18-2002 IEEE Standard For Shunt Power Capacitors
18-2002 IEEE Standard For Shunt Power Capacitors
18-2002 IEEE Standard For Shunt Power Capacitors
Published by
The Institute of Electrical and Electronics Engineers, Inc.
3 Park Avenue, New York, NY 10016-5997, USA
Print: SH94981
15 October 2002 PDF: SS94981
Recognized as an IEEE Std 18™-2002
American National Standard (ANSI) (Revision of
IEEE Std 18-1992)
Sponsor
Transmission and Distribution Committee
of the
IEEE Power Engineering Society
Abstract: Capacitors rated 216 V or higher, 2.5 kvar or more, and designed for shunt connection to
alternating-current transmission and distribution systems operating at a nominal frequency of 50 Hz
or 60 Hz, within the guidelines of IEEE Std 1036-1992, are considered.
Keywords: capacitors, shunt connection, transmission and distribution systems
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior
written permission of the publisher.
IEEE Standards documents are developed within the IEEE Societies and the Standards Coordinating Committees of the
IEEE Standards Association (IEEE-SA) Standards Board. The IEEE develops its standards through a consensus develop-
ment process, approved by the American National Standards Institute, which brings together volunteers representing varied
viewpoints and interests to achieve the final product. Volunteers are not necessarily members of the Institute and serve with-
out compensation. While the IEEE administers the process and establishes rules to promote fairness in the consensus devel-
opment process, the IEEE does not independently evaluate, test, or verify the accuracy of any of the information contained
in its standards.
Use of an IEEE Standard is wholly voluntary. The IEEE disclaims liability for any personal injury, property or other dam-
age, of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting
from the publication, use of, or reliance upon this, or any other IEEE Standard document.
The IEEE does not warrant or represent the accuracy or content of the material contained herein, and expressly disclaims
any express or implied warranty, including any implied warranty of merchantability or fitness for a specific purpose, or that
the use of the material contained herein is free from patent infringement. IEEE Standards documents are supplied “AS IS.”
The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market,
or provide other goods and services related to the scope of the IEEE Standard. Furthermore, the viewpoint expressed at the
time a standard is approved and issued is subject to change brought about through developments in the state of the art and
comments received from users of the standard. Every IEEE Standard is subjected to review at least every five years for revi-
sion or reaffirmation. When a document is more than five years old and has not been reaffirmed, it is reasonable to conclude
that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check
to determine that they have the latest edition of any IEEE Standard.
In publishing and making this document available, the IEEE is not suggesting or rendering professional or other services
for, or on behalf of, any person or entity. Nor is the IEEE undertaking to perform any duty owed by any other person or
entity to another. Any person utilizing this, and any other IEEE Standards document, should rely upon the advice of a com-
petent professional in determining the exercise of reasonable care in any given circumstances.
Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they relate to specific
applications. When the need for interpretations is brought to the attention of IEEE, the Institute will initiate action to prepare
appropriate responses. Since IEEE Standards represent a consensus of concerned interests, it is important to ensure that any
interpretation has also received the concurrence of a balance of interests. For this reason, IEEE and the members of its soci-
eties and Standards Coordinating Committees are not able to provide an instant response to interpretation requests except in
those cases where the matter has previously received formal consideration.
Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership affiliation with
IEEE. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate
supporting comments. Comments on standards and requests for interpretations should be addressed to:
Note: Attention is called to the possibility that implementation of this standard may require use of subject mat-
ter covered by patent rights. By publication of this standard, no position is taken with respect to the existence or
validity of any patent rights in connection therewith. The IEEE shall not be responsible for identifying patents
for which a license may be required by an IEEE standard or for conducting inquiries into the legal validity or
scope of those patents that are brought to its attention.
The IEEE and its designees are the sole entities that may authorize the use of the IEEE-owned certification marks and/or
trademarks to indicate compliance with the materials set forth herein.
Authorization to photocopy portions of any individual standard for internal or personal use is granted by the Institute of
Electrical and Electronics Engineers, Inc., provided that the appropriate fee is paid to Copyright Clearance Center. To
arrange for payment of licensing fee, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive,
Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational
classroom use can also be obtained through the Copyright Clearance Center.
Introduction
(This introduction is not part of IEEE Std 18-2002, IEEE Standard for Shunt Power Capacitors.)
This standard’s principal objective is to provide a basis for uniformity in design and testing of shunt power
capacitors.
This standard was revised in response to a need created by the continuous changes in capacitor technology,
primarily in the areas of internally fused and fuseless capacitors, and the need to move capacitor application
information previously contained in this standard to IEEE Std 1036-1992, IEEE Guide for Application of
Shunt Power Capacitors. It was also the aim of this revision to coordinate the information contained in this
standard, whenever possible, with other pertinent national and international standards.
Participants
This standard was revised by a working group sponsored by the Capacitor Subcommittee of the Transmis-
sion and Distribution Committee of the IEEE Power Engineering Society. At the time this standard was
approved, the Capacitor Subcommittee consisted of the following membership:
Jeffrey H. Nelson, Chair
Tom Grebe, Vice Chair
Clay Fellers, Secretary
Ignacio Ares Karl Fender J. Maneatis
S. Ashmore Chuck Gougler S. A. Miske, Jr.
B. Bhargava P. Griesmer Ed Reid
J. A. Bonner John Harder S. Rios-Marcuello
S. Cesari L. Holloman Don Ruthman
Bill Chai Ivan Horvat J. Samuelsson
Simon Chano Suresh C. Kapoor E. Sanchez
Stephen Colvin S. B. Ladd Richard Sevigny
Stuart Edmondson A. S. Mehraban P. Steciuk
Cliff Erven Rao Thallam
The working group that developed this standard consisted of the following membership:
Ignacio Ares, Chair
Jim Barcus Clay Fellers Allan Ludbrook
J. A. Bonner Karl Fender Jeffrey H. Nelson
Bill Chai Chuck Gougler George Newcomb
Simon Chano Tom Grebe Ed Reid
Stephen Colvin John Harder Richard Sevigny
Stuart Edmondson Luther Holloman Rao Thallam
Cliff Erven Ivan Horvat Don Ruthman
When the IEEE-SA Standards Board approved this standard on 21 March 2002, it had the following
membership:
James T. Carlo, Chair
James H. Gurney, Vice Chair
Judith Gorman, Secretary
*Member Emeritus
Also included are the following nonvoting IEEE-SA Standards Board liaisons:
Andrew Ickowicz
IEEE Standards Project Editor
1. Overview
1.1 Scope
This standard applies to capacitors rated 216 V or higher, 2.5 kvar or more, and designed for shunt connec-
tion to alternating current transmission and distribution systems operating at a nominal frequency of 50 Hz
or 60 Hz, within the guidelines of IEEE Std 1036™-19921.
2. References
This standard shall be used in conjunction with the following publications. When the following standards are
superseded by an approved revision, the revision shall apply.
ASTM D1535-01, Standard Practice for Specifying Color by the Munsell System.2
IEEE Std 1036™-1992, IEEE Guide for Application of Shunt Power Capacitors.3, 4
IEEE Std C37.41e™-1996, IEEE Standard Design Tests for External Fuses for Shunt Capacitors.
IEEE Std C37.99™-2000, IEEE Guide for Protection of Shunt Capacitor Banks.
IEEE Std C57.19.00™-1991 (R1997), IEEE Standard General Requirements and Test Procedures for Out-
door Power Apparatus Bushings.
NEMA 107-1993, Methods of Measurement of Radio Influence Voltage (RIV) of High-Voltage Apparatus.5
3. Definitions
The meaning of other terms used in this standard shall be as defined in The Authoritative Dictionary of IEEE
Standards Terms, Seventh Edition [B1]7.
3.1 ambient temperature: The temperature of the medium, such as air, water, or earth, into which the heat
of the equipment is dissipated.
NOTES
1—For self-ventilated equipment, the ambient temperature is the average temperature of the air in the immediate neigh-
borhood of the equipment.
2—For air- or gas-cooled equipment with forced ventilation or secondary water cooling, the ambient temperature is
taken as that of the ingoing air or cooling gas.
3—For self-ventilated enclosed (including oil-immersed) equipment considered as a complete unit, the ambient temper-
ature is the average temperature of the air outside of the enclosure in the immediate neighborhood of the equipment (see
5.7 and Table 2).
3.2 capacitor bank: An assembly at one location of capacitors and all necessary accessories, such as switch-
ing equipment, protective equipment, controls, etcetera, required for a complete operating installation. It
may be a collection of components assembled at the operating site or may include one or more piece(s) of
factory-assembled equipment.
3.3 capacitor element: The basic component of a capacitor unit consisting of two electrodes separated by a
dielectric.
3.4 capacitor equipment: A complete assembly of capacitors, including accessories such as buses, connec-
tors, dischargers, and fuses, suitable for connection to a power system.
3.5 discharge device: An internal or external device intentionally connected in shunt with the terminals of a
capacitor for the purpose of reducing the residual voltage after the capacitor is disconnected from a network.
3.6 externally fused capacitor bank: A capacitor bank with fuses external to the (power) capacitors.
3.7 fused capacitor: A capacitor having fuses mounted on its terminals, or inside a terminal enclosure, or
inside the capacitor case, for the purpose of interrupting current flow to a failed capacitor.
3.8 fuseless capacitor bank: A capacitor bank without any fuses, internal or external, which is constructed
of (parallel) strings of capacitor units.
NOTE—For example, an indoor capacitor unit is designed for indoor service or for use in a weatherproof housing. (See
also: outdoor.)
6NFPA publications are available from Publications Sales, National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101,
Quincy, MA 02269-9101, USA.
7The numbers in brackets correspond to those of the bibliography in Annex A.
3.10 internal fuse of a capacitor: A fuse connected inside a capacitor unit, in series with an element or a
group of elements.
3.11 internally fused capacitor (unit): A capacitor unit which includes internal fuses.
3.12 internally fused capacitor bank: A capacitor bank with internally fused capacitor units.
3.13 metal-enclosed equipment: A capacitor equipment assembly enclosed in a metal enclosure or metal
house, usually grounded, to prevent accidental contact with live parts. (Syn: metal-housed equipment.)
3.15 outdoor (prefix): Designed for use outside buildings and to withstand exposure to the weather.
3.16 power capacitor (capacitor, capacitor unit): An assembly of dielectric and electrodes in a container
(case), with terminals brought out, that is intended to introduce capacitance into an electric power circuit.
NOTE—The abbreviated term “capacitor” or “capacitor unit” is used interchangeably with “power capacitor” through-
out this standard.
3.17 proof (suffix): An apparatus is designated as dustproof, splashproof, etc., when so constructed, pro-
tected, or treated that its successful operation is not interfered with when subjected to the specified material
or condition.
3.18 string (string of capacitors): Capacitors connected in series between two terminals without parallel
connection(s).
4. Service conditions
Capacitors 2400 V and higher are expected to operate as indicated in the revision of IEEE Std 1036-1992, in
effect on the date that the capacitor is manufactured.
a) The ambient temperature is within the limits specified in 5.7. (Capacitors may be exposed to the
direct rays of the sun.)
b) The altitude does not exceed 1800 m above sea level. See 6.5.2 and Table 5.
c) The voltage applied between terminals does not exceed the rated voltage by more than the tolerance
specified in 5.3.
d) The impulse voltage applied between each terminal and the case does not exceed the basic impulse
insulation level (BIL) of that terminal.
e) The applied voltage including harmonics does not exceed the limit specified in 5.3.
f) The nominal operating frequency is equal to the rated frequency.
If capacitors are required to operate under abnormal service conditions, such as the following, the applica-
tion should be brought to the attention of the manufacturer:
The capacitance of a unit shall not vary more than –0% to +10% of the nominal value based on rated kvar,
voltage and frequency, measured at 25 °C uniform case and internal temperature.
Capacitors are intended to be operated at or below their rated voltage. Capacitors shall be capable of
continuous operation under contingency system and bank conditions provided that none of the following
limitations are exceeded:
86000 ft.
Typical voltage and reactive power ratings are given in Table 1. Capacitors shall not give less than rated reac-
tive power at rated sinusoidal voltage and frequency, and not more than 110% of this value, measured at 25
˚C uniform case and internal temperature.
240 2.5, 5, 7 1/2, 10, 15, 20, 25, and 50 1 and 3 30**
480, 600 5, 10, 15, 20, 25, 35, 50, 60, and 100 1 and 3 30**
2400 50, 100, 150, 200, 300, and 400 1 and 3 75, 95, 125, 150, and 200
2770 50, 100, 150, 200, 300, 400, and 500 1 and 3 75, 95, 125, 150, and 200
4160, 4800 50, 100, 150, 200, 300, 400, 500, 600, 1 and 3 75, 95, 125, 150, and 200
700, and 800
6640,7200,7620,7960, 8320, 9540, 9960, 50, 100, 150, 200, 300, 400, 500, 600, 1 95, 125, 150, and 200
11 400, 12 470, 13 280, 13 800, 14 400 700, and 800
15 125 50, 100, 150, 200, 300, 400, 500, 600, 1 125, 150, and 200
700, and 800
19 920 100, 150, 200, 300, 400, 500, 600, 700, 1 125, 150, and 200
and 800
20 800, 21 600, 22 800, 23 800, 24 940 100, 150, 200, 300, 400, 500, 600, 700, 1 150 and 200
and 800
*See 7.7.
**Not applicable to indoor ratings.
5.6 Frequency
Power capacitors shall be designed for operation at the rated nominal frequency of either 50 Hz or 60 Hz.
Capacitors shall be designed for continuous operation and frequent switching operations in outdoor loca-
tions with unrestricted ventilation and direct sunlight for the maximum ambient temperatures for each
mounting arrangement shown in Table 2. For applications with restricted air flow, ventilation must be ade-
quate so that the maximum ambient air temperatures as given in Table 2 for metal-enclosed or metal-housed
equipment are not exceeded.
Isolated capacitor 46
Capacitors shall be capable of both continuous operation and switching operations at a minimum ambient
temperature of –40 °C.
Capacitors shall be capable of withstanding, with full life expectancy, switching transients having crest volt-
ages up to two times the peak of the capacitor rated voltage, and other transient overvoltages and overcur-
rents normally associated with the operation of shunt power capacitors on electric power systems as outlined
in IEEE Std 1036-1992.
The continuous and short time overvoltage capabilities of any capacitor element of a capacitor unit shall be
considered to be its share of the total unit voltage capability.
6. Manufacturing
Capacitors shall be thermally stable in accordance with the definition and operating conditions outlined in
7.9.
At a minimum, capacitors shall withstand the BIL given in Table 3, as demonstrated by the tests outlined in
7.7. For capacitor units having bushings with different BIL ratings, the BIL of the internal terminal to case
insulation must be equal to the highest BIL rating given on the capacitor unit nameplate.
Range of capacitor voltage ratings (terminal to terminal) V, rms Minimum BIL (kV)
216–1199 30*
1200–5000 75*
5001–15000 95
15001–20000 125
20001–25000 150
*Not applicable to 216–5000 indoor capacitors or housed equipment.
Capacitors shall be equipped with an internal discharge device that will reduce the residual voltage to 50 V
or less within the following time limits after the capacitor is disconnected from the peak of rated voltage:
600 V or less 1
Over 600 V 5
NOTE—The internal discharge device provided in capacitors should not be considered as a substitute for the
recommended practice of manually discharging the residual stored charge before working on capacitors.
Radio influence voltage generated by a capacitor shall not exceed 250 µV, as determined in accordance with
7.10.
6.5 Bushings
Single-phase capacitors shall have either one or two bushings. Three-phase capacitors shall have three or
four bushings.
The bushings of outdoor capacitors shall have minimum electrical characteristics in accordance with Table
5. At elevations higher than 1800 m9 above sea level, and/or in locations with severe contamination,
increased insulation withstand and/or creepage may be required to prevent bushing flashovers or excessive
leakage current.
96000 ft.
30** 51 10 6 30
75** 140 27 24 75
95 250 35 30 95
Some capacitor equipment (such as some fuseless and internally fused banks) may have different voltage
requirements on the two bushings of a capacitor unit. For these equipment, capacitors may have bushings
with different BIL ratings; one bushing shall be rated for the highest voltage to rack and the other for the
lower voltage to rack.
6.6 Terminals
Outdoor capacitors shall be provided with the following types of terminals, as specified by the user:
a) Clamp connector to accommodate a minimum range of conductor sizes from Number 8 solid
through Number 2 stranded, AWG, or
b) Threaded stud with 3/8 in x 16 or 1/2 in x 13 threads suitable for bolting directly to bus bars, or
c) Threaded stud with M12 or M16 (metric) threads suitable for bolting directly to bus bars.
Single-bushing outdoor capacitors shall have the bushing terminal as specified under 6.6.1 and the case shall
have a suitable connection point as the other terminal.
Indoor capacitors shall be provided with terminals consistent with current-carrying requirements in NFPA
70-2002.
Each (power) capacitor shall be provided with a permanent nameplate that includes, but is not limited to, the
following information:
a) Name of manufacturer.
b) Unique serial number.
c) Manufacturer’s type, model, style, or catalog number.
d) Year of manufacture.
e) Rated reactive power.
f) Rated voltage, rms.
g) Number of phases.
h) Rated frequency.
i) BIL (if applicable). For capacitors having bushings with two different BIL ratings, the nameplate
shall show both BIL ratings, e.g. 150/95 kV BIL.
j) Flammability classification and volume of insulating fluid.10
k) Statement that capacitor contains an internal discharge device.
6.7.2 Information to be supplied with internally fused capacitors or capacitor units for fuse-
less capacitor equipment
a) The number of series groups between the terminals and the number of parallel elements in each
series group.
b) Maximum number of individual fuse operations in one series group of the capacitor unit before the
capacitor unit must be removed from service, when the capacitor unit is operated at 110% of rated
voltage across its terminals. (Overvoltages on unfaulted capacitor units also need to be considered in
the setting of the protective relays.)
The number of series groups between the terminals of the capacitor unit.
Additional marking (decal or stick-on label) shall be visible from the ground. A blue marking shall be used
to designate non-polychlorinated biphenyl (non-PCB) liquid.
10In the U. S., OSHA (Occupational Safety and Health Administration) flammability classification. Elsewhere, equivalent flammability
designation based on the country of manufacture or supply.
The standard mounting hole spacing for capacitors rated 50 to 600 kvar and 2400 V or higher shall be 397
mm ± 1.6 mm (15 5/8 in ± 1/16 in) between centers of 11.1 mm (7/16 in) minimum-diameter holes.
Cantilever-mounted capacitors (both brackets on one surface of the capacitor case) shall accommodate M16
(or 5/8-in) mounting bolts at 457.2 mm ± 1.6 mm (18 in ± 1/16 in) between centers. Mounting hole dimen-
sions that differ from these, such as for capacitor units larger than 600 kvar may be agreed between the
manufacturer and purchaser.
Capacitors shall have provision for effective electrical bonding of the case to capacitor hangers or mounting
frame.
6.10 Color
Colors for capacitor cases and bushings shall be light gray per Munsell Notation 5.0BG 7.0/0.4 as defined in
ASTM D1535-01.
7. Testing
7.1 General
Production tests shall be performed by the manufacturer on each capacitor and shall include the following:
Design tests shall be performed by the manufacturer to demonstrate compliance of the design with various
parts of this standard. Capacitors shall first meet production test requirements before being subjected to
design tests. The design tests shall include the following:
Each capacitor shall withstand the following test voltages for at least 10 s. Test voltages shall be applied in
such a manner as to avoid transients.
Each capacitor shall, with its case and internal temperature at 25 °C ± 5 °C, withstand for at least 10 s a
terminal-to-terminal insulation test at a standard test voltage of either of the following:
For three-phase wye-connected units where there is a neutral bushing or the neutral is connected to the case,
the above testing for terminal-to-neutral shall be followed by a test at the square root of 3 times the above
standard test voltage between each pair of bushings (not including any neutral bushing) to test the phase-to-
phase insulation.
For three-phase wye-connected units where there is no neutral bushing and the neutral is not connected to
the case, the rated voltage is the phase-to-phase voltage of the capacitor unit. In order to test both the phase-
to-phase insulation and each leg of the wye at the appropriate voltage, the test voltage shall be 1.16 times the
above standard test voltage between each pair of bushings (2 ÷ square root of three ≈ 1.16).
For three-phase delta connected units, the rated voltage is the phase-to-phase voltage of the capacitor unit.
The test voltage shall be the above standard test voltage between each pair of bushings.
The capacitance shall be measured on each unit both before and after the application of the test voltage. The
initial capacitance measurement shall be at low voltage. The change in capacitance, as a result of the test
voltage, shall be less than either a value of 2% of the originally measured capacitance or that caused by fail-
ure of a single element of the particular design, whichever is smaller.
7.2.2 Terminals-to-case test (not applicable to capacitors having one terminal common to
the case)
Terminals-to-case tests shall be made on capacitors having all terminals insulated from the case. The appro-
priate test voltage from Table 6 shall be applied for at least 10 s between all insulated terminals connected
together and the case.
For capacitors having bushings with two different BIL ratings, this test shall be based on the bushing with
the lower BIL. The nameplate shall show both BIL ratings, e.g. 150/95 kV BIL.
Capacitance tests shall be made on each capacitor to demonstrate that it will deliver not less than rated reac-
tive power and not more than 110% of rated reactive power at rated voltage and frequency, corrected to a
capacitor case and internal temperature of 25 °C. Measurements made at other than 25 °C are corrected by
adjusting for temperature difference according to the established temperature relationship for the capacitor
tested. Capacitance measurements shall be traceable to the National Institute of Standards and Technology.
A suitable test shall be made on each capacitor to ensure that it is free from leaks.
A suitable test shall be performed on each capacitor to ensure that the internal discharge device will reduce
an initial residual voltage equal to the square root of 2 times rated voltage rms to 50 V or less in the time lim-
its specified in 6.3.
Loss measurement shall be made by the manufacturer on each capacitor to demonstrate that the capacitor
losses are equal to or less than WM as defined in 7.9.2.3.
Impulse tests shall be applied between terminals and case, with the terminals connected together. For capac-
itors having bushings with two different BIL ratings, this test shall be based on the bushing with the lower
BIL. The nameplate shall show both BIL ratings, e.g. 150/95 kV BIL.
Single bushing capacitors, of which the case forms one electrode, shall not be subjected to the impulse with-
stand test. When one principal terminal of the capacitor is connected to the case, the BIL requirements shall
not apply to the internal insulation assembly. The internal insulation assembly shall assure that the capacitor
will meet the requirements of 7.2.1 in order to demonstrate that the insulation is adequate for the highest ter-
minal-to-case (or terminal-to-terminal) voltage in the intended equipment. However, the bushing shall meet
all the requirements of 6.5 and the nameplate shall carry the applicable BIL.
The impulse voltage shall be 1.2/50 microsecond full wave, as described in 7.7.3, with a crest value given in
Table 5. The tolerance on the crest value shall be ± 3%.
The time to crest of a 1.2/50 microsecond impulse wave shall be measured as 1.67 times the time for the
voltage to rise from 30% to 90% of crest value. The tolerance on the time to crest shall be ± 30%. The time
to 0.5 crest value point on the tail of the wave shall be measured from the virtual time zero and shall be 40 to
50 microseconds. The virtual time zero shall be taken at the intersection of the zero voltage line and a line
drawn through points on the front of the wave at 30% and 90% of the crest value.
Bushing test voltages shall be applied in accordance with the test procedures specified in IEEE Std
C57.19.00-1991.
If no flashover occurs, the bushings shall be considered as having passed the test successfully.
The bushing passes the impulse test if no flashover occurs with the first three applications of the test voltage.
If any one, but not more than one, of three applications of the test voltage causes flashover, three additional
impulses shall be applied. If no additional flashover occurs, the bushings shall be considered as having
passed the test successfully.
The test capacitor shall be considered thermally stable if the hot-spot case temperature reaches and main-
tains a constant value within a variation of 3 °C for 24 h, under the test conditions described in 7.9.1 and
7.9.2.
One sample shall be selected as the test capacitor. Two other capacitors of the same ratings and having
approximately the same power factor and capacitance (at rated voltage, rated frequency, and case and inter-
nal temperatures at tS) as the test capacitor shall be selected for barrier capacitors (barrier capacitors are
capacitor units to be mounted adjacent to the test capacitor during the thermal stability test, as described in
7.9.2). Resistor models having the same power loss, thermal characteristics, and physical dimensions as the
test capacitor may be substituted for the barrier capacitors.
The test capacitor, selected as above, shall be mounted in an enclosure between the two barrier capacitors at
the manufacturer’s minimum recommended center-to-center spacing. The mounting position selected shall
be the recommended operating position that produces the highest internal temperatures.
The air inside the test enclosure shall be maintained at an average temperature of 46 °C and shall not be
force-circulated. The inside wall temperature of the enclosure shall be within ± 5 °C of the ambient temper-
ature in the enclosure. The ambient temperature shall be measured by means of a thermocouple on the case
or within the dielectric of an isolated unenergized capacitor, supported and positioned so that it is subjected
to the minimum possible thermal radiation from the three energized samples.
All three sample capacitors (or only the test capacitor if resistive barrier capacitors are used) shall be ener-
gized at a test voltage to be determined as follows:
WM
V T = 1.1 V R --------
-
WA
where
NOTE—WM does not correspond to an exact limit on either capacitance or power factor but does correspond to an exact
limit on their product. The quantity WM/WA reduces to a ratio of
(Maximum product of capacitance and power factor):(Measured product of capacitance and power factor)
WA is the actual power loss of the test capacitor. This loss shall be calculated using 110% of rated volt-
age rms and the actual capacitance and power factor of the test capacitor measured at rated voltage
and frequency and at a stated case and internal temperature tS.
tS is the manufacturer’s dielectric temperature limit under the conditions of this thermal stability test.
The test voltage (VT) calculated for this test shall be limited to a value that will result in operation of the test
capacitor at a maximum of 144% of its kvar rating. This voltage shall be maintained constant, within ± 2%
throughout the last 24 h of the test period.
The temperature of the test capacitor shall be measured by means of thermocouples attached to the case side-
wall and cover. All temperature measurements shall be accurate to within ± 1 °C.
Radio influence voltage (RIV) tests on capacitors shall be conducted in accordance with 7.10.1 through
7.10.5.
7.10.1 Equipment
The equipment and general method used in determining the RIV shall be in accordance with the recommen-
dations of the Joint Coordination Committee on Radio Reception of the Edison Electric Institute (EEI), the
Electronic Industry Association (EIA), and the National Electrical Manufacturing Association (NEMA) as
set forth in NEMA 107-1993.
The test voltage shall be of rated frequency and 115% of rated voltage rms of the capacitor.
7.10.3 Method
Capacitors having two or more bushings with the windings fully insulated from the case shall be tested with
the case grounded and with the voltage specified in 7.10.2 applied between all bushings connected together
and the case. Capacitors having only one bushing per phase with the case as the other terminal should not be
tested, as this type of construction precludes any meaningful RIV measurement due to the high capacitance.
7.10.4 Precautions
The following precautions should be observed when measuring the RIV of capacitors:
a) The capacitor shall be at approximately the same temperature as the room in which the tests are
made.
b) The capacitor bushings shall be dry and clean.
c) The capacitor shall be mounted in its recommended position with the manufacturer’s recommended
minimum clearance between the live parts and grounded surfaces.
The RIV, when measured in accordance with the foregoing at a frequency of 1 MHz, shall not exceed 250
µV.
The capacitor shall be energized at a direct current voltage equal to the peak of rated ac voltage. The decay
of the voltage, when de-energized, shall be measured by suitable means. The time for decay of residual volt-
age to 50 V or less shall not exceed 5 min for capacitors rated higher than 600 V or 1 min for capacitors rated
600 V or less.
Internally fused capacitors shall be subjected to one short-circuit discharge test, from a dc voltage of 1.7
times rated voltage through a gap situated as closely as possible to the capacitor, without any additional
impedance in the circuit (see note below).
The capacitance shall be measured before and after the discharge test. The difference between the two mea-
sured values shall be less than an amount corresponding to one internal fuse operation.
The discharge test may be made before or after the voltage test between terminals. However, if it is made
after the voltage test between terminals, a capacitance measurement at rated voltage shall be made after the
discharge test to detect fuse operation.
If, by agreement with the purchaser, capacitors are accepted with operated fuses, the voltage test between
terminals shall be made after the discharge test.
NOTE—It is permitted that dc charging voltage be generated by initially energizing with an ac voltage having a peak
value of 1.7 times rated voltage and disconnecting at a current zero. The capacitor is then immediately discharged from
this peak value. Alternatively, if the capacitor is disconnected at a slightly higher voltage, the discharge may be delayed
until the discharge resistor reduces the voltage to 1.7 times rated voltage.
The purpose of the short-circuit discharge test is to verify the integrity of the internal connections and
conductors of the capacitor operating under normal service conditions. The test shall be carried out by the
manufacturer for a particular design that is to be manufactured or on a similar design that has equal or
smaller size conductors and equal or higher energy level, as compared to the design to be manufactured,
when subjected to this test. As such, the testing of a particular rating will be applicable to a wide range of
capacitor ratings.
One unit shall be charged to a dc voltage 2.5 times rated rms voltage and then discharged. It shall be sub-
jected to five such discharges. Before and after the five discharges, the terminal-to-terminal capacitance shall
be measured at low voltage.
The discharge circuit shall have no inductive or resistive devices included. The discharge device may be a
switch or spark gap and may be situated up to one meter from the capacitor such that the total perimeter of
the external discharge loop is less than 3 meters. The conductors used to connect the capacitor to the dis-
charge device shall be of copper and shall have a cross-section of at least 10 mm2.
The difference in capacitance between the initial and final measurements shall be less than an amount corre-
sponding to either the shorting of an element or operation of an internal fuse.
Annex A
(informative)
Bibliography
[B1] IEEE 100, The Authoritative Dictionary of IEEE Standards Terms, Seventh Edition.11
11The IEEE products referred to in Annex A are trademarks belonging to the Institute of Electrical and Electronics Engineers, Inc.