Im - 1044 - 110711 Iom
Im - 1044 - 110711 Iom
Im - 1044 - 110711 Iom
Models WSC,WDC,WCC,HSC
(Includes High Voltage 10/11kV WDC/WCC models)
Hazard Identification
! DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
! WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not
avoided.
! CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
Document: IM 1044
Issue Date: September 2009
Revision Date: November 2011
Replaces: August 2011
©2011 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to make
changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies:
BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a
license granted by Echelon Corporation; ElectroFin from AST ElectroFin Inc.; Modbus from Schneider Electric; FanTrol, MicroTech II, Open Choices, and
SpeedTrol from McQuay International; Loctite from Henkel Company; 3M, Scotchfil and Scotchkote from the 3M Company; Victaulic from Victaulic Company;
Megger from Megger Group Limited.
Unit Control
Panel Rigging
Compressor Control
Panel, At Rear Locations
(6) Available
Rigging
Locations
(6) Available
Evaporator
Compressor Starter,
Mounting Optional
Condenser
Oil Sump,
Pump, Heaters
Motor
Terminal Box
Rigging
Eyes
Rigging
Eyes
Condenser
Dual Relief
Valves
Common Oil
Cooler Water Lubrication &
Compressor Condenser
Connections
Control Boxes
Notes:
1. Chilled water and condenser connection location can vary. Check markings on unit or consult unit certified drawings for connection
locations on specific units.
2. WCC two-circuit units have separate evaporator and condenser relief valves on each circuit.
Note: Units are shipped with refrigerant and oil valves closed to isolate these fluids for shipment.
Valves must remain closed until start-up by the McQuay technician.
Nameplates
There are several identification nameplates on the chiller:
The unit nameplate is located on the side of the Unit Control Panel. It has a Style No. XXXX and Serial No.
XXXX. Both are unique to the unit and will identify it. These numbers should be used to identify the unit for
service, parts, or warranty questions. This plate also lists the unit refrigerant charge.
Vessel nameplates are located on the evaporator and condenser. Along with other information, they have a
National Board Number (NB) and serial number, either of which identify the vessel (but not the entire unit).
A compressor nameplate is located on the compressor itself and contains identification numbers.
65.0
44 LChWT
42 LChWT
60.0 46 LChWT
55.0
50.0
ECWT, F
45.0
40.0
35.0
30.0
0 10 20 30 40 50 60 70 80 90 100 110
Percent Load
65.0
44 LChWT
42 LChWT
60.0 46 LChWT
55.0
50.0
ECWT, F
45.0
40.0
35.0
30.0
0 10 20 30 40 50 60 70 80 90 100 110
Percent Load
For example; at 44F LWT, 10 degree F Delta-T, and 50% full load operation, the entering condenser water
temperature could be as low as 50.5F. This provides excellent operation with water-side economizer systems.
Depending on local climatic conditions, using the lowest possible entering condenser water temperature may
be more costly in total system power consumed than the expected savings in chiller power would suggest, due
to the excessive fan power required.
Cooling tower fans must continue to operate at 100% capacity at low wet bulb temperatures. As chillers are
selected for lower kW per ton, the cooling tower fan motor power becomes a higher percentage of the total
peak load chiller power. McQuay’s Energy Analyzer program can optimize the chiller/tower operation for
specific buildings in specific locales.
Even with tower fan control, some form of water flow control, such as tower bypass, is recommended.
Figure 5 illustrates two temperature actuated tower bypass arrangements. The “Cold Weather” scheme provides
better startup under cold ambient air temperature conditions. The check valve may be required to prevent
entraining air at the pump inlet.
The piping must be supported to eliminate weight and strain on the fittings and connections. Piping must also be
adequately insulated. A cleanable 20-mesh water strainer must be installed in both water inlet lines. Sufficient
shutoff valves must be installed to permit draining the water from the evaporator or condenser without draining
the complete system.
Tee
If flow switches, by themselves, are being used, electrical connections in the Unit Control Panel must be made
from the common T3-S terminal to terminal CF for the condenser switch and T3-S to terminal EF for the
evaporator switch. See Figure 19, Field Wiring Diagram on page 32. The normally open contacts of the flow
switch must be wired between the terminals. Flow switch contact quality must be suitable for 24 VAC, low
current (16ma). Flow switch wire must be in separate conduit from any high voltage conductors (115 VAC and
higher).
Table 1, Flow Switch Flow Rates
Pipe Size inch 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8
(NOTE) 204 (5)
mm 32 (2) 38 (2) 51 63 (3) 76 102 (4) 127 (4) 153 (4)
gpm 5.8 7.5 13.7 18.0 27.5 65.0 125.0 190.0 205.0
Min. Flow
Lpm 1.3 1.7 3.1 4.1 6.2 14.8 28.4 43.2 46.6
Adjst
. No gpm 3.7 5.0 9.5 12.5 19.0 50.0 101.0 158.0 170.0
Flow Lpm 0.8 1.1 2.2 2.8 4.3 11.4 22.9 35.9 38.6
gpm 13.3 19.2 29.0 34.5 53.0 128.0 245.0 375.0 415.0
Max. Flow
Adjst Lpm 3.0 4.4 6.6 7.8 12.0 29.1 55.6 85.2 94.3
. No gpm 12.5 18.0 27.0 32.0 50.0 122.0 235.0 360.0 400.0
Flow Lpm 2.8 4.1 6.1 7.3 11.4 27.7 53.4 81.8 90.8
See notes next page.
The piping should also include thermometers at the inlet and outlet connections and air vents at the high points.
The water heads can be interchanged (end for end) so that the water connections can be made at either end of the
unit. If this is done, new head gaskets must be used and control sensors relocated.
In cases where the water pump noise can be objectionable, vibration isolation sections are recommended at both
the inlet and outlet of the pump. In most cases, it will not be necessary to provide vibration eliminator sections in
the condenser inlet and outlet water lines. But they can be required where noise and vibration are critical.
Cooling Towers
The condenser water flow rate must be checked to be sure that it conforms to the system design. Some form of
temperature control is also required if an uncontrolled tower can supply water below about 65F (18C). If tower
fan control is not adequate, a tower bypass valve is recommended. Unless the system and chiller unit are
specifically for condenser bypass or variable condenser flow is not recommended since low condenser flow rates
can cause unstable operation and excessive tube fouling.
The condenser water pumps must cycle on and off with the unit. See Figure 19, Field Wiring Diagram on page 32
for wiring details.
Tower water treatment is essential for continued efficient and reliable unit operation. If not available in-house,
competent water treatment specialists can be contracted.
Heat Recovery Chillers
HSC heat recovery chillers control the chilled water leaving temperature. The cooling load determines
compressor loading and unloading, the same as in a conventional chiller. A heat recovery chiller’s control
algorithms are identical to a conventional cooling-only chiller.
The temperature of the hot water being supplied from the recovery condenser to the heating load is established by
manipulating the cooling tower water temperature. The 3-way cooling tower bypass valve is controlled by the
heating water inlet temperature to the recovery bundle of the condenser. Based on the signal the 3-way valve gets
from the heating hot water sensor, it will bypass sufficient water around the tower to force the tower condenser
water loop high enough for the recovery bundle to produce the desired hot water temperature.
The chilled water and its control system do not sense that the condensing pressure and condenser water
temperatures are being regulated in this manner.
HEAT LOAD
AUXILIARY
HEATER
OPEN TC
CIRCUIT RECOVERY
TOWER CONDENSER
TC
LEGEND
TC TEMPERATURE CONTROL POINT EVAPORATOR
PUMP
COOLING
LOAD
Compressor
Table 4, Compressor Weights
Compressor Size 063 079 087 100 113 126
Weight lb. (kg) 2000 (908) 3200 (1440) 3200 (1440) 6000 (2700) 6000 (2700) 6000 (2700)
Max. Unit Weight Without Starter Max. Unit Weight With Starter (1)
Evaporator / Condenser
Unit Shipping Operating Shipping Operating
Size
lbs. (kg) lbs. (kg) lbs. (kg) lbs. (kg)
WDC063 2416 / 2416 18673 (8470) 20422 (9263) 21407 (9710) 23156 (10503)
WDC063 2416 / 2616 19365 (8784) 21294 (9577) 22099 (10024) 23848 (10817)
WDC063 2616 / 2416 19282 (8746) 21207 (9639) 22016 (9986) 23763 (10779)
WDC063 2616 / 2616 20025 (9083) 22091 (9939) 22759 (10323) 24646 (11179)
WDC063 3016 / 3016 23545 (10680) 26405 (11830) 26279 (11920) 28815 (13070)
WDC063 3616 / 3016 27763 (12604) 31018 (14082) 30163 (13694) 33418 (15172)
WDC063 3616 / 3616 32027 (14540) 35115 (15942) 33427 (15176) 37515 (17032)
WDC079 3016 / 3016 25131 (11399) 27671 (12551) 27531 (12488) 30071 (13640)
WDC079 3616 / 3016 28763 (13047) 32018 (14523) 31163 (14135) 34418 (15612)
WDC079 3616 / 3616 32027 (14527) 36115 (16382) 34427 (15616) 38515 (17470)
WDC079 4216 / 4216 44470 (20189) 51463 (23364) 47204 (21431) 54197 (24605)
WDC087 3016 / 3016 26157 (11865) 28697 (13017) 28891 (13105) 31431 (14257)
WDC087 3616 / 3016 29789 (13512) 33044 (14989) 32523 (14752) 35778 (15322)
WDC087 3616 / 3616 33053 (14993) 37141 (16847) 35787 (16233) 39875 (18087)
WDC087 4216 / 4216 44470 (20189) 51463 (23364) 47204 (21431) 54197 (24605)
WDC100, 113 3616 / 3616 41816 (18967) 46513 (21098) See Note 2 See Note 2
WDC100, 113, 126 (<7kV) 4216 / 4216 50470 (22893) 57463 (26065) See Note 2 See Note 2
WDC100, 113, 126 (<7kV) 4816 / 4816 59185 (26846) 68996 (31296) See Note 2 See Note 2
WDC100, 113, 126 (<7kV) 4220 / 4220 54802 (24858) 63248 (28689) See Note 2 See Note 2
WDC100, 113, 126 (<7kV) 4820 / 4820 65964 (29921) 77698 (35243) See Note 2 See Note 2
WCC100, 113, 126 (<7kV) 3620 / 3620 37645 (17091) 41334 (19268) See Note 2 See Note 2
WCC100, 113, 126 (<7kV) 4220 / 3620 41320 (18759) 45609 (21317) See Note 2 See Note 2
WCC100, 113, 126 (<7kV) 4220 / 4220 45314 (20573) 50281 (23767) See Note 2 See Note 2
WCC100, 113, 126 (<7kV) 4820 / 4220 49759 (22590) 56173 (26305) See Note 2 See Note 2
WCC100, 113, 126 (<7kV) 4820 / 4820 55927 (25391) 62528 (29876) See Note 2 See Note 2
WDC100, 113, 126 (10/11kV) 4216/4216 55760 (25292) 63536 (28219) See Note 2 See Note 2
WDC100, 113, 126 (10/11kV) 4220/4220 62136 (28184) 71426 (32398) See Note 2 See Note 2
WDC100, 113, 126 (10/11kV) 4820/4820 73526 (33351) 86282 (39137) See Note 2 See Note 2
WCC100, 113, 126 (10/11kV) 4220/4220 55987 (25395) 63262 (28695) See Note 2 See Note 2
WCC100, 113, 126 (10/11kV) 4820/4820 65768 (29832) 75761 (34365) See Note 2 See Note 2
With starters (factory mounted) applies only to low voltage (200 to 600 volts) equipment.
Unit not available with factory mounted starters.
NOTES:
1. WDC and WCC dual compressor units will have twice the cooling water flow rate of the comparable WSC chiller and the
pressure drop will be the same.
2. Pressure drops include valves on the unit.
Compressors using chilled water for oil cooling will often start with warm "chilled water" in the system until the
chilled water loop temperature is pulled down. Data given above includes that condition. As can be seen, with
cooling water in the 45F to 65F (7C to 18C) range, considerably less water will be used, and the pressure
drop will be greatly reduced.
When supplied with city water, the oil piping must discharge through a trap into an open drain to prevent
draining the cooler by siphoning. The city water can also be used for cooling tower makeup by discharging it
into the tower sump from a point above the highest possible water level.
NOTE: Particular attention must be paid to chillers with variable chilled water flow through the
evaporator. The pressure drop available at low flow rates can very well be insufficient to supply the oil
cooler with enough water. In this case an auxiliary booster pump can be used or city water employed.
PUMP
CHILLER
OIL COOLER S
STOP
SOLENOID VALUE
VALVE
STOP
VALVE
STRAINER
MAX. 40 MESH
DRAIN VALVE
OR PLUG
OIL COOLER S
SOLENOID
VALVE
Oil Compressor
Reservoir Controller & Lub
Control Box
Solenoid Valve
Inlet
Connection
Temperature
(I id )
Control Valve
Outlet
Connection
(O id )
Solenoid Valves
Note:
All other WDC units
Temperature
have oil cooler
Control Valves
connections located on
the right hand tube
Inlet Connection
sheet under the
Outlet Connection evaporator.
Oil Heater
The oil sump is equipped with an immersion heater that is installed in a tube so that it can be removed without
disturbing the oil.
Relief Valves
As a safety precaution and to meet code requirements, each
chiller is equipped with pressure relief valves located on the
condenser, evaporator, and oil sump vessel for the purpose
of relieving excessive refrigerant pressure (caused by
equipment malfunction, fire, etc.) to the atmosphere. Most
codes require that relief valves be vented to the outside of a
building, and this is a desirable practice for all installations.
Relief piping connections to the relief valves must have
flexible connectors.
Common Piping
According to ASHRAE Standard 15, the pipe size cannot be less than the relief valve outlet size. The discharge
from more than one relief valve can be run into a common header, the area of which cannot be less than the sum
of the areas of the connected pipes. For further details, refer to ASHRAE Standard 15. The common header can
be calculated by the formula:
0.5
DCommon D2 D2 .... Dn2
1 2
The above information is a guide only. Consult local codes and/or latest version of ASHRAE Standard 15 for
sizing data.
Electrical
Wiring, fuse and wire size must be in accordance with the National Electric Code (NEC). Standard NEMA
motor starters require modification to meet McQuay specifications. Refer to McQuay Specification R35999901
or McQuay Product Manual PM WSC/WDC.
Important: Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage
unbalance per NEMA MG-1 Standard. This is an important restriction that must be adhered to.
Power Wiring
Power Factor Correction Capacitors
Do not use power factor correction capacitors withcentrifugal chillers with a compressor VFD. Doing so can
cause harmful electrical resonance in the system. Correction capacitors are not necessary since VFDs inherently
maintain high power factors
Power wiring to compressors must be in proper phase sequence. Motor rotation is set up for clockwise rotation
facing the lead end with phase sequence of 1-2-3. Care must be taken that the proper phase sequence is carried
through the starter to compressor. With the phase sequence of 1-2-3 and L1 connected to T1 and T6, L2
connected to T2 and T4, and L3 connected to T3 and T5, rotation is proper. See diagram in terminal box cover.
The McQuay start-up technician will determine the phase sequence.
CAUTION
Connections to terminals must be made with copper lugs and copper wire.
Note: Do not make final connections to motor terminals until wiring has been checked and approved by a McQuay
technician.
Under no circumstances should a compressor be brought up to speed unless proper sequence and rotation have
been established. Serious damage can result if the compressor starts in the wrong direction. Such damage is not
covered by product warranty.
It is the installing contractor's responsibility to insulate the compressor motor terminals when the unit voltage is
600 volts or greater. This is to be done after the McQuay start-up technician has checked for proper phase
sequence and motor rotation. Following this verification by the McQuay technician, the contractor should obtain
and apply the following items on medium voltage (above 600 volts) applications.
Materials required:
1. Loctite brand safety solvent (12 oz. package available as McQuay part number 350A263H72)
2. 3M Co. Scotchfil™ brand electrical insulation putty (available in a 60-inch roll as McQuay part number
350A263H81)
3. 3M Co. Scotchkote brand electrical coating (available in a 15 oz. can with brush as McQuay Part Number
350A263H16)
4. Vinyl plastic electrical tape
The above items are available at most electrical supply outlets.
Application procedure:
1) Disconnect and lock out the power source to the compressor motor.
2) Using the safety solvent, clean the motor terminals, motor barrel adjacent to the terminals, lead lugs, and
electrical cables within the terminal 4OX to remove all dirt, grime, moisture and oil.
3) Wrap the terminal with Scotchfil putty, filling in all irregularities. The final result should be smooth and
cylindrical.
4) Doing one terminal at a time, brush the Scotchkote coating on the motor barrel to a distance of up to '/2"
around the terminal and on the wrapped terminal, the rubber insulation next to the terminal, and the lug and
cable for approximately 10". Wrap additional Scotchfil insulation over the Scotchkote coating.
5) Tape the entire wrapped length with electrical tape to form a protective jacket.
6) Finally, brush on one more coat of Scotchkote coating to provide an extra moisture barrier.
! CAUTION
Exert extreme care when mounting the compressor motor terminal box on the compressor to avoid damage to the
motor terminals. Terminal damage can result in costly and time consuming repair.
Unbolt the protective shield covering the compressor motor terminals and discard.
Install the shipped-loose terminal box as follows:
1. A mounting gasket is shipped with the terminal box. Mount it on the face of the compressor terminal
housing (see Figure 14) using an appropriate adhesive to hold it in place until the terminal box is
mounted. The gasket must be located such that the gasket holes align with the threaded holes in the
casting.
2. Remove the terminal box door before lifting the terminal box helps to keep the box balanced. Lift using
lifting straps attached to the side lifting tabs. The top tab is used as a tie-off for balance, not for the main
weight of lifting.
3. To assist in mounting the box and to provide protection to the motor terminals, screw two
¼-20 x 12 in. all-thread into top and bottom holes of the casting (see Figure 14) to provide mounting
guides for aligning the box
4. Mount the box over the two all-threads using them as a guide and carefully position the box against the
compressor (gasket). Avoid contact with the motor terminals.
5. Mount the box using ¼-20 x 0.75 in. bolts in all the empty holes.
Terminal Housing
All-thread Locations
6. Remove the two all-thread and replace with two ¼-20 x 0.75 in. bolts.
Buss Connection
to Compressor
Terminals (3)
Rear Motor
Temperature
Sensors Cable
Brown---B6
White----B7
Blue------B8
Black-----Ground
Factory FO “Black Box” Factory Wired
Wired Isolator Fiber Optic
Motor Terminal Box to Chiller Control Panel
Cables
Field wiring is required between the terminal box and
the chiller control panel to transmit motor information
to the chiller. Data from the compressor is sent to a
“Black Box” fiber isolator via a factory-wired fiber
optic cable (to isolate motor voltage from the chiller
controls). A cable is factory connected to terminals 33,
34, 35, and 36 on CTB1 in the chiller control box.
This cable is field installed into the motor terminal Land wires on terminal strip TTB1
box and wires in it connected to like terminal numbers
on terminal strip TTB1 located in the small lower box of
the motor terminal box.
In the event a transformer supplies control voltage, it must be rated at 3 KVA, with an inrush rating of 12 KVA
minimum at 80% power factor and 95% secondary voltage. For control wire sizing, refer to NEC. Articles 215
and 310. In the absence of complete information to permit calculations, the voltage drop should be physically
measured.
Table 13, Control Power Line Sizing
Maximum Length, ft (m) Wire Size (AWG) Maximum Length, ft (m) Wire Size (AWG)
0 (0) to 50 (15.2) 12 120 (36.6) to 200 (61.0) 6
50 (15.2) to 75 (22.9) 10 200 (61.0) to 275 (83.8) 4
75 (22.9) to 120 (36.6) 8 275 (83.8) to 350 (106.7) 3
Notes:
1. Maximum length is the distance a conductor will traverse between the control power source and the unit control panel.
2. Panel terminal connectors will accommodate up to number 10 AWG wire. Larger conductors will require an
intermediate junction box.
The Unit On/Off switch located in the Unit Control Panel should be turned to the "Off" position any time
compressor operation is not desired.
Wiring for Optional BAS Interface
The optional Building Automation System (BAS) interface utilizing the MicroTech II unit controller’s
Open Choices feature is field wired and will be set-up by the McQuay startup service technician. The
following manuals explain the wiring and mounting procedures:
LONWORKS > IM 735
BACnet > IM 906
MODBUS > IM 743
Flow Switches
Water flow interlock terminals are provided on the Unit Control Panel terminal strip for field-mounted
switches. See the Field Wiring Diagram on page 32 or on the cover of the control panel for proper connections.
The purpose of the water flow interlocks is to prevent compressor operation until such time as both the
evaporator water and condenser water pumps are running and flow is established. If flow switches are not
furnished factory-installed and wired, they must be furnished and installed by others in the field before the unit
can be started.
System Pumps
Operation of the chilled water pump can be to 1) cycle the pump with the compressor, 2) operate continuously,
or 3) start automatically by a remote source.
The cooling tower pump must cycle with the machine. The holding coil of the cooling tower pump motor
starter must be rated at 115 volts, 60 Hz, with a maximum volt-amperage rating of 100. A control relay is
required if the voltage-amperage rating is exceeded. See the Field Wiring Diagram on page 32 or in the cover
of control panel for proper connections.
All interlock contacts must be rated for no less than 10 inductive amps. The alarm circuit provided in the
control center utilizes 115-volts AC. The alarm used must not draw more than 10 volt amperes.
See OM CentriMicro II for MicroTech II unit controller details.
Control Panel Switches
Three On/Off switches are located in the upper left corner of the main Unit Control Panel, which is adjacent to the
operator interface panel, and have the following function:
GND PE 54
85
POWER
* NOTE 7
86
NEUTRAL
* NOTE 10 70
H
80
* COOLING O 55
TOWER C4 74 H
A
FOURTH O
86
STAGE
STARTER EP2
A C
86
* NOTE 10
H 79
* COOLING O
TOWER C3 73
A H
THIRD O
STAGE
STARTER EP1
A C
78
77
* NOTE 10
H 76
* COOLING O
TOWER C2 75
A
SECONDH
STAGE
STARTER
H
O
* NOTE 10 A C
H CP2
* COOLING O
C1 T3-S
TOWER A
FIRST EF
STAGE
STARTER CF
81
COMMON
82(NO) ALARM RELAY
A (NOTE 4)
83(NC)
84
POWER
H
52
O
COOLING TOWER
71
BYPASS VALVE 1-10 VDC CP1
A C
71
1-10 VDC
COOLING TOWER VFD 53
4 4
6 11 T1 T6 T2 T4 T3 T5
COMPRESSOR TERMINALS
11 11
12 12
STARTER LOAD SIDE TERMINBALS
22 22 MEDIUM AND HIGH VOLTAGE
T1 T2 T3
-LOAD- NOTE 2 LESS
THAN
30V
OR T1 T2 T3
24VAC COMPRESSOR TERMINALS 330387901-0A
PIGTAIL
Chiller A
P P J10 J11
485
OPDR UCM
C B A
UNIT CONTROL
BLU/WHT
WHT/BLU
SHIELD
Chiller B
485 P P J10 (+) (-)
OPDR UCM PORT J11 PORT
C B A
UNIT CONTROL
BLU/WHT
WHT/BLU
SHIELD
(+) (-)
Chiller C
J11 Port
UNIT CONTROL
NOTE: A fourth chiller, Chiller D would be connected to chiller C same as chiller C to chiller B.
Table 14, pLAN Address and DIP Switch Settings for Controllers Using pLAN
Chiller Comp 1 Comp 2 Unit Reserved Operator Reserved
(1) Controller Controller Controller Interface (2)
Dec. 1 2 5 6 7 8
A
Bin. 100000 010000 101000 011000 N/A 000100
Dec. 9 10 13 14 15 16
B
Bin. 100100 010100 101100 011100 N/A 000010
Dec. 17 18 21 22 23 24
C
Bin. 100010 010010 101010 011010 N/A 000110
Dec. 25 26 29 30 31 32
D
Bin. 100110 010110 101110 011110 N/A 000001
NOTES:
1. Up to four single or dual compressors can be interconnected.
2. Operator Interface Touch Screen (OITS) setting is not a DIP switch setting. The OITS address is selected by
selecting the ‘service’ set screen. Then, with the Technician level password active, select the ‘pLAN Comm’
button. Buttons A(7), B(15), C(23), D(31) will appear in the middle of the screen, then select the letters for the
OITS address for the chiller that it is on. Then close the screen. Note that A is the default setting from the factory.
3. For the pCo2 controller, the pLAN address can be confirmed by viewing the DIP switch positions and comparing
to the table above (Bin. rows). Up is ‘On’, indicated by ‘1’. Down is ‘Off’, indicated by ‘0’.
WCC Settings
Since the WCC is essentially two chillers combined into one counterflow, single pass, dual-circuit chiller, the
compressor on the downstream circuit (leaving chilled water) must always be designated as the Stage 1
compressor-first on, last off.
Operating Sequence
For multiple-chiller, parallel operation, the MicroTech II controllers are tied together by a pLAN network and
stage and control compressor loading among the chillers. Each compressor, single or dual compressor chiller, will
stage on or off depending on the sequence number programmed into it. For example, if all are set to “1”, the
automatic lead/lag will be in effect.
When chiller #1 is fully loaded, the leaving chilled water temperature will rise slightly. When the Delta-T above
setpoint reaches the Staging Delta-T, the next chiller scheduled to start will receive a start signal and start its
pumps if they are set up to be controlled by the Microtech controller. This procedure is repeated until all chillers
are running. The compressors will load-balance themselves.
If any of the chillers in the group are dual compressor, they will stage and load according to the staging
instructions.
See OM CentrifMicro II (current revision) for a complete description of the various staging sequences available.
Note: This checklist must be completed and sent to the local McQuay service location two
weeks prior to start-up.
Standby Power
It is essential that any centrifugal chiller connected to standby power come to a complete stop before being restarted
on grid power. This is usually not an issue when running on grid power and experiencing a grid power failure since
the chiller’s control will shut down the chiller and disconnect it from the power source for the stop-to-start setpoint
time. It will have come to a complete stop before restarting.
Attempting to switch back and forth from regular grid line power and auxiliary power while the compressor is
running can result in extreme transient torque that will severely damage the compressor.
NOTE: Detailed information on the operation of the MicroTech II control is contained in the OM CentrifMicro II.
ON/OFF
Switches
UTB1 Unit
Terminal Block
110-volt
Circuit Breaker
Emergency
OFF Switch
Compressor Relay
Bias Block for Starter
Display Option Connection Oil Pump Contactor
pLAN Connection
Compressor Microprocessor
Oil Pump
Relief Valve Contactor
Oil Pump
Oil Sump Capacitor
Compressor
MicroTech II
Solenoid controller
Valve
Cooling
Water Inlet
Temperature
Control Valve Cooling
Water Outlet
NOTE: 4-way solenoid valve and vane close switches are located on the compressor
suction inlet. The mechanical high-pressure cutout is located in the discharge line.
LEGEND
HOLDING
Oil Under Pressure
Section “SA”
SA
De-energized
Adjustable Needle Valves
#1 Inlet
Integral With Four-Way
From Oil
Solenoid Valve
Pump Discharge
LEGEND
To Oil
#3 Outlet Pump Sump
Drain From Piston
SB Section “SB”
Energized
Section “SA”
SA
De-energized
#1 Intlet
From Oil
Pump Discharge
CLOSING
Piston Drain
To Oil
Pump Sump
#3 Outlet
SB Section “SB”
De-energized
Section “SA”
SA
Energized
Drain From Piston #1 Intlet
From Oil
Pump Discharge
Lubrication System
The lubrication system provides lubrication and heat removal for compressor bearings and internal parts. In
addition, the system provides lubricant under pressure to hydraulically operate the unloading piston for
positioning the inlet guide vanes for capacity control. WDC, dual compressor chillers, have completely
independent lubrication systems for each compressor.
Only the recommended lubricant, as shown in Table 16, can be used for proper operation of the hydraulic system
and bearing lubrication system. Each unit is factory-charged with the correct amount of the recommended
lubricant. Under normal operation, no additional lubricant is needed. Lubricant must be visible in the sump sight
glass at all times.
Compressor sizes, CE063 through CE126, utilize a separate lubricant pump located in the sump. The sump
includes the pump, motor, heater and lubricant/vapor separator system. The lubricant is pumped through the
external oil cooler and then to the oil filter located inside the compressor housing. WSC/WDC/WCC 063-126
units, single or dual compressor, all utilize a water-cooled oil cooler for each compressor.
The oil coolers maintain the proper oil temperature under normal operating conditions. The coolant flow control
valve maintains 95°F to 105°F (35°C to 41°C). Lubrication protection for coast down in the event of a power
failure is accomplished by a spring-loaded piston in models CE063 through 100. When the oil pump is started, the
NOTES:
1. Connections are not necessarily in correct relative location.
2. R = relief valve, P = pressure sensor, T = temperature sensor, S = solenoid valve
Pressure/Temperature Chart
HFC-134a Temperature Pressure Chart
Routine Maintenance
Lubrication
CAUTION
Improper servicing of the lubrication system, including the addition of excessive or incorrect oil, substitute quality oil filter,
or any mishandling can damage the equipment. Only authorized and trained service personnel should attempt this
service. For qualified assistance, contact your local McQuay service location.
After the system is once placed into operation, no other additional oil is required except in the event that repair
work becomes necessary to the oil pump, or unless a large amount of oil is lost from the system due to a leak.
If oil must be added with the system under pressure, use a hand pump with its discharge line connected to the
backseat port of the valve in the lubricant drain from the compressor to the sump. See Figure 25 on page 41. The
POE oils used with R-134a are hygoscopic and care must be exercised to avoid exposure to moisture (air).
The condition of compressor oil can be an indication of the general condition of the refrigerant circuit and
compressor wear. An annual oil check by a qualified laboratory is essential for maintaining a high level of
maintenance. It is useful to have an oil analysis at initial startup to provide a benchmark from which to compare
future tests. The local McQuay service office can recommend suitable facilities for performing these tests.
Table 17 gives the upper limits for metals and moisture in the polyolester lubricants required by McQuay chillers.
Key to Action
1) Re-sample after 500 hours of unit operation.
a) If content increases less than 10%, change oil and oil filter and re-sample at normal interval (usually
annual).
b) If content increases between 11% and 24%, change oil and oil filter and re-sample after an additional
500 hours of operation.
c) If content increases more than 25%, inspect compressor for cause.
2) Re-sample after 500 hours of unit operation.
a) If content increases less than 10%, change filter-drier and re-sample at normal interval (usually
annual).
b) If content increases between 11% and 24%, change filter-drier and re-sample after an additional 500
hours of operation.
c) If content increases more than 25%, monitor for a water leak.
3) If TAN is less than 0.10, system is safe as far as acid is concerned.
a) For TAN between 0.10 and 0.19, re-sample after 1000 hours of operation.
b) For TAN above 0.19, change oil, oil filter, and filter-drier and resample at normal interval
CAUTION
Never Megger a motor while in a vacuum. Severe motor damage can result.
6. The centrifugal compressor must rotate in the direction indicated by the arrow on the rear motor cover
plate, near the rotation sight glass. If the operator has any reason to suspect that the power system
connections have been altered, (phases reversed) the compressor must be jogged to check rotation. For
assistance, call the local McQuay service location.
Annual Startup
A dangerous condition can exist if power is applied to a faulty compressor motor starter that has been burned
out. This condition can exist without the knowledge of the person starting the equipment.
This is a good time to check all the motor winding resistance to ground. Semi-annual checking and recording
of this resistance will provide a record of any deterioration of the winding insulation. All new units have well
over 100 megohms resistance between any motor terminal and ground.
Whenever great discrepancies in readings occur, or uniform readings of less than 50 megohms are obtained, the
motor cover must be removed for inspection of the winding prior to starting the unit. Uniform readings of less
than 5 megohms indicate motor failure is imminent and the motor should be replaced or repaired. Repair before
failure occurs can save a great deal of time and labor spent in the cleanup of a system after a motor burnout.
1. The control circuit must be energized at all times, except during service. If the control circuit has been off
and oil is cool, energize oil heaters and allow 24 hours for heater to remove refrigerant from the oil before
starting.
2. Check and tighten all electrical connections.
3. Replace the drain plug in the cooling tower pump if it was removed at shutdown time the previous season.
4. Install fuses in main disconnect switch (if removed).
5. Reconnect water lines and turn on supply water. Flush condenser and check for leaks.
6. Refer to Manual OM CentrifMicro II before energizing the compressor circuit.
Do not use oxygen or a mixture of R-22 and air to build up pressure as an explosion can occur causing
serious personal injury.
If any leaks are found in welded or brazed joints, or it is necessary to replace a gasket, relieve the test pressure in
the system before proceeding. Brazing is required for copper joints.
After making any necessary repair, the system must be evacuated as described in the following section.
Evacuation
After it has been determined that there are no refrigerant leaks, the system must be evacuated using a vacuum
pump with a capacity that will reduce the vacuum to at least 1000 microns of mercury.
A mercury manometer, or an electronic or other type of micron gauge, must be connected at the farthest point
from the vacuum pump. For readings below 1000 microns, an electronic or other micron gauge must be used.
IMPORTANT: At this point, the charging procedure should be interrupted and prestart checks made
before attempting to complete refrigerant charge. The compressor must not be started at this time.
(Preliminary check must first be completed.)
NOTE: It is of utmost importance that all local, national, and international regulations concerning the
handling and emission of refrigerants are observed.
Oil Analysis
Interpreting Oil Analysis Data
Oil wear metals analysis has long been recognized as a useful tool for indicating the internal condition of rotating
machinery and continues to be a preferred method for McQuay centrifugal chillers. McQuay Service or a number
of laboratories specializing in oil testing can do the test. To accurately estimate the internal condition it is essential
to properly interpret the oil wear test results.
Numerous test results from various testing laboratories have recommended action that has prompted unnecessary
concern by customers. Polyolester oils are excellent solvents and can readily dissolve trace elements and
contaminants. Most of these elements and contaminates eventually end up in the oil. Also, the polyolester oils
used in R-134a chillers are more hygroscopic than mineral oils and can contain much more water in solution. For
this reason, it is imperative that extra care be used when handling polyolester oils to minimize their exposure to
ambient air. Extra care must also be used when sampling to ensure that sample containers are clean, moisture-free
leak proof and non-permeable.
McQuay International has done extensive testing in conjunction with refrigerant and lubricating oil manufacturers
and has established guidelines to determine action levels and the type of action required. Table 1 indicates these
parameters.
IM 1044-2 Centrifugal Chillers 51
In general McQuay International does not recommend changing lubricating oils and filters on a periodic basis.
The need to change lubricating oil and filters should be based on a careful consideration of oil analysis, vibration
analysis and knowledge of the operating history of the equipment. A single oil sample is not sufficient to estimate
the condition of the chiller. Oil analysis is only useful if employed to establish wear trends over time. Changing
lubricating oil and filter prior to when its needed will reduce the effectiveness of oil analysis as a tool in
determining machinery condition.
The following metallic elements or contaminates and their possible sources will typically be identified in an oil
wear analysis.
Aluminum
Typical sources of aluminum are bearings, impellers, seals or casting material. An increase in aluminum content
in the lubricating oil may be an indication of bearing, impeller or other wear. A corresponding increase in other
wear metals may also accompany an increase in aluminum content.
Copper
The source of copper can be the evaporator or condenser tubes, copper tubing used in the lubrication and motor
cooling systems or residual copper from the manufacturing process. The presence of copper may be accompanied
by a high TAN (total acid number) and high moisture content. High copper contents may also result from residual
mineral oil in machines which have been converted to R-134a. Some mineral oils contained wear inhibitors which
react with copper and result in high copper content in lubricating oil.
Iron
Iron in the lubricating oil can originate from compressor castings, oil pump components, shells, tube sheets, tube
supports, shaft material and rolling element bearings. High iron content may also result from residual mineral oil
in machines which have been converted to R-134a. Some mineral oils contain wear inhibitors which react with
iron and can result in a high iron content in the lubricating oil.
Tin
The source of tin may be from bearings.
Zinc
There is no zinc used in the bearings on McQuay chillers. The source, if any may be from additives in some
mineral oils.
Lead
The source of lead in McQuay centrifugal chillers is the thread sealant compounds used during chiller assembly.
The presence of lead in the lubricating oil in McQuay chillers does not indicate bearing wear.
Silicon
Silicon can originate from residual particles of silicon left from the manufacturing process, filter drier material,
dirt or anti-foam additives from residual mineral oil which may be present in machines that have been converted
to R-134a.
Moisture
Moisture in the form of dissolved water can be present in lubricating oil to varying degrees. Some polyolester oils
may contain up to 50 parts per million (ppm) of water from new unopened containers. Other sources of water may
be the refrigerant (new refrigerant may contain up to 10 ppm water), leaking evaporator condenser tubes or oil
coolers, or moisture introduced by the addition of either contaminated oil or refrigerant or improperly handled oil.
Liquid R-134a has the ability to retain up to 1400 ppm of water in solution at 100 degrees F. With 225 ppm of
water dissolved in liquid R-134a, free water would not be released until the liquid temperature reached -22
degrees F. Liquid R-134a can hold approximately 470 ppm at 15 degrees F (an evaporator temperature which
could be encountered in ice applications). Since free water is what causes acid production, moisture levels should
not be of a concern until they approach the free water release point.
Table 18, Upper Limit For Wear Metals And Moisture In Polyolester Oils In McQuay Centrifugal
Chillers
Elements Upper Limit (ppm) Action
Aluminum 50 1
Copper 100 1
Iron 100 1
Silica 50 1
Key To Action
1. Re-sample after 500 hours of unit operation. If content increases less than 10%, change oil and filter and
re-sample at normal interval. If content increases 25% or more, inspect compressor.
2. Re-sample after 500 hours of unit operation. If content increases less than 10%, change filter drier and re-
sample at normal interval. If content increases 25% or more, monitor for water leak. Since POE lubricants
are hygroscopic, many times the high moisture level is due to inadequate handling and packaging. The
TAN reading MUST BE USED in conjunction with moisture readings
3. For TAN between .10 and .19, re-sample after 1000 hours of unit operation. If TAN increases above .19,
change oil, oil filter and filter drier and re-sample at normal interval.
Quarterly
As Req’d
Annually
Monthly
Weekly
Daily
5-Yr
Maintenance Check List Item
I. Unit
· Operational Log O
· Analyze Operational Log O
· Refrigerant Leak Test Chiller O
· Test Relief Valves or Replace X
II. Compressor
· Vibration Test Compressor X
A. Motor
· Meg. Windings (Note 1) X
· Ampere Balance (within 10% at RLA) O
· Terminal Check (Infrared temperature measurement) X
· Motor Cooling Filter Drier Pressure Drop X
B. Lubrication System
· Clean Oil Cooler Strainer (water) X
· Oil Cooler Solenoid Operation O
· Oil Appearance (clear color, quantity) O
- Oil Filter Pressure Drop O
· Oil Analysis (Note 5) X
· Oil change if indicated by oil analysis X
III. Controls
A. Operating Controls
· Calibrate Temperature Transducers X
· Calibrate Pressure Transducers X
· Check Vane Control Setting and Operation X
· Verify Motor Load Limit Control X
· Verify Load Balance Operation X
· Check Oil Pump Contactor X
B. Protective Controls
· Test Operation of:
Alarm Relay X
Pump Interlocks X
Guardistor and Surgeguard Operation X
High and Low Pressure Cutouts X
Oil Pump Pressure Differential Cutout X
Oil Pump Time Delay X
Continued on next page.
Quarterly
As Req’d
Annually
Monthly
Weekly
Daily
5-Yr
Maintenance Check List Item
IV. Condenser
A. Evaluation of Temp Approach (NOTE 2) O
B. Test Water Quality V
C. Clean Condenser Tubes (NOTE 2) X X
D. Eddy current Test - Tube Wall Thickness V
E. Seasonal Protection X
V. Evaporator
A. Evaluation of Temp Approach (NOTE 2) O
B. Test Water Quality V
C. Clean Evaporator Tubes (NOTE 3) X
D. Eddy current Test - Tube Wall thickness V X
E. Seasonal Protection X
VI. Expansion Valves
A. Operational Evaluation (Superheat Control) X
VII. Starter(s)
A. Examine Contactors (hardware and operation) X
B. Verify Overload Setting and Trip X
C. Test Electrical Connections (Infrared temp measurement) X
VIII. Optional Controls
A. Hot Gas Bypass (verify operation) X
KEY:
O = Performed by in-house personnel.
X = Performed by McQuay authorized service personnel. (NOTE 4)
V = Normally performed by third parties.
NOTES:
1. Some compressors use power factory correction capacitors and all have a surge capacitor (excepting units with solid state
starters). The surge capacitor can be installed out of sight in the compressor motor terminal box. In all cases, capacitors
must be disconnected from the circuit to obtain a useful Megger reading. Failure to do so will produce a low reading. In
handling electrical components, only fully qualified technicians must attempt service.
2. Approach temperature (the difference between the leaving water temperature and the saturated refrigerant temperature)
of either the condenser or evaporator is a good indication of tube fouling, particularly in the condenser, where constant
flow usually prevails. McQuay's high efficiency heat exchangers have very low design approach temperatures, in the
order of one to one and one half degrees F.
The chiller unit controller can display the water and the saturated refrigerant temperatures. Simple subtraction will give
the approach. It is recommended that benchmark readings (including condenser pressure drop to confirm future flow
rates) be taken during startup and then periodically afterward. An approach increase of two-degrees or more would
indicate that excessive tube fouling could be present. Higher than normal discharge pressure and motor current are also
good indicators
3. Evaporators in closed fluid circuits with treated water or anti-freeze are not normally subject to fouling, hover it is
prudent to check the approach periodically. Some evaporators may have a mixture of ¾-inch and 1-inch tubes.
4. Performed when contracted for, not part of standard initial warranty service.
5. Oil filter change and compressor teardown and inspection should be done based on the results of the annual oil test
performed by a company specializing in this type of test. Consult McQuay Factory Service for recommendations.
Operator Schools
Training courses for Centrifugal Maintenance and Operation are held through the year at the McQuay Training
Center in Staunton, Virginia. The school duration is three and one-half days and includes instruction on basic
refrigeration, MicroTech controllers, enhancing chiller efficiency and reliability, MicroTech troubleshooting,
system components, and other related subjects. Further information can be found on www.mcquay.com or call
McQuay at 540-248-0711 and ask for the Training Department.
Warranty Statement
Limited Warranty
All McQuay equipment is sold pursuant to McQuay’s Standard Terms and Conditions of Sale and
Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer
to form 933-430285Y. To find your local representative, go to www.mcquay.com
This document contains the most current product information as of this printing. For the most
up-to-date product information, please go to www.mcquay.com.