AC5102
Technical Manual
Rev 4.0
A6V10320590 Siemens AB
13.09.2012
Copyright
Copyright
Technical specifications and availability subject to change without notice.
© Copyright Siemens AB
We reserve all rights in this document and in the subject thereof. By acceptance of
the document the recipient acknowledges these rights and undertakes not to
publish the document nor the subject thereof in full or in part, nor to make them
available to any third party without our prior express written authorization, nor to
use it for any purpose other than for which it was delivered to him.
Edition: 13.09.2012
Document ID: A6V10320590
2
Siemens AB A6V10320590
Security Products 13.09.2012
Table of Contents
3
Siemens AB A6V10320590
Security Products 13.09.2012
About this document
1
Contacting us
If you have technical questions regarding the product, please contact our Technical
Competence Center.
Hotline Europe
Phone +49 89 9221 8000
Email: [email protected]
Hotline South & North America
Phone: +1 800 877 7545
Email: [email protected]
Hotline Asia
Phone: +86 10 6296 0119
Email: [email protected]
4
Siemens AB A6V10320590
Security Products 13.09.2012
Scope of Delivery
2
2 Scope of Delivery
1 x AC5102 Advanced Central Controller
7 x 6-Position connector
1 x 3-Position connector
1 x Installation manual
5
Siemens AB A6V10320590
Security Products 13.09.2012
Details for Ordering
3
6
Siemens AB A6V10320590
Security Products 13.09.2012
General Safety Precautions
4
WARNING
WARNING
Please read and comply with the following notes before assembling and installing
the unit:
Please ensure that the controller is installed in a clean room. Please ensure
that the central control unit is protected from damaging environmental
influences such as direct sun exposure, operation-dependent vibrations, dust,
etc.
Never install the controller close to heaters and sinks. Avoid the proximity of
sources of electrical or mechanical interferences. If the controller is installed in
an enclosed space such as behind paneling or in small niches, please ensure
sufficient ventilation. Please use electrically conducting floor coverings to
minimize electrostatic charges.
Keep the conditions for ambient temperature and humidity as stated in the
technical data.
Use a separate electrical circuit with a specially marked fuse (“red") to supply
a.c. voltage to the unit.
Please ensure that switching off other tools or devices does not disconnect the
electrical circuit to the unit. Attach a note in the cabinet about the location of the
power supply fuse (low-voltage distributor number / mains fuse number).
Please ensure that the fuse is easy to access.
Please ensure that the cable duct covers the cable entry opening.
Use only shielded cables with extra-low voltage for all lines leading to the
inside of the controller. Connect the cable shielding to all connection points.
Ground cable shielding only on one side.
The precautions applicable for CMOS technology are to be applied to activities
involving server circuit boards and soldering.
Never install a live circuit board.
7
Siemens AB A6V10320590
Security Products 13.09.2012
Standards and Guidelines
5 EU Directives
5.1 EU Directives
This product complies with the requirements of the European Directives
89/336/EEC “Directive of Electromagnetic Compatibility” and 2006/95/EEC “Low
Voltage Directive”. The EU declaration of conformity is available from
Siemens AB, Infrastructure & Cities
Security Products
Englundavägen 7
SE-171 24 Solna, Sweden
5.2 FCC
This equipment complies with the FCC Rules CFR 47 Part 15 Emission Class B
limits.
This equipment has been tested and found to comply with the limits for a Class B,
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turnings the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
Reorient or relocate receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
8
Siemens AB A6V10320590
Security Products 13.09.2012
Standards and Guidelines
UL-Directives
5
5.3 UL-Directives
UL 294 Access control units, not UL evaluated for Household or Commercial
Burglary.
CSA C22.2 No. 205
RS232, RS422, USB, LAN, Power Fail, Tamper and Alarm Out connections not
evaluated by UL.
Wiring methods shall be in accordance with ANSI/NFPA 70, National Electrical
Code; CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical
Installations; and the authority having jurisdiction.
For UL approved installations, the unit must be powered by a UL 294 and CSA
C22.2 No. 205 power limited power supply, such as AlarmSaf CPS400C-UL/CSA-
APD8F.
The unit must be installed within a protected premise.
If the unit is wired for fail secure operation, it must be used in conjunction with UL
Listed panic hardware. The unit shall not impair the intended operation of panic
hardware used in conjunction with it.
9
Siemens AB A6V10320590
Security Products 13.09.2012
Technical Specifications
6 UL-Directives
6 Technical Specifications
Additional components ACK5110 cable for modem connection
Communication interfaces 6 x Field level network (FLN):
– FLN 1: RS232 (modem port) or RS422 / RS485
– FLN 2 & 3: RS232 / RS422 / RS485
– FLN 4,5,6: RS485 only (expansion module)
1 x RS232 RJ12 (RxD, TxD, GND)
2 x LAN: RJ45 (10/100 MB Ethernet)
1 x USB-A
1 x USB-B
Operating voltage 12-30 VDC
Power consumption Max. 10 W (fully loaded)
Alarm inputs 1 x Tamper input, 1 x Power fail input
Alarm output 1 x Alarm output (optical relay, max. 12 V, 100 mA)
Door capacity 96
Card capacity 500,000
Indicators Power, Active, Error, COM, USB, SD-Card, 4 x Ethernet
LCD Display None
Keypad None
Tamper switch Yes (Internal)
RTC battery 3.0 V, type CR2032
Microprocessor AT91SAM9G20
RISC Processor Based on ARM v5TEJ Architecture
Main memory 128 MB
Flash memory 256 MB; Firmware is field-updatable
Operating temperature 0 to +50 °C
Environment Indoor use only
Housing Steel
Colour Grey and blue
Storage temperature -30 to +65 °C (-22 to 149 °F)
Humidity 5 – 93% (non condensing)
Dimensions (W x H x D) 124 x 220 x 54 mm
Approval CE, UL294, C-Tick, FCC
10
Siemens AB A6V10320590
Security Products 13.09.2012
Technical Specifications
Dimensions
6
6.1 Dimensions
Note that the unit is recommended to be mounted in upright position to achieve the
best ventilation.
11
Siemens AB A6V10320590
Security Products 13.09.2012
Technical Specifications
6 Interfaces
6.2 Interfaces
12
Siemens AB A6V10320590
Security Products 13.09.2012
Technical Specifications
Indicators (LEDs)
6
The following tables describe the operation of the LEDs located on the ACC.
Front LEDs
POWER On: The ACC is connected to the power supply
ACTIVE Blinking: The ACC is working correctly.
ERROR On: An error has occurred.
COM Blinking: The ACC is communicating via the FLN ports
USB On: A USB device is connected
SD-CARD On: A SD-Card is inserted
Ethernet ports LEDs
Green On: Link 10 Mbp
Blinking: Activity 10 Mbp
Orange On: Link 100 Mbps
Blinking: Activity 100 Mbps
Yellow Off: Full duplex
On: Half duplex
Blinking: Collision activity
13
Siemens AB A6V10320590
Security Products 13.09.2012
Installation
7
7 Installation
Required tools & material
Medium-duty drill and associated drill-bits
4 Mounting screws or standoffs (approx. 4mm diameter)
T20 Torx screwdriver
Wire cutters
Cable strippers
Installation instruction
1. Place the ACC against the surface to which it is to be affixed and mark the
location of the mounting holes.
2. If being mounted within a cabinet, align the ACC mounting lugs with the holes
located on the cabinet backplane and proceed to step 5.
CAUTION
3. Select the appropriate drill bit according to the mounting surface / hole size and
drill the holes in the locations marked (if required).
4. Fasten the ACC to the surface using screws or standoffs.
5. Connect the ACC. See section: Hardware Connections [➙ 15].
6. Remove the cover and remove the battery protecting tab on the base board
(see arrow below). Mount the cover back.
7. Apply power to the ACC and test its operation. This step will require
configuration of the ACC and downloading of the device database. Firmware
upgrade may also be required.
14
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
Indicators (LEDs)
8
8 Hardware Connections
1. Connect an Ethernet cable to the LAN1 or LAN2 port on the ACC.
2. Connect the local devices to each of the 6 FLN ports on the ACC.
Up to 16 devices can be connected to each FLN port, for a total of 96 devices
per ACC. See section: FLN connectivity options [➙ 16].
NOTICE
3. Connect an alarm device (if required) to the ALARM OUT ports on the ACC.
4. Connect a tamper switch (if required) to the TAMPER ports on the ACC.
5. Connect the power fail signal from a PSU to the POWER FAIL ports of the
ACC.
Note: A short circuit between the two power fail input pins indicates a power
failure.
6. Ensure that the ACC is correctly grounded, by connecting the ground terminal
on the ACC's power port to the building earth ground.
7. Check all connections thoroughly.
15
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
8 FLN Connectivity Options
+ (non-inverting) + (non-inverting)
- (inverting) - (inverting)
S (shield) Unconnected
16
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
Bus Termination of the FLNs
8
FLN 1, 4, 5 & 6
For RS485 and RS422 functionality the following jumpers must be closed.
FLN 2 & 3
For RS485 and RS422 functionality the following double dip switches must be
closed.
FLN2 FLN3
17
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
8 Bus Termination of the FLNs
18
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
Jumper Description
8
Main board
19
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
8 FLN Device Load Limitations
X201 … X205 Jumper fitted on pins 2 & 3 = switch closed. End of line is enabled.
Jumper fitted on pins 1 & 2 or not fitted = switch open. End of line is
disabled.
The following table outlines the maximum value of configuration loads that can be
connected to each FLN.
FLN 1 16 loads
FLN 2 16 loads
FLN 3 16 loads
FLN 4 16 loads
FLN 5 16 loads
FLN 6 16 loads
20
Siemens AB A6V10320590
Security Products 13.09.2012
Hardware Connections
Recommended Cable Specifications
8
Communicat Cores Pairs AWG Strandin J-Y(st)Y Wire Type Insulation Shield Jacket
ion Type g Ø (mm)
RS485 4 2 24 7 x 36 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
6 3 24 7 x 36 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
8 4 24 7 x 36 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
RS232 4 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
6 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
8 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
RS422 4 2 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
6 3 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
8 4 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
RJ45 8 4 24 Solid 0,6 Bare Copper Polyethylene Aluminum foil- Polyester tape PVC
8 4 24 7 x 32 0,6 Tinned Copper Polyethylene Aluminum foil- Polyester tape PVC
Power 2 1 18 19 x 30 1,0 Tinned Copper Polyethylene Unshielded PVC
21
Siemens AB A6V10320590
Security Products 13.09.2012
Software Configuration
9
9 Software Configuration
The network settings of the AC5102 Controller can be configured using a Windows
application, and an appropriate USB cable. This configuration requires the USB
RNDIS driver (an Ethernet-over-USB driver) to be installed.
The pre-requisites required for this configuration are listed below.
To download a copy of the latest software and configuration guide, please contact
your Siemens product distributor.
Prerequisites
1. AC5102 Controller
2. Host PC with a spare USB port (running the Windows Operating System)
3. A-B USB Cable
4. Configuration application for the Windows Host
5. RNDIS USB driver
22
Siemens AB A6V10320590