Manual ACP824P (Sept 2020)
Manual ACP824P (Sept 2020)
P/N:20121119-5
ACP824P WIRING DIAGRAM
LED display
on Metal case GSM LED Flash
BAT
+_
Telephone
TEL
LI NE
Tel.line
AC AC + BELL- R B G Y +12V GND Z1 GND Z2 Z3 GND Z4 Z5 GND Z6 Z7 GND Z8
Power Arm
Disarm Fault
Delet e Confirm
Frice Panic Medical Check
1 2 3 Arm
4 5 6 Disarm
7 8 9 Home
0 # Bypass
Power supply
Only can use12V/7A sealed lead-acid battery,change battery every 3-5 years
With 1 keypad,power consumption 250mA,support for 16 working hrs.
Total power consumption(keypad,auxiliary power,siren)can~t exceed max.power
consumption of control panel
Max.Rechargeable current of battery:350MA
User manual ACP824P
Content
Foreword 1
Features 2
Alarm procedure 3
1.Remote control by phone 4
2.Follow me operation 4
GSM remote operation 6
GSM alarm receiving 6
GSM control via SMS 6
Keypad 7
LED display on Metal case 8
Basic operation 9
System setting 10
I.Set password 11
1.1 Set administrator password 11
1.2 Set user password 11
II.set CMS number 11
2.1 Set CMS number 11
2.2 Set user Id 12
2.3 Free arm telephone number 12
2.4 Free disarm telephone number 12
2.5 Set the user telephone number 12
2.6 CMS dialing times 13
2.7 The user phone dialing time 13
III.System options 13
3.1 System time setting 13
3.2 Entry delay time setting 13
3.3 Set exit delay time 14
3.4 Siren time 14
3.5 Set ring time 14
3.6 Detector loss check 14
3.7 Communication checking interval time 15
3.8 Arm,disarm indication sound 15
3.9 Arm/disarm report 15
3.10 Panic alrm sound 15
IV. Code wireless device 16
4.1 Code wireless remote controller 16
4.2 Auto code wireless detector 16
4.3 Manual code remote controller 16
User manual ACP824P
Foreword
ACP824P is a intelligent alarm control system which integrated
with burglarproof, fireproof, gas leak proof. It is compatible with
wired and wireless alarm mode.
ACP824P refers to the most advanced coding techniques of BUS
zone and multi-bit random code-hopping techniques in security &
reliability, to avoid false alarm and interference effectively.
1. 32 zones:8 wired, 24 wireless
2. 6 way to arm and disarm the system: User code, Key fob, Phone,
SMS, Auto timer, CMS
3. Alarm notification: When alarm occurs, user can have alarm
notification by phone call, SMS, GPRS, TCP/IP (optional)
Smart feature of ACP824P
1. Multi-zones combination alarm, special design for the places
such as watch room, bedromm and etc.
2.Can use without keypad
3.LED display on metal case, easier for user to check system info.
Warning!!!
●Don’t disassemble or modify, or else may be lead to danger and
the damage of panel.
●Be sure not to cause to break by falling or throwing down or
ACP824P 1
User manual Features
Features:
Zones: 8 wired/ 24wireless
Keypad and remote: Support 8 pcs LCD keypad and 8 remotes
Password: 1 installer code, 1 duress code, 15 user codes
CMS: 2 CMS follow me numbers, 1 account number
Voice number: 4 voice numbers, Voice prompting operation
Event log: 128 event logs
Module expanded: GSM/ GPRS module
Recording:10-second automatic message Recording
2 ACP824P
User manual Alarm procedure
Alarm procedure
d
ire
W
BUS
Alarm software
Alarm situation found,
start to send message
DISARM
ALARM
POWER FAULT
COM
ARM
ACP824P 3
User manual Remote control by phone
1 DI ~ DI ~ 2
3 4
1 2 3 4
"Welcome to your security Enter the user code as per voice
system Enter your user code" prompting(factory default
code: 1234)
2. Follow me operation
When the detector is triggered, the panel will sound alarm and display the triggered
zone number and alarm type on the LCD screen. The panel will give a alarm and dial
the preset voice numbers if the panel received the alarm.
The user can hear indication after he took th e phone.The user operate follow the
voice indication to disarm/arm、inquire and mornitor .
1 POWER
OC M
DISARM
ARM
ALARM
FAULT
2
Panel receivealarm,
Send the alarm signal and dial voice number
4 ACP824P
User manual Follow me operation
4
Cancel the alarm press one
Check alarm zone press two
Activate the hoot press three
To disable the siren press four
Disarm system press five
Arm the system press six
Stay arm the system press seven
Play the zone address recording press nine
Hand up press zero
ACP824P 5
User manual GSM remote operation
“
Remarks:There is no space between APN:
6 ACP824P
User manual Keypad
Keypad description
1 2 3 Arm
4 5 6 Disarm
7 8 9
Speech indication
Numeric keyboard Home
0 # Bypass
Power LED: it will normal ON when AC and battery without any trouble. It will off
when both AC and battery with trouble. It will slow flash when battery
with trouble, it will quick flash when AC with trouble.
Fault LED: It will slow flash when communication with trouble, it will off when
without any troubles.
Arm LED: It will ON when armed, slow flash when stay in, quick flash when alarm.
Disarm LED: It will ON when disarmed, it will OFF when zone trouble.
Fire : The panel will send out alarm Check : Press CHECK key to check the
signal when press FIRE key 3 for alarm events , it used as Confirme
seconds, it used as UP key when key when programming.
programming.
: W hen y ou e ntering n umbers,
Panic : The panel will send out alarm
press *, the LCD screen will
signal when press PANIC key for 3
seconds, it used as DOWN key display P, means 2s pause
when programming. when dialing, for other settings,
press * means EXIT.
Medical : The panel will send out alarm
signal when press HELP key for 3 # :When enter errors, press # can
seconds, it used as DELETE key delete the errors, it used as
when programming. Confirm key when programming.
Basic operation
Factory default Admin password: 012345
Factory default User password: 1234
Arm: User password [1234]+ Arm
ACP824P 7
User manual LED display on Metal case
#
Enter system setting : Admin password[012345]+
+ #
* +[0]+
Exit system setting:
*
Password reset: You can enter installer code 000000 to enter setup only during the
first 1 minute when the alarm is powered on.
8 ACP824P
User manual Basic operation
Basic operation
☆Arm ☆ Disarm
Power Arm
~嘀~ Power Arm
~嘀~
Disarm Fault Disarm Fault
Delete Confirm Delete Confirm
Frice Panic Medical Check Frice Panic Medical Check
1 2 3 Arm 1 2 3 Arm
4 5 6 Disarm 4 5 6 Disarm
7 8 9 Home 7 8 9 Home
0 # Bypass 0 # Bypass
Y Y
M D M D
User code[1234] + Arm or the away User code [1234] + Disarm or the
1 2 3 Arm 1 2 3 Arm
4 5 6 Disarm 4 5 6 Disarm
7 8 9 Home 7 8 9 Home
0 # Bypass 0 # Bypass
Y Y
M D M D
Emergency help:press key in the keyfob User code + Stay or press the home
or press Panic and hold for 3s ARM key in the keyfob.
Note: If the LCD also display zone alarm when the user disarmed the system after
alarming, please disarm the system again, then LCD display will resume.
ACP824P 9
User manual System setting
System setting
[012345] + + [0] + #
*
System setting display
2 0 6 0 5
10 ACP824P
User manual Set password
I.Set password
1.1 Set administrator password
For example: set the administrator password as 112233, the factory default password
is 012345.
[012345] +
* + [0] + # ---- + [01] + [112233]
Password
LCD screen display
01 3 06 + #
LCD screen display
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [04] + [5678]
04 8 04 + #
[012345] +
* + [0] + # ---- + [20] + [9 80012345]
Program *Telephone
address number
20 11 + #
ACP824P 11
User manual set CMS number
[012345] +
* + [0] + # ---- + [22] + [6666]
Program User ID
LCD screen address
22 05 + # display
[012345] +
* + [0] + # ---- + [62] + [ 84113252 ]
62 09 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [63] + [ 841132 68]
63 09 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [25] + [93872105]
25 09 + #
Press # return to standby interface
* +
12 ACP824P
User manual system options
[012345] +
* + [0] + # ---- + [27] + [04]
27 4 02 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [28] + [03]
28 3 02 + #
Press # return to standby interface
* +
III.System options
3.1 System time setting
Example: set the system time and date as 10:01,July,11,2012
[012345] +
* + [0] + # ---- + [30]
+ [1207111001]
Y M D H M
30 1 10 + #
Year Month Day Hour Minute
Press # return to standby interface
* +
3.2 Entry delay time setting:after triggerd the delay zone,panel start
alarming.the default setting is 10 seconds.
Example: set the entry delay time as 15 seconds.
[012345] +
* + [0] + # ---- + [31] + [015]
Program Time
LCD screen address
31 5 03 + # dispaly
LCD screen dispaly
Press # return to standby interface
* +
ACP824P 13
User manual system options
[012345] +
* + [0] + # ---- + [32] + [015]
32 5 03 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [33] + [10]
33 0 02 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [34] + [05]
Program Time
LCD screen address
34 5 02 + # dispaly
[012345] +
* + [0] + # ---- + [35] + [04]
35 4 02 + #
Press # return to standby interface
* +
14 ACP824P
User manual System options
Note: wireless detector send status report about every 3 hours. The panel check if receiver
the status report signal or alarm signal from detector at programed time. If not
receive the singal, will judge detector loss. We suggest set the neterval time of
detector inspection longer than 4 hours.
3.7 Communication checking interval time :
It is checking of communication between alarm panel and CMS. To check if the
communication is normal(default is 00, not checking)
Example: set the communication checking interval time as 15 hours.
[012345] +
* + [0] + # ---- + [36] + [015]
36 5 03 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [37] + [1]
37 1 01 + #
# return to standby interface
Press
* +
[012345] +
* + [0] + # ---- + [38] + [1]
Program 1>Report
LCD screen address
38 1 01 + # dispaly
LCD screen dispaly
Press # return to standby interface
* +
ACP824P 15
User manual system options
[012345] +
* + [0] + # ---- + [39] + [1]
39 1 01 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [40] + [5]
40 5 01 + # 40 1 01 + #
Trigger remote 1 01 is the first number of
controller remote is 9 digit address code
[012345] +
* + [0] + # ---- + [41] + [09]
41 9 02 + # 41 2 01 + #
2 01 is the first number of
Trigger wireless is 9 digit address code
wirelers detector
# return to standby interface
Press
* +
[012345] +
* + [0] + # ---- + [42] + [1]
42 1 01 + # [077230023] 41 3 09 + #
Press
* + # return to standby interface
16 ACP824P
User manual System zone setting
User manual
[012345] +
* + [0] + # ---- + [43] + [24]
43 4 02 + # [035126025] 43 5 09 + #
[012345] +
* + [0] + # ---- + [44] + [8]
Program Address
LCD screen address code
44 8 01 + # dispaly
LCD screen dispaly
# return to standby interface
Press
* +
[012345] +
* + [0] + # ---- + [45] + [11]
Program Address
LCD screen address code
45 1 02 + # dispaly
LCD screen dispaly
# return to standby interface
Press
* +
ACP824P 17
User manual system zone setting
Burglar alarm zone only trigger under system arm status, delay and perimeter zone
trigger under stay or arm status.
24 hours, emergency and fire alarm zone will trigger under any system status
Factory default:
Wired zone 1-8 enable, wireless zone 9-32 enable, bus zone 33-64 disable, 00 is system
zone. Pls connect resistor 2.2k to wired zone before power on the alarm panel, otherwiset
he alarm panel will make alarm or cause zone trouble. When need use bus zone, 7601 one
zone expand module is required.
Example: set the number 59 zone as fire alarm zone
[012345] +
* + [0] + # ---- + [50] + [59]
Program Zone
LCD screen address
+ [6] 50 6 03 + # dispaly
Type
LCD screen dispaly
Note: If only check the zone type, then enter zone number, then press # button.
The LCD will display the zone type.
5.2 Zone siren type setting(default continious sound)
The options of siren type:
0>mute 1> continious sound 1> pulse tone
Example:set zone 33 siren type as pulse tone
[012345] +
* + [0] + # ---- + [51] + [33]
Program Zone
LCD screen address
+ [2] 51 2 03 + # dispaly
Type
LCD screen dispaly
Press + # return to standby interface
*
Note: if only check the zone siren type, enter zone # , then press # button,
the LCD will display the siren type
18 ACP824P
User manual Other options setting
2.2KΩ NC
Z Z
NO 2.2KΩ
C C
Eol resistor N.G wiring Eol resistor N.O wiring
[012345] +
* + [0] + # ---- + [52] + [6]
+ [2] 52 2 02 + #
Note: if only see the loop type in the wired protection area, press # to display the
loop type after inputting the protection area number
5.4 The response speed of wireless protection area (default is 500ms)
Configurable response speed of wireless protection area as below
For example: set the response speed for protection area No.3 is 10ms, Screen shows
[012345] +
* + [0] + # ---- + [53] + [3]
Program Zone
LCD screen address
+ [1] 53 1 02 + # dispaly
1>10ms
LCD screen dispaly
Note: If only can see the response speed of wireless areas, after inputting the protection
areas No. and press # , it will display the response speed. The common detector’
s response speed is 500ms, 10ms for High speed detectors and vibration sensors.
[012345] +
* + [0] + # ---- + [98] + [05]
98 5 02 + #
ACP824P 19
User manual Other options setting
Note: if the delayed time setting is 0 minutes, it means that it will not report the power
fault information.
6.2 Time calibration
For example: If the panel time every 24 hours fast 20 seconds, take the formula
20x100/24=83 to calibrate, then set this value is 083. If slows 20 seconds, then
it is 183 to calibrate the time.
[012345] +
* + [0] + # ---- + [99] + [083]
99 3 03 + #
6.3 Force arming: Allow users to arm when protection area faults. In the state of
the arming, the protection areas and recovery information will report to alarm
receiving centre. Default is disable.
0>Disable force arming 1>Enable force arming
For example: set enable force arming
[012345] +
* + [0] + # ---- + [60] + [1]
60 1 01 + #
6.4 Cross protection areas: protection area 1+protection area 2 + time + mode.
Configurable cross protection area mode as below
0>Cancel cross model
1> The double direction twice-trigger mode : single trigger protection area 1, 2,
it will not alarm, trigger first protection 1, then trigger protection area 2 within
preset time, it will alarm; first trigger protection area 2 then area 1, it will not alarm.
2>The double direction One-Shot mode: trigger protection area 1, protection area 1
alarm; trigger protection area 2 first then protection area 1 within preset time, then
it will not alarm; trigger protection area 1 behind the preset time, the protection
area 2 will alarm.
3>Twice-trigger alarm mode: one-shot trigger protection are 1 or 2, it will not alarm,
trigger protection area 1 and 2 in preset time separately, then protection area 1 and
2 alarm.
20 ACP824P
User manual GSM setting
[012345] +
* + [0] + # ---- + [70] + [07080502]
Zone 1 Time Mode
70 2 08 + # Zone 2
Note: It can set 3 groups of cross protection areas. The corresponding No is 70-72
6.5 Dial back specific No. : dial telephone No. that connected with panel, input the
# + administrator’s password after off-hook. It will be on-hook automatically
and the panel will call the preset the telephone No. which can execute the arm and
disarm operation in a long distance.
For example: set the dial back telephone No. is 12345678.
[012345] +
* + [0] + # ---- + [61] + [12345678]
61 09 + #
VII.GSM setting
7.1 GSM module set (default is disable)
For example: set enable GSM module.Configurable GSM information as below.
0>Disable 1 > Enable
[012345] +
* + [0] + # ---- + [80] + [1]
80 1 01 + #
LCD screen dispaly
Press # return to standby interface
* +
ACP824P 21
User manual GSM setting
[012345] +
* + [0] + # ---- + [83] + [2]
Program Type
LCD screen address
83 2 01 + # dispaly
[012345] +
* + [0] + # ---- + [82] + [1]
82 1 01 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [91] + [1]
91 1 01 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [89] + [05]
Program Signal
LCD screen address stregth
89 5 02 + # dispaly
22 ACP824P
User manual GSM setting
[012345] +
* + [0] + # ---- + [90] + [70]
90 0 02 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [81] + [1]
81 1 01 + #
[012345] +
* + [0] + # ---- + [84]
+ [202101078002] 84 2 12 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [85] + [03467]
85 7 05 + #
Press # return to standby interface
* +
ACP824P 23
User manual GSM setting
[012345] +
* + [0] + # ---- + [86] + [75640001]
Program User ID
LCD screen address
86 1 08 + # dispaly
[012345] +
* + [0] + # ---- + [87] + [12345678]
87 8 08 + #
Press # return to standby interface
* +
[012345] +
* + [0] + # ---- + [88] + [1]
88 1 01 + #
Press # return to standby interface
* +
24 ACP824P
User manual Technical specification
Technical specification
General data
External AC power supply vdtage: Input:
185~230VAC
Output: 13VAC/2A
Backup battey(optiond): 12V/7AH
The method of alarming dial:Telephone alarm 、 GSM alarm and
GPRS alarm
DTMF dial frequency variation :< 1.5%
Backup power supply duration:16 hours
Communication Protocol with CMS: Ademco Contact ID
Frequency: 433MHz/868MHz
E Signal transmit distance: 100 to 120 meters (open area)
Operation temperature range: 32F to 120F(0℃ to 45℃ )
Storage temperature range: -4F to140F(-20℃ to 60℃ )
Relative humidity:85% at 30 (86F)
ACP824P 25
User manual Limitation of the Products