VL2900 Inverter Instruction

This document provides safety information and precautions for using a VL2900 series ozone power supply. It outlines dangers, warnings, and important attention items to follow before installation, during installation, at wiring, and after power-on to avoid injury, equipment damage, or fires. Proper grounding, using qualified personnel, and not modifying the device are emphasized.

Uploaded by

SangNgominh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
622 views51 pages

VL2900 Inverter Instruction

This document provides safety information and precautions for using a VL2900 series ozone power supply. It outlines dangers, warnings, and important attention items to follow before installation, during installation, at wiring, and after power-on to avoid injury, equipment damage, or fires. Proper grounding, using qualified personnel, and not modifying the device are emphasized.

Uploaded by

SangNgominh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 51

HIGH EFFICIENCY OZONE POWER SUPPLY

VL2900 Series

Quick Guide

For safe use of this product, be sure to read


the manual.
VL2900 series of high-performance Ozone Power Simple Manual I

Contents

01、Safety Information and Precautions--------------------- 1

02、Product Information------------------------------------- 4

03、System Connection--------------------------------------------8

04、Installation and wiring--------------------------------------- 11

05、Basic Operation------------------------------------------------ 23

06、List of parameters----------------------------------------------27

07、Fault diagnosis and exception handling--------------- 44

08、Maintenance and upkeep------------------------------------ 48


II Foreword

Please Read This Important Information

Thank you for choosing the VL2900 series ozone power supply.
At the same time, you will enjoy our comprehensive and sincere service for you.
Here accepts no liability for any consequences resulting from negligent or incorrect
installation or parameter adjustment of the Products.
Please strict adherence to this instruction is required to ensure a high level of safety. If
in doubt, please consult with ours.
VL2900 series of high-performance Ozone Power Simple Manual 1

01,Safety Information and Precautions


In this manual, there are three categories of security levels:

DANGER:indicates that failure to comply with the notice will result in severe personal injury or even death.

WARNING:indicates that failure to comply with the notice will result in personal injury or property damage.

ATTENTION:If the operation is wrong, it may result in moderate or minor injury, and equipment damage。

Please kindly be noted that these three kinds of mark relates to the safety.Any violation of these rules might lead to death
or injury, damage of machine and its system. In addition, we will be not responsible for any personal hurt or damage of
machine which is due to violation of principle mentioned in this manual.

Before installation
● Do not install the equipment if you find water seepage, component missing or damage upon
unpacking.
DANGER ● Donot installthe equipment ifthe packing listdoes not conform tothe product you received.
● Do not touch the components with your hands. Failure to comply will result in static electricity
damage.
● When handling the ozone power supply, be sure to hold on to the shell. If you grab the
front cover plate to carry the ozone power, the main body of the ozone power will fall,
there is a risk of injury.
●Handle the equipment with care during transportation to prevent damage to the
equipment.
WARNING
● Do not use the equipment if any component is damaged or missing Failure to comply
will result in personal injury.
● The device has been tested for withstand voltage before leaving the factory. No
voltage withstand test can be carried out on any parts of the ozone power supply. And
High Voltage may lead to ozone power insulation and internal device damage.

During installation

● Donot loosenthe fixed screws of the components, especiallythe screws with red mark.
● Refitting Ozone Power supply is strictly prohibited.The modified ozone power supply may
DANGER
pose a risk of electric shock.If your company or your company's customer has carried on the
transformation to the product, our company will not assume any responsibility.
● Do not install,maintain,inspect or replace parts unless you are an electrical professional. Or
WARNING
there's a risk of electrocution.
● Use a shielded cable for the encoder, and ensure that the shielding layer is reliably grounded.
● Do not install transformers and other electromagnetic waves or interference devices in the
ATTENTION
ozone power supply around, otherwise it will lead to ozone power supply misoperation.If you
need to install such equipment, should set shield plate between it and the ozone power supply.
2 01,Safety Information and Precautions

At wiring
● Do not operate the connection when the power is connected, otherwise there will be
electric shock.Before checking, please cut off the power supply of all equipment. Even if
the power supply is cut off, there is residual voltage in the internal capacitor. Please wait at
DANGER
least 10 minutes after power is cut off.
● The contact current of the ozone power supply is greater than 3.5 ma, please make sure
that the ozone power supply is well grounded. There's a risk of electrocution.
● Do not connect the power supply to the output terminal of the ozone power supply.
Otherwise, it will cause the ozone power supply to be damaged, even may cause the fire.
● Some systems may operate mechanically when energized, and there is a risk of death or
serious injury.
● Before connecting the ozone power supply, please make sure that the ozone power
supply cover plate is firmly installed and the motor is allowed to restart.
WARNING ● Before connecting the ozone power supply, please confirm whether the rated voltage of
the ozone power supply is consistent with the power supply voltage.
● If the main circuit power supply voltage is used in error, there will be a fire risk.
● It is forbidden to connect the input power supply to the output terminals (U, V, W) of the
ozone power supply. OTHERWISE CAUSE OZONE POWER DAMAGE!
● The brake resistance must not be directly connected to the DC bus (P +) , (N -) terminals.
Or there will be a fire!
● When using ozone power supply, please follow the steps required by electrostatic
prevention measures (ESD) , otherwise it will damage the ozone power supply.
● Please follow the local standards, take certain branch, Short Circuit Protection
Measures. If the protection measures are not appropriate, it may cause the ozone power
supply to be damaged.
● The ozone power supply is suitable for short-circuit current below 100ka, the maximum
voltage is 440VAC (400V class) circuit.
ATTENTION ● Please do not share the ground wire with the welding machine or the power machine
which needs high current, otherwise it will cause the ozone power source or the machine to
act badly.
● When using more than one ozone power supply, take care not to make the ground wire
into a loop. Otherwise, it will cause the Maloperation of the ozone power supply or the
machine.
● Do not connect or operate if the machine is visibly damaged or parts are missing.
● The wiring, the inspection and so on please operate by the professional personnel.

After power-on
● Do not open the cover plate when the power is on. OR YOU'LL GET ELECTROCUTED!
● Do not touch any input or output terminals of the ozone power supply. OR YOU'LL GET
DANGER ELECTROCUTED!
● Please do not remove the ozone power supply cover or touch the printed circuit board,
otherwise there will be the risk of electric shock.
● If you need to confirm the parameter identification, please note that there is a risk of
injury during the motor rotation. Otherwise, it could cause an accident!
WARNING
● Do not change the ozone power supply manufacturer parameters. Otherwise it may cause
damage to the equipment!
VL2900 series of high-performance Ozone Power Simple Manual 3

During operation
● Non-technical personnel should not detect the signal in operation. Otherwise, it may
cause personal injury or equipment damage!
DANGER
● Do not touch the fan or the discharging resistor to check the
temperature. Failure to comply will result in personal burnt.
● During the operation of the ozone power supply, no object is allowed to fall into the
equipment. OTHERWISE CAUSE EQUIPMENT DAMAGE!
WARNING
● Do not use contactor on-off method to control the start and stop of ozone power
supply. OTHERWISE CAUSE EQUIPMENT DAMAGE!

During maintenance
● Personnel without professional training are not allowed to carry out repair and
maintenance of ozone power supply, otherwise cause personal injury or equipment
damage!
● Please do not carry on the repair and maintenance to the equipment with live
electricity. OR YOU'LL GET ELECTROCUTED!!
● carry on the ozone power supply maintenance and repair 10mins after cutting off the
ozone power supply input power. Otherwise the residual charge on the capacitor will do
DANGER
harm to people!
● Before carrying out the maintenance work on the ozone power supply, please ensure
that the ozone power supply is safely disconnected from all the power supply.
● All the pluggable components must be plugged or removed only after power-off.
● After the replacement of ozone power supply must be set and check the parameters。
● Please do not power up the damaged machine, otherwise it will enlarge the damage of
the machine.
● The rotating electric motor will feed some electric energy back to the ozone power
supply, which will cause the ozone power to be charged even when the electric motor
WARNING stops and the power is cut off. Before carrying out the maintenance work on the ozone
power supply, please ensure that the motor is safely disconnected from the ozone
power supply.

Signs related to Ozone Power Supply Safety

The ozone power supply has warning signs for use at the following

locations. When using, be sure to follow the warning signs.

● Be sure to read the instructions before installation and operation,

otherwise there will be electric shock danger!

DANGER ● Please do not remove the cover plate when the power is on and the

power is cut off within 10 minutes!

● For maintenance, Inspection and wiring, please first cut off the input side

and output side power supply, and then wait 10 minutes, until the power

indicator completely extinguished, before allowing the operation.


VL2900 series of high-performance Ozone Power Simple Manual 4

02、Product Information
2.1 Type and Identification
Product Category:(Take 3-phase 2.2 kw ozone power supply with built-in Brake Unit as an example.)

VL2900 T 0022 B P

Ozone Power Supply

Braking Empty:None B:BUILT-IN BRAKE

Power Level 0022:2.2KW 0220:22KW

Voltage level T :Three Phase380V S:single-phase 220V

2T:three phase 220V

Product Line

Product Nameplate(Take 3-phase 2.2 kw ozone power supply with built-in Brake Unit as an example.)

Model of Ozone Power Supply MODEL :VL2900T0022GB/P

Rated input INPUT :AC3PH 380-480V 50Hz/60Hz

Rated output OUTPUT:AC2PH 0-540V 6.9A 2.2KW


0-10000Hz
Manufacture Number

SN: :Serial Number


5 02、Product Information

2.2 Product List


VL2900 series of ozone power supply power range is 0.4 ~ 1100KW, the main information is shown in table 2-2.
Configuration and installation dimensions of ozone power supply. Please refer to 4.1.3.

Form:2-2 VL2900 SERIES PRODUCT LIST


SINGLE-PHASE POWER SUPPLY:220V,50Hz/60Hz
Frequency
Rated output current Structural Power Supply
Model Number Range
(A) Code (KW)
(KHz)
VL2900S0004GB/P 5.5 D1 0.4 0.2-10
VL2900S0007GB/P 9 D1 0.75 0.2-8
VL2900S0015GB/P 13 D1 1.5 0.2-8
VL2900S0022GB/P 13 D2 2.2 0.2-8
VL2900S0030GB/P 17 D2 3 0.2-8
VL2900S0040GB/P 25 D2 3.7 0.2-8
VL2900S0055GB/P 32 D2 5.5 0.2-8
VL2900S0075GB/P 45 D3 7.5 0.2-8
VL2900S0110GB/P 60 D4 11 0.2-8
VL2900S0150GB/P 75 D4 15 0.2-8
VL2900S0185GB/P 91 D4 18.5 0.2-8
VL2900S0220G/P 112 D5 22 0.2-8
VL2900S0300G/P 150 D5 30 0.2-8
VL2900S0370G/P 176 D5 37 0.2-4
VL2900S0450G/P 210 D6 45 0.2-4
VL2900S0550G/P 304 D6 55 0.2-4
VL2900S0750G/P 350 D7 75 0.2-4
VL2900S0900G/P 380 D7 90 0.2-4
VL2900 series of high-performance Ozone Power Simple Manual 6

THREE-PHASE POWER SUPPLY:220V,50Hz/60Hz


Frequency
Rated output current Structural Power Supply
Model Number Range
(A) Code (KW)
(KHz)
VL29002T0004GB/P 5.5 D1 0.4 0.2-10
VL29002T0007GB/P 9 D1 0.75 0.2-8
VL29002T0015GB/P 13 D1 1.5 0.2-8
VL29002T0022GB/P 13 D2 2.2 0.2-8
VL29002T0030GB/P 17 D2 3 0.2-8
VL29002T0040GB/P 25 D2 3.7 0.2-8
VL29002T0055GB/P 32 D2 5.5 0.2-8
VL29002T0075GB/P 45 D3 7.5 0.2-8
VL29002T0110GB/P 60 D4 11 0.2-8
VL29002T0150GB/P 75 D4 15 0.2-8
VL29002T0185GB/P 91 D4 18.5 0.2-8
VL29002T0220G/P 112 D5 22 0.2-8
VL29002T0300G/P 150 D5 30 0.2-8
VL29002T0370G/P 176 D5 37 0.2-4
VL29002T0450G/P 210 D6 45 0.2-4
VL29002T0550G/P 304 D6 55 0.2-4
VL29002T0750G/P 350 D7 75 0.2-4
VL29002T0900G/P 380 D7 90 0.2-4
7 02、Product Information

THREE-PHASE POWER SUPPLY:380V,50Hz/60Hz


Frequency
Rated output current Structural Power Supply
Model Number Range
(A) Code (KW) (KHz)
VL2900T0004GB/P 2.5 D1 0.4 0.2-10
VL2900T0007GB/P 3.7 D1 0.75 0.2-10
VL2900T0015GB/P 5.5 D1 1.5 0.2-10
VL2900T0022GB/P 6.9 D1 2.2 0.2-8
VL2900T0030GB/P 9 D1 3 0.2-8
VL2900T0040GB/P 13 D1 3.7 0.2-8
VL2900T0055GB/P 17 D2 5.5 0.2-8
VL2900T0075GB/P 25 D2 7.5 0.2-8
VL2900T0110GB/P 32 D2 11 0.2-8
VL2900T0150GB/P 37 D3 15 0.2-8
VL2900T0185GB/P 45 D3 18.5 0.2-8
VL2900T0220GB/P 60 D4 22 0.2-8
VL2900T0300GB/P 75 D4 30 0.2-8
VL2900T0370GB/P 91 D4 37 0.2-8
VL2900T0450G/P 112 D5 45 0.2-8
VL2900T0550G/P 150 D5 55 0.2-8
VL2900T0750G/P 176 D5 75 0.2-4
VL2900T0900G/P 210 D6 90 0.2-4
VL2900T1100G/P 253 D6 110 0.2-4
VL2900T1320G/P 304 D6 132 0.2-4
VL2900T1600G/P 350 D7 160 0.2-4
VL2900T1850G/P 380 D7 185 0.2-4
VL2900T2000G/P 426 D7 200 0.2-4
VL2900T2200G/P 470 D8 220 0.2-4
VL2900T2500G/P 520 D8 250 0.2-4
VL2900T2800G/P 600 D8 280 0.2-2
VL2900T3150G/P 650 D8 315 0.2-2
VL2900T3550G/P 730 D9 355 0.2-2
VL2900T4000G/P 850 D9 400 0.2-2
VL2900T4500G/P 950 D9 450 0.2-2
VL2900T5600G/P 1160 D9 560 0.2-2
VL2900T6300G/P 1300 D10 630 0.2-2
VL2900T7100G/P 1450 D10 710 0.2-2
VL2900T8000G/P 1550 D11 800 0.2-2
VL2900T9000G/P 1700 D11 900 0.2-2
VL2900T10000G/P 1900 D11 1000 0.2-2
VL2900T11000G/P 2000 D11 1100 0.2-2
VL2900 series of high-performance Ozone Power Simple Manual 8

03、System Connection

3.1 Safety Information and Precautions

Safety Information and Precautions

● It is forbidden to connect the power supply when the power supply is turned
Danger
on. Or there's a risk of electrocution. Be Sure to keep the breaker OFF.

● When an ozone power supply is installed in a closed cabinet or other closed

environment, adequate cooling, such as cooling fans or air conditioners, must


Warning
be used to ensure that the inlet temperature of the ozone power supply is kept

below 50 °C, otherwise it will lead to overheating or fire.

● During the installation, please cover the upper part of the ozone power

supply with cloth or paper to prevent metal chips, oil, water and so on from

entering the inner part of the ozone power supply.

● If the foreign matter enters the ozone power supply, may cause the ozone

power supply breakdown.

● Please take off the cloth or paper when the work is finished. If continue to

Attention cover on the top, it will make the poor ventilation, resulting in abnormal heat

ozone power.

● When operating the ozone power supply, please follow the steps required by

electrostatic prevention measures (ESD) , otherwise the inner circuit of the

ozone power supply will be damaged by static electricity.

● Do not remove the hood of the State of the ozone power supply hanging,

otherwise may cause ozone power circuit board or terminal row damage.
9 03 、 System Connection

3.2 System Connection Diagram


When ozone power supply is used to make ozone system, it is necessary to install all kinds of electrical components on
the input and output side of ozone power supply to ensure the safety and stability of the system.
THREE-PHASE 380V ~ 480V 45kW and above product systems are constructed as follows:

Three-phase electric power Pleaseuse the power supplywithinthe inverter allowedspecificationrange.

No fuse breaker (MCCB) When the power input, a large impact current will flow into the inverter, so users

or residual-current device need to pay attention to the selection of circuit breakers.

To ensure safety, use an electromagnetic contactor.Please do not use the


electromagnetic contactor electromagnetic contactor to start and stop the converter, which will reduce the
service life of the converter.

AC Reactor Suppression of higher harmonics and improvement of power factor.

Input side EMC Filter

Reduce the EMI on the

input side.

Earthing

Output Reactor (schematic Diagram)

Transformer (schematic Diagram)

Oxygen Generation

Composition diagram of power supply for ozone production system


VL2900 series of high-performance Ozone Power Simple Manual 1 0

3.3 DESCRIPTION OF SYSTEM COMPOSITION

Form:3-1 Operating instructions for the peripheral electrical components of the Ozone Power Supply System.

Name of Mounting
Function description
accessories Position
Between the Short Circuit Breaker: cut off the power supply when the downstream
input side of equipment overflows to prevent accidents.
the power Earth Leakage Protection Circuit Breaker:High frequency leakage current
Circuit Breaker
supply and the may be produced when ozone power supply is working. In order to prevent
Ozone Power electric shock and electric fire, please select and install appropriate leakage
Supply. protection circuit breaker according to the situation on site.
Between the
breaker and Power-on and power-off operation of ozone power supply should avoid
(electromagnetic)
the input side frequent up-down operation (interval time is not less than one hour) or direct
CONTACTOR
of the Ozone start operation of ozone power supply through contactor.
Power Supply.
Increasing the power factor of the input side;
Input side of Effectively eliminate the input side of the higher harmonic, to prevent voltage
Input Reactor Ozone Power waveform distortion caused by other equipment damage;
Supply. Eliminate the unbalance of input current caused by the unbalance between
power supply phases.
Reduce the external conduction and radiation interference of Ozone Power
Input side of
EMC Supply;
Ozone Power
Filter Reduce the conduction interference from the power supply to the ozone
Supply.
power supply, improve the anti-interference ability of the ozone power supply.
Increasing the power factor of the input side;
Between the
Improve the efficiency and thermal stability of Ozone Power Supply;
direct current emc filter and
It can effectively eliminate the influence of higher harmonic on the input side
reactor the brake
of the ozone power supply and reduce the external conduction and radiation
resistance;
interference.
Between the
ozone power
supply output
Output side and the
high voltage If necessary, the output reactor can be installed or not.
Reactor package,
install close to
the ozone
power supply.
Output side of
Transformer Ozone Power Please select the suitable transformer.
Supply.
VL2900 series of high-performance Ozone Power Simple Manual 11

04、Installation and Wiring


4.1 Installation
4.1.1 Installation Environment
1) Ambient Temperature:Ambient temperature has a great effect on the lifetime of Ozone Power Supply,
The operating environment temperature of the ozone power supply is not allowed to exceed the allowable temperature
range (- 10 °C ~ 50 °C) .
2) ) The ozone power supply is mounted on the surface of the flame-retardant Object.There should be enough
space around to dissipate the heat.Ozone power supply is easy to produce a lot of heat when it works.And it is
mounted vertically with screws on the mounting support.
3) Please install in a non-vibrating place. Vibration should not be greater than 0.6 G.
4) Do not install in direct sunlight, wet, water places.
5) Do not install in the air has corrosive, flammable, explosive gas places.
6) Do not install in oil, dust places.
7 ) Ozone power supply is the product installed in the cabinet,need to be installed in the final system for use,the final
system shall provide the corresponding fireproof enclosure, electrical protective enclosure and mechanical protective
enclosure, etc.And comply with the local laws and regulations and related IEC standard requirements.

4.1.2 Direction and space of installation


In order to help the ozone power source to dissipate heat,to install the ozone power supply in the vertical direction (figure
4-1) .And ensure that the surrounding ventilation space.Table 4-1 shows the gap size for the ozone power supply
installation(recommended value).

Picture 4-1 Schematic diagram of installation space

Form 4-1 Installation Space Requirement


Power Level Size requirement (unit:mm)
0.4kW~18.5kW A1≥10 B1≥200 C1≥40
22kW~75kW A1≥50 B1≥200 C1≥40
90kW~1100kW A1≥50 B1≥300 C1≥40
12 04、Installation and wiring

4.1.3 External dimensions and mounting dimensions

Picture 4-2-A Outline size and installation size (schematic diagram)

Form 4-3 VL2900 series product size list (single phase / three phase 200V class)
installation
Structure Power Section of External Dimension (mm) Installs Weight
dimension(mm) remarks
Code Name Ozone Power Supply A B H W L Screw (kg)
D1 0.4KW~1.5KW 125 166 186 114 172 M4 1.1
D2 2.2KW~5.5KW 160 186 248 149 237 M4 2.5 Plastic shell
hanging type
D3 7.5KW 208 194 322 190 304 M6 6.5
D4 11KW~18.5KW 280 210 436 200 425 M6 20
D5 22KW~37KW 385 265 600 260 580 M8 32
D6 45KW~55KW 473 307 700 343 678 M12 47 Metal hanging
type
D7 75KW~90KW 500 359 860 400 840 M12 90
D8 110KW~132KW 660 370 1160 400 1139.5 M12 130

Form 4-4 VL2900 series product size list (3-phase 400V class)
installation
Structure Power Section of External Dimension (mm) dimension(mm) Installs Weight remarks
Code Name Ozone Power Supply A B H W L Screw (kg)
D1 0.4KW~4KW 125 166 186 114 172 M4 1.1
D2 5.5KW~11KW 160 186 248 149 237 M4 2.5 Plastic shell
hanging type
D3 15KW~18.5KW 208 194 322 190 304 M6 6.5
D4 22KW~37KW 280 210 436 200 425 M6 20
D5 45KW~75KW 385 265 600 260 580 M8 32
D6 90KW~132KW 473 307 700 343 678 M12 47 Metal hanging type.
D7 160KW~200KW 500 359 860 400 840 M12 90
D8 220KW~315KW 660 370 1160 400 1139.5 M12 130 Please refer to the
drawing of the
D9 355KW~560KW 700 432 1340 400 1309 M12 200 machine Case.
D10 630KW~1000KW 830 510 1180 600 1240 M12 240
D11 - - - - - - - -
C1 - - - - - - - - METAL CABINET
C2 - - - - - - - - TYPE
Please refer to the
C3 - - - - - - - - drawing of the
machine Case.
VL2900 series of high-performance Ozone Power Simple Manual 13

158mm

147mm

79mm
92mm

79mm
82,6mm

SECTION A-A
8,2mm

Picture 4-2-C Outline dimensions and mounting dimensions of VL2900 external panel (TJ2)

Form 4-4 Outline dimensions list of VL2900 series external keypad


Opening Hole installation
Structure Dimensions(mm) dimension(mm) Installs Weight
Code Name
Name Screw (kg)
remarks
A B H W L
VL2900External
TJ2 92 8.2 or 2 158 79 147 - -
Panel
14 04、Installation and wiring

4.2 Wiring
4.2.1 Standard wiring diagram
The following diagram is the VL2900 series 3-phase 380V voltage class 45kW ~ 1100kW model wiring diagram, other
specifications refer to the following section explanation.

breaker contactor fuse

Next stage load of


ozone-producing
VL2900 Equipment

wire jumper J2 External keypad interface

Analog output1: 0~10v/0~20mA

Factory setting:
wire jumper J3 Operating frequency: 0~10V, F15.00=1

Analog output2: 0~10v/0~20mA

Run/stop Factory setting:


Operating frequency (after compensation) :
0~10v, F15.01=2

Pulse train output: 0~100kHz


(this function is reserved)
Factory setting:
Operating frequency 0~50kHz, F15.02=1

earth terminal Open collector output 1:0~24Vdc/0~50mA


Factory setting:
no output, F17.00=0

wire jumper J1

Relay R1 output
250Vac above 10mA and below 3A
30Vdc above 10mA and below 1A
Factory setting:
inverter fault, F17.02=4
Communication
Selection

Relay R2 output
More Than One

Single Machine

250Vac above 10mA and below 3A


The maximum speed :115200bps 30Vac above 10mA and below 1A
Factory setting: no output, F17.03=0

earth terminal

Annotation: Shielded twisted-pair


Layer;

Picture 4-3 Typical wiring diagram of three-phase 380 ~ 480V


VL2900 series of high-performance Ozone Power Simple Manual 15

4.2.2 Main Circuit Power Terminal


Form 4-4 Main Circuit Terminal Specification
Terminal
Terminal Name Function description
Marking
R、S、T
or Power input terminal AC input three-phase power connection point.
L1、L2、L3
DC bus positive and negative Input point of common DC bus,connecting point of
P+、N-或 P-
terminals. External Brake Unit.
P+、PB Brake resistance connection terminal. Brake Resistance Connection Point
P+、P(P1) DC reactor terminal External DC reactor (or short connection)
U、V、W Ozone Power Supply Output Terminal connected load

Earthing terminal(PE) protective earthing

Wiring instructions of different specifications

Form 4-5 VL2900 single-phase 220V ozone power supply wiring instructions
Terminal
Terminal Name Function description
Marking
R、T 220VPower input terminal AC input single-phase power connection point
P+、P(P1) DC reactor terminal External DC reactor (or short connection)
Ozone Power Supply Output Terminal
V、W connected load
18.5 kw or less
Ozone Power Supply Output Terminal
U、W connected load
22 KW and above
Earthing terminal(PE) protective earthing

Form 4-5 VL2900 three-phase 220V ozone power supply wiring instructions
Terminal
Terminal Name Function description
Marking
R、S、T 220VPower input terminal AC input single-phase power connection point
P+、P(P1) DC reactor terminal External DC reactor (or short connection)
Ozone Power Supply Output Terminal
V、W connected load
18.5 kw or less
Ozone Power Supply Output Terminal
U、W protective earthing
22 KW and above

Earthing terminal(PE) protective earthing


16 04、Installation and wiring

Form 4-5 VL2900 three-phase 380V ozone power supply wiring instructions
Terminal
Terminal Name Function description
Marking
R、S、T 380VPower input terminal Ac input three-phase power supply connection point
P+、P(P1) DC reactor terminal External DC reactor (or short connection)
Ozone Power Supply Output Terminal
V、W connected load
37KW or less
Ozone Power Supply Output Terminal
U、W connected load
45KW and above
Earthing terminal(PE) protective earthing

4.2.3 Guide for selection of peripheral electrical components

Form 4-5Guide for selection of peripheral electrical components for Ozone Power Supply
SINGLE-PHASE POWER SUPPLY:220V,50Hz/60Hz

Input side main Output Side Main Control loop


Breaker contactor
Model circuit conductor Circuit Conductor conductor
(A) (A)
(mm2) (mm2) (mm2)

VL2900S0004GB/P 10 9 0.75 0.75 0.5


VL2900S0007GB/P 16 12 0.75 0.75 0.5
VL2900S0015GB/P 25 18 1.5 1.5 0.5
VL2900S0022GB/P 32 25 2.5 2.5 0.5

Three phase power supply: 220V, 50 Hz 60 HZ


Input side Output Side
Control loop
Breaker contactor main circuit Main Circuit
Model conductor
(A) (A) conductor Conductor
(mm2)
(mm2) (mm2)
VL29002T0004GB/P 6 9 0.75 0.75 0.5
VL29002T0007GB/P 10 9 0.75 0.75 0.5
VL29002T0015GB/P 10 9 0.75 0.75 0.5
VL29002T0022GB/P 16 12 1.5 1.5 0.5
VL29002T0030GB/P 20 18 2.5 2.5 0.75
VL29002T0040GB/P 20 18 2.5 2.5 0.75
VL29002T0055GB/P 40 32 4 4 0.75
VL29002T0075GB/P 50 38 6 6 0.75
VL29002T0110GB/P 63 50 10 10 0.75
VL29002T0150GB/P 100 65 16 16 0.75
VL29002T0185GB/P 100 80 25 25 1
VL29002T0220GB/P 125 95 35 35 1
VL29002T0300GB/P 160 115 50 50 1
VL29002T0370GB/P 225 170 70 70 1
VL29002T0450GB/P 250 205 95 95 1
VL29002T0550GB/P 315 245 120 120 1
VL29002T0750GB/P 500 300 150 150 1
VL29002T0900GB/P 500 350 170 170 1
VL2900 series of high-performance Ozone Power Simple Manual 17

Three phase power supply: 380V, 50 Hz 60 HZ


Input side Output Side
Control loop
Breaker contactor main circuit Main Circuit
Model conductor
(A) (A) conductor Conductor
(mm2)
(mm2) (mm2)
VL2900T0004GB/P 6 9 0.75 0.75 0.5
VL2900T0007GB/P 6 9 0.75 0.75 0.5
VL2900T0015GB/P 10 9 0.75 0.75 0.5
VL2900T0022GB/P 10 9 0.75 0.75 0.5
VL2900T0030GB/P 16 12 1.5 1.5 0.5
VL2900T0040GB/P 16 12 1.5 1.5 0.5
VL2900T0055GB/P 20 18 2.5 2.5 0.75
VL2900T0075GB/P 32 25 4 4 0.75
VL2900T0110GB/P 40 32 4 4 0.75
VL2900T0150GB/P 50 38 6 6 0.75
VL2900T0185GB/P 50 40 10 10 1
VL2900T0220GB/P 63 50 10 10 1
VL2900T0300GB/P 100 65 16 16 1
VL2900T0370GB/P 100 80 25 25 1
VL2900T0450G/P 125 95 35 35 1
VL2900T0550G/P 160 115 50 50 1
VL2900T0750G/P 225 170 70 70 1
VL2900T0900G/P 250 205 95 95 1
VL2900T1100G/P 315 245 120 120 1
VL2900T1320G/P 350 300 120 120 1
VL2900T1600G/P 400 300 150 150 1
VL2900T1850G/P 450 350 170 170 1
VL2900T2000G/P 500 410 185 185 1
VL2900T2200G/P 630 475 240 240 1
VL2900T2500G/P 630 475 2×120 2×120 1
VL2900T2800G/P 700 620 2×120 2×120 1
VL2900T3150G/P 800 620 2×150 2×150 1
VL2900T3550G/P 1000 800 2×185 2×185 1
VL2900T4000G/P 1250 800 2×240 2×240 1
VL2900T4500G/P 1250 1000 2×240 2×240 1
VL2900T5600G/P 1500 1200 2×260 2×260 1
VL2900T6300G/P 1500 1200 2×260 2×260 1
VL2900T7100G/P 1800 1500 2×260 2×260 1
VL2900T9000G/P 1800 1500 2×260 2×260 1
VL2900T10000G/P 2000 1700 2×280 2×280 1
VL2900T11000G/P 2000 1700 2×280 2×280 1
18 04、Installation and wiring

4.2.4 Control loop terminal distribution.


◆ Control loop terminal layout.

AI1 Input and output selection, the default is voltage input;

AI2 Input and output selection, the default is the current input;

AO1 Output selection, the default is voltage output;

AO2 Output Selection, the default is the current output;

wire jumper

External keyboard interface

wiring terminal

Picture 4-4 Terminal Layout of Control Circuit

Note: Due to different specifications or product upgrades, the control loop terminal may be different from
the actual product, please refer to the actual product.
VL2900 series of high-performance Ozone Power Simple Manual 19

Form 4-6 VL2900 series Ozone Power Control Terminal function description.
Terminal Terminal
Categories Function description
Symbol Name
External Provide +10V power to the outside,Maximum output current:
+10V Connection 10mA .Generally used as an external potentiometer power
- GND + 10VPower
Supply supply,Resistance range of potentiometer: 1kΩ~10kΩ.
Power
Supply External
Provide +24V power supply to the outside, generally used as the
Connection
+24V - COM working power supply of digital input and output terminals and the
+24V Power
maximum output current of external sensor power supply: 200mA.
Supply
AI -GND Analog Input 1 Input Range: 0Vdc~10Vdc/0mA~20mA,by the control panel J 1, J13
Analog Input jumper selection decision.
AI2 -GND Analog Input 2 Input Impedance: Voltage Input 22kΩ, current input 500Ω.
X1 -COM Digital Input 1
X2 -COM Digital Input 2
X3 - COM Digital Input 3
X5 - COM Digital Input 5 Switching Input of Optical coupling isolation
X6 - COM Digital Input 6 Input impedance: 1.39 k Ω
Digital Input X7 - COM Digital Input 7
X8 - COM Digital Input 8
In addition to the characteristics of X1~X3、X5~X8 ,it can also be used
as a high-speed pulse inputchannel.
X4 - COM Digital Input 4
Maximum input Frequency: 100kHz
Input Impedance: 1.03kΩ
The voltage or current output is determined by the choice of the J2
Analog Output jumper on the control panel.
AO1 - GND
1 Output voltage range:0V~10V
Analog Output current range: 0mA~20mA
Output The voltage or current output is selected by the J3 jumper on the control
Analog Output panel.
AO2 -GND
2 Output voltage range: 0V~10V
Output current range: 0mA~20mA
Optical coupling isolation,Open collector output.
Digital Output
Y1 - +24V Output voltage range:0V~24V
1
Digital Output Output current range:0mA~50mA
DO1 - High speed
COM(Retain) High speed pulse output up to 100kHz
pulse output
TA1 - TB1 NC terminal Contact driving capacity:250Vac,3A,COSØ=0.4,
TA1 - TC1 NO terminal 30Vdc,1A
Relay Output TA2 - TB2 NC terminal Contact driving capacity:250Vac,3A,COSØ=0.4,
TA2 - TC2 NO terminal 30Vdc,1A
RS485
485+ Communicatio
Communicati n positive end
on Interface RS485 Differential signal input and output, half duplex.
selection Communicatio
485-
n negative
end
External
Auxiliary
J11 keypad External Keypad
Interface
interface
AI1 Input
J1 Voltage and current input is optional, default is voltage input
selection
AI2 Input
J13 Voltage and current input is optional, default is current input
Selection
wire jumper
AO1 Output
J2 Voltage and current output is optional, default is voltage output
Selection
AO2 Output
J3 Voltage and current output is optional, default is current output
Selection
20 04、Installation and wiring

4.2.5 Signal input terminal wiring instruction:


1)AI Analog Input Terminal:
Weak analog voltage signals are particularly susceptible to external interference, so generally need to use shielded cable,
and wiring distance as short as possible, do not exceed 20m, as shown in figure 4-5.
In some cases where the analog signal is seriously disturbed, a filter capacitor or ferrite core should be added to the
source side of the analog signal, as shown in figure 4-6.

Picture 4-5 Analog input terminal wiring diagram

Cross or wind two or three


同向穿过或者
coils in the same direction VL2800
同向绕2~3匝
AI1

0.022uF、50V
GND

铁氧体磁环
Ferrite magnetic core

Picture 4-6 Analog input terminal processing wiring diagram


VL2900 series of high-performance Ozone Power Simple Manual 21

2)X Digital input terminal:


Generally need to use shielded cable, and wiring distance as short as possible, do not exceed 20m.When the active
driving mode is selected, the necessary filtering measures should be taken for crosstalk of power supply.Contact control
mode is recommended.

◆ SINK wiring

Signal

External inverter control panel


controlle

Picture 4-7 SINK wiring

This is the most common type of connection.


Note: In this connection mode, the x terminal of different ozone power supply can not be connected to
use, otherwise it may cause x Maloperation;If need x terminal to connect (between different ozone power
source) , then need to connect diode in series at x terminal (anode to x) to use,diodes are required:
IF>10mA、UF<1V, as shown below.

Inverter1 control panel

Inverter2 control panel

External
controlle

Picture 4-8 Multiple ozone power supply x

terminals connected in parallel in SINK mode.


22 04、Installation and wiring

3)Y1 Digital Output Terminal:


When a digital output terminal is required to drive the relay, an absorption diode should be installed on
either side of the relay coil.Otherwise, it is easy to damage the DC 24V power supply.The driving capacity
is less than 50mA.

Note 1: Be Sure to properly install the polarity of the absorption diode. Here's how. Otherwise, when the
digital output terminal has the output, will immediately burn out the DC 24V power supply.

diode

relay

Picture 4-9 Digital output terminal wiring diagram


VL2900 series of high-performance Ozone Power Simple Manual 23

05、Basic Operation
5.1 Operation Panel Instructions
Ozone power supply can be operated, monitored and controlled by LED operation panel.In addition to the LED operation
panel of ozone power supply, users can also choose the external operation panel.
Among them, the parameters can be modified and viewed through the LED operation panel, and the parameters can be
copied, downloaded and other functions through the selection of the external operation panel.

5.2 LED operation panel


(the following is VL2900 series operation panel)
Through the operation panel, the ozone power supply can be set/modified/monitored/controlled (start,
stop) and other operations.The appearance of the operation panel and the name of the operation key are
shown in the following figure:

Command source indicator


OFF:PanelRun Command Channel;
Forward/Reverserotation indicator
ON:Terminal RunCommand Channel; ON: reverse rotation
blinking quickly : Communication run OFF: forward rotation
command channel;
blinking slowly : Analog runs command
channel; Tuning/Torque control indicator
ON:Torque control mode;
RUN indicator OFF: blinking slowly:Tuning status;
RU N CH FW D /REV TU N E/TC

Stop; ON:operating;
Data display area
blinking slowly : Zero-frequency
operation;
blinking quickly:Dc brake; Hz A V Unit indicator
RPM %

Multi-function key
Potentiometer FU N
ESC
Exit/shortcut key
JO G

Increment key
Shift key

EN TER
Enter/set key
RUN key
STO P
RU N Stop/Reset key
RESET
Decrement key

Picture 5-1 Operation panel diagram


24 05 、 Basic operation and commissioning

5.2.1 Light Indicator:


Form 5-1 Indicator light description
Function indicator light
Indicator Light
State specification
Name Status
OFF Stop
RUN ON operation
(RUN indicator) blinking slowly Zero-frequency operation
blinking quickly Dc brake
OFF Panel Run Command Channel
CH ON Terminal Run Command Channel
(Command Communication run command
blinking quickly
source indicator) channe
blinking slowly Analog runs command channel
FWD/REV OFF forward rotation
(rotation indicator) ON reverse rotatio
TUNE/TC ON Torque control mode
(Tuning Status / torque control
blinking slowly Tuning status
indicator)
Unit indicator
Hz frequency indicator A Current indicator V voltage indicator State specification
ON OFF OFF unit of frequency
OFF ON OFF unit of current
OFF OFF ON unit of voltage
ON ON OFF unit of rotational speed
OFF ON ON Percentage Unit
All the indicator lights are blinking slowly except the running indicator Failure or alarm

5.2.2 LED Display area


There are 5-bit LED display on the operation panel, which can display setting frequency, output
frequency, various monitoring data and alarm code, etc. .
Form 5-2 Actual correspondence table and LED display correspondence table.
ACTUAL ACTUAL ACTUAL
LED display LED display LED display
SYMBOL SYMBOL SYMBOL
0 0 A A o o
1 1 b b n
2 2 C C u u
3 3 d d r
4 4 E E T
5 5 F F N
6 6 G U U
7 7 - - P P
8 8 - _ Y Y
9 9 - - - -

5.2.3 Keyboard Button Function


VL2900 series of high-performance Ozone Power Simple Manual 25

Form 5-3 A menu of keyboard keys


button Name Function
Press the shift key on themain interface to switch the display
monitoring parameters (F38.10 ~ F38.15 can set the
monitoring parameters);
Shift key
Press the shift key on the non-main interface, and the effective
bits can be switched between ones, tens, hundreds, thousands
and tens thousands.

Multi-function key (F37.00 can set its function) ;


Multi-function key In the "Operation Panel" Start and stop control mode, for the
point movement operation.

Escape key
Exit / Shortcut Key Main interface to enter monitoring parameters and fault record
parameters group (F39 group) shortcut key;

Enter/set key Step into the menu screen, set parameter confirmation.

In Operation Panel Start Stop Control Mode, used to run


RUN key
operations.

When running, press this key to stop running operation, this


Stop/Reset key characteristic is restricted by function code F37.00;
Can Be used for reset operation when the fault alarm state.

Increment key Increment of data or function code.

Decrement key Decrement of data or function code.

5.3 Basic operation ( Set parameters, restore factory values, command channel switch, change
monitoring parameters, password lock and unlock)
26 05 、 Basic operation and commissioning

5.3.1 Set parameters

Set parameters (the example restores the parameters to factory settings, other parameter settings are similar to this
example) :

Press Interface Press the shift key to


ENTER to display switch the
Power-on display enter the significance bit
main interface subinterface
F00
50.00

Press ENTER
to ENTER the
Toggle significant Interface
Next Modify the
bit display
subinterface interface to
F38.0
F38
0

Interface
Modify the Press ENTER Modify the
display
interface to to ENTER the interface to

F38.08
Next 0 2
subinterface

Press the ESC key twice in a Press Enter to set


Parameter initialization row to return to the home the data
completed screen.
Other parameter settings are
similar to this example
VL2900 series of high-performance Ozone Power Simple Manual 27

VL2900 series ozone power supply parameters list

1.Parameter List Reading Instruction

Symbols instructions

Function Number Parameter number, that is, the number shown on the LED panel.
(Communication Represents the register address used for MODBUS communication, where H represents the
Address) hexadecimal value and the number represents the specific address.
Name Parameter Name
Represents a hexadecimal value that can only be modified (not carried) by bits and is subject to
(H) upper and lower limits.
(myriabit、housands, hundreds, tens, ones)
Parameters set range, different control mode parameters set range may be different for
Range
different models.
factory default Factory set value, different control mode different model factory set value may be different.
V: (Voltage) Volt; A: (current) Ampere; C: (temperature) Centigrade; Ω: (Resistance) ohm; mH:
(Inductance) Milligram; rpm: (speed) rpm;% : percent; BPS: (Baud Rate) Bit per second; Hz,
unit
Khz: (frequency) Hertz, Khz; ms, Sec. , Min. H: (time) ms, s, Min, H; KW: (Power) KW; 1: No
units and so on
Change properties Indicates whether the parameters can be changed and the conditions changed.
√ A parameter that can be modified in any state.
× Non-modifiable parameters in the running state.
☆ Actual detection parameters cannot be modified.
Factory parameters are only modified by the factory. USERS ARE FORBIDDEN TO MODIFY

THEM.
Content A description of the parameter details

RUN indicator
OFF:Stop;/ON:operating; /blinking slowly:Zero-frequency operation;/blinking quickly:Dc brake;
Command source indicator
OFF:Panel Run Command Channel;/ON:Terminal Run Command Channel;
blinking quickly:Communication run command channel;
Function
indicator blinking slowly:Analog runs command channel;
description FWD/REV( direction indicator):
ON: reverse rotation /OFF: forward rotation
TUNE/TC(Tuning/Torque control indicator): ON:
Torque control mode; /blinking slowly:Tuning status;
All the indicator lights are blinking slowly except the running indicator:Failure or alarm.

HZ: Frequency Unit; A: Current Unit; V: Voltage Unit; RMP (Hz + a) : Speed Unit;% (a + V) :
percentage.
Unit indicator
Note: The Unit Indicator Light Hz is always on when the main interface shows the output
description
frequency, and the unit indicator light Hz flashes slowly when the main interface shows the set
frequency
► :Shift key;
Press the shift key on the main interface to switch the display monitoring parameters
(F38.10 ~ F38.15 can set the monitoring parameters);
Press the shift key on the non-main interface, and the effective bits can be switched between
ones, tens, hundreds, thousands and tens thousands.
FUN/JOG:Multi-function keyMulti-function key (F37.00 can set its function) ;
ESC:Exit key / main interface entry, monitoring parameters and fault record, parameter group
Key Definition (F39 group) shortcut key;
ENTER:Enter/set key;
RUN:RUN key
STOP/RESET:STOP/RESET(F37.00 can set its functions);
▲:Increment key;
▼:Decrement key;
Long Press, increment key or decrement key in the main interface to quickly modify the relevant
parameters (F01.08 can set its modified parameters) .
28 06 、 List of parameters

2List of parameters
GroupF00 - basic functional parameters
Function
Number
Name SCOPE | [factory value] [ changes properties] and contents
(Communication
Address)
Rated power
F00.00 (0.4 ~ 999.9)[ model setting (KW)]〖★〗〖☆〗
of ozone
(0000H) Note: CAN NOT BE INITIALIZED
power supply
0~2|【0】〖√〗
Run 0:Panel Run Command Channel(Command source indicator is OFF)
F00.01 command
1:Terminal Run Command Channel(Command source indicator is ON)
(0001H) channel
selection 2:Communication run command channel(Command source indicator is
blinking quickly)
0~1|【0】〖×〗0:
F00.02
Stop Mode Deceleration Stop
(0002H)
1: Free stop
0~1|【0】〖×〗
0:invalid
1:effective
When the power is switched on after power failure, if the starting conditions
F00.03 Power cut are met, the ozone power supply will automatically run in accordance with
(0003H) restart setting the set mode after waiting for the time defined by F03.09.
Starting conditions: the starting time after power failure is set to 1 or 2.
Before power failure, it is in the running state and there is no stop
command. There is no stop command during the waiting time after power
failure.
Wait time for
F00.04
power failure 0.0~100.0|【5.0Sec.】〖√〗
(0004H)
to restart
F01-Frequency function parameters
Function
Number
Name SCOPE | [factory value] [ changes properties] and contents
(Communication
Address)
0~7|【1】〖√〗
0:frequency panel potentiometer given (only valid for panel with
potentiometer)
1:Digital frequency given1
Frequency 2:Digital frequency given2(Retention)
F01.00
source
(0100H) 3:Frequency communication given1(Absolute Value)(Retention)
selection
4:Frequency communication given2(Percentage)(Retention)
5:Frequency AI 1Analog given(0~10V/20mA)
6:Frequency AI 2Analog given(0~20mA)
7:Frequency pulse given(0~100KHZ)(Retention)
Frequency
F01.01
source digital 200~〖F01.04〗|【1000Hz】〖√〗
(0101H)
setting
panel▲/▼Ke 〖F01.02〗Pane▲/▼Keys、Encoder adjustment contro(
l H):0000~011B|
F01.02 ys 、 Encoder 【0111】〖√〗
(0102H) adjustment 〖F01.03〗TerminalUP/DOWNadjustment control(H) :0000~011B|
control(H) 【0111】〖√〗

LEDBit:Adjust valid channel selection


0:frequency panel potentiometer given (only valid for panel with
potentiometer)
Terminal 1:Digital frequency given1
F01.03 UP/DOWNadj 2:Digital frequency given2(Retention)
(0103H) usting control 3:Frequency communication given1(Absolute Value)(Retention)
(H) 4:Frequency communication given2(Percentage)(Retention)
5:Frequency AI 1Analog given(0~10V/20mA)
6:Frequency AI 2Analog given(0~20mA)
7:Frequency pulse given(0~100KHZ)(Retention)
8:Torque digital setting(Retention)
VL2900 series of high-performance Ozone Power Simple Manual 2 9

9:PIDNumber set point


A:Voltage Digital given(Retention) B:
Proportional linkage coefficient
LED ten's digit:Shut down. KEEP IT SET0:SHUTDOWNNOT
MAINTAINED
1:Stop Hold
LED Hundred's digit:Power off storage Settings
0:Power off and no storage
1:Power down storage
LED Thousand bit:Retention
When the effective channel selection of LED bit adjustment changes, the
panel▲/▼key、encoder or terminal UP/DOWNThe modified value is reset
to zero。
Downtime is defined as the presence of a running status panel▲/▼key、
encoder or terminal UP/DOWNThe modified value remains valid after the
outage,While the stop is not maintained,After the machine is stopped, the
modification made in this running state will be lost。
Power-down storage refers to the on-state Panel▲/▼key 、 encoder or
terminalUP/DOWNThe modified value is automatically stored after power
off,The next power-up will still be on,If the power is lost without storage, it
will lose the modification made after the power is cut off。
200~8000|【8000Hz】〖×〗
0.4KW ~ 2.2KW 200~10000|【10000Hz】〖×〗
3.0KW ~ 5.5KW 200~ 8000|【 6000Hz】〖×〗
7.5KW ~ 18.5KW 200~ 8000|【 4000Hz】〖×〗
Maximum
F01.04 22.0KW ~ 55.0KW 200~ 8000|【 3000Hz】〖×〗
output
(0104H) 75.0KW ~ 250.0KW 200~ 4000|【 2000Hz】〖×〗
frequency
280.0KW ~1100.0KW 200~ 2000|【 1000Hz】〖×〗
The maximum output frequency is the maximum allowed output frequency
of the ozone power supply, is the basis for calculating the acceleration and
deceleration time.
F01.05 Frequency
(0105H) rise time 0.10~600.00|【10.00 (Sec.)】〖√〗
Set the output frequency from 0 to the maximum frequency rise time, or set
F01.06 Frequency the output frequency from the maximum frequency to 0 down time.
(0106H) drop time
Group F02 ~ group F12 - retention parameter group
Function
Number
Name SCOPE | [factory value] [ changes properties] and contents
(Communication
Address)
F13 group - ozone power supply special parameters
Function
Number
Name SCOPE | [factory value] [ changes properties] and contents
(Communication
Address)
0~3|【1】〖√〗
0:Panel potentiometer given(100% corresponding【F13.02】)
F13.00 Voltage-given
1:Voltage Digital given
(0D00H) Channel
2:AI1(100% corresponding【F13.02】)
3:AI2(100% corresponding【F13.02】)
Digital
F13.01 0.0~【F13.02】|【0.0V】〖√〗
Voltage
(0D01H) Set the output voltage of ozone power supply.
Setting
F13.02 Voltage Limit 0.0~Ue|【Ue×50%】〖√〗
(0D02H) Level This parameter sets the maximum output voltage of ozone power supply
F13.03 Voltage rise
0.10~600.00|【10.00Sec.】〖√〗
(0D03H) time
F13.04 Voltage drop
0.10~600.00|【10.00Sec.】〖√〗
(0D04H) time
F13.05
Retention 50.0~200.0|【100.0%】〖√〗
(0D05H)
30 06 、 List of parameters

0~1|【0】〖√〗0:
F13.06 Working
Constant voltage output
(0D06H) mode
1:Constant current output
0~3|【1】〖√〗
0:Panel potentiometer given(100% corresponding to the rated current of
Ozone Power Supply)
F13.07 Current given
1:Current digital given(100% corresponding to the rated current of Ozone
(0D07H) channel
Power Supply)
2:AI1(100% corresponding to the rated current of Ozone Power Supply)
3:AI2(100% corresponding to the rated current of Ozone Power Supply)
F13.08 Digital current
0.0~100.0%|【0.0%】〖√〗
(0D08H) setting
Current 0.0~30.0%|【5.0%】〖√〗
F13.09
adjustment The current adjustment deviation is the percentage of the given value of the
(0D09H) deviation relative current
Current 0~1|【0】〖√〗
F13.10
detection 0:invalid 1:
(0D0AH)
selection effective
F13.11 Current
0.0~100.0%|【90.0%】〖√〗
(0D0BH) detection level
Current
F13.12
detection 0.0~60.0|【5.0Sec.】〖√〗
(0D0CH)
delay time
0~1|【0】〖√〗
F13.13 Retention
0:invalid
(0D0DH) parameter
1:effective
F14 - analog and pulse input parameters
Function
Number
Name SCOPE | [factory value] [ changes properties] and contents
(Communication
Address)
AI1 minimum 0.00~10.00|【0.10V】〖√〗
F14.00
input voltage Set The minimum input voltage of Terminal AI1. When current signal is
(0E00H)
(current) selected, 0.00 v means 0.00 mA, 10.00 v means 20.00mA.
AI1 minimum 0.0~100.0|【0.0%】〖√〗
F14.01 input The percentage of the actual physical quantities corresponding to the
(0E01H) corresponding minimum input voltage of Terminal AI1.Above the corresponding set out of
setting its scope to take its critical value.
AI1 maximum 0.00~10.00|【10.00V】〖√〗
F14.02
input voltage Set the maximum input voltage of terminal AI1. When the current signal is
(0E02H)
(current) selected, 0.00V represents 0.00mA, and 10.00V represents 20.00mA.
AI1 maximum 0.0~100.0|【100.0%】〖√〗
F14.03 input The percentage of the actual physical quantities corresponding to the
(0E03H) corresponding maximum input voltage of Terminal AI1. Above the corresponding set out of
setting its scope to take its critical value.
F14.04 AI1 input
0.00~10.00|【0.10Sec.】〖√〗
(0E04H) filtering time
AI2 minimum 0.00~10.00|【0.10V】〖√〗
F14.05
input voltage Set the minimum input voltage of terminal AI2. When the current signal is
(0E05H)
(current) selected, 0.00V represents 0.00mA, and 10.00V represents 20.00mA.
AI2 minimum 0.0~100.0|【0.0%】〖√〗
F14.06 input Set the percentage of the actual physical quantity when terminal AI2 inputs
(0E06H) corresponding the minimum input voltage.When the above corresponding setting exceeds
setting its range, its critical value is taken.
AI2 maximum 0.00~10.00|【10.00V】〖√〗
F14.07
input voltage Set the maximum input voltage of terminal AI2. When the current signal is
(0E07H)
(current) selected, 0.00V represents 0.00mA, and 10.00V represents 20.00mA.
AI2 maximum 0.0~100.0|【100.0%】〖√〗
F14.08 input Set the percentage of the actual physical quantity when terminal AI2 inputs
(0E08H) corresponding the maximum input voltage.When the above corresponding setting
setting exceeds its range, its critical value is taken.
VL2900 series of high-performance Ozone Power Simple Manual 31

F14.09 AI2 input


0.00~10.00|【0.10Sec.】〖√〗
(0E09H) filtering time
F15 group - analog and pulse output parameters
Function
Number
Name SCOPE | [factory value] [ changes properties] and contents
(Communication
Address)
0~99|【0】〖√〗
F15.00 AO1 output
For more options, see:《Table 1:Monitor parameter variable comparison
(0F00H) selection
table》
0~99|【0】〖√〗
F15.01 AO2 output
For more options, see:《Table 1:Monitor parameter variable comparison
(0F01H) selection
table》
F15.02 AO1 minimum 0.00~10.00| 【 0.00V 】 〖 √ 〗
(0F02H) output AO1Minimum output voltage of the terminal
0.0~100.0|【0.0%】〖√〗
AO1 minimum The percentage of the physical quantity corresponding to the minimum
F15.03 output
output of the AO1 terminal,100.0% of the corresponding physical
(0F03H) corresponding
quantity quantity:For more options, see:《Table 1:Monitor parameter variable
comparison table》
AO1
F15.04 0.00~10.00| 【 10.00V 】 〖 √ 〗
maximum
(0F04H) Maximum output voltage of AO1 terminal
output
AO1 0.0~100.0|【100.0%】〖√〗
maximum The percentage of the physical quantity corresponding to the maximum
F15.05 output of the AO1 terminal,100.0% of the corresponding physical
output
(0F05H)
corresponding quantity:For more options, see:《Table 1:Monitor parameter variable
quantity comparison table》
F15.06 AO1 output
0.00~10.00|【0.10Sec.】〖√〗
(0F06H) filtering time
F15.07 AO2 minimum 0.00~10.00|【0.00V】〖√〗
(0F07H) output Minimum output voltage of AO2 terminal
0.0~100.0|【0.0%】〖√〗
AO2 Minimum The percentage of the physical quantity corresponding to the minimum
F15.08 output
output of the AO2 terminal,100.0% of the corresponding physical
(0F08H) corresponden
quantity:For more options, see:《Table 1:Monitor parameter variable
ce
comparison table》
AO2
F15.09 0.00~10.00|【10.00V】〖√〗
maximum
(0F09H) Maximum output voltage value of AO2 TERMINAL
output
AO2 0.0~100.0|【100.0%】〖√〗
Maximum The percentage of the physical quantity corresponding to the maximum
F15.10 output of the AO1 terminal,100.0% of the corresponding physical
output
(0F0AH)
corresponden quantity:For more options, see:《Table 1:Monitor parameter variable
ce comparison table》
F15.11 AO2Output
0.00~10.00|【0.10Sec.】〖√〗
(0F0BH) filtering time

Schedule 1: comparison table of monitor parameter variables


Note: monitor variables do not take direction into account
Serial
Monitor parameter variables 100.0%Full scale value
Number
0 No output -
1 Output frequency (before slip compensation) Maximum frequency
2 Output frequency (after slip compensation) Maximum frequency
Maximum frequency*60/Motor(Retention)Polar
3 Motor (Retention) speed
Logarithm
4 output current 250%*Ozone power supply rated current
5 output torque(Retention) Digital setting of corresponding upper torque limit
32 06 、 List of parameters

6 Output Voltage Motor(Retention)nominal voltage


7 Output Power 3*Motor(Retention) rated power
Equipment Temperature
8 Temperature 1 and temperature 2 100.0℃
Take a higher value
220V type:500V
9 Bus Voltage
380V type:1000V
10 Set frequency Maximum frequency
Maximum frequency*60/Motor(Retention)Polar
11 Speed Instruction(Retention)
Logarithm
12 Torque Instruction(Retention) 300% rated torque
13 Target Frequency Maximum frequency
Maximum frequency*60/Motor(Retention)Polar
14 Speed regulator deviation(Retention) Logarithm
15 Speed governor output(Retention) 300.0%
16 Process PID set 100.0%
17 Process PID Feedback 100.0%
18 Process PID Absolute deviation(Retention) 100.0%
19 Process PID Output 100.0%
20 AI1 input 10.00V(20.00mA)
21 AI2 input 10.00V(20.00mA)
22 Communication given analog quantity 100.0%
23 Communications GIVEN PULSE 100.0%
24 External pulse input frequency Maximum input frequency of external pulse
25 Current linear velocity (Fin calculation) Maximum permissible linear velocity
26 Accumulated length (linear velocity) Maximum comptroller
27 Counter value Counter period value
28 Timer value Timer period value
29~99 Retention -

Group F16 - switching input parameters


Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)
0~99|【0】〖√〗
F16.00 Input terminal X1
See detailed functional options:《Table 2:Multi-function input terminal comparison
(1000H) function
table》
0~99|【0】〖√〗
F16.01 Input terminalX2
See detailed functional options:《Table 2:Multi-function input terminal comparison
(1001H) function
table》
0~99|【0】〖√〗
F16.02 Input terminalX3
See detailed functional options:《Table 2:Multi-function input terminal comparison
(1002H) function
table》
0~99|【0】〖√〗
F16.03 Input terminalX4
See detailed functional options:《Table 2:Multi-function input terminal comparison
(1003H) function
table》
0~99|【0】〖√〗
F16.04 Input terminalX5
See detailed functional options:《Table 2:Multi-function input terminal comparison
(1004H) function
table》
0~99|【0】〖√〗
F16.05 Input terminalX6
See detailed functional options:《Table 2:Multi-function input terminal comparison
(1005H) function
table》
Input terminalX7 0~99|【1】〖√〗
F16.06 function See detailed functional options:《Table 2:Multi-function input terminal comparison
(1006H)
(X7-FWD) table》
Input terminalX8 0~99|【0】〖√〗
F16.07 function See detailed functional options:《Table 2:Multi-function input terminal comparison
(1007H)
(X8-REV) table》
VL2900 series of high-performance Ozone Power Simple Manual 33

0000~1111|【0000】〖√〗
LED unit's digit:X1 Logical Setting
LED ten's digit:X2 Logical Setting
Input terminal LED Hundred's digit:X3 Logical Setting
F16.08 Effective status
(1008H) LED Thousand's digit:X4 Logical Setting
setting 1(H) 0: represents the positive logic, that is, the corresponding terminal and the public
connection is valid, disconnect is invalid
1: Represents the anti-logic, that is, the corresponding terminal and the public
connection invalid, disconnect valid
0000~1111|【0000】〖√〗
LED unit's digit:X5 Logical Setting
LED ten's digit:X6 Logical Setting
Input terminal LED Hundred's digit:X7 Logical Setting
F16.09 Effective status
(1009H) LED Thousand's digit:X8 Logical Setting
setting2(H) 0: represents the positive logic, that is, the corresponding terminal and the public
connection is valid, disconnect is invalid
1: Represents the anti-logic, that is, the corresponding terminal and the public
connection invalid, disconnect valid
F16.10 Input terminal
0~200|【20ms】〖√〗
(100AH) filtering time

0~3|【0】〖√〗
Terminal control 0:Two-wire control mode1
F16.11 mode 1:Two-wire control mode2
(100BH)
(FWD、REV、SIn) 2:Three-wire control mode1
3:Three-wire control mode2
0~1|【0】〖√〗
0:The terminal running command is invalid when power on(the terminal is first
Power on disconnected and then closed)
F16.12 terminal running 1:The terminal running command is valid when the power is on.
(100CH) protection The given signal of the two-wire mode operation instruction is the level signal.
selection When the terminal is in the effective state, the ozone power supply will start
automatically.In a system that does not want to be powered up by itself, the
terminal operation command can be selected to be invalid when powered up.
UP/DOWN
F16.13 Terminal
10~1000|【100Hz/S】〖√〗
(100DH) frequency
modification rate

Attached table 2: multi-function input terminal function comparison table


Serial Serial
Number function Number function
0 Control end idle 1 Running forward(FWD)
2 Reverse run(REV) 3 Three-wire operation control(SIn)
4 Forward turning point control 5 Reverse point control
6 Free stop control 7 Fault reset signal
8 External device 1 fails 9 External device 2 fails
10 External equipment 3 failure 11 External equipment 4 failure
12 Emergency shutdown input 13 Increasing frequency (UP)
14 Decreasing frequency(DOWN) 15 UP/DOWN Terminal frequency reset
16 Auxiliary frequency reset 17 Frequency source A switches to B
18 Frequency source A switches to A+B 19 Switching frequency source A to a-b
20 Multispeed option 1 21 Multispeed option 2
22 Multispeed option 3 23 Multispeed option 4
24 Acceleration and deceleration time selection1 25 Acceleration and deceleration time selection2
26 No acceleration and deceleration 27 Overexcitation deceleration (flux braking)
28 Run command channel selection 1 29 Run command channel selection 2
30 Run the command to switch to the keyboard 31 Run the command to switch to the terminal
32 Run command to switch to communication 33 Prohibit Operating Instructions
34 PID Control input 35 PID Suspension control
36 PID Set the increment(Retention) 37 PID Set decrement (Retention)
34 06 、 List of parameters

38 Terminal PID setting reset(Retention) 39 PID Number Given Selection 1


40 PID Number Given Selection 2 41 Retention
pendulum frequency control Suspension
42 Swing frequency control input 43 (Retention)
44 Swing Frequency Control Reset 45 PLC Control input
46 PLC Suspension control(Retention) 47 PLC Control reset
48 Counter trigger signal 49 Counter input signal
50 Counter reset signal 51 Counter reset signal
52 Timer trigger signal 53 Timer reset signal
54 The timer clears the signal 55 Pulse frequency input (valid for DI4 only)
56 Length count input (valid for DI4 only) 57 Cumulative length clearing
V-F
V-FThe separation voltage setting is The separation voltage setting decreases
58 increasing(Retention) 59 (Retention)
60 Terminal voltage reset(Retention) 61 Speed and torque control switching
62 Torque control prohibited 63 Torque number given selection1
64 Torque number given selection2 65 Retention
66 Torque upper limit selection1 67 Torque upper limit selection 2
68 Retention 69 Zero servo input
70 Droop control input 71 Water shortage fault input
72 Temperature overheating fault input 73~99 Retention

F17 group - switch quantity output parameter


Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)
Open collector 0~99|【0】〖√〗
F17.00
Output terminal See detailed functional options:《Table 3:Multi-function output terminal
(1100H)
Y1 function comparison table》
Open collector 0~99|【0】〖√〗
F17.01 Output terminal
(1101H) Y2 function See detailed functional options:《Table 3:Multi-function output terminal
(keep) comparison table》
0~99|【4】〖√〗
F17.02 Programmable
See detailed functional options:《Table 3:Multi-function output terminal
(1102H) relay R1 function
comparison table》
0~99|【0】〖√〗
F17.03 Programmable
See detailed functional options:《Table 3:Multi-function output terminal
(1103H) relay R2 function
comparison table》
0000~1111|【0000】〖√〗
LED unit's digit :Y1Logical Setting
LED ten's digit :Y2Logical Setting
The output
F17.04 terminals LED Hundred's digit :R1Logical Setting
(1104H) Effective state LED Thousand's digit :R2Logical Setting
setting (H) 0: Represents Positive Logic, that is, the output terminal is effectively connected
to the common terminal, the disconnection is invalid.
1: Represents the anti-logic, that is, the output terminal is not connected to the
common terminal, the disconnection is valid.
0.0~100.0|【0.0Sec.】〖√〗
F17.05 Y1 output delay
(1105H) time This function code defines a delay between a change in the state of the Y 1
output and a change in the y 1 output.
0.0~100.0|【0.0Sec.】〖√〗
F17.06 Y2 output delay
(1106H) time This function code defines a delay between a change in the state of the Y 2
output and a change in the y 2 output.
0.0~100.0|【0.0Sec.】〖√〗
F17.07 R1 output delay
(1107H) time This function code defines the delay between a change in the R1 state of the
relay and a change in the output of the relay.
0.0~100.0|【0.0Sec.】〖√〗
F17.08 R2 output delay
(1108H) time This function code defines the delay between a change in the R2 state of the
relay and a change in the output of the relay.
VL2900 series of high-performance Ozone Power Simple Manual 35

Attached table 3: multi-function output terminal comparison table


Serial
Serial Numbe
Number function r function
0 no output 1 ready
2 Running forward 3 Reverse run
4 fault output 5 The alarm output
6 Fault or alarm output 7 Zero-frequency operation
8 The non-zero run 9 Accelerated operation
10 Decelerate Operation 11 Constant speed operation
12 Limit loss in quick action 13 In overpressure stall action
14 Undervoltage downtime 15 In the upper limit of swing frequency
In the lower limit of the pendulum
16 frequency 17 Torque limitation (retention)
18 Overtorque detection (retention) 19 Undertorque detection (retention)
20 Energy consumption braking action 21 Dc braking action
Deceleration overexcitation action
22 (flux braking) 23 Monitor 1 output
24 Monitor 2 output 25 Monitor 3 output
The counter detection value reaches the
26 Monitor 4 output 27 output
The counter cycle value reaches the The timer detection value reaches the
28 output 29 output
The timer cycle value reaches the
30 output 31 Length to output
The operation of simple PLC in the
current stage is completed (0.5s Simple PLC current cycle operation
32 pulse) 33 completed (0.5s pulse)
Simple PLC complete cycle Complete all cycle operation of simple
34 operation (0.5s pulse) 35 PLC (continuous level)
36 PID In sleep 37 Frequency arrival signal (FAR)
38 Processing frequency pump output 39 One tow two (motor (retained)1)
39~
40 One tow two (motor (retained)2) 99 Retention

Group F18 ~ F23 - retention parameter group(Retention)


Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)
F24 group - protection function parameters
Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)
0~1|【0】〖√〗
0: automatic control
1: the electrification process has been running
F24.00 Automatic control means that the internal temperature detection
Cooling fan control
(1800H) program is automatically started during the operation of the ozone power
supply, and the operation and stop of the fan are determined according
to the module temperature status and the operation status of the ozone
power supply.
0~100|【0】〖√〗
When set to 0, it means that the automatic fault reset function is off;
Frequency of when set to 100, it means that the automatic fault reset function has no
F24.01
automatic fault frequency limit, that is, countless times.When the fault self-reset function
(1801H)
reset is effective, if the ozone power supply is in the running state before the
fault, the ozone power supply will start up with the speed tracking when
the fault is reset.
36 06 、 List of parameters

0.1~10.0|【1.0Sec.】〖√〗
F24.02 Fault automatic
(1802H) reset interval time The shortest interval from the current fault self-reset to the next fault
self-reset.
F25 group - advanced functional parameters (retained)
Group F26 - communication function parameters
Function Number
SCOPE | [factory value] [ changes properties] and
(Communication Name
contents
Address)

0000~1551|【0030】〖×〗
LED units' digit:Protocol selection
0:MODBUS
1:Customizing(Retention)
LED Ten' digit :Communication baud rate setting 0:
1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
Communication 6:79600BPS(Retention)
F26.00
(1A00H) configuration(H) 7:115200BPS(Retention)
LED Hundred's digit:The data format
0:1-bit initiation bit、8-bit data bits、1 bit stop bit、No check for RTU
1:1-bit initiation bit、8-bit data bits、1 bit stop bit、Parity check for RTU
2:1-bit initiation bit、8-bit data bits、1 bit stop bit、Odd parity check for
RTU
3:1-bit initiation bit、8-bit data bits、2 bit stop bit、No check for RTU
4:1-bit initiation bit、8-bit data bits、2 bit stop bit、Parity check for RTU
5:1-bit initiation bit、8-bit data bits、2 bit stop bit、Odd parity check for
RTU
LED Thousand's digit:
0:The write operation has a response
1:Write operation no response

0~247|【1】〖×〗
0:master station 1~
247:Slave station
This parameter is used for serial port communication, set the address of
F26.01 Local machine this ozone power supply.0 is the broadcast address. When set to the
(1A01H) address broadcast address, only the broadcast command can be sent without
answering the host computer.1 ~ 247 slave address, set as slave
address, in the communication process, the machine only with the native
address (or broadcast address) consistent data frame to receive
instructions, and reply frame (broadcast address instruction does not
respond).
0~1000|【5ms】〖×〗
When the ozone power supply is the main engine, this is the
F26.02 Local reply (send) transmission delay time, the minimum delay time is 30ms, if the set
(1A02H) delay value is less than 30ms, it is 30ms.When the ozone power supply is the
slave machine, this is the response delay time, and the actual response
delay time is not less than the transmission time of 3.5 characters.

0000~0022|【0010】〖×〗
LED units' digit:Communication abnormal detection selection
0:No abnormal communication detected
1:Any state is checked 2:
Communication Run status detection only
F26.03 LED Ten' digit:Communication abnormal action selection
abnormal action
(1A03H)
selection 0:Communication failures(E-30)Free shutdown 1:
Alarm (A-30) and maintain the status quo
2:Alarm (a-30) and stop the machine according to the set stop mode
LED Hundred's digit:Retention
LED Thousand's digit:Retention

Communication 0.1~100.0Sec.|【10.0】〖√〗
F26.04
anomaly After the time delay is determined, the normal communication is still
(1A04H)
determination time
unable and the abnormal communication is handled.
Group F27 ~ Group F36-reserved parameter of Special Function
VL2900 series of high-performance Ozone Power Simple Manual 37

Group F37 - panel related parameters


Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)

0x0000~0x0144|【0x0140】〖×〗
LED units' digit :M-FUNC Key function selection
0:JOG(Positive inching turningt) 1:
JOG(reverse inching turning)
2:Reverse operation
3:Forward and Reverse Switching
4:Clear Panel▲/▼key Set frequency
LEDTen' digit:STOP/RSTKey function selection
F37.00 Panel function key
(2500H) setting (H) 0: only valid for keyboard control
1: effective for both keyboard and terminal control
2: effective for both keyboard and communication control
3: effective for both keyboard and analog command control(Retention)
4: works for all control modes
LED Hundred's digit :STOP+RUNKey function selection 0:
invalid
1:Free Parking
LED Thousand's digit:Retention

Panel▲/▼、
F37.01
Encoder 10~1000|【100】〖√〗
(2501H)
Adjustment Rate
0~2|【1】〖√〗
Panel
F37.02 0: protect action and stop freely
communication
(2502H) 1. Alarm and maintain the status quo
abnormal action
2. Alarm and stop according to the set stop mode
Panel
F37.03 communication 0.0~100.0|【1.0Sec.】〖√〗
(2503H) timeout checkout Note: do not do panel timeout detection when set to 0.0
time
Group F38-system management parameters
Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)
0~65535|【0】〖√〗0:
No Password Protection
1~65535:Password protected,Group F00 ~ F39 parameters need to
verify the password to view and modify
Password setting: ENTER this parameter without password, the
interface displays "00000", set the password value (non-zero) and press
"ENTER", the interface prompts "AgAIn", set the password value AgAIn
and press "ENTER" to ENTER.If the setting values are the same, the
interface prompts "End", then the password is set successfully, and the
F38.00
User Password password protection will take effect immediately;If the Settings entered
(2600H)
twice are different, the interface prompts "Error", then the password
setting fails and needs to be reset.
Password unlock: enter this parameter with password status, the
interface displays "----", enter the password value set last time.If the
password matches, the interface jumps to the next parameter, and the
password is unlocked successfully;If the password does not match, the
interface will prompt "Error", and the password unlock fails, and shall be
unlocked again.
Note: CAN NOT BE INITIALIZED
0~65535|【0】〖√〗0:
No Password Protection
1 ~ 65535: F0.00 REQUIRES PASSWORD VERIFICATION TO BE
F38.01 MODIFIED.
Agent password
(2601H) Password settings and password unlock operation the same user
password (F38.00) , but the password unlock 10 minutes will be
automatically locked.
Note: CAN NOT BE INITIALIZED
38 06 、 List of parameters

0 ~ 65535| 【 0 】 〖 √ 〗 0 :
No Password Protection
F38.02 Run limit function 1 ~ 65535: F38.03, F38.04 need to verify password to view and modify.
(2602H) password Password settings and password unlock operations with the same user
Password (F38.00)
Note: CAN NOT BE INITIALIZED
0~1|【0】〖√〗
0: ban
1: restricted operation
F38.03 Run limit function The operation time is calculated from the effective start of the limited
(2603H) selection operation. When the measured operation time is greater than the set
operation limit time, the ozone power supply enters the operation limit
time and reaches the protection, indicating e-21, which can be contacted
with the direct supplier.
Note: CAN NOT BE INITIALIZED
0.0~6000.0|【10.0h】〖√〗
The operation time is calculated from the effective start of the limited
F38.04 Operating limit operation. When the measured operation time is greater than the set
(2604H) time operation limit time, the ozone power supply enters the operation limit
time and reaches the protection, indicating e-21, which can be contacted
with the direct supplier.
Note: CAN NOT BE INITIALIZED

0~2|【0】〖√〗
LCD keyboard 0: Chinese
F38.05
Display language 1: English
(2605H)
selection 2: keep
Note: CAN NOT BE INITIALIZED

0~3|【1】〖√〗
LEDunits' digit:Parameter display mode selection (reserved)
LEDTen' digi:Main interface monitoring parameter cycle display
parameter selection0~1|【0】〖√〗
F38.06
Display mode 0: Do Not Cycle (the main interface only shows a monitoring parameters,
(2606H)
selection (H) need to show other parameters can be switched through the shift key)
1: AUTOMATIC LOOP (F38.10 ~ F38.12 or F38.13 ~ F38.15 set by the
monitoring parameters loop display, each parameter display 5 seconds
to switch to the next display parameters)
0~2|【0】〖√〗
0: All parameters are allowed to be modified (some parameters can not
F38.07 be modified at run time)
Write protection 1: only allow to change the frequency setting F01.06, F01.07
(2607H)
2: All parameters ARE FORBIDDEN TO BE MODIFIED
The above restrictions are not valid for this function code and User
Password
0~4|【0】〖×〗
0: No Operation
1: User Parameter Initialization 1
F38.08 Parameter
2: User Parameter Initialization 2
(2608H) initialization
3: User Parameter Initialization 3(reserved)
4: clear the fault record (the contents of the fault record are reset to
F39.76 ~ F39.99)
VL2900 series of high-performance Ozone Power Simple Manual 3 9

0~3|【0】〖×〗
0: no operation
1: parameters are uploaded to the panel
2: all function code parameters are downloaded to the ozone power
supply
3: all function code parameters except the motor (reserved) parameters
are downloaded to the ozone power supply
When set to 1 and confirmed, the ozone power will upload all the
function code set values between F00.00 and F38.15 in the control
panel to the memory of the operation panel for storage.
After setting it to 2 and confirming, ozone power will download all the
function code set values between F00.00 and F38.15 in the operation
panel to the internal control board for storage.
After setting it to 3 and confirming, ozone power will download all the
function code set values between F00.00 and F38.15 in the operation
F38.09 Parameter copy panel to the internal control board for storage.(motor parameters of F04
(2609H) function group and F05 group are not downloadable)
Note:
1) for the operation panel, the parameters must be uploaded first,
otherwise the memory of the operation panel is empty;After a parameter
upload operation, the function code parameters will always be saved in
the memory of the operation panel.
2) before the operation of the download as a parameter to ozone power
supply, power of ozone will check the integrity of the function code within
the operation panel parameters and version information, if the memory is
empty, or parameter is not complete, or parameter version does not
accord with the current ozone power supply software version (different)
function code number, all can not download the parameters, and prompt
copy error information;
3) after parameter download, the parameters in the memory of the
operation panel still exist, so repeated copies of multiple ozonepower
sources can be performed.
0~99|【9】〖√〗
This parameter defines one of the monitoring parameters that can be
displayed on the main interface under the running state of ozone power
supply. For example, the default setting is 4, which means that
Operation status
F38.10 monitoring parameters and fault record group (F39 group) no. 4
monitoring
(260AH) parameter F39.04 "output frequency" can be displayed. The next
parameter 1
monitoring parameter can be displayed through the shift key on the main
interface.
Detailed functional options can be found in <F39 Group - Monitoring
Parameters and Fault Records>
0~99|【4】〖√〗
This parameter defines one of the monitoring parameters that can be
displayed on the main interface under the running state of ozone power
Operation status supply. For example, the default setting is 9, which means that
F38.11
monitoring monitoring parameters and fault record group (F39 group) no.9
(260BH)
parameter 2 parameter F39.9 "output voltage" can be displayed. The next monitoring
parameter can be displayed under the main interface by the shift key.
Detailed functional options can be found in <F39 Group - Monitoring
Parameters and Fault Records>
0~99|【10】〖√〗
This parameter defines one of the monitoring parameters that can be
displayed on the main interface under the running state of ozone power
supply. For example, the default setting is 10, which means that the
Operation status
F38.12 monitoring parameters and fault record group (F39 group) no.10
monitoring
(260CH) parameter F39.10 "output current" can be displayed. The next
parameter 3
monitoring parameter can be displayed under the main interface through
the shift key.
Detailed functional options can be found in <F39 Group - Monitoring
Parameters and Fault Records>
0~99|【37】〖√〗
This parameter defines one of the monitoring parameters that can be
displayed on the main interface under the shutdown state of ozone
power supply. For example, the default setting is 3, which means that
Downtime
F38.13 monitoring parameters and fault record group (F39 group) no. 3
monitoring
(260DH) parameter F39.03 "target frequency" can be displayed. The next
parameter 1
monitoring parameter can be displayed under the main interface through
the shift key.
Detailed functional options can be found in <F39 Group - Monitoring
Parameters and Fault Records>
40 06 、 List of parameters

0~99|【2】〖√〗
This parameter defines one of the monitoring parameters that can be
displayed on the main interface under the shutdown state of ozone
Downtime power supply. For example, the default setting is 16, which means the
F38.14
monitoring monitoring parameters and fault record group (F39 group) no.16
(260EH)
parameter 2 parameter F39.16 "input voltage" can be displayed. The next monitoring
parameter can be displayed under the main interface by the shift key.
Detailed functional options can be found in <F39 Group - Monitoring
Parameters and Fault Records>
0~99|【17】〖√〗
This parameter defines one of the monitoring parameters that can be
displayed on the main interface under the shutdown state of ozone
Downtime power supply. For example, the default setting is 17, which means that
F38.15
monitoring monitoring parameters and fault record group (F39 group) no.17
(260FH)
paramete 3 parameter F39.17 is "bus voltage". The next monitoring parameter can
be displayed under the main interface through the shift key.
Detailed functional options can be found in <F39 Group - Monitoring
Parameters and Fault Records>
F38.16 Panel software 1.00~99.99|【1.00】〖☆〗
(2610H) version number Note: CAN NOT BE INITIALIZED
F38.17 Control software 1.00~99.99|【1.00】〖☆〗
(2611H) version number Note: CAN NOT BE INITIALIZED
0.0~800.0|【0.0V】〖★〗〖×〗
This parameter is used for bus voltage correction. When the ozone
power supply is stopped, directly input the correct bus voltage value, that
is, the bus voltage correction is completed. After the correction is
F38.18 Bus voltage completed, this parameter will automatically reset to zero.
(2612H) correction Note: in the case of bus voltage correction, the correction will be
abandoned if the difference between the input correction bus voltage
value and the detected voltage value is greater than 50%. At this time,
there may be a hardware fault. Please correct after removing the
hardware fault.
Note: CAN NOT BE INITIALIZED
Group F39-monitoring parameters and failure records
Function Number
(Communication Name SCOPE | [factory value] [ changes properties] and contents
Address)
F39.00
Set frequencyA 0~8000|【0Hz】〖☆〗
(2700H)
Set
F39.01
frequencyB(Retent 0~8000|【0Hz】〖☆〗
(2701H)
ion)
Set frequency
F39.02
(combined 0~8000|【0Hz】〖☆〗
(2702H) frequency)
target frequency 0~8000|【0Hz】〖☆〗
F39.03
( frequency Monitor the final frequency set by the user and the target frequency of
(2703H)
order) operation of the ozone power supply.
The output
0~8000|【0Hz】〖☆〗
F39.04 frequency
(2704H) Monitor the output frequency of the Ozone Power Supply (excluding slip
(before slip
compensation) compensation).
output frequency
0~8000|【0Hz】〖☆〗
F39.05 (Retention)
(2705H) (after slip Monitor the output frequency of the Ozone Power Supply (including slip
compensation) compensation) .
Estimated 0~8000|【0Hz】〖☆〗
F39.06
frequency of The operating frequency of the motor as estimated by the monitoring
(2706H) Motor(Retention) program.
Measured 0~8000|【0Hz】〖☆〗
F39.07
frequency of Monitor the actual motor operating frequency measured by photoelectric
(2707H)
motor(Retention) encoder.
F39.08 Motor 0~60000|【0rpm】〖☆〗
(2708H) speed(Retention) Monitor the running speed of motor.
F39.09 0.0~1140.0|【0.0V】〖☆〗
output voltage
(2709H) Monitor the output voltage of ozone power supply.
F39.10 0.0~6000.0|【0.0A】〖☆〗
output current
(270AH) Monitor the output current of ozone power supply.
VL2900 series of high-performance Ozone Power Simple Manual 41

F39.11 torque -3000.0~3000.0|【0.0A】〖☆〗


(270BH) current(Retention) Monitor the torque current when the motor is running.
F39.12 flux current -3000.0~3000.0|【0.0A】〖☆〗
(270CH) (Retention) Monitor the excitation current of the motor during operation.
-300.0~+300.0|【0.0%】〖☆〗
F39.13 output torque
(270DH) (Retention) Monitor the percentage of the motor output torque relative to the rated
Torque.
-300.0~+300.0|【0.0%】〖☆〗
F39.14 output power
(270EH) (Retention) Monitor the percentage of the motor output power relative to the rated
power.
F39.15 Motor power factor -1.00~1.00|【0.00】〖☆〗
(270FH) (Retention) Monitor the power factor when the motor is running.
F39.16 0.0~1140.0|【0.0V】〖☆〗
input voltage
(2710H) Monitor input voltage of ozone power supply.
F39.17 0.0~2500.0|【0.0V】〖☆〗
Bus voltage
(2711H) Monitor DC bus voltage of ozone power supply.
0.00~10.00|【0.00V】〖☆〗
F39.18 Monitor the input voltage value of analog input 1. If the input is current, it
analog input AI1
(2712H) will be converted to voltage value.
Converted voltage value = input current 500 ohms
0.00~10.00|【0.00V】〖☆〗
F39.19 Monitoring analog input 2 input voltage value, if the input current is
analog input AI2
(2713H) converted to the voltage value.
Converted voltage value = input current 500 ohms
Pulse frequency
F39.20 0.00~100.00|【0.00kHz】〖☆〗
input
(2714H) Monitor external pulse input frequency.
(Retention)
F39.21 PID set value 0.0~100.0|【0.0%】〖☆〗
(2715H) (Retention) Monitor the target value set by PID.
PIDFeedback
F39.22 0.0~100.0|【0.0%】〖☆〗
value
(2716H) Monitor the actual PID feedback.
(Retention)
0.00~10.00|【0.00V】〖☆〗
F39.23 Monitoring analog output 1 output voltage value, if the output current is
Analog output AO1
(2717H) converted to the voltage value.
Converted voltage value = output current 500 ohms.
0.00~10.00|【0.00V】〖☆〗
F39.24 The monitoring analog outputs a voltage value of 2, which is converted
Analog output AO2
(2718H) to a voltage value if the output is current.
Converted voltage value = output current 500 ohms.
F39.25 Pulse frequency 0.00~100.00|【0.00kHz】〖☆〗
(2719H) output(Retention) Monitor pulse frequency of DO3 output.
F39.26 Terminal input 0000~00FF|【0000】〖☆〗
(271AH) status(H) illustration
F39.27 Terminal output 0000~000F|【0000】〖☆〗
(271BH) status(H) illustration
Ozone power
F39.28 supply operation 0000~FFFF|【0000】〖☆〗
(271CH) status1(H) illustration
Ozone power
F39.29 0000~FFFF|【0000】〖☆〗
supply operation
(271DH) status2(H) illustration
Ozone power
F39.30 0000~FFFF|【0000】〖☆〗
supply operation
(271EH) status3(H) illustration
Multi - segment
F39.31 speed (PLC)
0~15|【0】〖☆〗
(271FH) current segment
number(Retention)
F39.32 Current
0~60000|【0】〖☆〗
(2720H) count(Retention)
F39.33 Current time
0~60000|【0Sec.】〖☆〗
(2721H) value(Retention)
F39.34 Current length
0~60000|【0m】〖☆〗
(2722H) value(Retention)
42 06 、 List of parameters

F39.35 Operating Line


0.01~500.00|【0.00m/Sec.】〖☆〗
(2723H) Speed(Retention)
0.0~6000.0|【10.0h】〖√〗
F39.36 Running limits the When the operation restriction function is effective, the monitoring
(2724H) remaining time operation restriction remaining time is monitored; when the operation
restriction function is invalid, the monitoring value is 6000.0.
F39.37
Set voltage 0.0~Ue|【0.0V】〖☆〗
(2725H)
F39.38
feedback voltage 0.0~Ue|【0.0V】〖☆〗
(2726H)
F39.39 Set the current 0.0~100.0|【0.0%】〖☆〗
(2727H) The percentage Monitor the set current of ozone power supply in percentage.
F39.40 Set the current 0.0~6000.0|【0.0A】〖☆〗
(2728H) ampere Monitor the setting current of the ozone power supply in Amperes.
F39.41
Retention Monitoring parameters of special model(Retention)
~F39.68
F39.69 Module 0.0~125.0|【0.0℃】〖☆〗
(2745H) Temperature Monitor the real-time temperature of IGBT module.
F39.70 Radiator 0.0~125.0|【0.0℃】〖☆〗
(2746H) temperature Monitor the radiator temperature in real time.
Accumulative
F39.71
power on time of 0~65535|【0H】〖☆〗
(2747H)
the machine
Cumulative
F39.72
running time of the 0~65535|【0H】〖☆〗
(2748H) machine
F39.73 Fan cumulative
0~65535|【0H】〖☆〗
(2749H) running time
Cumulative power 0~60000|【0KWH】〖☆〗
F39.74
consumption Cumulative power consumption = cumulative power consumption (high)
(274AH)
(high) 1000+ cumulative power consumption (low)
F39.75 Cumulative power
0.0~999.9|【0.0KWH】〖☆〗
(274BH) consumption (low)
F39.76 0~99|【0】〖☆〗
First failure type
(274CH) Record the failure type of the previous second failure.
The first time it
0~8000|【0Hz】〖☆〗
F39.77 broke down
(274DH) Operating Record the operating frequency of the ozone power supply at the time of
frequency the previous second failure.
The first time it 0.0~6000.0|【0.0A】〖☆〗
F39.78
broke down Record the ozone power supply output current at the time of the
(274EH) The output current previous second failure.
The first time it 0.0~2500.0|【0.0V】〖☆〗
F39.79
broke down Record the DC bus voltage of the ozone power supply at the time of the
(274FH) Bus voltage previous second failure.
The first time it 0.0~125.0|【0.0℃】〖☆〗
F39.80
broke down Record the highest temperature (module temperature or radiator
(2750H) The temperature temperature) at the time of the previous second failure.
The first time it
broke down 0000~FFFF|【0000】〖☆〗
F39.81
Ozone power To record the time of the previous second failure Ozone power supply
(2751H)
supply operation operation status。
status1(H)
The first time it
0000~00FF|【0000】〖☆〗
F39.82 broke down
(2752H) Terminal input Record the input status of the ozone power supply terminal at the time of
state (H) the previous second failure.
The first time it
0000~000F|【0000】〖☆〗
F39.83 broke down
(2753H) Terminal output Record the output status of the ozone power supply terminal at thetime
state (H) of the previous second failure.

F39.84 Second failure 0~99|【0】〖☆〗


(2754H) type Record the type of failure for the previous failure.
From the second 0~8000|【0Hz】〖☆〗
F39.85
malfunction Record the operating frequency of the ozone power supply at the time of
(2755H)
running frequency the previous failure.
VL2900 series of high-performance Ozone Power Simple Manual 43

0.0~6000.0|【0.0A】〖☆〗
F39.86 Output current in
(2756H) the second fault Record the ozone power supply output current at the time of the
previous failure.
Bus voltage in 0.0~2500.0|【0.0V】〖☆〗
F39.87
case of second Record the DC bus voltage of the ozone power supply at the time of the
(2757H) failure previous failure.
0.0~125.0|【0.0℃】〖☆〗
F39.88 The temperature of
(2758H) the second failure Record the maximum temperature (module temperature or radiator
temperature) at the time of the previous failure.
From the Second
Malfunction 0000~FFFF|【0000】〖☆〗
F39.89 Ozone power To record the time of the last failure Ozone power supply operation
(2759H) supply operation status。
status1(H)
Terminal input 0000~00FF|【0000】〖☆〗
F39.90
status in case of Record the input status of the ozone power supply terminal at the time of
(275AH) second failure(H) the previous failure.
Terminal output 0000~000F|【0000】〖☆〗
F39.91 status in case of
(275BH) Record the output status of the ozone power supply terminal at the time
Second Failure(H) of the previous failure.
F39.92 Type of third 0~99|【0】〖☆〗
(275CH) failure Record the type of fault for the current fault.
The operating 0~8000|【0Hz】〖☆〗
F39.93
frequency of the Record the operating frequency of the ozone power supply at the current
(275DH) third failure time of failure.
0.0~6000.0|【0.0A】〖☆〗
F39.94 Output current in
(275EH) the Third Fault Record the output current of the ozone power supply at the current time
of failure.
0.0~2500.0|【0.0V】〖☆〗
F39.95 Bus Voltage at the
(275FH) third fault Record the DC bus voltage of the ozone power supply at the current
time of failure.
0.0~125.0|【0.0℃】〖☆〗
F39.96 The temperature of
(2760H) the third failure Record the maximum temperature (module temperature or radiator
temperature) at the time of the current failure.
The third time it
malfunctioned: 0000~FFFF|【0000】〖☆〗
F39.97 Ozone power To record the time of the current failureOzone power supply operation
(2761H) supply operation status。
status1(H)
Terminal input 0000~00FF|【0000】〖☆〗
F39.98 status in case of
(2762H) Record the input status of the ozone power supply terminal at the current
third failure(H) time of failure.
Terminal output 0000~000F|【0000】〖☆〗
F39.99 status at the third
(2763H) Record the output status of the ozone power supply terminal at the
failure(H) current time of failure.
VL2900 series of high-performance Ozone Power Simple Manual 44

07、Fault diagnosis and exception handling


7.1 Fault phenomena and countermeasures
When the ozone power supply is abnormal, the LED digital tube will display the corresponding fault function code and its
content. When the fault relay is running, the ozone power supply will stop output.
The possible failure types of VL2900 series ozone power supply are shown in table 7-2.In case of ozone power failure, the
user shall first check according to this table and record the failure phenomenon in detail.If you need technical services,
please contact our after-sales service and technical support department or our local offices and agents.

7.2 Fault record query


This series of ozone power supply has recorded the last three failure codes and operating parameters of the ozone
power supply in the event of failure, query these information to help find the cause of failure.
The fault information is all saved in the F39 group of monitoring parameters. Please enter the F39 group of parameters to
inquire the corresponding fault information.

7.3 Fault Reset


In case of ozone power failure, the following operations can be selected to restore normal operation:
(1) When the fault code is displayed, after confirming that it can be RESET, press the Stop / Reset key.
(2) After any terminal of X1 ~ X8(F16.00 ~ F16.07) is set as a fault reset signal (No. 7 function) , the input terminal can be
reset after it is closed with the COM terminal.
(3) Cut The power and put it back on.

Attention :

(1) the cause of the failure must be thoroughly checked and removed before resetting, otherwise the ozone power supply
may be permanently damaged.
(2) if the device can not be reset or fails again after the reset, the reason should be checked. Continuous reset will
damage the ozone power supply.
(3) the protection action of overload and overheat should be reset 5 minutes later.

Form 7-1 Alarm code and alarm elimination


Alarm alarm
Possible Cause Solutions
code instructions
Warning of 1. Reduce the load or change to a larger
1,Overload
A-10 ozone power capacityozone power supply
2,Voltage rise time is too short
overload 2. Extend the voltage risetime
Ozone Power 1. Loose connection of ozone power supply to 1. Check the load connection and
A-12 Failure load troubleshoot
1. Read and write function code data process,
Internal data 1. Retry after reset
A-19 there is strong interference around
store alarm 2. Seek the services of manufacturers
2. Internal memory corruption
External device 1. Ozone power external equipment 1 fault
A-25 1. Check signal source and related equipment
1 alarms input terminal has signal input
External device 1. Ozone power external equipment 2 fault
A-26 1. Check signal source and related equipment
2 alarms input terminal has signal input
External device 1. Ozone power external equipment 3 fault
A-27 1. Check signal source and related equipment
3alarms input terminal has signal input
External device 1. Ozone power external equipment 4 fault
A-28 1. Check signal source and related equipment
4 alarms input terminal has signal input
Warning of
disconnection 1. Check the wiring from keyboard to ozone
A-29 1.Keyboard to ozone power cord loose
of Keyboard power supply
Communication
RS485 1. RS485 communication signal break 1. Check analog input signalwiring and
A-30 Communication 2. Unreasonable configuration of parameters analog input signalsource
break alarm related to wire breakage detection 2. Modify configurationparameters
45 07 、 Fault diagnosis and exception handling

Form 7-2 Trouble codes and troubleshooting


Fault Fault
Possible Cause Solutions
Code description
1. Voltage rise time set too short
E-01 Overcurrent 1. Adjust voltage rise time
2. Start immediately after output is
2. Need to troubleshoot before starting
stopped due to a Fault
E-02 Overcurrent 3. Choose the ozone power supply with
3. The power capacity of ozone is on the
matching capacity grade
low side
4. Eliminate the source of short circuit or
E-03 Overcurrent 4. The load end has short circuit or the
ignition failure
electrode ignites
E-04 overvoltage
E-05 overvoltage 1. Input voltage anomaly 1. Check the input power
E-06 overvoltage 2. Load to ground short circuit 2. Short circuit troubleshooting
E-07 overvoltage
1. Abnormal power supply voltage
1. Check the power supply voltage
E-08 undervoltage 2. There is a large load starting in the
2. Separate power supply
power grid

1. Voltage rise time set too short


1. Adjust voltage rise time
2. Start immediately after output is
2. Need to troubleshoot before starting
stopped due to a Fault
3. Choose the ozone power supply with
E-09 Load overload 3. The power capacity of ozone is on the
matching capacity grade
low side
4. Eliminate the source of short circuit or
4. The load end has short circuit or the
ignition failure
electrode ignites

1. Voltage rise time set too short


1. Adjust voltage rise time
2. Start immediately after output is
2. Need to troubleshoot before starting
Ozone Power stopped due to a Fault
3. Choose the ozone power supply with
E-10 Supply 3. The power capacity of ozone is on the
matching capacity grade
pre-overload low side
4. Eliminate the source of short circuit or
4. The load end has short circuit or the
ignition failure
electrode ignites

1,Overload 1. Reduce the load or replace with a


2. Voltage rise time is too short larger capacity ozone power supply
3. High Torque boost voltage or improper 2. Extend the voltage rise time
V / F Curve Setting 3. Reduce the torque boost voltage and
Ozone power 4. Grid Voltage's too low adjust the V/F curve
E-11
overload 5. No starting speed tracking and restart 4. Check the grid voltage
function directly starts the rotating load 5. Start/stop mode ([F03.00]) is set as
6. In closed loop vector mode, the speed tracking restart mode
encoder pulse direction is opposite to the 6. Check whether the encoder is
load direction reversed
Ozone power
E-12 off 1. Ozone power to load connection loose 1. Check the load wiring and troubleshoot
1. Clear air ducts or improve ventilation
1. Blocked air duct
conditions
Ozone power 2. The ambient temperature is too high
2. Improve ventilation conditions and
E-13 supply 3. Abnormal fan
reduce carrier frequency
overheating 1 4. Abnormal temperature detection circuit
3. Replace the fan
or power module 4. Seek support from manufacturers
1. Clear air ducts or improve ventilation
1. Blocked air duct
conditions
Ozone Power 2. The ambient temperature is too high
2. Improve ventilation conditions and
E-14 supply 3. Abnormal fan
reduce carrier frequency
overheating 2 4. Abnormal temperature detection circuit
3. Replace the fan
or power module 4. Seek support from manufacturers
Current
E-15 1. The current sensor is damaged 1. Replace Current Sensor
detection error
1. Reduce the load or change to a larger
Power module 1. The load current is too high
E-16 capacity ozone power supply
failure 2. Power module damaged 2. Replace the power module
Load tuning 1. The load is not connected when the 1. The load is not connected when the
E-17
failure load parameter is identified load parameter is identified.
VL2900 series of high-performance Ozone Power Simple Manual 46

Fault Fault
Possible Cause Solutions
Code description
1. CPU damage
E-18 CPU fault 1. Seek manufacturer's Service
2. Abnormal interference
1. In the process of reading and writing
Internal data functional code data, there is strong 1. Retry after reset
E-19
storage error interference around. 2. Seek the services of manufacturers
2. Internal memory damage
1. In the process of reading and writing
Parameter functional code data, there is strong 1. Retry after reset
E-20
copy error interference around. 2. Seek the services of manufacturers
2. Internal memory damage
Run limit time 1. The time limit for operation has
E-21 Please contact your direct supplier
reached expired.
1. The lead from the power grid to the
Phase is
ozone power supply is broken 1. Eliminate peripheral failures
E-22 missing on the
2. The three-phase voltage imbalance 2. Add AC or DC reactor
input side
ratio is large
Phase missing 1. The lead from ozone power supply to
on the output load is broken. 1. Eliminate peripheral failures
E-23 side Or the 2. Ozone power driver board or control 2. Seek support from manufacturers
output current board failure. 3. Troubleshoot load failures
is unbalanced 3. Load three-phase Winding Fault.
1. Ozone power output short circuit to the
Output to
ground 1. Troubleshoot peripheral faults
E-24 Ground Short
2. Load three-phase winding short-circuit 2. Troubleshoot load failures
Circuit Fault to the ground
External 1. The ozone power peripheral equipment
1. Check signal source and related
E-25 Equipment 1 1 fault input terminal has the SIGNAL
equipment
Failure INPUT.
External
1. Ozone power peripheral equipment 2 1. Check signal source and related
E-26 Equipment 2
fault input terminal has signal input. equipment
Failure
External 1. Ozone Power Peripheral Equipment 3
1. Check signal source and related
E-27 Equipment 3 FAULT INPUT TERMINAL HAS SIGNAL
Failure INPUT equipment
External 1. Ozone Power Peripheral Equipment 4
1. Check signal source and related
E-28 Equipment 4 FAULT INPUT TERMINAL HAS SIGNAL
equipment
Failure INPUT
Keyboard
1. Loose wiring from keyboard to ozone 1. Check the wiring from keyboard to
E-29 communicatio
power supply ozone power supply
n failure
1. RS485 communication signal break
RS485Commu 1. Check analog input signal wiring,
2. Unreasonable configuration of
E-30 nication analog input signal source
parameters related to wire breakage
failures detection 2. Modify configuration parameters
1. Voltage rise time set too short
1. Adjust voltage rise time
2. Start immediately after output is
2. Need to troubleshoot before starting
stopped due to a Fault
3. Choose the ozone power supply with
The current 3. The power capacity of ozone is on the
matching capacity grade
E-44 was detected low side
4. Eliminate the source of short circuit or
to be faulty 4. The load end has short circuit or the
ignition failure
electrode ignites
5. Modification of current detection
5. The setting of current detection
parameters is not reasonable parameters

E-45 retention retention retention

Voltage
E-99 —— ——
correction fault
VL2900 series of high-performance Ozone Power Simple Manual 4 7

08、Maintenance and upkeep.


The changes of operating environment, such as temperature, humidity, smoke, and the aging of the internal components
of ozone power supply, may lead to various failures of ozone power supply. Therefore, in the storage, use of the ozone
power must be routine inspection, and regular maintenance.

Form 8-1 Check content regularly


Check items Check content Exception handling
Main Circuit Terminal, Tighten with a screwdriver
Control Circuit If the screws are loose
Terminal Screw
Blow it off with dry compressed air
cooling fin If there's any dust
at 4 ~ 6kgcm2 pressure
PCB printed circuit Blow it off with dry compressed air
If there's any dust
board at 4 ~ 6kgcm2 pressure
Whether there is abnormal sound,
cooling fan abnormal vibration, the cumulative Replace cooling fan
time running up to 20,000 hours.
Blow it off with dry compressed air
power component If there's any dust
at 4 ~ 6kgcm2 pressure
aluminum electrolytic Replace the aluminum electrolytic
Discoloration, odor, bubbling
capacitor capacitor

8.1 Daily maintenance


When the ozone power supply is turned on normally, please confirm the following:
(1) whether the temperature of the ozone power supply is abnormal.
(2) whether the ambient temperature is too high.
(3) whether the load ammeter is the same as usual.
(4) whether the cooling fan of ozone power supply is in normal operation.

8.2 Regular maintenance and upkeep


8.2.1 Regular Maintenance
When the ozone power regularly maintenance inspection, first must cut off the power supply, to monitor no display and
the main circuit power indicator lights off, before the inspection. The contents of the check are shown in Table 8-1.

8.2.2 Regular upkeep


In order to make the ozone power supply work normally for a long time, it is necessary to carry out regular maintenance
for the service life of the electronic components inside the ozone power supply.The service life of the electronic
components of ozone power source is different because of the different environment and service conditions.As shown in
Table 8-2 ozone power supply maintenance period for user reference only.

Form 8-2 Ozone Power Supply Component Replacement Time


Part Name Standard Replacement Years
Cooling Fan 2 ~ 3 YEARS
electrolytic condenser 4~5 YEARS
Printed Circuit Board 5~8 YEARS
Fuse 10 YEARS
48 08 、 Maintenance and upkeep

The above ozone power supply parts replacement time of the use of the conditions:
(1) ambient temperature: 30 °C annual average.
(2) load factor: less than 80% .
(3) running time: less than 12 hours per day.

8.3 Warranty of Ozone Power Supply


The company will provide warranty service in the following situations:
(1) the warranty only refers to the ozone power supply itself;
(2)In normal use, the company is responsible for the warranty of ozone power supply failure or damage
within 12 months after the date of delivery.Reasonable maintenance costs will be charged.
(3)A maintenance fee shall also be charged within 12 months if:
● Do Not Follow the operating procedures of the Operation Manual, resulting in ozone power supply
damage;
● Ozone power supply damage caused by flood, fire, abnormal voltage or force majeure;
● Ozone power supply damage caused by wrong connection wire;
● Damage caused by using ozone power supply for abnormal functions;