Scope:
The design, development and order entry of:
- High, medium and low voltage products and accessories for sensing, terminating, connecting
and protecting of electrical cables, components and equipment.
- A family of powder and liquid products for electrical insulation and infrastructure corrosion
protection.
- A family of film, tapes, and coatings used in the manufacture and maintenance of solar
modules and wind turbines.
Through an audit, documented in a report, it was verified that the management system
fulfills the requirements of the following standard:
DQS Inc.
Brad McGuire
Managing Director
Accredited Body: DQS Inc., 1500 McConnor Parkway, Suite 400, Schaumburg, IL 60173 USA 1/2
Annex to certificate
Registration No. 10001720 QM15
3M Company
Electrical Markets Division
Business Center Division Science Center Division
13011 McCallen Pass 507 E. Howard Lane
Bldg C Bldg C
Austin, TX 78753 Austin, TX 78753
United States of America United States of America
Reference No. 10017609 Reference No. 10017609
Location Scope
10004719
3M Company The design, development and order entry of:
Electrical Markets Division - High, medium and low voltage products and accessories for
3M Center sensing, terminating, connecting and protecting of electrical
Maplewood, MN 55144 cables, components and equipment.
United States of America - A family of powder and liquid products for electrical
insulation and infrastructure corrosion protection.
- A family of film, tapes, and coatings used in the manufacture
and maintenance of solar modules and wind turbines.
These cold shrink terminations are lightweight for either free-hanging or bracket mounting
arrangements. 3M offers you two options for choosing a cold shrink termination. The QT- III
termination utilizes the latest technology with built-in Hi-K stress controlling mastic and
environmental sealing mastic resulting in a much more user-friendly application that reduces
chances of errors.
3M™ Cold Shrink QT-II and QT-III Terminations are designed using 3M developed track-
resistant silicone rubber and Hi-K stress control material in conjunction with 3M’s unique cold
shrink delivery system.
Terminations are supplied prestretched on a removable core. Removal of the core by unwinding
after positioning the termination allows the product to shrink into position, providing a living seal.
QT-II and QT-III cold shrink silicone rubber is specifically formulated as a high track-resistant
material with hydrophobicity (water repelling action) and UV resistance to ensure a longlife
expectancy when properly installed.
The QT-II termination offers some of the same advantages as the QT-III termination but without
a few of the integrated features that the QT-III termination posesses. All terminations meet or
exceed IEEE 48, IEC 60502-4 and CENELEC 629-1 (replaced VDE 0278) requirements.
Cold Shrink
Termination Kits
QTII (X) Series
4 Medium Voltage Cable Accesories
PRODUCTION DESCRIPTION
The 3M QTII (X) Series are Silicone Rubber Cold Shrink Quick
Terminating System that designed to accommodate medium
voltage metallic-shielded armored non-armored, copper or
aluminum conductor power cables configurations.
3M QTII (X) Series provide easy installation for indoor and outdoor
applications. QT-II (X) termination is based on specially formulated,
track-resistant silicone rubber insulators with built-in Hi-K stress
relief. The insulators are prestretched around a spiral -wound,
plastic core.
The QTII (X) Series Termination meet or exceed the specification
requirements of Standards:
• IEEE Standard 48-1990, for Class 1 termination.
• CENELEC Standards HD 628-S1 and HD 629.1.S1.
• VDE Standard 0278-628 and VDE 0278-629-1.
• British Standard BS 7888-4.1.
• IEC Standard 61442 & 60502-4.
• Vietnamese Standard TCVN 5935-4.
PRODUCTION APPLICATION
• For power cables up to 42kV.
• For polymeric cables: polyethylene, XLPE, EPR.
• For 1C/ 3C copper tape, wire shield, armored/ non-armored
power cables.
• For copper or aluminum conductors.
• For contaminated, pollution area, operating environment.
• For switchgear, transformer, motor lead (terminal type) bus,
overhead etc. connections.
SELECTION GUIDE
6/10(12) kV 12.7/22(24) kV 20/35(40.5) kV 22/38.5(42) kV
ID OD ID OD ID OD ID OD
4-Skirt ✓ ✓ ✓
6-Skirt ✓ ✓
8-Skirt ✓
12-Skirt ✓ ✓
KEY FEATURES
• Versatile- Install quickly and accommodates a wide range of cable sizes: from 25sqmm to 630sqmm.
• Simple hand application, no need for special installation tools.
• No torches or heat required.
• Excellent resistance to ozone and UV radiation.
• Good solvent resistant.
• Excellent thermal stability.
• High dry and wet insulation resistance.
• High flexible - accommodates all cable company bend radius recommendations.
• Reliable Seals - Termination assemblies retain resiliency and cable interface pressure after prolonged years of
aging and exposure.
DETAILED COMPOSITION
OF THE QTII (X)
• QTII Termination Assembly:
The cold shrink delivery system has repeatedly proven
itself to be unsurpassed as a positive and reliable electrical
insulating and moisture-sealing system for cable primary QT-II
insulation interface surface. Silicone
Insulator
Moisture Blocking
Onepiece cold shrink termination assembly is created when Silicon Tape
silicon rubber skirted insulator is mounted over a High
Dielectric Constant (High-K) stress relief on a common Applied separately
support core. Hi K Material Outer Insulator
Good track resistance
SILICONE RUBBER-MATERIAL Stress Control Tube
Intergrated
CHARACTERISTICS Silicone Grease Termination
• Smooth surface: minimum amount of contamination Silicone Grease -
adhenre to the termination. Stress Relief
Tape
• Hydrophobicity: When water comes in contact with the Applied separately
silicone it beads up and runs off the skirts rather than
completely wetting these surfaces. Thus a less conductive
path is formed on the silicone and leakage currents are
lowered.
• Non-organic/ nonconductive: degrade leakage current
and arcing occurs on the surface of termination.
NOTE: Length of phases depend on requirements
• High temperature with stand: An outstanding physical of Customer. Installed length of 3-phase 3M QTII
characteristic of silicone rubber is its retention of desirable termination standard kits are 1m approximate.
properties over the wide temperature range of 100oC to 180oC.
SELECTION GUIDE
6/10(12) kV 12.7/22(24) kV 20/35(40.5) kV 22/38.5(42) kV
Indoor/
Indoor Outdoor Indoor Outdoor Indoor Outdoor
Outdoor
QTII QTII QTII QTII QTII QTII QTII
1-phase
(X)4S-11 (X)4S-12 (X)6S-12 (X)6S-13 (X)8S-13 (X)8S-14 (X)12S-14
QTII QTII QTII QTII QTII QTII QTII
3-phase
(X)4S-31 (X)4S-32 (X)6S-32 (X)6S-33 (X)8S-33 (X)8S-34 (X)12S-34
QTII (X)xS-CV
QTII : Product Name Quick Termination II Ex.: QTII (L)6S-32 is QTII 3/C termitation, body
(X)xS : Type of QTII termination/body assembly type L 6S, outdoor application for 24kV class,
(J4S, L6S, M8S; S: Skirt ) 100oC to 180oC.
C : Number of Conductor/ Core (1, 3)
V : Class of Voltage (1: 12kV; 2: 24kV;
3: 36kV, 4: 40.5kV )
B C B C
8 Skirt Termination
A
B C
K K type 3M
(Example)
21
3M
21
2nd Quarter
2021
(Example)
Base of
Termination
Side A Assembly Side B
Cold Shrink
Termination Kits
8
QTIII (X) Series
Medium Voltage Cable Accesories
PRODUCTION DESCRIPTION
The 3M Cold Shrink QT-III Silicone Rubber Skirted The amount of airborne contamination determines the
Termination Kits, 7620-S, 7680-S and 7690-S Series, operating environment. Operating environments are
contain one-piece, skirted, silicone rubber terminations, described as areas having varying degrees of airborne
and two-piece, Inverted Skirted, silicone rubber contaminant or pollution severity that may, or may not,
terminations, qualified as IEEE Standard 48 Class 1 for affect the long-term performance of terminations. These
outdoor weather-exposed applications. The one-piece operating environments are defined as light, medium,
termination assemblies consist of a skirted insulator, heavy and extremely heavy variations according to
high-dielectric constant (High-K) stress control tube*, pollution severity. The appropriate termination selection
conformable High-K stress controlling compound and depends on the system voltage and operating
built-in environmental top sealing compound. The two- environment. (See following tables)
piece inverted skirted termination assemblies consist of
a non-skirted (tubular) insulator, high-dielectric constant KEY FEATURES
(High-K) stress control tube, conformable High-K Conforms to the IEEE Standard 48 Class 1 requirements
stress controlling compound, built-in environmental for 5, 8, 15, 25/28 and 35kV terminations. One-piece,
top sealing compound and a separate skirted assembly. and two-piece inverted skirted, versatile designs,
The insulators and separate skirted assemblies are allowing quick installation and accommodating a wide
made of a dark gray silicone rubber with excellent range of cable sizes. Cold Shrink delivery system for
tracking resistance and hydrophobic properties. easy installation: Simply place termination over prepared
*7620-S is designed and assembled with stress cable and unwind core to shrink into place (no force fit
controlling compound only. The complete assembly is required) High-K stress control: Specially formulated
pre-stretched and loaded onto a removable core. The high dielectric constant material minimizes surface
disposable core can be recycled. The kits are designed stress by more uniformly distributing the electrical field
for terminating solid dielectric shielded power cables over the entire surface of the insulator. Compact design
rated 5 through 35kV, with Tape Shield, Wire Shield and provides for easier installation in restricted spaces.
UniShield® constructions.
Silicone rubber insulators, EPDM stress control tubes,
PRODUCTION APPLICATION stress controlling compound and environmental sealing
compound are compatible with all common solid
3M Cold Shrink QT-III Silicone Rubber Skirted and
dielectric insulations, such as polyethylene (PE), cross-
Inverted Skirted Termination Kits, 7620-S, 7680-S and
linked polyethylene (XLPE) and ethylene propylene
7690-S Series are designed for:
rubber (EPR).
• 5, 8, 15, 25/28 and 35kV classes.
• Tape Shield, Wire Shield and UniShield® cables.
• Solid dielectric insulations, such as polyethylene,
XLPE and EPR.
• Protected and weather-exposed contaminated
locations.
• Free-hanging or bracket-mounting arrangements.
• Upright or inverted installation arrangements
available.
• Inverted termination kits are available in limited
versions, but cover 5kV to 35kV classes.
• These terminations can be field tested using normal
cable testing procedures (reference: ANSI/IEEE
Standard 400 “Guide for Field Testing and Evaluation
of the Insulation of Shielded Power Cable Systems.”
Refer to most recent version).
STRESS CONTROL
3M Cold Shrink QT-III Silicone Rubber Skirted and Silicone Rubber Termination reduces the cable stresses
Inverted Skirted Termination Kits, 7620-S, 7680-S at the termination to less than those in the continuous
and 7690-S Series, control the electric field stress shielded portion of the cable. Electrical flux is refracted
distribution with special High- K materials, which are to distribute the voltage stress in a controlled manner
an integral part of the termination. The High-K materials along the entire termination length extending beyond
with a dielectric constant (K) of greater than 15, the cable shield cutoff. By controlling the electric field,
capacitively distribute the field that surrounds the stress concentrations on the termination insulator
the termination. surface are kept below 15 V/mil at rated voltage. This
stress distribution permits high power frequency
The stress concentrations in a continuous length of
performance and impulse performance with a compact
shielded cable are typically 50 V/mil adjacent to the
termination design.
shield to about 70 V/mil at the conductor. The 3M Cold
Shrink QT-III. Figure 1 below illustrates an actual computerized stress
plot of the 3M Cold Shrink QT-III Silicone Rubber
Termination.
60%
70% Semi-conductive
Insulation Shield
80%
90%
Insulation
Figure 1
7693-S-INV-4, 7695-S-INV-4,
4 Skirt
7696-S-INV-4
35kV ✓ ✓ ✓
TYPICAL PROPERTIES
Not for specifications. Values are typical, not to be considered minimum or maximum. Properties measured at room
temperature 73°F (23°C) unless otherwise stated.
3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7620-S, 7680-S and 7690-S
Series can be used on cables with a rated maximum operating temperature of 221°F (105°C) and an overload
rating of 284°F (140°C). Terminations constructed from these kits meet the requirements of IEEE Standard 48,
“IEEE Standard Test Procedures and Requirements for High-Voltage Alternating-Current Cable Terminations” and
are designated Class 1 for outdoor weather-exposed locations. The current rating of these terminations meets or
exceeds the current rating of the cables on which they are installed.
TYPICAL DIMENSIONS
Heat Shrink
Technology
MHO/MHI Series
Medium Voltage Cable Accesories 13
Medium Voltage Terminations
MHO/MHI Series
PRODUCT DESCRIPTION
3M Heat Shrink Terminations up to 36KV, are
specially designed for conditions where the
terminations are exposed to precipitation, outdoor
sunlight, extreme climatic variances and heavily
polluted areas. The specially engineered kits also
take care of the typical partial discharge ans surface
corona phenomenon for all power cables under
challenging service conditions.
PRODUCT APPILCATION
3M Heat Shrink medium voltage terminations
are available for tape/wire shielded, armoured/
unarmoured medium voltage single core and three
core polymeric cables. 3M Heat Shrinkable
terminations utilizes a unique high dielectric constant
(High K) stress control tube and mastic for effective
grading of electrical stresses.
PRODUCT FEATURES
• Available for 1-core and 3-core polymeric cables.
• Provides excellent environmental protection
and moisture sealing.
• Wide conductor size ranges.
• Ease of installation.
• Simplified cable preparation.
• Outstanding long-term reliability.
• Effective and reliable stress control.
• Excellent mechanica, themal and electrical
characteristics.
• Superior resistance to weathering and UV.
• Resistant to water and corrosion.
• Immediate energization of cable on completion.
6. XLPE Insulation
7. Constant Force Spring
8. Copper Braid 7
9
9. Trifurcating break out (adhesive coated)
8
3 Core Terminations
Lug Lug
80 150
700mm 950mm
(Approx) (Approx)
Creapage
1100mm
Min
INDOOR OUTDOOR
1 Core Terminations
Lug
Lug
230
80 80 80
550mm 850mm
(Approx) (Approx) Creepage
1000mm
Min
INDOOR OUTDOOR
APPLICATIONS
3M QS 200 Cold Shrink Series Kits are designed for inline splicing up to 36kV Umax voltage class, single core & three
core polymeric power cable systems with copper wire screen according to HD 620 (IEC 60502). Splicing medium
voltage power cables of different voltage classes and cross sections is possible.
3M QS 200 Cold Shrink Series Kits includes the Cold Shrink QS 200 silicone splice body with integrated electrode,
stress control device, silicone elastomer insulation and outer semi-conductive layer. Also included are connectors,
copper screen sleeve, constant force springs. For rebuild the cable outer jacket with 3 options: EPDM rubber Cold
Shrink outer tubes, Heat shrinkable outer tubes or Resin Re-jacketing.
Application Range
Connector Dimensions Crimp
Cable Dimensions for Polymeric Cables
or Mechanical Connector
Kit Ref. Diameter over Diameter over Cross Section (mm²)
Diameter Length
Cable jacket Primary 12/20(24)kV 12/20(24)kV max. (mm) max. (mm)
max.(mm) Insulation (mm) 12,7/22(24)kV 12,7/22(24)kV
QS200 93-AK
220-1 (3) 46 19,1 - 38 50 - 300 38 160
QS200 93-AK
230-1 (3) 74 33,4 - 66 400 - 630 68 245
QS200 94-AK
220-1(3) 46 19,1 - 38 35 - 240 38 160
QS200 94-AK
230-1 (3) 74 33,4 - 66 300 - 500 68 245
QS200 93-AK
420-1 (3) 46 19,1 - 38 50 - 300 38 160
QS200 93-AK
430-1 (3) 74 33,4 - 66 400 - 630 68 245
QS200 94-AK
420-1(3) 46 19,1 - 38 35 - 240 38 160
QS200 94-AK
430-1 (3) 74 33,4 - 66 300 - 500 68 245
Cable Jacket
Copper Screen
Semi-Conductive
Primary Insulation
Conductor
KIT CONTENTS
• Silicon rubber splice body
• Grounding braid wire
• Cable preparation kit
• Constant force spring
• Copper shielding sleeve
• 2228# insulating & waterproof tape
(only c/w Armorcast tape)
• 23# insulating tape
• 13# semi-conducting tape
• Armorcast tape or Heat shrink / Cold shrink
EPDM Tube or Resin Rejacketing
FEATURES
• Special copper shielding sleeve design, which could uniformize the electrical stress at the metallic
connecting tube location.
• Enhanced insulation thickness, which is 16mm, and the AC voltage withstand margin up to 160kV.
• Optimized stress cone design ensures reliable electrical stress control performance.
• Cold shrink technology ensures quick, easy and tool-free installation.
• One-piece versatile design, have straight splice and insulating splice two types, allowing quick installation
and accommodating a wide range of cable sizes.
• Seals tight, retains its resiliency and pressure even after years of aging and exposure.
• Wide temperature range.
• High contact pressure ensures absolute watertightness.
• Apply constant force spring to install grounding wires, ensures reliable contact performance.
• Flexible Rejacketing type: Special Armorcast tape ensures reliable mechanical protection,
or Conventional Heat shrink / Cold Shrink Rejacketing, or water seal tight Resin Rejacketing.
• 100% production tested.
SELECTION GUIDE
1C XLPE/EPR amoured tape shield Cu cable, 24kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-5B-50-Cu/1 50 1 24kV
2 VN-5B-70-Cu/1 70 1 24kV
3 VN-5B-95-Cu/1 95 1 24kV
4 VN-5B-120-Cu/1 120 1 24kV
5 VN-5B-150-Cu/1 150 1 24kV
6 VN-5B-185-Cu/1 185 1 24kV
7 VN-5B-240-Cu/1 240 1 24kV
8 VN-5B-300-Cu/1 300 1 24kV
9 VN-5B-400-Cu/1 400 1 24kV
10 VN-5B-500-Cu/1 500 1 24kV
11 VN-5B-630-Cu/1 630 1 24kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-5B-50-AL/1 50 1 24kV
2 VN-5B-70-AL/1 70 1 24kV
3 VN-5B-95-AL/1 95 1 24kV
4 VN-5B-120-AL/1 120 1 24kV
5 VN-5B-150-AL/1 150 1 24kV
6 VN-5B-185-AL/1 185 1 24kV
7 VN-5B-240-AL/1 240 1 24kV
8 VN-5B-300-AL/1 300 1 24kV
9 VN-5B-400-AL/1 400 1 24kV
10 VN-5B-500-AL/1 500 1 24kV
11 VN-5B-630-AL/1 630 1 24kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-5B-50-Cu/3 50 3 24kV
2 VN-5B-70-Cu/3 70 3 24kV
3 VN-5B-95-Cu/3 95 3 24kV
4 VN-5B-120-Cu/3 120 3 24kV
5 VN-5B-150-Cu/3 150 3 24kV
6 VN-5B-185-Cu/3 185 3 24kV
7 VN-5B-240-Cu/3 240 3 24kV
8 VN-5B-300-Cu/3 300 3 24kV
9 VN-5B-400-Cu/3 400 3 24kV
10 VN-5B-500-Cu/3 500 3 24kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-6B-50-Cu/1 50 1 36kV
2 VN-6B-70-Cu/1 70 1 36kV
3 VN-6B-95-Cu/1 95 1 36kV
4 VN-6B-120-Cu/1 120 1 36kV
5 VN-6B-150-Cu/1 150 1 36kV
6 VN-6B-185-Cu/1 185 1 36kV
7 VN-6B-240-Cu/1 240 1 36kV
8 VN-6B-300-Cu/1 300 1 36kV
9 VN-6B-400-Cu/1 400 1 36kV
10 VN-6B-500-Cu/1 500 1 36kV
11 VN-6B-630-Cu/1 630 1 36kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-6B-50-AL/1 50 1 36kV
2 VN-6B-70-AL/1 70 1 36kV
3 VN-6B-95-AL/1 95 1 36kV
4 VN-6B-120-AL/1 120 1 36kV
5 VN-6B-150-AL/1 150 1 36kV
6 VN-6B-185-AL/1 185 1 36kV
7 VN-6B-240-AL/1 240 1 36kV
8 VN-6B-300-AL/1 300 1 36kV
9 VN-6B-400-AL/1 400 1 36kV
10 VN-6B-500-AL/1 500 1 36kV
11 VN-6B-630-AL/1 630 1 36kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-6BH-50-Cu/1 50 1 40.5kV
2 VN-6BH-70-Cu/1 70 1 40.5kV
3 VN-6BH-95-Cu/1 95 1 40.5kV
4 VN-6BH-120-Cu/1 120 1 40.5kV
5 VN-6BH-150-Cu/1 150 1 40.5kV
6 VN-6BH-185-Cu/1 185 1 40.5kV
7 VN-6BH-240-Cu/1 240 1 40.5kV
8 VN-6BH-300-Cu/1 300 1 40.5kV
9 VN-6BH-400-Cu/1 400 1 40.5kV
10 VN-6BH-500-Cu/1 500 1 40.5kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-6BH-50-AL/1 50 1 40.5kV
2 VN-6BH-70-AL/1 70 1 40.5kV
3 VN-6BH-95-AL/1 95 1 40.5kV
4 VN-6BH-120-AL/1 120 1 40.5kV
5 VN-6BH-150-AL/1 150 1 40.5kV
6 VN-6BH-185-AL/1 185 1 40.5kV
7 VN-6BH-240-AL/1 240 1 40.5kV
8 VN-6BH-300-AL/1 300 1 40.5kV
9 VN-6BH-400-AL/1 400 1 40.5kV
10 VN-6BH-500-AL/1 500 1 40.5kV
Cable
No. Product Description Phase Voltage
(mm2)
1 VN-6BH-50-AL/3 50 3 40.5kV
2 VN-6BH-70-AL/3 70 3 40.5kV
3 VN-6BH-95-AL/3 95 3 40.5kV
4 VN-6BH-120-AL/3 120 3 40.5kV
5 VN-6BH-150-AL/3 150 3 40.5kV
6 VN-6BH-185-AL/3 185 3 40.5kV
7 VN-6BH-240-AL/3 240 3 40.5kV
8 VN-6BH-300-AL/3 300 3 40.5kV
9 VN-6BH-400-AL/3 400 3 40.5kV
10 VN-6BH-500-AL/3 500 3 40.5kV
Portfolio
Kit Coding 6/10 kV 6.3/11 kV 8.7/15 kV 12.7/22 kV
Overview
Application Range
Cable Dimensions for
Connector Dimensions
Polymeric Cables
Kit Ref. Diameter over Diameter Cross Section Diameter Length
cable jacket over Primary (mm²) max. max.
max. (mm) Insulation (mm) (mm) (mm)
6/10(12) kV 12.7/22(24) kV
93-AS 220-1 46 19.1 - 36.8 95 - 300 50 - 300 38 170
93-AS 230-1 74 33.4 - 67.6 500 - 1000 400 - 1000 60 270
93-AS 220-3 19.1 - 36.8 95 - 300 50 - 300 38 170
93-AS 230-3 33.4 - 67.6 400 and above 400 and above 60 270
FEATURES
• The versatile design of the prefabricated one-piece cold shrink splice body allows installation on a wide
range of cable sizes and types.
• Fast and easy installation at temperatures ranging from -20°C to + 50°C.
• No heat or flame needed during splice body installation.
• Accommodates crimp or mechanical connectors up to 38mm diameter and 170mm length.
• Wide application range covering cable cross sectional areas from 50mm² - 300mm² **.
• Solderless earth connection by means of copper screen sleeve and constant force springs.
• Thick walled, heavy duty Heat Shrink outer re-jacketing tubes with mastic seal tapes provide physical
protection and moisture sealing of the completed Inline Splices.
• No special tools needed during splice installation.
Copper Screen
SELECTION GUIDE
Cable
No. Product Description Phase Voltage
(mm2)
1 24kV QS2000E-93-AS210-1C-35-70 35 - 70 1 24kV
2 24kV QS2000E-93-AS220-1C-95-120 95 - 120 1 24kV
3 24kV QS2000E-93-AS220-1C-150-300 150 - 300 1 24kV
4 24kV QS2000E-93-AS220-1C-240-400 240 - 400 1 24kV
5 24kV QS2000E-93-AS220-3C-50/120 50 - 120 3 24kV
6 24kV QS2000E-93-AS220-3C-150/300 150 - 300 3 24kV
7 24kV QS2000E-93-AS220-3C-240/400 240 - 400 3 24kV
Inline Joint
3M™ QS 200
30 Medium Voltage Cable Accesories
PRODUCTION DESCRIPTION
The 3M QS 200 is a cold shrink, one-piece multilayer During the installation the ribbon core in unwound counter
silicone rubber splice body with integrated electode, clockwise, allowing the splicebody to shrink onto the cable
stress control device, insulation and outer semi- joint. The applied permanent radial pressure guarantees a
conductive layer. reliable function over the entire lifetime.
The 3M QS 200 silicone splice body is delivered on a
removeable plastic supporting core.
FEATURES
The versatile design of the prefabricated one-piece splice bodies allows installation on a wide range of cable sizes
and types.
• Designed to fit all standard mechanical and compression connectors.
• Cold Shrink technology ensures quick, easy and tool-free installation.
• Excellent material properties allow the installation of the cold shrink splice body at temperatures ranging from -20°C
to + 50°C.
• Meets and exceeds CENELEC standard HD 629, as well as IEC 60502-4
• The integrated, semi-conductive electrode forms a faraday cage over the connector and eliminated the use of tapes or
additional molded or metallic electrodes.
• No heat or flame is needed during splice body installation.
• Delivered mechanical connector provides an adequate application range.
• Solderless earth connection by means of copper screen sleeve and constant force springs.
• Thick walled, medium heat shrinkable outer re-jacketing tubes provide physical protection and moisture sealing of the
completed Inline Splices. They can be stacked together providing a short parking position on the cable.
• No special tools needed during splice installation.
APPLICATIONS
3M QS 200 Cold Shrink Series Kits are designed for inline splicing up to 36kV Umax voltage class, single core & three
core polymeric power cable systems with copper wire screen according to HD 620 (IEC 60502). Splicing medium
voltage power cables of different voltage classes and cross sections is possible.
3M QS 200 Cold Shrink Series Kits includes the Cold Shrink QS 200 silicone splice body with integrated electrode,
stress control device, silicone elastomer insulation and outer semi-conductive layer. Also included are connectors,
copper screen sleeve, constant force springs. For rebuild the cable outer jacket with 3 options: EPDM rubber Cold
Shrink outer tubes, Heat shrinkable outer tubes or Resin Re-jacketing.
Application Range
Connector Dimensions Crimp
Cable Dimensions for Polymeric Cables
or Mechanical Connector
Kit Ref. Diameter over Diameter over Cross Section (mm²)
Diameter Length
Cable jacket Primary 12/20(24)kV 12/20(24)kV max. (mm) max. (mm)
max.(mm) Insulation (mm) 12,7/22(24)kV 12,7/22(24)kV
QS200 93-AK
220-1 (3) 46 19,1 - 38 50 - 300 38 160
QS200 93-AK
230-1 (3) 74 33,4 - 66 400 - 630 68 245
QS200 94-AK
220-1(3) 46 19,1 - 38 35 - 240 38 160
QS200 94-AK
230-1 (3) 74 33,4 - 66 300 - 500 68 245
QS200 93-AK
420-1 (3) 46 19,1 - 38 50 - 300 38 160
QS200 93-AK
430-1 (3) 74 33,4 - 66 400 - 630 68 245
QS200 94-AK
420-1(3) 46 19,1 - 38 35 - 240 38 160
QS200 94-AK
430-1 (3) 74 33,4 - 66 300 - 500 68 245
SELECTION GUIDE
Inline Joint
QS 3000 Series
34 Medium Voltage Cable Accesories
PRODUCT DESCRIPTION
3M QS 3000 cold shrink splices are provided in the expanded state, mounted on removable inner supporting
plastic cores. The cold shrink type splices are very easy for installation, only need to withdraw the supporting
cores. QS 3000 splices are integral preforming type, the splice bodies are made of high quality liquid silicon
rubber. Every splice does factory electrical test to insure reliable quality, the splices according to the Chinese
standard GB/T 12706.4, IEC 60502-4 and are applicable for 26/35(40.5) kV & 20/35(40.5) kV extruded
insulation power cables.
QS3000 have two types: straight splices QS 3000-K and insulated splices QS3000-AX applied in 1-C cable
cross-link grounding system.
KIT CONTENTS
• Silicon rubber splice body
• Grounding braid wire
• Cable preparation kit
• Constant force spring
• Copper shielding sleeve
• 2228# insulating & waterproof tape
(only c/w Armorcast tape)
• 23# insulating tape
• 13# semi-conducting tape
• Armorcast tape or Heat shrink / Cold shrink
EPDM Tube or Resin Rejacketing
FEATURES
• Special copper shielding sleeve design, which could uniformize the electrical stress at the metallic
connecting tube location.
• Enhanced insulation thickness, which is 16mm, and the AC voltage withstand margin up to 160kV.
• Optimized stress cone design ensures reliable electrical stress control performance.
• Cold shrink technology ensures quick, easy and tool-free installation.
• One-piece versatile design, have straight splice and insulating splice two types, allowing quick installation
and accommodating a wide range of cable sizes.
• Seals tight, retains its resiliency and pressure even after years of aging and exposure.
• Wide temperature range.
• High contact pressure ensures absolute watertightness.
• Apply constant force spring to install grounding wires, ensures reliable contact performance.
• Flexible Rejacketing type: Special Armorcast tape ensures reliable mechanical protection,
or Conventional Heat shrink / Cold Shrink Rejacketing, or water seal tight Resin Rejacketing.
• 100% production tested.
Connector
Shield
Insulation Layer
C A B
E
D -1-
35kV
1 2
J 35
7
GH I
4 6
K
Cable dimensions
Type
(3-C/1-C) Outer Cable Insulation
20/35(40.5) kV 26/35(40.5) kV
diameter (mm)
QS 3000-K1/QS 3000-I 27.3 - 42.0 50 - 240 50 - 185
QS 3000-K2/QS 3000-II 36.4 - 57.2 300 - 800 240 - 630
Cable dimensions
Type
(1-C) Outer Cable Insulation
20/35(40.5) kV 26/35(40.5) kV
diameter (mm)
QS 3000-AX 36.4 - 57.2 300 - 800 240 - 630
http://www.3m.com.vn
Independent, accredited testing statio n · Member labo ratory o f STL and LOVAG
Three-core silicone outdoor termination for three-core power cables with TEST OBJECT
extruded synthetic insulation
QTII(X)6S-32 TYPE
Based on NORMATIVE
DOCUMENT
CENELEC Harmonization Document HD 629.1 S1 November 1996
CENELEC Harmonization Document HD 628 S1 November 1996
DIN VDE 0278-629-1 (VDE 0278 Teil 629-1): 1997-11
DIN VDE 0278-628 (VDE 0278 Teil 628): 1997-11
and as agreed with the client
The type tests of test series A1, A2 and A3 have been PASSED. TEST RESULT
The test results are documented in EPM Test Report No. 410101.
This documentation shall not be reproduced in extracts without written approval by IPH GmbH.
The test results relate only to the object tested.
Independent test laboratory, accredited by Deutsche Akkreditierungsstelle Technik (DATech) e.V. in the fields of h.v. apparatus and
switchgear, power cables and power cable accessories, l.v. apparatus and switchgear, installation equipment and switching and
control equipment..
DAT - P - 019/92
Besuchsanschrift:
Franzstr. 9
80802 München
Sachbearbeiter:
Herr Nevihosteny
Telefon:
2361- 8022
Telefax:
2361- 8033
Test Report
Nr. 410101
Applicant: 3M Company
This report gives information only about the specimens submitted for testing; it is not a certificate of quality of the
series production. This test report may be brought to the notice of third parties only in its entire wording. Any publication or
duplication requires the previous written consent of the Elektrisches Prüfamt München. It is valid only in its entirety and
comprises 19 pages and 3 appendices.
Elektrisches Prüfamt München Report No. 410101 Page 2
Test Period
Start: 18.02.2002 Completion: 02.05.2002
Data of Test Specimen
Installation
Test Program
20 Examination - 19
∗
Test was conducted on a special test loop.
Elektrisches Prüfamt München Report No. 410101 Page 4
The following tests were conducted in compliance with the test sequence on page 3.
The test loops between conductor and screen were exposed to a negative D.C. voltage of
72 kV for 15 min.
The A.C. voltage share in the D.C. voltage was about 3%.
42 % 956 mbar 21 °C
ST HT G
380/0...380 V 380/100000 V
Pr C M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
M = D.C. voltage measuring instrument
G = Rectifier
C = Capacitor
An effectively sinusoidal A.C. voltage of 55 kV rms, 50 Hz, was applied successively between
one conductor, the other grounded conductors and the screen for 5 minutes each time.
The voltage was continuously increased to the specified value and was then held constant
during the required duration of the test.
Subsequently the test was repeated as described in test no. 2, with an effectively sinusoidal A.C.
voltage of 48 kV rms, 50 Hz, for 4 hours each time.
42 % 956 mbar 21 °C
SW
ST HT 30000
380/0...380 V 380/100000 V 60000 100 V (Kl 0,1)
Pr M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
SW = Measuring transformer
M = Voltage measuring instrument
The test specimen was arranged as specified and exposed to artificial rain in compliance with
HD 588.1, Section 9.1.
Conditions: Average quantity of rain: 3 mm/ min.
Temperature of the collected water approx. 20°C
Specific resistance of the water at 20 °C: 100 Ω×m
The specimen was exposed to a preliminary rain at a load-free condition for approx. 3 minutes.
Subsequently, under rain an effectively sinusoidal A.C. voltage of 48 kVrms, 50 Hz, was applied
successively between one conductor, the other grounded conductors and the screen, each time
for 1 minute.
The voltage was continuously increased to the specified value within 10 seconds and was then
held constant during the required duration of the test.
42 % 956 mbar 21 °C
SW
ST HT 30000
380/0...380 V 380/100000 V 60000 100 V (Kl 0,1)
Pr M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
SW = Measuring transformer
M = Voltage measuring instrument
a) Measuring instrument
b) Test circuit
Q CK
Tr U
D
ZA
Tr = High-voltage source
U = High-voltage measuring instrument
Z = Impedance
ZA = Coupling quadripole
CP = Test loop
CK = Coupling capacitor
D = Detector
Q = Calibrator
c) Test performance
The test loops were stored in a dry and clean condition for 3 hours before the test, at an
ambient temperature of about 20°C.
Afterwards the connection elements were made discharge free by use of shielding electrodes,
and a test A.C. voltage of 24 kV was applied and the maximum value of the partial discharge
intensity was measured within 1 minute.
Subsequently, the voltage was decreased to a test A.C. voltage of 15 kV and the
partial discharge intensity was repeated.
42 % 946 mbar 20 °C
The test specimens were arranged in compliance with the instruction, were heated with 523 A
for about 3 hours, and the temperature was held constant during the test performance.
The test was performed with an impulse voltage of which the rise time was approx. 1.2 µs and
the half-value decay was approx. 50 µs.
The test loops were exposed to 10 impulses each with an impulse voltage of 125 kV and
10 impulses each with an impulse voltage of 150 kV of positive and negative polarity
between one conductor, the other grounded conductors and the screen.
Prior to the tests with positive and negative polarity, the test loops were exposed once to 50 %,
F L Rd
U= Cb
Cs Re Pr
Cb M
CS = Impulse capacitor
F = Spark gap discharger
Re = Discharge resistor
L = Impulse circuit inductive resistor
Rd = Damping resistor
Cb = Additional load capacitor
Pr = Test specimen
T = Impulse voltage divider
M = Impulse voltage measuring instrument
The partial discharge test at ambient temperature was repeated as described in test no. 5.
46 % 952 mbar 20 °C
The test specimens were arranged in compliance with the instructions as described in test no. 5,
were heated with 523 A for about 3 hours, and the temperature was held constant during test
performance.
The impulse withstand test at ambient temperature was repeated as described in test no. 6,
without heating.
58 % 960 mbar 21 °C
The following impulse oscillograms of conductor 1 of test loop 1 do not show any
deviation from the calibration oscillogram and the impulse oscillograms of conductor 2 and
conductor 3.
The oscillogram of the second test loop was identical to those of test loop 1.
The test loops between conductor and screen were exposed to a negative D.C. voltage of
96 kV for 30 min.
The A.C. voltage share in the D.C. voltage was about 3%.
58 % 946 mbar 21 °C
ST HT G
380/0...380 V 380/100000 V
Pr C M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
M = D.C. voltage measuring instrument
G = Rectifier
C = Capacitor
Examination
( Test No. 19 )
The 3 core silicone outdoor terminations QTII 12/20(24) kV, Type QTII (X)6S-32 passed the test
according to CENELEC HD 628.1 S 1: 1996 and CENELEC HD 629.1 S 1: 1996,
however, a dynamic short circuit test was not performed.
( Nevihosteny )
Chief Test Engineer
Appendix 1
Elektrisches Prüfamt München Report No. 410101
Page 1 of 1
Three-core silicone outdoor termination for three-core power cables with TEST OBJECT
extruded synthetic insulation
QTII(X)6S-32 TYPE
Based on NORMATIVE
DOCUMENT
CENELEC Harmonization Document HD 629.1 S1 November 1996
CENELEC Harmonization Document HD 628 S1 November 1996
DIN VDE 0278-629-1 (VDE 0278 Teil 629-1): 1997-11
DIN VDE 0278-628 (VDE 0278 Teil 628): 1997-11
and as agreed with the client
The type tests of test series A1, A2 and A3 have been PASSED. TEST RESULT
The test results are documented in EPM Test Report No. 410101.
This documentation shall not be reproduced in extracts without written approval by IPH GmbH.
The test results relate only to the object tested.
Independent test laboratory, accredited by Deutsche Akkreditierungsstelle Technik (DATech) e.V. in the fields of h.v. apparatus and
switchgear, power cables and power cable accessories, l.v. apparatus and switchgear, installation equipment and switching and
control equipment..
DAT - P - 019/92
Besuchsanschrift:
Franzstr. 9
80802 München
Sachbearbeiter:
Herr Nevihosteny
Telefon:
2361- 8022
Telefax:
2361- 8033
Test Report
Nr. 410101
Applicant: 3M Company
This report gives information only about the specimens submitted for testing; it is not a certificate of quality of the
series production. This test report may be brought to the notice of third parties only in its entire wording. Any publication or
duplication requires the previous written consent of the Elektrisches Prüfamt München. It is valid only in its entirety and
comprises 19 pages and 3 appendices.
Elektrisches Prüfamt München Report No. 410101 Page 2
Test Period
Start: 18.02.2002 Completion: 02.05.2002
Data of Test Specimen
Installation
The following tests were conducted in compliance with the test sequence on page 3.
The test loops between conductor and screen were exposed to a negative D.C. voltage of
72 kV for 15 min.
The A.C. voltage share in the D.C. voltage was about 3%.
42 % 956 mbar 21 °C
ST HT G
380/0...380 V 380/100000 V
Pr C M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
M = D.C. voltage measuring instrument
G = Rectifier
C = Capacitor
An effectively sinusoidal A.C. voltage of 55 kV rms, 50 Hz, was applied successively between
one conductor, the other grounded conductors and the screen for 5 minutes each time.
The voltage was continuously increased to the specified value and was then held constant
during the required duration of the test.
Subsequently the test was repeated as described in test no. 2, with an effectively sinusoidal A.C.
voltage of 48 kV rms, 50 Hz, for 4 hours each time.
42 % 956 mbar 21 °C
SW
ST HT 30000
380/0...380 V 380/100000 V 60000 100 V (Kl 0,1)
Pr M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
SW = Measuring transformer
M = Voltage measuring instrument
The test specimen was arranged as specified and exposed to artificial rain in compliance with
HD 588.1, Section 9.1.
Conditions: Average quantity of rain: 3 mm/ min.
Temperature of the collected water approx. 20°C
Specific resistance of the water at 20 °C: 100 Ω×m
The specimen was exposed to a preliminary rain at a load-free condition for approx. 3 minutes.
Subsequently, under rain an effectively sinusoidal A.C. voltage of 48 kVrms, 50 Hz, was applied
successively between one conductor, the other grounded conductors and the screen, each time
for 1 minute.
The voltage was continuously increased to the specified value within 10 seconds and was then
held constant during the required duration of the test.
42 % 956 mbar 21 °C
SW
ST HT 30000
380/0...380 V 380/100000 V 60000 100 V (Kl 0,1)
Pr M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
SW = Measuring transformer
M = Voltage measuring instrument
a) Measuring instrument
b) Test circuit
Q CK
Tr U
D
ZA
Tr = High-voltage source
U = High-voltage measuring instrument
Z = Impedance
ZA = Coupling quadripole
CP = Test loop
CK = Coupling capacitor
D = Detector
Q = Calibrator
c) Test performance
The test loops were stored in a dry and clean condition for 3 hours before the test, at an
ambient temperature of about 20°C.
Afterwards the connection elements were made discharge free by use of shielding electrodes,
and a test A.C. voltage of 24 kV was applied and the maximum value of the partial discharge
intensity was measured within 1 minute.
Subsequently, the voltage was decreased to a test A.C. voltage of 15 kV and the
partial discharge intensity was repeated.
42 % 946 mbar 20 °C
The test specimens were arranged in compliance with the instruction, were heated with 523 A
for about 3 hours, and the temperature was held constant during the test performance.
The test was performed with an impulse voltage of which the rise time was approx. 1.2 µs and
the half-value decay was approx. 50 µs.
The test loops were exposed to 10 impulses each with an impulse voltage of 125 kV and
10 impulses each with an impulse voltage of 150 kV of positive and negative polarity
between one conductor, the other grounded conductors and the screen.
Prior to the tests with positive and negative polarity, the test loops were exposed once to 50 %,
F L Rd
U= Cb
Cs Re Pr
Cb M
CS = Impulse capacitor
F = Spark gap discharger
Re = Discharge resistor
L = Impulse circuit inductive resistor
Rd = Damping resistor
Cb = Additional load capacitor
Pr = Test specimen
T = Impulse voltage divider
M = Impulse voltage measuring instrument
44 % 944 mbar 21 °C
The following impulse oscillograms of conductor 1 of test loop 1 do not show any
deviation from the calibration oscillogram and the impulse oscillograms of conductor 2 and
conductor 3.
The oscillogram of the second test loop was identical to those of test loop 1.
The test loops were connected, in compliance with HD 628 S1:1996 Section 8, for one-phase
heating to the source of current and were exposed to 3 heat cycles in air, with a continuous test
voltage of 30 kV being applied.
Each heat cycle consisted of a five-hours heating period and a three-hours cooling period.
The current measured at a control cable was 523 A with a conductor temperature of 95°C.
At the end of the heating period of the first heat cycle, the current was adjusted to the specified
value and remained unchanged during the subsequent test run.
Ambient temperature during the heat cycling test was about 20°C.
After the 3rd heat cycling test the partial discharge test at ambient temperature was repeated
as described in test no. 5.
43 % 945 mbar 20 °C
The test specimens were arranged in compliance with the instruction as described in test no. 5,
were heated with 523 A for about 3 hours, and the temperature was held constant during test
performance.
43 % 945 mbar 20 °C
The test loops were arranged with the terminations in a water tank in such a way that the whole
termination, including the top of the connection element, was fully immersed in water. In this
position they were subjected to 10 heat cycles at a current of 523 A with a conductor temperature
of 95°C. Each heat cycle consisted of a five-hours heating period and a three-hours cooling
period. The conductivity of the water was 700 mS/ m.
Elektrisches Prüfamt München Report No. 410101 Page 13
The partial discharge test at ambient temperature was repeated as described in test no. 5.
46 % 952 mbar 20 °C
The test specimens were arranged in compliance with the instructions as described in test no. 5,
were heated with 523 A for about 3 hours, and the temperature was held constant during test
performance.
The short circuit current of the screen was 4.5 kA/ 1 s according to the manufacturer's
information.
Test set-up: Both ends of the screen were connected to the source of current.
The conductors were set up in compliance with the instruction, heated with 523 A for about 3
hours, and the temperature was held constant during test performance.
This short circuit loading was repeated once, following the cooling down of the cable screen to a
temperature of 5 K to 10 K above the initial short circuit temperature Θi.
( Room temperature 21 °C ).
The maximum admissible short circuit temperature of the cable conductor ΘSC was 250°C,
therefore a short- circuit- current of 27.2 kA is necessary.
Test set-up: One end of the cable was connected to the source of current and the other end
was short circuited.
Owing to the test device, the test had to be carried out with a lower current, while the test time
was prolonged accordingly.
The short circuit loading was repeated once, following the cooling down of the conductors
to a temperature of 5 K to 10 K above the initial circuit temperature Θ.
( Room temperature 21 °C ).
The impulse withstand test at ambient temperature was repeated as described in test no. 6,
without heating.
58 % 960 mbar 21 °C
The following impulse oscillograms of conductor 1 of test loop 1 do not show any
deviation from the calibration oscillogram and the impulse oscillograms of conductor 2 and
conductor 3.
The oscillogram of the second test loop was identical to those of test loop 1.
An effectively sinusoidal A.C. voltage of 30 kV rms, 50 Hz, was applied to both specimens
between one conductor, the other grounded conductors and the screen for 15 minutes each time.
The voltage was continuously increased to the specified value and was then held constant
during the required duration of the test.
54 % 947 mbar 21 °C
SW
ST HT 30000
380/0...380 V 380/100000 V 60000 100 V (Kl 0,1)
Pr M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
SW = Measuring transformer
M = Voltage measuring instrument
The test loops between conductor and screen were exposed to a negative D.C. voltage of
96 kV for 30 min.
The A.C. voltage share in the D.C. voltage was about 3%.
58 % 946 mbar 21 °C
ST HT G
380/0...380 V 380/100000 V
Pr C M
30 kVA 30 kVA
ST = Regulating transformer
HT = High-voltage transformer
Pr = Test specimen
M = D.C. voltage measuring instrument
G = Rectifier
C = Capacitor
The test loop was stored in a humidity chamber in compliance with the specifications of
CENELEC HD 628.1 S 1/ 1996 and CENELEC HD 629.1 S 1/ 1996.
l
Quantity of sprayed water : 0.4 ± 0.1
m3h
Description: All test specimens show salt incrustations on the cable lugs
and feathery discharge traces on the surface of the termination, however,
they are not burnt in.
Page 1 of Appendix 2 contains pictures of the test loop after test performance of 1000 hours.
Elektrisches Prüfamt München Report No. 410101 Page 19
Examination
( Test No. 19 )
The 3 core silicone outdoor terminations QTII 12/20(24) kV, Type QTII (X)6S-32 passed the test
according to CENELEC HD 628.1 S 1: 1996 and CENELEC HD 629.1 S 1: 1996,
however, a dynamic short circuit test was not performed.
( Nevihosteny )
Chief Test Engineer
Appendix 1
Elektrisches Prüfamt München Report No. 410101
Page 1 of 1