99spde e

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

PROFIBUS-DP-Adapter 99spde E

- page 1 of 2 -
_______________________________________________________________________
1,2 side view

3
1 Terminals supply voltage 4
2 Coding switches address adjustment
3 Status-LED
4 RJ-45 connector KFM device 1
5 9-pole D-SUB plug PROFIBUS 5
4 Configuration interface (service) for
PC connection 2 (covering
removed)
6
General description:
The connection of KFM devices to the PROFIBUS DP is realised by the external bus adapter 99spde, which
is configured to the requested transmission data e.g. actual value, setpoint. The PROFIBUS interface is able
to replace separate wiring of analogue (external setpoints, signal outputs) or digital signals (via binary inputs
and status bits respectively via relay outputs and control bits). The PROFIBUS-DP interface is carried out as
RS 485 bus interface referring to EN50170. The PROFIBUS adapter has to be connected via a 9-pole
D-SUB plug directly to the bus wiring. The communication between the adapter and the service interface of
the KFM device takes place by a patch cable(1,5m), which is delivered with each adapter. For each segment
32 devices could be installed, with a repeater up to 99. For the data transmission data modules for fixed and
floating point operation are available. The baudrate is detected automatically up to 12 Mbaud. Further
Information refer to the GSD file in the appendix.
An error bit makes it possible to monitor the function of the adapter. Additionally, connection errors are
registered and available for diagnosis by the use of fault memory.
Types:
99spde04. Adapter for 4 PROFIBUS values, power supply 24V DC
99spde12. Adapter for 12 PROFIBUS values, power supply 24V DC
99spde28. Adapter for 28 PROFIBUS values, power supply 24V DC
Device variants (last number):
.0 Functional module without power supply for connection to power supply modules
.0i Functional module for connection to power supply of already existing KFM-assemblies
..0b Functional module with binary input 24V DC; terminal open: normal function /
read and write possible, terminal closed: read only
Power supply module:
99e500 Power supply module 100-250 V AC
Adjustments:
The PROFIBUS adapter is delivered preadjusted. In case of changes, the preadjustments except from the
bus address, can easily be modified by a configuration program (WinPKS PC Software from version 1.9L).
factory setting
Data word 1 Bus setpoint 1 (1060 ref. to protocoll KFM 2.0) Bus setpoint 1
Data word 2 Actual value 1 (1010 " " " ) Actual value 1
Data word 3 Actual value 2* (1011 " " " )
Data word 4 Control signal* (1020 " " " )
for further parameter codes refer to page 5 and 6
* = depending on type
Bus address 0..99, Coding switch, available after removing the covering below the 5
power supply terminals
Hint: In case of multiple bus participants different addresses
have to be adjusted !
connection diagram: Functional m odule pow er supply m odule**
Bus- KFM-device- configuration- pow er supply* pow er supply
interface interface 8../9.. interface(PC)
b1 +24V(opt.) 27 L+ 100-
PROFIBUS KFM 2.0 KFM 2.0 27 L+ 24V DC 28 L- 250 V AC
DP 28 L- 29
29 ** In conjunction w ith
* When using w ithout functional modulew ith-
pow er supply module only out pow er supply only

data subjects to alerations 99spde_e1.doc / 1610511


Interface 99spde 99spde E
PROFIBUS-DP-adapter - page 2 of 2 -
_______________________________________________________________________

Installation note:
The modules must be locked on the designated mounting rail one after the other and then pushed together.
The plug connectors connect the individual modules. Before removal, the modules must be shifted apart one
after the other.
Commissioning:
Set the desired double-digit profibus-address by use of the two coding switches (available after removing the
covering below the power supply terminals). Different addresses have to be configured on multiple adapters.
Connect Profibus with 9-pole D-SUB connector and patch wire (1,5m) with service interface of the KFM
device.The LED on the front signalises the operating status:
yellow permanent: Normal operation
yellow flashing: Communication error between KFM device and PROFIBUS-DP adapter
Hint: all transmitted values are set to “0“,
bit 8 of the respective status byte (communication error) ist set to “0“.
The respective fault memory will be increased by 1.
red flashing: Communication error PROFIBUS DP, PROFIBUS DP not active
Hint: all transmitted values are set to “0“,
the respective fault memory will be increased by 1.
red yellow flashing: Communication error PROFIBUS DP and KFM device
Hint: all transmitted values are set to “0“,
each fault memory will be increased by 1.

Installation dimensions: Technical data:


Housing: for fastening to 35mm mounting rail
Installation orientation: optional
Type of protection: IP20 according to EN 60529
Perm. ambient temperature: 0..60°C
H
Nominal temperature: 20°C
Power supply: 24V DC, about 100 mA,
alternative 100-250V AC, about 12 VA

T
*
B

H= 99mm,
* version with or witout power supply module:
B = 22,5mm or 45mm, T = 116mm

Wiring example:
Plug Socket
Profibus master (master) (99spde.)
9 8 7 6 6 7 8 9
6 5 4 3 2 1 1 2 3 4 5

390 Ohm
Pin-out of the 9-pin connector
3 Please activate termination 3: RxD/TxD-P Receive / send data (+)
220 Ohm resistors in the first and the 4: CNTR-P RTS control signal for optical fibres
last connector, otherwise 5: DGND Reference for termination resistors
8 provide replacements ! 6: VP +5V supply for termination resistors
8: RxD/TxD-N Receive / send data (-)
390 Ohm

RS 485 ...
K1 K1

K2 K2
K3 K3
K4 K4

99spde.. KFM device 99spde.. KFM device


L99spde-d10910205

data subjects to alteration 99spde_e2.doc / 1610511

You might also like