Transformer Training (SNC Lavalin - District Cooling Project) - R01
Transformer Training (SNC Lavalin - District Cooling Project) - R01
Transformer Training (SNC Lavalin - District Cooling Project) - R01
2 C
2. Company Profile
P fil -------------------------------------------------------------- 3
4. Operation
p & Maintenance of oil-immersed Transformer ---------------- 37
Location
Sales & Marketing
140-2,
140 2, Kye-Dong,
Kye Dong, Chongro
Chongro-Ku,
Ku, Seoul, Korea
Design & Production
1, Cheonha-Dong, Dong-Ku, Ulsan, Korea
Factory Acreage :
HHI Complex CHINA
Area : ,
2,025 Acres
Building : 1,215 Acres
Electro Electric Systems(“EES”)
Area : 65 Acres
Building : 40 Acres
Employees : 26,000(EES : 3,000)
STATIONARY ROTATING
MACHINERY PLANT MACHINERY PLANT
2 1 Cores
2.1 C ------------------------------------------------------------------------------------------------------------------------- 17
. Drying
2.4 y g & Assembly
sse b y -------------------------------------------------------------------------------------------------------- 26
The primary winding is that winding to which the supply voltage is applied irrespective of whether it is the higher or
lower-voltage winding ; the other winding to which the load is directly connected is termed the secondary winding.
As the phenomenon of electromagnetic induction can only take place in static apparatus when the magnetic flux is
continually varying, it is clear that static transformers can only be used in electrical circuits having such characteristics,
that is, in Alternating-Current circuits. It means that transformers can not be used in Direct Current circuit
because there is no variation of magnetic flux in the circuit.
circuit
If an alternating Electromotive Force so called e.m.f is applied to the terminals of the primary windings of a
transformer with the secondary winding open circuited,
circuited a very small current will flow in the primary circuit only,
only
which serves to magnetize the core and to supply the iron loss of transformer.
We call the current no-load current.
Thus an alternating magnetic flux is established in the core which induces an e.m.f in both primary and secondary
windings. The magnetizing ampere-turns are given by the product of the magnetizing current and the primary turns.
Therefore, the no-load current is given by the total no load ampere turns divided by the primary turns.
E1
Primary induced voltage E1, E1 = 2 x π x f x N1 x Ф = 2 x π x f x N1 x B x S (V) =2XπXf XBXS
N1
E2
S
Secondary
d iinduced
d d voltage
lt E2 E2 = 2 x π x f x N2 x Ф = 2 x π x f x N2 x B x S (V) N2 = 2 X π X f X B X S
E2,
E1 E2
Therefore, above two formula can be expressed like this ; = N2 = 2 X π X f X B X S.
N1
As described in above formula, the induced voltage in a single turn of the primary and secondary windings is
exactly same and the induced voltages in the primary and secondary windings are proportional to the number
of turns of those windings,
g , correctly.
y
SSN
SS1
DS ; Core Diameter
HEK
(H i h )
(Height) SS ; Lamination Height
BS BF BS BF BS BS ; Silicon Steel Sheet Width
BSN
ES ES Fig. 2-2
BS1
Basic construction of core
Twin
R di l Twin
Radial T i
Triple
CTC
Fig. 2-3
The type of conductor
Fig. 2-4
Layer winding Helical winding Disk winding 3 kinds of windings
Fig. 2-5
Basic construction of windings
g
Fig. 2–7 Inserting the winding Fig. 2–8 a) Core & coil assembly
After the primary vacuum drying, core and coil assembly is pulled out of the vacuum drying oven to retighten the
loosed core and coil assembly caused by removing the moisture from the insulation material of the core and coil
assembly.
y
Furthermore after the insulating material has been retightened securely, the internal parts are given secondary vacuum
drying under the same conditions as mentioned previously because the insulation material of the core and coil
assembly absorbs some moisture of atmosphere during the retightening work up to a few percent
percent.
On the completion of the vacuum drying the core and windings are tanked and the transformer is filled with insulation
oil under high vacuum. The completion of the vacuum drying process can be judged by measuring insulation resistance,
tangent delta and hourly rate of extracted water from the transformer internal parts.
Since the insulation material is retightened firmly after complete drying through these both vacuum drying processes, it
iss abso
absolutely
u e y free
ee from
o further
u e sshrinkage
age due to
o yea
year round
ou d usage.
Fig. 2–15 Cooling Fan Fig. 2– 16 Attach to the flank Fig. 2–17 Attach to the bottom
ONAN 1. First letter : Internal cooling medium in contact with the windings ;
-. O : Mineral oil or synthetic insulation liquid with fire point ≤300℃
ONAF -. K : Insulating liquid with fire point >300℃
-. L : Insulating liquid with no measurable fire point
ONAN/ONAF/ONAF
2. Second letter : Circulation mechanism
ONAN/ONAF/OFAF -. N : Natural convection flow through cooling equipment and in
windings
ONAN/ODAF -. F : Forced circulation through cooling equipment, natural
ONAN/ODAF/ODAF convection flow in windings
-.. D : Forced circulation through cooling equipment, directed from
OFAF the cooling equipment into at least the main winding
3. Third letter : External cooling medium
OFWF
-. A : Air, W : Water
ODAF 4. Fourth letter : Circulation mechanism for external cooling equipment
-. N : Natural convection
ODWF -. F : Forced circulation
The life of a transformer is highly dependent upon the heat prevailing in the windings and core of the transformer.
International standards consider average transformer life to be 20 to 25 years.
years This estimation is based on continuous
operation at rated load and service conditions with a maximum ambient temperature of 40 ºC and a temperature rise of
65 K. The heat is caused by internal losses due to loading, high ambient temperature, and solar radiation. It is
important to understand how your particular transformers are cooled and how to detect problems in the cooling
systems. Therefore, it is important that the temperature of the transformer should be periodically or continuously
monitored. And also, the characteristic of insulating oil is extremely important and should be maintained at a high
quality according to the standard.
In case of On Load Tap Changer, it is important that the tap changer should be maintained in accordance with the
manufacturer’s recommendations. It is generally accepted that all new On Load Tap Changers are inspected internally
at the end of the first year of service, regardless of the number of operations.
There are the two important purposes of this internal inspection ;
First, it is to ensure that the internal mechanism is functioning properly.
Second, it is to measure switching contact wear so that the time interval between subsequent inspections may be
estimated.
For the first few days, daily inspections are recommended for recently energized transformers.
CONTENTS
1. GENERAL ---------------------------------------------------------------------------------------------------------------------- 40
2. SAFETY REGULATIONS -------------------------------------------------------------------------------------------------- 41
2.1 General ----------------------------------------------------------------------------------------------------------------------- 41
2.2 Safety ------------------------------------------------------------------------------------------------------------------------- 42
3. OPERATION AND CHECK ITEMS ------------------------------------------------------------------------------------- 44
3.1 Normal Operation ----------------------------------------------------------------------------------------------------------- 44
3.1.1 Conditions of valves ----------------------------------------------------------------------------------------------------- 44
3.1.2 Fan and pump operation ------------------------------------------------------------------------------------------------- 44
3.2 Emergency
g y operation
p ------------------------------------------------------------------------------------------------------ 45
3.2.1 Loading guide ------------------------------------------------------------------------------------------------------------- 45
3.2.2 Over excitation operation ------------------------------------------------------------------------------------------------ 45
3.3 Inspection and check ------------------------------------------------------------------------------------------------------- 46
3.3.1 Protective accessories and pre-set values ----------------------------------------------------------------------------- 46
3.3.2 Inspection and check items before operation ------------------------------------------------------------------------- 47
3 3 3 Inspection and check items of transformers in service -------------------------------------------------------------- 62
3.3.3
4. MAINTERANCE -------------------------------------------------------------------------------------------------------------- 88
4.1 Forwards --------------------------------------------------------------------------------------------------------------------- 88
4.2 Classification of maintenance and inspection -------------------------------------------------------------------------- 90
4.3 Daily maintenance and inspection --------------------------------------------------------------------------------------- 91
4.4 Periodical maintenance and inspection ---------------------------------------------------------------------------------- 95
4.5 Maintenance and inspection standard ----------------------------------------------------------------------------------- 115
4.5.1 Inspection of transformer insulation ----------------------------------------------------------------------------------- 115
4.6 Gas analysis
y on transformer oil ------------------------------------------------------------------------------------------ 123
4.6.1 Analysis method ---------------------------------------------------------------------------------------------------------- 123
4.6.2 Assessing the test results ------------------------------------------------------------------------------------------------ 123
5. TROUBLE SHOOTING ----------------------------------------------------------------------------------------------------- 126
6. RECOATING ------------------------------------------------------------------------------------------------------------------- 156
6.1 Recoating cycle ------------------------------------------------------------------------------------------------------------- 156
6 2 Method of recoating ------------------------------------------------------------------------------------------------------- 156
6.2
6.2.1 Outdoor service equipment --------------------------------------------------------------------------------------------- 156
6.2.2 Indoor service equipment ------------------------------------------------------------------------------------------------ 157
7 FACTORY REPAIR PROCEDURE -------------------------------------------------------------------------------------- 157
7.
1. General
This instruction manual is prepared as a guide to the operation and maintenance of Hyundai transformers.
Every man who works on the operation and maintenance of the transformer should be constantly aware of what he
should do and should not do to maintain the high quality and reliability of the transformer.
All work-operation, inspection and maintenance should be done according to this manual.
All
ll off possible
ibl contingencies
i i which
hi h may arise
i during
d i operation
i andd maintenance
i are not coveredd with
i h this
hi manual.
l
When further information is necessary or a particular problem not covered with this manual, contact the manufacturer
about that.
Hyundai Heavy Industries Company LTD. would furnish sufficient information willingly.
Before dealing with transformer, one must read and remember this manual especially clause 2. Safety
Regulations.
Not following these instructions may cause personal injury or property damage.
2. SAFETY REGULATIONS
2.1 General
Safety regulations are intended to alert personnel who are in charge of transformers with possible personal injury,
d h or property ddamage. One must avoid
death id improper
i working
ki mentioned
i d ini this
hi manual.
l Safety
f levels
l l quotedd in
i this
hi
manual are defined in three levels, have a mark of and are printed in bold characters as follows ;
Extreme hazardous working that can cause severe personal injury, death or property damage.
Hazardous or unsafe working that has possibility of injury, death or property damage.
Unsafe or improper working, which can result in minor personal injury or property damage.
All safety regulations with the symbol have to be strictly observed to prevent person from related hazard or
property damage. Each person, operator or who is in charge of a transformer, has to read and be aware of the
regulations.
g The whole pparts of clause 2 is related with safety.
y These instructions must be obeyed
y during
g working
g on a
transformer.
2.2 Safety
The following safety precautions must be observed while the transformer is in service.
1) Working near a energized transformer.
2) Liquid level
Do not open any valve or pull any plug on a transformer or any of its accessories while the
transformer is energized because the liquid level inside the transformer can drop below the minimum
level except gas or oil sampling valves.
A iinternal
An t l flashover
fl h may occur if the
th liquid
li id level
l l isi lowered
l d below
b l minimum
i i level.
l l
3) Control circuits
Caution must be used when operating any of the switches or breakers because the control circuits,
inside and outside the control cabinet, utilize voltages that can be dangerous to personnel.
If it is necessary to work on the circuits,
circuits the power supply must be switched off
off.
4) Cooling equipment
5) Jacking
When unloading the transformer or placing it in position, make sure that the jack lugs or places
designated for jacking it on the outline drawing are used when jacking the unit.
The use of jacks on any other part of the transformer may require costly repairs.
6) Pulling eyes
Always pull the transformer with pulling eyes supplied on the unit.
Check the outline drawings for the proper fittings to use.
7) Current transformers
The secondary terminals of any current transformers not connected to auxiliary circuits must be shorted
and
d grounded.
d d
8) Electrical grounding
3 2 2 Over
3.2.2 O excitation
it ti operation
ti
The transformer can be operated under over excitation condition as shown in Fig. 1. If a different permissible curve
was submitted, refer to that curve instead of Fig. 1. The great care must be taken to minimize the over excitation
period to avoid giving excessive thermal stress to the transformer.
transformer As explained in the Fig.
Fig 1 of permissible over-
voltage characteristics, the transformer can be continuously operated at 110 % of rated voltage and also operated at
about 140 % of rated voltage for 10 seconds after energizing the transformer.
150
140
Fig 1
130
P
Permissible
i ibl
120
over-voltage
110
100
Characteristic
Excitation [%] 0.2 1 10 100 ( Typical )
Time [ min ]
1 Buchholz relay ( EE3 of CED - ASPE ) Volume of gas : 250㎤ Oil velocity : 0.9 m/sec.
2 Protective relay for OLTC ( M Type of MR ) - Oil velocity : 1.2m/sec.
6 Oil level indicator For OLTC Low oil level ( Low-Low oil level )
7 Pressure relief device for main tank ( 0.7Kg/㎠ ) 0.7Kg/㎠
8 S dd pressure relay
Sudden l ( 00.035kg/㎠/sec.
035k /㎠/ ) 0 035k /㎠/
0.035kg/㎠/sec.
- These pre-set values may be changed according to the applied accessories and site conditions.
For more detail, refer to attached instruction of each component.
When oil level indication is not within ±10 ºC of oil temperature indication, adjust the oil level correctly in accordance
with calculation results from the temperature difference between oil level indication and oil temperature indication, the
coefficient of oil expansion of 0.78 X 10-3 / K as well as the total volume of transformer oil.
No
No. Accessories Check Items Normality Result Remarks
Insulation resistance value expresses the quality of insulation material inside the transformer. The measurement
sshould
ou d be made
ade betwee
between each
eac winding
w d g and
a d ground
g ou d as well
we as between
betwee windings
w d gs themselves
t e se ves by means
ea s of
o a megger
egge
tester of more than 1000V.
When there is some damage on the outside surface of transformer, the damaged parts are painted with touch up paint
according to instructions described in clause 6.11 touch-up painting of Hyundai’s another instruction manual HHIS-
WZ-TE-100 (6) titled “ SHIPMENT, STORAGE AND ERECTION OF OIL IMMERSED TRANSFORMERS”.
No. Items Contents and Notes Judging Standard Action in case of abnormality
No. Items Contents and Notes Judging Standard Action in case of abnormality
Transformer
5) Some more details for other type
temperature
infrared detecting devices are
1 indicator and
described at the below part of this
load
table.
indicator
Calibration of temperature indicators.
Each temperature indicator had been already calibrated by its manufacturer or transformer manufacturer
manufacturer. It means that
no further calibration is required in principle. But if necessary, take following procedure to calibrate the temperature
indicators when error is less than 5 ºC.
1. To check calibration, put the bulb of the temperature indicator in boiling
g water (100 ºC) or in a well stirred bath with
a control thermometer and read the indication of the indicator after 15 minutes.
2. If necessary, adjust the pointer by carefully turning the screw on its pointer or on its face.
3. If error is larger than 5 ºC, Hyundai recommends you to contact its manufacturer or transformer local agent.
4. Refer to another Note and Calibration Method for Resistance thermometer and Temperature monitor described in
clause 5. TROUBLE SHOOTING of this manual.
Somee more
So o e deta
detailss for
o ot
other
e type infrared
a ed detect
detecting
g dev
devices.
ces.
Since all matter emits infrared rays in proportion to its temperature, an infrared detecting device can be used to
determine loose connections, overloading of conductors, localized overheating in equipment, or similar conditions
before they become serious. Some equipment is sensitive to a fraction of a degree. Infrared inspection can be done
from a distance, since touch with the item being measured is not required. Substation equipment, such as bare bus,
disconnect switches and connections, can be checked without being de-energized. The inspection is made by aiming
the infrared detector at various area of the substation and everywhere the hot spots are.
Several types of infrared detectors are available. These vary from a simple hand held instrument similar to a gun,
through which the operator can detect hot spots and note their locations, to complex equipment requiring qualified
operators
t andd product
d t photographs
h t h as a permanentt record
d off th
the area bbeing
i checked.
h k d Th
The simpler
i l ddetectors
t t are usually
ll
sold outright, while the complex items are usually used by infrared detection services which contract to do the work.
Having an instrument readily available can be justified for a large installation with several substations, while a contract
to have a survey performed would probably be better for a small installation
installation. However
However, as a low cost alternative,
alternative a
camera with infrared sensitive film may be used, or a self calibrating portable indicating unit can be coordinated with a
polaroid camera.
At maximum rated current, the bushing outer terminal normally takes a temperature of about 35 to 45 K above the
ambient air. Significantly higher temperatures, especially at lower current loading, can be a sign of bad connections.
For bushing terminals and connections, maximum values of temperature and temperature rise above ambient air are
given
i in
i a table
t bl as described
d ib d on nextt page.
Maximum Maximum
Comments
Description of component temperature rise temperature
Note a
i K
in i ºC
in
Copper and copper alloys, uncoated Note d
In air 45 75
In SF6 60 90
In oil 50 80 Note b
Maximum Maximum
Comments
Description of component temperature rise temperature
Note a
in K in ºC
Silver / Nickel plated
Screwed In air or SF6 85 115
contacts In oil 70 100 Note b
Insulation class
A ( OIP ; Oil IImpregnated
dPPaper ) 75 105
E ( RBP ; Resin Bonded Paper or 90 120
RIP ) 100 130
Metallic parts in B ( GIF ; Gas Impregnated paper or
contact with plastic
l i Film
Fil )
SF6 e Note e
Oil e N t e
Note
N
No. It
Items C t t andd Notes
Contents N t J d i St
Judging Standard
d d A ti in
Action i case off abnormality
b lit
1) When the indication is much lower
considering transformer load and
1) After checking and
ambient temperature, it is possible
recording the indications of
When oil level that there are some leaks on the
oil level indicator, ambient
indication is within transformer caused by poor joints or
temperature, transformer
±10 ºC of oil temp. wrong welding parts.
2 Oil levels load (MW, MVAR) and
indication, the oil 2) After repairing them, fill the
voltage
voltage,
level indicator is transformer with insulating oil
2) compare the indications
operating, acceptably. according to calculation results
with the data previously
by using format described in the
obtained.
normality column of accessories oil
level indicator of clause 3.3.2
No. Items Contents and Notes Judging Standard Action in case of abnormality
No. Items Contents and Notes Judging Standard Action in case of abnormality
No. Items Contents and Notes Judging Standard Action in case of abnormality
1) In case severely corroded spots
1) Check excessive corrosion
should be brushed with steel wire
and oil leaks.
and painted with rust inhibition
2) Pay special attention to When there is no
Transformer paint.
11 the flanges and gaskets of corrosion and oil
tank 2) In case of oil leaks, refer to the third
bushing, valves, and leaks, it is normal.
and fourth items of the action in
radiators as well as the
case of abnormality column of
lower section of main tank.
tank
above item No. 5 Oil leaks.
No. Items Contents and Notes Judging Standard Action in case of abnormality
1) When there is some dirty oil trace
on the transformer tank or the
indication pin is not at the original
position,
i i cleanl up the
h trace, reset the
h
pin at the original position and
make the following measurements
after disconnecting the transformer
1) Check if there are dirty oil 1) When there is no f
from ttransmission
i i lines
li ;
traces around the pressure dirty oil traces, (1) Measure the insulation
Pressure relief device. 2) And the indication resistance value between each
13 winding and ground as well as
relief device 2) Check if the indication pin pin is at the
between the windings
of the device is at the original position, it
themselves.
original position. is normal.
(2) Ratio measurement either with
measuring kit or by applying low
voltage to the HV side.
(3) Measure the winding resistance
by using DC power.
(4) Measure the no-load current by
applying
pp y g low voltage g to the HV
side.
1) The utmost attention should be given to ensure that human life is not endangered, and to
protect the transformer or associated equipment from damage.
2)) The ppower supply
pp y must be isolated from the transformer to pprotect pperson from no
electric shock and malfunction of the equipment.
1 General
3) Every work must be properly planned to ensure that the necessary tools, spare parts and
person are available.
4)) The necessary y tools used in transformer tank should be tied to worker with a cord
and the dry, clean and lint free cloths should be used inside the transformer.
1) Before commencing every work on the transformer it must be isolated from power
supply and a work permit must be issued. This will involve isolating the relevant
breakers, checking that the supply is off by testing with correct electrical detectors or
instruments and ensuring that the switches are properly padlocked.
2) In addition, transformer terminals must be earthed by means of grounding switch.
Prior to
2 3) No one must be allowed to work on the transformer without a work permit signed by an
working
authorized person.
Be certain that auxiliary power supply is off and all the terminals are grounded before
all of the work. Not doing those can cause severe personal injury or property damage.
4.1 FORWARDS ( 2 / 2 )
N
No. INSPECTION CAUTIONS
1) If it is necessary to take an internal inspection, this should first be discussed with the
manufacturer Hyundai in ULSAN, KOREA or in the local representative.
Th workk should
The h ld onlyl be
b done
d either
i h byb a service
i engineer
i off the
h manufacturer
f or under
d
the supervision of an engineer of the manufacturer.
2) During an internal inspection it is essential that no foreign material or items are dropped
in the transformer tank and hence special precautions must be taken to prevent this.
Internal Before opening a transformer or removing any part of cover, make sure that the
3
inspection internal pressure is zero.
zero The oil level has to be lowered
Do not enter the transformer or do not breathe the inside air of the tank unless the
oxygen content of the gas inside the transformer is 19.5% ∼24%.
Oxygen contents less than this can cause drowsiness, injury or death.
Whenever anyone is inside the tank, other personnel must be near to the manhole on
the cover
cover.
Daily maintenance and inspection during operation together with checking a transformer at
regular intervals and visual inspections are as below ;
1) Read and record the indications of all gauges provided on the transformer.
transformer
Daily 2) These values should be compared with the values obtained previously to detect for any
1 maintenance
abnormalities.
and inspection
3)) Duringg the inspection,
p pay
p y attention to anyy abnormalities such as noise, irregular
g
vibration, discoloration, smoke etc.
4) Some more detailed daily maintenance and inspection are described in clause 4.3.
1) Check and record the oil level shown by the oil level indicator.
2 Oil level
2) Check that the glass of oil level indicator is not dirty.
After checking
g the sound and vibration of cooling
g fans,, oil ppumps
p or transformer tank,,
3 N i
Noise
compare them with those values of other units.
Check the positions of all valves according to our recommendation described in Table 6-6 of
14 Valves Hyundai’s another instruction manual (6) titled “SHIPMENT, STORAGE AND
ERECTION OF OIL IMMERSED TRANSFORMERS”.
1) Check the indications of all instruments and the operation condition of all relays
16 Instruments connected to instruments.
2) Check dew inside the control panel or cable boxes.
Oil flow
18 Check the indications of oil flow indicators.
indicators
19 Others Check abnormal exciting noise and vibration.
According to Hyundai’s recommendation described on this page through next several pages, carry out periodical
maintenance and inspection. As described on the previous page, it is very important that the frequency of the periodic
inspections may need to be increased or decreased in accordance with the historical information obtained during these
maintenances, inspections and the operating conditions as well. When some faults and abnormalities are found
d i periodical
during i di l maintenance
i t andd inspection,
i ti the
th faults
f lt should
h ld be
b treated
t t d ini accordance
d with
ith action
ti ini case off
abnormality of the clause 3.3.3 inspection and check items of transformers in service.
PERIOD
INSPECTION
No. CONTENTS AND NOTES CRITERIA
ITEMS 1 month
Annually
(service)
1) Di
Dielectric
l t i strength
t th
O More than 40KV / 2.5mm gap.
( IEC 60156 )
1) Check mechanical
mechanism such as the
d i shaft
drive h ft with
ith bevel
b l gear, No iinterruption
N t ti excepting
ti both
b th endd
Off circuit tap O
4 the motor drive unit and the tap positions.
changer safety interlock circuit, if
provided.
2) Check oil leaks O No oil leaks.
Off-circuit tap changers which are installed and operated in network transformers only barely need to be inspected in
regular intervals
intervals, because the mechanical operation of the off-circuit
off circuit tap changer does not involve any significant
contact wear. If after several years of service in one position, an off-circuit tap changer is to be operated in another
one, several switching operations must first be performed. In order to remove possible tarnish on the contacts, switch
the off
off-circuit
circuit tap changer from the previous position to the new one and also to the adjacent positions. Experience
shows that up to 25 switching operations on each contact are necessary for this purpose. It is recommended that the
efficiency of this measure is verified by resistance measurement. For more details, refer to IEC 60214 or IEEE
tap changer standards.
PERIOD
INSPECTION
No. CONTENTS AND NOTES 1 month CRITERIA
ITEMS A
Annually
ll
(service)
Note 1 ; Following are technical data for M and MS type On Load Tap Changers of MR in Germany ( 1 / 2 ).
On Load Tap Changer Inspection inter
intervals
als (Operations) Water Dielectric
No.
Type Current Without oil filter With oil filter content strength
1 MIII 350 Y / MSIII300 Up to 350 A
100,000
,
Up to 350 A
2 MIII 500 Y More than
Less than
Up to 500 A 80,000 150,000 30 KV
40 ppm
(IEC60156)
Up to 350 A 100,000
3 MIII 600 Y
Up to 600 A 80,000
Note 1 ; Following are technical data for M and MS type On Load Tap Changer of MR in Germany ( 2 / 2 ).
On Load Tap Changer Inspection intervals (Operations) Water Dielectric
No.
Type
yp Current Without oil filter With oil filter content strength
3) Check the bushing oil level 2 or 3 The oil level is within ±10 ºC of oil
or the oil level gauge. O years temperature indication.
Bushings
6 ; refer to 4) Bushing terminal 2 or 3 The terminal temperature is less
O
Note 2. temperature years than
h 70 0 ºC at ratedd current.
PERIOD
INSPECTION
No. CONTENTS AND NOTES 1 month CRITERIA
ITEMS Annually
(service)
1) Th
The power factor
f off the
h
capacitance or potential tap will
generally be about 1.0 % or less.
2) The measurement will vary from
the original values according to
the loading history and
Bushings environment condition of the
2 or 3
6 ; refer to 7) Bushing capacitance values bushings
bushings.
years
Note 2. 3) Bushings showing signs of
deterioration should be tested at
intervals of 6 months to 1 year
andd removedd from
f service
i if the
h
test show a dangerous condition.
4) Regarding to Maintenance Tests
g refer to Note 3.
for Bushings,
Note 2 ; Followings are additional information for condenser type bushings, only ( 1 / 3 ).
There is no perfect insulator ; a small amount of leakage current always exists. This current leaks through and along
the bushing surface from the high voltage conductor to ground. If the bushing is damaged or heavily contaminated,
leakage current becomes excessive, and visible evidence may appear as carbon tracking (treeing) on the bushing
surface. Flashovers may occur if the bushings are not cleaned periodically.
Carbon tracking may occur more often in atmospheres where salts and dust deposits appear on the bushing.
Refer to the bushing manual for detailed instructions on cleaning and repairing your specific bushing surface.
Different solvents, wiping materials, and cleaning methods may be required for different bushings.
Note 2 ; Followings are additional information for condenser type bushings, only ( 2 / 3 ).
When the bushing has a gage with a pointer, look carefully, because the oil level should vary a little with temperature
changes. If the pointer never changes, even with wide ambient temperature and load changes, the gage should be
checked at the next outage. A stuck gage pointer coupled with a small oil leak can cause explosive failure of a
bushing, damaging the transformer and other switchyard equipment.
If th
the oil
il level
l l isi low
l andd there
th is i an external
t l oil
il leak,
l k check
h k the
th bolts
b lt for
f proper torque
t andd the
th gasket
k t for
f proper
compression. It is very important that the correct type gasket should be installed and the correct compression should
be applied. A leaky gasket is probably also leaking water and air into the transformer, so check the most recent
transformer Dissolved Gas Analysis for high moisture and oxygen.
oxygen If the oil level is low and there is no visible
external leak, there may be an internal leak around the lower seal into the transformer tank. After repairing the gasket,
the bushing should be passed with an internal oil pressure test and tightness tests in accordance with IEC 60137 or
IEEE bushing
g standards at the bushingg terminal capp and the bottom of the bushingg center tube,, respectively.
p y
Never open the fill plug of any bushing if it is at an elevated temperature because pressurized hot oil may suddenly
gush from the fill plug. Generally, bushings have a nitrogen blanket on top of the oil which pressurizes as the oil
e pands When oil temperat
expands. temperature
re is bet
between
een 15 ºC and 35 ºC,
ºC the bbushing
shing ma
may be safel
safely opened
opened.
If one phase bushing terminal shows markedly higher temperature, there is probably a bad connection. The
connection at the top is usually the poor one ; however, a bad connection inside the transformer tank will usually show
a higher temperature at the top as well. In addition, a bad connection inside the transformer will usually show hot
Note 2 ; Followings are additional information for condenser type bushings, only ( 3 / 3 ).
As a convenient accessory, condenser type bushings have its terminal of bushing voltage tap for measuring the power
factor and capacitance of the bushing.
Corona (air ionization) may be visible at tops of bushings at twilight or night, especially during periods of rain, mist,
f
fog, or high
hi h humidity.
h idit At the
th top,
t corona is
i considered
id d normall ; however,
h as a bushing
b hi becomes
b more andd more
contaminated, corona will creep lower and lower. If the bushing is not cleaned, flashover will occur when corona
nears the grounded transformer top. If corona seems to be lower than the top of the bushing, clean the bushing as
quickly as possible.
possible
ohm or better. While in this case, anything that is attached to the bushing ( such as contact assemblies or transformer
windings ) would also be energized ; only the insulation of the bushing between the center conductor and the
ungrounded tap or flange would be measured. In the case of bushings equipped with capacitance taps, a supplementary
test should always be made on the insulation between the tap and the flange.
When bushings with capacitance or potential taps are tested by the ungrounded test specimen method described in the
above subparagraph 1), it is recommended practice to include a separate power factor test on the tap insulation as well.
The exception to the separate power factor test is condenser type bushing which have tap outlets designed to operate at
less than 100 voltages. On all other capacitance or potential taps, tests are performed at several voltage levels from 2 to
5 KV.
KV It means that the maximum permissible test potential should be limited to bushing instruction manual and
specification for test instrument as well. The procedure is to energize the tap with the bushing center conductor and
flange grounded.
grounded The power factor of a capacitance or potential tap will generally be around 1.0
1 0 % or less.
less There are
the principal exception to this in some bushings because the inherent properties of the fibrous Bakelite material used
for the tap insulator have resulted in power factors up to 10 % for apparently satisfactory taps. In such cases, field
measurement, particularly ungrounded specimen tests, should compare with and the bushings be rated on the basis of
nameplate power factors. In general, any bushing that exhibits a history of continuous increase in power factor should
be questioned and scheduled for removal from service. Measured power factor values should be temperature corrected
to 20 ºC. The table of correction values are given in the Table 7-2 Temperature corrections for insulation power factor
test of Hyundai’s another instruction manual HHIS-WZ-TE-100 (6) titled “ SHIPMENT, STORAGE AND
ERECTION OF OIL IMMERSED TRANSFORMERS”.
When bushing deterioration can not be detected by DC insulation resistance, it is generally in an advanced stage
requiring immediate attention. A 2500 voltage insulation resistance meter may be used for an insulation resistance
check, but a high reading should not be completely relied upon as indicating a good bushing. Any bushing testing less
than 20,000 meg ohms has questionable insulating value.
4 Hot
4. H t wire
i test
t t for
f moisture.
it
Plastic type compound used to filled bushings may absorb moisture if there are leaks through the shell or cap.
A moisture content of as little as 0.15 % in soft compounds can be detected by pushing a red hot rod into the
compound If moisture is present
compound. present, a crackling,
crackling sputtering,
sputtering or hissing sound will be heard.
heard If no moisture is present
present, the
compound will melt quietly. Another test is to put some compound on a wire and melt it in the flame of a match.
If moisture is present, there will be a sputtering sound and small sparks will be thrown off. Dry compound will melt
without disturbance.
PERIOD
INSPECTION
No. CONTENTS AND NOTES 1 month CRITERIA
ITEMS A
Annually
ll
(service)
1) There is any air bubble inside
the relay.
2) Th
The flap
fl valve
l off the
th relay
l has
h a
vertical position in the middle of
1) Visual inspection. inspection window.
3) The pipe connected to the OLTC
Protective 2 or 3 conservator is placed with an
7 inclination of at least 2%.
relays years
2) Check operating and
insulation resistance of
thermometer, level gauge,
More than 10 ㏁.
flow indicator, gas detector,
pressure relay, vacuum
gauge etc
etc.
If necessary, replace the gasket with
Control panel 1) Check waterproof.
2 or 3 a new one
8 and terminal
2) Check the tightness of all years
box If necessary, tighten
i h theh connections.
i
connections.
There are two kinds of the deterioration of transformer insulation material as below ;.
The first is the deterioration of transformer
transformer’ss solid insulation material
material.
The second is the deterioration of insulating oil.
(1) For details of insulating oil test method and testing apparatus, refer to IEC-60296 or IEEE oil test standards such as
ASTM D1816 or ASTM D877 .
(2) When sampling insulating oil, utmost care should be taken to ensure no foreign objects such as water or dust are
mixed with the oil. Sample the insulating oil directly from the sampling valve on the transformer. Leave the
sampled oil in the test container for the specified period of time and conduct the test as soon as possible afterwards.
All testing and sampling apparatus should be cleaned and dried prior to oil sampling and testing.
Table 3.5.1 are standard test items to determine the first deterioration of transformer’s solid insulation material.
As explained in Table 3.5.1, there are inspection items such as insulation resistance, dielectric loss factor and other
method.
method
Refer to the explanatory notes and judging standards of each inspection items as below ;
INSPECTION JUDGING
No. EXPLANATORY NOTES
ITEMS STANDARD
In connection with determination of insulating oil deterioration as the second deterioration of transformer insulation
material, refer to this judging standard for each inspection item of insulating oil.
[ Table 3.5.2
3 5 2 ] Determination of insulating oil deterioration ( 1 / 2 )
INSPECTION JUDGING
No. EXPLANATORY NOTES
ITEMS STANDARD
INSPECTION JUDGING
No. EXPLANATORY NOTES
ITEMS STANDARD
Moisture
4 Karl fisher reagent method. Refer to Table 3.5.6
content
The life of transformer is considered the same as the life of insulating material in the transformer tank such as
insulating oil and solid insulation material as well.
Especially insulating oil should be controlled in accordance with the requirements of following four tables described
Especially,
on next page because the characteristics of the oil can extend the life of transformer.
As an example, when the high voltage of a transformer is lower than 154KV, the breakdown voltage of insulating oil is
more than 50KV as a minimum requirement.
When the high voltage of a transformer is lower than 500KV and higher than 154KV, the breakdown voltage of
insulating oil is more than 60KV.
And the good condition of oxidation of the oil is less than 0.2mg KOH/g for 164 hours at 100℃
In case the good condition of resistivity of the oil is more than ten to 13th power ( = 1 X 1013 ) ohm - cm at 80℃.
2 ≤ 154㎸ CLASS, OLTC Less than 20 ppm 20 ∼ 30 ppm More than 30 ppm
As described in above table, when the high voltage of a transformer is lower than 154KV, the good condition of the
water content of insulating oil is less than 20 ppm.
In case of typical faults in transformer active part, the models of gas contents are shown in Table 3.6.2.
Table 3.6.1 and Table 3.6.2 may be referred to evaluate transformer condition.
Quantitatively, total amount of combustible gases (TCG) of 0.06㎖/100㎖ oil excluding carbon dioxide (CO2) is
generally accepted to determine the presence of incipient fault in transformer.
However, rate of increase in combustible gases shall be regarded most important.
Therefore we recommend gas analysis to be made once or twice a year to monitor change in the gases.
If the transformer is suspected of some incipient fault, consult with HYUNDAI agent or specialists.
5. TROUBLE SHOOTING ( 1 / 30 )
Trouble shooting described on this page through next some ten pages are also very important for you to operate
transformers under emergency condition. In case of the trip signal of Buchholz relay and pressure relief device as well,
the transformer should be inspected closely after completely isolating the transformer from transmission line as soon as
possible. Especially when an accessory of the transformers makes alarm signal or trip signal, refer to the previous
paragraph of 4.6.Gas Analysis on Transformer Oil along with the dissolved gas analysis results of your transformers.
Please remember this table of trouble shooting described on this page through next some ten pages because the trouble
must be treated in accordance with Hyundai’s recommendation for each fault described in the column of remedial
measures. And refer to the possible cause described in another column of the table.
5. TROUBLE SHOOTING ( 2 / 30 )
Accessories FAULT Possible Cause Remedial Measures
HHIS-WZ-TE-100 (6) titled “SHIPMENT, STORAGE
1) Oil loss. AND ERECTION OF OIL IMMERSED
TRANSFORMERS”.
1) Vent air bubbles from the Buchholz relay. The relay will be
automaticallyy filled with the oil duringg exhaustingg the air
2) Accumulation bubbles from the relay because there is sufficient insulation
of air. oil inside the conservator.
2) Put the relay back into operation when faults cannot be
found or the faults have been eliminated.
1) Check all the electrical connections.
Buchholz Buchholz relay 2) Check the signal mechanism of the Buchholz relay.
relay. - Alarm. 3) Signal fault.
3) After repairing the electrical connections and the signal
mechanism,, pput the relay
y back into service.
1) Take 1 liter oil sample from tank top and carry out a
4) Gas dissolved gas analysis in the sample.
generation due 2) Fill dry nitrogen gas into the Buchholz relay for 5 hours and
to inside analyze the gas for DGA.
DGA
failure. 3) When there is abnormal gas in analyzed results, the
transformer should be internally inspected with care to
5) Violent eliminate the fault.
vibration. If not, continuously operate the transformer after venting the
gas from the relay.
5. TROUBLE SHOOTING ( 3 / 30 )
Accessories FAULT Possible Cause Remedial Measures
4) Gas
4) Take 1 liter oil sample from tank bottom and check the
generation due
dielectric strength of the oil. When the dielectric strength
to inside
is less than Hyundai’s recommendation as described in
failure.
Table 3.5.3 of this manual, the oil should be dried out in
5) Violent
accordance with the procedures of Degassing and Drying
vibration such
Buchholz relay Transformer Oil as described in clause 6.9 of Hyundai’s
as the
- Alarm. another instruction manual HHIS-WZ-TE-100 (6) titled “
mechanical
SHIPMENT, STORAGE AND ERECTION OF OIL
shock of
IMMERSED TRANSFORMERS”
TRANSFORMERS .
earthquake or
Buchholz other
5) If the oil has enough dielectric strength, continuously
relay. mechanical
operate the transformer.
shock.
1) Oil loss.
2) Violent oil 1) Maintain the shutdown status of the transformer.
surge due to 2) Make the following measurements :
2.1) Measure the insulation resistance value between each
inside
Buchholz relay winding and ground as well as between the windings
flashover.
- Trip. themselves.
3) Violent gas
2.2) Ratio measurement either with measuring kit or by
generation due applying low voltage to the HV side.
to inside 2 3) Measure
2.3) M th
the winding
i di resistance
it by
b using
i DC power.
failure.
5. TROUBLE SHOOTING ( 4 / 30 )
Accessories FAULT Possible Cause Remedial Measures
2.4)) Measure the no-load current by y applying
pp y g low voltage
g
to the HV side.
1) Oil loss. 3) Take all remedial measures including tests and analysises
2) Violent oil described in the remedial measures column of Buchholz
surge
g due to relayy – Alarm.
inside 4) Compare the results with the test certificates attached to the
flashover. transformer instruction manual. When the difference
Buchholz Buchholz relay 3) Violent gas between both results is not within permissible tolerance, the
relay.
y - Trip.
p generation due
g transformer should be internally y inspected
p with care to
to inside eliminate it after finding out the fault. When the difference
failure. between both results is within permissible tolerance, vent air
4) Violent from the Buchholz relay and put the transformer back into
vibration. service.
5) Fault tripping. 5) When any faults cannot be found or faults have been
eliminated, vent air from the Buchholz relay and put the
transformer back into service.
When the Buchholz relay makes alarm signal, the transformer can be continuously operated but some tests and
examinations for fault analysis should be made as soon as possible.
While when the relay
y makes trip
p signal,
g , maintain the shutdown status of the transformer to eliminate the fault.
5. TROUBLE SHOOTING ( 5 / 30 )
Accessories FAULT Possible Cause Remedial Measures
1) Maintain the shutdown status of the transformer.
2) Check the pipes and shut-off devices. When the valve
fitted between the transformer tank and the conservator is
1) Conservator
closed, open the valve after unscrewing the locking bolts of
pipe shut off
Pressure relief the valve and put the transformer back into service.
Pressure or clogged.
device Wh inside
When i id the
h pipe
i isi clogged,
l d clean
l out the
h inside
i id off the
h
relief device. pipe by using hot oil flush procedure, compressed air or
- Trip.
cylinder type steel wire brush.
2)) Electric Check the transformer accordingg to the pprocedure as
flashover described in the remedial measures column of Buchholz relay
inside the tank. – Trip.
Pressure 1) Maintain the shutdown status of the transformer.
relief device Pressure relief 2) Check the tripping mechanism of the relay.
relay
of diverter device 3) After removing the diverter switch from its chamber, check
switch - Trip. it and especially measure the resistance values of transition
chamber. Oil surge
resistors to compare the measurements with the original
produced by a
values marked on the name plate of the tap changer.
changer
Protective fault in the
If necessary, change it with a new one.
relay of Protective diverter switch
4) When main or auxiliary contact had been worn too much,
diverter relay chamber.
the contact should be replaced with a new one.
switch - Trip. 5)) After takingg above remedial measures,, reset the tripping
pp g
chamber. mechanism and put the transformer back into service.
5. TROUBLE SHOOTING ( 6 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Resistance 1) Transformer Reduce transformer load by using other transformers
thermometer. overload.
l d connected
d to the
h same load
l d in
i parallel.
ll l
Oil or winding 1) In case oil and winding temperatures are too much higher or
temperature lower considering transformer load and ambient temperature,
- Alarm or 2) Inadequate
Temperature correctlyy adjust
j the indications byy turningg the bolt fitted on
trip. li
cooling
monitor. the needle or face of indicators after calibrating them ( refer
equipment.
to calibration method described in Note as below ).
If not, replace the indicators with a new one.
Note ; Calibration
C lib ti method th d recommended
d d by
b one off thermometer
th t manufacturers.
f t
In principle, it is not necessary for you to calibrate any kind of the temperature indicators because each temperature
indicator had been calibrated in its factory, already. But sometimes the calibration can be required for the indicator due
to another heating source located near to the capillary tube of the thermometers, solar irradiation and etc.
Calibration Method
1) After putting the bulb of the temperature indicator in 100 ºC boiling water or in a well stirred bath with a control
thermometer, check the temperature indication of the indicator after 15 minutes.
2) If necessary, adjust the pointer by turning the screw fitted on the needle or face of the indicator with care.
3) If error is more than 5 ºC,
ºC Hyundai recommends you to contact the local agent or representative of the thermometer
manufacturer.
4) In case of winding temperature indicator, the calibration should be done on the result of transformer temperature rise
test. The gradient between average winding temperature and average oil temperature should be adjusted by means of
the secondary current of bushing current transformer connected to the temperature indicator and a temperature
compensation component fitted inside the temperature indicator as well.
ELECTRO ELECTRIC SYSTEMS 131 www.hyundai-elec.com
OPERATION & MAINTENANCE / HHIS-WZ-TE-300 (06)
5. TROUBLE SHOOTING ( 7 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Resistance 2)) When radiator surfaces are dirty, y, the surfaces should be
thermometer. clean out by using compressed air.
3) When there are some leaks on radiator surfaces,
disassemble the damaged radiator from the transformer after
closingg butterflyy valves and drainingg out insulatingg oil from
the radiator and the leaks should be repaired by means of
metal bond or a suitable welding procedure.
After repairing the radiator completely, the radiator can be
reassembled at the original
g pposition and filled with new
Oil or winding insulating oil by using the oil drain valve, air vent of the
2) Inadequate
temperature radiator and oil purifiers as well.
cooling
Temperature - Alarm or 4) When the indications of oil temperature indicators are too
equipment.
monitor
monitor. trip.
p high
g consideringg transformer load and ambient temperature,
p ,
check if butterfly valves of cooling equipment are opened.
If not, open the valves.
5) When there are some leaks on the cooling equipment, take
the same remedial measures described in above item 3)) of
this accessories.
6) When there are some foreign matter inside the coolers,
eliminate the foreign matter from the coolers by using
hot oil flush p
procedure,, compressed
p air or cylinder
y type
yp steel
wire brush.
5. TROUBLE SHOOTING ( 8 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Resistance 7)) Check control device for cooling g equipment.
q p
thermometer. If the device has been damaged, stucked, or contaminated,
repair it or replace it with a new one.
8) When the previous setting values for alarm or trip signal are
too lower considering g transformer operation
p condition and
ambient temperature, reset new setting values according to
Oil or winding manufacturer’s recommendation described in the instruction
2) Inadequate
temperature manual of each accessory.
cooling
Temperature - Alarm or 9)) Check current transformers connected to thermometers.
equipment.
i t
monitor. trip. When the current transformers have been burned out due to
disconnecting the secondary leads of the transformers from
terminals or the concerned relay, replace the current
transformers with a new one and filter insulatingg oil by
y
using oil purifier.
10) After taking above remedial measures, put the
thermometers or the transformers back into service.
1) When the indication is too much lower considering
transformer load and ambient temperature,
1) Not enough
Oil level Oil level 2) It is possible that there are some leaks on the transformer
oil caused by
indicator. - Alarm. caused by poor joints or wrong welding parts.
oil leaks.
3) After repairing them, fill the transformer with insulating oil
according to calculation results from the temperature
5. TROUBLE SHOOTING ( 9 / 30 )
Accessories FAULT Possible Cause Remedial Measures
1) Not enough difference between oil thermometer indication and oil level
oil caused by indication, the total oil quantity of the transformer as well
oil leaks. as the coefficient of oil expansion of 0.78 X 10-3 / K.
2) Too much oil In case the oil level is higher than 10 ºC of oil temperature
due to indication due to overfilling transformers with insulating oil,
oil
overfilling some oil should be drained from the transformer according to
transformers the calculation result described in item 3) of above remedial
Oil level Oil level with insulation measures column for possible cause of not enough oil caused
indicator
indicator. - Alarm.
Alarm oil
oil. by oil leaks of this accessory.
accessory
1) If the oil level indicator indicates minimum oil level or
3) Too little oil make alarm signal caused by the damaged rubber bag or
due to the diaphragm of transformer oil preservation system, the
damaged rubber bag or diaphragm should be repaired or replaced
rubber bag or with a new one.
diaphragm. 2) After taking above remedial measures, put the relay back
into service.
If some oil should be added to the transformer tank, refer to oil filling procedure described in clause 6.8.6 of
Hyundai’s another instruction manual HHIS-WZ-TE-100 (6) titled “ SHIPMENT, STORAGE AND ERECTION OF
OIL IMMERSED TRANSFORMERS”.
If the oil level inside the transformer is insufficient
insufficient, some relays such as Buchholz relays or the protective relays of On
Load Tap Changer may make trip signal to protect the transformer from internal discharge due to the lower oil level.
5. TROUBLE SHOOTING ( 10 / 30 )
Accessories FAULT Possible Cause Remedial Measures
1)) S
Slide
de vvalve
ve Ope thee slide
Open s de valve
v ve aftere uunscrewing
sc ew g thee locking
oc g cap
c p bolts
bo s of
o
closed. the valve and put the oil flow monitor back into service.
Clean up inside the pipe by using hot oil flush procedure,
compressed air or cylinder type steel wire brush after
2) Pi
Pipe clogged.
l d di
disassembling
bli the
th pipe
i from
f the
th transformer
t f andd assembling
bli it
at the original position, put the oil flow monitor back into
service.
Seal leaks on the p
pipe
p byy means of suitable weldingg procedure
p
3) Pipe leaked. or adhesive such as metal bond and put the oil flow monitor
Oil flow back into service.
No oil flow.
monitor.
4) The incorrect
When the direction of motor is not correct,, change
g two wire
di ti off
direction
positions out of 3 phase power lines each other.
rotation
5) Oil pump fault 1) Repair the oil pump according to the source of the trouble
such as no such as no voltage,
g , or too low voltage.
g
voltage, too 2) When the trouble is caused by defective windings or
low voltage, damaged bearings, replace the damaged motor with a new
the defective one.
windingg of 3)) Check the setting g value of over current relay.
y If necessary,
y,
motor, and etc. adjust the setting value according to the starting current and
5. TROUBLE SHOOTING ( 11 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5)) Oil ppumpp fault
starting
t ti time
ti off the
th pump motor t or replace
l existing
i ti over-
such as no
current relay with a suitable new one if necessary.
voltage, too
4) Check the electrical connections of the tripping
low voltage,
Oil flow mechanism of the oil flow monitor. If necessary, take the
No oil flow. the defective
monitor.
it di l measures ddescribed
same remedial ib d in
i item
it 1) off above
b
winding of
remedial measures column of this accessory.
motor, or
5) After taking above remedial measures, put the oil flow
damaged
monitor back into service.
bearing.
g
1) Protective Clean up the protective screens of fan blades by using
screen iced up. compressed air, put it back into service.
No air flow or 1) Remove impurities from the coolers or clean them out by
Air flow
reduced
d d 2) Cooler is too using compressed air, put the air flow monitor back into
monitor
airflow. much dirtied service.
or clogged. 2) If the coolers are too much clogged, replace the coolers with
a new one.
1) When the trouble is caused by the defective winding or
Difference No air flow or damaged bearing, replace it with a new one.
pressure reduced Fan motor fault. 2) Check the setting value of over current relay.
switch airflow
airflow. If necessary
necessary, adjust the setting value of the over current
relay according to the starting current and starting time of
5. TROUBLE SHOOTING ( 12 / 30 )
Accessories FAULT Possible Cause Remedial Measures
1) Motor
1) Check the source of electric power of the motor drive unit.
protection
2) If necessary, repair the electric connection leads, the
switch
i h ( Q1 )
tripping mechanism, and the switches of the no-fuse
is not in
Motor-drive breakers of motor-protection switch ( Q1 ) and put the
The unit is out operating
unit of On motor drive unit back into service.
of service, position.
Load Tap
electrically. 2) When putting
Changer.
hand crank in After pulling out the hand crank from the drive shaft hole and
the drive shaft setting the crank at the original position inside the motor drive
hole of motor unit,, p
put the motor drive unit back into service.
drive unit.
5. TROUBLE SHOOTING ( 13 / 30 )
Accessories FAULT Possible Cause Remedial Measures
3) Open circuit
on one or After correctly fixing motor phase connections to the source of
more motor electric power, put the motor drive unit back into service.
phases.
4) Motor current When the trouble is caused by defective windings or damaged
is excessive bearings, replace the damaged motor with a new one or repair
due to phase the motor according to the source of the trouble and put the
failure. motor drive unit back into service.
5. TROUBLE SHOOTING ( 14 / 30 )
Accessories FAULT Possible Cause Remedial Measures
1) Relay
Motor-drive contractor is
stuck. After cleaning it up by using compressed air, repairing it
unit of On Drive keeps on
according to fault status or replacing it with a new one, put the
Load Tap running 2) Emergency motor drive unit back into service.
Changer.
g stop button is
stuck.
1) After checking all outside the mechanism, request a factory
1) Some engineer if a mechanical fault in the tap-changer is
components suspected.
d
defect from 2) The shield cap of the OLTC selector s/w part can make
operation partial discharge due to loosed bolts.
Operation mechanism 3) When insulation barrier touched to grounding parts, partial
T changer
Tap h mechanism
h i iis di h
discharge can occur
stuck.
2) Poor contact After checking all the contacts, request a factory engineer if a
making. mechanical fault in the tap-changer is suspected.
3) Carbon Clean out the carbon formation and perform the remedial
formation on measures of Buchholz relay – Trip fault as described in the
contacts. initial part of this trouble shooting.
5. TROUBLE SHOOTING ( 15 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5. TROUBLE SHOOTING ( 16 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5. TROUBLE SHOOTING ( 17 / 30 )
5. TROUBLE SHOOTING ( 18 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5. TROUBLE SHOOTING ( 19 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Mix 100 parts by weight ( p.b.w. ) epoxy resin in 20 p.b.w
hardener and the mixture shall be used within 45 minutes.
Brush the adhesive onto both surfaces.
The joint is hardened by means of contact pressure itself at
room temperature for 15 hours or at 70-80 ºC for 3 hours.
N t ;
Note
If the broken piece consists of several smaller porcelain
pieces, a polyacrylate adhesive can be used e.g. Lactate
401.
After cleaning out,
out brush the adhesive onto one surface of
two broken parts in a thin, covering layer.
Bushing Damaged Mechanical Place the two pieces in exact position as they were and
porcelains porcelain. shock. press the two pieces by hand together for 1 minute.
Excess adhesive is cleaned out. If necessary, y, fill voids
with epoxy paste as below ;
(2.2) Filling chips and voids where the piece is missed.
(2.2.1) Procedure ; Brown porcelain.
The damaged surface must be cleaned out by using ethyl
acetate.
This repair is performed by using epoxy resin, e.g. Araldite
121 P, and brown colored paste as well.
If necessary, the paste is mixed in Araldite coloring agent,
DW 0133 ( red ) to get the same color of the porcelain.
5. TROUBLE SHOOTING ( 20 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5. TROUBLE SHOOTING ( 21 / 30 )
Accessories FAULT Possible Cause Remedial Measures
The Araldite 2014 consists of two kinds of epoxy resins
in a 200 ml cartridge and can be applied to a handgun with
a mixer.
Mix them with some blue paint paste e.g. Araldite DW
0135 to o get
ge thee same
s e color
co o of
o thee porcelain.
po ce .
The resin is applied to layers and can be held in position
by using tapes.
After hardening it at room temperature for 15 hours or 70 –
80 ºC for 3 hours,, remove the tape,
p , wash off the resin
surface and smooth the surface by using sandpaper.
Bushing Damaged Mechanical Apply more compound if necessary - wash off the resin
porcelains porcelain. shock. surface and smooth the surface by using sandpaper.
Apply
pp y the varnish coatingg twice for hardeningg time of 2
hours at room temperature after the first coating and a
finish hardening time of 24 – 48 hours at room temperature
or 70 – 80 ºC for 3 hours after the last coating.
((2.2.3)) Procedure ; Unglazed
g surface.
This repair is performed by using epoxy resin e.g. Araldite
2014.
The Araldite 2014 consists of two kinds of epoxy resins
in a 200 ml cartridge
g and can be applied
pp to a handgun
g with
a mixer.
5. TROUBLE SHOOTING ( 22 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5. TROUBLE SHOOTING ( 23 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Following methods can be applied for repairing the leaks
under condition that the upper part of conservators is under
vacuum by means of vacuum pump and also the oil level of a
transparent vinyl tube connected to the drain valve of
transformer tanks is lower than the leaks,,
1) The small leaks through a pin hole on the transformer tank
wall possibly may be stopped by peening with a ball peen
hammer. Generally, the small leaks can occur after the
several yyear operation
p of a transformer without anyy leaks at
Hyundai’s factory or during transformer installation
Tanks and Mechanical including long storage because the pin hole is temporarily
Small leaks.
radiators shock. blocked due to the shoot ball blasting as well as painting on
the tank surface at Hyundai’s
y factory.
y
2) As an alternative, the small leaks may be stopped by using
metal bond or welding while the transformer filled with
insulation oil. When welding them, take an oil sample from
the transformers for Dissolved Gas Analysis
y jjust before and
just after welding as well as 24 hours later after transformers
are energized to check if gas increases due to the welding
work.
3)) When makingg vacuum inside transformer tank for the
welding procedures, the waiting period between releasing
5. TROUBLE SHOOTING ( 24 / 30 )
Accessories FAULT Possible Cause Remedial Measures
the vacuum from the transformer and putting the
transformer in service is longer than instructions described
Mechanical
Small leaks. in Table 6-7 of Hyundai’s another instruction manual
shock.
HHIS-WZ-TE-100 (6) because a vacuum may cause
bubbles to be formed in the insulating oil and cause arcing.
5. TROUBLE SHOOTING ( 25 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Cooling water
Oil leakage
l k 1) M
Maintain
i i theh shutdown
h d status off the
h transformer.
f
leaks into oil
detector 2) Request factory engineer service if an electrical fault in the
circulation
- Trip. transformer is suspected.
Oil-water system.
cooler 1) Leaks in After temporarily sealing up the leaks on the pipe or
No water flow
cooling water permanently repairing the leaks by suitable welding
or reduced
supplying procedure, put the cooling water supplying system back into
water flow.
system. service.
5. TROUBLE SHOOTING ( 26 / 30 )
Accessories FAULT Possible Cause Remedial Measures
to prevent the cooling fans from vibration and put the fans
1) Loose blades
blades.
back into service.
When fan motor load current is high due to impeded fan
Fans are out of 2) Damaged rotation or fan motor makes abnormal noise, replace the fans
Cooling fans. bearing.
g with a new one after disconnecting
g the fans from their power
p
service.
source and put the new fans back into service.
Repair the wires after disconnecting the wires from their
3) Broken wires.
power source and put them back into service.
Replace the starter with a new one and put the pumps back
1) Pump starter.
into service.
Pumps are out 2) Damaged
Oil pumps. Same as that of cooling fan.
of service. bearing
bearing.
3) Broken wires. Same as that of cooling fan.
1) High Replace dehydrating agent with a new one and put the breather
Silica gel has humidity
humidity. back into service.
service
been
Dehydrating 2) Glass cylinder Seal up the leaks on the glass cylinder, completely and put the
discolored, not
breather leaks. breather back into service.
from bottom to
top. 3) Moisture in Dry out inside the conservator by using dry air or nitrogen and
conservator. put the conservator back into service.
5. TROUBLE SHOOTING ( 27 / 30 )
Accessories FAULT Possible Cause Remedial Measures
5) Glass cylinder Replace the cylinder with a new one and put the breather back
Silica gel has is cracked. into service.
been
Dehydrating 1) When the moisture content of insulating oil is less than
discolored, not
breather Hyundai’s recommendation as described in Table 3.5.6
from bottom to
standard of water content of this manual, the transformer
top.
6) Too long can be continuously operated.
maintenance 2) If not, the oil should be dried out according to the procedure
interval of Degassing and Drying Transformer Oil as described in
clause
l 6.9
6 9 off Hyundai’s
H d i’ another
h iinstruction
i manuall HHIS-
HHIS
WZ-TE- 100 (6) titled “ SHIPMENT, STORAGE AND
ERECTION OF OIL IMMERSED TRANSFORMERS”.
1) Excessive
After checking the electric air clearance among live parts and
current on the
transformer tank, eliminate foreign matter on the transformer
Grounding Grounding line transformer
tank and the live parts and make sure that the tank and live
connection interrupted. tank due to
parts have sufficient electric clearance.
external
.
flashover.
5. TROUBLE SHOOTING ( 28 / 30 )
Accessories FAULT Possible Cause Remedial Measures
Electrical Dry out the excessive humidity inside the panel by using
Excessive
apparatus does compressed air or dry N2 gas, lower the setting value of
humidity in
not operate hygrograph stat as well as that of thermostat and put the panel
control panel
panel.
properly. back into service.
After drying out water or blowing off dust from inside the
Control Contacts
Water or dust panel by using compressed air, seal up the panel door and if
ppanel corroded or
inside the panel
panel. necessary fit a dust filter and put the control panel back into
necessary,
contaminated.
service.
Excessive high After fixing the distortion of the panel, protect the panel from
Apparatus
temperature
p in solar irradiation byy using
g shading,
g, pprovide the p
panel with a
h i bent.
housing b t
the panel. better ventilation and put the panel back into service.
5. TROUBLE SHOOTING ( 29 / 30 )
Accessories FAULT Possible Cause Remedial Measures
1) When
h theh moisture
i content iis more than
h Hyundai’s
d i’
1) Breather is not
recommendation as described in Table 3.5.6 standard of
suitable for
water content of this manual, take the second remedial
operation
measures of 6) too long maintenance interval in possible
condition
cause column
l off dehydrating
d h d i breather.
b h
considering
2) Shorten the maintenance interval of dehydrating breather or
transformer
add extra breathers to existing breather pipe line by using T
load variation
branch pipe.
and ambient
The
Th Breakdown
B kd 3) If possible,
ibl change
h oil
il preservation
i system from
f open type
humidity as
electrical voltage is too conservator system to rubber bag type conservator system
well.
break-down low due to high (close type) as an alternative method.
voltage of water content
oil.
il off oil.
il After temporarily sealing up the leaks in the system by using
2) Leaks in water
adhesive such as metal bond and permanently repairing the
cooling
leaks in the system or replacing it with new one, put the
system.
coolingg system
y back into service.
3) Water
1) After checking the water pressure, request factory engineer
pressure
service if a mechanical fault in the cooling water circulation
reducer is out
system is suspected
suspected.
of service.
5. TROUBLE SHOOTING ( 30 / 30 )
Accessories FAULT Possible Cause Remedial Measures
The Breakdown 2)) If possible,
p temporarily
p y seal upp the leaks byy usingg a suitable
3) Water
electrical voltage is too adhesive such as metal bond and permanently repair the
pressure
break-down low due to high leaks in the cooling water circulation system or replacing a
reducer is out
voltage of water content of damaged water pump in the system with a new one, put the
of service.
oil. oil. cooling system back into service.
1) Improper
Correctly set the ball position in the bottom of the
floating ball
condensation globe and put the breather back into service.
position.
Silica gel is not
blue. 2) Improper Shorten or prolong the frequency of regeneration cycles by
regeneration turning the blue dial on the control timer as necessary, and put
cycle. the breather back into service.
Maintenance
Free 1) Ch
Checkk supply
l feeders.
f d
Silica gel is not No voltage
Dehydrating 2) After repairing the electrical connections and the tripping
blue. supply.
Breather. mechanism, put the breather back into service.
1)) Leaks on the After temporarily
p y sealing
g up
p the leaks on the ppipe
p or
Silica gel is not connection permanently repairing the leaks, put the breather back into
turning pink pipe line. service.
during normal 2) Improper
operation.
p Prolong regeneration interval by turning the blue dial on the
regeneration
controll timer
i andd put the
h breather
b h backb k into
i service.
i
cycle.
6. RECOATING.
6.1 RECOATING CYCLE.
Since a coating is influenced by circumstances, it is difficult to show exactly the service life of coating.
Therefore, refer to the coating period for your reference as follows:
In case of bolt connecting point, primer is painted with heavy thickness and then finish coating should be done.
After the final coating is finished, it must be dried out for 2 hours at 25 degree C.
Repair work on touch up painting should be carried out only in dry weather and at the temperature of at least 5 ºC
because surfaces damped by dew must not be painted.
** HEAD OFFICE **
1) HYUNDAI HEAVY INDUSTRIES CO., LTD
ELECTRO ELECTRIC SYSTEMS,
SYSTEMS CUSTOMER SERVICE DEPARTMENT
1, CHEONHA-DONG, DONG-KU, ULSAN, KOREA, 682-792
2) HOMEPAGE: www.hyundai-elec.com
3) TEL: 82-52-202-7772
4) FAX: 82-52-230-8665
5) E-MAIL: [email protected].
** S
SEOUL
O O
OFFICE
C **
1) HYUNDAI HEAVY INDUSTRIES CO., LTD
ELECTRO ELECTRIC SYSTEMS, HYUNDAI B/D
140 2 KYE
140-2, KYE-DONG,
DONG JONGNO-GU,
JONGNO GU SEOUL
SEOUL, KOREA
3) FAX: 82-2-3668-0888
5.3 Main Accessories and Sub-Vendor List for Power Transformers --------------------------------------------------------- 162
Connection Dyn1
Temp. Rise ( Oil / Winding / Hottest ) 50 / 55 / 68
HV Winding 650 KV
Basic Impulse Level
( B.I.L. )
LV Wi
Winding
di / LV neutral
t l 110 / 110 KV
HV Winding 275 KV
P.F. Test Volt.
LV Winding / LV neutral 50 / 50 KV
% IZ between HV and LV Winding, at Principal tap 9 % ( at 22 MVA )
8 OIL TEMP
TEMP. INDICATOR 1 AKM34406-15X-12 0
AKM34406-15X-12.0 AKM / SWEDEN
BUCHHOLZ RELAY
10 1 EE3-ML WITH RG3.3 CEDASPE / ITALY
WITH GAS RELEASE DEVICE
12 PRESSURE RELIEF DEVICE FOR OLTC 1 213-012-01 (20 PSI) QUALITROL / U.S.A
COOLING FAN
15 88+2
2 3PH 60HZ 208V 1/2HP TAIJIN / KOREA
(INCLUDING SPARE COOLING FAN 25%)
No. Accessory
3,4 LV / LVN Bushing
10 O.L.T.C
24 P.R.D for Main Tank
25 P.R.D for OLTC
67 Vacuum Valve
96,97
, Pocket for WTI / OTI Sensor
98 Pocket for Spare
133 Core / Clamp Earth Device
138 LVN Earthingg Device
No
No. Accessory
1 HV Bushing
3,4 LV / LVN Bushing
21 Buchholz Relayy
41 Local Control Panel
110 Jack Pad with Pulling Eye
111 Man Hole for Side
112 Hand Hole for Bushing
115 Inspection Hole for Bottom
117 TR Base
Grounding
G di Pad
P d ffor M
Main
i
131
Body
No
No. Accessory
Average Winding Top Oil Temperature ; Top Oil Temperature ᅀΘWO x 1.3
Temperature 40.17 K = Oil Thermometer Ind.
ᅀΘWO
Core
Average Oil Temp.
; 28.32 K
Radiator Radiator ᅀΘWO Hottest spot Temp. =
Height
Winding Ther.
Hot spot Ind ; 62.19
Ind. 62 19 k
H
Coil
Average Winding
Temperature ; 45.26 K
Temperature
Bottom Oil Temp. Hot spot temperature above yearly The life of
Cooling Fan ; 16.47 K average ambient temperature transformer
110 °C 5 Years
Description IEC 60076 THE TROPICS
Max. / Yearly Average / Min. 104 °C
° 10 Years
Ambient Temperature 40 / 20 / - 20 °C 50 / 30 / - 5 °C
98 °C 20 Years
Temperature Rise 60 / 65 / 78 K 50 / 55 / 68 K
( Oil / Winding / Hot spot ) 92 °C 40 Years
Hot spot temperature above yearly 98 °C
average ambient temperature 86 °C 80 Years
H H H
Hydrogen Methane Ethane
H H H C H H C C H Type of Fault Main gases in Oil
H H H
Corona Sparking
p g Corona Hydrogen H2
H H H H H H H H
Methane CH4
C C C C Sparking
C C C C C Ethane C2H6
H H H H H H H H H H Heating Ethylene C2H4
Heating Arcing
H
Arcing Acetylene C2H2
H
C C H C C H
H H
Eh l
Ethylene A
Acetylene
l T
Temperature M i gases in
Main i Oil
C≡O O=C=O ≥ 105 ºC H2O, CO, CO2
Carbon monoxide Carbon dioxide
Heating ≥ 150 ºC H2, CH4
Fault types described in below table is taken from IEC 60599 of key gases, possible faults, and possible findings.
This table is not all inclusive and should be used with other information.
Fault Types ( 1 / 2 )
Key Gases Possible Faults Possible Findings
H2, possible trace of CH4 Partial discharge Weakened insulation from aging and electrical
and C2H6,
C2H6 possible CO CO. ( corona ).
) stress
stress.
Pinhole punctures in paper insulation with
H2, CH4 (some CO if discharges carbon and carbon tracking.
Low energy discharges
involve paper insulation). ( sparking and may be Possible carbon particles in oil.
oil Possible loose
Possible trace amounts of C2H6. static discharge ). shield.
Poor grounding of metal objects.
H2, CH4
H2 CH4, C2H6
C2H6, C2H4
C2H4, and the key
Metal fusion ( poor contacts in tap changer or
gas for arcing C2H2 will be present
lead connections ).
perhaps in large amounts.
High energy discharges Weakened insulation, from aging and electrical
If C2H2 is beingg generated,
g , arcing
g is
( arcing ).
) stress
stress.
still going on.
Carbonized oil. Paper destruction if it is in the
If paper is being heated, CO will be
arc path or overheated.
present.
Fault types described in below table is taken from IEC 60599 of key gases, possible faults, and possible findings.
This table is not all inclusive and should be used with other information.
Fault Types ( 2 / 2 )
Key Gases Possible Faults Possible Findings
All the above gases and acetylene in High energy electrical Same as above with metal discoloration.
large amounts. arcing 700 ºC and above Arcing may have caused a thermal fault.