0% found this document useful (0 votes)
27 views2 pages

Analytical Estimation of Short Circuit Axial Force - 4

1) The document analytically calculates the axial and radial forces exerted on the windings of a power transformer during short circuit conditions. 2) It uses the method of images to determine the magnetic flux density and models the transformer window region as a rectangular area containing conductor windings. 3) The calculations show that the short circuit currents and resulting forces on the secondary windings are larger than those on the primary windings. Graphs of the simulated short circuit currents and calculated forces are presented.

Uploaded by

amulya s
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views2 pages

Analytical Estimation of Short Circuit Axial Force - 4

1) The document analytically calculates the axial and radial forces exerted on the windings of a power transformer during short circuit conditions. 2) It uses the method of images to determine the magnetic flux density and models the transformer window region as a rectangular area containing conductor windings. 3) The calculations show that the short circuit currents and resulting forces on the secondary windings are larger than those on the primary windings. Graphs of the simulated short circuit currents and calculated forces are presented.

Uploaded by

amulya s
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

17518695, 2014, 2, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2013.0268 by National Medical Library The Director, Wiley Online Library on [15/11/2022].

See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
  are larger than primary windings. However, these forces
tn−1 t
should be calculated precisely for discussing and evaluating
Rpr i1sc (t)dt + i1sc (t)dt short circuit conditions accurately. It is notable that,
0 tn−1
applicable approaches have been presented to detect short
circuit fault in transformers [16, 17]. These methods can be
 
  tn−1 t
+ Lpr i1sc (t) − i1sc (0) + u(t)dt + u(t)dt utilised to protect transformers in different conditions.
0 tn−1 These methods can distinguish inrush currents with the

Dt   

  huge magnitude from short circuit currents to implement a
= Rpr j2 + i (t) + i1sc tn−1 + Lpr i1sc (t) − i1sc (0) reliable protection.
2 1sc
V1 
 
Dt     3 Analytical calculation of exerted axial and
+ j1 + u(t) + u tn−1 = m cos u − cos (vt + u)
2 v radial forces on power transformers windings
(18b)
Interaction between the winding currents which calculated in

tn−1 t 
  the previous part and the existing leakage flux in the winding
Rse i2sc (t)dt + i2sc (t)dt + Lse i2sc (t) − i2sc (0) regions which is estimated in this part, generate
0 tn−1 electromagnetic forces in transformers. Here, the method of
  images is utilised to obtain the magnetic flux density as a
Dt     
double-Fourier series [18]. The transformer window region
= Rse j3 + i2sc (t) + i2sc tn−1 + Lse i2sc (t) − i2sc (0)
2 has been exhibited in Fig. 4 in which all the four

Dt   
 boundaries have been assumed infinitely permeable. This
= j1 + u(t) + u tn−1 (18c) rectangular region contains an arrangement of a number of
2 rectangular conductors (q) carrying current. Based on the
method of images, an infinite number of images both in the
where V1m is the maximum magnitude of the applied primary x and y directions are made by the q conductors. The vector
voltage, ω is the angular supply frequency, θ is the angular potential (A) is described using Laplacian equation by
position. Furthermore, ξ1, ξ2 and ξ3 are defined as follows
tn−1 ∂2 A ∂2 A
Dt  + 2 = −m 0 J (20)
j1 = u(t)dt = u(0) + 2u(Dt) + 2u(2Dt) + · · · ∂x2 ∂y
0 2

+2u((n − 2)Dt) + u((n − 1)Dt) (19a) where J is the current density. This current density is
computed using magneto motive force of the primary
tn−1
Dt 
j2 = i1sc (t)dt =
i (0) + 2i1sc (Dt) + 2i1sc (2Dt) + · · ·
0 2 1sc

+2i1sc ((n − 2)Dt) + i1sc ((n − 1)Dt) (19b)
tn−1
Dt 
j3 = i2sc (t)dt = i (0) + 2i2sc (Dt) + 2i2sc (2Dt) + · · ·
0 2 2sc

+2i2sc ((n − 2)Dt) + i2sc ((n − 1)Dt) (19c)

The necessary variables which include short circuit currents


are calculated by solving (12), (15), (16), (18a)–(19c) as
non-linear algebraic equations. Fig. 3 illustrates simulated
short circuit currents using the above explained method.
According to Fig. 3, the enormous currents are flowed
through the windings which generate enormous forces.
Comparison between primary and secondary short circuit
currents reveals that the peak and steady state values of the
secondary windings are larger than primary windings. So, it
is predicted that exerted forces to the secondary windings Fig. 4 Transformer window region with conductors

Fig. 3 Analytical simulation of short circuit currents (left) primary and (right) secondary

IET Gener. Transm. Distrib., 2014, Vol. 8, Iss. 2, pp. 250–260 255
doi: 10.1049/iet-gtd.2013.0268 & The Institution of Engineering and Technology 2014
17518695, 2014, 2, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2013.0268 by National Medical Library The Director, Wiley Online Library on [15/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org

Fig. 5 Analytical simulation of forces on the power transformer winding


a Axial-LV (steady-state)
b Axial-HV (steady-state)
c Radial-LV (steady-state)
d Radial-HV (steady-state)
e Axial-LV (transient-state)
f Axial-HV (transient-state)
g Radial-LV (transient-state),
h Radial-HV (transient-state)

256 IET Gener. Transm. Distrib., 2014, Vol. 8, Iss. 2, pp. 250–260
& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-gtd.2013.0268

You might also like