Reference : CTA proiect
VENTILAȚII
Dated : 22/05/2022
Page : 1 / 5
1 AIR TREATMENT UNIT
Make: CIAT or equivalent
Flow rate : SUPPLY UNIT 21.050 m3/h / EXTRACT UNIT 18.945 m3/h (Frontal speed : 2.32 / 2.09 m/s)
(Filtration surface area / Filtration surface area)
PED 2014/68/UE Article 4.3
AHU Assembly Delivery : Side by side / Internal
Altitude : 308 m
Reference temperature : SUPPLY UNIT 18 °C
Reference humidity : SUPPLY UNIT 50 %(RH)
Density : 1,16 kg/m3
Reference temperature : EXTRACT UNIT 20 °C
Reference humidity : EXTRACT UNIT 50 %(RH)
Density : 1,16 kg/m3
Designed for wet conditions
ERV_2016, Subgroup 1 Energy class E
Speed class V5 EN13053
EN 1886-2007 CAL(R) -400 Pa = 0,00875 m3/s
EN 1886-2007 CAL(R) +700 Pa = 0,01283 m3/s
Winter fresh air reference temperature EUROVENT -21 °C
Mixing ratio 0,65
This device may not be installed and used in an EU member country
SUPPLY UNIT : Ancillaries
Doors : right in air flow direction
Piping : right in air flow direction
EXTRACT UNIT : Ancillaries
Doors : Non standard
EXTRACT UNIT : Position 1HHS
Block A1 658 kg with
1 Extraction : central section upstream panel B370326
1 filtration section B371719
SRight face access in the direction of air
Pressure tappings (fitted) B371554
1 Fan type LP (forward curved blades) B376840
Brand : COMEFRI
Air flow rate : 18.945 m3/h 5,2625 m3/s
Duct available pressure : 380 Pa
C:\Users\Florin\Desktop\PROIECTE\Anul 4\Ventilatii\Proiect FINAL\CTA PROIECT VENTILAȚII.GIW - 019 - W CLIMGIW 10.00.20-P0 09/2016
Reference : CTA proiect
VENTILAȚII
Eroare! Fără sursă de referință. Dated : 22/05/2022
Page: 2 / 5
Power input : 5.872 W
Specific Fan Power :1.116 W/(m3/s), 0,31 W/(m3/h)
Vitesse de l'air en sortie du ventilateur : 10,3 m/s
Single motor
Motor IE
1 Colmant Cuvelier support B371397
Voltage : 400 V / 3 ph / 50 Hz
Vibration-damping chassis on spring mounts and internal flexible sleeve
Packing box for motor electrical supply
Brand : ABB
Right face access in the direction of air
Hinged doors with locking device for hexagonal screws
Spring mounts suspension
Block A2 583 kg with
1 side-by-side economizer mixing box B371316
Internal damper boxes
Opposed dampers with gaskets on the thin plates extremities
Cog wheel drive
Mixing point WINTER
fresh air : 7.300 m3/h / -21 °C / 80 %(RH)
recycled air : 13.700 m3/h / 18 °C / 50 %(RH)
air outlet t° / rh % : 3,2 °C / 87,1 %(RH)
Mixing point SUMMER
fresh air : 7.300 m3/h / 34,1 °C / 41 %(RH)
recycled air : 13.700 m3/h / 26 °C / 50 %(RH)
air outlet t° / rh % : 28,8 °C / 47 %(RH)
External spindle (actuator by others) B371360
Right face access in the direction of air
Commands on the right in the direction of air
internal mounting B371327
SUPPLY UNIT : Position 1HVS
Block A2 583 kg with
1 side-by-side economizer mixing box B371316
Block A3 597 kg with
1 filtration section B371719
Slides assembly 2, hinged door B372087
Efficiency F7 :80 <= Em < 90 % opaci
With pressure valves
Right face access in the direction of air
Pressure tappings (fitted) B371554
Heating coil
Heating capacity : 48,3 kW
Heating fluid : Water
inlet t° / outlet t° : 80 °C / 60 °C
air inlet t° / rh % : 4,6 °C / 83,1 %(RH)
Slide mounting
Right face access in the direction of air
C:\Users\Florin\Desktop\PROIECTE\Anul 4\Ventilatii\Proiect FINAL\CTA PROIECT VENTILAȚII.GIW - 019 - W CLIMGIW 10.00.20-P0 09/2016
Reference : CTA proiect
VENTILAȚII
Eroare! Fără sursă de referință. Dated : 22/05/2022
Page: 3 / 5
Pipings on the right in the direction of air
For an anti-frost coil for which outlet temperature
is below 15°C, use a constant flow control
to avoid anti-frost fault or frost
upon the coil
Cooling coil
Cooling capacity : 120 kW
Refrigerant : Water
inlet t° / outlet t° : 7 °C / 12 °C
air inlet t° / rh % : 28,8 °C / 47,2 %(RH)
Fluid pressure drop : 38.910 Pa
Standard droplet eliminator
Air pressure drops : 28 Pa
Slide mounting
Right face access in the direction of air
Pipings on the right in the direction of air
Galva./steel drain pan for condensates recovery B375615
Lift off panel on droplets eliminator B375527
Block A4 427 kg with
1 spraying humidifier HC B372286
Efficiency : 80,00 % B375473
air inlet t° / rh % : 15,5 °C / 92,4 %(RH)
Right face access in the direction of air
Pipings on the right in the direction of air
230V Water tight bulkhead light (supplied loose item) B376608
Stainless steel drain and separator cells B372296
Not Eurovent Certified
Block A5 686 kg with
Heating coil
Heating capacity : 112 kW
Heating fluid : Water
inlet t° / outlet t° : 80 °C / 60 °C
air inlet t° / rh % : 7,7 °C / 90 %(RH)
Slide mounting
Right face access in the direction of air
Pipings on the right in the direction of air
1 Fan type LP (forward curved blades) B376841
Brand : COMEFRI
Air flow rate : 21.050 m3/h 5,8472 m3/s
Duct available pressure : 673 Pa
Power input : 12.580 W
Specific Fan Power :2.151 W/(m3/s), 0,60 W/(m3/h)
Vitesse de l'air en sortie du ventilateur : 11,4 m/s
Single motor
Motor IE
1 Colmant Cuvelier support B371397
Voltage : 400 V / 3 ph / 50 Hz
Vibration-damping chassis on spring mounts and internal flexible sleeve
Packing box for motor electrical supply
C:\Users\Florin\Desktop\PROIECTE\Anul 4\Ventilatii\Proiect FINAL\CTA PROIECT VENTILAȚII.GIW - 019 - W CLIMGIW 10.00.20-P0 09/2016
Reference : CTA proiect
VENTILAȚII
Eroare! Fără sursă de referință. Dated : 22/05/2022
Page: 4 / 5
Brand : ABB
Right face access in the direction of air
Hinged doors with locking device for hexagonal screws
Spring mounts suspension
Accessories
1 External damper (supplied loose item)
5 Baseframe B380274
78 Support base frame (per module) B380206
C:\Users\Florin\Desktop\PROIECTE\Anul 4\Ventilatii\Proiect FINAL\CTA PROIECT VENTILAȚII.GIW - 019 - W CLIMGIW 10.00.20-P0 09/2016
Reference : CTA proiect
VENTILAȚII
Eroare! Fără sursă de referință. Dated : 22/05/2022
Page: 5 / 5
1 AIR TREATMENT UNIT
DIMENSIONS AND WEIGHT
Length : 5.650 mm Width : 3.636 mm Height : 1.666 mm
Weight 3.058 kg (+/-10%)
All weights are dry weights
C:\Users\Florin\Desktop\PROIECTE\Anul 4\Ventilatii\Proiect FINAL\CTA PROIECT VENTILAȚII.GIW - 019 - W CLIMGIW 10.00.20-P0 09/2016