POSIDYN
SDS 4000
MANAGEMENTSYSTEM
POSITIONING CONTROL
SYNCHRONOUS
OPERATION
TECHNOLOGY
SV. 4.5
06/2008
®
POSIDYN SDS 4000 STÖBER
ANTRIEBSTECHNIK
Table of Contents
Table of contents
1. Notes on Safety 1 10. Positioning Control 19
10.1 Function Overview 19
2. Technical Specifications 2
10.2 Connections 19
3. Physical Installation 3 10.3 Dest. Positions and Proc. Blocks 20
3.1 Installation Site 3 10.4 Absolute / Relative Positioning 20
10.5 Commissioning 21
4. Electrical Installation 3 10.5.1 Limited Position Range 21
4.1 EMC-Compatible Installation 4 10.5.2 Continuous Traversing Range (Rotary Axis) 21
4.2
4.3 FI
DCCircuit Breaker
Link Coupling 4
4 10.6 Reference Point Traversing 22
10.7 Position Controller 23
4.3.1 Direct coupling of devices 4 10.8 Process Block Chaining 23
4.3.2 Coupling of devices with DC fuse 4 10.9 Simple Examples 24
4.4 Electrical Installation 4 10.10 Emergency Off 25
4.5 Motor Connection, Halting Brake, X13 5 10.11 Ext. Rot./Lin. Path Measurement 25
4.6 Brake Resistor, X12 5 10.11.1 Position Encoder 25
5. Connection Assignment 6 10.11.2 Parameterization – Motor/Ext. Meas. Sys. 25
5.1 Terminal Overview 6 10.11.3 Special reactions with SSI encoders 25
5.2 Terminal Assignments 7 10.12 Posi Switching Points 26
5.2.1 Terminal X1 (I/O) 7 11. Synchronous Running, Elec. Gearbox 26
5.2.2 Terminal X2 (24 V) 7 11.1 Function Overview 26
5.2. 3 Terminals: X3 (Service), X20 (Encoder), 11.2 Connection of Pulse Source 27
X40 (Resolver), X41 (Sin/Cos) 8 11.3 Master - Slave 27
5.2.4 Terminals X11 and X12 (RBallast) 8 11.4 Commissioning 28
5.2.5 Terminal X13 (Motor) 8 11.5 Angle Difference 28
5.3 Control Portion, Terminal Strip X1 9 11.6 Angle and Speed Sync. Running 28
5.4 X3 Service Plug Connector (RS232, CAN) 10 11.7 Emergency Off 28
5.5 X40 Resolver 10 11.8 Reference Point Traversing - Slave 28
5.6 X20 Encoder In/Out (TTL) 10
5.7 Encoder Input (External Encoder) 11 12. Technology 29
5.8 X41 Sin/Cos, Absolute Value Encoder 12 12.1 PID Controller 29
12.2 Winders 29
6. Multi-Motor Operation 13 12.2.1 Diameter Sensor on AE1/AE2 29
7. Operator Control 14 11.2.2 Indirect Tension Control at M-Max Limit 30
7.1 Status Indication 14 11.2.3 Winding with Compensating Roller 30
7.2 Controlbox 14 11.2.4 Winding with Tension Sensor 30
7.2.1 Local Mode 14 11.2.5 Compensation of Fault Variables 30
7.2.2 Operation Indication 14 13. Parameter Description 31
7.2.3 Parameter Memory 15 14. Option Boards 59
7.2.4 Parameterization 15
14.1 Option Board SEA 4000 59
7.2.5 Password 15
14.2 Option Board SDP 4000 60
8. Commissioning 16 14.3 Opt. Board SEA+SDP 4000 (Combi Board) 60
8.1 Default Setting 16 15. Result Table 61
8.2 Motor, Braking Resistor 16
8.3 Speed Specification 16 16. Operating States 62
8.3.1 Speed Specification via Controlbox 16 17. Faults / Events 63
8.3.2 External Speed Specification 16
8.3.3 Speed Spec. via Potentiometer 16
STÖBER ANTRIEBSTECHNIK Deutschland 65
8.3.4 Characteristic Curve of Ref. Value 17 STÖBER ANTRIEBSTECHNIK International 67
8.3.5 Speed Spec. via Fixed Ref. Value 17 18. Block Circuit Diagram - Sync. Running 69
8.3.6 Speed Spec. via Clk Pulse Generator 17
8.3.7 Motor Potentiometer 17
19. Block Circuit Diagrams 69
8.3.8 Frequency Reference Value 17 19.1 Fast Speed Ref. Value Active (D99=1) 69
8.4 Speed Controller 17 19.2 Reference Value Processing 70
8.5 Halt / Quick Stop 17 20. Parameter Table 71
8.6 Brake Control 17 21. Accessories 74
8.7 Binary Inputs BE1 to BE4 (Opt. BE5 to BE15) 18
21.1 Accessories Overview 74
8.8 Parameter Record Selection 18
21.2 Braking resistor 76
8.9 Acknowledgment of Faults 18
21.2.1 Allocation of braking resistor to SDS 76
8.10 Motor Startup
21.2.2 Braking Resistor FZT/FZZT (Dimensions) 76
9. Torque Limits / Operating Range 18 21.2.3 Braking Resistor VHPR (Dimensions) 77
9.1 Torque Limits 18 21.3 Input Filter (Dimensions) 77
9.2 Operating Range 19 21.4 Output Derating (Dimensions) 77
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
1. Notes on Safety
1 NOTES ON SAFETY
To prevent avoidable problems from occurring during commissioning and/or operation, it is essential to
read and comply with this entire instruction manual before starting installation and commissioning.
Based on DIN EN 50178 (once VDE 0160), SDS-series servo inverters are defined as electronic power
equipment (BLE) for the control of power flow in high-voltage systems. They are designed exclusively to power
servo machines. Handling, installation, operation and maintenance must be performed in accordance with valid
and/or legal regulations, applicable standards and this technical documentation.
The servo inverter are products of the restricted sales class (in accordance with IEC 61800-3). Use of this
products in residential areas may cause high-frequency interference in which case the user may be ordered to
take suitable measures.
The safety notes and specifications stated in additional sections (items) must be adhered to by the user.
Never under any circumstances may the housing be left open or connections disc onnected when the power is
on. Disconnect the power plug of the servo inverter and wait at least 5 minutes after the power voltage has been
switched off before opening the servo inverter to install or remove option boards. Correct configuration and
installation of the inverter drive are prerequisites to correct operation of the servo inverter. Only appropriately
qualified personnel may transport, install, commission and operate this device.
• Permissible protection class: Protective ground; operation only permitted when protective
conductor is correctly connected. The devices may not be operated directly on IT networks.
• Installation work may only be performed in a voltage-free state. When work has to be done on the drive,
inhibit the enable and disconnect the complete drive from the power network. Adhere to the 5 safety
regulations.
• Do not penetrate the interior of the device with any kind of object.
• When performing installation or other work in the switching cabinet, protect the device against falling
objects (e.g., pieces of wire, flexible leads, metal parts and so on). Conductive parts may cause short
circuiting or device failure on the frequency inverter.
• Before commissioning, remove all extra coverings to prevent the device from overheating.
The servo inverter must be installed in a switching cabinet which does not exceed the maximum ambient
temperature (see technical data).
Only copper wiring may be used. For wire cross sections, see table 310-16 of standard NEC at 60° C or 75° C.
The motor must have an integral temperature monitoring device or external motor overload protection must be
used.
Either the motor itself must be equipped with temperature monitoring, or external protection against motor
overload must be used.
Only suitable for use on power networks which cannot supply more than a symmetric, nominal short-circuit
current of 5000 A at 480 Volt.
Notes: Subject to technical changes for improvement of the devices without prior notice. This documentation
is solely a product description. It is not a promise of f eatures in the sense of warranty rights.
1
®
POSIDYN SDS 4000 STÖBER
ANTRIEBSTECHNIK
2. Technical Specifications
Type of device SDS 4011 SDS 4021 SDS 4041 SDS 4071 SDS 4101 SDS 4141
Conductor cross section, power connection 1.5 mm² 1.5 mm² 1.5 mm² 1.5 mm² 2.5 mm² 4 mm²
Conductor cross section, motor connection 1.5 mm² 1.5 mm² 1.5 mm² 1.5 mm² 2.5 mm²
Conductor cross section, halting brake Min. of 0.75 mm² (consider voltage loss)
Conductor cross section, ext. 24 V/GND Max. of 2.5 mm² (consider voltage loss)
Overvoltage source
Permissible length of motor cable 25 m, shielded; 25 to 100 m, shielded with output derating
Auxiliary voltage, 24 V
18 to 36 V, 1 A
without brake connection
Auxiliary voltage, 24 V
24 V - 0% to 24 V + 10%, 3 A + 0.5 A at Sin/Cos
with brake connection
Fuses, 24 V Internal: 3.15 AT, external: max. of 16 AF due to conductor cross section 2.5 mm²
Installation altitude Up to 1000 m without restriction; 1000 to 2500 m with derating of 1.5%/100 m
1
Line circuit breaker - tripping characteristic D in accordance with EN 60898
2
External braking resistors with thermal monitoring are recommended. Mandatory for UL use!
2
®
POSIDYN SDS 4000 STÖBER
ANTRIEBSTECHNIK
3. Physical Installation
4. Electrical Installation
3 PHYSICAL INSTALLATION
•
Operate only in closed switching cabinet. •
Keep installation site free of dust, corrosive fumes and all liquids
• Install inverter only in vertical position. (in accordance with soil degree 2 in acc. with EN 60204/EN 50178).
• Avoid installation over heat-producing devices. • Avoid atmospheric humidity.
• Ensure sufficient air circulation in switching cabinet. • Avoid condensation (e.g., by anti-condensation heaters).
(Minimum free space of 100 mm over and under the • Use unpainted mounting plates with conductive surface (e.g.,
device!) unpainted) to conform with EMC regulations.
4 ELECTRICAL INSTALLATION
CONTROLBOX
SE RIE 4000 Resolver doubly shielded
F1 F2 E sc
Sin/Cos encoder doubly shielded
F3 F4
I 0
RS 232
Control lines
Controller shielded TTL
PLC Shielded Apply
shield
Terminate
shield Motor
(U,V,W)
Sharp edges, shielded
danger of injury
24 V
power pack
Power
Apply shield
3
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
4. Electrical Installation
4
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
4. Electrical Installation
11 12 13 Terminal block
L1 L2 L3 PE R1 R2 U+ U- B- B+ PE U V W
* * * * *
6 5 1 2 3
Tip:
With F08=0, the
brake is always Aux. contact
released. F08=1 Brake
activates auto- +24 V Power connector
matic brake con- Power STÖBER
trol by the invert- 0V Connector Cable
er. Also consider U 1 1 (U1)
BE function Free-wheeling V V 2 2 (V2)
4
F31=32:brakeRel diode V 2 )
0 +
= ) ) 1 W 6 3 (W3)
ease =
) ) 1 1 W
2 2 (U (V (
U
( ( E
W
2 1 P U V W
+ 24 V 4 5 (BR1)
* Cores in STÖBER
power cable
M 0V 5 6 (BR2)
L1 L2 L3 PE R1 R2 U+ U- L1 L2 L3 PE R1 R2 U+ U-
5
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
X41 Sin/Cos
X40 Resolver
X20 Encoder
X3 Service
X1 I/O
X2 24 V
Bottom of device
L1 L2 L3 PE R1 R2 U+ U- B- B+ PE U V W
6
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
Steuerungen X1
ANALOG GND 1 ANALOG GND
Digital ...
Controls X1
Safety 2 RELAY1
circuit READY
3
11 INPUT BE1
+ 24V
+ 24V 12 INPUT BE2
13 INPUT BE3
14 INPUT BE4
16 OUTPUT BA1
17 OUTPUT BA2
GND DIG. I/O 18 DGND
X2 (24 V)
V +24 24 V L1
V +24 = L2
XGND L3
XGND
7
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
see table 1 NC 1
9 see table 6 PTC
0V (GND) 2 PTC 2
10 0V-Sense 7 S4 Sin+
see table 3 S2 Sin 0V 3
11 see table 8 S3 Cos+
Up 10V geregelt 4 S1 Cos 0V 4
12 Up-Sense 9 R2 Erreg.+
DATA+ 5 R1 Erreg. 0V 5
13 DATA-
NC 6 14 PTC
PTC 7
15 CLOCK-
CLOCK+ 8
X41 Sin/Cos
H40=2 H40=3
Pin H40=1:Sin/Cos Encoder Schrittmotor
X20 Encoder
1 B- (+Sin) B+ Freq.+
3 A- (+Cos) A+ Vorz.+
9 B+(REFSin) B- Freq.- see table 5
9 NC
see table 4
11 A+ (REFCos) A- Vorz.- 8 +8 V, 250 mA
Null- 3
®
Standard: EnDat Sin/Cos absolute encoder 7 see table
Null+ 2
®
In parentheses: HIPERFACE - encoder 6 see table
PGND 1
X3 Service / CAN
X20 Encoder
PGND1 5
TxD 4 9 CANH Pin H20=1; 2 H20=3 H20=4 H20=5
8 4 A- Freq.- CLK+ CLK-
TxD 3
7
RxD 2 5 A+ Freq.+ CLK- CLK+
6 CANL
+8V 1 6 B+ Vorz.+ DATA+ DATA+
7 B- Vorz.- DATA- DATA-
R1 internal 2 R2
R2 braking resistor RBext
FB2
3 U+
U+
U- 4 U-
8
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
Ter-
Function Circuiting
minal
1 AGND: Reference ground for analog signals Reference potential for terminals X1.4 to X1.9
Controller
+24V
Binary output BA1 1
3k3
Open collector, 36 V (max.), 10 mA (max.), ϑ
BA1
16 Ta = 4 msec Outputs which can 25W
16
Pullup resistance µ 3.3 kΩ be programmed as 17
DGND
18
desired. Function is
specified with
parameters F80 Controller
Binary output BA21 (BA1) and F00 (BA2). A1 14
+24V
ϑ
Open collector, 36 V (max.), 10 mA (max.),
17 16
Ta = 4 msec 25W 17
BA2
A2 13 Digital 2
Pullup resistance µ 3.3 kΩ 18
DGND
1
Evaluation of the outputs via inverting interface terminals (e.g., Phönix DEK-REL-24/I/1)
9
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
Networking with an RS 232 ring is supported by FDS Tool. • Use only suitable cables with cores which are twisted
in pairs and shielded.
The RS232 ring can be used to control the inverters by • On the receiver side, the lines require low-ohmic termination
communication via USS protocol. and differential evaluation. Recommended termination
impedance: 150 Ω.
For more information on the USS protocol, see the USS • Connect ground on pin 1 with the ground of the higher-level
documentation (no. 441564). controller.
• Apply shield on both sides over a large surface to the
housing of the plug connector.
Top of device
8
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
9
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
5. Connection Assignment
Pin 1 2 3 4 5 6 7 8
B- A-
Signal 0V Up Data+ - PTC Clock+
+Sin +Cos
1)
Motor13 10 16 7 14 - 6 8
or-
Cable² br/bl yel br/rd gray - br/yel wt/bk
ange
Pin 9 10 11 12 13 14 15
B+ 0V A+ Up
Signal Data- PTC Clock-
RefSin Sense RefCos Sense
Motor1) 12 4 15 1 17 5 9
10
®
POSIDYN SDS 4000 STÖBER
ANTRIEBSTECHNIK
6. Multi-Motor Operation
6 MULTI-MOTOR OPERATION
D
B B V G
T T 4 N + - E E 1 2 + -
2 1 2 3
B B + X B B P U V W L L L P R R U U
3 1 2
1 2 1 1 1
X X X X X
0
2
3
D
A
m
5
2
<
m
c
0
2
>
V D
B B 4 G
T T 2 N + - E 1 2 3 E 1 2 + -
B B + X B B P U V W L L L P R R U U
3 1 2
1 2 1 1 1
X X X X X
m
ly 5
2
p <
p
u
-
s r ils r
g o
t te e V
n r c z
tw V m
tu e tzta e o 44 c
isw u N p 22 0
o hn 2
ep co <
L sc
= M
D
B B V G
T T 4 N + - E E 1 2 + -
2 1 2 3
B B + X B B P U V W L L L P R R U U
3 1 2
1 2 1 1 1
X X X X X
m
5
2
<
tz
ü
h T
c A
s 0
s 2
b x
ie 3 M
tr .
r n x
e A a
lt m
a
h
c
ts
p
u
a
H
1 2 3 E
L L L P
13
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
7. Operator Control
There are three ways to control and program When manual tipping is used for the drive, Controlbox can be
the SDS servo inverter. used to turn the motor shaft without having to address the
binary inputs.
• External Controlbox operator unit
• FDS PC software Switches to local mode and back. The drive stops
• Simubox Fieldbus communication (internal enable = off). An appears on the bottom right
of the display. A55 (manual key function) must be active.
7.1 Status indication Enable = turn on with local mode. The drive is in the
state 5:halt and can be controlled with the arrow keys
The SDS servostatus
three-position inverter is equipped
display, with
showing thea and .
operational status (e.g., "rdy" for ready) or Enable = off with local mode
the flashing number of a fault which has occurred If not already active, local mode is activated (i.e., the
(e.g., "E31" for fault 31:short/ground). drive stops).
Controlbox offers a plain-text display with additional diagnostic
capabilities (see chap. 16 + 17). 7.2.2 Operation indication
Operational states In speed (C60=0) mode, the layout of the operational display
Illegal direction of rotation. Specified direction of is shown below.
dir rotation contradicts the permissible direction of Speed Current
rotation in C02.
Turned on. Only for control via fieldbus (DRIVECOM
EnA
profile) clockwise
HLt Halt signal active (e.g., during manual traversing) Oper. state Brake
Switch-on disable (see chap. 16) chopper
inH. - Inverter is powered with +24 V but the network Parameter active
power is missing. set no. 2 active
Switch-on disable
- Enable was active during power-on and Autostart All possible operational states are listed in chap. 16. When
inH
was deactivated by A34=0. Inverter expects a is on, the inverter is using parameter record no. 2. No special
change from H to L level on enable input X1.15. indication is provided when parameter record no. 1 is active
i2t i2t message. Current limitation due to overload. (default setting). The symbol appears when the brake
chopper is running.
PoS Positioning mode. Drive is stationary.
C51 is used to scale the speed (when a gearbox is installed
rEF Reference point traversing on the motor, C51 can be used to indicate the output speed).
rdy Ready for operation (not enabled) The measured actual speed / C51 s indicated.
run Drive is enabled. The first line of the display can also be customized. A variable
selected via C50 (e.g., power) is divided by C51 and provided
Self test and calibration after +24 V becomes available with the unit in C53 (e.g., "items/min"). The unit can only be
on X2. Standard devices show the software version specified via FDS Tool. The number of positions after the
tSt after the 24 V power is turned on. Customized devices decimal point is provided by C52.
with modifications indicate tSt. For complete version In position mode (C60=2), the first line shows the act. position.
designation, see parameter E50. The second line shows the status.
FDS Tool has removed the enable so
Position
OFF parameterization can be performed. Enable again with
FDS Tool or turn 24 V OFF-ON to resume operation.
StP Limit switch is active.
ovin
14
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
7. Operator Control
7.2.3 Parameter memory immediately. The change value is accepted by pressing the
key. The Esc key undoes the change. To return from parameter
Controlbox offers memory space for the parameters of up to 7 selection to the group letters, press Esc . To return to the status
SDS servo inverters.
display, press Esc again.
Store parameterization of the SDS on Controlbox
Parameter changes must be saved with A00=1
• Press key. Display shows " A.. inverter." (save parameters) before the device is turned off.
• Press key. Display shows " A00 save param."
• Press key until "A03 write PBox" appears. Status rpm
• Press key until the second line of the display flashes. display clockwise
• Press the and keys to select the memory address
number (1 to 7). If the memory address is already occupied,
this is indicated with the name of the data record on the A.. B.. C..
display. inverter motor machine
• Press key to save the parameterization.
Read data from Controlbox
• Press key. Display shows" A.. inverter." Parameter
• Press key. Display shows "A00 save param." groups
• Press key. "A01 readBox&save" appears.
• Press key. The second line of the display flashes.
• Press the and keys to select the memory address
number (1 to 7). The data record names of the already
stored parameterizations are indicated. Parameter Value
EMC constant
• Press key to read in the parameterization and store input flashes
automatically, safe from power failures.
The data are not automatically stored with A40 (read Parameter Motor type Motor type
Parabox). selection
Accept change
The Controlbox Tool program makes it possible to directly Reject change
transmit the parameters between Controlbox and a PC.
In the default setting (status on delivery), the inverter only
7.2.4 Parameterization displays the most important parameters required for
commissioning. For complex drive tasks, the expanded menu
The following six keys are used for the parameterization with is activated with A10=1.
Controlbox. With A10=2:service; Access to rarely used service parameters
• Return to prev. menu level • Select various menu levels Both the normal menu and the expanded menu do not show
• Reject changes • Accept changes parameters which are not related to the current task.
• Acknowledgement of mal- Example: When a predefined STÖBER motor (e.g., ES 44)
functions (A31=1) is selected in parameter B00 (motor type), param-
eters B10 to B17 (poles to M0) are not shown.
Approximately 50 sec after the last key was pressed, the
device returns automatically to the status display. This return
can be switched off with A15=0 (auto return inactive).
Fieldbus: Most of the parameters pertaining to the fieldbus can
• Group selection • Parameter selection
only be set on the PC with FDS Tool.
• Edit parameters
To program, press the key (Enter). You are now in group 7.2.5 Password
selection. The menu is divided into groups which are
The parameters can be protected against unauthorized
identified as A, B, C, … . Select the groups with the arrow change. To do this, enter a password (a number between
keys (i.e., and ). Press the key again to access the
parameters of the selected group.
1 and 9999) in parameter A14, and save it with A00=1.
Password protection is inactive if A14=0. The Parameter A14
The parameters are designated with the group letters and a can only be accessed in the extended menu with A10=1.
number (e.g., A10 or D02).
Only when parameter in On a protected device, the parameters can only be changed
parameter set no. 2 after the correct password has been entered in A13.
Parameter Parameter name
no.
Value
Parameters are selected with the and keys. To change
a parameter, press the key again. The flashing value can
now be changed with and . The changes take effect
15
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
8. Commissioning
8.1 Default setting There are many ways to specify the speed. However,
remember that parameter D99 fast reference value restricts
To obtain the default setting, set parameter A04=1. the possibilities.
The default settings are listed below. D99=1:active Fast sampling (1 msec) of analog input AE1.
Caution: Reference value options and fixed
• Run mode: Speed reference values are not shown.
• Speed reference value via AE1 (fast reference value D99=1) D99=0:inactive Release the fixed reference values and
• 10 V = 3000 rpm access to all reference value parameters.
• Encoder output X20: 1024 imp./U. Sample analog input AE1 = 4 msec
•
Ramps: Not active
• Binary input 1 (F31): 1:Halt (ramp inactive) 8.3.1 Speed specification via Controlbox
• Binary input 2 (F32): 2:Direction of rotation
• Binary input 3 (F33): 9:Quick stop Controlbox offers a commissioning function without circuiting
• Analog output 1 (F40): 4:E08 n-motor the control terminals. The tipping speed is determined by the
• Analog output 2 (F45): 1:E00 I-motor following selection. It can be changed with the appropriate
• Holding brake is not addressed. parameters.
The expanded menu is activated with A10=1. Speed control C60=1: Tip speed / Tip ref. value (A51)
Position control C60=2: Tip speed (I12)
8.2 Motor, braking resistor
Activation/deactivation of local operation is signaled
Before the drive is commissioned, the STÖBER ES servo by LED.
motor must be identified on the SDS. Selection with B00 is
performed from a motor database. Connect drive. Motor is under power. Indicated by
LED.
• In B00, select the motor type (e.g., 64:ES44). Move drive (right/left) as long as the keys are
• In B02, enter the "EMK" constant (standard = 110 V). pressed.
• In B26, enter the motor encoder (standard = resolver).
• When a holding brake is to be addressed, set F08=1, and Motor becomes currentless.
enter the application and release time in F06 and F07.
•
• If an external fan
With exists,
braking set B03
resistor, =1.
set the type in A20. 8.3.2 External speed specification
• Torque limits C03 and C04 must be adjusted to the • Connect speed reference value to analog input AE1.
loadability of the mechanical parts (i.e., gear box). C03 • Enter speed at 10 V in parameter D02.
and C04 are percentages relative to standstill torque M0 • When higher-level position control is being used, D02
of the motor. Limit C04 is used for quick stop, for example. must exceed the maximum speed actually required by at
Usually least 10% (i.e., control reserve).
• Any offset for the analog input can be compensated for
C03 = C04 < M2B_gearbox / M0_motor/ i (*) with D06.
• If required, program ramps with D00 and D01.
must be set (M2B = max. acceleration torque of the gear box, Ref. AE1
i = transmission). Starting with the 1999 edition, the SMS ground level
catalog lists in column S C03 the value (*) to be entered as a
suggestion. For more information on torque limits, see chapter
9.2. Ref. val.
This can be monitored with a phase test using B40=1
(procedure: enable off; B40=1; enable on; enable off again
when finished). Caution: The drive must be decoupled from
8.3.3 Speed specification via potentiometer
the load since movement takes place. For details, see B40 in
the parameter list. When a potentiometer is used to specify the reference values,
With external motors, the selection "60:user defined" must be the analogvoltage.
reference outputs (must be parameterized
Caution: Ri=2.2 KΩ). to +10 V or -10 V
made in B00 with input of the other motor parameters B02 to
B17. This information can usually be found on the motor • F40=7:+100% for + 10 V on analog output 1
nameplate. • F45=8:-100% for - 10 V on analog output 2
This procedure must be concluded with B40=1 (phase test). • Set F47 (analog output 2 factor) = 100%
AE1
Caution: Make sure that the load is decoupled from the drive!
level
Ref. val.
16
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
8. Commissioning
With fast reference value ( D99=1) active, the reference value There are two ways to accept the frequency reference value.
must be available on AE1. With D99=0, the (main) reference • Incremental encoder, tracks A and B
value can be available on either AE1 or AE2, but the AE • Stepper motor signal, frequency + sign
function (i.e., either F25 or F20) must be 10:reference value For connection, see chapters 4 and 5. The software must be
(default setting for AE1). The speed is calibrated with the programmed to "el. gear," as described in chapter 11.
parameters D06 (RV offset) and D02 (speed at maximum
reference value). Parameter D03 (maximum reference value)
8.4 Speed controller
is helpful, for example, when the higher-level controller can
output a maximum of 5 V (i.e., D03=50% would then have to The speed controller is an ideal PI controller with reference
be entered). value smoothing. With STÖBER ES motors, the optimum
function of the speed controller is ensured by the default
AE1 AE1 AE1 AE1 setting. The necessity of controller adjustment (parameters
level offset gain function C31, C32 and C33) is usually restricted to:
n RV
• Great external moments of inertia (C31 , C32 , C33 )
(RV-Max) Max
RV • Mechanical parts with oscillation capability (C31 , C33 )
offset
n-RV low n-controller
n-post pass n-controller Ki
ramp Kp
M-Max
M-ref.
value
8.3.5 Speed specification via fixed ref. value n-motor T=C34
With D99=0 (fast reference value inactive), 8 fixed ref. values n-actual
(FSW) are available with the corresponding ramps in group D.
Binary coding via signals RV-select 0 to RV-select 2 (param.
F31 to F34) is used for the selection. The combination "000"
8.5 Halt / quick stop
corresponds to the conventional analog reference value.
In the default setting, binary input BE1 is programmed to
8.3.6 Speed specification via clock pulse F31=8:halt. In the default setting, the halt is performed without
ramp since D01=0 sec is preset. A separate deceleration ramp
generator
can be implemented with the function "9:quick stop" (D81
A clock pulse generator is available to optimize the speed Decel-S). In the default setting, BE3 is programmed to
controller. F33=9:quick stop.
With operational mode "position," the ramp function is always
• Enter desired speed in A51 (e.g., 50 rpm). active. The process block Decel ramp takes effect with halt.
• Activate clock pulse generator with D93=1. Max. acceleration I11 takes effect with quick stop.
• Enter clock pulse cycle in D94 (e.g., 0.5 sec).
• Activate enable. 8.6 Brake control
The drive switches the speed between + A51 and –A51 with The addressing of a +24 V motor halting brake is activated with
cycle D94. F08=1. The connections are available on X13 (B+ and B-).
The brake is released by the end stage enable and closed with
8.3.7 Motor potentiometer falling enable. The set release time F06 and the application
time F07 of the brake is considered.
The "motorpoti function" can be used to steplessly increase or
decrease the motor speed via two binary inputs. The brake is applied again under the following conditions:
• Two binary inputs are programmed to "4:motorpoti up" or • Removal of the enable. Watch F38=1.
"5:motorpoti dwn" via F31 to F34. • Halt. One BE must be programmed to HALT (e.g., F31=8).
• The "motorpoti function" is activated with D90=1. • Quick stop. One BE must be programmed to quick halt
17
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
8.7 Binary inputs BE1 to BE4 (Opt. BE5 to BE15) When autostart is active ( A34=1), the switchover takes place
immediately when the edge of the signal "11:Paraset“ occurs.
With the default setting, the binary inputs which can be Enabling is automatically deactivated internally.
programmed as desired have the following meaning.
• BE1 = 8:Halt Parameter records can be copied via A42 and A43 (copy
• BE2 = 6:Direction of rotation (left/right)
paraSet). A42: copy paraSet 1 > 2 to " 1:active" overwrites
• BE3 = 9:Quick stop
parameter record 2 with the values of parameter record 1.
• BE4 = 0:Inactive Usually, the first parameter record should be set up first.
The parameters are then copied to parameter record 2
Option board SEA-4000 offers 10 additional binary inputs. The with A42=1 (active). A11=2 is then used to switch to
function of the binary inputs is specified via the parameters parameter record 2 and edit the necessary values there.
F31 to F34, and F60 to F69 in the extended menu ( A10=1). After completion, all parameters are saved with A00=1.
BE1-
function 1:RV-select0 Remember: When the mode ( C60) is switched from position
2:RV-select1
to speed, the actual position during C60=1 is only partially
included. This means the reference position is lost when you
3:RV-select2
switch back (I86→0).
With electronic gear boxes, the internal variables like the
31:RV-select4 current angle of deviation are retained when a parameter
32:brake Release record is switched (prerequisite: C60 remains the same).
However, the parameters of group G.. are switched.
When several inputs are connected to one function, the
signals are either AND or OR-linked ( F30 BE-logic). Functions
8.9 Acknowledgment of faults
without a connection to a BE signal are provided internally
with an L-level signal. The table of possible faults is located on page 48. Faults are
acknowledged in the following ways.
8.8 Parameter record selection • Enable: Change from L to H level on the enable input, and
then back to L. Always available.
The SDS inverter supports two separate parameter records. • Binary input (F31 to F34=13)
Specification of the active parameter record is performed in • key (only when A31=1) Caution!
one of the following ways. and only in the display) Drive starts up
• Externally via a binary input (A41=0) • Auto reset (only when A32=1) immediately.
Internally via a keyboard (A41=1 or 2)
}
•
Parameters E40 and E41 can be used to scan the last
The active parameter record is indicated in E84. To specify via 10 faults. Value 1 represents the last fault. FDS Tool can be
a binary input, one of the parameters F31 to F35 must be set used to define the inverter reaction (e.g., fault, warning,
to "11:paraSet-select" in both parameter records. Selection message or nothing) to certain events (e.g., overload,
never takes place unless the power section is deactivated. excessive
temperature, and operating range) as desired.
The parameters of both parameter records can be indicated
and programmed regardless of which parameter record is The fault "37:n-feedback“ can only be acknowledged by
currently active. A11 (paraSet Edit) is used to specify the turning the 24 V supply off and on.
parameter record (1 or 2) to be edited. When parameters of
the 2nd record are involved (A11=2), a is indicated to the 8.10 Motor startup
right of the parameter number.
A34=0 (auto-start inactive) in the default setting
Certain parameters (e.g., operation input, A30) are only prevents the motor from starting up by itself after the
available once, and a is then not indicated next to the power is turned on. Cf. operation status "12:inhibited"
parameter number. This applies to all parameters of group A, on page 45. Before activating auto start (A34=1),
the display parameters of group E (e.g., torque, utilization and check to determine whether safety requirements
similar), and positioning (groups I, J, L and N). permit an automation restart.
Example of time behavior with quick stop for enable-off
(F38=1, for enable see also F31=11): Signals for
9 TORQUE LIMITS / OPERATING RANGE
Enable fieldbus control
E101.6 9.1 Torque limits
LOW min. 4 msec
Speed Ramp D81 There are several methods of limiting motor torque.
(F38>0 !) • In the default setting, C03 (M-Max 1) is the current torque
11:Param. record limit in % of motor standstill torque M0.
F31
(Input) A41 or E101.5 • A binary input (assign BE funct. "10:torque select" via one
7:Param. record of the param. F31 to F34) can be used to switch between
F00
(Output) E84 or E100.14 the two torque limits C03 (M-Max 1) and C04 (M-Max 2).
Power stack • Analog input AE2 can also be used to limit torque. Set
E100.31
parameter F20=2.10 V corresponds to 100% motor
Conversion ... Duration 100 to
standstill torque M0. Other scaling is available via F22
800 msec (AE2 gain).
F00 32:Param. active E100.15 • With quick stop, C04 always takes effect.
(Output)
18
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
The actually effective torque limit is calculated from the 10.2 Connections
minimum of the various limit values. It can be scanned in
parameter E62. Maximum available torque is always limited by The standard device without option board is used for simple
the maximum inverter current. applications.
Applications with greater demands on binary inputs require the
use of the SEA 4001 option board.
9.2 Operating range
The SEA 4000 expansion board offers 10 binary inputs and
Freely programmable comparators can be used to 5 binary outputs.
simultaneously monitor 3 measured values (i.e., "operating An analog input can be used to adjust positioning speed
range"). The first 2 values (speed and torque) are fixed. The
steplessly. Called "speed override," this function is not only
third value can be selected as desired with C47. The limit
values are specified with the following parameters. useful
changesduring commissioning
in the but also
number of pulses of a for tippingand
machine, mode,
so on.
• C41, C42: n-Min, n-Max
Below is a typical configuration with option.
• C43, C44: M-Min, M-Max
BE5...BE14
• C45, C46: Measured value "X" (specified in C47)
BA3...BA7
C48=1 monitors the absolute value of measured value "X"
(C47). C48=0 also includes the sign. Parameter C49 specifies
whether monitoring is also to be continued during acceleration
phases and enable-off. When at least one of the limits is
exceeded, this can be signaled on a binary output with the
"6:operation range" function (e.g., F00=6). Another use is the 0-10 V
control of process-block chaining (cf. J17=4). r
e
Can be used lv
If only one or two of these range monitoring options are used, o
s
the limits of the unused ranges must be set to their limit values as desired e
R
(e.g., C43=0% and C44=400% when torque monitoring is not
required).
10 POSITIONING CONTROL
The following functions for binary inputs (parameters F31 to
The basic model of the SDS 4000 servo inverter offers
integrated positioning control. F34 and F60 to F69) are important:
• RV-select0 to 4: Binary coded position selection. Process
Since the capabilities of standard devices are limited by the block 1 is selected with "00000," and process block 32 is
number of inputs available, use of option board SEA-4000 or selected with "11111."
digital communication (e.g., RS 232, CAN bus and • 8:halt: Rising edge interrupts running motion with the
PROFIBUS-DP) is recommended for solving typical current process block ramp. Since tip mode (i.e., inching)
positioning tasks. via binary inputs is not possible unless halt is active, halt
switches between tip and automatic operation.
10.1 Function overview • 9:quick stop: Rising edge interrupts positioning with
maximum acceleration I11.
• 32 positions can be programmed as 32 process blocks.
• 16:posi.step: When a chain of process blocks is being
• Continuous position control with following error monitoring used, posi.step starts the consecutive process blocks. A
• Parameterization in units (e.g., degrees, mm) movement which is in progress is not interrupted.
• Resumption of interrupted process blocks possible • 19:posi.start: Starts the just selected process block. A
• Change in destination possible during traversing movement which is in progress is always interrupted.
• Reference point travel with several modes • 20:posi.next: Only for chained process blocks. If
• Sequence programming possible via process block chaining programmed appropriately (cf. J17=3), immediately
(e.g., "Go to pos. 1, wait 2 sec, go on to pos. 2, wait for concludes the running process block, and starts the next
signal and return") one. A remaining path which is to be traveled after posi.next
• Tip mode (inching) occurs can be defined. See chapter 10.8.
•
Teach-in function • 17:tip+, 18:tip-: Tip mode (i.e., inching)
• Speed override via analog input possible • 21:stop+, 22:stop-: Limit switch
• Any gear ratios are calculated with fractions without • 23:reference input: Reference switch connection
rounding errors. No drifting with continuous axes. • 24:start reference: Starts reference point traversing
• Continuous referencing for continuous axes • 25:teach-in: Actual position is assumed in the just selected
• "Electrical cam" function switches digital output within process block.
programmed position range. The binary inputs can be inverted via F51 to F54 and F70
• Hardware and software limit switch to F73. Removal of the enable always causes a quick stop
• Rotary attachment function with maximum acceleration I11.
• Path specification via analog input possible
• Brake control for lifting systems Analog inputs AE2 and AE1 (par. F20 and F25)
• Positioning with absolute value encoders (also continuous • 1:additional RV: Relative traversing paths are multiplied by
mode) (100% + level). Example: 0 V → no additional reference
value (i.e., 100% of the traversing path).
19
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• 4:RV-factor: Relative traversing paths are multiplied by the When a process block cannot be started (e.g., see
level. Example: 0 V → no movement (i.e., 0% of the "51:refused"), the selected block continues to be shown
traversing path). inverted. This happens even when a movement is terminated.
• 5:override: The programmed positioning speed can be
RV-ackn..= Posi.start or posi.step=1: RV-ackn..=
changed online via potentiometer ("speed override" function /RV-select RV-ackn..= active roc. blk /RV-select
for CNC controllers), for example.
• 6:posi. offset: An offset can be added to the current Posi.start
position online via AE2. Cf. parameter I70.
RV-select 0
Binary outputs (par. F00, F80, F81, ... ) RV-ackn0
• 3:Ref Val reached: Location in position window I22. Signal
20
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
10.5 Commissioning The enable can now be activated as the first test. The display1
shows
Before positioning control is activated, speed control must be
commissioned and, if necessary, optimized with the FDS 17:posi.active
Scope function. The position control loop functions, and the current position is
Positioning control is activated with maintained. During the next step, the drive is moved via tip
mode (i.e., inching mode). Set parameter J03=1 for this. The
C60=2:position
keys can be used to traverse the drive.
The status indicator1 changes and displays the actual
position in the first line. The speed can also be changed during traversing via
Actual pos. analog input AE2 (F20=5).
The next step is the commissioning of reference traversing.
read . See chapter 10.6. Software limit switches I50 and I51 can
be programmed with a referenced axis ( I86=1). The software
Oper. status Brake chopper limit switches prevent movement to positions outside I50 and
(see chap. 16) active I51.
Important: If you want to change the location of the decimal A short relative movement (J11=0) can be specified in J10
point in the position display via I06 (I06=decimal point shift), (destination position process block 1) for testing purposes.
do this at the beginning of commissioning since the The speed is entered in J12, while the ramps are entered in
significance of all positions is changed. J13 and J14. J00=1 can be used to start and monitor the
movement. Do not forget the enable.
10.5.1 Limited position range
10.5.2 Continuous traversing range (rotary axis)
Position range limited (I00=0)
Unlimited traversing range (I00=1)
1
Only in connection with a Controlbox
21
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
When the 24 V supply voltage is turned on, the actual position Reference switch Active
is unknown. A defined preliminary position is achieved with
reference traversing. Absolute movements can only be
performed in referenced status. The referenced state is Reference
signaled with I86=1 and can be output on the binary output. direction reversed
Reference point traversing is parameterized with I30 to I38.
The primary parameters are listed below. Zero pulse Slow (I33
• I30: Type of reference point traversing Incremental Fast (I32)
• I31: Direction of reference point traversing encoder
• I32: High-speed reference point traversing
• I33: Low-speed reference point traversing
• I35: Zero-pulse of the motor encoder
The direction defined in I31 is reversed if the reference
switch is active at the beginning.
• I37: Automatic reference point traversing at power-on
There are three ways to start reference point traversing. Example 3: I30=0:ref.input, I31=0:positive
• Automatically (I37=1 or 2) Limit switch +
• Signal on binary input (F31 to F34=24)
• Inching with J05=1 Reference switch
1 v²
Distance = -------
2a Zero pulse
Incremental
With v: Speed encoder
a: Acceleration (I11/2 here).
After reference point traversing has been concluded, the drive A limit switch can be used for referencing instead of a
remains where it is after the required braking distance reference switch.
(I332/I11) and does not return to the reference position. Cf.
above. The AE2 "override" function (F20=5) changes the When the power or the external 24 V voltage supply fails,
speed and also the braking distance. the information on the reference position is lost. After power
returns, I37=1 is used to automatically trigger reference point
Example 1: I30=0:ref.input I31=0:positive traversing with the first start command (i.e., posi.start or
posi.step).
Reference switch
After a reference point traversing procedure has been
concluded, you can automatically move to any initial position
Fast (I32) by programming parameter I38 (ref. block) to the number of
the parameter record to be approached.
22
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
10.7 Position controller Example 3: A conveyor belt is to stop after exactly 100 mm
following a sensor signal.
To minimize following error deviation (i.e., difference between Solution: J11=2:endless positive
reference value and actual position), the SDS uses speed
J16=2 (Next block no. 2)
precontrol (speed feed forward). The maximum permissible
J17=3:posi.next (Next start)
following error deviation specified in I21 is continuously
J20=100 mm
monitored. The position controller is running continuously J21=0:relative
during the entire movement.
Reference value generator Posi Posi.next signal
I88 speed
v Speed
x ref.value
Speed feed
I25 forward
S-ramp
I16 x I08 x H23* x 60
I07 The posi.start signal starts process block no. 1. The drive
x-ref. n-post- continues to run until the rising edge of the posi.next signal
val. I84 Following
error
E07 ramp after which a branch is made to process block no. 2. When
Posi
offset Speed
posi.next is connected to BE1, the reaction occurs without
controller a delay time. If the J17=3:posi.next setting is not made,
X20 gear
ratio - - posi.next is ignored! Cf. example 4.
n-motor
H23 + I23 I20
E08 Example 4: Positioning of a shelf handling device. The exact
x-acutal Dead- Kv-factor
band destination position is specified by a light barrier
which is triggered briefly at each shelf. Until just
• H23 (X20 gear ratio): Example of position control using X20 before the destination, the signals of the light
The gain of position control I20 (i.e., the "stiffness" of control) barrier must be ignored. We will assume that the
is called the "Kv factor." destination is located between 5.1 m and 5.4 m.
The parameter I16 (S-ramp) can be used to parameterize Solution:
"joltless" traversing profiles and prevent high-frequency The approximate position is traveled to with block no. 1.
excitation due to a low pass. The time constant I16 J10=5.1m (Approximate position)
corresponds to a low-pass limit frequency of fg=2 π/I16. J11=1:absolute
J16=2 (Next block no. 2)
10.8 Process block chaining J17=2:no stop (Next start)
The "next block" parameters J16, J26, J36 and so on can be Posi.next is activated in block 2 ( J27).
used to chain process blocks into sequences. For example, at J20=5.4 m (Maximum position)
the end of one process block, this can be used to automatical- J21=1:absolute
ly move to an additional position (i.e., next block). The follow- J26=3 (Next block no. 3)
ing parameters apply to the 1st process block. J27=3:posi.next (Next start)
• J16 next block. If J16=0, then no chaining. The braking distance is defined in block 3.
• J17 next start. Specifies how next block J16 is to be started. J30=0.05 m (Braking distance)
• J18 delay. Applies when J17=1:with delay J31=0:relative
For details on J17, see the parameter table. Posi.next signal
23
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The inverter assumes the basic state "17:posi.active" when Example 5: A toothed belt drive is to move continuously and
the enable is turned off and on. without drift in fixed increments (41 catches per
• The "17:posi.active" state can also be output on BA1 or BA2. circular length). The toothed disk has 23 teeth,
while the belt has 917 teeth. For gearbox, see
10.9 Simple examples
above.
41 catches
Without the option board, 4 digital inputs are available.
Example 1: Belt drive (i.e., endless movement). Four
different feed lengths are traversed relatively. 23teeth 917teeth
Solution: BE1: RV-select0 ( F31=1)
BE2: RV-select1 (F32=2) Solution: To obtain
length a precise
is taken solution,
as the unit of 1/41 of the
distance circular
(I05=0).
BE3: posi.start (F33=19) One unit of distance is exactly one catch. The
BE1 BE2 Block Process Block Parameter belt drive rotates precisely 198 / 3354 x 23 x 41 /
0 0 1 J10,J12,J13,J14 917 units of distance per motor revolution. Thus,
1 0 2 J20,J22,J23,J24 I07=186714, and I08=3075618. The path is
0 1 3 J30,J32,J33,J34
programmed in units of distance=1/41 of the
circular length. The circular length I01 is 41 units.
1 1 4 J40,J42,J43,J44
Example 6: A conveyor belt drive with slip is to move in
The traversing method (e.g., J11, J21, J31 and so on) fixed increments continuously and without drift.
remains set to "0:relative" for all blocks. The selected Exactly 41 catches are distributed over acircular
process block is indicated in I83. length of 4 m.
Example 2: Linear axis with end stops. Two fixed positions 41 catches
are traversed absolutely.
Solution: BE1: RV-select0 ( F31=1)
BE2: posi.start (F32=19)
BE3: ref.input (F33=23) Ref. switch
BE1 Position Process Block Parameter Solution: The distance per motor revolution is 2 πR/i. Thus
0 1 J10,J12,J13,J14 I07=37.09 mm/R. Drift is prevented by contin-
1 2 J10,J12,J13,J14 uous referencing (I36=1) or the posi.next signal.
Important: The distance to be traveled (e.g.,
The traversing method (J11 and J21) for both process J10) multiplied by the number of catches (41)
blocks is "1:absolute." After power-on, reference point must precisely equal the circular length I01. If
traversing is automatically executed by I37=1 with the first not, the drive will drift away even with continuous
posi.start command. The reference switch must have the referencing. If necessary, I01 and I07 must be
characteristics shown in example 1 of chapter 10.6. adjusted accordingly. The reference switch
Example 3: Belt drive (endless movement) with stop at should be located between two catches.
pulse (i.e., defined braking distance) Important: When continuous referencing I36=1
is used, I07 must always be rounded off to the
Solution: BE1: posi.start ( F31=19) next higher number.
BE3: posi.next (F33=20)
J11=2:endless positive Example 7: Screw/press controller
J17=3:posi.next Starting at a certain position, the torque is to be
J20=...(braking distance) monitored. When a limit is exceeded, a return to
the start position is made.
We recommend applying the posi.next signal to BE1
Solution: The first part of the movement is handled by
(F31=20) so that the delay time of 4 msec is omitted. process block no. 1. Without stopping, the system
Evaluation of posi.next is activated with J17=3. switches to process block no. 2 before the end
For additional details on posi.next, see chapter 10.8 (chaining position (J16=2) and J17=2). The speed remains
of process blocks). the same (J12=J22). When the torque limit
(working area) specified by C44 is exceeded, the
Example 4: A rotary attachment
continuously is to be
and without driftpositioned
in 60° increments. system switches to process block no. 3 (J26=3
and J27=4). In our example, the working area is
A STÖBER K302 0170 with i=16.939393... is to limited by the maximum torque C44.
be used as the gearbox. The exact ratio is
i=3354/198. Accel. Incr. press.
torque force
3354
M i=
198
If the power is cut off from the inverter with the emergency off The movement of the external measuring system (rotary or
switch, all information on the position is lost. When the inverter straight) must be defined with I07 and I08. First, the increments
goes on again, the power must be referenced again. of the encoder must be specified (for SSI encoder, the resolu-
tion is converted from bits to increments; 24 bits equal 1024
When 24 V is provided via an option board, a movement pulses). See table above. Then the physical implementation is
which is interrupted by an emergency off can be continued defined with I07 and I08.
and completed under the following conditions.
• The HALT signal becomes active at least 4 msec before the Examples:
enable is removed.
1) A revolving table with a rotation angle of 360° is directly
• The HALT signal remains present until power returns and coupled with a pulse encoder (1024 pulses per revolution).
the enable is minimum 4 msec active. H20 = 2:encoder In
Another method of interrupting and continuing a process block H22 = 1024 I/R
is to use the following sequence of signals. I05 = 2:°
I07 = 360
EMERGENCY OFF Operation
I08 = 1 R
E07 Inc./R
n-post- I08
x x H23* x 60 H22
Important: The external measuring system must be able to I07
ramp
supply at least 30 measuring increments per revolution - as y
The encoder for position control is selected with I02 and the 10.11.3 Special reactions with SSI encoders
motor encoder for motor control is selected with B26. The The connection of the encoder is made on interface X20
following table lists the possible interfaces with the inverter's (H20=5).
supply voltages UB and the parameters for the number of At a resolution of 24 or 25 bits (see H61), one revolution has
increments (inc/R) and the gear ratios between motor and 12 bits (i.e., one revolution is divided into 4096 positions). This
encoder (gear-i). corresponds to a resolution of a pulse encoder with 1024 lines
Remarks UB Inc/R Gear-i (quadruple evaluation).
X20 TTL incremental encoder, - H22 H23 H20 must thus be set to 1024.
SSI encoder Be sure that the coding (gray or binary) is set correctly in H62.
BE HTL incremental encoder - F36 F49
X41 TTL incremental encoder 5 V H41 H42
(no galv. isolation)
25
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Max. of 2 switch
Switch point Switch point Switch point 11.1 Function overview
points per
process block. S1 S2 S4
One switch point
• Precise speed and angle ratio
can control all 3 • Gear ratio can be set as fraction.
s-memories. S-memory S-memory S-memory • Following error monitoring
Each output
1 2 3 •
can be Free wheeling via binary input for high dynamics
programmed to • Precontrol (speed feed forward)
an s-memory.
• No stationary angle error
Binary outputs BA function • Angle offset via binary inputs
• Fine adjustment of the gear ratio possible via AE2
Example 1: Binary output 2 (relay 2) should be set in process • Master signals as incremental encoder (tracks A and B) or
block 2, 150 mm before the target position and then reset just stepper motor (frequency and sign)
before the Posi window is reached. • SSI as master encoder
Solution: Two switch points (S1 and S2) are required. Switch The block circuit diagram for synchronous running is shown
point S1 activates switch memory 1 (s-memory1). Switch point in chapter 18.
S2 deactivates the same memory.
26
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Connector side
SSI interface:
• Use plug connector X20.
• Set H20 to SSI master (H20=5).
• Set H61 (SSI code) in accordance with encoder used.
• Set H62 (data bits) in accordance with the resolution of the
• Use plug connector X20. Remember terminal resistance for The parameter H60 (SSI-inverse) can be used to influence the
cables longer than 1 m. direction of rotation.
• Set H20=2:encoder in for incremental encoder.
• Set H20=3:stepMot in for stepper motor simulation. 11.3 Master – slave
• Enter resolution (pulses/revolution) in H22. When two SDS 4000 inverters are coupled as master-slave,
• Set master encoder G27=1:X20. signals of the encoder simulation on plug connector X20 are
(Activate synchronous run with G20 before.) connected to the same plug connector of the next inverter.
• X41 can also be used instead of X20. See chap. 5.5.
Master:
SDS 4000 • Set encoder simulation on X20 with H20=1.
X20
Freq.+ • If necessary, change number of increments in H21.
A+ 5
Freq.- Slave:
A- 150Ω
• Deactivate fast reference value with D99=0.
4 • Set H20=2:encoder in.
R GND 1 • Set the number of pulses/revolution in H22 for the master
L PGND (i.e., H22 on slave = H21 on master).
T
T Sign + • Activate angle synchronous run with G20=2.
V B+ 6
•
Sign - 150Ω Set master encoder to G27 =1:X20 . /G21.
B- • Set slave/master speed ratio in G22
7 • If necessary, change direction of revolution in D92.
• The primary functions are listed below.
A finished, cascadeable master slave connection (ID no. Binary inputs (parameters F31 to F34)
42940) can be used to pass the pulses from one SDS to the • 12:ext fault;
next. The cable length has been optimized for inverters up to • 17:tip +; The slave is shifted in the positive direction in
20 A (SDS 4141). relation to the master. The speed is the result of the current
speed reference value (AE1 or fixed reference value).
• 18:tip -; Same as "17:tip +" but in the negative direction.
• 27:syncFreeRun; Switch off synchronous running to run the
drive with the analog reference value, for example.
• 28:syncReset; Current synchronous difference G29 is reset.
27
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Binary outputs (parameters F00 and F80, F81) 11.6 Angle and speed synchronous running
• 12:sync.diff.; The synchronous difference exceeds limit
value G24. With angle synchronous running (G20=2), all angle deviations
are acquired and adjusted. However, this is not always
Analog inputs AE2 (parameter F20, F25) desired. In speed synchronous running mode ( G20=1), the
• 5:override.; The gear ratio is affected during operation (i.e., angle controller can be partially or completely deactivated.
change every 250 msec).
• 13:Sync.offset; Slave position is changed via analog voltage The following setting is used to limit angle difference G29 to
(100% = G38). the value G24.
• 14:Sync. n-RV; External speed feed forward with analog G20=1:speed synchron run
reference value G23>0 (Kp synchronous running)
Although the speed ratio is precisely adhered to, the slave
11.4 Commissioning never attempts to catch up with an angle difference over G24.
• Commission master and slave separately (speed control). This is similar to a mechanical safety notching coupling.
Parameters F26, F36 and H22 are important. Make the following selection for pure speed synchronous
• Configure the encoder input/master on the slave (F31=14 running.
and F32=15 or H20=2).
• On the slave, speed synchronous running is activated with G24=0
G20=1, and the angle synchronous running is activated with The speed ratio is not mathematically precise.
G20=2.
• On the slave, enter the number of encoder increments of the
master (F36 or H22). 11.7 Emergency off
• On the slave, specify the speed ratio (G22/G21). The following measures are helpful in minimizing divergence
• Direction of rotation can be changed with D92. of master and slave when the power goes off.
The master often requires no further parameterization. • Select master low voltage limit A35 higher than that of the
slave.
11.5 Angle difference • Set master quick stop to F38=2.
• Couple DC links between master and slave.
The current difference between master and slave is indicated • Adapt master quick stop ramp (D81) and torque limits ( C04)
in G29. The angle of difference is reset when: on the master and slave to the mass ratios.
• When voltage is turned on (power and 24 V) if G20<3
• Always for BE function "28:SyncReset" Turning off the power while the enable is active causes the
• For enable, halt and quick stop. See G25. fault "46:low voltage." After power returns, a device
• For BE function "27:SyncFreeRun." See G25. initialization is performed which may take several seconds.
We recommend removing the enable at the same time the
The angle controller multiplies angle difference G29 by G23 power is removed so that the inverter does not go into
(Kp.). The resulting speed offset is limited to ±G26 (n-correc- "fault mode".
tion-Max).
A continuous angle shift between master and slave can be 11.8 Reference point traversing - slave
implemented with the BE functions Tip + and Tip -. The speed
difference is the current speed reference value (i.e., analog Reference point traversing permits you to automatically put
input AE1 or the fixed reference value). Another way to shift the slave into a defined initial position.
the angle is the AE function "13:synchron-offset." Reference point traversing is specified with parameters G31 to
The dynamic angle difference during acceleration is reduced G35. Reference point traversing is started with a binary input
with speed feed foward. (function F31=24:Start ref.).
• Usually, the master increments are differentiated and added Reference input
as speed feed forward to the speed reference value.
Advantage: No extra wiring required
Disadvantage: The master must move first before the slave Fast (G32)
can react. The speed obtained by differentiation is
smoothed with a low pass. (T=G22/G21 * F36/H22*4 msec if
G27=0:BE-encoder. Otherwise T= G22/G21 * H22/F36 *4
msec. In addition: T ≥ 16 msec). Zero pulses Slow (G33)
• The "14:Synchron reference value” function can be used to Incremental
directly switch the speed reference value (post ramp) from encoder
the master to the analog input of the slave (F20=14). The
function of the analog output F40=11:E07 n-postRmp can The drive moves at speed G32 in direction G31 until the
be used for this with the master. No ramp can be param- reference switch (reference input) on a BE becomes active
eterized on the slave for the external precontrol (speed feed (function F31=23:Ref.input). The angle deviation is reset, and
forward). If the analog reference value is circuited in parallel the drive halts.
on master and slave, no ramps may be active on the
master. If only one direction of revolution is permitted (C02), the drive
moves in direction C02 at speed G33 until the rising edge of
the reference switch. The reference direction ( G31) is ignored
in this case.
28
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
12. Technology
12 TECHNOLOGY Task
aster
12.1 PID controller 3 Winding with compen- drive
F=const.
sating rollers via speed
offset and PID add.
The PID controller on analog input AE2 can be used as a RV
technology controller for compensating rollers, pressure, controller on AE2 v-
master v-master
throughput and similar. It is activated with G00=1.
Fref.val. Master
AE2 AE2 lowpassAE2 AE2 AE2 AE2 4 Winding with direct drive
PID F=const.
level offset gain
control
offset2 function tension control with
tension sensor
on AE2 v- v-
master master
• Use of differential input AE2. The two signals are connected • F20=7:wind.diameter (for AE1: F25)
to "+" and "-" in relation to analog ground. • G10=1:n mode
• A fixed reference value can be defined in F21 (AE2 offset). • G11=0:AE2-measured
• AE1 can be programmed to F25=11:PID-reference. • G12 winder D-Min., G13 winder D-Max.
• PID-reference via fieldbus (E121) Parameters F21 and F22 are used to assign the values D-Min.
The low pass filter (smoothing, time constant F23) suppresses and D-Max. to the related sensor voltages U-Min. and U-Max.
undesired high-frequency oscillations. The output of the PID • F21 = - U-Min. 10
÷ V x 100% (AE2 offset)
controller is usually used as an additional reference value • F22 = 10 V ÷ (U-Max. - U-Min.) x 100% (AE2 gain)
(F20=1). The binary input function " 26:disable PID" (F31 to
F35) deactivates the controller. The controller output (i.e., Since the reference value decreases with increasing diameter
adjustment variable) can be limited by G04 and G05. Active in accordance with the reciprocal value 1/D, the master re-
limitation can be signaled on relay 2 (F00=11), for example. ference value is the highest possible speed with an empty roll.
This can be used to indicate a malfunction in the process AE2
(e.g., tearing of wound material). function D-Min. D-Max.
Important: Enable-off sets the output of the PID controller and AE2 AE2 AE2 AE2 AE2
the I portion to zero. level offset gain lowpas offset2
12.2 Winders
The standard inverter software contains functions for solving
simple winding tasks (i.e., reel drives). The following tasks are 0 to 100% = D-Min.
D-Min. to D-Max. D-act.
supported. D-ist
Speed referene value n-ref. value
Task (e.g. of AE1 or
fixed reference value
Diameter
1 Winding with diameter sensor
v=const.
sensor at constant
speed v = const
v-
ref.val.
aster
2 Winding with indirect drive
F=const.
tension control at the
M-max. limit Fsoll
v- v-
master master
29
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
12. Technology
12.2.2 Indirect tension control at M-max limit calculates the diameter in accordance with D v-master / n-
∼
motor and multiplies both the master reference value and the
Winders or unwinders with constant tension without extra offset reference value by 1/D. The primary parameters are
sensors. The winding speed is specified by a master drive. listed below.
The master reference value must be such that it precisely • G10=1:n mode
corresponds to the motor speed required there for D-Min. (i.e., • G11=1:n-line/n-motor
empty roll). The master reference value must always be • G12 Winding D-Min., G13 winding D-Max
positive. See E10 (AE1 level). If necessary, the direction of
• G14 Winding D-ini
motor revolution must be adjusted with D92.
• G00=1 (PID controller active)
The winding drive calculates the diameter in accordance with
• G01 PID controller Kp, G02 PID controller Ki
D v-master n-motor and affects the torque limit in
∼ ÷
proportion to D. The torque limit on AE2 or C03 is the greatest • F20=1:additional reference value
possible torque with a full roll. The primary parameters are Block circuit diagram:
listed below: D-Min. D-Max.
30
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
A.. Inverter
Para. No. Description
A00 1) Save parameter:
0: inactive;
1: The parameters of both parameter records are saved in non-volatile memory. Saving is triggered when the
value changes from 0 to 1. "A02 check parameter" is then performed automatically.
Read parabox & save: Read parameters from Controlbox and save in non-volatile memory. The inverter
A01• recognizes automatically what is connected to X3.
With Controlbox: First select desired data record (1 to 7), and then press .
"A02 check parameter" is started automatically. When read errors occur (e.g., Parabox disconnected while
being read accessed), all parameters are rejected, and the settings last saved with A00 are restored.
0: inactive;
1: active; 1 to 7 for Controlbox (number of the data record)
A02 1) Check parameter: Parameterization is checked for correctness. For possible results, see chap. 15.
0: inactive;
1: active; Parameters of the parameter record to be edited (see A11) are checked for the following.
- Adherence to the value range
- Correct programming of the binary inputs (F31 to F35)
1) Write to Parabox: Write data of the inverter to external data medium (Parabox, Controlbox)
A03 0: inactive;
1 to 7; The parameters of both parameter records are copied from the inverter to Parabox (Controlbox). For
handling, see A01.
A04•1) Default settings: All parameters are reset to their default settings.
0: inactive;
1: active; The procedure is triggered when the value changes from 0 to 1.
Menu level: Specifies the parameters which can be accessed by the user
A10 0: standard; Parameters which can be accessed are highlighted in gray in the parameter table (see chap. 21).
All parameters remain in effect including those in the "1:extended" menu level.
1: extended; Access to all parameters which can be set
2: service; Access to rarely used service parameters. Small print (e.g., A37).
A11 Parameter set edit: Specifies the parameter record to be edited. The parameter record to be edited ( A11) and
the active parameter record (status indication) do not have to be identical. For example, parameter record 1 can
be edited while the inverter continues operation with parameter record 2. See also chapter 9.4.
1: parameter set 1; Parameter record 1 is edited.
2: parameter set 2; Parameter record 2 is edited.
Language: When the language is changed, FDS-Tool-specific texts U22, U32, U42 and U52 are reset to the
A12 default setting. This also applies to C53 and I09.
0: deutsch;
1: english;
2: french;
Set password: Password is requested. If a password is defined in A14, this must be entered here before
A13
parameters can be changed. See chapter 7.3.
Edit password: Definition and modification of the password. 0 means that no password has been set. All other
A14
values are valid passwords. See chapter 7.3. A defined password can only be read out via FDS Tool.
Auto-return: Permits automatic return from the menu to the status indication. In edit mode (i.e., the edited
A15 parameter is flashing), there is no automatic return to the status indication.
0: inactive;
1: active; If 50 seconds pass without a key being pressed, the display jumps back to the status indication.
Braking resistor type: Specification of the braking resistor type
A20 19:inactive; Brake transitor deactivated. Too much braking force causes fault "36:overcurrent."
20: Internal; Integrated braking resistor. See page 2 of technical data.
21: User defined; Any external braking resistor. See A21, A22 and A23.
22: 80Ohm0.3kW
23: 80Ohm0.6kW A thermal model monitors the max. permissible power which can be led off via the
24: 30Ohm0.6kW braking resistor. This protects the braking resistor against thermal overload. A thermal
25: 30Ohm1.0kW overload causes the fault "42:tempBrakeRes."
26: 30Ohm1.2kW
27:30Ohm2.5kW
Brake resistor resist.: Only with A20=1 (user defined), resistance value of the braking resistor used.
A21
Value range in Ω:: Depends on type, up to 600
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
31
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
A.. Inverter
Para. No. Description
Braking resistor rating: Only with A20=1 (user defined), capacity of the braking resistor used.
A22
Value range in kW: 0 to ..., depends on type
Braking resistor therm.: Only with A20=1 (user defined), thermal time constant of the braking resistor.
A23
Value range in sec: 0.1 to 40 to 100
Operation input: Specifies the srcin of the control signals (i.e., enable, direction of rotation and ref. value)
A30• 0: control interface (X1); Control signals (e.g., enable and so on) are generated via the X1 terminals. All binary
inputs must be programmed accordingly. Fieldbus operation without Drivecom profile.
1: serial (X3); Control signals (e.g., enable and so on) are generated from the PC (FDS Tool software). The
inverter is connected to the PC via sub D plug connector X3 (RS 232-C interface). See chapter 9.9. Remote
control via the PC requires that the enable input (X1.15) be high.
2: inactive;
3: SDP 4000; Control of the device via PROFIBUS-DP. This requires the PROFIBUS-DP option board.
4: CAN-bus; Control of the device via CANopen with the integrated CAN bus interface which is standard.
The following applies to both settings (i.e., "3: Profibus-DP" and "4: CAN-bus"). The servo inverter is put into
a drive-compatible mode for device control. This control is performed exclusively either via the selected
fieldbus (requires that all parameters for the function of the binary and analog inputs F20, F31, F32, F33 and
so on be set to inactive) or in mixed operation with these inputs. The high level must always be present on
the enable input (X1.15).
A31 Esc-reset: Use the Esc key to acknowledge faults while they are being indicated.
0: inactive;
1: active; Faults can be acknowledged with Esc .
Auto-reset: Faults which occur are acknowledged automatically.
A32 0: inactive;
1: active; The inverter acknowledges some faults automatically. See chapter 17. Faults can be automatically
acknowledged successfuly three times within a time period of 15 minutes (default setting). A fourth fault is not
acknowledged automatically. Instead, relay 1 opens, and the fault must be acknowledged in some other way
(i.e., enable, binary input F31 to F35=13, or Esc key A31). The automatic acknowledgment counter is reset.
After three unsuccessful attempts at acknowledgment, the inverter ignores automatic acknowledgment and
malfunctions.
Time auto-reset:The
Timetime period
period forforautomatic
automaticacknowledgment.
acknowledgmentSee
canA32
be parameterized
. from 1 to 255 min in A33.
A33
Value range in min: 1 to 15 to 255
Auto-start: Before you activate auto-start A34=1, check to determine whether safety requirements permit an
A34 automatic restart. Use only permitted when the standards or regulations pertaining to the system or machine are
adhered to.
0: inactive; After power-on, the enable must change from L level to H level to enable the drive ( → message
"12:inhibited"). This prevents the motor from starting up unintentionally (i.e., machine safety).
1: active; When auto-start is active, the drive can start running immediately (if enabled) after the power is turned
on.
Low voltage limit: If the inverter is enabled and the DC-link voltage is less than the value set here, the inverter
A35 assumes fault "46:low voltage. " A35 should usually be approx. 85% of the power voltage present to offset
possible failure of a power phase.
Value range in V: 150 to 350 to 570
Mains voltage: Maximum voltage provided to the motor by the inverter. Usually the power voltage. Starting at
A36 this voltage, the motor runs in the field weakening range.
Value range in V: 140 to 400 to 480
Reset memorized values: The six different follo wing error counters E33 to E38 (e.g., maximum current,
A37
maximum temperature and so on) are reset.
DC power-input:
A38 0: inactive;
1: active;
A40•1) Read parabox: Read parameters from a Controlbox without automatic storage.
0: inactive;
1 to 13: active; For function, cf. A01.
Select parameter set: Two parameter records are available. These can be selected via the binary inputs or
A41 directly via A41. The selected parameter record does not become active until the enable has been removed and
after a maximum of 300 msec have passed. Some parameters retain their validity in both parameter record 1
and parameter record 2 (e.g., the posi. parameters in I, J and L). Parameters which can be programmed sepa-
rately in parameter record 2 are indicated by a between the coordinate and parameter name. See chap. 7.1.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
32
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
A.. Inverter
Para. No. Description
0: external; The active parameter record is selected via binary inputs BE1 to BE5. At least one of the para-
meters F30 to F35 must be set to 11 (parameter set-select) in both parameter records. Parameter record 1 is
active when a LOW signal is present on BE. Parameter rec. 2 is active when a HIGH signal is present on BE.
1: parameter set 1; The inverter uses parameter record 1. External selection is not possible.
2: parameter set 2; The inverter uses parameter record 2. External selection is not possible.
Caution: Parameter A41 is only provided for testing purposes. It is not saved with A00=1. Use a BE or the
E101 parameter (bus access) if you want to switch parameter records during operation.
1) Copy parameter set 1>2: Copies parameter record 1 to parameter record 2. The old values of parameter
A42• record 2 are overwritten. The procedure is started when the value changes from 0 to 1.
The result is always "0:error free." The new parameter assignment must be stored in non-volatile memory with
A00.
0: error free;
A43•1) Copy parameter set 2>1: Same as A42 except parameter record 2 is copied to parameter record 1
0: error free;
A50 Tip: Only if C60≠2 (run mode≠position). Permits commissioning with minimum circuiting of the control terminal
as long as A51 is entered.
0: inactive; Normal operation
1: active; The controller only requires a high signal on the "enable" input. All other binary control signals have no
function when C60<2. The and keys can be used to accelerate the drive counterclockwise or clockwise
to the speed set in A51. Since an enable is generated which has a higher priority than the additional enable,
operation remains possible even when additional-enable = low via fieldbus.
A51 Tip reference value: Only if C60≠2 (run mode≠ position). Reference value for speed for commissioning without √
external circuiting of the control inputs. The "enable" input must be high! The current actual speed is shown on
the right of the display. When A50=1 and A51 is in input mode (value flashing), A51 becomes active as
continuous reference value. For behavior of enable and BEs, see A50.
Value range in rpm: -6000 to 300 to 6000
A55 Key hand function: Can be used to disable the MANUAL key on Controlbox for turning local operation
on/off. For additional information, see Controlbox documentation (publ. no.: 441445).
0: inactive; key has no function.
1: local; key activates local operation. Device enabling is then handled exclusively by the keys "green I“
and "red 0“ . The and keys can be used to move backward and forward in the status display. Active
local operation and active enable are indicated by LEDs on Controlbox. The reference speed value results
from A51 for speed mode and from I12 for POSI.
CAUTION: When local operation is disabled with the key (LED goes off), the drive immediately switches
back to the queued control signals (i.e., danger of unintentional startup!).
Serial address:Only if A10=2. Address for communication via X3 with FDS Tool and with master via USS protocol
A80 (cf. documentation „USS link for POSIDRIVE® and POSIDYN®“, pupl. no.:441564).
Value range: 0 to 31
CAN-baudrate: Sets the baud rate for the CAN bus. Cf. CAN bus documentation publ. no.: 441562.
A82 0: 10 kBit/s 2: 50 kBit/s 4: 125 kBit/s 6: 500 kBit/s 8: 1000 kBit/s
1: 20 kBit/s 3: 100 kBit/s 5: 250 kBit/s 7: 800 kBit/s
Busaddress: Specifies the device address for use with the fieldbus (i.e., Kommubox). For permissible value
A83 range, see documentation of the applicable Kommubox. A83 has no effect on device programming via PC with
FDS Tool or the RS 232 interface with the USS protocol.
Value range: 0 to 125
Profibus baudrate: When the SDS is used with the PROFIBUS-DP option board, the baud rate found on the
A84 bus is indicated (!) here. Cf. PROFIBUS documentation publ. no.: 441535.
0: not found 3: 45.45 kBit/s 6: 500 kBit/s 9: 6000 kBit/s*
1: 9.6 kBit/s 4: 93.75 kBit/s 7: 1500 kBit/s 10: 12000 kBit/s*
2: 19.2 kBit/s 5: 187.5 kBit/s 8: 3000 kBit/s
* Available starting with Kommubox hardware version 06.2002.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
33
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
B.. Motor
Para. No. Description
Motor-type: Motor selection from the motor data base. The STÖBER system motor used is specified with √
B00• B00=61 to 69. B00=60 (user defined) is used for special windings or motors of other manufacturers.
60: user defined 62: ES 33 64: ES 44 66: ES 54 68: ES 74
61: ES 32 63: ES 42 65: ES 52 67: ES 72 69: ES 76
The EMC voltage constant must be entered in B02.
An "*" on the display means that at least one of the parameters (B53, B64 and B65) differs from the default
setting of the STÖBER motor data base.
EMC-constant: Specifies the peak value of inducted voltage between two phases at 1000 rpm. √
B02 Value range in V: 5 to 110 to 3000
2
Motor fan: Only if B00 > 60 (STÖBER motors). The thermally permissible motor torque is increased (i t model √
B03
of the motor). B03=1 thus also increases the torque limits since M-Max limits C03 and C04 are specified relative
to motor standstill torque M0. To prevent overloading a gearbox after installing a motor fan retroactively,
C03/C04 must be adjusted to the new M0. See catalog or name plate.
0: inactive;
1: active;
Poles: Calculated from the nominal speed of the motor p=2 x (f x 60/nNom). Internally, the controller works with √
B10•
frequencies. Correct speed indication requires entry of the number of poles.
Value range: 2 to 6 to 16
P-nominal: Nominal power as per nameplate √
B11•
Value range in kW: 0.12 to (depends on type)
I-nominal: Nominal current as per nameplate. √
B12
Value range in A:0 to (depends on type)
n-nominal: Nominal speed as per nameplate √
B13
Value range in rpm: 0 to depends on type to 6000
M0 (standstill): Standstill torque M0 as shown on name plate. Reference value for M-max limits C03 and C04. √
B17 Value range in Nm: 0 to (depends on type) to 327.67
Motor-encoder: B26 specifies which encoder input will b e used for motor control. The encoder increments are √
B26•
specified with F36 or H22. Regardless of B26, the master encoder is set for synchronous operation (G20=1)
with
2: resolverand
G27 the POSI
(X40); encoder
Standard (C60=2)ES
for STÖBER is set with I02.
motors
3: X41 (SinCos); Single and multi-turn, absolute-value encoders with sin/cos track
B40•1) Phase test:
0: inactive;
1: active; Tests motor symmetry in increments of 60°. The following points are checked.
- Connection of phases U, V and W
- Motor and resolver pole number
- Phase position of resolver or sin/cos encoder
- Symmetry of the winding resistors of the phases U, V and W. If a winding resistor deviates by ±10%, the
inverter reports "19:symmetry."
The function is started when the level on the input enable (X1.9) changes from low to high. Exiting the
parameter requires another low signal on the enable.
B41•1) Autotuning:
0: inactive;
1: active; Winding resistors of the motor are measured. The function is started when the level on the input
enable (X1.9) changes from low to high. Exiting the parameter requires another low signal on the enable.
A00=1 saves the measuring results in non-volatile memory.
B00=60, autotuning of the motor is essential! Important for optimum coordination between inverter and motor.
B00=61 to 69, autotuning of the motor is not required.
L-motor: Inductivity Lu-v of the motor winding. Only enter for motors of other manufacturers. √
B52 Value range in mH: 0.01 to depend on type to 327.67
R1-motor:Stator resistance (Ru-v) of the motor winding. Only entered for non STÖBER motors. √
B53 Value range in Ω:: 0.01 to depends on type to 327.67
Ki-IQ (torque):Integral gain of the torque controller. √
B64 Value range in %: 0 to depends on type to 400
Kp-IQ (torque):Proportional gain of the torque controller. √
B65 Value range in %: 0 to depends on type to 400
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
34
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
C.. Machine
Para. No. Description
C00 n-Min: Only if C60≠2 (run mode≠position). Minimum permissible speed. The speed refers to the motor shaft √
speed. Reference values less than n-Min are ignored and raised to n-Min.
Value range in rpm: 0 to C01
C01 n-Max: Maximum permissible speed. The speed refers to the motor shaft speed. Reference values over √
n-Max are ignored and limited to n-Max.
Value range in rpm: C00 to 3000 to 6000
C02• Permitted. direction of rotat.: Only if C60≠2 (run mode≠position). Determines the permissible direction of √
rotation.
0: The &direction
clockwise of rotation can be specified via the binary inputs.
counter-clockwise;
1: clockwise;
2: counter-clockwise;
C03 M-Max 1: Maximum torque in % of motor zero current. The active torque limit can be further reduced with an √
analog input (see F25=2). If the maximum torque is exceeded, the controller responds with the message
"47:drive overload." See also remarks for C04.
Value range in %: 0 to 150 to 400 (and any M-Max signal present on analog input-AE function " 2:Torque limit")
C04 M-Max 2: Additional torque li mit. You can switch between C03 and C04 with a binary input (F3..=10:torque √
select). See chap. 9.2.
Remarks: Since C04 is always active for a quick stop, C04 ≥ C03 should usually apply!
Value range in %: 0 to 150 to 400
C30 J-mach/J-motor: Ratio of the inertia of load to motor. This factor is effective for all control modes and is √
important for optimization between inverter and motor (i.e., dynamics). Entry is not mandatory.
Remarks:In winding mode, the effective inertia torque is calculated for C30 ≥ 1.5 to the fourth power with the winding
diameter for compensation of the acceleration torque.
The following applies: J(D-Min) = 1.5 * J-motor, J (D-Max)= C30 * J-motor. The torque supplied by the drive is increased so
that tension remains constant and extra torque is available for acceleration.
Value range: 0 to 1000
C31 n-controller Kp: Proportional gain of the speed controller. n-controller Kp √
Remarks:In winding mode ( G10>0), the Kp gain with the n-post n-contr. Ki
ramp
winding diameter is quadratically reduced from C31 for D-Max M-ref.val
down to C31*C35 for D-Min.
Value range in %: 0 to 60 to 400 n-motor
C32 n-controller Ki: Integral gain of the speed controller. Reduce C32 when overswinging occurs in the target √
position.
Remarks:In winding mode ( G10>0), the Ki gain with the winding diameter is quadratically reduced from C32*C31 for D-Max
down to C32*C31*C35 for D-Min.
Value range in %: 0 to 30 to 400
C33 n-RefVal low pass: Reference value smoothing. C33 should be i ncreased for reference value noise, physical √
oscillation or large foreign masses.
Value range in msec: 0 to 2 to 3276.7
C34 n-motor low pass: Smoothing of the motor speed. √
Value range in msec: 0.3 to (depends on type) to 3276.7
C35 n-control. Kp standstill: √
Without winders: C31 and C32 are multiplied by C35 as soon as the motor speed drops below C40.
With winders: The formulas described under C31 and C32 apply.
Value range in %: 5 to 100
C40 n-window: If F00=3 (BA 2 as signal relay for "3:reference value-reached") or F00=2 (BA 2 as signal contact for √
speed "2:standstill"), the reference value is considered achieved in a window of reference value ±C40. Also
applies to the other binary inputs. A halting brake is not activated as long as [n] > C40.
Value range in rpm: 0 to 3 to 300
C41 Operating range n-Min: Parameters C41 to C46 can be used to specify an operating area. An output (F00=6) √
can be used to signal that these values have been exceeded. All area monitoring procedures are performed at
the same time. If area monitoring is not required, the minimum parameters must be set to the lower-limit values,
and the maximum parameters must be set to the upper-limit values. Cf. chapter 9.3. When C49=0, operating-
range monitoring is suppressed when the motor is not powered and during acceleration/braking procedures.
When C48=1, amount generation is activated.
Value range in rpm: 0 to C42
C42 Operating range n-Max: See C41. √
Value range in rpm: C41 to 6000
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service.
Parameters marked with a " √ " can be parameterized separately from each other in parameter record 1 and 2.
35
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
C.. Machine
Para. No. Description
Operating range M-Min: See C41. √
C43 Value range in %: 0 to C44
Operating range M-Max: See C41. √
C44 Value range in %: C43 to 400
Operating range X-Min.: See C41. Monitors range defined in C47. √
C45 Value range in %: -400 to 0 to C46
Operating range X-Max.: See C41. Monitors range defined in C47. √
C46 Value range in %: C45 to 400
Operating range C45/C46: Defines the range to be monitored. √
C47 0: E01 P-motor; 5: E22 i2t-device; 10: E71 AE1-scaled;
1: E02 M-motor; 6: E23 i2t-motor; 11: E72 AE2-scaled;
2: E10 AE1-level; 7: E24 i2t-braking resistor; 12: E73 AE2-scaled 2;
3: E11 AE2-level; 8: E62 actual M-Max; 13: inactive
4: E16 analog-output1-level; 9: E65 PID-error; 14: E08 n-motor; (% ref. to C01)
C48 Operating range of amount C47: √
0: absolute; First, the amount is generated from the signal selected in C47.
Example: C47=AE2; C45=30%; C46=80%. The operating range is -80% to -30% and +30% to +80%.
1: range; The signal selected in C47 must be located in range C45 to C46.
Example: C47=AE2, C45= -30%, C46= +10%. The operating range is -30% to +10%.
C49 Operating range accel&ena: √
0: inactive; During acceleration or deactivated enable, the "operating range" signal for the binary outputs is set
to "0"=ok. The three ranges are only monitored during stationary operation (compatible with device software
V 4.4).
1: active; The operating range is always monitored.
C50 Display function: Only if C60≠ 2 (operating mode≠position). Parameters C50 to C53 can be used to design the √
first line of the display as desired. See chapter 6.1. Eight characters are available for a number, and 8 charac-
ters are available for any unit. Display value = raw value/display factor.
0: n2 & I-motor;
1: E00 I-motor; The inverter supplies the actual motor current in amperes as the raw value.
2: E01 P-motor; The inverter supplies as the raw value the actual active power as a percentage of the nominal
motor power.
3: E02 M-motor; As the raw value, the inverter supplies the actual motor torque as a percentage of the nominal
motor torque.
4: E08 n-motor; The inverter supplies the actual speed in rpm as the raw value.
C51 Display factor: Only if C60≠2. Raw value (C50) is divided by the value entered here. √
Value range: -1000 to 1 to 1000
C52 Display decimals: Only if C60≠2. Number of positions after the decimal point for the value in the display. √
Value range: 0 to 5
C53 Display text: Only if C60≠2 (operating mode≠position) and C50>0. Text for customer-specific unit of measure in √
the operating display (e.g., "units/hour"). Maximum of 8 positions. Can only be entered with FDS Tool.
C60• Run mode √
0: torque; Specification of a b ipolar torque reference value. Reference value processing on AE1 at 1 msec.
1: speed; Speed reference value, conventional operating mode
2: position; Position control activated. When enable signal on X1.9, the position controller is turned on, and the
current position is maintained. If C60=2, group "D.. reference value") is not shown at all.
When the mode is switched from speed to position, the reference position is lost.
3: postion extern;
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
36
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
37
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
38
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
value" is indicated.
Indicates Cf.
the chap. 10.7.
E08 n-motor: current motor speed.
Rotor position: Position of the motor shaft. With absolute-value encoders, the encoder position read from the
E09 encoder is entered when the device starts up. This position is available in all modes. The display shows whole
motor revolutions with 3 positions after the decimal point. The full resolution of 20 bit/R is supplied via fieldbus.
E10 AE1-level: Level of the signal present on analog input 1 (X1.2 to 4). ±10 V is 100%.
E11 AE2-level: Level of the signal present on analog input 2 (X1.6 to X1.7). ±10 V is 100%.
E16 Analog-output1-level: Indicates the level on the analog output (X1.5 to 6). ±10 V corresponds to ±100%.
Relay 1: Status of relay 1 (ready for operation).
E17 0: open; For meaning, see parameter F10.
1: closed; Ready for operation.
Relay 2: Status of BA 2. The function of BA 2 is specified with parameter F00.
E18 0: inactive;
1: active;
E19 BE15...BE1 & enable: The status of the binary inputs including the option board is shown as a binary word.
Device utilization: Indicates the current load of the inverter in %. 100% corresponds to the nominal capacity of
E20 the inverter.
Motor utilization: Indicates the current load of the motor in %. Reference value is the nominal motor current
E21
specified under B12. 2
i2t-device: Level of the thermal device model (i.e., i t model). If utilization is 100%, the fault message
E22 "39:tempDev.i2t" appears.
2
i2t-motor: Level of the thermal motor model (i.e., i t model). 100% corresponds to full utilization.
E23 The thermal model is based on the design data specified under group B (motor) (e.g., continuous operation (S1
operation)).
2
i2t-braking resistor: Level of the thermal braking resistor model (i.e., i t model). 100% corresponds to full
E24 utilization. The data of the braking resistor are specified with A20 to A23.
E25 Device temperature: Current device temperature in °C.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
39
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
running.
Run time:Indicates the current run time. Run time means that the inverter i s connected to the power supply.
E30
E31 Enable time:Indicates the active time. Active time means that the motor is powered.
E46 Status word:Status of the device during fieldbus operation with Kommubox. See fieldbus documentation.
E50 Device: Indication of the exact device type (e.g., SDS 4041).
E52 Device-number:Number of the device from a manufactured series. Same as the number on the nameplate.
E53 Variant-number
Option-board: Indication of the option board detected during initialization.
E54 10: none; 11: SDP 4000 12: SEA 4000 13: SEA + DP 4000
Identity-number:Number assigned by the user as desired from 0 to 65535. Can only be write-accessed with FDS Tool or
E55 fieldbus.
E56 Parameter
unauthorizedset ident. 1:
Indicates
manipulation whetherThe
of parameters. parameters in parameter
parameter record
record ID does not1 change
were changed. Can
when the be used
actions tophase
“B40 detecttest” and
“J04 Tech-in” are executed.
0: All values are default settings (A04=1).
1: Specified value during initialization by FDS Tool.
2 to 253: Customer specification/configuration with FDS Tool. Status without change.
253: When parameters are changed via fieldbus or via the USS protocol, E56 and E57 = 254 are set.
254: At least one parameter value was changed with the keyboard (Controlbox or device)!
E57 Same as E56 but for parameter set 2.
Parameter set ident. 2:
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
40
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
E72 AE2 scaled: AE2 signal after smoothing, offset and factor. E72= (E11 + F21) * F22.
AE2 scaled 2: AE2 signal after smoothing, offset and factor as well as PID controller and offset 2.
E73 E72= ( PID ( ( E11 + F21) * F22 ) ) + F24. Cf. block circuit diagram in chap. 19.
Operating condition:Indicates the current operating state as shown by the operational displ ay. Cf. chapter 16 (Operating
E80 States). Useful for fieldbus polling or serial remote control.
Event level:Indicates whether a current event is present. The type of event is indicated in E82. Useful for fieldbus polling or
E81 serial remote control.
0: inactive; No event is present.
1: message;
2: warning;
3: fault;
E82 Event name:Indicates the current event/fault. Cf. table in chapter 17. Useful for fieldbus polling or serial remote control.
Warning time:The time remaining until the fault is triggered is indicated for the active warnings. This time can be changed via
E83 FDS Tool. Useful for fieldbus polling or serial remote control.
Active parameter set: Indicates the current parameter record. Cf. chapter 9.4. Useful for fieldbus polling or
E84 serial remote control.
1: parameter set 1;
2: parameter set 2;
E100... Parameters E100 and above are used to control and parameterize the inverters by fieldbus. For details, see the
documentation of your fieldbus system.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
41
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
29: BE5
30: BE4;;
31: BE6;
32: parameters active; Low signal means internal parameter conversions not completed. Useful for the
handshake with a higher level controller when converting parameter records, and similar.
BA2 t-on: Causes a delay in switch-on of BA2. Can be combined with all functions of √
F03
BA2. The related function must be present for at least t-on so that the BA 2 becomes active.
Value range in sec: 0 to 5.024
BA2 t-off: Causes a delay in switch-off of BA2. Can be combined with all functions of BA2. √
F04
Value range in sec: 0 to 5.024
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
42
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
43
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
F24 AE2-offset2: An additional offset after multiplication by F22. Used when the reference value is to be multiplied
between 95% and 105% via AE2, for example. √
Value range in %: -400 to 0 to 400
F25 AE1-function: See F20 AE2 function. Caution: Parameters F25 and F20 may not be equal! F25≠F20. √
Value range: 0 to 10 to 14
AE1-offset: Cf. F21. √
F26
Value range in %: -400 to 0 to 400
AE1-gain: Cf. F22. √
F27
Value range in %: -400 to 100 to 400
BE-logic: Logical link when several BEs are programmed for the same function. √
F30 0: OR;
1: AND;
BE1-function: All binary inputs can be programmed as desired. Selection points 0 to 13 and those greater than √
F31• 16 are identical for all binary inputs. If the same function is used by several BEs, F30 can be used to program a
logical link. Inversion can be performed with F51 to F55 and F70 to F74.
0: inactive;
1: reference value-select 0; Binary coded selection of fixed reference values or process blocks. The result of
the reference value selection is indicated in E60.
2: reference value-select 1; See above.
3: reference value-select 2; See above.
4: motorpoti up; If D90=1, two binary inputs can be used to simulate a motor potentiometer. One BE must be
programmed as "4:Motorpoti up," and another BE must be programmed as "5:Motorpoti dwn." See also D90.
5: motorpoti down; Same as "4:Motorpoti up."
6: direction of rotation; Negation of the current reference value.
7: additional enable; BE provides the function of an additional enable (i.e., a fault can also be acknowledged
via this additional enable). The drive is not enabled unless a high signal is present on the "enable" input
(X1.15) and the binary input.
8: halt; With high signal, drive is slowed with the selected deceleration ramp. If F08=1, the brake is then applied.
Ramps: Analog RV specification/motor potentiometer: D01; fixed reference values: D12 to D72;
Positioning: process block ramp.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
44
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
45
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
46
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
G.. Technology
Para. No. Description
G00• PID-controller: Activates the PID controller on input AE2. Cf. chapter 12.1. √
0: inactive;
1: active;
PID-controller Kp: Only if G00=1 (i.e., PID controller active). Loop gain. The total gain of the control loop is √
G01
also affected by F22 (AE2 gain) in addition to G01. Cf. block circuit diagram in chap. 12.1.
Value range: 0 to 0.3 to 100
PID-controller Ki: Only if G00=1 (i.e., PID controller active). Gain of I share in 1/sec. Example: If G02=0.2 x √
G02
1/sec, then a 20% higher constant input signal is integrated within one second.
Value range in 1/sec: 0 to 10
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
47
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
G.. Technology
Para. No. Description
PID-controller Kd: Only if G00=1 (i.e., PID controller active). Gain of D share in msec. √
G03
Value range in msec: 0 to 1000
PID-controller limit: Only if G00=1 (i.e., PID controller active). Adjuster-variable limit. For scaling, see F22. √
G04
Asymmetric limits can be specified with G04 and G05 (e.g., from -10% to +30%). Upper and lower limit values
are automatically (internally) sorted correctly.
Value range in %: -400 to 400
PID-controller limit2: See G04. √
G05
Value range in %: -400 to 400
PID-controller Kp2: Pure proportional gain of the PID controller. Effective parallel to I and D portion. √
G06
Value range: 0 to 1 to 10
Winding operation: Activates the winding functions (speed reduction based on diameter). √
G10•
0: inactive;
1: n mode; Speed adjustment in accordance with n~1/D. No effect on torque limit M-Max.
2: M-Max mode; Maximum torque is reduced based on D-Act ./D-Max.
G11 Diameter: Only if G10≠0 (winding operation active). Specifies the type of diameter definition. √
0: AE-measurement; Diameter sensor 0 to 10 V is connected to AE2.
1: n-line/n-motor; For traction or compensating roller controllers. The diameter is calculated from the ratio of
control speed to motor speed. The control speed (i.e., speed reference value) always refers to an empty reel
(i.e., the smallest diameter).
2: roller; The diameter is calculated with an overtravel ramp based on E122 (from fieldbus or via analog input
function "12:winder roller"). If E122 > 5%, G19 is increased by ramp G16. If E122 < -5%, G19 is decreased by
ramp G16. Otherwise G19 remains constant.
G12 Min. winding diameter: Only if G10≠0 (winding operation active). Diameter of an empty reel. √
Value range in mm: 10 to 3000
G13 Max. winding diameter: Only if G10≠0 (winding operation active). Diameter of a full reel. √
Value range in mm: 10 to 100 to 3000
G14 Begin. winding diameter: Only if G10≠0 (winding operation active). Initial diameter. Must be set via a binary √
input with the function "29:wind.setD-ini" (F31 to F35).
Value range in mm: 10 to 3000
G15 Overdrive ref. value: Only if G10≠0 (winding operation active). G15 is added to the control reference value √
while winding at the torque limit ( G10=2) so that M-limit is triggered and the winding material remains taunt.
Value range in rpm: -6000 to 0 to 6000
Diam.calculator ramp: Only when G10>0. Integration speed of the diameter calculation. √
G16
G11=0: no function
G11=1: limitation of the integration speed for G19
G11=2: ramp with which the diameter is changed when -5% < E122 < +5%.
Value range in mm/sec: 0 to 10 to 100
Tension reduction: Only when G10>0. Reduction of tension as diameter n 100% √
G17 e
t
increases. If min. diameter D-Min: winding with 100% tension. Up to -
F
D-Max: tension reduced linearly up to (100% - G17).
Value range in %: 0 to 100
D-Min D-Max
G19 Actual. winding diameter: Only if G10≠0 (winding operation active). Indication of the current diameter.
Electronic gear: Only when C60=1:speed. Activates the "electronic gear/synchronous running" function √
G20•
(chap. 11). See block circuit diagram in chap. 18.
0: inactive;
1: speed synchron run; G24 limits the effect of the angle controllers. Cf. chap. 11.6.
2: angle synchron run
3: angle + save; Same as G20=2. However, each time enable-off occurs, the angle deviation is stored non-
volatilely and thus remains available after power off and on. See also G25.
Speed master: Only if G20>0 (electronic gear active). The slave speed is calculated from nSlave=G22/G21 x √
G21
nMaster. The increments of the incremental encoders are specified with F36 and H22. If G21=1 and G22=2, the
slave is twice as fast as the master. We recommend selecting the number of increments for the master encoder
(in acc. w. G27) as a power of 2 (e.g., 1024).
Value range: 1 to 2147483647
Speed slave: Only if G20>0 (electronic gear active). See G21. At a speed ratio of 1:1, G21=G22=1 must be √
G22
parameterized. The direction of rotation of the slave can be changed with D92.
Value range: 1 to 2147483647
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
48
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
G.. Technology
Para. No. Description
Kp synchron: Only if G20>0 (electronic gear active). Gain of the angle controller in 1/sec. Typical values are 10 √
G23
to 60. G23=0 activates speed synchronous running. The slave then no longer attempts to catch up with the
master (e.g., after a blockage). Instead, the mathematically precise speed ratio is only ensured within the
window ±G24. When G23=0 and G24=0, the master encoder is only used as a speed reference value, and the
ratio set in G22/G21 is not precisely maintained mathematically. Cf. chapter 11.6.
Value range in 1/sec: 0 to 30 to 100
Max. synchron. difference: Only if G20>0 (electronic gear active). Maximum angle of deviation between √
G24
master and slave (following error). When this value is exceeded, a signal is generated on the output (cf. F00 or
F80=12:synch.diff.), but no fault is triggered. This can be performed with external wiring and the input function
"12:ext.fault" (F31 to F35). In G20=1:speed sync. mode, G24 limits the effect of the angle controller. This
smooths the transition between pure speed synchronous and angle synchronous running.
Value range in °: 0 to 3600 to 30000
Synchron reset: Only if G20>0. Defines conditions for resetting the current synchronous deviation. √
G25
0: with BE; Reset only possible with BE function "28:SyncReset" (always possible).
1: enable & BE; Reset also with removal of the enable as well as with halt and quick stop.
2: free run & BE; Reset only with BE functions "27:syncFreeRun" and "28:SyncReset."
3: enable & free run & BE; All methods above will cause a reset.
The synchronous deviation is always set to zero when the device is turned on. (Exception: G20=3. Reset is only
performed when the stored deviation exceeds 5°).
n-correction-Max: Only if G20>0 (electronic gear active). G26 limits the output of the angle controller. √
G26
Important when large angle deviations must be reduced (e.g., when the free-run function is used).
Value range in rpm: 0 to 3000 to 6000
Synchronous encoder: Only when G20>0. Signals of the master arrive over this interface. √
G27
0: BE-encoder; Master signals are connected to binary inputs.
1: X20; Master signals arrive over plug connector X20.
2: X41;
n-Master: Only when G20>0. For monitoring during commissioning. Speed of reference value encoder as per
G28
G27.
Value range
Synchron in rpm: ± 6000
difference: Only if G20>0 (electronic gear active). Indication of the current synchronous deviation in
G29
degrees as related to the slave motor. n-controller Ki>0 is required for a synchronous deviation near 0.
Value range in °: - 2147483648 to 0 to 2147483647
Speed feed forward: Speed precontrol for synchronous running. When G30=100%, no following error is used √
G30
when speed is constant (synchronous deviation is zero). With dynamic movements, G30 must be reduced (50 to
80%). Otherwise the slave will overswing.
Value range in %: 0 to 80 to 100
Reference direction: Only if G20>0. Starting direction to look for the reference point. Referencing searches for √
G31
a reference cam. Cf. I30=0:Ref.input in positioning mode and the examples in chap. 10.6. Synchronous
deviation is reset at the reference position. Other ways of resetting the synchronous deviation include the BE
signal "28:Synchron Reset" or automatically with parameter G25.
0: positive;
1: negative;
Reference speed fast: Only if G20>0. Speed for first phase of referencing (rough traversing). √
G32
Value range in rpm: 0 to 1000 to 6000
Reference speed slow: Only if G20>0. Speed for final phase of referencing. √
G33
Value range in rpm: 0 to 300 to 6000
Ref.encoder signal 0: Only if G20>0. Referencing to zero pulse of the motor encoder. Do not use for √
G35
continuous mode with an odd-number gear ratio.
0: inactive;
1: Motor-encoder;
Synchronous offset: Only if G20>0. An offset distance based on the voltage on an analog input can be added √
G38
to the current slave position. 10 V corresponds to the angle entered in G38.
Value range in °: -214748364.8 to 0 to 214748364.7
Static friction torque: Only if G10>0. Offset of the static friction (i.e., the friction (coulomb) independent of the √
G40
speed). Value is converted to the motor shaft.
Value range in Nm: 0 to 327.67
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
49
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
G.. Technology
Para. No. Description
Dynamic friction torque: Only if G10>0. Offset of the speed-proportional Friction √
G41
friction. Value converted to the motor shaft at 1000 rpm. G41*n
Value range in Nm/1000 rpm: 0 to 327.67 G40
n
T-dyn lowpass: Only if G10>0. Torque for acceleration/deceleration can be offset dynamically. The load/motor √
G42
inertia ratio with a full reel (D-Max) must be entered for this in parameter C30. The acceleration portion to be
offset
Value is obtained
range by differentiation
in msec: of the speed. G42 specifies the related smoothing time constant.
0 to 50 to 10000
H.. Encoder
Para. No. Description
X20-function: See also description in chap. 5.4. √
H20• 0: inactive;
1: encoder simulation; Encoder simulation (TTL) output for a host controller. H21 specifies the number of
pulses.
2: encoder In; Connection of an incremental encoder with ROD signals. Wire-break monitoring active.
3: stepmotor In; Stepper motor input function. Track A is the sign (low = positive, high = negative). Track B is the
counting frequency (chapters 11.2 and 14.1).
4: SSI simulation; Simulation of a multi-turn SSI encoder. Useful for an absolute-value encoder on X41 for motor
control. The host controller can scan the absolute position in SSI format on X20.
5: SSI master; Connection of an SSI encoder (absolute value encoder). Note: SSI encoders can be used as
external encoders for POSI. The absolute position for POSI can only be read from the encoder when the
device starts up. If H20 is reparameterized and H20 was or is now H20=5, this triggers fault "37:n-feedback“
which cannot be acknowledged. Save values with A00, and turn basic device off/on.
Encodersim. increments: Only if H20=1. Specifies the number of pulses per motor revolution. √
H21
0: 256; 1: 512; 2: 1024; 3: 2048; 4: 4096;
X20-increments: Number of increments for incremental encoders. With SSI encoders, the range of H23 (X20 √
H22 gear ratio) can be expanded with H22. See chap. 10.11. H22=1024 is the neutral setting.
Value range in I/R: 30 to 1024 to 4096
X20-gear ratio: Only if C60=2. Conversion of an external posi encoder to the motor shaft. √
H23
Caution: Parameter has no effect on the speed calculation for motor control (vector control). It is only used to
convert the position of an external encoder.
The following must apply: H23 = number of motor revolutions/number of encoder revolutions. If this formula
results in values over 32.767, the number of encoder increments in H22 must be divided by a suitable factor
(e.g., 2). The result of the above formula is then also divided and entered in H23. See also chapter 10.11.2.
With SSI encoders, the gear ratio is expanded by setting H22 to a value other than 1024.
Value range: -32.768 to 1 to 32.767
X20-zero-Pos.: Zero pulse shift during encoder simulation. √
H24
Value range in °: 0 to 360
Resolver poles: Number of poles of the connected resolver. Typical values are 2 (standard for STÖBER) and 6. √
H31 Value range: 2 to 16
Commutation-offset: Shifts the resolver zero position in comparison to the motor. Since STÖBER motors are √
H32 set to H32=0 at the plant and tested, it is usually never necessary to change H32. If the B40 phase test results
in an H32 value > 0, this probably indicates a problem with the plug connectors or wiring.
Value range in °: 0 to 360
X41-function: See description in chapters 5.5 and 5.6. √
H40 0: inactive;
1: SinCos in;
2: encoder in;
3: stepMot in;
® ®
X41-increments: The value is automatically determined with sin/cos encoders with EnDat or Hiperface √
H41
interface.
Value range in I/R: 30 to 1024 to 4096
X41-gear ratio: See H23. √
H42
Value range: -32.768 to 1 to 32.767
H60 SSI-invert: Reverse sign for external SSI encoders. Wrong sign → unstable control loops. √
0: inactive; Clockwise revolution of motor shaft while facing the shaft (A side) counts as positive.
1: active; Clockwise revolution of motor shaft counts as negative.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
50
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
H.. Encoder
Para. No. Description
SSI-coding: Entry as per encoder data sheet. √
H61
0: gray;
1: binary;
SSI-data bits: Entry as per encoder data sheet. √
H62
Value range: 24 to 25
Posi.encoder: Position control is usually performed by the encoder mounted on the motor ( I02=2). A second
I02 encoder (e.g., also linear measuring system) can be used to prevent slip or inaccuracies caused by the
mechanics. Calibration of an external measuring system is described in chap. 10.11.
0: BE-encoder; HTL encoder on binary inputs.
1: X20; Incremental or SSI encoder on input X20.
2:motorEncoder; The encoder selected with B26 (motor feedback).
3: X41; Encoder on connector X41 (sin/cos encoder for motor control or external TTL incremental encoder with
regulated 5 V (voltage supply).
Direction optimization: Only if I00=1. Activate/deactivate automatic direction optimization for absolute process
I03
blocks ("rotary axis" function). In contrast to the permissible direction of revolution I04>0, manual traversing is
always permitted in both directions. Cf. chap. 10.5.2.
0: inactive; The direction of rotation depends on the sign of the destination position (e.g., J10). When the
circular length is I01=360°, the same position is approached with J10=90° and J20= -270° as with 90°. In the
latter case, however, the direction of rotation is negative.
1: active; Absolute process blocks are approached over the shortest path.
Move direction: Only if I00=1. For continuous axes with only one physically permissible direction of movement.
I04
Movements in the wrong direction are answered with the message "51:Refused." Reference point traversing is
performed completely with the speed I33. A reverse in direction does not occur.
0: positive & negative; Both directions are permitted.
1: positive; Only the positive direction is permitted. (Also applies to manual traversing.)
2: negative;
Measure unit selection: The unit of measure does not yet mean a conversion. The numerical relationship
I05 between the physical mechanics and the indicated position is provided by I07 and I08.
0: user (I09); The unit (4 characters) can be programmed as desired with FDS Tool. See also I09.
1: increments; Encoder increment based on quadruple evaluation (i.e., quadrature pulses).
2: degrees;
3: millimeter;
4: Inch;
Decimal digits: Number of decimal positions for the display and the entry of position reference values, speeds,
I06 accelerations and I07.
Important: Since a change in I06 will cause a shift in the decimal point and thus a change in the affected
values, I06 should be programmed at the very beginning of commissioning.
Example: If I06 is reduced from 2 to 1, values such as 12.27 mm are changed to 122.7 mm. The reason for this
lies in the error-free rounding used by the positioning software.
Value range: 0 to 2 to 3
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
51
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
chaining without
Caution: stop tovalue
The override generate simple
affects n(x) speed
acceleration profiles.
to the power of two. Danger of overload when override
> 100%. During ramps, changes in accel-override are only adjusted slowly in a background task.
When Accel-Override (I15=1) is activated, the override value should not be decreased to 0%. This would make
the ramp infinitely long and the drive would never stop!
S-ramp: Reverse limitation through square sinus ramp. The generated acceleration profile is smoothed with the
I16 specified time constant. Positioning takes a little longer.
Value range in msec: 0 to 32767
ENA-interrupting: In the default setting, removal of the enable causes the position controller to be reset (status
I19 "17:posi.active"). Particularly during continuous positioning, it is important that interrupted process blocks can be
concluded after emergency off or similar. I19=1 offers particularly simple process block interruption. See also
chap. 10.10.
0: inactive; Enable-off resets the positioning controller.
1: active; Enable-off while process block is running causes status " 23:interrupted." The interrupted process
block is completed with Posi.step. Not possible for process blocks which are chained without Stop (J17=2).
Kv-factor: Gain of position controller (only P characteristic) with unit of 1/sec. The Kv factor is also known as
I20 the speed gain. In actual practice, the Kv factor is sometimes specified with the unit m/min/mm which is exactly
0.06 x 120. See also block circuit diagram in chap. 10.7.
Value range in 1/sec: 0 to 30 to 100
Max. following error: The output function ( F00=9:follow.error) is activated when the following error defined in
I21 I21 is exceeded. FDS Tool can then be used to specify the desired reaction to the exceeded following error as a
fault (default setting), warning or message.
Value range in I05: 0 to 90 to 31 bits
Target window: Window for the output signal "reference value reached" (F00=3:RefVal-reached). I22 must be
I22 greater than I23!.
Value range in I05: 0 to 5 to 31 bits
Dead band pos. control. "Dead zone" of the position controller. Useful to prevent idle-state oscillation particu-
I23 larly when an external position encoder is used and there is reversal play in the mechanics. Cf. chap. 10.7.
Caution: I23 Dead band must be smaller than target window I22!
Value range in I05: 0 to 31 bits
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
52
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
I34 Reference position: Value which is loaded to the reference point (e.g., provided by the reference switch or the
stop switch) as the actual position. The drive stops after reference point traversing. The position is determined
by brake ramp I11/2. Cf. chapter 10.6.
Value range in I05: -31 bits to 0 to 31 bits
I35 Ref.encoder signal 0: Only if I36=0 and I30≠2. Referencing to zero pulse of an incremental encoder.
0: inactive; Zero pulse is not evaluated. Referencing to the edge of the stop or reference switch. Important for
continuous axes with transmissions, for example. Also useful when there are not enough binary inputs and
demands on accuracy are not high.
1: motor encoder;
2: posi encoder; In acc. w. parameter I02 (under preparation).
Continuous reference: Only for continuous axes ( I30=0). Used for fully automatic compensation of slip or inex-
I36
act gear ratio. After the reference points are traversed for the first time, actual position I80 is always overwritten
with reference position I34 each time the reference switch is passed over in direction I31 (but only in this direc-
tion!). Since the path which is still to be traversed is corrected, the axis is able to perform any number of relative
movements in one direction without drifting, even when drives have slip. If the reference switch is connected to
BE3, the signal is processed immediately.
Remember: When I36=1, the other edge of the reference switch is evaluated than the one for I36=0 during
reference point traversing. Circular length I01 must be as close as possible to the path between two reference
signals (e.g., after one belt rotation, the same position must be indicated). Check actual position I80 during a
rotation with I36=0, and adjust I07 if necessary. The distance per rotation I07 must always be rounded to the
next higher number to prevent undesired counterclockwise offsets. The reference switch should not be triggered
during a deceleration ramp since a negative offset would cause a counterclockwise movement.
Important: Target window I22 must be greater than the maximum physical inaccuracy!
0: inactive;
1: active
Power-on reference: Automatic reference point traversing after power-on.
I37 0: inactive;
1: posi.start; After power-on, the inverter assumes operating mode "24:ref.wait." The first posi.start or posi.step
signal starts the reference point traversing procedure.
2: automatic; Reference point traversing is started automatically as soon as the enable appears.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
53
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
54
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
3: endless
Speed: negative;
Unit/sec. Caution: If you enter a value greater than the maximum speed I10 in J12, the actual traveling
J12 speed is limited to I10.
Value range in I05/sec: 0 to 1000 to 31 bits
2
Accel: Acceleration, unit/sec . Caution: If the values J13 and J14 exceed the maximum acceleration I11, accel-
J13 eration during movement is limited to I11. Up to software version 4.5: If the direction of rotation must be changed
during a change in process blocks on the fly, the entire reversal procedure is performed with the Accel ramp
(J13).
2
Value range in I05/sec : 0 to 1000 to 31 bits
2
Decel: Deceleration, unit/sec .
J14 2
Value range in I05/sec : 0 to 1000 to 31 bits
Repeat number: Only available if J11=0:relative.
J15
If necessary, a relative movement can be repeated several times based on the value J15. With J17=0, posi.step
is waited for after each partial movement. With J17=1, the partial movements are run through automatically.
Delay J18 is inserted between the movements. J15=0 means no repetition (i.e., one single movement).
Value range: 0 to 254
Next block: Chaining of process blocks. Specification of a process block to which a jump is to be made at the
J16 end of the movement or after a posi.next signal.
0: stop; No process block chaining.
1 to 32: Number of the next process block. Cf. chapter 10.8.
Next start: Only if J15≠0 or J16≠0. J17 defines when and how the branch is made to next block J16.
J17 0: posi.step; Continued movement via posi.step function (rising edge). Cf. J01.
1: with delay; Automatic continued movement after delay J18 expires. In contrast to J17=2, an intermediate
stop is also always performed with J18=0 sec. Delays between process blocks (J18) are prematurely con-
cluded by posi.step.
2: no stop; When the reference position reaches the target position J10, the speed is adjusted without halting
(on-the-fly process block change without intermediate stop!). Drive travels to J10 without braking and then
changes to process block J16. Also useful for generating n(x) speed profiles with support points in up to 8
positions. Cf. I15, chapter 10.8, example 4.
When process blocks are terminated with HALT of enable off, resumption of the terminated movement is not
possible with Posi.Step.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
55
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
The layout of process block nos. 2 to 8 is identical. Process block no. 2 is located in J20 - J28, process block
no. 3 in J30 - J38, etc.
The layout of extended process block parameters is identical for all process blocks. Process block no. 1 is located in L10 to
L12, process block no. 2 in L20 to L22, and so on.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
56
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Posi switching points S2 to S4 are set up identically. Switching point S2 is located in N20 to N24, and so on.
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
57
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
• The power pack must be turned off before these parameters can be changed.
Italics These parameters are sometimes not shown depending on which parameters are set.
1) See result table in chap 15. 2) Only available when D90≠1 3) Only available when D99=0
Parameters which are included in the normal menu scope ( A10=0). For other parameters, select A10=1:extended or A10=2:service .
Parameters marked with a "√ " can be parameterized separately from each other in parameter record 1 and 2.
58
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
V
D
E E E E E E E E E E
G B B B B B B B B B B B B B B B
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
X21
2
1
n
POSIDYN
SDS 4000 F
Purpose:
®
Expansion of the digital inputs/outputs of a POSIDYN SDS 4000 servo inverter
10 additional binary inputs (BE5 to BE14), galvanically isolated
5 additional binary outputs (BA3 to BA7), galvanically isolated
Inputs/outputs identical to those of option boards SEA + SDP4000 (combi board)
Installation:
Remove the cover from the top of the housing with a suitable tool (side cutting pliers).
Do not saw. Do not allow metal shavings to penetrate the device.
Install board vertically in the housing, and secure with two screws.
Ter-
Function Parameter Circuiting
minal
1 Input BE5 F35
L - level: 0 to 7 V / 0 mA
2 Input BE6 F60
H - level: +12 to 30 V / 7 mA, Ri=3,3 kΩ
3 Input BE7 F61
59
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
123456789
X32
n
2
1 POSIDYN
SDS 4000 F
Purpose:
®
PROFIBUS link to aPOSIDYN SDS 4000 servo inverter
Plug connector allocation is identical to the SEA + SDP4000 option board (combi-board).
Installation:
Remove the cover from the top of the housing with a suitable tool (side cutting pliers).
Do not saw. Do not allow metal shavings to penetrate the device.
Install board vertically in the housing, and secure with two screws.
Ter-
Function Comment
minal
1 Not used For correct function, use only suitable plug connectors for connection of the bus cable.
2 Not used The incoming and outgoing bus cable can be inserted in this plug connector and screwed
2 down.
3 3 TxD/RxD (P) = B
X The sliding switch on the plug connector must be set to "on" for the last station so that the
p
i 4 RTS
trs bus terminal resistors are connected.
l 5 DGND
a
n
i 6 VP
m
r
e 7 Not used
T
8 TxD/RxD (N) = A
9 Not used
14.3 Option board SEA 4000 and SDP 4000 (combi board)
V
D
E E E E E E E E E E
G B B B B B B B B B B B B B B B
171 61 51 41 31 21 1 10 9 8 7 6 5 4 3 2 1 X32
X21
2
1
n
POSIDYN
SDS 4000 F
Purpose:
®
Expansion of the digital inputs/outputs of a POSIDYN SDS 4000 servo inverter
10 additional binary inputs (BE5 to BE14), galvanically isolated
5 additional binary outputs (BA3 to BA7), galvanically isolated
®
PROFIBUS link to a POSIDYN SDS 4000 servo inverter
Installation:
Remove the cover from the top of the housing with a suitable tool (side cutting pliers).
Do not saw. Do not allow metal shavings to penetrate the device.
Install board vertically in the housing, and secure with two screws.
For terminal allocation X21 and X32, see option boards SEA 4000 and SDP 4000.
60
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Result Table
The result of actions (e.g., save parameter (A00=1) is indicated on the display. Possible results are listed below.
0: Error free The data were transferred correctly.
2: Wrong box Controlbox's data memory has incompatible data structure (e.g., formatting for another memory size).
3: Invalid data Controlbox's data memory contains invalid data. Write Controlbox again, and repeat the procedure.
Software version of Controlbox data (or similar) and inverter differ in several parameters. Confirm with
5: OK (adjusted)
the key. Message does not affect functionality of the controller.
Software version of Controlbox data (or similar) and inverter differ in several parameters. Confirm with
6: OK (adjusted)
the key. Message does not affect functionality of the controller.
• If synchronous reference value G27=0:BE encoder or posi encoder I02=0:BE encoder, the following
must apply: F31=14(15), F32=15(14).
• If G27=1 (synchronous reference value = X20) or I02=1 (posi encoder = X20), the following must
9: BE encoder signal
apply: F31≠14(15), F32≠15(14).
Values in parentheses: Encoder (signal A, B) and stepper motor connection (frequency + sign) access
the same counter.
Conflict while accessing the encoder pulse counter (there is only one) or error in parameterization of the
sin/cos encoder
• X20 may not be simultaneously programmed as the pulse input with BE1/BE2 or X40 (F31, F31≠14,
12: BE/X20/X41 15 and H40≠2:encoder In when H20=2, 3 and vice versa).
• When motor encoder B26=3:SinCos, H40=1:Sincos must be programmed.
• When motor encoder B26=3:SinCos, neither X20 nor BE1/BE2 may be programmed as the pulse
input (encoder or stepper motor).
Programming F31=14 and F32=14 can be used to simulate the direction of rotation of inverters with
13: BE cw/ccw software SDS 3.2. The functions "direction of rotation," "halt," and "quick stop" may not be assigned to
other BEs.
• The B40/B41 actions could not be executed correctly.
• Action canceled (e.g., due to removal of enable).
14: Canceled
• The current exceeded the permissible maximum value (e.g., short circuit or ground fault) during
"autotuning" or "phase test" (B40, B41).
A stator resistance measured during "autotuning" (B41) was too high. Motor is circuited incorrectly.
15: R1 too high
Motor cable is defective.
19: Symmetry Error in symmetry of phases U, V and W. Deviation of a winding resistor by ±10%.
22: F20=F25 ?? Both analog inputs (AE1 and AE2) are programmed for the same function. F20≠F25 must apply.
Error in motor wiring (order of the phases, U, V, W incorrect). Is reported as the result of the B40 phase
25: Phase order test.
• Check motor wiring and, if necessary, resolver cable too.
The zero offset of the motor encoder (resolver) is not correct. Is reported as the result of the B40 phase
test. With STÖBER ES motors, the error is usually to be found in the wiring or in the plug connector.
26: Encoder offset • Check motor and resolver wiring. Then start phase test (B40) again.
• If no wiring error can be found, the measured offset is stored (non-volatile) via A00=1 in H32 with all
other parameters.
61
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Operating States
The operating state is indicated in the display of Controlbox with number and name and can be queried under E80 during
fieldbus access. An abbreviation appears in the LED status display of the device.
0: Ready Inverter is ready. Voltage is available.
7: n > n-Max Reference value is greater than minimum of C01 and E126 (via analog input or fieldbus).
8: Illegal direction Specified direction of rotation is not the permissible direction of rotation (C02).
13: Serial (X3) Not al- Parameter A30=1 parameterized. Inverter is controlled by the PC via serial interface.
ways
16: Fault Exy Inverter's power pack is disabled. “xy” is the fault code (see chap. 17).
17: Positioning-active Position control is active. Waiting for a start command. Basic state of positioning control.
Processing a traversing job. Drive is moving. Indicated instead of the states of the speed
18: Moving
mode (i.e. accelerate, brake, left and right).
For process block chaining with defined delay or for repetition of relative movements. During
19: Delay a stop between two sequential jobs, the signal "in position" is generated, but the display
shows "delay."
20: Wait For process block chaining with defined manual start (i.e., wait for posi.step signal)
21: Referencing During reference point traversing with posi or synchronous running
62
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Faults / Events
When faults occur, the inverter is no longer able to control the drive and is disabled. An entry is made in the fault memory
(E40/E41), and relay 1 (ready for operation) releases. If installed when the fault occurs, the Parabox is written automatically.
Certain events (cf. last column of the table below) can be declared via FDS Tool as faults, messages, warnings or not effective.
Auto FDS
Reset Tool*
The hardware overcurrent switch-off is active.
31: Short/ground • Motor requires too much current from the inverter (e.g., interwinding fault or √
overload).
34: Hardw. fault The non-volatile data memory is defective or software version is time-limited.
Monitors the load and functions of the microprocessor
35: Watchdog This malfunction may also be caused by EMC problems (e.g., shield of the motor cable √
or PE conductor not connected at all or connected incorrectly).
DC-link voltage too high
• Power too high
• Reverse powering of the drive while braking (no brake resistor connected, brake
36: High voltage √
chopper defective, brake chopper deactivated with A20). See chap. 4.6.
• Braking resistor with too low resistance value (overcurrent protection).
• Automatic ramp extension at Umax is possible with A20=1 and A22=0.
Resolver: Wire break or signal level too low
Fault can only be acknowledged by turning 24 V off and on!
Sin/cos absolute-value encoder:
• During device startup
37: n-feedback - Communication to the device is faulty.
- Absolute-value encoder unknown
- Communication protocol unknown (neither EnDat® nor HiperFace)
• During operation
- Wire break or signal level too low
- Change in B26
The heat dissipater temperature is over the limit value. Cf. E25.
38: tempDev.sens
• Temperature of environment/switching cabinet is too high.
The inverter limits the output current to 99% of the nominal current.
The i2t model calculated for the inverter has reached 100% of the thermal load.
• Inverter is overloaded. (inverter too small).
39: TempDev.i2t • Temperature of the environment/switching cabinet is too high.
• Closed brake
• Motor connected incorrectly
• Resolver connected incorrectly
The data in non-volatile memory are incomplete. Reset non-volatile memory with "A00
40: Invalid data
save values." This loads the default values.
The i t programmed
• A20 model for theincorrectly
braking resistor reaches 100% thermal load.
42: Temp.brakeRes • Permissible power loss of brake resistance is too high.
• With internal brake resistance: No jumper on X12. chap. 5.2.
• With external brake resistance: Brake resistor not connected.
44: Ext.fault Fault triggered by BE
• Motor overloaded
45: OTempMot.i2t √
• Cooling insufficient
DC-link voltage is below the limit value set in A35.
46: Low voltage • Drops in the power supply √ √
• Acceleration times are too short (ramps, D..).
* Events can be programmed with FDS Tool as messages, warnings or faults, or can be completely deactivated.
63
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
Faults / Events
When faults occur, the inverter is no longer able to control the drive and is disabled. An entry is made in the fault memory
(E40/E41), and relay 1 (ready for operation) releases. Certain events (cf. last column of the table below) can be declared via
FDS Tool as faults, messages, warnings or not effective.
Auto FDS
Reset Tool*
The maximum torque has been exceeded.
47: Device overl. The permissible torque is limited by parameters C03 and C04 and the possible torque √ √
limitation via analog input. See chap. 9.2.
Same as "47:Device overload" except for an acceleration procedure. M-Max 2 ( C04) is
48: Accel.overl. permitted for the acceleration procedure with "cycle characteristic" startup (C20=2). √ √
49: Decel.overl. Same as "47:Device overload" except for a deceleration procedure √ √
50: Operat.area The operating area defined under C41 to C46 has been exited. See also chap. 9.3. √ √
Only for positioning (C60=2). Posi.start or posi.step was not accepted.
• Destination position is located outside software limit switches I50 and I51.
51: Refused • In non-referenced status (I86=0), no absolute positions (e.g., J11=1) are traveled to. √ √
• The direction of rotation in the current process block is not the same as the permissible
direction I04.
• Fault during communication between inverter and FDS Tool during remote control via
52: Communication PC √
• Communication fault during fieldbus operation
A limit switch connected via a BE input or monitored via fieldbus has been triggered.
53: Stop input During referencing at the limit switch (I30=1), a reversal of the limit switches will cause a √
fault.
The maximum following error (i.e., deviation between actual position and reference value
position) permitted by I21 has been exceeded.
54: Follow. error √ √
Motor overload,
•• Kv-factor I20 tootoo much
small, acceleration
speed or blockage
feed forward I25 too small
• When option board SEA-4000 is used, the external 24 V voltage is not present or the
55: OptionBoard card is defective. No fault if enable is deactivated.
• No option card found
* The events checked in the "FDS Tool" column can be parameterized with FDS Tool as messages, warnings or faults in the
group U.. protective functions.
Acknowledgment of faults:
Parameters E40 and E41 can be used to scan the last 10 faults (i.e., value 1 is the last fault). FDS Tool can then be used to
assign the inverter's reaction (fault, warning, message or nothing) to certain events.
64
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
AE2 (AE1)
tip +
RV-gain
offset direction
(displacement of
tip - rotation
AE2-
function t
synchron n
e
offset m
e
c F20 γ 14 &
BE- negate la
p F25 γ 14
BE1/BE2
Increment ref. value is
d
master
incre-
ment
t synchron
X20 e n difference
o
X20-
Inc. s
e
r ati
n-motor ti n-korr. el.
Kp
(slave) m gear
li max.
direction synchronous n-slave el. gear
of rotation encoder n-master
message
synchron
AE2- AE2- difference
gain offset2 (relays2, BA1)
AE2 intervension in max. synchron
250-m sec difference
5:override clock pulse n
u
-r
e
e
fr
synchron reset
AE2-function
C60=1 n
ro
h
c
n
Run mode = s eed y
s
synchron free-run
D99=1 Operation
input When n-Max (C01) is exceeded, the
C32 Ki
69
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
A37 Reset memorized values D03 Reference value -Max [%] 100 E28 Analog-output2-level [%]
A38 DC power-input 0 D04 Speed (min. ref. value) [rpm] 0 E29 n-ref. value raw [rpm]
A40 Read parabox [%] D05 Ref. value-Min [%] 1 E30 Run time [h,m,sec]
A41 Select parameter set D06 Ref. value offset [%] 0 E31 Enable time [h,m,sec]
A42 Copy para set 1>2 [%] D07 Ref. value enable 0 E32 Energy counter [kWh]
A43 Copy para set 2>1 [%] D08 Monitor ref. value 0 E33 Vi-max-memo value [V]
A50 Tip D09 Fix reference value no. 0 E34 I-max-memo value [A]
A51 Tip ref. value [rpm] 300 D10 Accel 1 [msec/3000rpm] 60 E35 Tmin-memo value [°C]
A55 Key hand function 1 D11 Decel 1 [msec/3000rpm] 60 E36 Tmax-memo value [°C]
A80 Serial address 0 D12 Fix ref. value 1 [rpm] 750 E37 Pmin-memo value [kW]
A84 Profibus baudrate D22 Fix ref. value 2 [rpm] 1500 E41 Fault time
B.. Motor D30 Accel 3 [msec/3000rpm] 120 E42 Fault count
B00 Motor-type * D31 Decel 3 [msec/3000rpm] 120 E45 Control word
B02 EMC-constant [V] 110 D32 Fix ref. value 3 [rpm] 3000 E46 Status word
B03 Motor fan 0 D40 Accel 4 [msec/3000rpm] 5 E47 n-field-bus [rpm]
B10 Poles 6 D41 Decel 4 [msec/3000rpm] 5 E50 Device
B11 P-nominal [kW] * D42 Fix ref. value 4 [rpm] 500 E51 Software-version
B12 I-nominal [A] * D50 Accel 5 [msec/3000rpm] 10 E52 Device-number
B13 n-nominal [rpm] * D51 Decel 5 [msec/3000rpm] 10 E53 Variant-number
B17 M0 (standstill) [Nm] * D52 Fix ref. value 5 [rpm] 1000 E54 Option-board
B26 Motor-encoder 2 D60 Accel 6 [msec/3000rpm] 20 E55 Identity-number
B40 Phase test [%] D61 Decel 6 [msec/3000rpm] 20 E56 Parameter set ident. 1
B52 L-motor [mH] * D62 Fix ref. value 6 [rpm] 2000 E57 Parameter set ident. 2
B53 R1-motor [Ω] * D70 Accel 7 [msec/3000rpm] 25 E58 Kommubox
B64 Ki-IQ (Moment) [%] * D71 Decel 7 [msec/3000rpm] 25 E60 Reference value selector
B65 Kp-IQ (moment) [%] * D72 Fix ref. value 7 [rpm] 2500 E61 Additional ref. value [rpm]
C.. Machine D81 Decel-quick [msec/3000rpm] 2 E62 Actual M-max [%]
C00 n-Min [rpm] 0 D90 Reference value source 0 E63 PID-controller limit
C01 n-Max [rpm] 3000 D91 Motorpoti function 0 E64 Brake
C02 Perm. dir. of rotation 0 D92 Negate reference value 0 E65 PID-error [%]
C03 M-Max 1 [%] 150 D93 RV-generator E71 AE1 scaled [%]
C04 M-Max 2 [%] 150 D94 Ref. val. generator time [msec] 500 E72 AE2 scaled [%]
C30 J-mach/J-motor 0 D99 Fast reference value 1 E73 AE2 scaled 2 [%]
C31 n-controller Kp [%] 60 E80 Operating condition
71
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
E83 Warning time F80 BA1-function 1 I01 Circular length [I05] 360
F45 Analog-output2-function 1 G28 n-Master [rpm] I60 Electr. cam1 begin [I05] 0
F46 Analog-output2-offset [%] 0 G29 Synchron difference [°] 0 I61 Electronic cam1 end [I05] 100
F47 Analog-output2-gain [%] 50 G30 Speed feed forward [%] 80 I70 Position-offset [I05] 0
F49 BE-gear ratio 1 G31 Reference direction 0 I80 Actual position [I05]
F51 BE1-invert 0 G32 Reference speed fast [rpm] 1000 I81 Target position [I05]
F52 BE2-invert 0 G33 Reference speed slow [rpm] 300 I82 Active process block
F53 BE3-invert 0 G35 Ref.encoder signal 0 0 I83 Selected process block
F54 BE4-invert 0 G38 Synchronous offset [°] 0 I84 Following error [I05]
F55 BE5-invert 0 G40 Static friction torque [Nm] 0 I85 In position
F60 BE6-function 0 G41 Dyn. friction torque [Nm/100rpm] 0 I86 Referenced
F61 BE7-function 0 G42 T-dyn lowpass [msec] 50 I87 Electronic cam 1
F62 BE8-function 0 H.. Encoder I88 Speed [I05/sec]
F63 BE9-function 0 H20 X20-function 1 J.. Posi.Command
F64 BE10-function 0 H21 Encodersim. increments 2 J00 Posi.start
F65 BE11-function 0 H22 X20-increments [I/R] 1024 J01 Posi.step
F66 BE12-function 0 H23 X20-gear ratio 1 J02 Process block number 0
F67 BE13-function 0 H24 X20-zeroPos. [°] 0 J03 Tip-mode
F68 BE14-function 0 H31 Resolver poles 2 J04 Teach-in
F70 BE6-invert 0 H32 Commutation-offset [°] 0 J05 Start reference
F71 BE7-invert 0 H40 X41-function 0
F72 BE8-invert 0 H41 X41-increments [I/R] 1024 = Standard menu level. Cf. par. A10
F73 BE9-invert 0 H42 X41-gear-ratio 1 Extended menu level: A10=1
F74 BE10-invert 0 H60 SSI-invert 0
WE = Default setting
F75 BE11-invert 0 H61 SSI-Code 0
* = Depends on type
F76 BE12-invert 0 H62 SSI-databits 25
72
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
20. Parametertabelle
Parameter DS Entry of Process Blocks 1 to 8 (Process blocks 9 to 32 can only be programmed with FDS-Tool)
Block 1 Block 2 Block 3 Block 4 Block 5 Block 6 Block 7 Block 8
J10 to J18 J20 to J28 J30 to J38 J40 to J48 J50 to J58 J60 to J68 J70 to J78 J80 to J88
J..0 Position [I05] 0
J..1 Position mode 0
J..2 Speed [I05/sec] 1000
2
J..3 Accel [I05/sec ] 1000
J..4 Decel [I05/sec2] 1000
J..5 Repeat number 0
J..6 Next block 0
Parameter DS Entry
L.. Posi.Command 2 (Extended Process Block Parameters)
L10 to L12 L20 to L22 L30 to L32 L40 to L42 L50 to L52 L60 to L62 L70 to L72 L80 to L82
L..0 Brake 0
L..1 Switch A 0
L..2 Switch B 0
Parameter DS Entry
M.. Menu skip (Menüsprungziele)
Jump to F1 Jump to F2 Jump to F3 Jump to F4
M50 to M52 M60 to M62 M70 to M72 M80 to M82
M50 F1-jump to
M51 F1-lower limit
M52 F1-upper limit
Parameter DS Entry
N.. Posi.Switches
73
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
21. Accessories
74
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
21. Accessories
Controlbox documentation:
Publ. no. 441445 (german)
Publ. no. 441479 (englisch)
Publ. no. 441651 (french)
Additional cables:
5 m = Id.-no. 43216
10 m = Id.-no. 43217
42225 External operator,
in a built-in DIN housing 96x96 mm
see above
Protection rating IP54
75
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
21. Accessories
FFZT
ZT FZZT
FZ ZT FZDT
FZD T
L R R R
M 10 K K K
O U U U
76
POSIDYN® SDS 4000 STÖBER
ANTRIEBSTECHNIK
21. Accessories
VHPR150V VHPR600V
Type
150 W, 100 600 W, 100
L 212 420
C 193 400
B 40 60
500 ±10
A 21 31
D 4,3 5,3
E 8 11,5
F 13 19.5
Weight [g] approx. 310 approx. 1300
[dimensions in mm]
M5 FS4834-10-29 FS4835-25-29
M5
5 5 Constr. height 60 Constr. height 70
9 4
M4 M4
M6 M6
280
320
310
55
Output derating AD 320 (complete)
77
Additional information under:
http://www.stoeber.de
G
K
.
o
C
+
H
b
m
G
8
IK 0
N 0 -
H .26 e
ic
C t
STÖBER . . . The Drive for Your Automation E
T
0
· n
o
S 2 r
o
B .0 ri
Presented by: E
I 2 p
.0 t
R u
T 9 o
4 h
N 4 it
A 1 w
4 e
R 4 g
E . n
STÖBER ANTRIEBSTECHNIK B o a
Ö n h
c
GmbH + Co. KG T n
GERMANY o ot
S ti t
Kieselbronner Strasse 12 · 75177 Pforzheim 8 a c
Postfach 910103 · 75091 Pforzheim 0 c
li je
0 b b
u
Fon +49 (0) 7231 582-0, Fax +49 (0) 7231 582-1000 2 u
Internet: http://www.stoeber.de / e-Mail: [email protected] S
© P -