01 - Advanced Process Control
01 - Advanced Process Control
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-1
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Introduction
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-2
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Introduction
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-3
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Introduction
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-4
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Introduction
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-5
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Introduction
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-6
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-7
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Process Overview
F
3105 To C-1
Hydrogen Addition
and Preheat CW
TA TA < T B
T
3510 D-102
C-101
E-201 TB
F
Naphtha Hydrotreating F 3503
Preheat 3502
F-100 Furnace
D-101 H 2S Reactor L
H 2 from D-7 F
3501
3501
T
3511 L To Depropanizer
High
3500
Temperature E-101R
DPIC-501
HVN to E-20
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-8
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Heat Exchanger Detail
NHT Unit H 2S
Stripper - Existing
Preheat/Reboil T C-101
Controls 3510
E-201
F
NHT Unit
3502
Preheat
F-100
D-101
T
3511
E-101R
DPIC-501
F
E-100 3504
E-102
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-9
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Observations
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-10
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
General Control Issues
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-11
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Solution
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-12
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Solution (continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-13
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Bypass Control
NHT Unit H 2S Stripper -
Resolution of the Reboiler
and Feed Temperature T C-101
Control Problems 3510
E-201
F
NHT Unit
3502
Preheat
F-100
D-101
T T
3500 3511
E-101R
Split
Range
A B
F
E-100 3504
E-102
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-14
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
Bypass TIC Set Point
NHT Unit H 2S Stripper -
Constraint Control for
T3500 Set Point T C-101
3510
SP
VPC
T 3511 T
3500 SP = 5% Open 3511
(Valve A)
Split
Range
E-101R
A B
F
E-100 3504
E-102
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-15
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-16
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Example
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-17
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-19
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-20
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
Control Tool Chart
Process Control - Problem/Technique Matrix
Process Control Technique
Problem
PID Split Nonlinear Process Cascade Override/ Feedforward Inferential Multivariable, Decoupling
Tuning Range Controller Linear- Constraint Predictive
ization Control
Dynamics
- Deadtime √ √ √
- Stability √ √ √ √
Nonlinearity
- Gains √ √ √
- Dynamics √ √
Variables
- MV
- Limits √ √ √
- Disturb. √
- CV
- Unmeas. √
- Limits √ √
- Interact. √ √ √
- DV √ √ √ √
changes
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-21
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-22
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-23
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-24
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Process Dynamics
Endothermic Reaction
CV
Deadtime
MV Controller in Manual
Time
TIC
MV: Flow Rate of Fuel Gas
CV: Reactor Outlet Temperature
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-25
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Dynamics
Controller Tuning
∫
Controller Output = G e + (1 / T i) e dt - T d
de
o dt
where: G = Controller gain
e = Error (difference between SP and CV)
Ti = Integral time constant
Td = Derivative time constant
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-26
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Dynamics
Cascade Control
The effects of
disturbances in the
manipulated flow stream
such as pressure changes
are measured and
controlled so that the
important controlled
variable (reactor outlet
Set Point
temperature) is not upset.
FIC
Secondary Controller
Primary Controller
TIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-27
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Dynamics
Feedforward Control
Feedback
Signal
Σ
Feedforward
Signal
Set Point
FIC
TIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-28
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Dynamics
Multivariable Predictive Control (MPC)
TT
LIC
FIC FIC
Targets:
Top Composition
MPC
TT
Bottom Composition
FIC
LIC
Composition
FIC
By design, the Multivariable Predictive Controller (MPC) handles many of the problems
encountered in process control. Feedforward control action is easily added to the
controller to improve the control system’s dynamic response to disturbances.
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-29
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-30
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Non-Linearity
n What is “non-linearity?”
– “Linearity” addresses the relationship
between controller and process gains
– The gain is the ratio of the change in output
caused by a change in input
– Most controllers are linear - once they are
tuned, the gains are constant
– Most processes are not linear
n How the controls deal with this problem is
the subject of this section
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-31
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Non-Linearity
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-32
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Non-Linearities
Process Linearization
PI FIC
Because the pump’s head (discharge pressure) drops as the flow increases, the change in flow for a change in valve
flow area is not the same at high flow rates as it is at low flow rates. This is a nonlinear process if the flow area
and valve travel have a linear relationship - “ a linear control valve characteristic.” Controller tuning determined
at high flow rates may be unstable at low flow rates.
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-33
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Non-Linearities
Process Linearization (continued)
Pump Discharge Pressure
Flow
Valve
Open Area Installed Flow
Characteristic
Discharge
Pressure Valve Open Area
Controller Output
PI FIC
With an “equal percentage valve,” the nonlinear valve characteristic compensates for the
nonlinear process characteristic. Controller tuning is more “robust.” No matter what
the flow rate is, the control loop performs well.
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-34
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Non-Linearities
Controller Gain Scheduling
Controller
Gain
Flow Rate
Controller Gain vs. Flow
Gain
PI Filter FIC
If a linear valve must be used, another way to linearize the overall system is needed. Because the
process gain decreases at higher flow rates because the pump’s discharge pressure drops, higher
controller gain is needed as flow rate increases. The filter is added to smooth the noisy flow signal.
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-35
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-36
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MV Limits and Disturbances
n MV Limits
– Control applications
– Split range (example - furnace firing)
– Control at the limit (example - distillation)
Ÿ Valve position control
Ÿ Tuning
– MPC
n MV Disturbances
– Cascade (example - reboiler)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-37
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MV Limits
Split Range
100% A B C
Valve Opening
FI 0
0 100%
Refinery A PIC Output
Fuel Gas
FI PIC FIC
Propane B
FI
Fuel Gas Header
To Other Users
Purchased C
Natural Gas
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-38
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MV Limits
Controlling at the Limits
What should be
the SP value? PIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-39
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MV Limits
Valve Position Controller
VPC
PIC
Cooling Water
Temperature
Valve Opening
Tower Pressure
Time
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-40
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MV Disturbances
Cascade Control
TIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-41
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MV Disturbances
Cascade Control
Because the MV
disturbances are handled
by the secondary
controller, it is usually
possible to tune the
primary controller with
higher gain resulting in
Set Point better performance.
FIC
Secondary Controller
Primary Controller
TIC
The effects of disturbances in the manipulated flow
stream such as pressure changes are measured and
controlled so that the important controlled variable
(reactor outlet temperature) is not upset.
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-42
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Limits and Inference
n CV Limits
– Variables held within limits
– Override or constraint controls (example -
TWT)
n CV Inference
– Alternative to direct measurement
– Property estimation
— Rigorous
— Neural networks
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-43
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Limits
Override/Constraint Control
TIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-44
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Limits
Override/Constraint Control
(continued)
Tube Wall Temperature
Controller
Low SS TIC
Signal
Selector
Transfer Line
Temperature
Controller
TIC
As long as the tube wall temperature is below its limit, the transfer line temperature
controller manipulates the furnace firing rate. However, if the tube wall temperature
exceeds its limit. the tube wall temperature controller will “override” the transfer line
temperature controller to reduce firing. Unlike a shutdown, the transfer line
temperature will only drop enough to keep the tube wall temperature at its limit.
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-45
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-46
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Disturbances
n Unmeasured Disturbances
– Feedback control
– Tuning - Aggressive
– MPC
n Measured Disturbances
– Feedforward control
– MPC
n Special Case - Level Control
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-47
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Unmeasured Disturbances
Feedback Control
One of the best features of feedback control is that no matter
what disturbances cause the controlled variable to deviate from
the set point, the controller will try to bring the CV back to the
target. In this example, the disturbances might come from
changes in the charge rate and composition, changes in the fuel
composition and header pressure, changes in the reactor catalyst
activity or internal flow, and even changes in air temperature
and soot build-up on the heater tubes. To get better performance
the disturbances causing the worst problems could be measured
and control action taken before the disturbance upsets the
Transfer Line Temperature. This is feedforward control.
TIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-48
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Measured Disturbances
Feedforward Control
TIC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-49
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Measured Disturbances
Feedforward Control
Feedback
Signal
Σ
Feedforward
Signal
FIC
TIC
FI
Emphasis on Emphasis on
LIC
level control flow control
FI
Level
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-51
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
APC Concepts
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-52
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Interaction
n CV Interaction
– Blending Example
– Control Application
— Variable pairing selection
— Tuning
— Decoupling (example - crude fractionator)
— MPC
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-53
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Interaction
(continued)
n Blending Example
Which valve
should each
controller
manipulate?
MV1
CV1 CV2
Mixer
MV2
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-54
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Interaction
(continued)
n Blending Example
MV1
Mixer
CV1 CV2
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-55
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
CV Interaction
(continued)
MV1 MV2
Flow Target
MPC
Composition Target
CV1 CV2
Mixer
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-56
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
n Basic Operation
– Prediction of a set of MV changes that will
cause the CVs to be at their targets at some
time in the future
– “Feedback” is achieved by periodically
recalculating the control moves
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-58
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-59
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
CV1
CV2
CV3
MV1
What MV changes must be made at t = 0 to drive the
MV2 CVs to their set points at some time in the future?
MV3
t = -1 t=0
Time
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-60
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
The MV changes are made at t=0 with the expectation that CV2
will move back to its target after an initial deadtime and that CV1
and CV3 will remain at their target values. After making the MV
changes, the controller waits for the next execution cycle.
CV1
CV2
CV3
MV1
MV2
MV3
t = -1 t=0 t=2
Time
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-61
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
At t=2 after one time interval (which is typically less than the time expected for all the
CVs to reach their targets), the controller again samples the CVs. The actual CVs may
deviate from their expected values because the predictions are in error or because
other disturbances have upset the process as appears to have happened for CV2.
CV1
CV2
CV3
MV1
MV2
MV3
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-62
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
No matter what caused the deviations from the CV targets, new control moves are
calculated and applied based on the dynamic response models which are part of the
controller. This sequence of control calculations is repeated indefinitely.
CV1
CV2
CV3
MV1
MV2
MV3
Time
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-63
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
CV1
CV2
CV3
MV1
Looking at the problem in another way, why can’t
MV2 a steady state optimization with steady state
process models be used to determine the new MVs?
MV3
t=0
Time
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-64
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC
(continued)
CV1
A
?
CV2 B
C
CV3
MV1
...because past history does make
MV2 a difference in what MVs will be
calculated!
MV3
t=0
Time
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-65
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC Controller
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-66
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
MPC Controller
(continued)
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-67
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Summary
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-68
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.
Summary
(continued)
n Control Concepts
– Disturbance minimization
– Feedback and feedforward
– Control tools matched to control problems
– MPC is the first truly “digital” control tool
n Application of Engineering Knowledge to
Operations
2003 ENGINEERING DESIGN SEMINAR – LIMITED DISTRIBUTION: This material is UOP LLC technical information of a confidential EDS-03/APC-69
nature for use only by personnel within your organization requiring the information. The material shall not be reproduced in any manner or
distributed for any purpose whatsoever except by written permission of UOP LLC and except as authorized under agreements with UOP LLC.