The document summarizes the register map for a Gutor PXC UPS system. It includes 3 notes on data transmission and supported functions. The register map contains 62 registers numbered 40001 to 40062 with associated address, data type, units and module support. Registers provide system information like load percentage, power levels, voltages and currents for output, input and bypass systems.

Uploaded by

Jose Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views6 pages

Mbpn-Ar6ava R1 en

The document summarizes the register map for a Gutor PXC UPS system. It includes 3 notes on data transmission and supported functions. The register map contains 62 registers numbered 40001 to 40062 with associated address, data type, units and module support. Registers provide system information like load percentage, power levels, voltages and currents for output, input and bypass systems.

Uploaded by

Jose Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

GUTOR PXC Register Map 990-5920A

Notes:
1. 16-bit registers are transmitted MSB first (i.e. big-endian).
2. "Absolute Starting Register Address" = 0 (the column heading used in this table) is equivalent to "Register 40001 for holding registers" in Modicon terminology, which is address zero when transmitted over the wire.
3. Data format is in 0xFFFF.(hexadecimal)
4. Reserved Fields are filled with 0.

The Gutor modbus interface can support modbus queries with the following restrictions:
1. Only Modbus RTU is supported.
2. Baud rates of 9600 and 19200 with parity settings of odd,even and none are supported.
3. Modbus function code 1 and 3 are serviced.

Absolute Starting
Modicon Absolute Starting Register Address, Data Point Valid Response Supported Modules
Standard Register (Decimal) Multiply Divide
Register Address, Length Reading Reading
Number (Hexadecimal) Bit # registers Type By: By:
System Rating
System load in percent (% of VA) :
0 Percent of UPS power 1 UINT16 %VA
40001 0x0000 capacity presently used. 10
System load in percent (% of W) :
40002 Percent of UPS power
0x0001 1 capacity presently used. 1 UINT16 10 %W
40003 0x0002 2 Apparent system load 1 UINT16 10 kVA
40004 0x0003 3 Real system load 1 UINT16 10 kW
40005 0x0004 4 Output apparent power L1 1 UINT16 10 kVA
40006 0x0005 5 Output apparent power L2 1 UINT16 10 kVA
40007 0x0006 6 Output apparent power L3 1 UINT16 10 kVA
40008 0x0007 7 Output Real power L1 1 UINT16 10 kW
40009 0x0008 8 Output real power L2 1 UINT16 10 kW
40010 0x0009 9 Output real power L3 1 UINT16 10 kW
40011 0x000A 10 Output power factor L1 1 UINT16 100 1
40012 0x000B 11 Output power factor L2 1 UINT16 100 1
40013 0x000C 12 Output power factor L3 1 UINT16 100 1

40014 0x000D 13 1 UINT16


Total output load in percent (% of VA) :
40015 only available with a %VA
0x000E 14 redundant system. 1 UINT16 10
Total output load in percent (% of W) :
15
only available with a redundant system.
40016 0x000F 1 UINT16 10 %W
Total output load (VA) : only available
VA
40017 0x0010 16 with a redundant system. 1 UINT16 10
Total output load (W) : only available
40018
0x0011 17 with a redundant system. 1 UINT16 10 W
Output
40019 0x0012 18 Output Frequency 1 UINT16 10 Hz
40020 0x0013 19 Output Voltage L1(phase L1 to L2) 1 UINT16 10 Volts
40021 0x0014 20 Output Voltage L2(phase L2 to L3) 1 UINT16 10 Volts
40022 0x0015 21 Output Voltage L3(phase L3 to L1) 1 UINT16 10 Volts
40023 0x0016 22 Output current L1 1 UINT16 10 Ampere
40024 0x0017 23 Output current L2 1 UINT16 10 Ampere
40025 0x0018 24 Output current L3 1 UINT16 10 Ampere
40026 0x0019 25 8
Input
40035 0x0022 34 Input Frequency 1 UINT16 10 Hz
40036 0x0023 35 Input Voltage L1(phase L1 to L2) 1 UINT16 10 Volts
40037 0x0024 36 Input Voltage L2(phase L2 to L3) 3 UINT16 10 Volts
40038 0x0025 37 Input Voltage L3(phase L3 to L1) 1 UINT16 10 Volts
40039 0x0026 38 6
40045 0x002C 44 Input current L1 1 UINT16 10 Ampere
40046 0x002D 45 Input current L2 1 UINT16 10 Ampere
40047 0x002E 46 Input current L3 1 UINT16 10 Ampere
40048 0x002F 47 9
Bypass
40057 0x0038 56 Input Bypass Frequency 1 UINT16 10 Hz
Input Bypass Voltage L1(phase L1 to
40058 0x0039 57 1 Volts
L2) (0 if not available) UINT16 10
Input Bypass Voltage L2(phase L2 to
40059
0x003A 58 L3) (0 if not available) 1 UINT16 10 Volts
Input Bypass Voltage L3(phase L3 to
40060 59
0x003B L1) (0 if not available) 1 UINT16 10 Volts
Input Bypass current L1 (0 if not
40061 1
0x003C 60 available) UINT16 Ampere
Input Bypass current L2 (0 if not
40062 61
0x003D available) 1 UINT16 Ampere
Input Bypass current L3(0 if not
40063 1
0x003E 62 available) UINT16 Ampere
40064 0x003F 63 6
Battery
40071 0x0046 70 Battery Current 1 UINT16 10 Ampere
40072 0x0047 71 Battery Voltage 1 UINT16 10 Volts
40073 0x0048 72 18
Temperature
40090 0x0046 89 Temperature Sensor 1(if available) 1 UINT16 1 °C
40091 0x0047 90 2
40093 0x005A 92 Temperature T001(if available) 1 UINT16 1 °C
40094 0x005B 93 Temperature T401(if available) 1 UINT16 1 °C
40095 0x005C 94 Temperature T501(if available) 1 UINT16 1 °C
40096 0x005D 95 149
Digital Values
read coil registers 001 - 016 : The
40245 registers are lined up the following way 1
16-13 12-9 8-5 4-1
0x00F4 244 1 UINT16
40246 0x00F5 245 read coil registers 017 - 032 1 UINT16 1
40247 0x00F6 246 read coil registers 033 - 048 1 UINT16 1
40248 0x00F7 247 read coil registers 049 - 064 1 UINT16 1
40249 0x00F8 248 read coil registers 065 - 080 1 UINT16 1
40250 0x00F9 249 read coil registers 081 - 096 1 UINT16 1
40251 0x00FA 250 read coil registers 097 - 112 1 UINT16 1
40252 0x00FB 251 read coil registers 113 - 128 1 UINT16 1
40253 0x00FC 252 read coil registers 129 - 144 1 UINT16 1
40254 0x00FD 253 read coil registers 145 - 160 1 UINT16 1
40255 0x00FE 254 read coil registers 161 - 176 1 UINT16 1
40256 0x00FF 255 read coil registers 177 - 192 1 UINT16 1
40257 0x0100 256 read coil registers 193 - 208 1 UINT16 1
Notes:
Notes:
1. 16-bit registers are transmitted MSB first (i.e. big-endian).
2. "Absolute Starting Register Address" = 0 (the column heading used in this table) is equivalent to "Register 00001 for coil registers" in Modicon terminology, which is address zero when transmitted over the wire.
3. Data format is in 0xFFFF.(hexadecimal)
4. Reserved Fields are filled with 0.

The Gutor modbus interface can support modbus queries with the following restrictions:
1. Only Modbus RTU is supported.
2. Baud rates of 9600 and 19200 with parity settings of odd,even and none are supported.
3. Modbus function code 1 and 3 are serviced.
4. Data format is in boolean
5. Value of 1 indicated respective individual status or alarm is active.
6. Reserved Fields are filled with 0.

Absolute
Modicon Absolute Starting Starting Data Point Valid Response Supported Modules
Standard Register Register Multiply Divide
Register Address, Address, Length Reading Reading
Number (Hexadecimal) (Decimal) Bit # registers Type By: By:

1 0x0000 0 22
System Status / SBS Status
1 : System in standby
System switched on 1 BOOLEAN
23 0x0016 22 0 : System is not in standby
Standby 1 : System in Standby
1 BOOLEAN
24 0x0017 23 0 : System is not in standby
Normal Operation 1 : the system is in normal operation
1 BOOLEAN
25 0x0018 24 0 : the system is not in normal operation.
Battery operation 1 : the system is in battery operation
1 BOOLEAN
26 0x0019 25 0 : the system is not in battery operation.
Bypass operation 1 : Static bypass switch ON
1 BOOLEAN 0 : Static bypass switch OFF.
27 0x001A 26
1 : The battery charger has been set to
1 BOOLEAN ‘Initial charge’ mode.The batteries are
28 0x001B 27 Initial charge charged with initial charge voltage.
1 : The battery charger has been set to
1 BOOLEAN ‘Initial charge’ mode.The batteries are
29 0x001C 28 Float charge charged with initial charge voltage.
Boost charge 1 : The battery charger has been set to ‘Float
1 BOOLEAN charge’ mode.The batteries are charged with
30 0x001D 29 float charge voltage.
Cyclic charge 1 : The battery charger has been set to
1 BOOLEAN 'Cyclic charge’ mode.The batteries are
31 0x001E 30 charged with cyclic charge voltage.
32 0x001F 31 7
Temporary Static bypass 1 : The system is in static bypass operation
1 BOOLEAN
39 0x0026 38 due to a fault.
Requested Static bypass 1 : The system is in static bypass operation
1 BOOLEAN
40 0x0027 39 due to a user request.
41 0x0028 40 SBS Error 1 BOOLEAN
42 0x0029 41 12
Breaker Status / MBS Status
1 : The rectifier mains input switch Q001 is
closed
1 BOOLEAN
0 : The rectifier mains input switch Q001 is
54 0x0035 53 Q001 closed open.
55 0x0036 54 1
1 : The battery switch Q201 is closed
56 0x0037 55 Q201 closed 1 BOOLEAN
0 : The battery switch Q201 is Open.
1 : The bypass mains input switch Q501 is
closed
1 BOOLEAN
0 : The bypass mains input switch Q501 is
57 0x0038 56 Q501 closed open.
58 0x0039 57 5
1 : The UPS output switch Q692 is closed
1 BOOLEAN
63 0x003E 62 Q692/Q694 closed (if available) 0 : The UPS output switch Q692 is open.
64 0x003F 63 1
1 : The load is supplied from the bypass. The
inverter output is separated from the load.
1 BOOLEAN
The bypass input of the UPS is still
65 0x0040 64 Q528 closed supplied with bypass voltage.
1 : The load is supplied from the bypass. The
inverter output is separated from the load.
1 BOOLEAN
The bypass input of the UPS is not supplied
66 0x0041 65 MBS: BYPASS with bypass voltage.
1 : The load is supplied from the inverter,
1 BOOLEAN
67 0x0042 66 MBS: AUTO normal or battery operation.
Temperature Status / Fan Failure / PM HW Failure
1 : Overtemperature in PM or transformers
1 BOOLEAN
68 0x0043 67 Overtemperature detected (if available)
69 0x0044 68 2 BOOLEAN
1 : Overtemperature on the rectifier mains
1 BOOLEAN
71 0x0046 70 T001 Overtemperature transformer.
1 : Overtemperature on the output
1 BOOLEAN
72 0x0047 71 T401 Overtemperature transformer.
1 : Overtemperature on the bypass
1 BOOLEAN
73 0x0048 72 T501 Overtemperature (if available) transformer.
Battery temperature 1 : The battery temperature exceeds the
1 BOOLEAN
74 0x0049 73 warning programmed warning level.
Battery temperature 1 : The battery temperature exceeds the
1 BOOLEAN
75 0x004A 74 shutdown programmed shutdown level.
1 : The temperature sensor, connected to
1 BOOLEAN the external connection board, is over the
76 0x004B 75 Temperature 1 warning temperature warning level
77 0x004C 76 2
1 : The mains input transformer temperature
T001 Temperature 1 BOOLEAN
sensor PT100 is not connected or shorted
79 0x004E 78 sensor fault
T401 Temperature 1 : The output transformer temperature
1 BOOLEAN
80 0x004F 79 sensor fault sensor PT100 is not connected or shorted
T501 Temperature 1 : The bypass transformer temperature
1 BOOLEAN
81 0x0050 80 sensor fault sensor PT100 is not connected or shorted
1 : Fan failure in the UPS system
1 BOOLEAN
82 0x0051 81 Fan failure (transformer-, SBS- or power module- fan)
83 0x0052 82 6
Faults
1 : The digital input of Emergency Power Off
Emergency Power Off 1 BOOLEAN (EPO) is activated (contact open) or the EPO
89 0x0058 88 (EPO) wiring is disconnected
90 0x0059 89 1
1 : General PSU fault (Alarm if any PSU fault
1 BOOLEAN
91 0x005A 90 PSU fault occur).
1 : General Mains fault (Alarm if any Mains
92 1 BOOLEAN
0x005B 91 General Mains fault fault occur)
1 : The rectifier mains voltage is out of
1 BOOLEAN
93 0x005C 92 Mains RMS fault tolerance.
1 : The rectifier mains voltage on primary
side of the input transformer is out of
94 1 BOOLEAN
tolerance. This event is only active if a
0x005D 93 Mains input RMS fault transformer is installed.
95 0x005E 94 6
1 : General Bypass fault (Alarm if any
101 1 BOOLEAN
0x0064 100 General Bypass fault Bypass fault occurs)
102 0x0065 101 Bypass RMS fault 1 BOOLEAN 1 : The bypass voltage is out of tolerance.
1 : The bypass mains voltage on primary
side of bypass transformer is out of
103 1 BOOLEAN tolerance. This event is only active if a
transformer and the bypass measurement is
0x0066 102 Bypass input RMS fault installed
104 0x0067 103 4
1 : General Output fault (Alarm if any Output
108 1 BOOLEAN
fault occurs, overload or voltage issue).
0x006B 107 General Output fault
1 : The output voltage on the secondary side
1 BOOLEAN
of the output transformer is out of tolerance.
109 0x006C 108 Output RMS fault
1 : The UPS output voltage is out of
Inverter output RMS fault 1 BOOLEAN
110 0x006D 109 tolerance.
111 0x006E 110 5
1 : The UPS output is overloaded (>100%) or
Output overloaded 1 BOOLEAN
116 0x0073 115 the inverter current limiter is active.
117 0x0074 116 2
0: negative; the battery is discharged
Battery current positive 1 BOOLEAN
119 0x0076 118 1: positive; the battery is charged.
120 0x0077 119 1
1 : The battery voltage is out of tolerance or
Battery: Warning or error 1 BOOLEAN the runtime is too
121 0x0078 120 short.
1 : The interface has detected a battery earth
Battery earth fault 1 BOOLEAN
122 0x0079 121 fault (if available).
1 : Battery voltage above the high battery
High Battery shutdown 1 BOOLEAN
123 0x007A 122 shut-down level.
1 : Battery voltage above the ‘High battery
High Battery warning 1 BOOLEAN warning’ level (no warning in battery
124 0x007B 123 operation).
1 : Battery voltage below the ‘Low battery
Battery discharged 1 BOOLEAN
125 0x007C 124 warning’ level.
1 : Battery voltage below ‘Low battery shut-
Low Battery shutdown 1 BOOLEAN
126 0x007D 125 down’ level.
1 : The interface has detected a battery
Battery earth fault positive 1 BOOLEAN
127 0x007E 126 positive earth fault (if available).
1 : The interface has detected a battery
Battery earth fault negative 1 BOOLEAN
128 0x007F 127 negative earth fault (if available).
129 0x0080 128 11
1 : Rectifier or charger is off because of a
Rectifier fault / error 1 BOOLEAN
140 0x008B 139 fault.
141 0x008C 140 00141 B Inverter fault / error 1 BOOLEAN 1 : Inverter is off because of a fault
142 0x008D 141 12
External Connection Board Input Status
0 = open
Input status Ecb 1 1 BOOLEAN
154 0x0099 153 1 = closed
0 = open
Input status Ecb 2 1 BOOLEAN
155 0x009A 154 1 = closed
156 0x009B 155 16
HMI Alarm LED Status
0 = off
HMI alarm LED 1 1 BOOLEAN
172 0x00AB 171 1 = on
0 = off
HMI alarm LED 2 1 BOOLEAN
173 0x00AC 172 1 = on
0 = off
HMI alarm LED 3 1 BOOLEAN
174 0x00AD 173 1 = on
0 = off
HMI alarm LED 4 1 BOOLEAN
175 0x00AE 174 1 = on
0 = off
HMI alarm LED 5 1 BOOLEAN
176 0x00AF 175 1 = on
0 = off
HMI alarm LED 6 1 BOOLEAN
177 0x00B0 176 1 = on
0 = off
HMI alarm LED 7 1 BOOLEAN
178 0x00B1 177 1 = on
0 = off
HMI alarm LED 8 1 BOOLEAN
179 0x00B2 178 1 = on
0 = off
HMI alarm LED 9 1 BOOLEAN
180 0x00B3 179 1 = on
0 = off
181 0x00B4 180 HMI alarm LED 10 1 BOOLEAN
1 = on
0 = off
HMI alarm LED 11 1 BOOLEAN
182 0x00B5 181 1 = on
0 = off
HMI alarm LED 12 1 BOOLEAN
183 0x00B6 182 1 = on
0 = off
HMI alarm LED 13 1 BOOLEAN
184 0x00B7 183 1 = on
0 = off
HMI alarm LED 14 1 BOOLEAN
185 0x00B8 184 1 = on
0 = off
HMI alarm LED 15 1 BOOLEAN
186 0x00B9 185 1 = on
External Connection Board Output Status
0 = open
ECB Common Alarm 1 BOOLEAN
187 0x00BA 186 1 = closed
0 = open
ECB Output 1 1 BOOLEAN
188 0x00BB 187 1 = closed
0 = open
ECB Output 2 1 BOOLEAN
189 0x00BC 188 1 = closed

You might also like