The document provides information about grounding systems used in buildings. It discusses how a single ground is typically run throughout commercial buildings to keep impedance low. It also describes how large electrical equipment can introduce noise into the grounding system. Protective earth connections are designed to safely discharge fault currents. Unfortunately, achieving a clean ground is difficult due to interference from devices like air conditioners and dimmers.

Uploaded by

gerrzen64
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
187 views11 pages

Building Grounding

The document provides information about grounding systems used in buildings. It discusses how a single ground is typically run throughout commercial buildings to keep impedance low. It also describes how large electrical equipment can introduce noise into the grounding system. Protective earth connections are designed to safely discharge fault currents. Unfortunately, achieving a clean ground is difficult due to interference from devices like air conditioners and dimmers.

Uploaded by

gerrzen64
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Groundloop information pages

[ index ][ back ][ site search ] [ acronyms ] [ discussion ] [ mail to a friend ] [ post message ]

What's the problem in grounding systems used in


buildings ?
NOTE: This documents tries to give you general information about electrical wiring inside
building. This documents is only written to give a general understanding of some of the most
common electrical wiring systems. This document is not ment to be an accurate description of all
wiring systems. Don't do any electrical work based on information provided here. Leave the work
to professionals who know all this and the local regulations.

Building grounding
In the construction of most commercial buildings, one ground is usually run throughout the building to keep
the impedance as low as possible. Low impedance in the ground is needed to makse sure that the the fuse
blows when something gets short circuited to ground wire (for example cable insution breaks inside the
equipment and touches the grounded metal case). The grounding system is primarily designed for electrical
safety in mind. The Protective Earth connection should be able to carry a heavy current to protect the user
from live-to-chassis faults by ensuring that the fuse or circuit breaker will operate so the requirement is that
the Protective Earth conductors can carry a 25A fault current for at least 1 minute. The grounding system in
the building electricity distribution has only effect on the electromagnetic environment inside the building
which you must understand.

Unfortunately all building have big electrical equipment such as air conditioning units, refrigerators, washers/
dryers and other high current devices connected to the building ground (the same ground you use for your
AV system). Computers and other equipments which use stiched power supplies generate harmonics to the
electrical power which usually end up being noise in the gounding system. Light dimmers are also a storng
source of interference and some of it typically ends to the ground wires also. Thus the chances of getting a
clean ground in a typical audio visual installation is slim, especially in large commercial buildings, hotels,
hospitals or convention centers.

Grounding practices in buildings

Electric power distribution throughout Finland and many parts of Europe is made by 230/400Vac, 3 phase,
four wire, Multiple Earth Neutral (MEN). One, two or three phases are brought into the customer's premises
depending on the maximum demand. This applies to both residential and business premises.

For those not aware of the MEN system, the neutral bar is connected to an earthing stake driven into the
ground as near as possible to the customer's switchboard. All earth wiring from power points, etc, is
connected to the neutral bar. In the UK the same practice is called Protective Multiple Earthing (PME). With
P.M.E. the neutral and earth conductors of the supply are combined. The supply company connects the
neutral solidly to earth frequently throughout the distribution network. At the customer's connection point
the company supplies an 'earth' (which is actually connected to the neutral) to which all the installation
earths and equipotential bonding are connected.

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (1 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

Another approach to bring grounding to the building is to bring it through armouring of the supply cable. If
the electricity company cannot easily supply or guarantee an adequate earth conductor (for example supply
comes on a pair of overhead wires), the ser is generally responsible for the adequacy of the earth electrode.
The method of earthing can normally be found out by tracing the wiring from the meter/consumer unit. It is
usually fairly obvious.

How Good Should the Earth Be ?

This is a difficult question to answer; in general the impedance of the earth connection must be low enough
to ensure that sufficient current can flow through the protective device so that it disconnects the supply
quickly (<0.4 second) and that voltage on the earth connection does not rise more than 50V. Measuring the
resistance of an earth electrode is not easy and should be left to professionals.

Safety if the neutral in the feeding is cut

How safe or unsafe MEN or PME is depends on the rules which cover its application, and the record of the
supply utility in avoiding neutrals going open circuit.

The key word in the titles is MULTIPLE. The exact situation will vary dramatically depending on where the
break in the neutral occurs. If it is just outside the substation, then the neutral conductor will be replaced by
all of the multiple earths in parallel, and providing the load is balanced over the three phases, the voltage
disturbance will not be too serious.

When the supply company neutral goes open, the neutral return is via the earth stake. Soil types here
range from sand to loam to clay to rock, so the ground stake can range from a good to a very poor earth.
The voltage from each active to the "neutral" will depend on the loads on each phase and the ground
resistance.

The worse the balancing of your load over the three phases, the worse the voltage disturbance will be. If we
assume that the earthing spike has a resistance of 100 ohm, it is pretty clear that your equipment is not
going to work, but your neutral and earthed metal work is going to rise to something near to phase voltage.
This sound horrific, but is actually not dangerous provided that all earthed metal work is nicely bonded, and
there are no unbonded earthed objects around that are better earths than your earth spike.

How the ground connections are made in the main distribution board

The three phase power power comes from power company using just four wires L1, L2, L3 and PEN
(protective earth and neutral). L1, L2 and L3 are just connected to the power bars in the main distribution
panel. The PEN wire is connected to the PE (protective earth) bar which is connected to the central
grounding bar. Neutral bar is connected to the PE bar in the main distribution panel and nowhere else in the
building which has 5 wire 3 phase wiring.

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (2 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

The central grounding bar works as the central point for whole building grounding system and every
grounded system in the building is connected to it. The central grounding bar is just a metal bar which
connected the grounding wires from the mains power, telephone equipments, antenna wiring, lightning
protectors, metal plumbing, water pipes, building steel structures and building grounding electrodes
together.

As mentioned elsewhere, a fault current flowing in the earth wiring will cause the voltage on that wiring to
rise relative to true earth potential. This could cause a shock to someone touching, for instance, the case of
a faulty washing machine and a water tap at the same time. In order to minimise this risk, an 'equipotential
zone' is created by connecting the services to the main earthing point. Such services are metal pipes (gas,
water, etc.), central heating, metallic ventilation trunking, exposed parts of building structure, lighting
conductor and any other metallic service.

The equipotential bonding reduces the voltage difference which could exist between the metalwork of these
services if an earth fault occurred to any one of them.

How the ground is wired to electrical outlets

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (3 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

The best way would be to run all the grounds separately back to a single block of copper at the central
grounding bar. Unfortunately this is often difficult to achieve in practice. The practical way is to arrange
your grounds as a strict 'tree' structure, with equipment only connecting to the leaves of the tree.

For ground wire routing the electrical installation regulations worldwide generally state that the ground
wires should be routed on the same route than the mains curren carrying wires going to the same outlet or
distribution panel. This is the most often used practice. Usually the safety ground is a separate yellow/green
wire in the cable and sometimes it is a separate wire in the same cable bundle (for example for 3 phase
distribution you might see sometimes a 4 or 5 wire cable and a separate safety ground cable bundled on the
side of the cable). In some countries (for example in USA) in some case the metallic piping used to protect
the mains carrying wire inside the walls can be used as safety ground conductor (not usually very good or
reliable in practice I think, but is allowed in some cases).

How power is delivered to the house

Typical one phase feeding to building

One phase distribution is typically used in small residental building. The power company feed live wire and
neutral+gound wire to your house. The power in the power company system is typically three phase power
and the power company then feed one phase to your house (you neighbour can have their power from other
phase for even distribution of load).

Single phase power in North America

ANSI C84.1 "Electric Power Systems and Equipment - Voltage Ratings (60 Hz) sets the preferred nominal
voltage at 120V and allows a range of 114 - 126V (240V nominal, range 228 - 252V). Equivalent Canadian
spec is CAN3-C235.

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (4 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

Voltage at a 120 volt nominal single phase receptacle should be 110 to 125V under normal conditions.

However, the California Public Utilities Commission has specified that the service voltage shall be kept in the
range 114-120V, with some exceptions. This was done because some studies showed a reduction in energy
consumption at the lower voltages.

Information on NEMA plug configurations is available in NEMA Configuration Chart, Form No. H4513. For
availability check http://www.hubbell-wiring.com/.

Single phase power in Europe

The nominal European voltage is now 230V 50 Hz (formerly 240V in UK, 220V in the rest of Europe) but this
does not mean there has been a real change in the supply.

Instead, the new "harmonised voltage limits" in Europe are now:

● 230V -10% +6% (i.e. 207.0 - 243.8V) in most of Europe (the former 220V nominal countries)
● 230V -6% +10% (i.e. 216.2 - 253.0V) in UK (former 240V nominal)

his is really a fudge and means there is no real change of supply voltage, only a change in the "label", with
no incentive for electricity supply companies to actually change the supply voltage.

To cope with both sets of limits an equipment will therefore need to cover 230V +/-10% i.e. 207-253V. This
will actually become the official limit for the whole of the EU in 2003.

Single phase power in rest of the world

A listing of nominal voltage/frequency and plug/socket types used in many countries is given at http://
kropla.com/electric2.htm.

Three phase distribution

The 3-wire system that the user sees is typically derived from three phase distribution, which uses a 5-wire
system. In the 5-wire system, there are 3 hot wires, 1 neutral wire, and 1 grounding wire. The common 3-
wire receptacle uses only one of the 3 hot wires. This 5 wire wiring system is basically good and it is used in
most buildings and places where ground loops are expected to be a problem.

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (5 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

This three phase power system is called THREE-PHASE STAR; FOUR-WIRE; EARTHED NEUTRAL system. This
is the most common way used in European wiring systems (and used almost everywhere in Finland), but
note that three-phase distribution circuits come in several flavours. There is a distinct difference between
those in the US and those in Europe. They are classified as follows:

● TN: Transformer star point earthed. Protective Earth and Neutral share the "ground" conductor (PEN)
and are separated at the fuse panel. This circuit is also referred to as TN-C (C for common PE and
N). In UK this is called TN-C-S (i.e. combined in supply and separate in the installation), and it is also
referred to as Protective Muliple Earthing (PME - as the PEN supply conductor is grounded at regular
intervals along the supply).
● TN-S: As above, but PE and N are brought separatley all the way from the earthed transformer and
never allowed to get into contact with each other elsewhere. The idea is that PE shall never carry any
current (it shall consequently not carry any potential and is supposed to be very "clean". All return
currents go through the N conductor all the way to the transformer star point. This system has
become very popular in new installations in Europe and has been a standard in hospitals for a long
time.
● IT: The transformer is not erthed at all. The star point floats. Mostly used in heavy and process
industry where continued operation - even if there is an earth fault - is required. The more common
(european) voltages in these systems are 500 V and 690 V. In this case housing of the objects are
connected to local grouns.
● TT: Transformer and objects have separate grounds. Common in US.

Three phase in Europe

In Europe most use 230/400V where the 230V can be found between any of the 3 phases and neutral and
the 400V can be found between two of the three phases. Phase difference between phases is 120 degrees.
Three phase power is normally available in at least Finland, Sweden and Germany being used for ovens,
electric stoves, large motors and dryers. Three phase power is also typically available in places where large
sound and light systems are used (around stages etc.).

Typically there are 4 wires routed to every house for 3 phase feed. Those are typically them are labeled R,
S, and T, the fourth being ground. The phase shift between R and S are 120 deg., the same phase shift
exists between S and T and between T and R. The voltage difference between the live phases is 400 V, the
voltage difference between any live phase and ground is around 235 V. The usual household power outlet
connection uses one phase and ground. Three phase is usally used only on some permanetly wired high
power loads (typically ovens and electric stoves in normal household). A typical rating for mains fuse in
typical household in Finland which has three phase power is 3x25A (25A per phase).

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (6 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

If three phase connector is avaible some heavy equipments (in places where heavy machinery is used),
then the most common one available is 3x16A connection.

Other possibilities for power distribution

Some smaller electrical installations (small houses) only use one phase feed. In those cases the power
company only brings one of the three phases to the house. In those cases the wiring from power company
is implemented using two wires: "neutral+ground" and "phase". The frequency in USA is 60 Hz and nominal
voltage in USA is defined in the following manner:

● 120 volts is the voltage at the transformer


● 115 volts is the voltage at the panel (voltage drop losses in the cable from the transformer to the
panel)
● 110 volts is the voltage at the receptacle (voltage drop losses in the cable from the panel to the
receptacle)

So if the outlest are very lightly loaded, you will get nearly 120V and if wiring hevily loaded, the voltage
drops to around 110V. In Europe the frequency is 50 Hz and voltage on the outlet is nowadays is 230V (the
real voltage typically is between 220V and 240V).

In USA the domestical service has typically 3 wires: 2 hots and a neutral. The voltage between the 2 hots is
240 and the voltage from either hot to the neutral is 120 (half). Normal electrical outlets are connected
between the neutral and one hot wire. Some heavy loads (like air conditioners) are connected between
those two hot wires and receive the full 240V load.

House wiring details

What does a typical power outlet look like ?

A typical office wall outlet has three electrical connections, which are the "hot", "neutral", and "grounding"
wires.

All office equipment requires only the hot and neutral wires to function. The third or grounding wire is
connected to exposed metal parts on the equipment. Within the building, the grounding connections of all
electrical receptacles are wired to one another and are connected to the water piping. This ensures that all
electrical equipment with exposed metal parts has these parts electrically connected to each other and to
exposed metal fixtures in the building such as water fixtures.

The hot and neutral wires are interchangeable as far as the equipment is concerned (be warned that there
are some exceptions in some countries). Both are power carrying wires. One of the power carrying wires is
grounded for reasons of safety. In many parts of Europe (nordic counties, Germany etc), the normal 3-wire

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (7 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

receptacle is symmetrical so that the neutral and hot wire connections can be swapped by simply rotating
the plug.

Earthing of Electrical Installation

Each circuit requires an earth conductor to accompany (but kept separate from) the line and neutral
conductors throughout the distribution. All metal boxes should be connected to the earth.

What are the wire colors used in wiring

House wiring colors used in USA

Green body color Grounding Conductor

White body color Grounded Conductor (Neutral)

ANY other Body Color Figure that it's HOT

Wiring colors used in equipment cables

GREEN with YELLOW stripes Ground


BLUE Neutral
BROWN Live

Typical colors used in house wiring in Europe

Information of this is from regulations in use in Finland.

GREEN with YELLOW stripes Ground


BLUE Neutral
BROWN or BLACK Live

Grounding (Green or green/yellow) means that it's there to tie all of the stray metal parts together so that
(hopefully) none of them can get to where they'll make a hazard. A far better term for this wire is that it is
the "Bonding" conductor. Grounding wire should NEVER be asked to carry current.

Do not thrust the color coding unless you know under which standard the wiring is done. There some some
other color codes also in use. Inside of any electronic equipment, it is dangerous to trust any color codes

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (8 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

unless you know which "Standard" that unit was built under.

House wiring problems

Problematic old wiring

The most problematic are those builing which are wired using 4 wire 3 phase wiring, where neutral and
ground share the same conductor at some places of wiring. This is a bad thing because in this situation
there will be always current flowing in the same wire which should distribute the same ground potential to
different places. If your building has four wire 3 phase wiring you can expect quite noticable ground
potential differences of the power taken from different distribution panels.

The practice where safery ground is connected using the same conductor as neutral is called PEN (TN-C)
and practice where there is separate ground wire in whole system is called PE (TN-S).

Two wire 1 phase grounded outlet

And worst of all is a 2 wire 1 phase jack wiring where neutral and ground share a common wire. This
practice is very often used in older buildings in Finland and causes terrible ground loop problems even
between nearby power outlets. If your are planning to install any dedicated equipments (computer
connected to LAN, interconnected audio or video equipment etc.) to building which has this kind wiring
system is advicable to get a lincensed electrician to rewire the room with proper outlets. This wiring has also
some other problems and that's why it is not allowed anymore in new installations in Finland.

Circuit breaker boxes: The main breaker box to the building is the single location where the neutral and the
ground wires come together. The electrical service will be grounded at this point. IN ALL DOWNSTREAM
BREAKER BOXES BOTH THE NEUTRAL AND GROUND WIRES MUST BE KEPT APART FROM ONE ANOTHER.
Otherwise you will have neutral currents flowing on the ground wire. This is extremely important and is a
major safety and signal issue.

These simple rules apply to ALL cabling including CATV, Video, AC and signal. One exception is the ethernet.
Ground the computer LAN one end (preferably to the same point as your audio system) and make sure that
the thin ethernet connector metal parts do not touch any parts of computer case (there are nice plastic
isolation cases available for them). I would recommend to use 10 Base-T ethernet which used twisted pair
wiring because it does not need any grounding and does not cause ground loops in any case.

What are isolated ground receptables ?

NOTE: The following description describes isolated ground as defined in USA wiring system. In other
countries "isolated ground" can mean different things (for example real ground but not connected to the
power ground bar).

Many new buildings in USA are equipped with "Isolated ground" receptacles. These are normally
recognizable because they are bright orange and have a triangle marked on the face. Basically, these
receptacles have a separate "green wire" equipment ground, and the wire goes back directly to the circuit
breaker panel, without being connected to anything else. Isolated ground receptacles are installed in the
hope that electrical noise generated in the building, or by other pieces of equipment, will not disturb the
operation of delicate computer equipment plugged into them.

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (9 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

As far as what the NEC allows, an isolated ground is a grounding connection which is grounded only at the
separately derived system from which the circuit is supplied. It is permitted to pass through panelboards,
junction boxes, etc. without being bonded to the equipment grounding conductor which serves those
devices, thus minimizing electromagnetic interference. It must be used in conjunction with an isolated
grounding receptacle to be effective. More details of isolated ground can be found at NEC 250-74 Exc #4.

My understanding on using a term "isolated ground" is mostly for marketing purposes. I feel that their
purpose is a marketing response to inadequate design by some electronic equipment manufacturers and to
inadequate grounding practices by some electricians. The ground terminal is isolated from the mounting
yoke; in conventional receptacles the yoke and the ground terminal are connected. The "idea" is that the
electrician connects a special "clean" ground to the ground terminal, while the yoke and all other non-
energized metallic parts are connected to the "dirty" equipment ground.

How to avoid ground loop problems


Most electronic equipment is sensitive to ground loops and ground-induced noise. A proper earth ground at
the building services entrance is the first step to avoiding such problems. In many cases, a proper earth
ground is provided by a connection to the steel rebar in the building's foundation.

All outside service grounds must be solidly connected to this ground point, including power, telephone and
cable television. For lightning protection, any antenna masts should be grounded here as well. Ground
connection points from the telephone system controller, security alarm panel, audio equipment and other
electronics gear should be connected to this ground buss. All distribution of 3 phase voltage inside of
building should be done using 5 wire system. Distribution of 1 phase power should be done using 3 wire
system. The safety ground wires should be interconnected in star or tree like fashion. For more information
check Residential Wiring and Grounding Guidelines from Power Clinic.

If possible, all electronics and computer equipment should have a separate isolated electrical subpanel with
isolated ground receptacles provided at all locations remote from the main. Isolated ground means that the
ground wiring is otherwise isolated form all other wiring except that it is connected to the main grounding
bar for one single point. This practice will ensure that all electronic equipment grounds are at the exact
same electrical potential and avoid the "minute differences" in grounds that cause ground loops. These
differences are reflected in signal-carrying conductors or shields between the components and may be
amplified to audible or visible levels.

Components that cannot have "equal-potential" grounds should have signals that are isolated from each
other. This can be expensive and difficult to achieve. It is much easier to prevent the problems in the first
place when designing the electrical distribution. More information on that is available from Equitech articles:
Power Management in the Studio, Audio Wiring and Grounding, 1996 National Electrical Code Technical
Support Bulletin and Installing a Technical Grounding System. Those articles provide you understanding how
to make good grounding system for studio.

Do not try to modify your electrical wiring yourself. When you know what needs to be done call
professionals to do the job properly (you might need a special consultant to do the plans for modifications
because standard electricians don't usually know all the special requirements audio studio has). When you
have proper groundung system in your studio then you can start doing the the audio wiring in a right way.
You can easily easily make your system very sensitive to power system noise if you do not do the wiring
properly. Rane application note Sound System Interconnections gives you good undertanding how the audio
connections should be done.

The problem is that in many cases you don't have possiblity to change the electrical distrubution system
already in the place, because it will come hard to do and expensive. Then you have to live with what you

http://www.epanorama.net/documents/groundloop/electrical_wiring.html (10 of 11)6/12/2006 5:04:59 PM


Groundloop information pages

get and try to solve those problems with suitable isolation devices.