Load Calculation

This document calculates load and sizing requirements for a building with 8 flats. It summarizes: 1) The total building load is 164.4KW when all loads are running, but typically only 70% of loads run at a time, giving a total load of 115.08KW. 2) The recommended transformer rating is 150KVA to supply this typical load while allowing for 20% overload. 3) The emergency generator rating is 40KVA to supply the 30.6KW emergency load from flats, common areas, lift and water pump. 4) A 90KVR power factor improvement plant is recommended to correct the power factor of 0.8 used in the calculations.

Uploaded by

Abdul Alim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views4 pages

Load Calculation

This document calculates load and sizing requirements for a building with 8 flats. It summarizes: 1) The total building load is 164.4KW when all loads are running, but typically only 70% of loads run at a time, giving a total load of 115.08KW. 2) The recommended transformer rating is 150KVA to supply this typical load while allowing for 20% overload. 3) The emergency generator rating is 40KVA to supply the 30.6KW emergency load from flats, common areas, lift and water pump. 4) A 90KVR power factor improvement plant is recommended to correct the power factor of 0.8 used in the calculations.

Uploaded by

Abdul Alim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Load Calculation [ Ground Floor + Stair + Roof]

Load Description Quantity Total Watt Total Watt


Number per
of Loads Load
Light Items :

Tube Light(TL) 5+0+2 7 100 700

Wall Light(WL) 6+10+2 18 25 450

Celling Light(CEL) 5+0+2 7 25 175


1325
Fan Items :

Celling Fan (FA) 2+0+1 3 75 225

Exhaust Fan(EXF) 2+0+0 2 25 50


275
Power Outlets

P ( 3 pin,5A,240V,1 2+0+2 4 300 1200


phase)
2+0+2 4 100 400
R ( 2 pin,5A) 1600

3200

Load Calculation [A single Flat ]


Load Description Quantity Watt per Total Watt
Load
Light Items :

Tube Light(TL) 8 100 800

Wall Light(WL) 10 25 250

Candlelight(CL) 1 200 200 1250

Fan Items :

Celling Fan (FA) 6 75 450

Exhaust Fan(EXF) 1 25 25
475
Power Outlets :

P ( 3 pin,5A,240V,1 6 300 1800


phase)
7 100 700
R ( 2 pin,5A)
4 2000 8000
Q ( 3pin,15A,2000W)
3 1500 4500 15000
G ( 3 pin , 15A,1500W)
Emergency Load :

Emergency wall Light(EL) 2 100 200

Emergency Celling Fan 1 75 75


(EFA)
1 25 25 300
Calling bell (CB)
17025

Find out transformer rating :


Our designed building 4 floor each floor having 2 flat.so total number of flat 8.
So
1) 8 flat total load = 17025*8= 136200 watt =136.2 KW
2) (Ground Floor + Stair + Roof ) load =3200W=3.2KW
3) Lift Load =20KW
4) Water Pump =5KW

Total load our designed building = 164.4KW

We know at a time all load doesn’t running .so we assume 70% of load running at
a time.
So now total number of load =70% of 164.4=115.08 KW

Transformer rating= 115.08/0.8=143.85≅ 150 KVA


[ here, let power factor 0.8 ]

Find out Generator rating :

1) 8 flat total Emergency Load =300*8=2400W=2.4KW


2) (Ground Floor + Stair + Roof ) load =3200W=3.2KW
3) Lift Load =20KW
4) Water Pump =5KW

Generator supply emergency case Total load our


designed building = 30.6 KW

Generator rating= 30.6/0.8=38.25≅ 40 KVA


Find PFI(power factor Improvement) Plant rating :

PFI Plant rating = 150*0.6=90KVR