In some places in this Code, reference is made to “Authority Having Jurisdiction.” The
identity of an Authority Having Jurisdiction will be established by the act that gives legal
standing to the Code provisions.
Proposed changes to the Code can be submitted by any interested party on forms available from
NAPHCC. Cutoff dates for submitting proposed changes are published by NAPHCC, along with
the dates for public hearings and final voting by the NSPC Committee. The NSPC is reprinted
on a three-year cycle with at least one Code Change Supplement published between reprints of
the Code.
Personal appearance before the Committee for a hearing on any Code matter can be had
by interested parties after a request in writing.
In the course of revision, certain outdated sections have been deleted. In order to
maintain consistency and perpetuity of the numbering system, those deleted sections and
numbers have been removed from this printed text, or placed in reserve.
v
2009 National Standard Plumbing Code Committee
J. Richard Wagner, PE, Chairman Thomas C. Pitcherello Frank R. Maddalon
The Poole & Kent Corporation NJ Department of Community Affairs Executive Committee Liaison
4530 Hollins Ferry Rd Codes Assistance Unit F. R. Maddalon Plumbing & Heating
Baltimore, MD 21227-4670 101 S. Broad Street, PO Box 802 1550 Sylvan Ave
Phone: (410) 247-2200 Trenton, NJ 08625-0802 Hamilton, NJ 08610-4461
Fax: (410) 247-2331 Phone: (609) 984-7609 Phone: (609) 587-8317
[email protected] Fax: (609) 984-7717 Fax: (609) 587-9848
[email protected] [email protected]
Charlie Chalk
Maryland PHCC Luis A. Rodriguez, CPD, LEED AP Julie A. Turner
10176 Baltimore National Pike, #205 KSi Professional Engineers Staff Liaison
Ellicott City, MD 21042 149 Yellowbrook Road Plumbing-Heating-Cooling
Phone: (410) 461-5977 P.O. Box 628 Contractors–National Association
Fax: (410) 750-2507 Farmingdale, NJ 07727 180 S. Washington St.,
[email protected] Phone: (732) 938.2666 Ext.109 Falls Church, VA 22046
Fax: (732) 938.2521 (703) 237-8100 or (800) 533-7694
William Chamberlin Cell: (732) 996-5760 Fax: (703) 237-7442
Chamberlin Plbg. & Htg Company www.ksi-pe.com e-mail: [email protected]
P.O. Box 390 URL: http://www.phccweb.org
1274 Route 130 South Ronald W. Stiegler
Windsor, NJ 08561 Schaefer Mechanical Services, Inc.
Phone: (609) 448-1848 620 Old Westminster Pike
Fax: (609) 448-8683 Westminster, MD 21157
[email protected] Phone: (410) 876-6825
Fax: (410) 857-0011
Michael J. Kastner [email protected]
Kastner Plumbing & Heating
12630 Frederick Road Alex Tucciarone
West Friendship, MD 21794 Old Bridge Plumbing Inspector
Phone: (301) 725-5000 58 Lear Ct
Fax: (410) 442-7626 East Brunswick, NJ 08816-1853
[email protected] Phone: (732) 721-5600 2420
Fax: (732) 607-7912
Leon LaFreniere [email protected]
City of Manchester, Dept. of Buildings
One City Plaza Jerry Van Pelt, CIPE
Manchester, NH 03101 GVP Consulting, LLC
Phone: (603) 624-6475 9087 Central Avenue
Fax: (603) 624-6324 Sebastian, FL 32976
[email protected] Phone: (772) 664-6975
Fax: (772) 664-6976
Frank R. Maddalon [email protected]
F. R. Maddalon Plumbing & Heating
1550 Sylvan Ave Shawn Martin
Hamilton, NJ 08610-4461 Plumbing Manufacturers Institute
Phone: (609) 587-8317 18210 Pages End
Fax: (609) 587-9848 Davidson, NC 28036
[email protected] Phone: (847) 481-5500 x 108
[email protected]
Michael Maloney
Plumbers & Pipefitters Local Union #9 Robert Kordulak
2 Iron Ore Rd NSPC Secretariat
Manalapan, NJ 07726-8086 The Arkord Company
Phone: (732) 792-0999 206 1st Ave., # 603
Fax: (732) 792-1144 Belmar, NJ 07719-2006
[email protected] Phone: (732) 681-5400
Fax: (732) 681-5047
[email protected]
vi
Contents
National Standard Plumbing Code – Illustrated ......................................................................................... i
Foreword ................................................................................................................................................... iii
Introductory Notes .................................................................................................................................... v
Committee Members ................................................................................................................................. vi
Administration ............................................................................................................................................ 1
Basic Principles .......................................................................................................................................... 9
Chapter 1 Definitions ............................................................................................................ 13
Chapter 2 General Regulations .............................................................................................. 65
Chapter 3 Materials .............................................................................................................. 83
Chapter 4 Joints and Connections ........................................................................................115
Chapter 5 Traps, Cleanouts and Backwater Valves .............................................................139
Chapter 6 Interceptors ...................................................................................................... 155
Chapter 7 Plumbing Fixtures, Fixture Fittings and Plumbing Appliances .......................... 165
Chapter 8 Hangers and Supports ........................................................................................ 197
Chapter 9 Indirect Waste Piping and Special Wastes ......................................................... 201
Chapter 10 Water Supply and Distribution ........................................................................... 213
Chapter 11 Sanitary Drainage Systems ................................................................................. 255
Chapter 12 Vents and Venting ............................................................................................... 277
Chapter 13 Storm Water Drainage ........................................................................................ 317
Chapter 14 Special Requirements for Health Care Facilities ................................................ 331
Chapter 15 Tests and Maintenance ..................................................................................... 337
Chapter 16 Regulations Governing Individual Sewage Disposal Systems for Homes
& Other Establishments Where Public Sewage Systems Are Not Available ..... 341
Chapter 17 Potable Water Supply Systems ............................................................................357
Chapter 18 Mobile Home & Travel Trailer Park Plumbing Standards ............................... 365
Appendix A Sizing Storm Drainage Systems ........................................................................ 373
Appendix B Sizing the Building Water Supply System ........................................................ 381
Appendix C Conversions: Customary Units to Metric .......................................................... 417
Appendix D Determining the Minimum Number of Required Plumbing Fixtures .............. 419
Appendix E Special Design Plumbing Systems ................................................................... 425
Appendix F Requirements of the Adopting Agency ............................................................... 433
Appendix G Graywater Recycling Systems ......................................................................... 435
Appendix H Installation of Medical Gas and Vacuum Piping Systems ................................ 439
Appendix I Fixture Unit Value Curves for Water Closets ..................................................... 441
Appendix J Reserved ............................................................................................................. 445
vii
Appendix K Flow in Sloping Drains ........................................................................................ 447
Appendix L An Acceptable Brazing Procedure for General Plumbing .............................. 451
Appendix M Converting Water Supply Fixture Units (WSFU) To Gallons Per Minute Flow
(GPM) ................................................................................................................. 459
Index Alphabetical Index .......................................................................................... 465
viii
Administration
ADM 1.1 TITLE
The regulations contained in the following chapters and sections shall be known as the “National Standard Plumb-
ing Code" and may be cited as such, and hereinafter referred to as “this Code”.
1.4.8 Appendices
The provisions in the appendices are intended to supplement the requirements of this Code and are consid-
ered to be part of this Code when adopted by the Authority Having Jurisdiction
1.5.5 Retesting
The Authority Having Jurisdiction may require any tests to be repeated if, at any time, there is reason to be-
lieve that any material or method of installation no longer conforms to the requirements on which the original
approval was based.
1.6.7 Liability
The Authority Having Jurisdiction, or any individual duly appointed or authorized by the Authority Having
Jurisdiction to enforce this Code, acting in good faith and without malice, shall not thereby be rendered per-
sonally liable for any damage that may occur to persons or property as a result of any act, or by reason of any
act or omission in the lawful discharge of his duties. Should a suit be brought against the Authority Having
Jurisdiction or duly appointed representative because of such act or omission, it shall be defended by legal
counsel provided by this jurisdiction until final termination of the proceedings.
1.7.2 Penalties
Any individual, partnership, firm or corporation who shall violate or fail to comply with any of the require-
ments of this Code shall be deemed guilty of a , and if convicted, shall be punishable by a fine or
imprisonment or both as established by this jurisdiction. Each day during which a violation occurs or contin-
ues, shall constitute a separate offense.
1.9.2 Plans
Two or more sets of plans shall be submitted with each permit application. The plans shall contain all the
engineering calculations, drawings, diagrams and other data as required for approval. The Authority Having
Jurisdiction may also require that the plans, drawings, diagrams and calculations be designed by an engineer
and/or architect licensed by the state in which the work is to be performed.
Except that the Authority Having Jurisdiction may waive the submission of plans and other data, provided it
is determined that the nature of the work covered by the permit does not require plan review to obtain code
compliance.
1.9.3 Specifications
All specifications required to be on the plans shall be drawn to scale and sufficiently clear to indicate the
nature, location and extent of the proposed work so as to show how it will conform to the requirements of
this Code.
1.11.2 Exception:
For moved-in or relocated structures, minor installations and repairs, the Authority Having Jurisdiction may
make other such inspections or tests as necessary to assure that the work has been performed and is safe for
use in accordance with the intent of this Code.
Definitions
1.1 GENERAL
For the purpose of this Code, the following terms shall have the meaning indicated in this chapter. No attempt
is made to define ordinary words that are used in accordance with their established dictionary meaning, except
where it is necessary to define their meaning as used in this Code to avoid misunderstanding.
Accessible: access thereto without damaging building surfaces, but that first may require the removal of an
access panel, door or similar obstructions with the use of tools. See Figure 1.2.1
Readily accessible: access without requiring the use of tools for removing or moving any panel, door or simi-
lar obstruction. See Figure 1.2.1
Figure 1.2.1
AN EXAMPLE OF ACCESSIBLE AND READILY ACCESSIBLE
Adopting Agency (See also “Authority Having Jurisdiction”) The agency, board or authority having the duty
and power to establish the plumbing code that will govern the installation of all plumbing work to be performed in
the jurisdictions.
Air Break (drainage system): A piping arrangement in which a drain from a fixture, appliance, or device
discharges into a receptor at a point below the flood level rim and above the trap seal of the receptor. See Figure
1.2.2 and Section 9.1.3
Figure 1.2.2
AIR BREAKS
Air Chamber: A pressure surge absorbing device operating through the compressibility of air.
Comment: The Code no longer mentions air chambers. Air chambers were usually field-fabricated and
were initially filled with air at atmospheric pressure. There was direct contact between the captive air
and water, which permitted the air to be absorbed into the water over a period of time. The Code now
calls for water hammer arrestors, which are pre-charged with compressed air or gas and have bellows or
pistons that separate the air or gas from the water. See Figure 1.2.3.
NOTES:
1. For maximum effectiveness, the water hammer arrestor should be oriented so that the direction of the
shock wave caused by the quick-closing valve is into the arrestor. Refer to the manufacturer’s instruc-
tions.
2. The number of elbows upstream from the water hammer arrestor should be minimized. Each elbow
represents a point of shock and potential failure.
Figure 1.2.3
A WATER HAMMER ARRESTOR
Comment: Air gaps are required where backflow can occur due to back-siphonage.
Figure 1.2.4
AN AIR GAP FOR INDIRECT WASTE PIPING
Air Gap (water distribution system): The unobstructed vertical distance through the free atmosphere between
the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture or other device and the
flood level rim of the receptor. See Figure 1.2.5
Comment #1: The minimum required air gap distance is based on the effective opening of the water
supply outlet. The air gap must be increased if the outlet is close to walls or other vertical surfaces. See
Section 10.5.2 and Table 10.5.2.
Comment #2: If air is being drawn into the tub spout by a vacuum in the water supply piping, waste
water at the flood level rim of the fixture will tend to be lifted upward towards the spout opening by the
flow of air. The water will lift higher if the spout opening is close to a wall.
Figure 1.2.5
AN AIR GAP FOR A POTABLE WATER OUTLET
Anti-scald Valve: See “Water Temperature Control Valve.” See Section 10.15.6
Approved: Accepted or acceptable under an applicable standard stated or cited in this Code, or accepted as suit-
able for the proposed use under procedures and powers of the Authority Having Jurisdiction as defined in
Section 3.12. See Sections 3.1.1, 3.1.2, 3.1.3, and 3.12
Area Drain: A receptor designed to collect surface or storm water from an open area. See Figures 1.2.6 and
13.1.6
Figure 1.2.6
AREA DRAINS IN WINDOW WELLS AND STAIR WELLS
Aspirator: A fitting or device supplied with water or other fluid under positive pressure that passes through an
integral orifice or “constriction” causing a vacuum. See Figure 1.2.7 and Section 14.13
Comment: Backflow prevention is required where the fluid supply is potable water.
Figure 1.2.7
AN ASPIRATOR FITTING
Automatic Flushing Device: A device that automatically flushes a fixture after each use without the need for
manual activation.
Auxiliary Floor Drain: A floor drain that does not receive the discharge from any indirect waste pipe or other
predictable drainage flows. Auxiliary floor drains have no DFU loading.
Backflow Preventer: A device or means to prevent backflow. See Figures 1.2.5, 1.2.8, 1.2.9, 1.2.23, 1.2.25,
1.2.26, 1.2.27, 1.2.48, 1.2.66, and 1.2.67.
Figure 1.2.8
BACKFLOW CAUSED BY BACK-PRESSURE
NOTES:
1. Back-pressure backflow is generally caused by water pressure producing equipment within a building.
2. The hot water heating boiler operates at up to 30 psig and has a chemical shot feeder.
3. The pressure in the public water main can drop below 30 psig due to a shutdown for repair or heavy
demand for fire fighting operations.
Figure 1.2.9
BACKFLOW CAUSED BY BACK-SIPHONAGE
Backflow (Water Distribution): The flow of water or other liquids, mixtures or substances from any source or
sources into the distribution pipes of a potable water system. Back-siphonage is one type of backflow. See Figures
1.2.8 and 1.2.9
Backpressure Backflow: Backflow through a cross connection caused by a higher pressure in the non-potable
system than in the potable supply system. See Figure 1.2.8
Back-Siphonage: Backflow through a cross connection caused by a greater negative pressure in the potable sys-
tem than in the non-potable supply system. See Figure 1.2.9
Backwater Valve: A device installed in a drain pipe to prevent reverse flow in the drainage system. See Figure
1.2.10
Comment: Backwater valves are swing-type check valves that are installed in drainage piping to prevent
the reversal of flow in the piping and overflows due to stoppages, flooding, or other abnormal conditions.
Refer to Section 5.5.1 for where backwater valves are required.
Bathroom Group: A group of fixtures in a dwelling unit bathroom consisting of one water closet, one or two
lavatories, and either one bathtub, one combination bath/shower or one shower stall. Other fixtures within the
bathing facility shall be counted separately when determining the total water supply and drainage fixture loads for
the bathroom group.
Battery of Fixtures: Any group of two or more similar adjacent fixtures that discharge into a common horizontal
waste or soil branch. See Figure 1.2.11
Comment: Batteries of fixtures can be “battery vented” in groups of up to eight fixtures in accordance
with Section 12.13. Fixtures that are “battery vented” do not have to be the same type.
Figure 1.2.11
A BATTERY OF FIXTURES
Bedpan Steamer: A fixture used for scalding bedpans or urinals by direct application of steam. See Section
14.10
Boiler Blow-off: An outlet on a boiler to permit emptying or discharge of sediment. See Figure 1.2.12
Boiler Blow-off Tank: A vessel designed to receive the discharge from a boiler blow-off outlet and to cool the
discharge to a temperature that permits its safe discharge to the drainage system. See Figure 1.2.12
Comment: Boiler blow-off must be cooled to 140°F or less before being discharged into the drainage
system. If potable water is supplied for cooling, the water source must be protected from backflow.
An air break can be provided at the discharge from the blow-off tank into the drainage system if the
makeup water supply to the boiler is protected against backflow.
Branch: Any part of the piping system other than a riser, main or stack. See Figure 1.2.13
Comment: Branch piping can serve more than one fixture or appliance.
Branch Interval: A distance along a vertical soil or waste stack corresponding, in general, to a story height, but
in no case less than 8 feet within which the horizontal branches from one floor or story of a building are connected
to the stack. See Figure 1.2.14
Comment: Branch intervals are used to determine the potential drainage load on stacks for the purpose
of sizing the stacks.
Figure 1.2.14
BRANCH INTERVALS
Building Classification: The arrangement adopted by the Authority Having Jurisdiction for the designation of
buildings in classes according to occupancy. See Table 7.21.1
Comment: The building classifications in Table 7.21.1 for the minimum number of required plumbing
fixtures include assembly, business, education, factory and industrial, institutional, mercantile, residen-
tial, storage, and utility/miscellaneous.
Figure 1.2.15
A COMBINED BUILDING DRAINAGE SYSTEM
Building Drain: The lowest piping in a drainage system that receives the discharge from stacks and horizontal fixture
branches within a building that convey sewage, waste, or other drainage to a building sewer beginning three (3) feet
outside the building wall. Horizontal fixture branches are sized according to Table 11.5.1B until they connect to the
building drain or a branch of the building drain that serves two or more horizontal fixture branches.
Building Drain, Combined: A building drain that conveys both sewage and storm water or other drainage.
See Figure 1.2.15
Building Drain, Sanitary: A building drain that conveys sewage only. See Figure 1.2.16
Building Drain, Storm: A building drain that conveys storm water or other drainage, but no sewage. See Figure
1.2.16
Building Sewer: That part of the drainage system that extends from the end of the building drain and conveys
its discharge to a public sewer, private sewer, individual sewage disposal system or other point of disposal. The
building sewer begins at a point three feet beyond the outside face of the building. See Figure 1.2.16
Building Sewer, Combined: A building sewer that conveys both sewage and storm water or other drainage. See
Figure 1.2.15
Building Sewer, Sanitary: A building sewer that conveys sewage only. See Figure 1.2.16
Building Sewer, Storm: A building sewer that conveys storm water or other drainage but no sewage. See Figure
1.2.16
Building Subdrain: That portion of a drainage system that does not drain by gravity into the building drain or
building sewer. See Figure 1.2.17
Building Trap: A device, fitting, or assembly of fittings, installed in the building drain to prevent circulation of
sewer gas between the building sewer and the drainage system in the building. See Figure 1.2.18
Comment: Building traps are currently installed only when required by the Authority Having Jurisdic-
tion.
Figure 1.2.18
A BUILDING TRAP
Comment: Chapter 16 does not permit cesspools or cesspits, into which untreated sewage is discharged
and allowed to seep into the ground. Chapter 16 requires septic tanks to retain the sewage until digested
and absorption trenches or seepage pits for underground disposal of the effluent.
Chemical Waste: Includes industrial liquid waste, process waste, diluted and undiluted acid waste and corrosive
and non-corrosive chemical liquid waste. See Sections 2.10, 3.11, and 9.4.
Clear Water Waste: Effluent in which impurity levels are less than concentrations considered harmful by the
Authority Having Jurisdiction, such as cooling water and condensate drainage from refrigeration and air condi-
tioning equipment, cooled condensate from steam heating systems, and residual water from ice making processes..
Comment: Refer to Section 9.1.8 for whether a clear water waste requires an air gap or an air break at
its discharge into the drainage system.
Clinical Sink: A sink designed primarily to receive wastes from bedpans, having a flushing rim, intergral trap
with a visible trap seal, and having the same flushing and cleansing characteristics as a water closet. See Section
14.8
Code: These regulations, or any emergency rule or regulation that the Authority Having Jurisdiction may law-
fully adopt.
Combination Fixture: A fixture combining one sink and laundry tray, or a two- or three-compartment sink or
laundry tray in one unit. See Figure 1.2.19
Comment: Combination fixtures with waste outlets not more than 30 inches apart can have one trap
Figure 1.2.19
COMBINATION FIXTURES
Combination Waste and Vent System: A designed system of waste piping embodying the horizontal wet vent-
ing of one or more sinks or floor drains by means of a common waste and vent pipe adequately sized to provide
free movement of air above the flow line of the drain. See Figure 1.2.20 and Section 12.17
Comment #2: Only floor drains, floor receptors, sinks, lavatories, and standpipes can be discharged into
a combination waste and vent piping system.
Figure 1.2.20
COMBINATION WASTE AND VENT PIPING
Commercial Kitchen: One or more rooms in a building that is licensed to prepare food to be served for consump-
tion or process food to be packaged for distribution.
Conductor: A pipe within a building that conveys stormwater from a roof to its connection to a building storm
drain or other point of disposal. See Figure 1.2.21
Figure 1.2.21
A STORMWATER CONDUCTOR
Continuous Waste: A drain from two or more fixtures connected to a single trap. See Figure 1.2.22
Comment: Continuous waste piping can connect up to three adjacent sinks or lavatories to a single trap
if the fixture outlets are no more than 30” apart. See Section 5.1.
Figure 1.2.22
CONTINUOUS WASTE PIPING
Critical Level: The marking on a backflow prevention device or vacuum breaker established by the manufactur-
er, and usually stamped on the device by the manufacturer, that determines the minimum elevation above the flood
level rim of the fixture or receptor served at which the device must be installed. When a backflow prevention
device does not bear a critical level marking, the bottom of the vacuum breaker, combination valve, or the bottom
of any approved device constitutes the critical level. See Figure 1.2.23 and Sections 10.5.5.b, c, and e
Figure 1.2.23
THE CRITICAL LEVEL (C-L) OF A VACUUM BREAKER
Comment: The backflow of contamination into a potable water system through a cross connection can
occur by back-siphonage caused by the water system or back-pressure from the source of contamination.
Day Care Center: A facility for the care and/or education of children ranging from 2-1/2 years of age to 5 years
of age.
Day Nursery: A facility for the care of children less than 2-1/2 years of age.
Dead End, Potable Water: A branch line terminating at a developed length of two (2) feet or more from an ac-
tive potable water line by means of a plug or cap. See Figure 1.2.24
Comment: An extension of 2 feet or more to make a cleanout accessible is not considered to be a dead
end.
Figure 1.2.24
DEAD ENDS IN DRAIN AND VENT PIPING
Dead End, Soil, Waste, or Vent: A branch leading from a soil, waste or vent pipe, building drain, or building
sewer line and terminating at a developed length of two (2) feet or more by means of a plug, cap, or other closed
fitting.
Developed Length: The length of a pipe line measured along the center line of the pipe and fittings.
Domestic Sewage: The water-borne wastes derived from ordinary living processes.
Double Check Valve Assembly: A backflow prevention device consisting of two independently acting check
valves, internally force loaded to a normally closed position between two tightly closing shut-off valves, and with
means of testing for tightness. See Figure 1.2.25
Drain: Any pipe that carries waste or water-borne wastes in a building drainage system.
Drainage, Sump : A liquid and air-tight tank that receives sewage and/or liquid waste, located below the eleva-
tion of a gravity drainage system, that is emptied by pumping.
Drainage System: All the piping within public or private premises that conveys sewage, rain water, or other
liquid wastes to a point of disposal. It does not include the mains of a public sewer system or private or public
sewage-treatment facilities.
Drainage System, Building Gravity: A drainage system that drains by gravity into the building sewer. See
Figure 1.2.16
Dwelling Unit, Multiple: A room, or group of rooms, forming a single habitable unit with facilities that are used,
or intended to be used, for living, sleeping, cooking and eating; and whose sewer connections and water supply,
within its own premise, are shared with one or more other dwelling units. Multiple dwelling units include apart-
ments, condominums, and hotel and motel guest rooms.
DWV: An acronym for “drain-waste-vent” referring to the combined sanitary drainage and venting systems. This
term is equivalent to “soil-waste-vent” (SWV).
Effective Opening: The minimum cross-sectional area at the point of water supply discharge, measured or ex-
pressed in terms of (1) diameter of a circle, or (2) if the opening is not circular, the diameter of a circle of equiva-
lent cross-sectional area. See Figures 1.2.26 and 1.2.27
Comment: The required air gap distance for a water supply outlet is based on its effective opening. The
air gap must be increased if the outlet is near a wall or other vertical surface. Refer to Table 10.5.2 for
minimum air gaps for plumbing fixtures.
Figure 1.2.26
THE EFFECTIVE OPENING OF A POTABLE WATER OUTLET
Figure 1.2.27
AN AIR GAP BETWEEN POTABLE AND NON-POTABLE WATER SYSTEMS
Equivalent Length: The length of straight pipe of a specific diameter that would produce the same frictional
resistances as a particular fitting or line comprised of pipe and fittings. See Tables B.9.7A and B.9.7B
Existing Plumbing System: An existing plumbing system, or any part thereof, installed prior to the effective date
of this Code.
Existing Work: An existing plumbing system, or any part thereof, installed prior to the effective date of this
Code.
Family: One or more individuals living together and sharing the same facilities.
Fixture Branch, Drainage: A drain serving one or more fixtures that discharges into another drain. See Figure
1.2.28
Comment: See Table 11.5.1.B for the maximum number of drainage fixture units (DFU) permitted on
each size of horizontal fixture branch.
Figure 1.2.28
A FIXTURE DRAIN AND FIXTURE BRANCH
Fixture Branch, Supply: A branch of the water distribution system supplying one fixture. See Figure 1.2.29
Comment: See Table 10.14.2.A for minimum supply fixture branch sizes for various fixtures.
Figure 1.2.29
A FIXTURE SUPPLY BRANCH AND FIXTURE SUPPLY TUBE
Fixture Drain: The drain from the trap of a fixture to the junction of that drain with any other drain pipe.
Fixture Unit (Water Supply - WSFU): An index number that represents the load of a fixture on the water sup-
ply system so that the load of various fixtures in various applications can be combined. The value is based on the
volume rate of supply for the fixture, the time duration of a single supply operation, and the average time between
successive uses of the fixture. Water supply fixture units were originally based on a comparison to a flushometer
valve water closet, which was arbitrarily assigned a value of 10 WSFU. See Table 10.14.2A. Also Tables B.5.2
and B.5.3.
Flexible Water Connector: A connector under continuous pressure in an accessible location that connects a supply
fitting, faucet, dishwasher, cloths washer, water heater, water treatment unit, or other fixture or equipment to a stop
valve or its water supply branch pipe.
Flood Level Rim: The edge of the receptor or fixture over which water flows if the fixture is flooded. See Fig-
ure 1.2.30
Comment: Air gaps are measured from above the flood level rim of receptors and fixtures.
Figure 1.2.30
THE FLOOD LEVEL RIM OF FIXTURES
Flooded: The condition that results when the liquid in a receptor or fixture rises to the flood level rim.
Flow Pressure: The pressure in the water supply pipe near the faucet or water outlet while the faucet or water
outlet is fully open and flowing. See Figure 1.2.31
Comment: The minimum required flowing water pressure for most fixtures and appliances is 15 psig.
Blowout water closets and blowout urinals require 25 psig minimum. Some one-piece water closets
require 30 psig minimum and 1/2” supply tubes.
Flush Pipes and Fittings: The pipe and fittings that connect a flushometer valve or elevated flush tank to a water
closet, urinal, or bed pan washer.
Flushing Type Floor Drain: A floor drain that is equipped with an integral water supply connection, enabling
flushing of the drain receptor and trap. See Figure 1.2.32
Comment: The water supply to flushing floor drains must be protected from backflow.
Figure 1.2.32
A FLUSHING TYPE FLOOR DRAIN
Flush Valve: A device located at the bottom of a flush tank for flushing water closets and similar fixtures. See
Figure 1.2.33
Flushometer Tank: A water closet flush tank that uses an air accumulator vessel to discharge a predetermined
quantity of water into the closet bowl for flushing purposes. See Figure 1.2.34
Comment: Flushometer tanks are pressure-assisted flush tanks that store water for flushing water clos-
ets at the inlet water supply pressure, as opposed to gravity tanks. The discharge rate from flushometer
tanks is approximately 35 gallons per minute.
Figure 1.2.34
A PRESSURE-ASSISTED WATER CLOSET WITH A FLUSHOMETER TANK
Flushometer Valve: A device that discharges a predetermined quantity of water to fixtures for flushing and is
closed by direct water pressure or other means. See Figure 1.2.35
Comment: Flushometer valves are typically used on public water closets and public urinals. They can
be manually operated or electronically operated.
Force Main: A main that delivers waste water under pressure from a sewage ejector or pump to its destination.
Full-way valve: Full-way valves include gate valves, full port ball valves, and other valves that are identified by
their manufacturer as full port or full bore.
Grade: The fall (slope) of a line of pipe in reference to a horizontal plane. See Figure 1.2.36.
Comment: See Tables 11.5.1A and 11.5.1B for sizing building drains, building sewers, and horizontal
fixture branches. See Table 13.6.2 for stormwater drains.
Figure 1.2.36
GRADE ON A SLOPING GRAVITY DRAIN
Grease Interceptor: A plumbing appurtenance that is installed in the sanitary drainage system to intercept oily
and greasy wastes from wastewater discharges, typically in commercial kitchens and food processing plants. Such
equipment has the ability to intercept commonly occurring free-floating fats and oils.
Grease Removal (or Recovery) Device (GRD): A plumbing appurtenance that is installed in the sanitary drainage
system to intercept and remove free-floating fats, oils, and grease from wastewater discharges, typically in commer-
cial kitchens and food processing plants. Such equipment operates on a time or event- controlled basis and has the
ability to remove the entire range of commonly occurring free-floating fats, oils, and grease automatically without
intervention from the user except for maintenance. The removed material is essentially water-free, which allows for
recycling of the removed product.
Grinder Pump: A pump for sewage that shreds or grinds the solids in the sewage that it pumps.
Half-Bath: A room that contains one water closet and one lavatory within a dwelling unit.
Health Hazard: In backflow prevention, an actual or potential threat of contamination of the potable water sup-
ply to the plumbing system of a physical or toxic nature that would be a danger to health. Health hazards include
any contamination that could cause death, illness, or spread of disease.
Horizontal Branch Drain: A drain pipe extending laterally from a soil stack, waste stack or building drain with
or without vertical sections or branches, that receives the waste discharged from one or more fixture drains and
conducts the waste to a soil stack, waste stack, or building drain.
Horizontal Pipe: Any pipe or fitting that makes an angle of less than 450 with the horizontal. See Figure 1.2.37
Comment: The sizing of offsets in drainage stacks varies depending on whether the offset is horizontal
or vertical. See Section 11.6.
Figure 1.2.37
THE DEFINITION OF "HORIZONTAL PIPE"
Hot Water: Potable water that is heated to a required temperature for its intended use.
Indirect Connection (Waste): The introduction of waste into the drainage system by means of an air gap or air
break.
Indirect Waste Pipe: A waste pipe that does not connect directly with the drainage system, but which discharges
into the drainage system through an air break or air gap into a trap, fixture, receptor or interceptor. See Figure
1.2.38
Individual Fixture Supply Valve: A valve installed in fixture supply branch piping used for the purpose of
regulating or stopping water flow to an individual fixture for installation, repair, or replacement of the fixture or its
faucet.
Industrial Wastes: Liquid or liquid-borne wastes resulting from the processes employed in industrial and com-
mercial establishments.
Comment: Industrial wastes must not be discharged into public sewers if they will damage the sewer or
interfere with the operation of the sewage treatment plant.
Interceptor: A device designed and installed so as to separate and retain deleterious, hazardous, or undesirable
matter from normal wastes while permitting normal sewage or liquid wastes to discharge into the drainage system
by gravity. See Figure 1.2.39
Comment: Interceptors include grease interceptors, oil/water separators, sand interceptors, solids inter-
ceptors, and neutralizing or dilution tanks.
Invert: The lowest portion of the inside of a horizontal pipe. See Figure 1.2.40
Comment: Invert elevations are used to design and install drainage piping at the required grade or
slope.
Figure 1.2.40
THE INVERT OF A DRAIN PIPE
Leaching Well or Pit: A pit or receptor having porous walls that permit the liquid contents to seep into the
ground. See Figure 1.2.41
Comment: Leeching wells or pits are used to disperse the effluent from septic tanks into the ground for
secondary treatment. They may supplement or be used in lieu of absorption trenches. Leaching wells
or pits can only be used where there is very deep soil of good permeability and considerable depth to
groundwater.
Leader: An exterior vertical drainage pipe for conveying storm water from roof or gutter drains. See Figure
1.2.42
Figure 1.2.42
A STORMWATER LEADER
Local Ventilating Pipe: A pipe on the fixture side of the trap through which vapor or foul air is removed from a
fixture. See Figure 1.2.43
Comment: Local vent piping may be required for clinical sinks, bedpan washers, and sterilizers. Local
vents for sterilizers must not be connected to local vents for clinical sinks and bedpan washers. Refer to
Section 14.9 for clinical sinks and bedpan washers. Refer to Section 14.10 for sterilizers.
Figure 1.2.43
A STERILIZER LOCAL VENTILATING PIPE
Macerating Toilet System: A system that collects drainage from a single water closet, lavatory and/or bathtub
located in the same room. It consists of a receiving container, a grinder pump, and associated level controls. The
system pumps shredded or macerated sewage up to a point of discharge
Main, Water Supply: That portion of the water supply distribution piping that branches, fixture supply branches,
and risers are connected to.
Medical Gas System: The complete system used to convey medical gases for direct application from central
supply systems (bulk tanks, manifolds and medical air compressors) through piping networks with pressure and
operating controls, alarm warning systems, etc., and extending to station outlet valves at use points.
Comment: Medical gas systems must comply with NFPA 99 - Standard for Health Care Facilities or
NFPA 99C - Gas and Vacuum Systems. NFPA 99 is the parent document for NFPA 99C. NFPA 99 ad-
dresses all safety aspects of health care facilities, whereas NFPA 99C limits itself to the medical gas and
vacuum portions of NFPA 99.
Non-Health Hazard: In backflow prevention, an actual or potential threat to the physical properties or potability
of the water supply to the plumbing system, but which would not constitute a health or system hazard.
Non-Potable Water: Water not safe for drinking, personal or culinary use.
Nominal Size: (Pipe or Tube): The industry-recognized size of a plumbing pipe or tube that is not necessarily
an actual dimension. It indicates the size of the pipe or tube as indicated in its material standard listed in Table
3.1.3.
Nuisance: Public nuisance at common law or in equity jurisprudence; whatever is dangerous to human life or
detrimental to health; whatever building, structure, or premises is not sufficiently ventilated, sewered, drained,
cleaned, or lighted in reference to its intended or actual use; and whatever renders the air, human food, drink or
water supply unwholesome.
Offset: A combination of elbows or bends that brings one section of the pipe out of line but into a line parallel
with the other section. See Figure 1.2.44 - Parts A and B for single offsets
Comment: Offsets can occur in vertical and horizontal piping. Offsets can consist of 90-degree, 45-de-
gree, or other angle fittings. Single offsets have one change of alignment.
Figure 1.2.44
OFFSETS IN PIPING
Offset, Double: Two offsets installed in succession or series in a continuous pipe. See Figure 1.2.44 - Parts E
and F
Comment: Double offsets have two offsets, both away from the original alignment of the pipe.
Offset, Return: A double offset installed so as to return the pipe to its original alignment. See Figure 1.2.44 –
Parts C and D
Comment: Return offsets have two offsets, both in different directions. The second offset does not nec-
essarily bring the pipeline back into exact alignment with the first. The alignment of the piping on both
sides of the offset is not necessarily exactly the same laterally.
Person: A natural person, his heirs, executors, administrators or assigns; including a firm, partnership or corpora-
tion, its or their successors or assigns. Singular includes plural; male includes female.
Plenum: An enclosed portion of the building structure, other than an occupiable space being conditioned, that is
designed to allow air movement, and thereby serve as part of an air distribution system.
Plumbing
The practice, materials, and fixtures within or adjacent to any building structure or conveyance, used in the instal-
lation, maintenance, extension, alteration and removal of any piping, plumbing fixtures, plumbing appliances, and
plumbing appurtenances in connection with any of the following:
Plumbing Appliance: Any one of a special class of plumbing fixture that is intended to perform a special plumb-
ing function. Its operation and/or control may be dependent upon one or more energized components, such as
motors, controls, heating elements, or pressure or temperature-sensing elements. Such fixtures may operate
automatically through one or more of the following actions: a time cycle, a temperature range, a pressure range, a
measured volume or weight; or the fixture may be manually adjusted or controlled by the user or operator.
Comment: Plumbing appliances include clothes washers, dishwashers, food-waste-disposal and grinder
units, water heaters, water softeners, and similar devices. Refer to Table 3.1.3 - Part VII for listed appli-
ances.
Plumbing Fixture: A receptacle or device connected to the water distribution system of the premises, and
demands a supply of water there from; or discharges used water, liquid-borne waste materials, or sewage either
directly or indirectly to the drainage system of the premises; or which requires both a water supply connection and
a discharge to the drainage system of the premises. Plumbing appliances as a special class of fixture are further
defined.
Comment: Plumbing fixtures include water closets, urinals, bidets, lavatories, bathtubs, whirlpool baths,
showers, sinks, floor drains, and receptors. Refer to Table 3.1.3 - Part V for listed plumbing fixtures.
Plumbing System: Includes the water supply and distribution pipes, plumbing fixtures and traps; soil, waste and
vent pipes; sanitary and storm drains and building sewers; including their respective connections, devices and ap-
purtenances to an approved point of disposal.
Pollution (of Potable Water): An impairment of the quality of the potable water to a degree that does not create
a hazard to the public health but that does adversely and unreasonably affect the aesthetic qualities of such potable
water for domestic use. (See the definition of “contamination”).
Potable Water: Water free from impurities present in amounts sufficient to cause disease or harmful physiologi-
cal effects and conforming in its bacteriological and chemical quality to the requirements of the Public Health
Service Drinking Water Standards or the regulations of the public health authority having jurisdiction.
Pressure Balancing Valve: A mixing valve which senses incoming hot and cold water pressures and compen-
sates for fluctuations in either to stabilize its outlet temperature.
Comment: Pressure balancing control valves for individual bathing facilities must comply with ANSI/
ASSE 1016, Type P.
Private Sewage Disposal System: A system for disposal of domestic sewage by means of a septic tank or me-
chanical treatment, designed for use apart from a public sewer to serve a single establishment or building. See
Chapter 16
Private Use - Plumbing facilities for the private and restricted use of one or more individuals in dwelling units
(including hotel and motel guest rooms), and other plumbing facilities that are not intended for public use. Refer
to the definition of “Public Use”.
Private Water Supply: A supply, other than an approved public water supply, which serves one or more build-
ings. See Figure 1.2.46 and Chapter 17
Figure 1.2.46
A TYPICAL PRIVATE WATER SUPPLY SYSTEM
Comment: This Code does not cover public sewers. The design and construction of public sewers is
regulated by the sewage authority, a public works department, or other Authority Having Jurisdiction.
Public Toilet Room: A toilet room intended to serve the transient public, such as in, but not limited to the follow-
ing examples: service stations, train stations, airports, restaurants, and convention halls.
Public Water Main: A water supply pipe for public use controlled by public authority.
Comment: This Code does not cover public water mains. The design and construction of public water
mains is regulated by the water purveyor, a public works department, or other Authority Having Juris-
diction.
Push-Fit Fittings: A type of mechanical joint used with copper, CPVC and/or PEX that is either permanent or
removable and may be used separately or integrated into plumbing fitting devices used in domestic or commercial
applications in potable water distribution systems.
Receptor: A fixture or device which receives the discharge from indirect waste pipes. See Figure 1.2.47
Reduced Pressure Backflow Preventer Assembly: See Reduced Pressure Zone Backflow Preventer Assembly
Reduced Pressure Principle Assembly: A reduced pressure zone backflow preventer assembly.
Reduced Pressure Zone Backflow Preventer Assembly: A backflow prevention device consisting of two inde-
pendently acting check valves, internally force loaded to a normally closed position and separated by an interme-
diate chamber (or zone), in which there is an automatic relief means of venting to atmosphere, internally loaded to
a normally open position, and with means for testing for tightness of the checks and opening of the relief means.
See Figure 1.2.48
Comment: Reduced pressure principle backflow preventor assemblies provide the highest level of pro-
tection against backpressure backflow. The shutoff valves on these assemblies are resiliently seated to
assure tight close-off for testing. Provisions must be made to drain any discharge from the relief vent
outlet, which may occur due to normal variations in system pressure.
Figure 1.2.48
A REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY
Comment: The flood level rim of a fixture or appliance is the level from which it will overflow if its drain
outlet is closed or blocked.
Riser: A water supply pipe that extends vertically one full story or more to convey water to branches or to a
group of fixtures. See Figure 1.2.49
Comment: The term "riser" refers to vertical water supply piping serving one or more fixtures in build-
ings having one or more story heights.
Figure 1.2.49
A WATER SUPPLY RISER
Roof Drain: A drain installed to receive water collecting on the surface of a roof and to discharge it into a leader
or a conductor. See Figure 1.2.50
Comment: Roof drains include flat deck drains and scupper drains.
Figure 1.2.50
A GENERAL PURPOSE ROOF DRAIN
Roughing-in: The installation of all parts of the plumbing system that can be completed prior to the installa-
tion of fixtures. This includes drainage, water supply, and vent piping, and the necessary fixture supports, or any
fixtures that are built into the structure.
Sand Filter: A treatment device or structure, constructed above or below the surface of the ground, for remov-
ing solid or colloidal material of a type that cannot be removed by sedimentation, from septic tank effluent. See
Figure 1.2.51 and Section 16.12
Comment #1: Sand filters provide additional treatment of septic tank effluent. They are used where the
soil depth is shallow and cannot provide sufficient secondary treatment of the effluent.
Comment #2: Sand interceptors (or sand traps) are associated with oil/water separators in Chapter 6.
Figure 1.2.51
A SAND FILTER FOR SEPTIC TANK EFFLUENT
Comment: Sand interceptors (or sand traps) are associated with oil/water separators in Chapter 6. Sand
filters are associated with the effluent from septic tanks in Chapter 16.
Comment: The term "sand trap" is used interchangeably with "sand interceptor."
Sanitary Sewer: A sewer that carries sewage and excludes storm, surface and ground water.
SDR: An abbreviation for “standard dimensional ratio” that relates to a specific ratio of the average specified
outside diameter to the minimum wall thickness for outside diameter controlled plastic pipe.
Septic Tank: A watertight receptacle that receives the discharge of a building sanitary drainage system or part
thereof; and that is designed and constructed so as to separate solids from the liquid, digest organic matter through
a period of detention, and allow the liquids to discharge into the soil outside of the tank through a system of open
joint or perforated piping, or a seepage pit. See Figure 1.2.52 and Section 16.6
Comment: Figure 1.2.52 shows baffles at the inlet and outlet connections with two access covers.
Figure 16.6.6 shows 6" long drop pipes on the inlet and outlet connections with cleanouts and a single
access cover. Both arrangements perform the same functions and either arrangement is acceptable.
Service Sink: A sink or receptor intended for custodial use that is capable of being used to fill and empty a jani-
tor's bucket. Included are mop basins, laundry sinks, utility sinks, and similar fixtures. (See Table 7.21.1)
Sewage: Liquid containing human waste (including fecal matter) and/or animal, vegetable, or chemical waste
matter in suspension or solution.
Sewage Ejector, Pneumatic Type: A unit that uses compressed air to discharge and lift sewage to a gravity sew-
age system. See Sections 11.7 and 12.14.3
Sewage Pump or Pump-Type Ejector: A non-clog or grinder-type sewage pump or ejector. Sewage pumps and
pump-type ejectors are either the submersible or vertical type. See Figure 1.2.54 and Section 11.7
Comment: Figure 1.2.54 shows a pedestal-type sewage pump. Sewage pumps can also be submersible
pumps or dry pit centrifugal pumps.
Figure 1.2.54
A PEDESTAL TYPE SEWAGE PUMP
Shock Arrestor (mechanical device): A device used to absorb the pressure surge (water hammer) that occurs
when water flow is suddenly stopped. See Figure 10.14.7 and Section 10.14.7 for Water Hammer Arrestors.
Also Figure 1.2.3
Comment: Water hammer arrestors are either the bellows or piston type and are pre-charged with com-
pressed air or gas. The Code no longer mentions air chambers, which are subject to losing their
initial captive air charge through absorption into the system water.
Shut-off Valve: A ball, gate, or other full way valve located in water supply mains, risers, and branches for the
purpose of controlling water supply to a fixture or group of fixtures.
Sink, Commercial: A sink other than for a domestic application. Commercial sinks include, but are not limited
to:
1. pot sinks
2. scullery sinks
3. sinks used in photographic or other processes
4. laboratory sinks
Size of Pipe and Tubing, Incremental: Where relative size requirements are mentioned, the following schedule
of sizes is recognized, even if all sizes may not be available commercially: 1/4, 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2,
2-1/2, 3, 3-1/2, 4, 4-1/2, 5, 6, 7, 8, 10, 12, 15, 18, 21, 24.
Slip Joint: A connection in drainage piping consisting of a compression nut and compression washer that permits
drainage tubing to be inserted into the joint and secured by tightening the compression nut. Slip joints are typi-
cally used in trap connections for lavatories, sinks, and bathtubs. They permit the trap to be removed for cleaning
or replacement, and to provide access to the drainage piping.
Soil Pipe or Soil Stack: Pipes that convey sewage containing fecal matter to the building drain or building sewer.
Special Wastes: Wastes that require special treatment before entry into the normal plumbing system. See Fig-
ures 1.2.55 and 9.4.1. Also Section 9.4
Comment: Figure 1.2.55 shows a neutralizing tank for acid waste using limestone or marble chips. Fig-
ure 9.4.1 shows an automatic neutralizing tank that could treat either acid or caustic wastes, depending
on the neutralizing solution used.
Special Waste Pipe: Pipes which convey special wastes. See Section 3.11 for acceptable piping materials
Stack: A general term for any vertical line including offsets of soil, waste, vent or inside conductor piping. This
does not include vertical fixture and vent branches that do not extend through the roof or that pass through not
more than two stories before being reconnected to the vent stack or stack vent. See Figure 1.2.56, Section
11.5.2, and Table 11.5.1B
Comment: Stacks include soil stacks, waste stacks, vent stacks, and stack vents. See separate defini-
tions.
Figure 1.2.56
A STACK VENT
Stack Vent: The extension of a soil or waste stack above the highest horizontal drain connected to the stack. See
Figure 1.2.56
Stack Venting: A method of venting a fixture or fixtures through the soil or waste stack. See Figure 1.2.57 and
Section 12.11
Figure 1.2.57
STACK VENTING
Standpipe (indirect waste receptor): A vertical drain pipe that has an open top inlet that provides an air break or
air gap for indirect waste discharge.
Storm Sewer: A sewer used for conveying rainwater, surface water, condensate, cooling water, or similar liquid
wastes.
Subsoil Drain: A drain that collects subsurface or seepage water and conveys it to a place of disposal. See Fig-
ure 1.2.59 and Section 13.1.5 for foundation drains
Comment: Refer to Table 3.8 for acceptable materials for subsoil drains.
Suction Line: The inlet pipe to a pump on which a negative pressure may exist under design conditions.
Sump: A tank or pit that receives only liquid wastes, located below the elevation of a gravity discharge, that is
emptied by pumping.
Sump, Drainage (sewage): A liquid and air-tight tank that receives sewage and/or liquid waste, located below
the elevation of a gravity drainage system, that is emptied by pumping. See Figure 1.2.54
Sump Pump: A permanently installed mechanical device for removing clear water or liquid waste from a sump.
See Figure 1.2.60
Figure 1.2.60
DIFFERENT TYPES OF SUMP PUMPS
Swimming Pool: Any structure, basin, chamber or tank containing a body of water for swimming, diving, or
recreational bathing. See Section 9.1.11
Tempered Water: A mixture of hot and cold water to reach a desired temperature for its intended use, typically
95ºF - 105ºF.
Thermostatic/Pressure Balancing Valve, Combination: A mixing valve that senses outlet temperature and
incoming hot and cold water pressures and compenstates for fluctuations in incoming hot and cold water tempera-
tures and/or pressures to stabilize its outlet temperature.
Comment: Combination thermostatic/pressure balancing control valves are used for individual bathing
facilities and must comply with ASSE 1016, Type PT.
Thermostatic (Temperature Control) Valve: A mixing valve that senses outlet temperature and compensates
for fluctuations in incoming hot or cold water temperatures.
Comment: Thermostatic control valves used for individual bathing facilities must comply with ASSE
1016, Type T. Thermostatic control valves for other point-of-use applications should comply with the
appropriate standard.
Toilet Facility: A room or combination of interconnected spaces in other than a dwelling that contains one or
more water closets and associated lavatories, with signage to identify its intended use.
Trap: A fitting or device that provides a liquid seal to prevent the emission of sewer gasses without materially
affecting the flow of sewage or waste water through it. See Figure 1.2.62 and Sections 5.1, 5.2, and 5.3
Figure 1.2.62
ELEMENTS OF A FIXTURE TRAP
Trap Arm: That portion of a fixture drain between a trap and its vent. See Figure 1.2.63 and Section 12.8.1
Comment: Refer to Table 12.8.1 for the maximum allowable length of trap arms to avoid trap siphon-
age.
Figure 1.2.63
THE LENGTH OF A TRAP ARM
Trap Primer: A device or system of piping to maintain a water seal in a trap. See Figures 1.2.64 and 1.2.65.
Also Section 7.16.2
Figure 1.2.64
A FLOW-ACTIVATED TRAP PRIMER
Figure 1.2.65
CONNECTION OF A TRAP PRIMER TO A TRAP
Vacuum Breaker, Atmospheric Type: A vacuum breaker that is not designed to be subject to continuous line
pressure. See Figure 1.2.66
Figure 1.2.66
TYPES OF ATMOSPHERIC VACUUM BREAKERS
Vacuum Breaker, Pressure Type: A vacuum breaker designed to operate under continuous line pressure.
See Figure 1.2.67
Figure 1.2.67
A PRESSURE TYPE VACUUM BREAKER
Vacuum Relief Valve: A device to prevent vacuum in a pressure vessel. See Figure 1.2.69 and Section 10.16.7
Comment: Vacuum relief valves are required on storage-type hot water heaters that are located above
the fixtures that they serve to prevent the tank from being siphoned dry and damaged by dry-firing.
Figure 1.2.69
A VACUUM RELIEF VALVE
Vent, Branch: A vent connecting one or more individual vents with a vent stack or stack vent. See Figure 1.2.70
Figure 1.2.70
A BRANCH VENT
Vent, Circuit: A vent that connects to a horizontal drainage branch and vents from two to eight traps or trapped
fixtures connected in a battery. See Figure 1.2.71
Comment: Circuit vents connect to vent stacks. Loop vents connect to stack vents.
Vent, Common: A vent connected at the common connection of two fixture drains and serving as a vent for both
fixtures. See Figure 1.2.72
Figure 1.2.72
A COMMON VENT
Vent, Continuous: A vertical vent that is a continuation of the drain to which it connects. See Figure 1.2.73
Figure 1.2.73
A CONTINUOUS VENT
Vent, Dry: A vent that does not receive the discharge of any sewage or waste.
Vent, Individual: A pipe installed to vent a single fixture drain. See Figure 1.2.74
Vent, Loop: A circuit vent that loops back to connect with a stack vent instead of a vent stack. See Figure 1.2.75
Comment: Loop vents connect to stack vents. Circuit vents connect to vent stacks.
Figure 1.2.75
A LOOP VENT
Vent, Relief: An auxiliary vent that permits additional circulation of air in or between a drainage and vent sys-
tem. See Figures 12.3.1, 12.3.2, 12.3.3-A, 12.3.3-B, 12.13.1, 12.15.1, and 12.16.2
Comment: Relief vents are required at points in some vertical drainage stacks, at horizontal offsets
in some drainage stacks, at the base of some stacks, and at some battery vented branch connections to
stacks. Refer to Chapter 12.
Vent, Side: A vent connecting to a drain pipe through a fitting at an angle not greater than 45° to the vertical. See
Figure 1.2.76
Vent Stack: A vertical vent pipe that extends through one or more stories and that is intended to provide circula-
tion of air to and from the drainage system. See Figures 1.2.78 and 12.3.1
Vent, Sterilizer: A separate pipe or stack, indirectly drained to the building drainage system at the lower termi-
nal, that receives the vapors from non-pressure sterilizers, or the exhaust vapors from pressure sterilizers, and
conducts the vapors directly to the outer air. Sometimes called vapor, steam, atmosphere or exhaust vent. See
Section 14.11
Figure 1.2.76
SIDE VENTS
Vent, Wet: A vent pipe that is sized and arranged in accordance with this Code to receive the discharge of waste
from a fixture. See Figure 1.2.77. Refer to Section 12.10 for other arrangements of wet venting.
Figure 1.2.77
A WET VENT
Vent, Yoke: A pipe connecting upward from a soil or waste stack to a vent stack for the purpose of equalizing the
pressures in the stacks. See Figure 1.2.78
Vertical Pipe: Any pipe or fitting that makes an angle of 45o or more with the horizontal. See Figure 1.2.79
Figure 1.2.79
THE DEFINITION OF "VERTICAL PIPE"
Figure 1.2.80
A WALL HUNG WATER CLOSET
Waste: Any remaining liquid, or liquid-borne material or residue intended to be discharged to the drainage sys-
tem after any activity or process, but not including any such materials that contain animal or human fecal matter.
Waste Stack, Pipe or Piping: Pipes that convey the discharge from fixtures (other than water closets), appliances,
areas, or appurtenances, that do not contain fecal matter.
Water Closet, Pressure Assisted: A low consumption water closet with an air accumulator vessel in the tank that
stores water and air under pressure, using the water supply pressure. When flushed, the air produces a high veloc-
ity jet of water and air that forces the contents out of the bowl.
Water Closet, Pump Assisted: A low consumption water closet with a fractional horsepower pump in the tank
that produces a high velocity jet in the trap way that assists the flushing action.
Water Closet, Vacuum Assisted: A low consumption water closet that uses the falling water level in the tank to
induce a vacuum near the outlet of the trap way that assists the flushing action.
Water Distribution Piping: Piping within the building or on the premises that conveys water from the water
service pipe to the points of use. See Figure 1.2.81
Water Main: A water supply pipe available for public connection. See "Public Water Main"
Water Outlet: A discharge opening through which water is supplied to a fixture, into the atmosphere (except into
an open tank that is part of the water supply system), to a boiler or heating system, to any devices or equipment
requiring water to operate but that are not part of the plumbing system.
Water Service Pipe: The pipe from the water main, or other source of potable water supply, to the water distribu-
tion system of the building served. See Figure 1.2.82 and Section 10.6
Figure 1.2.82
THE WATER SERVICE PIPE IN A PUBLIC WATER SUPPLY
Water Supply System: The water service pipe, the water distribution pipes, and the necessary connecting pipes,
fittings, control valves, and appurtenances in or adjacent to the building or premises.
Water Temperature Control Valve: A valve of the pressure balance, thermostatic mixing, or combination pres-
sure balance/thermostatic mixing type that is designed to control water temperature to reduce the risk of scalding.
Whirlpool Bathtub: A plumbing appliance consisting of a bathtub fixture that is equipped and fitted with a circu-
lation piping system, pump, and other appurtenances and is so designed to accept, circulate, and discharge bathtub
water upon each use. See Figure 1.2.83
Figure 1.2.83
A WHIRLPOOL BATH
NOTES:
1. Horizontal-to-vertical changes in direction are not as critical as other changes because gravity controls
the velocity in vertical drops.
2. No-hub cast iron fittings are shown. See Table 2.3.1 for fitting patterns for other drainage pipe materi-
als.
3. Short pattern fittings are permitted in piping for individual fixtures.
4. Long pattern fittings are not permitted to connect fixture trap arms to vertical and vent piping because
the vent opening at the end of the trap arm will be below the weir of the trap, causing the trap to self-
siphon.
Figure 2.3.1 - A
DRAINAGE FITTINGS FOR HORIZONTAL-TO-VERTICAL CHANGES IN DIRECTION
Figure 2.3.1 - B
DRAINAGE FITTINGS FOR HORIZONTAL-TO-HORIZONTAL
CHANGES IN DIRECTION
NOTES:
1. Long pattern fittings are required at the base or drainage stacks serving two or more fixtures. Short pat-
tern fittings are permitted for vertical-to-horizontal drains from individual fixtures.
2. No-hub cast iron fittings are shown. See Table 2.3.1 for fitting patterns for other drainage pipe materi-
als.
3. See Sections 11.11 and 12.15 for restrictions on branch drain connections near the base of stacks that
are subject to suds pressure.
Figure 2.3.1 - C
DRAINAGE FITTINGS FOR VERTICAL-TO-HORIZONTAL
CHANGES IN DIRECTION
Figure 2.3.1 - D
USE OF SHORT AND LONG PATTERN DRAINAGE FITTINGS
NOTES:
1. Double pattern fittings can be used in horizontal and vertical piping.
2. Long pattern fittings are not permitted to connect fixture trap arms to vertical drain and vent piping be-
cause the vent opening at the end of the trap arm will be below the weir of the trap, causing the trap to
self-siphon.
Figure 2.3.2
DOUBLE PATTERN DRAINAGE FITTINGS
Figure 2.3.3
PREVENTING CROSSFLOW BETWEEN BACK-TO-BACK BACK-OUTLET FIXTURES
Figure 2.4.2 - A
HORIZONTAL HEEL OR SIDE INLET VENT CONNECTION
Figure 2.4.2 - B
VERTICAL HEEL INLET VENT CONNECTION
Comment #1: This Section does not prohibit double hub fittings for soil pipe installations since they cre-
ate no more restriction to flow that would be encountered with a hubless coupling or similar fitting.
Comment #2: Failure to ream or deburr drainage piping constitutes an obstruction to flow.
NOTES:
1. The soil under the pipe must be stable. Unstable bedding may damage the pipe, fittings, or joints when
settlement occurs.
2. The side-fill should be shoveled under the pipe to make sure that there are no voids in the side-fill.
Figure 2.6.1 - A
UNDERGROUND PIPING BEDDED ON SOIL
Figure 2.6.1 - B
UNDERGROUND PIPING BEDDED ON SAND OR GRAVEL
2.6.2 Side-fill
The haunch areas adjacent to the pipe between the bottom of the pipe and its horizontal centerline shall be
filled with a clean coarse-grain material such as sand, gravel, or soil. Such side-fill shall be placed by hand,
extending to the sides of the trench, and be compacted to provide lateral support for the pipe. See Figure
2.6.1-A and 2.6.1-B
Figure 2.6.3
TYPICAL BACKFILLING PROCEDURE
2.6.5 Tunneling
When pipe is installed in a dug or bored earth tunnel, the space around the pipe between the pipe and the wall
of the tunnel shall be completely filled with packed concrete or grout. When pipe is installed in a jacked-in-
place conduit or sleeve, the space around the pipe between the pipe and the inside of the conduit or sleeve
shall be sealed in an approved manner in accordance with Section 2.12.d.
2.6.9 Supervision
Where excavation, bedding or backfilling are performed by persons other than the installer of the under-
ground piping, the pipe installer shall supervise the bedding, side-fill, and initial backfill, and shall be respon-
sible for its conformance to this Code.
Comment: When piping beneath paving or concrete floors is replaced by the trenchless method, there
must be sufficient distance above the pipe to prevent cracking the paving or floor slab when the pipe be-
ing replaced bursts.
2.7 SAFETY
Any part of a building or premise that is changed, altered, or required to be replaced as a result of the installation,
alteration, renovation, or replacement of a plumbing system, or any part thereof, shall be left in a safe, non-haz-
ardous condition.
2.9.2 Corrosion
Pipe subject to corrosion by passing through or under corrosive fill, such as, but not limited to, cinders, con-
crete, or other corrosive material, shall be protected against external corrosion by protective coating, wrap-
ping, or other means that will resist such corrosion.
Comment #2: Job site debris should not be allowed in the backfill for piping trenches. Material such as
metal cans, metal studs, and gypsum board may chemically react with some types of pipe.
2.9.4 Penetration
a. Plastic and copper piping run through framing members to within one inch of the edge of the framing
shall be protected by steel nail plates not less than 18 gauge. Where such piping penetrates top plates or sole
plates of the framing, the nail plate shall extend at least two inches below top plates and two inches above
sole plates.
b. Where plastic and copper piping runs through metal framing members, it shall be protected from abra-
sion caused by expansion and contraction of the piping or movement of the framing.
Comment: Where industrial wastes will be created, the facility should provide the following informa-
tion to the Authority Having Jurisdiction for the sewerage system: (1) the quantity of water and waste
material that will be discharged into the sewer system, (2) the industrial processes that create the waste,
(3) the composition and concentration of the chemicals in the waste, (4) the water supply demand for the
facility, and (5) the intended design of the pre-treatment or neutralizing system for the wastes prior to its
discharge into the sewer system.
2.12 SLEEVES
a. All piping passing through concrete walls, floors, slabs, and masonry walls shall be provided with
sleeves for protection.
NOTES:
1. The sleeve must be sealed where necessary to prevent the entrance of ground water into the building.
Figure 2.12
A PIPE SLEEVE THROUGH A FOUNDATION WALL
NOTES:
1. Refer to the adopting ordinance for this Plumbing Code to determine the minimum required cover for
water service and sewer piping.
2. Locating piping in exterior walls where freezing is possible should be avoided if possible. Thermal insu-
lation only retards the loss of heat, it does not prevent it.
3. Heat tracing may be required where piping is exposed outdoors or in unheated spaces.
Figure 2.16
DEPTH OF COVER FOR WATER SERVICE AND SEWER PIPING
NOTES:
1. Check the project design documents to verify that a 45 degree angle of repose is permissible.
2. Consult the project structural engineer if conditions dictate that excavations must be closer
than 45 degrees from the bottom edge of footings.
Figure 2.17
PROTECTING STRUCTURAL FOOTINGS FROM BEING UNDERMINED
NOTES:
1. Refer to the adopting ordinance for this Plumbing Code to determine the distance from which properties
must be connected to public water and sewer systems.
2. Connections to public water and sewer systems are more desirable than private systems, from the
standpoint of public health and convenience.
Figure 2.19.1
REQUIRED CONNECTION OF PROPERTIES TO PUBLIC WATER AND SEWER SYSTEMS
Comment: Plumbing in buildings connected to private water or sewage systems must comply with all
applicable requirements of this Code or the Authority Having Jurisdiction.
NOTES:
1. Reducing fixture drains for water closets from 4" to 3" is permissible.
Figure 2.22
WATER CLOSET DRAIN CONNECTIONS
Comment: Rough-ins for future fixtures are not considered dead ends if the piping is accessible and can
be cleared of any blockages when the future fixtures are installed.
Comment: The seating areas in restaurants, cafeterias, and other dining areas are not subject to the
requirements of Section 2.25.1.
NOTES:
1. The 3/4" extended sleeve prevents spillage on the floor above from leaking down into the food handling
area and contaminating the food products.
Figure 2.25 - A
A PIPE PENETRATION OF A FLOOR ABOVE A FOOD HANDLING AREA
Figure 2.25 - B
PLUMBING FIXTURES ABOVE A FOOD HANDLING AREA
Materials
3.1 MATERIALS
3.1.1 Minimum Standards
The standards cited in this chapter shall control all materials, systems, and equipment used in the construc-
tion, installation, alteration, repair, or replacement of plumbing or drainage systems or parts thereof.
EXCEPTIONS:
(1) The Authority Having Jurisdiction shall allow the extension, addition to or relocation of existing water,
soil, waste, drainage and vent pipes with materials of like grade or quality as permitted in Section 3.12.2.
(2) Materials not covered by the standards cited in this chapter may be used with the approval of the Au-
thority Having Jurisdiction as permitted in Section 3.12.2.
3.2.2 Lead
See Table 3.1.3. Sheet lead shall be not less than the following:
a. Shower pans—not less than 4 pounds per square foot (psf) and be coated with an asphalt paint or
equivalent.
b. Flashings of vent terminals—not less than 3 pounds per square foot (psf).
c. Lead bends and lead traps shall not be less than 1/8" wall thickness.
3.2.3 Plastic
a. Trap and tailpiece fittings— minimum 0.062" wall thickness.
b. Piping— see specific application — Sections 3.4 to 3.11.
c. Shower pans—approved plastic sheeting material.
Comment: Plastic shower pans should not be covered with asphalt unless recommended by the manu-
facturer.
Comment #1: The standards for plumbing fixtures that are listed in Table 3.1.3 reflect consensus agree-
ment between manufacturers, industry representatives, and consumer groups.
Comment #2: Slip resisting surfaces in bathtubs and showers do not constitute a violation of the re-
quirement for smooth surfaces.
Comment: The manufacturer's markings on plastic water service pipe must indicate that it is suitable
for 160 psig @ 73°F and complies with NSF 61.
Comment: Refer to the standards listed in Table 3.1.3 to determine the pressure and temperature ratings
of the various piping materials.
Comment: The limit of 8% lead is based on the EPA Safe Drinking Water Act. Generally, fixture fitting
castings do not exceed 7% lead.
3.5.6 Fittings
Fittings in drainage systems shall be compatible with the pipe used and shall have no ledges, shoulders, or
reductions that can retard or obstruct flow. Threaded fittings shall be the recessed drainage type.
3.6.4 Fittings
Fittings in vent piping shall be compatible with the pipe material used. Where threaded pipe is used, fittings
shall be either the drainage or pressure type, galvanized or black.
3.7.7 Fittings
Fittings in drainage systems shall be compatible with the pipe used and shall have no ledges, shoulders, or
reductions that can retard or obstruct flow. Threaded fittings shall be the recessed drainage type.
3.12.3 Tests
When there is insufficient evidence to verify claims for alternate materials, the Authority Having Jurisdic-
tion may require tests of compliance as proof of suitability. Such tests shall be made by an approved testing
agency at the expense of the applicant.
V. PLUMBING FIXTURES
1 Bath Units, Plastic: ANSI Z124.1.2-2005,
CSA B45.5-2002 (2008).
2 Ceramic Plumbing Fixtures, Non-Vitreous: ASME A112.19.9M-1991
(2008),
CSA B45.1-2002 (2008).
3 Drains for Prefabricated and Precast Showers ASME A112.18.2-2005,
CSA B125.2-2005.
4 Drinking Fountains and Water Coolers, Self Contained, ARI 1010-2002,
Mechanically Refrigerated: UL 399 Edition 6-1993
(2006).
5 Enameled Cast Iron Plumbing Fixtures: ASME A112.19.1M-1994
(2004),
CSA B45.2-2002 (2008).
6 Enameled Steel Plumbing Fixtures: ASME A112.19.4M-1994
(2004),
CSA B45.3-2002 (2008).
7 Floor and Trench Drains: ASME A112.6.3-2001 (2007).
8 Lavatories, Plastic: ANSI Z124.3-2005,
CSA B45.5-2002 (2008).
9 Roof, Deck, and Balcony Drains: ASME A112.6.4-2003 (2008).
10 Plastic Bathtub and Shower Units: ANSI Z124.1.2-2005,
CSA B45.5-2002 (2008).
11 Stainless Steel Plumbing Fixtures (residential design): ASME A112.19.3-2001
(2004),
CSA B45.4-2002 (2008).
6 Copper Tube, seamless, Type M A A A ASTM B88 ASME B16.22 (wrought, solder joint)
ASME B16.18 (cast, solder joint)
ASME B16.50 (wrought, braze joint)
ASME B16.24 (cast, flanged)
ASSE 1061 (push-fit)
ASME B16.26 (cast, flared)
Mechanically crimped (pressed) per Section 4.2.6
Split couplings per Section 4.2.17
7 CPVC Plastic Pipe, schedule 40 A A A ASTM F441 ASTM F438 (socket)
8 CPVC Plastic Pipe, schedule 80 A A A ASTM F441 ASTM F437 (threaded), ASTM F439 (threaded, socket)
9 CPVC Plastic Pipe, SDR A A A ASTM F442 ASTM F438 (sched 40 socket), ASTM F439 (sched 80 socket)
10 CPVC Plastic Hot and Cold Water Distribution A A A ASTM D2846 ASTM D2846 (socket, metal transition), ASSE 1061 (push-fit)
(SDR 11) CTS
11 Ductile Iron Pipe, cement-motar lined A X X ASTM A377 AWWA C110/A21.10, AWWA C153/A21.53 (compact)
AWWA C151/A21.50 AWWA C606 (split couplings)
12 Fiberglass Pressure Pipe A X X ASTM D3517, ASTM D3517, AWWA C950
AWWA C950
12a Flexible Pre-Insulated Piping A A A ASTM F2165
13 Galvanized Steel Pipe and Fittings X A A ASTM A53 ASME B16.3 (malleable, threaded)
ASME B16.4 (gray iron, threaded)
ASME B16.5 (cast, forged, flanged)
Split couplings per Section 4.2.17
105
106
Table 3.4 MATERIALS FOR POTABLE WATER (continued)
30 Crosslinked Polyethylene (PEX) Pressure Pipe A X X AWWA C904 ASTM F1960 (metal cold expansion insert)
for Water Service ASTM F2080 (metal cold expansion compression)
ASTM F1807 (crimped metal insert)
31 PE-AL-PE Composite Pressure Pipe A X X AWWA C903 AWWA C800 (metal insert)
32 PEX-AL-PEX Crosslinked Pressure Pipe A X X AWWA C903 AWWA C800 (metal insert)
33 Polyethylene of Raised Temperature (PE-RT) A X X ASTM F2623 ASTM D3261 (butt heat fusion), ASTM D2683 (socket fusion)
SDR 9 Tubing ASTM F1055 (electro-fusion)
Approved A A A
Disapproved X X X
Table 3.4.3
PLASTIC HOT AND COLD WATER DISTRIBUTION PIPING (1)
(water pressure rated for not less than 100 psi at 180 deg F and 160 psi at 73 deg F)
MATERIAL COMPOSITION DIMENSIONS JOINTS PIPE SIZES
CPVC (ASTM D2846) CPVC 4120 SDR 11 not threaded all sizes
CPVC (ASTM F441) CPVC 4120 Schedule 40 not threaded up through 1”
Schedule 80 threaded up through 1/2”
Schedule 80 not threaded up through 2-1/2”
CPVC (ASTM F442) CPVC 4120 SDR 11 not threaded all sizes
PEX (ASTM F876) PEX 1006 SDR 9 not threaded all sizes
PEX 1008
PEX (ASTM F877) PEX 1006 SDR 9 not threaded all sizes
PEX 1008
PE-AL-PE (ASTM F1282) PE-AL-PE ASTM F1282 not threaded all sizes
PEX-AL-PEX (ASTM F2262) PEX-AL-PEX SDR 9 not threaded all sizes
PEX-AL-PEX (ASTM F1281) PEX-AL-PEX ASTM F1281 not threaded all sizes
Composite Pipe (ASTM F1335) PE-AL-PE ASTM F1335 compression all sizes
Composite Pipe (ASTM F1335) PEX-AL-PEX ASTM F1335 compression all sizes
111
112
Table 3.7 MATERIALS FOR STORM DRAINAGE (1)
ABOVE GROUND WITHIN BUILDINGS
UNDERGROUND WITHIN BUILDINGS PIPE FITTINGS
SEWERS OUTSIDE OF BUILDINGS
1 ABS Plastic Pipe and Fittings A A A ASTM D2661 (DWV, sched 40 IPS) ASTM D2661 (socket, threaded)
2 ABS Cellular Core Plastic Pipe A A A ASTM F628 (DWV, sched 40 IPS) ASTM F628, ASTM D2661 (socket, threaded)
3 ABS Sewer Pipe and Fittings A X X ASTM D2751 (2) (3) ASTM D2751 (socket) (2) (3)
4 ABS and PVC Composite Sewer Pipe A X X ASTM D2680 ASTM D2680 (socket), PVC (gasket)
5 Cast Iron Soil Pipe and Fittings (bell & spigot) A A A ASTM 74 ASTM A74
6 Cast Iron Soil Pipe and Fittings (no-hub) A A A CISPI 301, ASTM A888 CISPI 301, ASTM A888
7 Concrete Sewer Pipe, Non-reinforced A X X ASTM C14 ASTM C14
8 Concrete Sewer Pipe, Reinforced A X X ASTM C76 ASTM C76
9 Copper Drainage Tube, DWV A A A ASTM B306 ASME B16.23 (cast copper solder joint)
10 Copper Water Tube, K, L, M A A A ASTM B88 ASME B16.23 (cast copper solder joint)
11 Fiberglass Sewer Pipe A X X ASTM D3754 ASME D3840
12 Galvanized Steel Pipe X X A ASTM A53 ASME B16.12 (cast iron drainage)
13 PE Plastic Pipe, SDR-PR A X X ASTM F714 (6)
14 PVC Plastic Pipe and Fittings, DWV A A A ASTM D2665 ASTM D2665 (socket), ASTM F1866 (socket)
15 PVC Sewer and Drain Pipe (cellular core) A X X ASTM F891 ASTM D2665 (socket), ASTM F1866 (socket)
16 PVC Sewer and Drain Pipe (cellular core) (4) A A X ASTM F891 (4) ASTM D2665 (socket), ASTM F1866 (socket)
17 PVC IPS Schedule 40 (cellular core) A A A ASTM F891 ASTM D2665 (socket), ASTM F1866 (socket)
18 PVC Plastic Sewer Pipe (PSM) and Fittings A X X ASTM D3034 ASTM D3034
19 Stainless Steel DWV Systems - Type 316L (5) A A A ASTM A112.3.1 ASTM A112.3.1
20 Stainless Steel DWV Systems - Type 304 (5) X X A ASTM A112.3.1 ASTM A112.3.1
21 Vitrified Clay Pipe, Standard Strength A X X ASTM C700 ASTM C700
22 Vitrified Clay Pipe, Extra Strength A A X ASTM C700 ASTM C700
23 PVC Plastic Pipe and Fittings, DWV, 3.25” OD X A A ASTM D2949 ASTM D2949
Approved A A A
Not Approved X X X
Comment: Perforated and open-joint piping is also used for the piping in absorption trenches for private
sewage disposal systems. See Section 16.9.5.
Comment: For industry standards for the various joining methods, refer to Table 3.1.3 - Part IV Pipe
Joints, Joining Materials, Couplings, Gaskets.
Figure 4.2.1.1
A LEAD CAULKED JOINT IN CAST IRON SOIL PIPE
Figure 4.2.1.2
A LEAD CAULKED JOINT IN IRON WATER PIPE
Figure 4.2.2
A THREADED PIPE JOINT
4.2.3 Wiped
Joints in lead pipe or fittings, or between lead pipe or fittings and brass or copper pipe, ferrules, solder
nipples, or traps, shall be full wiped joints. Wiped joints shall have an exposed surface on each side of a joint
not less than 3/4 inch and at least as thick as the material being jointed. Wall or floor flange lead-wiped joints
shall be made by using a lead ring or flange placed behind the joints at wall or floor. Joints between lead pipe
and cast-iron, steel, or wrought iron shall be made by means of a caulking ferrule, soldering nipple, or bush-
ing. See Figure 4.2.3
Figure 4.2.3
A WIPED JOINT ON LEAD PIPE
4.2.4 Soldered
a. Soldered joints in copper water piping shall be made using wrought pressure fittings complying with
ASME B16.22, cast pressure fittings complying with ASME B16.18, or cast copper alloy flanges complying
with ASME B16.24.
NOTE: Short-cup brazing fittings complying with ASME B16.50 and bearing the mark “BZ” shall not be
used where joints are soldered.
b. Soldered joints in copper drain and vent piping shall be made with wrought drainage fittings complying
with ASME B16.29 or cast drainage fittings complying with ASME B16.23.
c. Soldered joints shall be made in accordance with ASTM B828.
d. Solder shall comply with ASTM B32. Flux shall comply with ASTM B813.
e. Solder for joints in potable water piping shall contain not more than 0.2% lead. See Figure 4.2.4
Figure 4.2.4
A SOLDERED JOINT
4.2.5 Flared
Flared joints for copper water tube shall be made with fittings complying with ASME B16.26. The tube shall
be reamed and then expanded with an approved flaring tool. See Figure 4.2.5
NOTES:
1. A long flare nut is shown. Short flare nuts are permissible where vibration is not a factor.
Figure 4.2.5
A FLARED COPPER JOINT
4.2.8 Brazed
4.2.8.1 General
a. Brazed joints in copper tubing shall be made in accordance with accepted industry practice. See Ap-
pendix L for an accepted practice for general plumbing.
b. Brazed joints in medical gas and vacuum piping shall be made in accordance with NFPA 99 or NFPA
99C.
4.2.8.2 Fittings
a. Fittings in copper tubing with brazed joints shall be wrought solder joint fittings complying with ASME
B16.22 or short-cup brazing fittings complying with ASME B16.50. Short-cup brazed joint fittings shall
be clearly marked by the manufacturer to differentiate them from solder-joint fittings and avoid their being
used in piping with soldered joints.
b. Fittings for medical gas and vacuum piping shall be as required by NFPA 99 or NFPA 99C.
Comment: The added welding material must be of the same composition as the lead pipe being joined.
Figure 4.2.11.2-A
A SHIELDED COUPLING ON HUBLESS CAST IRON SOIL PIPE
Figure 4.2.11.3
A MECHANICAL JOINT ON IRON WATER PIPE
Figure 4.2.11.5
A JOINT IN BELL AND SPIGOT CONCRETE PIPE
4.2.12 Reserved
4.2.13 Reserved
Figure 4.2.14-A
A SOLVENT CEMENT JOINT IN PLASTIC DWV OR WATER PIPING
Figure 4.2.14-C
A SHIELDED COUPLING ON PLASTIC DWV PIPING
Figure 4.2.14-D
A SOLVENT CEMENT JOINT IN SOCKET (BELL) END PLASTIC PRESSURE PIPE
Figure 4.2.14-E
AN INSERT FITTING JOINT IN PLASTIC TUBING
Figure 4.2.14-F
A HEAT FUSED JOINT IN PLASTIC WATER PIPING
4.2.15 Slip
Slip joints using washers or approved packing or gasket material, when installed in concealed locations,
shall be provided with an access panel. Slip joints using approved ground joint brass compression rings that
allow adjustment of tubing but provide a rigid joint when made up, shall not be considered as slip joints that
require access. See Figures 4.2.15-A and-B
Figure 4.2.15-A
A SLIP JOINT IN DRAIN TUBING
NOTES:
1. When a compression joint does not permit free movement when assembled, it is not considered to be a
slip joint and does not need to be accessible. Refer to the definition of "accessible".
Figure 4.2.15-B
A COMPRESSION JOINT IN DRAIN TUBING
Comment: Expansion joints must to be accessible for adjustment or replacement. Refer to the definition
of "accessible".
Figure 4.2.16-A
AN EXPANSION JOINT FOR PLASTIC DWV PIPING
Figure 4.2.16-B
A MECHANICAL EXPANSION JOINT IN PRESSURE PIPING
Figure 4.2.17
A GROOVED PIPE JOINT
4.2.19 Bending
Changes in direction in copper water tube shall be permitted to be made by the use of factory or field bends.
Field bends shall be made in accordance with Table 4.2.19. Bends shall be made only with bending equipment
and procedures intended for that purpose. Hard drawn tubing shall not be bent with tubing benders intended
for only annealed (soft) tube. All bends shall be smooth and free from buckling, cracks, and other evidence of
mechanical damage.
NOTES:
1. The rubber rings must be sized to adapt to the different outside diameters (O.D.) of the different piping
materials being joined.
2. There are hundreds of different adapters available for joining different materials, different pipe sizes, and
different wall thickness, as well as clay pipe from different manufacturers.
Figure 4.3.1-A
A RUBBER RING TRANSITION JOINT TO VITRIFIED CLAY PIPE
Figure 4.3.1.B
AN EXTERNALLY CLAMPED TRANSITION COUPLING JOINT
TO VITRIFIED CLAY PIPE
4.3.2 Reserved
4.3.3 Reserved
Figure 4.3.4
A THREADED PIPE TO CAST IRON ADAPTER FITTING
Figure 4.3.6
A CAULKING FERRULE FOR CAST IRON TO SWEAT COPPER TRANSITION
Figure 4.3.7-B
DIELECTRIC UNION, FLANGE, AND WATERWAY FITTING
NOTES:
1. Shielded couplings can be used aboveground and underground. They can partially support the pipe.
Center stops are required except for repair couplings.
Figure 4.3.8-A
A SHIELDED COUPLING ON DRAINAGE PIPING
Figure 4.3.8-B
A RIGID UNSHIELDED COUPLING ON DRAINAGE PIPING
Figure 4.3.8-C
A TRANSITION CONNECTION USING A SHIELDED COUPLING
Figure 4.3.8-D
A TRANSITION CONNECTION USING A FLEXIBLE UNSHIELDED COUPLING
NOTES:
1. Plastic pipe that is lead caulked must be solid plastic. Molten lead will melt cellular core plastic pipe.
Figure 4.3.9-B
A LEAD CAULKED JOINT FOR PLASTIC DWV TO CAST IRON HUB
NOTES:
1. Plastic fittings that are lead caulked must be solid plastic. Molten lead will melt cellular core pipe fittings.
Figure 4.3.9-D
A LEAD CAULKED PLASTIC SOCKET JOINT TO CAST IRON PIPE
NOTES:
1. Vertical distances greater than 24" may induce self-siphoning of the trap seal due to the momentum of
the drainage flow.
Figure 5.1 - A
THE VERTICAL DISTANCE FROM A FIXTURE OUTLET TO ITS TRAP WEIR
NOTES:
1. Refer to the definitions of "Continuous Waste" and "Combination Fixture".
Figure 5.1 - C
A CONTINUOUS WASTE WITH END OUTLET
NOTES:
1. Refer to the definitions of "Continuous Waste" and "Combination Fixture".
Figure 5.1 - D
A CONTINUOUS WASTE WITH CENTER OUTLET
Comment: A drain pipe that is smaller than the trap to which it is connected could create an obstruction
to flow through the trap.
Table 5.2
MINIMUM SIZE OF NON-INTEGRAL TRAPS
Plumbing Fixture Trap Size in inches
Bathtub (with or without overhead shower) 1-1/2
Bidet 1-1/4
Clothes washing machine standpipe 2
Combination sink and wash (laundry) sink with food waste grinder unit 1-1/2 (1)
Combination kitchen sink, domestic dishwasher, and food waste grinder 1-1/2
Dental unit or cuspidor 1-1/4
Dental lavatory 1-1/4
Drinking fountain 1-1/4
Dishwasher, commercial 2
Dishwasher, domestic (non-integral trap) 1-1/2
Floor drain 2
Food waste grinder, commercial use 2
Food waste grinder, domestic use 1-1/2
Kitchen sink, domestic, with food waste grinder unit 1-1/2
Kitchen sink, domestic 1-1/2
Lavatory, common (private and public) 1-1/4
Lavatory (barber shop, beauty parlor or surgeon’s) 1-1/2
Lavatory, multiple type (wash fountain or wash sink) 1-1/2
Laundry tray (1 or 2 compartments) 1-1/2
Shower stall or shower drain (single shower head) 1-1/2
Shower stall or shower drain (multiple shower heads) 2
Sink (surgeon’s) 1-1/2
Sink (flushing rim type, flush valve supplied) 3
Sink (service type with floor outlet trap standard) 3
Sink (service type with P trap) 2
Sink, commercial (pot, scullery, or similar type) 2
Sink, commercial (with food grinder unit) 2
NOTES:
1. Access is not mandatory for traps with solid connections.
Figure 5.3.1 - A
A FIXTURE TRAP WITH SOLID CONNECTIONS
NOTES:
1. Slip joints must be accessible
Figure 5.3.1 - B
A FIXTURE TRAP WITH SLIP JOINTS
Figure 5.3.1 - C
A FIXTURE TRAP WITH THREE DIFFERENT TYPES OF JOINTS
NOTES:
1. The minimum trap seal depth of 2" is based on the design criteria for the vent piping. Trap seals deeper
than 4" will tend to trap solids and create a breeding ground for bacteria.
Figure 5.3.2
TRAP SEAL DEPTH
Figure 5.3.3
TRAPS MUST BE LEVEL AND PROTECTED FROM FREEZING
Figure 5.4.1
CLEANOUT SPACING ON HORIZONTAL DRAIN LINES
NOTES:
1. Cleanouts must have flush top covers if located in a walkway or other paved area.
2. The length of the vertical extension to grade must be included in the developed length between clea-
nouts.
Figure 5.4.2
A SEWER CLEANOUT EXTENDED TO FINISHED GRADE
Figure 5.4.3
WHERE CLEANOUTS ARE REQUIRED AT CHANGES IN DIRECTION
Figure 5.4.4
ACCESS TO CONCEALED CLEANOUTS
NOTES:
1. The extension of a cleanout for access in not considered to be a dead end.
Figure 5.4.5 - B
A CLEANOUT EXTENDED TO OUTSIDE OF THE BUILDING FOR ACCESS
Figure 5.4.5 - C
A CLEANOUT NEAR THE BASE OF A RAIN LEADER
5.4.6 Building Drain and Building Sewer Junctions and the Property Line
a. There shall be a cleanout near the junction of a building drain and building sewer either inside or outside
the building wall.
b. Cleanouts shall be placed in the building sanitary sewer and the building storm sewer at the property
line and brought to the surface in accordance with the requirements of the Adopting Agency.
See Figures 5.4.6 - A and - B
Figure 5.4.6 - A
A CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER
Figure 5.4.6 - B
A CLEANOUT AT THE PROPERTY LINE
NOTES:
1. Cleanouts must have flush top covers if located in a walkway or other paved area.
Figure 5.4.7
THE FLOW DIRECTION OF CLEANOUTS
Figure 5.4.10
LOCATION AND SPACING OF MANHOLES
NOTES:
1. Minimum clearance "X" is 12" if pipe size "D" = 2" or less
2. Minimum clearance "X" is 18" if pipe size "D" = 3" or more
Figure 5.4.11 - A
CLEANOUT CLEARANCE ABOVE THE BASE OF A STACK
NOTES:
1. Minimum clearance "X" is 12" if pipe size "D" = 2" or less
2. Minimum clearance "X" is 18" if pipe size "D" = 3" or more
Figure 5.4.11 - B
CLEANOUT CLEARANCE AT THE BASE OF A STACK
Figure 5.4.13 - A
A WATER CLOSET AS A CLEANOUT EQUIVALENT
Figure 5.4.13 - B
A REMOVABLE TRAP AS A CLEANOUT EQUIVALENT
Figure 5.5.1
BACKWATER VALVES
NOTES:
1. MH = Manhole
2. BWV = Backwater Valve
3. Vent piping not shown
Figure 6.1.1
DIFFERENT TYPES OF INTERCEPTORS
6.1.2 Design
The size and type of liquid waste treatment equipment shall be based on the maximum volume and rate of
discharge of the plumbing fixtures and equipment being drained.
6.1.4.2 Grease Interceptors and Grease Removal (or Recovery) Devices (GRD)
Grease interceptors rated for up to 100 gallons per minute shall be certified according to PDI Standard
G101 or ASME A112.14.3. Grease removal (or recovery) devices rated for up to 100 gallons per
minute shall be certified according to ASME A112.14.4.
6.1.5 Venting
Liquid waste treatment equipment shall be so designed that they will not become air-bound if tight covers are
used. Equipment shall be properly vented if loss of its trap seal is possible.
6.1.6 Accessibility
a. Liquid waste treatment equipment shall be so installed that it is accessible for the removal of covers and
the performance of necessary cleaning, servicing and maintenance.
b. The need to use ladders or move bulky objects in order to service interceptors and other liquid waste
treatment equipment shall constitute a violation of accessibility.
6.2.1 General
a. Grease interceptors shall comply with the requirements of the Adopting Agency.
b. Grease interceptors include the following types:
1. Type I Hydro-mechanical interceptors
2. Grease removal (or recovery) devices (GRD)
3. Type II Gravity interceptors
c. Grease interceptors shall be provided to receive the waste discharges from fixtures in food handling areas
that introduce grease into the sanitary drainage system. Fixtures include, but are not limited to pot washing sinks,
utensil soak sinks, pre-rinse sinks at dishwashers, dishwashers, wok range stations, drains from wash-down
ventilation hoods, can washing drains, mop sinks, floor drains and floor sinks in areas around grease producing
fixtures, and similar fixtures.
d. Water closets, urinals, and other fixtures that discharge human waste shall not discharge through a grease
interceptor.
e. Handwashing sinks, lavatories, salad prep sinks, ice machine drains, and other non-grease waste drainages
shall be permitted to discharge through a grease interceptor along with grease producing fixtures.
NOTES:
1. Flow control devices are necessary to prevent the waste flow from exceeding the design flow rating of
the grease interceptor.
2. When the fixtures connected to the grease interceptor have traps, the air intake on the flow control
device must be connected to the fixture vent piping system.
3. Air intake through the flow control device aerates the grease-laden waste, which is essential to the
separation process.
Figure 6.2-A
A GREASE INTERCEPTOR SERVING A TRAPPED AND VENTED FIXTURE
Figure 6.2-B
A GREASE INTERCEPTOR SERVING AS A FIXTURE TRAP
Figure 6.2.5
A FOOD WASTE GRINDER WITH SOLIDS SEPARATOR AND GREASE INTERCEPTOR
6.2.7 Location
Hydro-mechanical and GRD interceptors shall be permitted to be installed within buildings unless otherwise
prohibited by the Adopting Agency. Where gravity grease interceptors or holding tanks are remote from the
fixtures served, the drain piping between the fixtures and the interceptor or holding tank shall be as direct as
possible and shall include provisions for periodic cleaning.
Table 6.2.10
FIXTURE DRAINAGE FLOW RATES FOR SIZING
HYDRO-MECHANICAL AND GRD GREASE INTERCEPTORS
FIXTURE FLOW
1-1/4” Sink Drain Outlet (each) 7.5 GPM
1-1/2” Sink Drain Outlet (each) 15 GPM
2” Sink Drain Outlet (each) 22.5 GPM
Floor Drain without Indirect Waste 0 GPM
Floor Drain or Floor Sink with Indirect Waste (1)
Commercial Dishwasher (2)
Figure 6.4.2 - A
A SAND INTERCEPTOR SERVING AN OIL SEPARATOR
NOTES:
1. Where a stand-alone sand interceptor is installed, it must include a 6" trap seal depth to block the flow
of sewer gas from the building sewer into the building.
Figure 6.4.2 - B
A STAND-ALONE SAND INTERCEPTOR
7.3 INSTALLATION
7.3.1 General
Plumbing fixtures, fixture trim, and plumbing appliances shall be installed in accordance with the require-
ments of this Code and the manufacturer's instructions and recommendations.
NOTES:
1. Wall hung water closets are designed to be supported by carriers.
2. For fixtures other than water closets, such as lavatories and urinals, the carrier may be either floor or
wall supported, depending on the strength of the wall.
Figure 7.3.5
A CARRIER FOR A WALL HUNG WATER CLOSET
Comment: Access to concealed slip joints and cleanouts can require the use of tools.
NOTES:
1. Openings or gaps between fixtures and walls or floors can collect dirt and moisture. They are unsani-
tary and can cause water damage to the building structure. These openings must be caulked or other-
wise sealed.
Figure 7.3.8
SEALING FIXTURES TO WALLS AND FLOORS
NOTES:
1. See Figure 7.4.4 - A for bowl heights for children's use.
2. See Figure 7.4.4 - B for bowl heights for adult accessible use.
Figure 7.4.3 - A
AN ADULT-HEIGHT ELONGATED WATER CLOSET BOWL
COMPARED TO A ROUND BOWL
NOTES:
1. Seats for water closets must fit the water closet bowl. Section 7.4.5 requires elongated seats on elon-
gated bowls and round seats on round bowls.
Figure 7.4.3 - B
AN OPEN FRONT ELONGATED WATER CLOSET SEAT (LESS LID)
Figure 7.4.4 - A
PERMITTED HEIGHTS OF WATER CLOSET BOWLS FOR CHILDREN'S USE
Figure 7.4.4 - B
PERMITTED HEIGHT OF WATER CLOSET BOWLS FOR ADULT ACCESSIBLE USE
7.5 URINALS
7.5.1 Compliance
a. Water-fed vitreous china urinals shall comply with ASME A112.19.2.
b. Non-water vitreous china urinals shall comply with ASME A112.19.19.
c. Water-fed and waterless plastic urinals shall comply with ANSI Z124.9.
d. Waterless (non-water) urinals shall have a liquid trap seal as required by Section 5.3.2, ASME
A112.19.19, and ANSI Z124.9.
e. Water-fed urinals with a concealed trap seal and/or an outlet strainer shall be supplied by an automatic
flushing device.
7.6 LAVATORIES
7.6.1 Compliance
a. Lavatories shall comply with the following standards:
1. Ceramic, non-vitreous; ASME A112.19.9M
2. Enameled cast-iron; ASME A112.19.1M
3. Enameled steel; ASME A112.19.4M
4. Plastic; ANSI Z124.3
5. Stainless steel; ASME A112.19.3M
6. Vitreous china; ASME A112. 19.2M
Comment: Overflows are not provided in all lavatories. Lavatories with overflows are not used in hospi-
tals because of the potentially unsanitary condition caused by inaccessible surfaces exposed to waste.
Figure 7.6.4
A LAVATORY OVERFLOW
7.7 BIDETS
7.7.1 Compliance
Vitreous china bidets shall comply with ASME A112.19.2M. Bidet faucets shall comply to ASME A112.18.1/
CSA B125.1.
7.8 BATHTUBS
7.8.1 Compliance
a. Bathtubs shall comply with the following standards:
1. Plastic, cultured marble and other synthetic products or finishes; ANSI Z124.1
2. Enameled cast-iron; ASME A112.19.1
3. Enameled steel; ASME A112.19.4
4. Bathtubs with pressure sealed doors; ASME A112.19.15
7.9.2 Compliance
Whirlpool bathtubs shall comply with ASME A112.19.7M.
7.9.3 Drainage
The arrangements of circulating piping and pumps shall not be altered in any way that would prevent the
pump and associated piping from draining after each use of the fixture.
7.9.4 Access
One or more removable panels shall be provided where required for access to pumps, heaters, and controls,
as recommended by the fixture manufacturer. See Figure 7.9.4
Figure 7.9.4
ACCESS REQUIREMENTS FOR A WHIRLPOOL BATH
7.10 SHOWERS
7.10.1 Compliance
Plastic shower receptors and stalls shall comply with ANSI Z124.2.
Figure 7.10.6
A SHOWER PAN AND DRAIN
Figure 7.10.7
A SHOWER HEAD SUPPLY RISER PIPE
7.11 SINKS
7.11.1 Compliance
a. Sinks shall comply with the following standards:
1. Enameled cast-iron; ASME A112.19.1M
2. Enameled steel; ASME A112.19.4M
3. Stainless steel; ASME A112.19.3M
4. Plastic; ANSI Z124.6.
7.13.1 Compliance
Automatic clothes washers shall comply with AHAM HLW-2PR or ASSE 1007, and shall have an air gap
incorporated in the internal tub fill line.
Comment: Automatic clothes washers that comply with the referenced appliance standards include an
internal air gap in the water fill line and do not require the installation of an external backflow preven-
tion device.
7.14.1 Compliance
Domestic food-waste-grinder units shall comply with UL 430 and either AHAM FWD-1 or ASSE 1008.
Figure 7.14.3
A COMMERCIAL FOOD WASTE GRINDER INSTALLATION
Figure 7.15.4
A COMMERCIAL DISHWASHING MACHINE
7.16.1 Compliance
Floor and trench drains shall comply with ASME A112.6.3 or ASME A112.3.1.
Figure 7.16.2 - A
A FLOOR DRAIN TRAP AND STRAINER
Figure 7.16.2 - B
A DEEP SEAL TRAP
Figure 7.16.2 - C
A FLOOR DRAIN WITH TRAP PRIMER
7.18.2 Approval
Special installations requiring water supply and/or drainage shall be submitted to the Authority Having Juris-
diction for approval.
Figure 7.19.3
FLUSH VALVES FOR WATER CLOSET FLUSH TANKS
Figure 7.19.5
FLUSHOMETER VALVE INSTALLATIONS
192
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES - Page 1
No. Classifica- Description No. Of Persons of Water Closets Lavatories Drinking Bath or Other
tion Each Sex (Urinals) Water Shower
Facilities
Male Female Male Female
1 - 50 1 1 1 1
1 Assembly a) Theatres and other buildings for the performing arts and 1 per 1 service sink
motion pictures usually with fixed seats 51 - 100 add 1 add 1 add 0 add 1 1000 people per floor
101 - 200 add 1 add 2 add 1 add 1
201 - 300 add 1 add 1 add 0 add 1
See Notes: 4, 6, 9, 12, 16
ea. add’l. 300
add 1 add 2 add 1 add 2
over 300
1 - 25 1 1 1 2
b) Dance halls, nightclubs and for similar purposes. 1 per 1 service sink
26 - 50 add 1 add 1 add 1 add 1 200 per floor
people
51 - 100 add 1 add 2 add 1 add 0
See Notes: 2, 3, 4, 6, 9, 12, 13, 16 ea. add’l. 200
add 1 add 2 add 1 add 2
over 100
1 - 50 1 1 1 1
c) Auditoriums without permanent seating, art galleries, 1 per 1 service sink
exhibition halls, museums, lecture halls, libraries, restaurants 51 - 100 add 1 add 1 add 0 add 1 1000 people per floor
other than nightclubs, food courts.
101 - 200 add 1 add 2 add 1 add 1
d) Places of worship and other religious services. 201 - 300 add 1 add 1 add 0 add 1
Churches without assembly halls.
ea. add’l. 300
See Notes 4, 6, 9, 12, 16 add 1 add 2 add 1 add 2
over 300
1 - 100 2 2 1 2
e) Arenas, convention halls, outdoor assembly 1 per 1 service sink
including grandstands, bleachers, coliseums, 101 - 200 add 2 add 3 add 1 add 2 1000 people per floor
stadiums, amusement park structures, fair and
201 - 400 add 2 add 5 add 0 add 1
carnival structures, passenger terminals.
ea. add’l. 200
add 1 add 2 add 2 add 2
See Notes: 2, 3, 4, 6, 9, 12, 13, 16 up to 2,600
ea. add’l. 300
add 1 add 2 add 2 add 2
over 2,600
1 - 40 1 2 1 2
f) Recreational facilities: includes health spas, golf 1 per 1 shower per 1 service sink
courses, public swimming pools and similar uses. 75 15 people per floor
people over 150
ea. add’l. 40
See Notes: 2, 3, 4, 6, 9, 12, 16, 20 add 1 add 2 add 1 add 2 add 1 per 30
over 40
people
No. Classification Description No. Of Persons of Water Closet Drinking Bath or Other
Lavatories
Each Sex (Urinals) Water Shower
Facilities
Male Female Male Female
1 - 15 1 1 1 1 1 per 1 service sink
2 Business Buildings for the transaction of business, professional services,
100 people per floor
other services involving merchandise, office buildings, banks, 16 - 40 add 1 add 1 add 0 add 1
light industrial and similar uses.
41 - 75 add 1 add 1 add 1 add 1
See Notes: 2, 4, 6, 7, 12, 15, 16 ea. add’l. 60 over 75 add 1 add 2 add 1 add 2
1 - 15 1 1 1 1 1 per 1 service sink
3 Education a) Educational facilities: Preschool, Day Care, Kindergarten
100 people per floor
16 - 30 add 1 add 1 add 1 add 1
See Notes: 4, 6, 9, 16 ea. add’l. 50 over 100 add 1 add 1 add 1 add 2
See Notes: 4, 6, 9, 16, 17 ea. add’l. 60 over 120 add 1 add 2 add 1 add 2
193
Table 7.21.1
194
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES - Page 3
No. Classification Description No. Of Persons of Water Closets Lavatories Drinking Bath or Other
Each Sex (Urinals) Water Shower
Facilities
Male Female Male Female
5 Institutional Six or more individuals in a supervised environment, 1 - 8 patients 1 1 1/2 of required 1 per 1 per 1 service
group homes, alcohol and drug centers, convalescent water closets 100 20 people sink per floor
facilities, hospital wards. people
ea. add’l. 8 over 8 add 1 add 1
See Notes: 4, 16
a) Buildings, with six or more individuals, used for 1 water closet per 1 per patient room 1 per patient 1 service sink
medical, surgical, psychiatric, nursing or custodial care. patient room room per floor
Buildings, with six or more persons under some restraint 1 per cell or 1 per 4 1 per cell or 1 per 6 1 service sink
or security: inmates 1 per 4 inmates inmates per floor
a) Detention centers (short term).
b) Prisons, jails and reformatories (long term). 1 per cell or 1 per 8 1 per cell or 1 per 15 1 service sink
inmates 1 per 8 inmates inmates per floor
See Notes: 4, 14, 16
1 – 50 1 1 1 1
6 Mercantile 1 per 1 service sink
Buildings occupied for display and sales purposes. Retail
51 – 150 add 1 add 1 add 0 add 1 1000 people per floor
stores, service stations, shops, salesrooms, markets and
shopping centers. 151 – 300 add 0 add 1 add 0 add 2
ea. add’l. 300
See Notes: 2, 4, 6, 7, 12, 15, 16 add 1 add 2 add 1 add 2
over 300
No. Classification Description No. Of Persons Water Closets Drinking Bath or Other
Lavatories
of Each Sex (Urinals) Water Shower
Facilities
Male Female Male Female
7 Residential a) Hotels, motels. 1 water closet per 1 per guest room 1 per guest 1 service sink
guest room room per floor
d) One and two-family dwellings, 1 water closet per 1 per unit 1 per unit 1 kitchen sink
Detached one and two-family dwellings unit
8 Storage a) Structures for the storage of goods, warehouses, store- 1 water closet per 1 per unit 1 service sink
houses and freight deposits. Moderated hazard. units per unit
9 Utility and Accessory buildings: Barns, carports, stables, sheds, No fixtures are
Miscellaneous greenhouses. required
195
Notes for Table 7.21.1:
196
1. Plumbing fixtures shall be provided in numbers not less than those shown in this table for the type of building occupancy. For accessible re-
quirements, see local, state, or national codes. Additional fixtures may be required where environmental conditions or special activities may be
encountered.
2. Drinking fountains are not required in restaurants or other food service establishments if drinking water service is available. Drinking water is
not required for customers where normal occupancy is short term. A kitchen or bar sink may be used for employee water drinking facilities.
3. In food preparation areas, fixture requirements may be dictated by local Health Codes.
4. Wherever both sexes are present in approximately equal numbers, multiple the total census by 50% to determine the number of persons of each
sex to be provided for. This regulation only applies when specific information, that would otherwise affect the fixture count is not provided.
5. Not more than 50% of the required number of water closets may be urinals.
6. In buildings with multiple floors, accessibility to the fixtures shall not exceed one vertical story.
7. Fixtures for public use as required by this section may be met by providing a centrally located facility accessible to several stores. The maximum
distance from entry to any store to this facility shall not exceed 500 feet.
8. In stores with floor areas of 150 sq. ft. or less, the requirements to provide facilities for use by employees may be met by providing central facili-
ties located accessible to several stores. The maximum distance from entry to any store from this facility shall not exceed 300 feet.
9. Fixtures accessible only to private offices shall not be counted to determine compliance with this section.
10. Multiple dwellings or boarding houses without public laundry rooms shall not require laundry trays.
11. (Reserved)
12. Requirements for employees and customers may be met with a single set of restrooms.
13. If the design number of customers in food handling establishments exceeds 100, separate facilities for employees and customers are re-
quired.
14. Water closet and lavatory may be a combination fixture. All showers and lavatories shall have thermostatic control and timing devices.
15. See Section 7.21.4 and Section 7.21.7 for toilet facilities for occupancies with a total floor area of 1,500 square feet or less.
16. In determining the number of required fixtures for numbers of persons that fall in the “each additional (xx) over (xx)” listings, the requirement
applies to fractions of the listed group.
17. Laboratories in higher education facilities shall have safety showers.
18. Warehouse storage area requirements shall be permitted to be met by providing a facility centrally located within the storage area. The maxi-
mum travel distance to the facility shall not exceed 500 feet.
19. Multiple individual self storage areas shall be permitted to be met by fixtures located in the facilities administration building. The administration
office must be accessible during normal business hours.
20. Showers may be omitted in recreational facilities without locker rooms when approved by the Authority Having Jurisdiction.
Figure 8.5 - A
AN EXPANSION LOOP IN A HOT WATER PIPE LINE
Figure 8.5 - B
AN EXPANSION COMPENSATOR IN A HOT WATER PIPE LINE
Figure 9.1.5 - B
INDIRECT WASTES FOR COUNTER SINKS AND COUNTER-MOUNTED EQUIPMENT
Figure 9.1.5 - C
PROTECTING A FOOD PREP OR
DISHWASHING SINK FROM SEWAGE BACKUP
EXCEPTIONS:
(1) For multi-compartment commercial sinks, only the compartment used for washing pots, tableware,
kitchenware, and utensils shall discharge to the drainage system through a grease interceptor in accor-
dance with Sections 6.1.1 and 6.2.
(2) The rinsing and sanitizing compartments of multi-compartment commercial sinks shall be drained
indirectly, in accordance with Section 9.1.1.
(3) If a properly vented floor drain is installed immediately adjacent to a sink used for washing, a prop-
erly trapped and vented sink or sink compartment shall be permitted to connect directly to the drainage
system, on the sewer side of the floor drain trap.
(4) Indirect drains shall not be required for domestic kitchen sinks or domestic dishwashers.
Figure 9.1.10
DRAINING AIR CONDITIONING CONDENSATE
Figure 9.3.2
FLOOR SINKS WITH STRAINER OR BASKET
9.3.4 Standpipes
A standpipe, 2-inch minimum pipe size and extending not more than 48 inches nor less than 18 inches
above its trap, shall be permitted to serve as a receptor for a domestic clothes washer. In a dwelling, a
laundry sink shall be permitted to drain into the standpipe. See Figure 9.3.4
Figure 9.3.4
STANDPIPE RECEPTORS
Figure 9.4.1
AN AUTOMATIC WASTE TREATMENT NEUTRALIZING TANK
NOTES:
1. The condensate drain traps on air conditioning (cooling) units must have sufficient trap seal depth to
offset the static pressure (positive or negative) at the condensate drain connection of the unit. The
traps are shown with a seal depth for a negative pressure
Figure 9.4.3 - A
SIZING INDIRECT WASTE PIPING FOR AIR CONDITIONING CONDENSATE
NOTES:
1. Individual outlet protection is required by this Code. It protects the potable water distribution piping from
being contaminated by a cross connection within the property.
Figure 10.4.3 - A
CROSS CONNECTION CONTROL BY INDIVIDUAL OUTLET PROTECTION
Figure 10.4.3 - B
CROSS CONNECTION CONTROL BY CONTAINMENT OF THE BUILDING
Comment: Interconnections between private water supplies and public water supplies are generally
prohibited because private supplies are usually not monitored continuously for water quality.
Comment: The toxicity rating of a piping material can be found in the material standard listed in Table
3.1.3. The piping materials listed in Table 3.4 are non-toxic and are suitable for conveying potable
water.
10.4.6 Reserved
10.4.7 Reserved
Table 10.5.2
MINIMUM AIR GAPS FOR PLUMBING FIXTURES
Minimum Air Gap
Fixture When not Affected by a When Affected by a
Near Wall1 (Inches) Near Wall2 (Inches)
Lavatories with effective opening not greater than 1/2 inch diameter 1 1-1/2
Sink, laundry trays, goose-neck bath faucets and other fixtures with effective
1-1/2 2-1/4
openings not greater than 3/4” diameter
Over rim bath fillers and other fixtures with effective openings not greater
2 3
than 1 inch diameter
Drinking water fountains-single orifice not greater than 7/16 (0.437) in. diam-
eter or multiple orifices having total area of 0.150 square inches (area of circle 1 1-1/2
7/16 in. diameter)
Effective openings greater than one inch 2X diameter of 3X diameter of
effective opening effective opening
Figure 10.5.2
MINIMUM REQUIRED AIR GAPS
Figure 10.5.5 - A
THE POTABLE WATER SUPPLY TO A COMMERCIAL FOOD WASTE GRINDER
PROTECTED BY AN ATMOSPHERIC VACUUM BREAKER
NOTES:
1. Atmospheric vacuum breakers are not rated for periods of more than 12 hours of continuous water pres-
sure.
Figure 10.5.5 - B
THE POTABLE WATER SUPPLY TO A SERVICE SINK
NOTES:
1. Atmospheric vacuum breakers are not rated for periods of more than 12 hours under continuous water
pressure.
Figure 10.5.5 - C
THE POTABLE WATER SUPPLY TO A LAB SINK
PROTECTED BY AN ATMOSPHERIC VACUUM BREAKER
NOTES:
1. Atmospheric vacuum breakers are not rated for periods of more than 12 hours under continuous water
pressure.
Figure 10.5.5 - D
THE POTABLE WATER SUPPLY TO AN ASPIRATING DEVICE
PROTECTED BY AN ATMOSPHERIC VACUUM BREAKER
Figure 10.5.5 - E
THE POTABLE WATER SUPPLY TO A WATER CLOSET OR URINAL
PROTECTED BY AN ATMOSPHERIC VACUUM BREAKER
Figure 10.5.5 - F
THE POTABLE WATER SUPPLY TO A WATER CLOSET GRAVITY FLUSH TANK
PROTECTED BY AN ANTI-SIPHON BALLCOCK WITH INTEGRAL VACUUM BREAKER
NOTES:
1. Double check valve assemblies or reduced pressure backflow preventor assemblies are required for back
pressure applications.
2. Double check valve assemblies must be installed between 12" and 60" above the floor or other working
surface to provide sufficient access for periodic testing and maintenance.
3. Double check valve assemblies subject to back-siphonage require an intermediate vacuum breaker and a
relief vent.
4. Double check valve assemblies with an intermediate vacuum breaker and relief vent must not be located
in pit or other area subject to flooding. The relief vent will create a cross-connection if submerged.
Figure 10.5.5 - H
THE POTABLE WATER SUPPLY TO A NON-HEALTH HAZARD BACKFLOW APPLICATION
PROTECTED BY A DOUBLE CHECK VALVE ASSEMBLY
Figure 10.5.5 - I
THE POTABLE WATER SUPPLY TO A HEALTH HAZARD BACKFLOW APPLICATION
PROTECTED BY A REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY
Figure 10.5.7
A POTABLE WATER TANK OR VAT WITH ITS INLET BELOW THE OVERFLOW RIM
Figure 10.6.1 - A
THE MINIMUM DISTANCE BETWEEN AN UNDERGROUND WATER SERVICE
AND A BUILDING DRAIN OR BUILDING SEWER
NOTES:
1. The minimum clearance is 12 inches.
2. Where possible, the water service should cross over the building drain or building sewer.
3. If necessary, the water service can cross under the building drain or building sewer.
4. The 12" minimum separation prevents direct contact between the pipe lines, even with considerable
settlement.
Figure 10.6.1 - B
CROSSING A WATER SERVICE OVER (OR UNDER)
A BUILDING DRAIN OR BUILDING SEWER
Figure 10.6.2
MINIMUM CLEARANCE BETWEEN A WATER SERVICE PIPE
AND SOURCES OF CONTAMINATION
Comment: Open waste outlets on underground water service shutoff valves would permit ground water
to contaminate the potable water supply.
Figure 10.6.4
WATER SERVICE PIPE SLEEVES FOR METALLIC AND PLASTIC PIPING
10.8.2 Reserved
Table 10.8.3
SIZES1 OF OVERFLOW PIPES FOR WATER SUPPLY TANKS
Table 10.8.3
1
Sizes Of Overflow Pipes For Water Supply Tanks
Maximum Capacity of Diameter of Maximum Capacity of Diameter
Water Supply Line Overflow Pipe Water Supply Line Overflow Pipe
to Tank (Inches ID) to Tank (Inches ID)
0-13 gpm 1-1/2 356-640 gpm 5
14-55 gpm 2 641-1040 gpm 6
56-100 gpm 2-1/2 over 1040 gpm 8
101-165 gpm 3
166-355 gpm 4
1
Computed by the method of NBS Mono. 31, for vertical pipes flowing not greater than 1/2 full at terminal velocity.
(1/3 full for 1-1/2 in. pipe).
10.8.4 Covers
All water supply tanks shall be covered to keep out unauthorized persons, dirt, and vermin. The covers of
gravity tanks shall be vented with a return bend vent pipe having an area not less than the area of the down
feed riser pipe and the vent shall be screened with corrosion resistant screen having not less than 14 and not
more than 20 openings per linear inch. See Figure 10.5.7
10.9.2 Disinfecting
a. Where required by the Authority Having Jurisdiction, the water service piping and the hot and cold water
distribution piping in new or renovated potable water systems shall be disinfected after flushing and prior to
use. The procedure used shall be as follows or an approved equivalent:
1. All water outlets shall be posted to warn against use during disinfecting operations.
2. Disinfecting shall be performed by persons experienced in such work.
3. The water supply to the piping system or parts thereof being disinfected shall be valved-off from the
normal water source to prevent the introduction of disinfecting agents into a public water supply or portions
of a system that are not being disinfected.
4. The piping shall be disinfected with a water-chlorine solution. During the injection of the disinfecting
agent into the piping, each outlet shall be fully opened several times until a concentration of not less than 50
parts per million chlorine is present at every outlet. The solution shall be allowed to stand in the piping for at
least 24 hours.
5. An acceptable alternate to the 50 ppm/24-hour procedure described in Section 10.9.2.a.4 shall be to
maintain a level of not less than 200 parts per million chlorine for not less than three hours. If this alternate
procedure is used, the heavily concentrated chlorine shall not be allowed to stand in the piping system for
more than 6 hours. Also, special procedures shall be used to dispose of the heavily concentrated chlorine in
an environmentally acceptable and approved manner.
6. At the end of the required retention time, the residual level of chlorine at every outlet shall be not less
than five parts per million. If the residual is less than five parts per million, the disinfecting procedure shall
be repeated until the required minimum chlorine residual is obtained at every outlet.
7. After the required residual chlorine level is obtained at every outlet, the system shall be flushed to re-
move the disinfecting agent. Flushing shall continue until the chlorine level at every outlet is reduced to that
of the incoming water supply.
8. Any faucet aerators or screens that were removed under Section 10.9.1 shall be replaced.
9. A certification of performance and laboratory test report showing the absence of coliform organisms
shall be submitted to the Authority Having Jurisdiction upon satisfactory completion of the disinfecting
operations.
Comment: The chemical composition of the service water should be considered when selecting the water
service pipe material. Refer to Appendix Section B.2.3. The aggressive nature of the soil or fill material
around the water service pipe should be evaluated when considering if additional corrosion protection is
need for the exterior surfaces of the pipe.
NOTES
1. The building shutoff valve must be a full-way type with a bleed to drain the piping within the building.
2. The water heater shutoff valve must not be a globe valve.
3. Additional shutoff valves can be provided to isolate the water heater and branches of the water distribu-
tion piping.
4. Shutoff valves for powder rooms and bathroom groups are not required if all fixtures within the group
have individual shutoff valves. One set of shutoff valves can serve two bathroom groups if they are
piped as one group of fixtures without separate branch pipes for each group.
5. Water closets and lavatories usually have individual supply stop valves where the fixture supply tube
connects to the fixture branch supply pipe.
6. Where manifold-type parallel water distribution systems are used, the individual fixture shutoff valves
are located on the manifold.
Figure 10.12.4 - A
REQUIRED WATER SHUTOFF VALVES IN SINGLE DWELLING UNITS
Figure 10.12.4 - B
REQUIRED WATER SHUTOFF VALVES IN MULTI-DWELLING UNITS
NOTES:
1. The cold water shutoff valve permits the water heater to be serviced or replaced, but requires that the
hot water distribution piping be drained.
2. The optional hot water shutoff valve permits the water heater to be serviced or replaced without draining
the hot water distribution piping.
3. The water heater relief valve must not be isolated from the water heater tank by any shutoff valves.
4. Water heater shutoff valves must be the full-flow type. Globe valves are not permitted.
Figure 10.12.7
WATER HEATER SHUTOFF VALVE(S)
Figure 10.12.8 - A
METER SHUTOFF VALVES IN A SMALL WATER SERVICE
Figure 10.12.8 - B
METER SHUTOFF VALVES IN A LARGE WATER SERVICE
Comment: Access to water supply shutoff valves can require the use of tools to remove access panels or
doors.
Bathroom Group with 3.5 GPF (or higher) Flushometer Valve 8.0 6.0
Figure 10.14.6 - A
INSTALLATION OF A WATER PRESSURE REDUCING VALVE
WHERE THE WATER SUPPLY PRESSURE EXCEEDS 80 PSIG
Figure 10.14.6 - B
ONE POSSIBLE ARRANGEMENT OF PRESSURE REDUCING VALVES
IN A HIGH-RISE BUILDING
Figure 10.14.7
WATER HAMMER ARRESTORS
Figure 10.15.2
HOT WATER TEMPERATURE MAINTAINENCE BY RECIRCULATION
10.15.9.2 Construction
a. Drip pans shall be watertight and constructed of corrosion-resistant materials. Metallic pans shall
be 24 gage minimum. Non-metallic pans shall be .0625-inch minimum thickness. Pans shall be not
less than 1-1/2" deep and shall be of sufficient size to hold the heater without interfering with drain
valves, burners, controls, and any required access.
b. High impact plastic pans shall be permitted under gas-fired water heaters where the heater is listed
for zero clearance for combustible floors and the application is recommended by the pan manufacturer.
10.15.9.3 Drainage
a. Drip pans shall have drain outlets not less than ¾” size, with indirect drain pipes extending to
an approved point of discharge, a suitably located indirect waste receptor, or floor drain, or extend to
within 2 to 6 inches above the adjacent floor.
b. Discharge from a relief valve into a water heater pan shall be prohibited.
NOTES:
1. Relief valves can discharge to the floor where permitted by the Authority Having Jurisdiction.
2. A shutoff valve in the hot water supply is permitted.
3. Shutoff valves must not isolate relief valves from the tank that they are protecting.
4. Threads are prohibited on the ends of relief valve discharge pipes to prevent the installation of a pipe
cap if the valve begins to leak.
5. Drains or indirect waste pipes that receive the discharge from relief valves must be sized according to
Table 10.16.6, based on the size of the relief valve discharge pipe.
6. The inlet to indirect waste piping must be elevated to establish sufficient static head above the horizon-
tal portion of the drain to prevent spillage.
7. Where two indirect waste pipes from relief valves are joined, the cross-sectional area of the common
drain must be equal to or larger than the sum of the areas of the individual waste pipes. Refer to Sec-
tion 9.3.6.b.
Figure 10.16.6
WATER HEATER RELIEF VALVES AND DISCHARGE PIPING
NOTES:
1. Vacuum relief valves at water heaters prevent vacuum conditions that could siphon water from a tank,
causing it to be damaged from dry firing or collapse.
2. Vacuum relief valves are tested and rated under ANSI Z21.22 - Relief Valves for Hot Water Supply Sys-
tems.
3. Backflow prevention vacuum breakers are not intended for use as vacuum relief valves.
4. Vacuum relief valves must be mounted higher than the tank being protected.
Figure 10.16.7
VACUUM RELIEF VALVES ON OVERHEAD WATER HEATER TANKS
10.17.2 Sizing
See Appendix B for sizing manifolds and distribution lines. Distribution line sizes shall be as recommend-
ed by the system manufacturer to provide the fixture flow rates listed in Section 10.14.2a. The minimum line
size shall be 3/8” nominal.
10.17.3 Valving
a. Each manifold outlet that is equipped with a shutoff valve shall identify the fixture being supplied. Ad-
ditional shut-off or stop valves at the fixtures shall be provided as required by Section 10.12.4.
EXCEPTION: Additional shut-off or stop valves at the fixtures shall not be required if a manifold with
shutoff valves is located within the same room as the fixtures, or in an adjacent closet.
b. Manifolds having shutoff valves shall be readily accessible.
10.17.4 Support
a. Tube bundles for manifold systems shall be supported in accordance with Chapter 8 of this Code.
b. Supports at changes in direction shall be in accordance with the system manufacturer’s recommenda-
tions.
Table 10.19
SIZING OF RESIDENTIAL WATER SOFTENERS
1
Required Size of Softener Connection (in.) Number of Bathroom Groups Served
2
3/4 Up to 2
3
1 Up to 4
¹ Installation with a kitchen sink and dishwasher, laundry tray and automatic clothes washer.
² An additional water closet and lavatory shall be permitted without an increase in sizing.
³ Over four Bathroom Groups, the softener shall be engineered for the specific installation.
11.1 MATERIALS
See Section 3.1.
Comment: The Authority Having Jurisdiction may permit the use of a diversity factor in systems where
the number of fixtures per person is higher than normal. A hospital is such an example where toilet
facilities are provided in each patient room for the convenience of the patients. The load on the drain-
age system is created by the number of persons served, not by the number of plumbing fixtures that are
installed.
Table 11.5.1B
HORIZONTAL FIXTURE BRANCHES AND STACKS
Maximum Number of Drainage Fixture Units (DFU) That May Be
Connected to Any Horizontal Fixture Branch, a Stack of Three Branch
Intervals or Less, or Stacks of more than Three Branch Intervals
Stacks with more than
Three Branch Intervals
1-1/4 1 1 1 1
1-1/2 3 4 8 2
2 6 10 24 6
3 202 483 723 203
4 160 240 500 90
5 360 540 1,100 200
6 620 960 1,900 350
8 1,400 2,200 3,600 600
10 2,500 3,800 5,600 1,000
12 3,900 8,400 8,400 1,500
15 7,000
1. To size the drainage system, start at the top floor and work down to the building drain.
2. Draw a diagram of the system showing the various fixtures.
3. Assign a drainage fixture unit (DFU) value to each fixture or fixture group using Table 11.4.1. Where a spe-
cific fixture type is not listed, use the “Sink” or “Trap Size” values.
4. Size the horizontal fixture branches on each floor using the pipe sizes in Table 11.5.1.B for the number of
DFUs listed in the second column.
5. Size the stacks using the pipe size in Table 11.5.1.B for the number of DFUs listed in columns 3,4, or 5,
depending on the number of branch intervals. Check the limits on DFUs in any one branch interval and the
total for the stack. Size the stack accordingly.
6. For Stack A in Figure 11.5.1-B, each horizontal branch drain has 90 DFU and is 4" size. The stack is 4" size
from top to bottom.
7. For Stack B in Figure 11.5.1-B, the horizontal branch drains are all 4" size. Although the total number of
DFUs is the same as Stack A (450 DFU), the lowest branch interval has more than 90 DFU and must be 5"
size. The stack cannot be smaller than any of its branches and thus must be 5" size at the base. The upper
portions of the stack can be 4" size.
8. For Stack C in Figure 11.5.1-B, although the total number of DFUs is less than Stack A and Stack B, the top
horizontal branch drain must be 5" size because it has 200 DFUs. The entire stack must 5" size, even though
4" would have been adequate for the total number of DFUs.
9. Stack D in Figure 11.5.1-B only has three branch intervals and can be sized using column 3 in Table 11.5.1.B.
Each of the 3" horizontal fixture branches is limited to four 1.6 GPF water closets per Section 11.5.6.b. Each
branch interval of the 3" stack is limited to four 1.6 GPF water closets and the entire 3" stack is limited to
twelve 1.6 GPF water closets per Section 11.5.6.c. If the number of water closets on any branch or the stack
exceed the limits for 3" pipe, the branch and downstream stack must be increased to 4" size.
10. In Figure 11.5.1-A, Stack A is 4" size with 450 DFUs. In Table 11.5.1.A, Branch A of the building drain must
be 5" size sloped 1/4" per foot. If 1/4" slope cannot be maintained, the branch must be increased to 6" size
sloped 1/8" per foot.
11. In Figure 11.5.1-A, Stack B is 5" size with 450 DFUs. In Table 11.5.1.A, Branch B of the building drain can
remain 5" size if sloped 1/4" per foot. Otherwise, the size must be increased if run at less slope.
12. In Figure 11.5.1-A, Section B-C of the building drain is 450 + 450 = 900 DFUs. In Table 11.5.1.A, it needs to
be 8" size, but the slope can be reduced to 1/8" per foot.
13. In Figure 11.5.1-A, Stack C is 5" size with 404 DFUs. In Table 11.5.1.A, Branch C can remain 5" size, but
must be sloped at 1/4" per foot. Otherwise, the size must be increased if run at less slope.
14. In Figure 11.5.1-A, Section C-D of the building drain is 900 + 404 = 1304 DFUs. Section C-D of the building
drain must be at least 8" size because Section B-C is 8" size. In Table 11.5.1.A, 8" size is adequate at 1/8" or
1/16" per foot slope. Section 11.3.1 requires 1/8" slope for pipe 4" and larger. However, Table K-1 indicates
that the velocity in Section C-D when flowing 1/2 full at 1/16" slope is not less than the 2 feet per second mini-
mum and the reduced slope might be approved by the Authority Having Jurisdiction.
15. In Figure 11.5.1-A, Stack D is 3" size with 48 DFUs. In Table 11.5.1.A, branch D of the building drain could
remain 3" if sloped 1/2" per foot. However, Section 11.5.6a limits it to four 1.6 GPF water closets. Otherwise,
it would have to be increased to 4" size.
16. In Figure 11.5.1-A, Section D-E of the building drain is 1304 + 48 = 1352 DFUs. Section D-E must be at least
8" size because Section C-D is 8" size. In Table 11.5.1.A, 8" size is still adequate for 1352 DFUs.
17. In Figure 11.5.1-A, horizontal fixture branch E is 4 + 1 + 4 + 1 = 10 DFUs. In Table 11.5.1.B, the branch
needs to be 3" size. It has less than the allowable number of water closets in Section 11.5.6.b.
18. In Figure 11.5.1-A, the load on the last section of the building drain and the building sewer is 1352 + 10 =
1362 DFUs. The 8" size of Section D-E is still adequate for the final section of the building drain and for the
building sewer.
NOTES:
1. The figure shows a sanitary drainage piping system with one branch interval.
2. The horizontal branch drain with 30 DFU must be 4" minimum size per Table 11.5.1B.
3. The stack size must be 4" minimum size, even though Table 11.5.1B indicates that a 3" stack with one
branch interval could handle 48 DFU.
4. The building drain must be 4" minimum size, even though Table 11.5.1A indicates that a 3" building drain
could handle 42 DFU at 1/4" slope.
5. The stack vent must be 2" minimum size, which is 1/2 the size of the 4" drainage stack.
Figure 11.5.2
MINIMUM SANITARY DRAINAGE PIPE SIZES
Comment: Drainage or vent piping installed with plugged or capped fittings for the connection of future
fixtures does not constitute a dead end. Such piping should be accessible.
NOTES:
1. Vertical offsets in drainage stacks do not affect the stack size.
2. If a drain stack with ten or more branch intervals above a vertical offset has fixtures or horizontal
branches connected within two feet above or below the offset, a relief vent must be provided for the
lower portion of the stack.
Figure 11.6.1
VERTICAL OFFSETS IN DRAINAGE STACKS
11.6.2 Reserved
11.6.4 Reserved
Figure 11.6.3
OFFSETS IN STACKS ABOVE THE HIGHEST BRANCH DRAIN CONNECTION
Figure 11.6.5
HORIZONTAL OFFSETS IN STACKS
NOTES:
1. Sewage pumps and ejectors must have audible, visual, or combination high level alarms per Section
11.7.11.
Figure 11.7.1
A BUILDING SUBDRAIN AND SEWAGE PUMP
11.7.2 Reserved
11.7.3 Reserved
Comment: Sump pits with centrifugal sewage pumps must be vented in accordance with Section 12.14.2
and Table 12.14.2. Pneumatic sewage ejectors must be separately vented according to Section 12.14.3.
11.7.5 Reserved
Figure 11.7.9
INDIVIDUAL FIXTURE DRAIN PUMPS
11.8 RESERVED
11.9 BRANCH CONNECTIONS NEAR THE BASE OF STACKS
a. Horizontal branch drain connections shall not be made within 10 pipe diameters downstream from the base
of a stack.
b. A relief vent shall be provided for stacks of five or more branch intervals, either above the base of the stack
or within 10 pipe diameters downstream from the base of the stack.
c. Branch drains shall not connect between the base of a stack and its relief vent.
See Figures 11.9 and 12.3.1
Figure 11.9
HYDRAULIC JUMP AT THE BASE OF DRAINAGE STACKS
Comment #2: Suds pressure relief vents in Section 12.15 are larger than ordinary vents for drainage
systems because the suds are heavier than air. Suds can weight from 2 to as much as 19 pounds per
cubic foot.
Figure 11.11.3
SEPARATE DRAINAGE STACKS FOR LOWER FLOORS
WHERE THERE ARE SUDS PRODUCING FIXTURES ABOVE
11.11.4 Exceptions
The requirements of Sections 11.11 and 12.15 shall not apply to the following:
a. Stacks that are less than three stories in height.
b. Stacks in individual dwellings having their own building sewer.
NOTES:
1. Trap at rest with 2" trap seal.
2. Trap subjected to 1" suction from building drainage piping.
3. Trap at rest with 1/2" loss of trap seal. Trap will continue to spillover and lose trap seal when subjected
to 1" suction until the trap seal is reduced to 1". The 2" initial trap seal permits the trap to withstand 1"
suction and still maintain a trap seal of at least 1".
Figure 12.2.1 - A
TRAP SEAL REDUCTION FROM 1" NEGATIVE PRESSURE
Figure 12.2.1 - B
TRAP SEAL REDUCTION FROM 1" POSITIVE PRESSURE
12.3.2 Relief Vents for Stacks Having Ten or More Branch Intervals
a. Where drainage stacks have ten or more branch intervals, a relief vent shall be provided for each ten
branch intervals, starting at the top of the stack.
b. The lower end of each relief vent shall connect to the drainage stack as a yoke vent below its tenth
branch interval.
c. The upper end of the relief vent shall connect to the vent stack at an elevation not less than 3 feet above
the floor level served by the branch interval.
See Figure 12.3.2
Figure 12.3.2
RELIEF VENTS FOR DRAINAGE STACKS HAVING TEN OR MORE BRANCH INTERVALS
NOTES:
1. The vent stack must be sized for the entire DFU load on the drain stack per Table 12.16.4.
2. The relief vents for the upper and lower portions of the drain stack are required to relief backpressure
from the hydraulic effect of the offset. The relief vents must be the same size as the vent stack.
3. The vent stack must connect to the base of the drainage stack, either below the lowest branch connec-
tion above the base of the stack or within 10 pipe diameters downstream from the base of the stack.
Figure 12.3.3 - A
RELIEF VENTS FOR HORIZONTAL OFFSETS IN DRAINAGE STACKS HAVING ONE VENT STACK
Figure 12.3.3 - B
RELIEF VENTS FOR HORIZONTAL OFFSETS IN DRAINAGE STACKS
HAVING TWO VENT STACKS
NOTES:
1. Refer to Section 12.5 for provisions to prevent frost closure.
Figure 12.4.1
VENT EXTENSIONS THROUGH THE ROOF
NOTES:
1. The separation of vent terminals from doors, windows, and air intake and exhaust openings keeps foul
odors from entering the building.
2. The vent terminal is less than 2 feet above the window, but the window is 10 feet or more from the vent
terminal horizontally.
3. The air intake or exhaust opening can be within 10 feet horizontally from the vent terminal if the vent
terminal is 2 feet or more above the top of the opening.
Figure 12.4.4
ALLOWABLE LOCATIONS FOR VENT TERMINALS
NOTE:
1. Where pipe size increases are necessary to avoid frost closure, the increase in pipe size must be
one foot below an area subject to freezing temperatures.
Figure 12.5
MINIMUM VENT EXTENSION SIZE TO PREVENT FROST CLOSURE
NOTE:
1. Vent piping that is sloped allows condensation and moisture that may form in the piping to drain to the
drainage system.
2. Vent piping must not have any trapped sections. Water may collect in trapped piping, fill the piping, and
render the vent ineffective.
3. Vent piping can slope back to the fixture served or forward away from the fixture, as long as it drains to
the drainage system.
Figure 12.6.1
VENT PIPING SLOPE
Figure 12.6.2 - A
VENT PIPE CONNECTIONS TO HORIZONTAL DRAINS
NOTES:
1. A separate vent will be required for the bathtub if the developed length of its trap arm exceeds the maxi-
mum allowable length in Table 12.8.1.
2. If a vent is required for the bathtub, it can have a horizontal offset below the flood level rim of the bath-
tub, but it must be 6 inches above the flood level rim of the lavatory before it connects to another vent.
The horizontal offset below the flood level rim must be sloped so that it drains to the drainage system.
Figure 12.6.2 - B
HORIZONTAL VENT PIPING
BELOW THE FLOOD LEVEL RIM OF FIXTURES
12.6.2.3 Cleanouts
Cleanouts shall be provided in the vent piping so that any blockages in the vent piping below the flood
level rim of the fixture served can be cleared into the drainage system.
Comment: Suitable double fittings for connecting adjacent fixtures such as lavatories, sinks, tubs, showers,
urinals, or floor-outlet water closets to a stack are double sanitary tees, double fixture fittings (plastic), and
sanitary crosses. These fittings have high branch openings into the stack that keep the top of the vent
opening above the weir of the traps to prevent self-siphonage.
Figure 12.7
VENTING ADJACENT FIXTURES
CONNECTED TO A VERTICAL DRAIN AT THE SAME LEVEL
NOTES:
1. Trap arm lengths are limited by Table 12.8.1 to prevent self-siphonage of the fixture trap.
2. The top of the opening at the vent pipe must not be below the elevation of the trap weir. The maximum
trap arm lengths in Table 12.8.1 are based on using sanitary tees or other short turn fittings to connect
trap arms to the drainage system. Long turn fittings should not be used with Table 12.8.1.
3. The trap arm length is the developed length along its centerline, including any changes in direction.
Figure 12.8.1 - A
THE MAXIMUM LENGTH OF TRAP ARMS
Table 12.8.1
MAXIMUM LENGTH OF TRAP ARM
Size of Trap Arm (Inches) Length – Trap Arm to Vent Slope – Inches per Foot
1- 1/4 3’ 6" 1/4
1-1/2 5’ 1/4
2 8’ 1/4
3 10’ 1/8
4 12’ 1/8
NOTES:
1. Vents connected too close to the crown or weir of a trap are subject to clogging, thereby rendering the
vent ineffective. Vent connections must be at least two pipe diameters from the weir of the trap.
Figure 12.8.3
CROWN VENTS ARE PROHIBITED
NOTES:
1. When the upper fixture is 3 DFU and the lower is 1 DFU, the vertical drain must be 3" instead of 2" so
that the 1 DFU fixture is wet vented during the heavier discharge from the 3 DFU fixture.
Figure 12.9.2
VENTING FIXTURES CONNECTED TO A
VERTICAL DRAIN AT DIFFERENT LEVELS
NOTES:
1. The vent for the bathroom group is 1-1/2", which is 1/2 the size of the 3" drain for the bathroom group.
Figure 12.10.1 - A
A WET VENTED BATHROOM GROUP WITH A 3" CLOSET BEND
(SINGLE STORY OR TOP FLOOR)
NOTES:
1. The vent for the bathroom group is 2", which is 1/2 the size of the 4" drain for the bathroom group. Even
though the bathroom group could have had a 3" drain with a 1-1/2" vent, installing a 1-1/2" vent on the
4" drain would cause unnecessary confusion for the installer and inspector.
Figure 12.10.1 - B
A WET VENTED BATHROOM GROUP WITH A 4" CLOSET BEND
(SINGLE STORY OR TOP FLOOR)
Figure 12.10.2
WET VENTED BACK-TO-BACK BATHROOM GROUPS
(SINGLE STORY OR TOP FLOOR)
Figure 12.10.3 - A
WET VENTED BACK-TO-BACK BATHROOM GROUPS ON A LOWER FLOOR
WITH BACK VENTED WATER CLOSETS
(ONE ARRANGEMENT)
NOTES:
1. This is an example of Exception #1 to Section 12.10.3.
2. Two adjacent bathroom groups are shown but individual bathroom groups can also be wet vented in this
manner.
3. A lower floor is shown, but the arrangement can be used at the top of a stack.
Figure 12.10.3 - C
ADJACENT BATHROOM GROUPS WET VENTED WITH 45 DEGREE WYE TAPS
Figure 12.10.3 -D
A BATHROOM GROUP WET VENTED WITH A SPECIAL STACK FITTING
NOTES:
1. This is an example of Exception #3 to Section 12.10.3.
2. The oversized 4" water closet fixture drain permits the tub/shower on one side of the drain to be wet
vented by the lavatory on the other side of the drain.
3. Two adjacent bathroom groups are shown, but individual bathroom groups can be wet vented in this
manner.
4. A lower floor is shown, but the arrangement can be used at the top of a stack.
Figure 12.10.3 -E
ADJACENT BATHROOM GROUPS WET VENTED WITH 4" CLOSET BENDS
HAVING TWO 2" WYE TAPS
NOTES:
1. The maximum distance from the water closet outlet to its vent connection is 9 feet horizontal and 3 feet
vertical.
2. A lower floor is shown, but the arrangement can be used at top of stack.
Figure 12.10.4
A WATER CLOSET WET VENTED BY A BATHTUB
12.10.5 Reserved
NOTES:
1. The arrangement shown is permitted in a one-story building or at the top of a stack.
2. Each fixture must connect independently to the stack except that the tub/shower connection to the 4"
water closet fixture drain is considered to be a connection to the stack because the 4" drain is oversized
for the water closet.
3. The length of all trap arms from their trap weir to their vent opening at the stack must not exceed the
limits in Table 12.8.1. The vent distance for the water closet must be in accordance with Section 12.8.4.
4. Bathroom groups without kitchen sinks can also be stack vented as shown.
Figure 12.11.1 - A
STACK VENTING A BATHROOM GROUP AND AN ADJACENT KITCHEN SINK
NOTES:
1. The arrangement shown is permitted in a one-story building or at the top of a stack.
2. Each fixture must connect independently to the stack except that the tub/shower connections to the 4"
water closet fixture drains are considered to be connections to the stack because the 4" drains are over-
sized for the water closets.
3. The length of all trap arms from their trap weir to their vent opening at the stack must not exceed the
limits in Table 12.8.1. The vent distance for the water closets must be in accordance with Section
12.8.4.
4. Bathroom groups without kitchen sinks can also be stack vented as shown.
Figure 12.11.1 - B
STACK VENTING ADJACENT BATHROOM GROUPS AND AN ADJACENT KITCHEN SINK
NOTES:
1. Each fixture in the stack group must connect independently to the sub-stack except that the connection
to the 4" water closet fixture drain is considered to be a connection to the sub-stack because it is over-
sized for the water closet.
2. The length of all trap arms from their trap weir to their stack must not exceed the limits in Table 12.8.1.
The vent distance for the water closet must be in accordance with Section 12.8.4.
Figure 12.11.2 - A
STACK VENTING A BATHROOM GROUP ON A LOWER FLOOR OF A DRAIN STACK
Figure 12.12.2
FIXTURES ON HORIZONTAL BRANCHES OF A STACK WITHOUT REVENTS
12.12.3 Fixtures without Revents Above Highest Bathtubs and Water Closets
a. Fixtures without revents may be connected to a soil or waste stack above the highest water closet or
bathtub connection if all the following conditions are met:
1. The total load does not exceed 3 dfu's.
2. The soil or waste stack is 3" or larger.
3. The total load on the stack is in accordance with Table 11.5.1B.
4. The waste piping of the fixture above the water closet or bathtub connection is in accordance with Sec-
tions 12.8.1 and 12.12.2.
See Figure 12.12.3
Figure 12.12.3
UNVENTED FIXTURES ABOVE THE HIGHEST BATHTUBS AND WATER CLOSETS
Figure 12.13.1
CIRCUIT AND LOOP VENTING BATTERIES OF FIXTURES
Comment: Suds pressure relief vents in Section 12.15 are larger than ordinary vents for drainage sys-
tems because the suds are heavier than air. Suds can weight from 2 to as much as 19 pounds per cubic
foot.
Figure 12.15.1
RELIEF VENTS FOR DRAIN CONNECTIONS IN A SUDS PRESSURE ZONE
Table 12.15.1
SUDS PRESSURE RELIEF VENTS
Drain Size (inches) Relief Vent Size (inches)
1-1/2 2
2 2
3 2
4 3
5 4
6 5
8 6
Table 12.16
SIZE AND LENGTH OF VENTS
Size of Drainage Diameter of Vent Required (inches)
Fixture Drain, Fixture for the Maximum Length of Vent (feet)
Drainge Stack, Units
or Building Drain Connected 1-1/4” 1-1/2” 2” 2-1/2” 3” 4” 5” 6” 8”
(inches)
1-1/4” 1 (1)
1-1/2” 8 50 150
2” 12 30 75 200
2” 20 26 50 150
3” 10 30 100 200 600
3” 30 60 200 500
3” 60 50 80 400
4” 100 35 100 260 1000
4” 200 30 90 250 900
4” 500 20 70 180 700
5” 200 35 80 350 1000
5” 500 30 70 300 900
5” 1100 20 50 200 700
6” 350 50 200 400 1300
6” 620 30 125 300 1100
6” 960 24 100 250 1000
6” 1900 20 70 200 700
8” 600 50 150 500 1300
8” 1400 40 100 400 1200
8” 2200 30 80 350 1100
8” 3600 25 60 250 800
10” 1000 75 125 1000
10” 2500 50 100 500
10” 3800 30 80 350
10” 5600 25 60 250
NOTES FOR TABLE 12.16
(1) The length of the vent is not limited.
Figure 12.16.1 - A
THE SIZE OF INDIVIDUAL FIXTURE VENTS
NOTES:
1. Two groups of public toilet rooms are connected to a combined vent.
2. The size of the vent for the 4" drain stack from each group with more than 100 DFU must be 3" if the
overall length to the vent terminal is 100 feet. (Table 12.16).
3. The size of an equivalent drainage stack with 300 DFU is 5" (Table 11.5.1B).
4. The size of the combined vent for the 5" equivalent stack with 300 DFU and 100 feet is 4" in Table 12.16
Figure 12.16.1 - B
THE SIZE OF VENTS FOR MULTIPLE FIXTURES ON DIFFERENT STACKS
NOTES:
1. A lower floor is shown. It requires a relief vent because there are more than 4 water closets on the
branch.
2. The horizontal branch drain is 4" size
3. The circuit vent must be 2" minimum size per Section 12.16.2.
4. The relief vent must be 2" minimum size per Section 12.16.3.
Figure 12.16.2
THE SIZE OF CIRCUIT AND LOOP VENTS
Table 12.16.6
NOMINAL PIPE CROSS SECTIONAL AREA (Sq. Inches)
Nominal Pipe Size (ID) Cross Sectional Area (sq in.)
1-1/4” 1.2
1-1/2” 1.8
2” 3.1
2-1/2” 4.9
3” 7.1
4” 12.6
5” 19.6
6” 28.3
8” 50.3
10” 78.5
12” 113.1
15” 176.7
Table 12.17.4
PIPE SIZING FOR COMBINATION WASTE AND VENT SYSTEMS
slope slope slope slope
Load
1/8” per ft 1/4” per ft 3/8” per ft 1/2” per ft
3 dfu 4” 2” 2” 2”
12 dfu 4” 4” 3” 3”
20 dfu 5” 4” 4” 4”
180 dfu 5” 5” 4” 4”
218 dfu 6” 5” 5” 5”
390 dfu 8” 8” 5” 5”
480 dfu 8” 8” 6” 6”
700 dfu 8” 8” 6” 6”
840 dfu 10” 8” 8” 8”
1600 dfu 10” 10” 8” 8”
1920 dfu 12” 10” 10” 10”
Figure 12.18
ISLAND SINK VENTING
Figure 12.19.6
WASTE STACK VENTING
Comment #1: The peak storm water flows in combined sanitary and storm sewer systems can overload
the sewage treatment facility, causing it to bypass untreated sewage into its point of discharge.
Comment #2: In many cities with combined sewers, it is impractical to install separate sewers in the
downtown areas because of the number of existing utilities under the streets.
Comment #3: Some jurisdictions with combined sewers require that new or renovated buildings have
separate sanitary and storm building drains so that they could be connected to separate sewers in the
future.
13.1.4 Reserved
Figure 13.1.5 - A
A FOUNDATION DRAIN OUTSIDE OF A FOOTING
NOTES:
1. Where subject to freezing weather, the discharge pipe should be sloped downward so that the outlet
drains by gravity.
Figure 13.1.5 - B
A SUMP PUMP FOR FOUNDATION DRAINS
NOTES:
1. The foundation drains can be inside or outside of the footings. See Figures 13.1.5 - A and 13.1.5 - B.
2. The areaway drain can connect to a foundation drain if the size of the areaway (and any adjacent areas
that drain into the areaway) is 100 square feet or less. It must discharge separately if the area being
drained is larger than 100 square feet.
3. Drain pipes for areaways must be sized according to Table 13.6.2, based on the rainfall rate and the
size of the areaway and any adjacent areas that may drain into the areaway. The minimum drain pipe
sizes are 2" if sloped 1/4 in./ft or more and 3" if sloped 1/8 in./ft.
Figure 13.1.6
THE ARRANGEMENT OF AN AREAWAY DRAIN
Figure 13.1.7 - A
A WINDOW WELL DIRECTLY DRAINED
NOTES:
1. The foundation drain must be outside of the footings. See Figure 13.1.5 - B.
2. The porous filter bed must extend from the area drain in the window well to the foundation drain. Install-
ing a filter fabric between the earth and the filter bed will keep the porous bed from becoming clogged
with fine soil particles.
Figure 13.1.7 - B
A WINDOW WELL INDIRECTLY DRAINED
13.1.9 Reserved
13.2 MATERIALS
See Section 3.7.
See Table 3.7 for approved materials for storm water drainage.
Comment: Floor drains or other receptors that are connected to a storm drainage system or combined
sewer and are subject to evaporation of the trap seal must be provided with a deep seal trap or other
means of maintaining the trap seal. See Section 5.3.6.
Figure 13.3.2
A TRAP IN A STORM DRAINAGE SYSTEM CONNECTED TO A COMBINED SEWER
Comment #1: The "10 feet downstream" requirement allows the sanitary discharge to stabilize before
mixing with the storm water flow. It also reduces the backpressure on the sanitary drainage system that
may be caused by heavy storm water discharges.
Comment #2: The horizontal wye connection between the two drainage systems permits the flows to mix
more uniformly without blocking the drain.
Comment: Double pattern wye fittings are not permitted to connect sanitary drains and storm drains to a
combined drain. This is to prevent a heavy flow in one drain branch from causing a backpressure in the
other drain branch.
Table 13.6.1
SIZE OF VERTICAL STORM WATER CONDUCTORS
Nominal Allowable Projected Roof Areas (sq ft)
Flow Capacity
Diameter at Various Rates of Rainfall per Hour (inches)
(GPM)
(inches) 1” 2” 3” 4” 5” 6”
2” 23 2,180 1,090 727 545 436 363
3” 67 6,426 3,213 2,142 1,607 1,285 1,071
4” 144 13,840 6,920 4,613 3,460 2,768 2,307
5” 261 25,094 12,547 8,365 6,273 5,019 4,182
6” 424 40,805 20,402 13,602 10,201 8,161 6,801
8” 913 87,878 43,939 29,293 21,970 17,576 14,646
10” 1655 159,334 79,667 53,111 39,834 31,867 26,556
12” 2692 259,095 129,548 86,365 64,774 51,819 43,183
15” 4880 469,771 234,886 156,590 117,443 93,954 78,295
7” 8” 9” 10” 11” 12”
2” 23 311 272 242 218 198 182
3” 67 918 803 714 643 584 536
4” 144 1,977 1,730 1,538 1,384 1,258 1,153
5” 261 3,585 3,137 2,788 2,509 2,281 2,091
6” 424 5,829 5,101 4,534 4,080 3,710 3,400
8” 913 12,554 10,985 9,764 8,788 7,989 7,323
10” 1655 22,762 19,917 17,704 15,933 14,485 13,277
12” 2692 37,014 32,387 28,788 25,910 23,554 21,591
15” 4880 67,110 58,721 52,197 46,977 42,706 39,146
13.9.1 Application
In lieu of sizing the storm drainage system on the basis of actual maximum projected roof areas as previously
described in this Chapter, the roof drainage system, or part thereof may be sized on equivalent or adjusted
maximum projected roof areas that result from controlled flow and storage of storm water on the roof pro-
vided flow control devices are used.
13.9.2 Design
A controlled flow storm water system shall be designed, installed, inspected and certified as an engineered
special design plumbing system as outlined in Appendix E of this Code.
Comment: Plumbing that is accessible to mental patients must be suicide-proof, vandal-proof, and
sound-proof. Piping is installed in chases that are not accessible to the patients. Special fixtures, such
as combination lavatory/toilets, are available for such applications. The fixtures are pushbutton operat-
ed to avoid faucet handles. Most fixtures are constructed of stainless steel. The plumbing fixtures used
in mental facilities are similar to those used in correctional institutions.
Figure 14.8
TYPES OF BEDPAN WASHERS
14.9.2 Material
Local vent piping shall be of a material acceptable for sanitary vents in accordance with Section 3.6.
14.10 STERILIZERS
14.10.1 General
The requirements of this Section apply to sterilizers and bedpan steamers. Such equipment shall be installed
in accordance with this Code and the manufacturer’s instructions.
14.11.2 Material
Sterilizer vapor vent piping shall be of a material acceptable for sanitary vents in accordance with Section
3.6.
14.12.2 Positive Pressure Drainage from Air/Waste Separators in Dental Vacuum Systems
a. The waste outlet from an air/waste separator on the discharge side of a vacuum pump or blower shall be
direct-connected to the sanitary drainage system through a deep-seal trap that is conventionally vented within
the plumbing system. The trap vent shall extend vertically to not less than 6 inches above the top of the separator
before making any horizontal turns. The vacuum exhaust air flow from the separator shall be separately vented
to outodoors as required under NFPA 99 and NFPA 99C.
b. The trap and drain branch size shall be at least two pipe sizes larger than the waste pipe from the separator,
but not less than 1-1/2" pipe size. The vent shall be the full size of the trap and drain. The trap seal shall be at
least two times the exhaust backpressure in the separator, but not less than 4 inches deep.
14.12.3 Gravity Drainage from Waste Holding Tanks in Dental Vacuum Systems
a. The drainage from waste holding tanks shall extend from the vacuum check valve on the waste outlet
of the tank and be direct-connected to the sanitary drainage system through a deep-seal trap that is conven-
tionally vented within the plumbing system. In addition, a vent shall be installed between the vacuum check
valve and the drain trap, on the inlet side of the trap, to seal the check valve when the holding tank is operat-
ing under vacuum and collecting waste. This vent shall be connected to the plumbing system vents. Both
vents shall extend vertically to not less than 6 inches above the top of the holding tank before making any
horizontal turns.
b. The trap and drain size shall be at least two pipe sizes larger than the waste outlet and vacuum check valve,
but not less than 2" pipe size. The trap shall be not less than 4 inches deep. The vent for the vacuum check
valve shall be not less than the size of the check valve. The trap vent shall be not less than one-half the size of
the trap and drain branch.
14.13 ASPIRATORS
Provisions for aspirators or other water-supplied suction devices shall be installed only with the specific approval
of the Authority Having Jurisdiction. Where aspirators are used for removing body fluids, they shall include a
collection bottle or similar fluid trap. Aspirators shall indirectly discharge to the sanitary drainage system through
an air gap, in accordance with Chapter 9. The potable water supply to an aspirator shall be protected by a vacuum
breaker or equivalent, in accordance with Sections 14.7 and 10.5.3.
15.3.2 Exceptions
a. When required by the Authority Having Jurisdiction, where an existing concealed sewer or drain is reused
as part of a new or renovated drainage system, the line shall be traced to its point of termination and shall be
tested to determine that:
1. It is connected to the proper drainage system, such as sanitary or storm,
2. It will withstand a leak test, and,
3. It is free-flowing and not restricted.
Comment: The smoke or peppermint tests on the finished plumbing can be waived by the Authority
Having Jurisdiction when they are considered to be unnecessary. However, the finished plumbing tests
should be performed if the installation appears to be improper or there is the odor of sewer gas.
15.8 MAINTENANCE
15.8.1 General
The plumbing and drainage systems shall be maintained at all times in compliance with the provisions of this
Code.
15.8.2 Exception
Existing plumbing installed under prior regulations or lack thereof, may remain unchanged unless immediate
hazards to health, life, or property are evident.
Comment: Federal and local environmental agencies have criteria for the allowable contaminant levels
that can be discharged into a water course or other point of discharge. Improper disposal of sewage can
result in; (1) contamination of public or private water supplies, (2) spread of disease by insects or ver-
min, (3) creation of objectionable odors, (4) pollution of public water resources, or (5) other conditions
that are detrimental to public health and safety.
Comment: This requirement applies to all abandoned dry wells, septic tanks, cesspools, distribution
boxes, seepage pits, and other structures that have handled sewage or sewage by-products.
Comment: The development of properties must be limited by the ability of the soil to absorb the effluent
of the required sewage disposal system. Bacterial action within the soil provides secondary treatment of
the effluent from septic tanks.
16.2 RESERVED
Comment #1: The primary factors in the design of private sewage disposal systems are; (1) the location
of the disposal system, (2) the absorption capacity of the soil, (3) the size of the drainage field, (4) the
size of the septic tank, (5) the elevation of the ground water table, (6) the location of water supplies for
the property and neighboring properties, (7) the use and population of the building(s) served, (8) the
topography of the property.
Comment #2: Problems with topography (elevation differences) can be overcome by sewage pumps,
which can pump to elements of the disposal system that are at higher elevations than others.
Comment: Storm water and foundation drains must not be connected to a private sewage disposal sys-
tem.
16.3.5 Backflow
Plumbing fixtures connected to a private sewage disposal system that are subject to backflow, shall be pro-
tected by a backwater valve or a sewage ejector.
Comment: Where plumbing fixtures connected to a private sewage disposal system are subject to back-
flow from a blockage in the disposal system, they must be protected by a backwater valve. Sewage pumps
and ejectors having check valves provide this protection for the fixtures that they serve.
16.3.6 Reserved
16.4.2 Reserved
Table 16.4.3
MINIMUM DISTANCE BETWEEN COMPONENTS
OF AN INDIVIDUAL SEWAGE DISPOSAL SYSTEM (in feet)1
Single
Shallow Deep Distribution Disposal Seepage Property
Suction Septic Tank Dry well Building
Well Well Box Field Pit Line
Line
Bldg. Sewer
other than 50 50 50 - - - - - - -
cast-iron
Bldg. Sewer
10 10 10 - - - - - - -
cast-iron
Septic Tank 100 50 50 - 5 10 10 10 10 10
Distribution
100 50 50 5 - - 5 5 10 20
Box
Disposal
100 50 50 10 5 - - - 10 20
Field
Seepage Pit 100 50 50 10 5 - - - 10 20
Deep Well - - - 50 50 50 50 50 - -
Suction Line - - - 50 50 50 50 50 - -
1
Minimum distances may be reduced if approved by the Authority Having Jurisdiction.
16.4.4 General
All sewage disposal systems shall conform with the following general principles regarding the site:
16.4.4.1 Location
Sewage disposal systems shall be located at the lowest point on the premises consistent with the
general layout topography and surroundings, including abutting lots. Locations at a higher elevation
through employment of a forced system may be used with the specific approval of the Authority Hav-
ing Jurisdiction.
16.4.4.2 Watersheds
Sewage disposal facilities shall not be located on any watershed for a public water supply system.
Comment: Determine the total daily sewage flow for the system from Table 16.3.7. Divide this number
by 100 and determine the required length of trenches in the disposal field from Table 16.5.4. Tile lengths
are limited to 100 feet by Section 16.9.4.
Comment: Observe safety requirements regarding sheeting, shoring, and bracing for deep excavations.
Comment: The absorption area of a seepage or leaching pit is the square foot area of the sidewalls. The
sidewall area = 3.1416 x diameter x depth (both in feet).
Table 16.5.6
REQUIRED ABSORPTION AREA IN SEEPAGE PITS FOR EACH
100 GALLONS OF SEWAGE PER DAY
Time in Minutes for 1-inch Drop Effective Absorption Area in Square Feet
1 32 sq ft/100 gpd
2 40 sq ft/100 gpd
3 45 sq ft/100 gpd
5 56 sq ft/100 gpd
10 75 sq ft/100 gpd
15 96 sq ft/100 gpd
20 108 sq ft/100 gpd
25 139 sq ft/100 gpd
30 167 sq ft/100 gpd
Comment: The septic tank sizes in Table 16.6.1 have allowances for sludge storage space and the use of
domestic food waste disposal units.
Table 16.6.1
CAPACITY OF SEPTIC TANKS
Single family dwelling- Multiple dwellings units or Other uses, maximum Minimum septic tank
number of bedrooms apartments-one bedroom each fixture units served capacity in gallons
1-3 20 1000
4 2 units 25 1200
5 or 6 3 33 1500
7 or 8 4 45 2000
5 55 2250
6 60 2500
7 70 2750
8 80 3000
9 90 3250
10 100 3500
Extra bedroom: 150 gallons each.
Extra dwelling units over 10: 250 gallons each.
Extra fixture units over 100: 25 gallons per fixture unit.
16.6.2 Reserved
Comment: Septic tanks with two compartments operate more efficiently than single-compartment tanks
at removing solids in the effluent. The liquid that enters the second compartment is already substantially
clarified. There is less turbulence in the second chamber, which permits finer suspended solids to settle
out.
Comment: Modern septic tanks are typically constructed of concrete (pre-cast), polyethylene, or fiber-
glass. Steel septic tanks are prohibited by many jurisdictions because of leakage due to corrosion.
Comment: Steel septic tanks are no longer approved by most jurisdictions because of leakage due to cor-
rosion. The average life expectancy of a steel septic tank is only 7 years.
16.6.5.1 Welding
All steel tanks shall be continuous welded. (No spot welding is permitted.)
16.6.5.3 Coatings
Metal tanks shall be coated inside and out with an approved coating.
16.6.5.4 Baffles
The inlet and outlet baffles shall be at least 12 inches in diameter at the point opposite the opening in
the tank.
16.6.5.9 Manhole
There shall be a 24 x 24-inch manhole held in position by four 3/8" bolts securely welded in place.
16.6.5.10 Partition
There shall be a supporting partition welded in the center of these tanks as per drawings.
16.6.6.2 Tops
The tops shall have a 24-inch manhole with handle to remove same, or be cast in three or four sections
cemented in place.
16.6.6.7 Watertight
The tank shall be watertight.
Comment: The typical depth of cover on the top of a septic tank is 12" - 18". Where the depth of cover
exceeds 36", the structural design of the tank must be adequate for the imposed earth loads.
16.6.8 Limitation
No septic tank shall serve more than one property unless authorized by the Authority Having Jurisdiction.
16.6.9 Effluent
The effluent from all septic tanks shall be disposed of underground by subsurface irrigation or seepage pits or
both.
Comment: The minimum distances from distribution boxes to the septic tank, disposal field, seepage pit,
dry well, potable water wells, or suction lines from potable water wells must be in accordance with Table
16.4.3.
16.7.4 Watertight
The distribution box shall be of watertight construction arranged to receive the septic tank effluent and have
an outlet or connecting line serving each trench or seepage pit.
16.7.5 Baffle
A baffle at least 6 inches high and 12 inches long shall rest on the bottom of the box and be placed at right
angles to the direction of the incoming tank effluent and 12 inches in front of it.
16.7.6 Reserved
16.7.7 Inspection
The sides of the box shall extend to within a short distance of the ground surface to permit inspection, and
shall have a concrete marker at grade.
16.8.4 Excavation
The excavation for a seepage pit shall be greater in diameter than the outside diameter of the vertical side-
walls to allow for the footing.
16.8.6 Construction
Seepage pits shall be constructed with the bottom being open with an outer ring, or footing, to support the
sidewalls.
Table 16.8.11
DESIGN OF SEEPAGE PIT COVERS
Reinforcing Steel Required in
Pit Diameter Pit Wall Thickness Cover Thickness Cover Weight
Two Perpendicular Directions
5ft. 4” 5” 1230 lb #5 @ 10-1/2” c/c
6ft. 8” 5” 1770 lb #5 @ 9” c/c
8ft. 8” 6” 3780 lb #5 @ 7-1/2” c/c
10ft. 8” 8” 7850 lb #5 @ 6-1/2” c/c
16.9.1 General
Absorption trenches shall be designed and constructed on the basis of the required effective percolation area.
Comment; Where the required length of trenches from Section 16.5.4 would require lateral tiles longer
than 100 feet, two or more laterals must be provided.
16.9.6 Grade
The trench bottom shall be uniformly graded to slope from a minimum of 2 inches to a maximum of 4 inches
per 100 feet.
16.10 RESERVED
Comment: Refer to Section 3.5 and Table 3.5 for approved materials for drainage piping. Refer to Sec-
tion 16.9.5 and Table 3.8 for approved materials for sub-soil drainage and absorption lines.
16.12.1.1 General
A sand filter shall consist of a bed of clean, graded sand on which septic tank effluent is distributed by
means of a siphon and pipe, with the effluent percolating through the bed to a series of underdrains
through which it passes to the point of disposal.
16.12.1.4 Siphon
The siphon shall be of a commercial type and shall discharge the effluent to the sand filter intermit-
tently. The siphon shall be omitted if a pump is used to lift the septic tank effluent to the sand filter.
16.12.1.6 Underdrains
Four-inch diameter vitrified clay pipe in 2-foot lengths laid with 1/2 inch open joints or unglazed farm
tile in 1-foot lengths laid with open joints, with the top half of each joint covered with 4-inch wide
strips of tar paper, burlap, or copper screen, or perforated bituminized-fiber pipe or other approved
material shall be used for the underdrains.
Comment: This chapter applies to private water supply systems serving one or more buildings
independent of any public water supply.
17.1.2 Pumps
Pumps shall be installed only in wells, springs and cisterns that comply with the rules and regulations as
determined by the Authority Having Jurisdiction.
Comment: A capacity of 1 GPM per fixture in a single dwelling unit is a rough rule of thumb.
The peak demand should be verified using Tables 10.14.2A and 10.14.2B. See Section 17.2.4
where well yields do not satisfy the peak demand.
Comment: See Section 10.14.3 for determining the peak demand on the potable water supply
system.
Comment: Table 16.3.7 indicates the daily design sewage flows from various establishments.
The available water supply must be able to satisfy this daily volume requirement, as well as the
peak GPM demand.
Comment: Where the primary potable water supply source cannot provide sufficient volume
to satisfy the 24-hour demand of the water distribution system, water storage facilities must be
provided.
17.3 PRESSURE
Pressure shall be as required in Section 10.14.3.b.
Comment: Private potable water supply systems must provide adequate pressure for fixtures to
deliver the flow rates for the various fixtures listed in Section 10.14.2.
Comment: See Sections 3.4.1 and 3.4.2 for general requirements. See Table 3.4 for approved
materials for water service piping.
17.6 PUMPS
17.6.1 Certified Pumps
Pumps shall be certified under Water Systems Council Rating and Rating Standards.
Comment #1: Well pumps for private water supplies include shallow well jet pumps, deep well
jet pumps, and submersible pumps.
Comment #2: Jet pumps circulate water through an ejector fitting that develops a vacuum and
draws water from the well. Shallow well jet pumps are used for wells less than 25 feet deep and
have the ejector fitting located outside of the well. Deep well jet pumps can be used for wells up
to 75 feet deep and have the ejector fitting located within the well casing. Some jet pumps are
convertible and can be used for either one-pipe shallow well or two-pipe deep well installations,
although their rated capacity is less for deep wells than for shallow wells.
Comment #3: Submersible well pumps are located at the bottom of the drop pipe within the
well casing. Submersible well pumps can lift water up to 500 feet or more.
17.6.2 Installation
Pumps shall be installed in accordance with the manufacturer’s recommendations.
17.8 CONTROLS
a. The following controls are required on all pump installations:
1. Pressure switch
2. Thermal overload switch
3. Pressure relief valve on positive displacement pumps
4. Low water cut-off switch where the pump capacity exceeds the source of water.
17.9.2.2 Installation
Installation shall be by threaded, welded or compression-gasketed connection to cutoff casing or at-
tachment to the exterior wall of the casing and shall be watertight.
17.9.3.2 Installation
The bell base of the pump shall be bolted with a gasket to a flange that is securely attached to the cas-
ing or pipe sleeve.
17.10 VENTS
17.10.1 Size
All vent piping shall be of adequate size to allow equalization of air pressure in the well and shall not be less
than one-half inch in diameter.
17.15.2 Limitations
No water supply shall serve more than one property unless authorized by the Authority Having Jurisdiction.
18.1 DEFINITIONS
Comment: The requirements of this chapter are intended as general requirements for parks and camp-
grounds that serve travel trailers, recreational vehicles, and mobile homes. Travel trailers and recre-
ational vehicles are used as temporary dwellings for travel or recreational purposes. Mobile homes
are movable structures or units that are designed as living quarters. The requirements of the Authority
Having Jurisdiction may vary for the different types of parks and campgrounds.
Service Buildings
A building housing toilet, laundry and any other such facilities as may be required.
Sewer Connection
Sewer connection is that portion of the drainage piping that extends as a single terminal under the trailer
coach for connection with the trailer park drainage system.
Trailer Coach
Any camp-car, trailer, or other vehicle with or without motive power, designed and constructed to travel on
the public thoroughfares in accordance with provisions of the Vehicle Code and designed or used for human
habitation.
Trailer Park
Any area or tract of land where space is rented or held-out for rent, or occupied by two or more trailer
coaches.
Trailer Site
That area set out by boundaries on which one trailer can be located.
18.2 STANDARDS
18.2.1 General
Plumbing systems hereafter installed in trailer home parks shall conform to the provisions set forth in the
preceding chapters of this Code, where applicable, and also to the provisions set forth in this Chapter. Trailer
home park plumbing and drainage systems shall, in addition, conform to all other applicable Authority Hav-
ing Jurisdiction regulations.
18.2.2.4 Conformance
Trailer park plumbing systems shall be designed and installed in accordance with the requirements of
this Code and shall, in addition, conform to all other pertinent local ordinances and State regulations.
18.2.3 Materials
Materials shall conform to the approved standards set forth in other sections of this Code.
18.3.2 Alternate
The trailer park drainage system may be installed by the use of a combination waste and vent drainage system
(see Section 12.17), which shall consist of an installation of waste piping, as hereinafter provided in this Sec-
tion, in which the traps for one or more trailer connection fixtures are not separately or independently vented,
but which is vented through the waste piping of such size to provide free circulation of air therein. See Sec-
tion 12.17 for combination waste and vent systems
18.3.5.2 Material
All traps, tail pipes, vertical vents, the upper five feet of any horizontal vent, and the first five feet of
any trap branch shall be fabricated from materials approved for use within a building. See Sections
3.5 and 3.6
18.3.6 Restriction
No vertical pipe shall be used in a special waste and vent system, except the vent pipe, and the connection to
the trailer connection fixture.
18.3.8 Cleanouts
Cleanouts shall be provided as required by Chapter 5 of this Code, except cleanouts shall be provided in the
vent stacks one foot above grade.
18.3.10 Slope
The grade on sewers shall provide a minimum velocity of two feet per second when the pipe is flowing half
full. See Table K-2 in Appendix K
18.3.11 Discharge
The discharge of the park drainage system shall be connected to a public sewer. Where a public sewer is not
available within 300 feet for use, an individual sewage disposal system of a type that is acceptable and ap-
proved by the Authority Having Jurisdiction shall be installed.
Comment: It is preferred that trailer parks be connected to public sewers, even if more than 300 feet
away. Trailer sites are typically densely spaced to maximize the use of the property, which leaves little
space for an adequate on-site sewage disposal system.
Table 18.3.12
DRAIN PIPE SIZING
Maximum Number of Trailers, Maximum Number of Trailers,
Size of Drain
Individually Vented Systems Wet-Vented Systems
2 1 3”
30 10 4”
100 50 6”
400 - 8”
1000 - 10”
18.4 VENTING
18.4.1 Location
Each wet-vented drainage system shall be provided with a vent not more than 15 feet downstream from its
upper trap, and long mains shall be provided with additional relief vents at intervals of not more than 100
feet thereafter. The minimum size of each vent serving a wet-vented system shall be as set forth in Table
18.4.1.
Table 18.4.1
VENT SIZING
Size of Wet-Vented Drain Minimum Size of Vent
3” 2”
4” 3”
5” 4”
6” 5”
18.4.2 Reserved
18.4.3 Reserved
18.4.4 Reserved
18.4.8 Reserved
18.6 RESERVED
18.7 TESTING
Installations shall be tested and inspected as required by this Code.
Comment: Dependent trailers are not equipped with a water closet and lavatory and are dependant on
the trailer park for such facilities.
Comment: Independent trailers are equipped with a water closet and lavatory and are not dependent on
the trailer park for such facilities.
Comment: Section 18.8.1.4 applies to trailer parks with combined trailer use, as in Section 18.8.1.3.
18.8.2 Exclusivity
Each toilet facility shall be for the exclusive use of the occupants of the trailer sites in the trailer park.
18.8.3 Showers
In every trailer park, shower bathing facilities with hot and cold running water shall be installed in separate
compartments. Every compartment shall be provided with a self-closing door or otherwise equipped with a
waterproof draw curtain.
18.9 MAINTENANCE
All required devices or safeguards shall be maintained in good working order. The owner, operator, or lessee of
the trailer park, or his designated agent shall be responsible for the maintenance.
Sizing Storm
Drainage Systems
1. Rainfall rates in Hawaiian Islands vary from 1.5 in/hr to 8.0 in/hr depending on location and elevation. Consult local data.
Proper design of the water-distributing system in a building is necessary to avoid excessive installed cost and in
order that the various fixtures may function properly under normal conditions. The instantaneous flow of either
hot or cold water in any building is variable, depending on the type of structure, usage, occupancy, and time of
day. The correct design results in piping, water heating, and storage facilities of sufficient capacity to meet the
probable peak demand without wasteful excess in either piping or maintenance cost.
For additional information on this subject, the reader is referred to:
National Bureau of Standards Building Materials and Structures Report BMS 65 (1940), Methods of Estimating
Loads in Plumbing Systems, by R. B. Hunter
National Bureau of Standards Building Materials and Structures Report BMS 79 (1941), Water-Distributing Sys-
tems for Buildings, by R. B. Hunter
New York State Division of Housing and Community Renewal Building Codes Bureau Technical Report No. 1,
(1964), A Simplified Method for Checking Sizes of Building Water Supply Systems, by Louis S. Nielsen.
B.2.7 Elevations
The relative elevations of the source of water supply and the highest water supply outlets to be supplied in
the building must be determined. In the case of a public main, the elevation of the point where the water
service connection is to be made to the public main should be obtained from the local water authority. It has
the most authoritative record of elevations of the various parts of the public system, and such elevations are
generally referred to a datum as the reference level, usually related to curb levels established for streets.
Elevation of the curb level directly in front of the building should be obtained from building plans, as such
information is required to be shown on the building site plans. Elevations of each floor on which fixtures are
to be supplied also may be determined from the building plans.
More recent faucets, however, are equipped with flow limiting devices that control the discharge rate at a nearly
constant value over a large range of pressures.
384 2009 National Standard Plumbing Code - Illustrated
Where necessary, it is recommended that means to control the rate of supply should be provided in the fixture sup-
ply pipe (or otherwise) wherever the available pressure at an outlet is more than twice the minimum pressure re-
quired for satisfactory supply. For this purpose, individual regulating valves, variable orifice flow control devices,
or fixed orifices may be provided. They should be designed or adjusted to control the rate of supply to be equal to
or less than the maximum rates set by law.
Table B.3
MAXIMUM DEMAND AT INDIVIDUAL WATER OUTLETS
Type of Outlet Maximum Demand, (gpm)
Metering lavatory faucet 0.25 gal/cycle
Public lavatory faucet 0.5 @ 60 psi
Drinking fountain jet 0.75
Private lavatory faucet 2.2 @ 60 psi
Kitchen sink faucet 2.2 @ 60 psi
Shower head 2.5 @ 80 psi
Ballcock in water closet flush tank 3.0
Dishwashing machine (domestic) 4.0
Laundry machine (8 or 16 lbs.) 4.0
Laundry sink faucet 5.0
Service sink faucet 5.0
Bath faucet, 1/2" 5.0
Hose bibb or sillcock (1/2") 5.0
1/2" flush valve (15 psi flow pressure) 15.0
1" flush valve (15 psi flow pressure) 27.0
1" flush valve (25 psi flow pressure) 35.0
NOTES:
1. The “total” WSFU values for fixtures represent their load on the water service. The separate cold water and hot water supply fixture
units for fixtures having both hot and cold connections are each taken as 3/4 of the listed total value for the individual fixture.
B.4 RESERVED
B.5 ESTIMATING DEMAND
Note that the concept of maximum probable demand is one of probability. We are saying, in effect, that the
calculated flow rate at any point in a water piping system will not be exceeded more than, say, 0.1% of the
time. For most systems designed by the method described herein, the design flow rates are never reached.
Therefore, the method gives a conservative approach that still does not result in wasteful oversizing.
2009 National Standard Plumbing Code - Illustrated 385
B.5.2 Water Supply Fixture Units (WSFU) Assigned to Fixtures
Individual fixture branch piping should be sized to provide the flow rates listed in Table B.3 for the particular
fixture. Minimum fixture branch pipe sizes are listed in Table B.5.2.
Peak demand in building water supply systems serving multiple fixtures cannot be determined exactly. The
demand imposed on a system by intermittently used fixtures is related to the number, type, time between
uses, and probable number of simultaneous uses of the fixtures installed in the building. In the standard
method, fixtures using water intermittently under several conditions of service are assigned specific load
values in terms of water supply fixture units. The water supply fixture unit (WSFU) is a factor so chosen that
the load-producing effects of different kinds of fixtures under their conditions of service can be expressed ap-
proximately as multiples of that factor. WSFUs for two or more fixtures can then be added to determine their
combined effect on the water supply system.
Values assigned to different kinds of fixtures and different types of occupancies are shown in Table B.5.2.
The total WSFUs represent the fixture’s demand on the domestic water service to the building. For fixtures
having both hot and cold water supplies, the values for separate hot and cold water demands are taken as
being three-quarters (3/4) of the total value assigned to the fixture in each case, rounded to the nearest tenth
of a WSFU. As an example, since the value assigned to a kitchen sink in an individual dwelling unit is 1.5
WSFU, the separate demands on the hot and cold water piping thereto are taken as being 1.1 WSFU.
Another consideration, added in 1994, is the nature of the application of the plumbing fixture. Table B.5.2 in-
cludes columns for Individual Dwelling Units, More Than 3 Dwelling Units, Other Than Dwelling Units, and
Heavy-Use Assembly. The concept behind these added classifications is that the maximum probable demand
created by plumbing fixtures varies depending on the type of occupancy in which they are installed.
1. National Bureau of Standards Building Materials and Structures Report BMS 6, Methods of Estimating Loads in Plumbing Systems, by R. B. Hunter.
NOTES:
1. The fixture branch pipe sizes in Table B.5.2 are the minimum allowable. Larger sizes may be necessary if the water supply pressure at the fixture will be too low due to the
available building supply pressure or the length of the fixture branch and other pressure losses in the distribution system.
2. Gravity tank water closets include the pump assisted and vacuum assisted types.
387
B.5.3 Water Supply Fixture Units for Groups of Fixtures
Table B.5.3 lists water supply fixture unit values for typical groups of fixtures in bathrooms, kitchens, and
laundries in dwelling units. There is more diversity in the use of the fixtures in these groups than is reflected
by WSFU values for the individual fixtures. The “Total WSFU” represents the demand that the group places
on the domestic water service to the building. The separate cold and hot WSFU’s for the group are each
taken as 3/4 of the WSFU values for the individual fixtures in the group according to Table B.5.3, but not
greater than the “Total WSFU” for the group. An exception is that the hot WSFU values for bathroom groups
having 3.5 GPF (or greater) water closets are the same as those having 1.6 GPF water closets, since the hot
WSFU’s are not affected by the demand of the water closet.
Note in the table that the maximum probable demand corresponding to a given number of water supply fix-
ture units is generally much higher for a system in which water closets are flushed by means of direct-supply
flushometer valves than for a system in which the water closets are flushed by other types of flushing devices.
The difference in maximum probable demand between the two systems diminishes as the total number of
fixture units of load rises. At 1,000 water supply fixture units, the maximum probable demand in both types
of systems is the same, 210 gpm.
Where a part of the system does not supply flushometer water closets, such as in the case with hot water sup-
ply piping and some cold water supply branches, the maximum probable demand corresponding to a given
number of water supply fixture units may be determined from the values given for a system in which water
closets are flushed by flush tanks.
Note that some continuous-flow outlets may be controlled to be used only during low-flow periods in the
system. Such time-controlled loads should not be added to the maximum probable demand for intermittently
used fixtures, since they will not occur at the same times. In such cases, it will be necessary to consider both
situations and size the piping for the worse case.
NOTES:
1. The “Total WSFU” values for fixture groups represent their load on the water service. The separate cold and hot water supply fixture units for the
group are each taken as 3/4 of the WSFU values for the individual fixtures in the group according to Table B.5.2, but not greater than the “Total WSFU” for the group in Table
B.5.3, except that the hot WSFU for groups having 3.5 GPF water closets are the same as those having 1.6 GPF water closets.
2. The WSFU values for tank-type water closets apply to gravity tanks and pressurized tanks, flushometer tanks (pressure assisted), pump assisted tanks, and vacuum as-
sisted tanks.
389
Table B.5.4
TABLE FOR CONVERTING DEMAND IN WSFU TO GPM1, 4
GPM GPM GPM GPM
WSFU 2 3 WSFU 2
Flush Tanks Flush Valves Flush Tanks Flush Valves 3
3 3 120 49 74
4 4 140 53 78
5 4.5 22 160 57 83
6 5 23 180 61 87
7 6 24 200 65 91
8 7 25 225 70 95
9 7.5 26 250 75 100
10 8 27 300 85 110
11 8.5 28 400 105 125
12 9 29 500 125 140
13 10 29.5 750 170 175
14 10.5 30 1000 210 210
15 11 31 1250 240 240
16 12 32 1500 270 270
17 12.5 33 1750 300 300
18 13 33.5 2000 325 325
19 13.5 34 2500 380 380
20 14 35 3000 435 435
25 17 38 4000 525 525
30 20 41 5000 600 600
40 25 47 6000 650 650
50 29 51 7000 700 700
60 33 55 8000 730 730
80 39 62 9000 760 760
100 44 68 10,000 790 790
NOTES:
1. This table converts water supply demands in water supply fixture units (WSFU) to required water flow in gallons per
minute (GPM) for the purpose of pipe sizing.
2. This column applies to the following portions of piping systems:
(a). Hot water piping;
(b). Cold water piping that serves no water closets; and
(c). Cold water piping that serves water closets other than flush valve type.
3. This column applies to portions of piping systems where the water closets are the flush valve type.
4. Refer to Appendix M for WSFU to GPM listings between those in Table B.5.4 to avoid the need to interpolate between
the values in Table B.5.4.
Note that this velocity is too great for systems where the flow is continuous, as in the case of recirculated hot
water piping. The continuous flow rate for hot water with modest chemical content should be limited to not
more than 2 fps for such continuous systems. That is, verify that the flow rate in the system as a result of the
circulation pump only does not exceed 2 fps at any point.
It is also recommended that maximum velocity be limited to 4 fps in water supply piping that supply a
quick-closing device, such as a solenoid valve, pneumatic valve, or a quick-closing valve or faucet of the
self-closing, push-pull, push-button, or other similar type. This limitation is necessary in order to avoid
excessive and damaging shock pressures in the piping and equipment when flow is suddenly shut off. Plumb-
ing equipment and systems are not designed to withstand the very high shock pressures that may occur as the
result of sudden cessation of high velocity flow in piping. (Also see Section 10.14.1)
To control erosion/corrosion effects in copper water tube, and copper and brass pipe, pipe manufacturers’
recommendations are as follows:
(1) Where the water supply has a pH value higher than 6.9 and a positive scale-forming tendency, such as
may be shown by a positive Langelier Index, peak velocity should be limited to 8 fps;
(2) Where the water supply has a pH value lower than 6.9 and may be classified as aggressively corro-
sive, or where the water supply has been softened to zero hardness by passage through a water softener, peak
velocity should be limited to 4 fps; and
(3) The velocity in copper tube conveying hot water at up to 140oF should be limited to 5 fps because of
the accelerated corrosion rate with hot water. Velocities should be limited to 2 - 3 fps for temperatures above
140o F.
Note that the above values apply to velocities at maximum probable demand. For continous flow circulating
systems, do not exceed 2 fps flow rate for the flow produced by the circulator.
B.7.1 Application
A simplified method for sizing building water supply systems in accordance with the maximum probable de-
mand load, in terms of water supply fixture units, has been found to constitute a complete and proper method
for adequately sizing the water supply systems of a specific category of buildings. In this category are all
buildings supplied from a source at which the minimum available water pressure is adequate for supplying
the highest and most remote fixtures satisfactorily during peak demand. Included are almost all one- and
two-family dwellings, most multiple dwellings up to at least three stories in height, and a considerable por-
tion of commercial and industrial buildings of limited height and area, when supplied from a source at which
the minimum available pressure is not less than 50 psi. Under such conditions, the available pressure gener-
ally is more than enough for overcoming static head and ordinary pipe friction losses, so that pipe friction is
not an additional factor to consider in sizing.
The pressure loss data in the B.7.3 tables is based on friction for straight pipe and tube and does not include
allowances for fittings, valves, and appurtenances. The equivalent length of the piping can be determined by
adding the equivalent length of fittings and valves in Tables B.9.7.A, B, C, D, and E. If the exact layout of the
piping systems cannot be determined, allowances for fittings and valves range up to 50% of the pipe length for
smooth bore piping such as copper and solvent cement joint plastic piping and up to 75% of the pipe length for
steel and plastic piping with threaded joints.
In Tables B.7.3.A through B.7.3.G, the columns headed “WSFU (tanks)” apply to piping that serves water closets
having gravity or pressure-type flush tanks and no fixtures that are flushed by flushometer valves. The columns
headed “WSFU (valves)” apply to piping that serves fixtures that are flushed by flushometer valves.
On each of the above-grade stories there are three dwelling units. Each dwelling unit has a sink and dish-
washer, tank-type water closet, lavatory, and bathtub/shower combination.
The basement contains two automatic clothes washing machines, two service sinks, and a restroom with a
flush-tank water closet and lavatory.
Two lawn faucets are installed, one on the front of the building and one in the rear.
Hot water is to be supplied from a central storage-tank water heater.
The water supply to the building will be metered at the water service entry point to the building.
An isometric drawing of the water piping layout is shown in Figure B.8.1.
398
PIPING
Copper water tube, Type L
wrought fittings and lead-free solder
WATER SUPPLY FIXTURE UNITS (WSFU)
PUBLIC WATER SUPPLY Piping Serving Piping Serving Piping Serving
10 inch main, 50 psig minimum pressure Fxtures Fitures in Fitures in 3 or Fitures in Other
1 or 2 Dwellings more Dwellings than Dwellings Units
WATER CHARACTERISTICS
Total Cold Hot Total Cold Hot Total Cold Hot
No significant fouling or corrosive agents
Bathroom Group (1.6 GPF tank-type WC) 5.0 5.0 3.8 3.5 3.5 3.0
ELEVATIONS Half Bath (1.6 GPF tank-type WC) 3.5 3.3 0.8 2.5 2.5 0.4
Curb as datum 10.0 ft Kitchen Group (sink & dishwasher) 2.0 1.1 2.0 1.5 0.8 1.5
Water main 6.0 ft
Clothes Washer 4.0 3.0 3.0
Basement floor 2.0 ft
First floor 12.0 ft Service Sink 3.0 2.3 2.3
Second floor 22.0 ft Hose Bibb 2.5 2.5
Third floor 32.0 ft Hose Bibb, each additional 1.0 1.0
Highest outlet @ “K” 35.0 ft
VELOCITY LIMITATIONS
8 fps WATER SERVICE PIPE SIZING
except 4 fps for branches with quick-closing valves
Fixtures Qty WSFU Total
and 5 fps for hot water up to 140 deg F
Bathroom Groups (1.6 tank-type WC) (1) 9 3.5 31.5
LENGTH OF RUN TO FARTHEST OUTLET Kitchen Groups (sink + dishwasher) (1) 9 1.5 13.5
Main - A 50 ft Clothes Washers (2) 2 4.0 8.0
A-B 12 ft
Service Sinks (2) 2 3.0 6.0
B-C 8 ft
C-D 10 ft Half Bath (2) 1 3.5 3.5
D-E 8 ft Hose Bibb (2) 1 2.5 2.5
E-F 8 ft Hose Bibb (each additional) (2) 1 1.0 1.0
F-G 10 ft
TOTAL WSFU 66.0
G-H 4 ft
H-I 10 ft DEMAND (GPM) 34.8
I-J 10 ft
J-K 10 ft 1) Fixtures in 3 or more dwellings
Total = 140 ft plus fitting allowance (2) Fixtures in other than dwelling units.
The sum of all friction losses due to flow through pipe, valves, and fittings is found to be 17.9 psi, whereas
the amount of excess pressure available for such friction loss is 19.4 psi. Thus, the sizes determined on the
basis of velocity limitations exclusively are proven adequate. Checking of friction loss in this case is per-
formed following steps 8 through 15 of the Detailed Sizing Method for Building of Any Height presented in
Section B.10. The calculations are shown on Figure B.8.2.
If this calculation had shown that the pressure drop was excessive at "K", it would be necessary to examine the design for sections of the
Basic Design Circuit that had the highest pressure drops and then increasse those segment pipe sizes.
Where water is supplied by direct pressure from a public main, to calculate the static pressure at the highest
outlet, deduct from the certified minimum pressure available in the public main the amount of static pressure
loss corresponding to the height at which the outlet is located above the public main (i.e., deduct 0.433 psi
pressure for each foot of rise in elevation from the public main to the highest outlet).
Where supplied under pressure from a gravity water supply tank located at an elevation above the highest
water outlet, the static pressure at that outlet is calculated as being equal to 0.433 psi pressure for each foot
of difference in elevation between the outlet and the water level in the tank. In this case, the minimum static
pressure at the outlet should be determined as that corresponding to the level of the lowest water level at
which the tank is intended to operate.
This circuit is called the Basic Design Circuit (BDC) for sizing the main water lines and risers.
In most systems, the BDC will be found to be the run of cold water supply piping extending from the source
of supply to the domestic hot water vessel plus the run of hot water supply piping extending to the highest
and most remote hot water outlet on the system. However, in systems supplied directly from the public main
and having flushometer-valve water closets at the topmost floor, the BDC may be found to be the run of cold
water supply piping extending from the public main to the highest and most remote flushometer valve in the
system.
5/8" 20 gpm
3/4" 30 gpm
1" 50 gpm
1-1/2" 100 gpm
2" 160 gpm
3" 300 gpm
Also, the standard establishes the maximum pressure loss corresponding to these maximum capacities as fol-
lows:
15 psi for the 5/8", 3/4" and 1" meter sizes
20 psi for the 1-1/2", 2", 3", 4" and 6" sizes.
As a general finding, it has been shown by experience that the equivalent length to be allowed for fittings and
valves as a result of such calculations is approximately fifty percent of the developed length of the BDC in
the case of copper water tube systems, and approximately seventy-five percent for standard threaded pipe
systems.
Table B.9.7.B
EQUIVALENT LENGTH OF PIPE FOR FRICTION LOSS IN COPPER TUBE FITTINGS &VALVES
Equivalent Feet of Pipe for Various Tube Sizes
Fitting or Valve
1/2” 3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4” 5” 6”
45 deg Elbow 0.5 0.5 1.0 1.0 1.5 2.0 2.5 3.5 5.0 6.0 7.0
90 deg Elbow, std 1.0 2.0 2.5 3.0 4.0 5.5 7.0 9.0 12.5 16.0 19.0
Tee, run 0.0 0.0 0.0 0.5 0.5 0.5 0.5 1.0 1.0 1.5 2.0
Tee, Branch 2.0 3.0 4.5 5.5 7.0 9.0 12.0 15.0 21.0 27.0 34.0
Gate Valve 0.0 0.0 0.0 0.0 0.0 0.5 1.0 1.5 2.0 3.0 3.5
Globe Valve 17.6 23.3 29.7 39.1 45.6 58.6 70.0 86.9 114.0 143.0
Angle Valve 0.0 0.0 0.5 0.5 0.5 0.5 0.0 0.0 0.0 0.0 0.0
Butterfly Valve 7.8 10.3 13.1 17.3 20.1 25.8 30.9 38.4 50.3 63.1 75.8
Swing Check Valve 7.5 10.0 15.5 16.0 11.5 13.5
Fitting or Valve 2.0 3.0 4.5 5.5 6.5 9.0 11.5 14.5 18.5 23.5 26.5
NOTES FOR TABLE B.9.7.B
1) Equivalent lengths for valves are based on the valves being wide open.
2) Data based in part on the 2004 Copper Tube Handbook by the Copper Development Association.
Table B.9.7.C
EQUIVALENT LENGTH OF PIPE FOR FRICTION LOSS IN SCHEDULE 40 CPVC FITTINGS
Equivalent Feet of Pipe for Various Pipe Sizes
Fitting
1/2” 3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4” 5” 6”
45 deg Elbow 0.8 1.1 1.4 1.8 2.1 2.7 3.3 4.1 5.3 6.7 8.0
90 deg Elbow 1.5 2.0 2.6 3.4 4.0 5.1 6.1 7.6 12.5 15.1
Tee, Run 1.0 1.4 1.7 2.3 2.7 3.4 4.1 5.1 6.7 8.4 10.1
Tee, Branch 3.0 4.1 5.2 6.8 8.0 10.2 12.2 15.2 25.1 30.2
Table B.9.7.E
EQUIVALENT LENGTH OF PIPE
FOR FRICTION LOSS IN CPVC SDR 11 CTS TUBING FITTINGS
Equivalent Feet of Pipe for Various Pipe Sizes
Fitting
1/2” CTS 3/4” CTS 1” CTS 1-1/4” CTS 1-1/2” CTS 2” CTS
45 deg Elbow 0.8 1.1 1.4 1.8 2.2 2.8
90 deg Elbow 1.6 2.1 2.6 3.5 4.0 5.2
Tee, Run 1.0 1.4 1.8 2.3 2.7 3.5
Tee, Branch 3.1 4.1 5.3 6.9 8.1 10.3
These charts are based on piping in average service. If piping is used in adverse service or in retrofit applica-
tions, conservative practice suggests selecting lower flow rates for a given pipe, or larger pipe for a given
required flow rate.
For new work, with the range of materials now available, select a piping material that will not be affected by
the water characteristics at the site.
The water supply is to be metered by a meter through which flow at the maximum probable demand rate will
produce a pressure drop of 5.6 psi. Copper tubing, Type L, is to be used for the entire system. Quality of the
water supply is known to be noncorrosive to copper tubing in the water district, and is recognized as being
non-scaling in characteristic.
The entire system has been initially sized in accordance with the simplified method based solely on velocity
limitations. Applying these sizes, the total equivalent length of piping from the public main to the highest and
most remote fixture outlet has been calculated to be 600'.
B.11.2 Solution
Steps 1-7. The first seven steps of the detailed sizing method have already been performed. These steps
constitute the simplified sizing method based solely on velocity limitations established as the design basis.
All that remains is to perform steps 8 through 15 of the detailed sizing method which relate to sizing in
accordance with the frictional limitation which must be observed for this particular system, and with allow-
ances which may be necessary in view of the water characteristics.
Step 8. Assuming conditions of no-flow in the system, the amount of excess pressure available at the top-
most fixture in excess of the minimum required at the fixture for satisfactory supply conditions is determined
as follows:
Excess pressure available = 60 psi - 12 psi - (64.67 x 0.4333 psi/ft) = 20 psi
Step 9. The BDC should be specifically identified on the schematic elevation provided as per step 2.
Step 10. The pressure loss through the water meter selected for this system for flow at maximum probable
demand is given in the example as being 5.6 psi. No other items of equipment through which significant fric-
tion losses may occur have been noted in the example.
Step 11. The amount of pressure remaining for dissipation as friction loss during peak demand through
pipes, valves, and fittings in the basic design circuit is determined as follows:
Table B.11.2
TYPE L COPPER TUBING, FOR "FAIRLY SMOOTH" CONDITION
Nominal Pipe Size Flow Rate Corresponding to Friction Loss of
(in) 2-4 psi/100' (gpm)
1/2 1.4
3/4 3.9
1 7.5
1-1/4 14.0
1-1/2 21.0
2 47.0
2-1/2 78.0
3 130.0
4 270.0
B.12.1 Manifolds
The total water supply demand for the dwelling shall be determined in accordance with Section 10.14 and
Appendix B.5. Manifolds shall be sized according to Table B.12.1 based on the total supply demand.
Table B.12.1
MANIFOLD SIZING1
Nominal Size Maximum GPM Available @ Velocity
Inches @ 4 fps @ 8 fps @ 10 fps
1/2 2 5 6
3/4 6 11 14
1 10 20 25
1-1/4 15 31 38
1-1/2 22 44 55
1
Refer to Section 10.14 for maximum velocity permitted.
Conversions:
Metric to U.S. Customery Units
LENGTH
1 millimeter = 0.03937 inches
100 millimeters = 3.937 inches
1000 millimeters = 39.37 inches
1 meter = 3.2808 feet
AREA
1 square meter = 10.764 square feet
VOLUME
1 liter (L) = 0.2642 gallons (U.S.)
10 liters (L) = 2.642 gallons (U.S.)
VELOCITY
1 meter per second (m/s) = 3.2808 feet per second (ft/s)
FLOW
1 liter per minute (L/min) = 0.2642 gallons per minute (GPM)
10 liters per minute (L/min) = 2.642 gallons per minute (GPM)
PRESSURE
1 kilopascal (kPa) = 0.145 pounds per square inch (PSI)
10 kilopascals (kPa) = 1.45 pounds per square inch (PSI)
TEMPERATURE
Deg C Deg F
0C 32 F
5C 41 F
10 C 50 F
15 C 59 F
20 C 68 F
25 C 77 F
30 C 86 F
35 C 95 F
40 C 104 F
45 C 113 F CONVERTING WSFU DEMAND
50 C 122 F TO LITERS PER MINUTE (L/min) FLOW
55 C 131 F Flush Tanks Flush Valves Flush Tanks Flush Valves
60 C 140 F WSFU WSFU
L/min L/min L/min L/min
65 C 149 F 3 11 120 186 280
70 C 158 F 4 15 140 201 295
75 C 167 F 5 17 83 160 216 314
80 C 176 F 6 19 87 180 231 329
85 C 185 F 7 23 91 200 246 345
90 C 194 F 8 27 95 225 265 360
95 C 203 F 9 28 98 250 284 379
100 C 212 F 10 30 102 300 322 416
11 32 106 400 398 473
12 34 110 500 473 530
PIPE SIZES
13 38 112 750 644 662
mm NPS
14 40 114 1000 795 795
15 1/2
15 42 117 1250 909 909
20 3/4
16 45 121 1500 1022 1022
25 1
17 47 125 1750 1136 1136
32 1-1/4
18 49 127 2000 1230 1230
40 1-1/2
19 51 129 2500 1438 1438
50 2
20 53 133 3000 1647 1647
65 2-1/2
25 64 144 4000 1987 1987
80 3
30 76 155 5000 2271 2271
100 4
40 95 178 6000 2460 2460
125 5
50 110 193 7000 2650 2650
150 6
60 125 208 8000 2763 2763
200 8
80 148 235 9000 2877 2877
250 10
100 167 257 10,000 2990 2990
300 12
EXAMPLE A
Since the given population is based on egress requirements, the population for plumbing purposes can be 2/3 of
that value (Section 7.21.2.b). The ratio of male and female occupants can be assumed to be 50% each (Section
7.21.2.c).
The minimum required number of plumbing fixtures is determined from Table 7.21.1 under No. 1 Assembly
The number of males and females are greater than the numerical groups listed in Table 7.21.1. To determine the
total number of fixtures required, calculate the number of fixtures required by the listed numerical groups and then
determine how many additional groups of 300 there are over the first 300.
The listed numerical groups account for the first 300 males.
The additional groups of 300 = (953-300) divided by 300 per group = 2.18 = 3 groups.
The listed numerical groups account for the first 300 females.
The additional groups of 300 = (953-300) divided by 300 per group = 2.18 = 3 groups
Male Lavatories
first 50 men (1-50) = 1 lavatory
next 50 men (51-100) = 0 lavatories
next 100 men (101-200) = 1 lavatory
next 100 men (201-300) = 0 lavatories
add 1 lavatory for each additional group of 300 over 300 (or parts thereof)
The listed numerical groups account for the first 300 males.
The additional groups of 300 = (953-300) divided by 300 per group = 2.18 = 3 groups
Female Lavatories
first 50 females (1-50) = 1 lavatory
next 50 females (51-100) = 1 lavatory
next 100 females (101-200) = 1 lavatory
next 100 females (201-300) = 1 lavatories
add 2 lavatories for each group of 300 over 300 (or parts thereof)
The listed numerical groups account for the first 300 females.
The additional groups of 300 = (953-300) divided by 300 per group = 2.18 = 3 groups
Service Sinks
Table 7.21.1 requires a minimum of 1 per floor.
The minimum required number of plumbing fixtures is determined from Table 7.21.1 under No. 2 Business.
The number of males and females are greater than the numerical groups listed in Table 7.21.1. To determine the
total number of fixtures required, calculate the number of fixtures required by the listed numerical groups and then
determine how many additional groups of 60 there are over the first 75.
The listed numerical groups account for the first 300 males.
The additional groups of 300 = (953-300) divided by 300 per group = 2.18 = 3 groups.
Male Lavatories
first 50 men (1-50) = 1 lavatory
next 50 men (51-100) = 1 lavatory
next 100 men (101-200) = 2 lavatories
next 100 men (201-300) = 2 lavatories
The listed numerical groups account for the first 300 males.
The additional groups of 300 = (953-300) divided by 300 per group = 2.18 = 3 groups
Female Lavatories
first 15 females (1-15) = 1 lavatory
next 25 females (16-40) = add 1 lavatory
next 35 females (41-75) = add 1 lavatory
add 2 for each additional group of 60 over 75 (or parts thereof)
Service Sinks
Table 7.21.1 requires a minimum of 1 per floor.
Special Design
Plumbing Systems
E.1 GENERAL REQUIREMENTS
E.1.1 Special design plumbing systems shall include all systems that vary in detail from the requirements of
this Code.
E.1.2 The provisions of this Appendix shall control the design, installation, and inspection of special design
plumbing systems.
E.1.3 Special design plumbing systems shall conform to the Basic Principles of this Code.
E.1.4 Special design plumbing systems shall be designed by a registered design professional who is licensed
to practice in the particular jurisdiction.
E.1.5 The requirements of Section E.1, E.2, E.3, and E.4 shall apply to all special plumbing systems in this
Appendix E
E.2.2 The design plans shall indicate that the plumbing system (or portions thereof) is a special design
system.
E.3.2 The installation shall comply with Chapter 2 - General Regulations and other applicable requirements
of this Code.
E.4.2 The complete installation and performance of the special design plumbing system shall be certified
by the registered design professional as complying with the requirements of the special design.
E.5.1.2 Fixtures
Gravity type fixtures used in vacuum drainage systems shall comply with Chapter 7 of this Code.
E.5.1.6 Materials
Vacuum drainage pipe, fittings and valve materials shall be as recommended by the vacuum drainage
system manufacturer and as permitted by this Code.
1. NP = not permitted
2. Not more than two (2) water closets are permitted on a 3" stack.
E.8.2.1 Branch, circuit, common, continuous, and individual vents shall be permitted to terminate with a
connection to an individual or branch type air admittance valve complying with ASSE 1051. Individual
and branch type air admittance valves shall only vent fixtures that are on the same floor level and connect
to a horizontal branch drain.
E.8.2.2 Vent stacks and stack vents shall be permitted to terminate at a stack type air admittance valve
complying with ASSE 1050.
EXCEPTIONS
(1) Vent stacks and stack vents serving drainage stacks that exceed six (6) branch intervals in height.
(2) Vent stacks and stack vents that serve relief vents in Section E.8.3.
E.8.2.3 Air admittance valves shall not be permitted in the following applications:
a. vents for special waste drainage systems (Sections 9.4.1 and 9.4.2).
b. vents for sewage pump or ejector sump pits.
c. vents for pneumatic sewage ejectors.
d. suds pressure zone venting.
e. relief vents required by Section E.8.3.1.
E.8.3.1 A relief vent shall be provided where a horizontal branch drain that is vented by one or more air
admittance valves connects to a drainage stack more than four (4) branch intervals from the top of the stack.
The relief vent shall connect vertically to the horizontal branch drain between the drainage stack and the
most downstream fixture drain connection on the horizontal branch drain. Relief vents shall extend from
the horizontal branch drain to a vent stack, stack vent, or other vent that terminates outdoors in open air.
E.8.3.2 Relief vents shall be the full size of the horizontal branch drain that they serve, up to 3" maximum
required size.
E.8.3.3 Relief vents shall be permitted to vent fixtures other than those on the horizontal branch drain be-
ing relieved.
E.8.4 Installation
E.8.4.1 Air admittance valves shall be installed in accordance with the manufacturer’s instructions and
Section E.8.
E.8.4.2 Air admittance valves shall connect to fixture trap arms within the maximum allowable trap arm
lengths in Table 12.8.1.
E.8.4.3 Individual and branch type air admittance valves shall be installed at least 4 inches above the top
of the trap arm or horizontal branch drain that they serve.
E.8.4.4 Stack type air admittance valves shall be installed at least 6 inches above the flood level rim of the
highest fixture served by the valve.
E.8.4.5 Air admittance valves shall be installed in accessible locations having free movement of air to enter
the valve.
E.8.4.6 Air admittance valves shall not be installed in HVAC supply or return air plenums or other areas
subject to other than atmospheric pressure.
E.8.4.7 Air admittance valves installed in insulated attic or ceiling spaces shall be installed in free air at
least six inches above the insulation.
E.8.4.8 Air admittance valves shall be the same size as the vent pipe to which they are connected.
E.8.4.9 Air admittance valves shall not be installed until all required leak tests of the drainage and vent
piping are successfully completed.
E.8.5.1 Where a plumbing drainage system is vented by one or more air admittance valves, at least one vent
pipe shall extend to an outdoor vent terminal complying with Section 12.4. Outdoor venting shall comply
with either Section E.8.5.2 or E.8.5.3.
E.8.5.3 Where the aggregate size of outdoor vent terminals does not comply with Section E.8.5.2, a dry
vent, sized according to Table 12.16, shall be provided downstream from the last fixture connection, branch
connection, or stack connection to the building drain before the connection of the building drain to the
building sewer.
Requirements of the
Adopting Agency
F.1 GENERAL
This Code does not include specific requirements in certain cases where local practices may vary from one ju-
risdiction to another. This appendix lists those sections of this Code where the Adopting Agency must establish
requirements. Adopting agencies should review the sections listed under Appendix F.2.
F.2 REFERENCES
1.4.8: Appendicies
2.16.1: Minimum earth cover for water service pipe.
2.16.2: Minimum earth cover for building sewers.
2.19.1: Distance for required connections to public water supplies and sewers.
2.19.2: Standards and requirements for private water and sewage disposal systems.
2.26 Elevator Pits
10.9.2: Disinfecting water piping.
11.7.6: Use of grinder pumps.
15.3.1: Testing new plumbing work.
15.3.2: Testing existing sewers and drains.
16.1: State or local requirements for private sewage disposal systems.
Chapter 18: Mobile home and travel trailer park plumbing requirements.
G.2 DEFINITIONS
Biological Treatment: A method of wastewater treatment in which bacterial or biochemical action is intensi-
fied as a means of producing an oxidized wastewater.
Black Water: Used untreated water that is flushed down toilets and urinals. This water cannot be directly
reused.
Effluent: Partially or completely treated liquid waste discharge from a wastewater treatment system.
Graywater: Used untreated water generated by clothes washing machines, showers, bathtubs and lavatories.
It shall not include water from kitchen sinks or dishwashers.
Reclaimed Water: Effluent from a wastewater treatment facility that has been subjected to extensive treat-
ment in order to remove organic material, heavy metals, and harmful pathogens (such as bacteria, viruses,
and protozoa). Reclaimed water is non-potable.
Septic Tank: A water-tight receptacle that receives the discharge of a building sanitary drainage system or
part thereof, and is designed and constructed so as to separate solids from the liquid, digest organic matter
through a period of detention, and allow the liquids to discharge into the soil outside of the tank through a
system of open joint or perforated piping, or a seepage pit.
Wastewater: The combination of liquid and water-carried pollutants from residences, commercial buildings,
industrial plants, and institutions.
G.7.1
Disinfection techniques shall be chosen with regards to the compatibility of the materials used in the pipes,
fittings, tanks and other equipment in the system.
G.10 TESTING
a. All applicable sections of this appendix shall conform to the body of this Code. Installation of the gray-
water system shall conform in all aspects to the manufacturers recommended installation procedures.
b. Systems shall be tested and comply with the requirements of the Authority Having Jurisdiction. Piping,
valves, and fittings shall be tested in compliance with Chapter 15 of this Code.
G.11 MAINTENANCE
The graywater system shall be maintained in accordance with the manufacturers recommended maintenance
instructions.
INSTALLATION OF
MEDICAL GAS
AND VACUUM PIPING
SYSTEMS
Chart I.1(a)
Chart I.1(b)
Chart I.1(c)
Chart I.2(a)
Chart I.2(b)
Reserved
Flow In
Sloping Drains
The minimum flow velocity to achieve scouring in horizontal sanitary drain lines is two (2) feet per second.
For this reason, based on Table K-2 for smooth pipe, drains that are 2 inches and smaller must be sloped at
not less than 1/4 inch per foot. Drains that are 3" size and larger can be sloped at 1/8 inch per foot.
Even at 1/4" per foot slope, the uniform velocity in drains that are 1-1/4", 1-1/2", and 2" size is less than 2
feet per second. Either the slope should be increased or the length of such drains should be kept to a mini-
mum so that the entrance velocity will provide scouring for the short distance involved.
Tables K-1 and K-2 are based on the Manning Formula for 1/2 full pipe. For full flow, multiply the flow by
2.00 and the velocity by 1.00. For 1/4 full flow, multiply the flow by 0.274 and the velocity by 0.701. For 3/4
full flow, multiply the flow by 1.82 and the velocity by 1.13.
In Table K-l, which is based on fairly rough pipe with "n" = 0.015, for smoother pipe, multiply the flow and
velocity by 0.015 and divide by the "n" value of the smoother pipe.
Horizontal sanitary drain and waste pipes are sized to be one-half (1/2) full under design loads. Horizontal
storm drains are sized to run full under design loads.
Table 11.5.1A Building Drains and Sewers and the horizontal piping in Table 11.5.1B "Horizontal Fixture
Branches and Stacks" is based on Table K-2 for smooth pipe.
Table 13.6.2 "Size of Horizontal Storm Drains" is based on Table K-1 for fairly rough pipe, adjusted for full
flow.
An Acceptable Brazing
Procedure for General
Plumbing
Introduction
Strong, leak-tight brazed connections for copper tube may be made by brazing with filler metals which melt at
temperatures in the range between 1100 F and 1500 F, as listed in Table 12. Brazing filler metals are sometimes
referred to as hard solders or silver solders. These confusing terms should be avoided.
The temperature at which a filler metal starts to melt on heating is the solidus temperature; the liquidus tempera-
ture is the higher temperature at which the filler metal is completely melted. The liquidus temperature is the mini-
mum temperature at which brazing will take place.
The difference between solidus and liquidus is the melting range and may be of importance when selecting a filler
metal. It indicates the width of the working range for the alloy and the speed with which the a1loy will become
fully solid after brazing. Filler metals with narrow ranges, with or without silver, solidify more quickly and, there-
fore, require more careful application of heat. The melting ranges of common brazing metals are shown in Figure
8a.
Brazing filler metals suitable for joining copper tube are of two classes:
(1) alloys that contain phosphorus (the BCuP series) and
(2) alloys containing a high silver content (the BAg series)
The two classes differ in their melting, fluxing and flowing characteristics and this should be considered in selec-
tion of a filler metal. (See Table 12.) For joining copper tube, any of these filler metals will provide the necessary
strength when used with standard solder-type fittings or commercially available short-cup brazing fittings.
Fluxes
The fluxes used for brazing copper joints are different in composition from soldering fluxes. The two types cannot
be used interchangeably.
Brazing fluxes are water based, whereas most soldering fluxes are petroleum based. Similar to soldering fluxes,
brazing fluxes dissolve and remove residual oxides from the metal surface, protect the metal from re-oxidation
during heating and promote wetting of the surfaces to be joined by the brazing filler metal.
Fluxes also provide the craftsman with an indication of temperature. If the outside of the fitting and the heat-
affected area of the tube are covered with flux (in addition to the end of the tube and the cup), oxidation will be
prevented and the appearance of the joint will be greatly improved.
The fluxes best suited for brazing copper and copper alloy tube should meet AWS Classification FB3-A or FB3-C
as listed in Table 4.1 of the AWS Brazing Handbook. Figure 9, illustrates the need for brazing flux with different
types of copper and copper-alloy tube, fittings and filler metals when brazing.
Assemble the joint by inserting the tube into the socket hard against the stop and turn if possible. The assembly
should be firmly supported so that it will remain in alignment during the brazing operation.
Step one: Apply heat to the parts to be joined, preferably with an oxy-fuel flame. Air-fuel is sometimes used on
smaller sizes. A neutral flame should be used. Heat the tube first, beginning about one inch from the edge of the
fitting, sweeping the flame around the tube in short strokes at right angles to the axis of the tube.
It is very important that the flame be in motion continuously and not remain on anyone point long enough to dam-
age the tube. The flux may be used as a guide as to how long to heat the tube; continue heating the tube until the
flux becomes quiet and transparent like clear water. The behavior of flux during the brazing cycle is described in
Figure 8b.
Step two: Switch the flame to the fitting at the base of the cup. Heat uniformly, sweeping the flame from the fit-
ting to the tube until the flux on the fitting becomes quiet. Avoid excessive heating of cast fittings.
Step three: When the flux appears liquid and transparent on both the tube and fitting, start sweeping the flame
back and forth along the axis of the joint to maintain heat on the parts to be joined, especially toward the base of
the cup of the fitting. The flame must be kept moving to avoid melting the tube or fitting.
Step four: Apply the brazing filler metal at a point where the tube enters the socket of the fitting. When the
proper temperature is reached, the filler metal will flow readily into the space between the tube and fitting socket,
drawn in by the natural force of capillary action.
Keep the flame away from the filler metal itself as it is fed into the joint. The temperature of the tube and fitting at
the joint should be high enough to melt the filler metal.
Keep both the fitting and tube heated by moving the flame back and forth from one to the other as the filler metal
is drawn into the joint.
When the joint is properly made, a continuous fillet of filler metal will be visible completely around the joint. Stop
feeding as soon as you see that fillet. Table 11 is a guide to estimating how much filler metal will be consumed.
For 1-inch tube and larger it may be difficult to bring the whole joint up to heat at one time. It frequently will
be found desirable to use a multiple-orifice torch tip to maintain a proper temperature over large areas. A mild
preheating of the whole fitting is recommended for larger sizes. Heating then can proceed as outlined in the steps
above.
When brazing horizontal joints, it is preferable to first apply the filler metal at the bottom, then the two
sides, and finally the top, making sure the operations overlap. On vertical joints it is immaterial where
the start is made. If the opening of the socket is pointing down, care should be taken to avoid overheat-
ing the tube, as this may cause the brazing filler metal to run down the outside of the tube. If this hap-
pens, take the heat away and allow the filler metal to set. Then reheat the cup of the fitting to draw up the
filler metal.
After the brazed joint has cooled the flux residue should be removed with a clean cloth, brush or swab using warm
water. Remove all flux residue to avoid the risk of the hardened flux temporarily retaining pressure and masking
an imperfectly brazed joint. Wrought fittings may be cooled more readily than cast fittings, but all fittings should
be allowed to cool naturally before wetting.
If the filler metal fails to flow or has a tendency to ball up, it indicates oxidation on the metal surfaces or insuf-
ficient heat on the parts to be joined. If the tube or fitting start to oxidize during heating there is too little flux. If
the filler metal does not enter the joint and tends to flow over the outside of either member of the joint, it indicates
that one member is overheated or the other is under heated.
Testing
Test all completed assemblies for joint integrity. Follow the testing procedure prescribed by applicable codes gov-
erning the intended service.
Table 12
Filler Metals for Brazing
AWS Principal Elements Temperature F
Classification¹ Silver Phosphorus Zinc Cadmium Tin Copper Solidus Liquidus
Footnote 1
The amount of filler material indicated is based on an average two-thirds penetration of the cup and with no provision
for a fillet. For estimating purposes, actual consumption may be two to three times the amounts indicated in this table,
depending on the size of the joints, method of application and level of workmanship.
NOTE:
1090 inches of 1/16 inch wire = 1 pound
534 inches of 1/8 inch x .050-inch wire = 1 pound
484 inches of 3/32 inch wire = 1 pound
268 inches of 1/8 inch wire = 1 pound
INTRODUCTION
The water supply fixture unit (WSFU) values in this Appendix are interpolated between the values listed in Table
10.14.2.B to the degree that the increments between the WSFU listings are close enough that they do not produce
GPM differences that will be significant in sizing the water supply distribution piping.