Sirius en
Sirius en
1. Edition
sirius
Safety guidelines
This manual contains notices which you should observe to ensure your own personal safety, as well as to pro-
tect the product and connected equipment. These notices are highlighted in the manual by a warning triangle
and are marked as follows according to the level of danger:
Danger
indicates that death, severe personal injury or substantial property damage will result if proper precautions
are not taken.
Warning
indicates that death, severe personal injury or substantial property damage can result if proper precautions are
not taken.
Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken.
Caution
indicates that property damage can result if proper precautions are not taken.
Attention
draws your attention to particularly important information on the product, handling the product, or to a particu-
lar part of the documentation.
Qualified personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are defi-
ned as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in
acc. with established safety practices and standards.
Correct usage
Note the following:
Warning
This device and its components may only be used for the applications described in the catalogue or the techni-
cal descriptions, and only in connection with devices or components from other manufacturers which have
been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly,
and operated and maintained as recommended.
Brands
SIMATIC®, SIMATIC HMI® and SIMATIC NET® are brands of SIEMENS AG.
Some other designations used in these documents are also brands; the owner's rights may be violated if they are used by
third parties for their own purposes.
Technical Assistance: Telephone: +49 (0) 9131-7-43833 (8°° - 17°° CET) Fax: +49 (0) 9131-7-42899
E-mail: [email protected]
Internet: www.siemens.com/lowvoltage/technical-assistance
Technical Support: Telephone: +49 (0) 180 50 50 222
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschäftsgebiet Niederspannungs-Schalttechnik Siemens AG 2001
D-91050 Erlangen Technical data subject to change without notice.
Siemens Aktiengesellschaft
Contents
1 System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Index Index-1
Introduction
Siemens is one of the leading manufacturers of switchgear. The product
range extends from devices that switch a few mA to circuit breakers used in
power distribution.
We have been able to meet the demands resulting from increased environ-
mental awareness, particularly in the last ten years or so, by developing and
using environment-friendly and recyclable materials. As a result, we have
developed modern industrial switching devices, particularly in the field of
low-voltage switchgear, that meet all the relevant demands in terms of envi-
ronment-friendliness.
These new SIRIUS devices fulfill all the demands placed on them in practice
and can be used as stand-alone devices or modular components of com-
plete load feeders, or integrated in low-voltage distribution cabinets or low-
voltage switching stations.
1.1 Specifications/regulations/approvals
Explosion protection Motor protection devices that protect a motor from overload in a hazardous
area must meet certain requirements. These requirements are defined in
the following standards:
DIN VDE 0660, DIN VDE 0165, EN 60947-1:1991..+A11:1994, EN 60947-4-1,
EN 50014:1994, EN 50019:1978+A1 to A5
Compliance with these standards has up until now been established by
means of a test. Compliance could be documented in two ways:
1. By a test certificate from the manufacturer
2. By a test certificate from an independent test laboratory (e.g. PTB, DMT,
KEMA, etc.).
EU directive Testing of explosion protection has been defined more precisely as a result
of the harmonization of the European Union. In addition to the above stan-
dards, tests will also carried out in acc. with the EU directive 94/9/EC or
ATEX 100a.
Two procedures are in operation during the transition period up until 2003:
Procedure 1
Test certificate from an independent test laboratory as usual (e.g. PTB, DMT,
KEMA, etc.).
Procedure 2
Special test certificate from certified test laboratories (in acc. with extended
European rules). The statutory basis for this is the Official Journal of the
European Union (no. 95/C2 15/02 of 19.08.1995).
Certificate 1 Test certificate from KEMA in the same way as before (valid until 2003) in
acc. with:
• DIN VDE 0660, DIN VDE 0165
• EN 60947-1:1991/A11
• EN 60947-4-1:1992, EN 50019:1978+A1 to A5
DMT-BVS The DMT-BVS is, like the PTB, a certified German testing organization in
compliance with the EU directive 76/117/EEC and EIExV. Like the PTB and
other testing institutes in Europe, the DMT-BVS tests and awards certifi-
cates in acc. with the explosion protection directive 94/9/EC and is accred-
ited accordingly.
Over 100 years ago, the DMT-BVS became the first testing station for explo-
sion protection in Germany, and it has been a testing station for electrical
equipment as well since 1912. DMT-BVS certificates are recognized through-
out the world. For support in export matters, the DMT-BVS works with the
chemical industry and is of course recognized by it.
The individual devices are developed and built in such a way that it is very
easy to put them together to make load feeders. This is possible because
the devices are all built to work together on both an electrical and a mechan-
ical level.
NSB00296
4
2
1
6.1
3
5 NSB00005c
Circuit breakers with frame sizes of S0, S2, and S3 and attachable accessories:
8
2
4
7
1
6.2
3
5
NSB00006c
Figure 1-3: Circuit breakers, accessories (frame sizes S0, S2, and S3)
Attachable accessories for frame sizes S00, S0, S2, and S3:
1) Transverse auxiliary switch
2) Lateral auxiliary switch with 2 contacts
3) Lateral auxiliary switch with 4 contacts
4) Shunt release
5) Undervoltage release
6.1)Undervoltage release with leading auxiliary contacts (S00)
6.2)Undervoltage release with leading auxiliary contacts (S0 to S3)
7) Alarm switch (S0 to S3)
8) Disconnecting module (S0 and S2)
5
12
1
6 19 13
20
7
2
8
10
11
14
15
16
NSB00448
1) Contactor
2) Contactor relay
3) Solid-state time relay block, on-delay
4) Solid-state time relay block, off-delay
5) Auxiliary switch block, time-delay
(on-delay or off-delay or star-delta function)
6) 1-pole auxiliary switch block, infeed from above
7) 2-pole auxiliary switch block, infeed from above
8) 1-pole auxiliary switch block, infeed from below
9) 2-pole auxiliary switch block, infeed from below
10) 4-pole auxiliary switch block
(terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005)
11) 2-pole auxiliary switch block, standard or electronic
type (terminal markings in acc. with DIN EN 50 005)
12) Soldering pin adapter for contactors with 4-pole auxiliary switch block
13) Soldering pin adapter for contactors and contactor relays
14) Additional load module to increase the permissible residual current
15) Surge suppressor with LED
16) Surge suppressor without LED
17) 3-phase feed-in terminal
18) Parallel link (neutral bridge), 3-pole, without terminal
19) Parallel link, 3-pole, with terminal
20) Parallel link, 4-pole, with terminal
5
17 20
11
18
10 21
16 2
12
1
14
1
6
9
15
7
19
8
16
20
13
21
22 3
23
NSB00449
12) 2-pole auxiliary switch block, attachable on the right or left side
(terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005)
13) 1-pole auxiliary switch block (a maximum of 4 can be snapped on)
14) Mechanical interlock, attachable at the side
15) Mechanical interlock, attachable at the front
16) Wiring blocks above and below (reversing mode)
17) Surge suppressor (varistor, RC element, diode combination),
attachable above or below (varies for S0 and S2/S3)
18) Coupling link for direct connection to the contactor coil
19) LED block to display contactor function
For frame sizes S2 and S3 only:
20) Terminal for contactor coil for setting up contactor combinations
21)Terminal cover for box terminals
For frame size S3 only:
22)Terminal cover for terminal end and bar connection
23)Auxiliary connecting lead terminal, 3-pole
Modular system The individual components of the SIRIUS range are building blocks in a mod-
ular system that are harmonized in terms of both their frame size and their
technical specifications. This ensures that individual requirements can be
met quickly and cost-effectively.
Uniformity The devices are harmonized with regard to their ratings and their technical
specifications:
• The same width ensures rapid installation.
• The terminal systems are standardized, and devices with the same rated
current have the same terminals.
Performance capability All SIRIUS devices can be mounted side by side without derating in an ambi-
ent air temperature of up to 60 °C.
Accessories All accessories, such as the auxiliary switches and surge suppressors, can
be mounted and removed without tools.
You can use link modules that connect devices both mechanically and elec-
trically to put together combinations of devices and build fuseless load feed-
ers.
The following table contains a list of the components of the SIRIUS system
together with the most important accessories:
3RT10 motor contac- - Switch motors up to 4 kW and currents up to - Auxiliary switch blocks
tors 95 A - Surge suppressors
- Types: 3-pole for switching - Parallel links
- 4-pole, with 4 NO and 2 S + 2 NC contacts - Time relay blocks
- Soldering pin adapter - Link modules
- Capacitor switching contactor - Wiring blocks
- Reversing and star-delta combinations
3RB12 overload relays - CLASS 5 to CLASS 30 can be set - Summation current transformer for
- Phase loss sensitivity external ground fault monitoring
- 2 outputs per 1 NO + 1 NC contact - DC adapter
- Integrated current transformers in all sizes - Terminal cover
- Motor protection due to the connection of a
thermistor sensor circuit
- Internal ground fault monitoring
- Overload warning
- Remote and automatic reset possible
- High tripping accuracy
- Wide adjustment ranges
- Self-monitoring
3RA1 load feeders - Fuseless load feeder consisting of a circuit - Accessories for the basic devices
breaker and contactor (contactors and circuit breakers)
- Simple assembly with link modules and wir- - Special accessories:
ing blocks Auxiliary switches connectable from
- Reversing combination (link modules) above or below
- Star-delta combination
3RP10/15 solid-state - 8 adjustable time ranges from 0.05 seconds - Coding plug sets
time relays to 10 hours - Locking device
- Constantly high repeatability
- Type with combination voltage (24 VDC and
110 to 240 VAC)
- 2 device types: on-delay and multifunctional
(7 functions)
- Long mechanical and electrical service life
3RW30/31 soft starters - Reduction of the starting current for a smooth - Fans
start
- Soft coasting down function
- Only 3 motor supply leads are required
- System adaptation using setting options:
starting time, starting voltage, coasting down
time
Device combinations The following diagrams show you the possible device combinations, using
the S00 frame size as an example:
Fuseless Fused
load feeder load feeder
3RV10 circuit
3RT10 contactor
breaker
3RA19 link
module
Contactor combination for reversing the S00 frame size (with accessories):
1
14 14 13
2
NSB00459
14 14
14
16
13 6
Individual parts:
1/2) Contactors
4/5/6) Kit
The kit includes:
4) Mechanical interlock
5) 2 connection clips for 2 contactors
6) Wiring blocks above and below to connect the main conducting paths with electrical interlock
(NC contact interlock - can be removed if required)
Attachable accessories:
13) Soldering pin adapter
14) Auxiliary switch block, on the front (only an auxiliary switch blocks that complies with
DIN EN 50 005 can be used)
16) Surge suppressor
The method of mounting the equipment is uniform within each frame size.
Screw-on mounting The SIRIUS switching devices can be screwed on to a flat surface.
Please note the following points with some of the devices:
• 3RV1 circuit breaker, frame sizes S00/S0: Push-in lugs are required for
screw-type mounting
• 3RP15 time relay: Push-in lugs are required for screw-type mounting
• Coupling links: No screw-type mounting
• Soft starters: No screw-type mounting
Snap-on mounting The SIRIUS switching devices are snapped onto 35 mm rails in acc. with
DIN EN 50 022 without a tool.
The devices with a frame size of S3 require a rail with an installation height
of 15 mm. Alternatively, they can also be snapped onto 75 mm rails.
The following table shows you how to mount the device onto the rail:
Frame Procedure Illustration
size
The following table shows you how to remove the device from the rail:
Frame Procedure Illustration
size
You will find notes on mounting the different devices on the rail in the rele-
vant parts of section n.5 on mounting methods and terminal systems.
The terminals used do not vary within a frame size. The current switched by
the different devices of a single frame size does not vary either. This means
you can use the same tool, torque, and conductor cross-section for the cir-
cuit breakers, contactors, and overload relays of a single frame size. The
stripped lengths are also the same. This is important in the case of prefabri-
cated wiring.
Screw-type terminals All the devices have screw-type terminals, either a terminal with a top
washer or a box terminal, depending on the frame size.
Devices with frame sizes S00 and S0 have terminals with captive screws
and terminal washers that enable you to connect 2 conductors, even if they
have different cross-sections.
The box terminals of frame size S2 and S3 can also take 2 conductors with
different cross-sections.
Lugs and connecting You can remove the box terminals from the devices with a frame size of S3
bars to connect conductors with lugs or connecting bars. A terminal cover is
available as shock protection and to ensure that you comply with the
required creepages and clearances when the box terminals are removed.
You can find a detailed description in section n.4 on accessories.
The Cage Clamp terminal system is now available for circuit breakers, con-
tactors, overload relays, and time relays.
Cage-type clamping units, known as Cage Clamp terminals in the case of
SIRIUS products, facilitate quick and maintenance-free wiring.
Power rail
Conductors The Cage Clamp terminal on the switching devices clamps all copper wires
(single-core, stranded and finely stranded) from 0.25 mm2 to 2.5 mm2. The
conductors can be clamped directly or with some protection for splicing. To
this end, wire end ferrules or pin-end connectors can be placed on the con-
ductor ends. The best solution is an ultrasonically condensed conductor.
Safety The devices are equipped with a two-wire connection. In other words, there
are two independent connections for each conducting path.
Only one conductor is connected to each clamping unit.
The clamp presses the conductor against the power rail, which is curved at
this point. The high specific compressive load thus achieved is gas-tight.
The clamp presses its flat surface against the conductor, thus avoiding dam-
age to it. The spring force of the clamp is designed so that it automatically
adjusts to the radius of the conductor. This allows any deformation of the
conductor to be dealt with. It is not possible for the clamping unit to loosen
by itself.
This connection is vibration- and shock-proof. These types of stress do not
damage the conductor or cause any loss in contact.
Machines and systems in which this type of stress occurs, such as vibrators
and elevators, are particularly suitable applications for this connection.
Transfer The contact pressure between the conductor and power rail is optimal, mak-
accuracy ing this clamp terminal suitable for high-voltage installations and also for the
transfer of voltages and currents in the mV and mA ranges in measuring
technology and electronics.
Tool Screwdrivers can be obtained from the NSK (low-voltage switchgear) cata-
log for opening the Cage Clamp terminals.
Procedure The following table shows you how to use the Cage Clamp:
Step Procedure
open.
Small conductor cross- With conductor cross-sections that are ≤ 1 mm2, you have to use an insula-
sections ting stop to ensure the conductors remain securely clamped.
The illustration below shows the procedure:
3RT1916-4JA02
≤ 1 mm²
Figure 1-9: Conductor cross-sections ≤ 1 mm²
1.6 Communication
Interface
DP/3WN6 Motor protection and
Distributed and control device
SIMOVERT I/O device Circuit SIMOCODE-DP
PROFIBUS-DP MASTER DRIVES ET 200X breaker 3WN6 3UF50
CP 343-2
DP/AS-Interface
Link
S7-300
NT NT
Motor starter 3RA5
Safety
monitor M M M
3 3 3
Signal column
AS-Interface LOGO! NSA00001b
AS-Interface
digital analog pneumatisch Motor starter
Input/output modules
Input/output modules Proximity in IP 67
in IP 20 switch Command Membrane keyboard 3SB4 secure digital input modules
BERO devices M
SIGNUM 3
PROFIBUS-DP PROFIBUS-DP (DP being a German abbreviation for distributed I/O) is used
for switching devices with higher communication requirements (e.g. the
transmission of analog actual values with extremely fast response times). It
is also used to link individual AS-Interface segments.
Parameter assignment • For SIMATIC S7 masters, all the functions are integrated in the STEP 7
tools programming language.
• For SIMATIC S5 masters and various non-Siemens masters, the COM
PROFIBUS parameter assignment software is required.
• Manufacturers of non-Siemens masters offer other configuration and
parameter assignment programs.
Applications The above program packages make it easy to carry out the following for
PROFIBUS-DP and its nodes:
• Configuration
• Parameter assignment
• Documentation
• Commissioning
• Testing
• Diagnostics
Replacement for the Process signals that occur in situ, are normally transferred to the open loop
cable harness control using extensive parallel wiring and input/output modules. This
means that each sensor or actuator in the field is connected to the input/
output modules with its own cable. AS-Interface makes it possible to
replace this cable harness with a simple two-wire cable for all sensors or
actuators.
Data and power on a The master communicates with the nodes via the AS-Interface cable. As
two-wire cable well as data, this cable also transfers the supply voltage for the electronic
components and sensors. The voltage is supplied to the AS-Interface cable
from a special AS-Interface power supply unit with a data link.
Setting up different The AS-Interface cable is laid in the same way as for an electrical installa-
structures tion. A new feeder can be inserted at any point. This makes it possible to set
up network structures (e.g. tree, star or line structures). No shielding or ter-
minating resistors are required. The wiring can be adapted individually to the
system or machine.
IP 67 degree of AS-Interface is a networking system for direct use on the machine. The AS-
protection Interface user compact modules have IP 67 protection. They can be used in
situ without being enclosed.
There are also AS-Interface modules for use with IP 20 protection in the
cubicles or distributed switchboxes.
New installation All compact modules are placed on a mounting plate. The mounting plate
system takes the AS-Interface cable and keeps it in place. Polarity reversal is not
possible due to the profile of the cable. The compact modules are simply
hooked on at the top of the mounting plate and secured with just one screw.
When you secure the modules, contact is made with the AS-Interface cable.
You do not have to strip or screw on the cable.
Coding prevents errors All the modules are mechanically and electrically coded.
The coding system prevents errors occurring in the event of replacement. At
replacement, only one module of the same type can ever be mounted. This
stops digital or analog modules (or even inputs or outputs) getting mixed up.
Addressing To participate in data transfer with the master, each node must be assigned
an address before commissioning of the AS-Interface network. Addressing
devices are available for this.
Addressing an installed There is an additional feature which makes new Siemens modules even
module more user-friendly: the addressing socket.
Using this socket you can address a module after it has been installed. It is
not necessary to unscrew the module. Installation can be carried out in the
system by personnel who are not familiar with the AS-Interface. The com-
missioning engineer can address the modules easily when they are already
installed. For the first time, this type of addressing is also possible with
IP 67 protection.
Diagnostics at a glance The new generation of AS-Interface modules (compact modules, analog
modules, and SlimLine modules) has the new display system developed by
Siemens.
Certificates of the AS- All Siemens AS-Interface products are tested in acc. with the relevant
Interface association testing regulations in an accredited test laboratory and certified by the AS-
Interface association.
Digital compact mod- The AS-Interface modules in the compact range are characterized by opti-
ules with IP 67 mized operating features and improved user-friendliness.
protection This can reduce mounting and commissioning times for AS-Interface by up
to 40%. Additional LEDs provide information on the most important operat-
ing modes of the module, resulting in a considerable increase in system
availability.
The modules of the compact range consist of two components:
Mounting plate and compact module
The mounting plate mechanically fixes the AS-Interface profile cables, takes
the compact module, and serves as a template with drill holes.
The compact module contains the electronic components for communica-
tion and the M12 standard connections for inputs/outputs. Up to four sen-
sors and four actuators can be easily and reliably connected to the compact
module using the M12 standard connection.
The mounting plate and compact module are only connected to each other
by means of a single screw. Contact is established with the AS-Interface
cable by means of the proven insulation displacement method.
AS-Interface modules in the compact range that have an M12 connection
can have a protective conductor (PE) connected to them.
Using an addressing socket integrated in the compact module, you can also
allocate addresses when the module is in place.
Analog compact mod- The design of the analog modules has been adapted for the compact mod-
ules with IP 67 ules. The analog input and output modules each have two channels. You can
protection connect measuring sensors and analog actuators using standard M12 con-
nectors. The following groups of analog modules exist:
• Input module for two current sensors
• Input module for two voltage sensors
• Input module for two thermal resistors
• Output module for two current actuators
• Output module for two voltage actuators
All the measured values - except for the thermal resistance value of Pt 100
(not linear) - are available in linear form. In other words, the non-linear trans-
mission curve of the thermal resistor sensor is automatically linearized in
the analog module, and measured values can be processed directly in the
programmable controller.
The input and output channels are isolated. Two-wire and four-wire sensors
can be connected. Differential inputs produce considerable suppression of
common-mode interference. The integrating sigma-delta converter ensures
high measurement accuracy.
Pneumatic compact The pneumatic compact module is a highly integrated AS-Interface slave. As
modules with IP 65 and an input/output module that is entirely suitable for field deployment, it has
IP 67 protection four electrical inputs and two pneumatic outputs. The electrical inputs
behave in the same way as the inputs of the digital input/output compact
modules.
Both integrated pneumatic outputs are implemented by means of two pre-
set 4/2-way valves (2 to 8 bar; 550 Nl/min) with a shared compressed-air
supply and separate exhaust air collection and can be operated manually
using separate slide valves. Two cylinders that work in tandem, for example,
can be connected to a module in this range.
Connections to AS-Interface are made via the standard mounting plate. The
AS-Interface cable is inserted into the corresponding cable guides, and the
upper part is secured to the mounting plate by means of a screw. The mod-
ule is ready for use.
Safety first - AS-Interface is the first system on the market that can transmit both stan-
emergency stop via dard signals and safety-related input signals (e.g. emergency stop) via the
AS-i same cable.
Only an additional safety monitor and safe modules are required to use AS-
Interface as a safety bus. This enables category 4 in acc. with EN 954-1 to
be achieved. A failsafe programmable controller or special master is not nec-
essary.
The concept and implementation of AS-Interface Safety at Work (AS-Inter-
face SaW) have been tested and certified by TÜV (technical testing associa-
tion).
This means that the system can be converted to the considerably more flex-
ible AS-Interface network, which is already available, thus obviating the
need for the complex, separately implemented emergency stop wiring that
has been necessary up to now.
2.4.6 Terminals for "Combination Motor Controller Type E" in acc. 2-31
with UL 508
2.7.3 Limiter function with standard devices for 500 VAC and 690 2-65
VAC in acc. with IEC 60 947-2
2.1 Specifications/regulations/approvals
Standards • The 3RV1 circuit breakers comply with the specifications for circuit break-
ers in acc. with IEC 60947-2/DIN VDE 0660, Part 101.
• The circuit breakers for motor protection comply with the specifications in
acc. with IEC 60947-4-1/DIN VDE 0660, Part 102.
• The auxiliary switches comply with IEC 60947-5-1/DIN VDE 0660
Part 200.
Main and emergency The specifications for the main and emergency switches comply with
stop switches IEC 60204/DIN VDE 0113 Part 1.
Shock protection 3RV1 circuit breakers are shockproof in acc. with DIN VDE 0106 Part 100,
even without accessories. You can find additional information on the subject
of shock protection in the "Switching, Protection and Distribution in Low-
Voltage Networks" manual, p. 37 ff.
Degree of protection The degree of protection of the 3RV1 circuit breaker is IP 20.
In the terminal area of frame sizes S2 and S3 the degree of protection is
IP 00.
Railway vehicles
DIN EN 50 155
Frame sizes 3RV1 circuit breakers are available in 4 frame sizes (S00 to S3).
S00 S0 S2 S3
The following table shows you the frame sizes and the corresponding maxi-
mum rated operational current at a voltage of 400 VAC. The last column in
the table tells you which three-phase induction motor is suitable for which
particular size.
S00 45 mm 12 A 5.5 kW
S0 45 mm 25 A 11 kW
S2 55 mm 50 A 22 kW
S3 70 mm 100 A 45 kW
Auxiliary release The circuit breakers can also be equipped with one of the following auxiliary
releases:
• Shunt release
• Undervoltage release
• Undervoltage release with leading auxiliary contacts
Auxiliary contact ele- The circuit breakers can be equipped with a transverse auxiliary switch, an
ments electronically optimized transverse auxiliary switch or a lateral auxiliary
switch (Section 2.4 Accessories).
Shock protection Shock protection can be improved by covering the terminals and connec-
tions. This can be achieved with the following accessories:
• Frame size S00, S0: protective caps for transverse auxiliary switches
• Frame size S2, S3: terminal covers for box terminals
• Terminal covers for lug and bar connection
2.2.2 Operation
Setting the values Using a screwdriver, set the load rated current (current setting) Ie on the
scale of the circuit breaker.
Note the two possible markings:
• Dash marking: marking for a circuit breaker in a stand-alone installation
• Triangle marking: marking for a circuit breaker in a side-by-side installation
Max. + 60 °C
A
Max. + 70 °C
RV-00222
Ie
360° o.k.
Figure 2-2: Setting the current setting Ie (example: frame size S00)
Warning
The adjusting knob can be turned 360° clockwise. You can only turn it coun-
terclockwise within the adjustment range.
Sealing the You can prevent unauthorized adjustment of the current setting by placing a
adjustment scale transparent cover over it and sealing it.
3RV1908-0P
Switches The state of the circuit breakers can be determined by the position of the
switches:
Frame size Switch STOP ON Tripped
Locking the circuit You can prevent the circuit breaker from being switched on by unauthorized
breakers persons by securing the switch drive (toggle switch or rotary switch) with a
padlock (shackle diameter 3.5 to 4.5 mm).
Ø 3.5 to 4.5 mm
After the circuit breaker has been tripped, the switch goes into the tripped
position to indicate this. You use the switch to close the circuit again.
In the case of frame sizes S0 to S3, the rotary switch must be put in the
OFF position manually before it is switched on again to avoid switching to
the fault inadvertently.
In the case of frame sizes S2 and S3, it is possible to switch on and off using
a motorized remote-control mechanism (see Section 2.4, Accessories).
Testing overload The following table shows you how overload tripping of the circuit breaker is
tripping tested:
Short-circuit protection The short-circuit releases of the 3RV1 circuit breakers execute a three-phase
isolation of the faulty load feeder from the network and prevent any further
damage.
With a short-circuit breaking capacity of 50 kA or 100 kA and a voltage
of 400 VAC, the switches are considered to be short circuit-proof, since hig-
her short-circuit currents are not to be expected where the switches are
installed.
Backup fuses are only required if the short-circuit current at the point of
installation exceeds the rated short-circuit breaking capacity of the circuit
breakers.
You will find the short-circuit breaking capacity for other voltages and the
size of any required fuse listed in Section 2.6, Technical specifications.
Conditions of applica- 3RV1 circuit breakers are climate-proof. They are intended for use in closed
tion areas where there are no harzardous operating conditions such as dust, cor-
rosive fumes or destructive gases.
Appropriate housings are available as an accessory for use in dusty and
damp areas (see Section 2.4).
Inrush current Because the operational currents, the starting currents and the current
spikes vary on account of the inrush current, even in motors of the same
power, the motor powers listed in the tables are only guide values. Most
important when selecting the correct circuit breakers are the concrete start-
ing data and rating of the motor to be protected. This also applies to circuit
breakers used for transformer protection.
Phase loss The phase loss sensitivity of the circuit breaker ensures that it is tripped in
sensitivity good time in the event of the loss of a phase and the resulting overcurrents
in the other phases.
During normal operation, the device should have a three-pole load. To pro-
tect single-phase loads or direct current loads, all 3 main conducting paths
should be switched in series.
opening time
10 000 NSB00004
100
min 5000
60
40 s
2000
1000
10
500
5
200 three-pole
2 load
100
1 class 20
50
three-pole
20 load
class 10
10
5
two-pole
2 load
class 10
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
0,002
0,001
0,6 1 2 3 4 6 8 10 20 30 40 60 A 80 x n
0,8 current
Frequency sensitivity of The characteristics of the short-circuit releases apply to frequencies of 50/
the short-circuit 60 Hz. For lower frequencies, such as 16 2/3 Hz, for higher frequencies up
releases to 400 Hz, and for direct current, appropriate correction factors have to be
taken into account.
The following characteristic curve illustrates the frequency sensitivity of the
short-circuit releases (calibrated to 12 times Iu +20%):
40
Tripping current
Change in %
30
20
10
-10
-20
-30
0 50 100 150 200 250 300 350 400 Hz
Figure 2-7: Frequency sensitivity of the n-short-circuit releases
Frequency converters The thermal switch disconnectors do not have to be corrected when you
use frequency converters.
Set current The current of the motor that is to be protected is set on the adjustment
scale. The short-circuit release is set at the factory to 12 times the value of
the rated current of the circuit breaker. This ensures problem-free startup
and reliable protection of the motor.
Phase loss The phase loss sensitivity of the circuit breaker ensures that it is tripped in
sensitivity good time in the event of the loss of a phase and the resulting overcurrents
in the other phases.
CLASS10/CLASS20 Circuit breakers of frame sizes S00 to S3 with thermal overload releases
comply with tripping class 10 (CLASS 10). Circuit breakers with the
CLASS 20 tripping characteristic are available for frame sizes S2 and S3 in
difficult startup conditions.
Inrush current In the case of primary protection of control transformers, the high inrush
currents that occur when the transformers are switched on often result in
the unwanted tripping of the protective devices.
The 3RV1 circuit breakers with frame sizes S0 and S2 therefore have over-
current releases for the protection of transformers that are set at the factory
to approximately 19 times the rated current. This makes it possible to pro-
tect transformers in which the inrush currents reach peak values of up to 30
times the rated current with circuit breakers in the primary circuit.
In the case of 4AM control transformers with low inrush current (Siemens
control transformers, for example), this is not required. 3RV1 circuit brea-
kers can be used here for motor protection.
2.3.3 Starter protection The 3RV13 starter protection switches are circuit breakers without overload
releases. They are used together with a contactor and overload relay if the
circuit breaker is not to be triggered in the case of overload tripping.
Circuit breakers with the 3RV11 overload relay function are available for
frame sizes S0, S2, and S3.
Description Circuit breakers with the overload relay function contain overload releases
that do not affect the breaker mechanism of the circuit breakers. In the
event of an overload, the circuit breaker remains switched on.
To protect the following loads, 2 auxiliary contacts (1S + 1Ö) are attached on
the right side. These are operated in the event of an overload. The auxiliary
switch function can be evaluated or used to disconnect a downstream con-
tactor. After the circuit breaker has cooled down, the auxiliary contacts are
reset automatically.
Caution
In the overload range, the circuit breaker does not protect itself with the
overload relay function. You must therefore ensure that the circuit breaker is
safely disconnected by means of a downstream switching device (e.g. a
contactor).
Diagrams
S0: 3RV1121-.... S2: 3RV1131-.... S3: 3RV1141-....
TEST
TEST TEST
Figure 2-8: Circuit breaker with overload relay function (frame sizes S0 to S3)
The 3RV16 11-0BD10 circuit breaker is used with frame size S00 for fuse
monitoring.
A conducting path of the circuit breaker is switched in parallel for each fuse.
If one fuse fails, the current flows via the parallel-switched conducting path
of the circuit breaker and trips it.
Warning
Fuse monitoring using the 3RV16 11-0DB10 circuit breaker is not permissible
in feeders with power control regulators where a DC feedback with higher
values can occur in the event of a fault.
Auxiliary switch func- The circuit breaker used for fuse monitoring can be equipped with a trans-
tions verse or lateral auxiliary switch (Section 2.4, Accessories). The auxiliary
switch reports the tripping of the circuit breaker and thus the failure of the
fuse and initiates an all-pole disconnection of the problem circuit by a corre-
sponding switching device.
Attention
To ensure isolation, also disconnect
the fuse-monitoring device with the
item designation ............
Voltages The 3RV16 11-0DB10 circuit breaker is suitable for fuse monitoring in the fol-
lowing voltage ranges:
• 24 to 690 VAC, 50/60 Hz
• 24 to 250 VDC, 100 to 600 VDC
Switching capacity ICN 100 kA
I» I» I» I» I» I» I» I» I»
The 3RV1 circuit breakers for alternating current are suitable for switching
direct current. However, you must note the maximum permissible DC volt-
age per conducting path. In the case of higher voltages, series connection
of 2 or 3 conducting paths is required.
Response thresholds The response thresholds of the overload releases remain unchanged. The
response thresholds of the short-circuit releases are increased with direct
current by approximately 40%.
The following table lists suggestions for switching direct current:
Max.
Suggestion Circuit Frame permissible Meaning
breaker size direct voltage
EI
Since the circuit breakers meet the requirements for disconnectors in acc.
with IEC 60947-3 and the additional test requirements for circuit breakers
with disconnector features in acc. with IEC 60947-2, they can be used with
the appropriate accessories as main and emergency stop switches. They
must also comply with DIN VDE 0113.
2.4 Accessories
2.4.1 Attachable accessories: Overview
Electronically One transverse auxiliary switch can be attached for each circuit
optimized trans- breaker:
verse auxiliary Variants:
switch • 1 changeover contact
Lateral One lateral auxiliary switch can be attached for each circuit breaker: Left side
auxiliary switch • 1 NO + 1 NC contact 9 mm
• 2 NO contacts
• 2 NC contacts
• 2 NO + 2 NC contacts 18 mm
Alarm switch One alarm switch can be attached at the side of the circuit breakers 18 mm
Frame sizes with rotary switches.
S0, S2 and S3
The alarm switch has two contact systems:
• One contact system (1 NO + 1 NC) reports a general
tripping operation, irrespective of whether it was caused by a
short circuit, overload or auxiliary release.
• The other contact system (1 NO + 1 NC) only switches in
the event of a short circuit tripping operation.
To reclose the circuit breaker after a short circuit, the alarm switch
must be reset manually after the cause of the error has been elimi-
nated.
Motorized The circuit breakers can be opened and closed via the remote-con-
remote-control trolled mechanism by means of electrical commands. This enables a
mechanism load or system to be disconnected from and then reconnected to the
For frame sizes power system from an operator control panel.
S2 and S3 The circuit breaker can be disconnected from and reconnected to the
remote-control mechanism in situ.
Rotary switch The rotary switch extension for the door consists of a knob, a drive
extension for coupling and an extension shaft. They comply with IP 65. The door
the door interlock prevents the cubicle door being opened inadvertently when
the switch is in the on position. The off position can be secured with
a maximum of 3 padlocks.
The maximum configuration for each 3RV1 circuit breaker is one transverse
auxiliary switch, one lateral auxiliary switch, one alarm switch, and one aux-
iliary release.
Possible combinations The following combinations of auxiliary switches and alarm switches or of
auxiliary switches are possible:
• Auxiliary and alarm switches can be installed individually or together. The
lateral auxiliary switch is installed on the left of the alarm switch.
• Transverse and lateral auxiliary switches can be combined.
• One auxiliary release can be attached on the right for each circuit breaker:
Mounting the The auxiliary switches, alarm switches, and auxiliary releases are mounted
auxiliary switches in the same way for all frame sizes:
Figure 2-10: Mounting the transverse auxiliary switch (frame size S00)
1
1
3
2 3
2
1
3
1
Figure 2-11: Mounting/removing the lateral auxiliary switch/undervoltage release (frame size S00)
Voltage ranges of the One undervoltage release or shunt release can be installed for each circuit
auxiliary releases breaker. The following voltage ranges are possible:
Undervoltage release AC 50 Hz AC 60 Hz
24 V
110 V 120 V
208 V
230 V 240 V
400 V
415 V 480 V
20 V - 24 V 20 V - 70 V
90 V - 110 V 70 V - 190 V
210 V - 240 V 190 V - 330 V
350 V - 415 V 330 V - 500 V
500 V -
Table 2-6: Voltage ranges of the auxiliary releases
1) Transformer operational voltage of the lower mark of the voltage range at 0.85 (Tu = 60 °C)
is valid for 100% (continuous) duty cycle only at AC 50/60 Hz
2) Transformer operational voltage of the lower mark of the voltage range at 0.9 (Tu = 60 °C) is
valid for 5 seconds duty cycle at AC 50/60 Hz and DC
Tripped signal
Tripped position Switch off (0 position)
LED: Red Switch on again (I position)
RESET button (blue):
remains depressed
1 2
Short circuit
Tripped postion Switch off (0 position)
LED: red Switch on again (I position)
RESET button (blue): RESET button (blue): press
not depressed
Table 2-8: Alarm switch with tripped signal and short circuit signal
Mounting and connec- The following table shows you how to mount and connect the motorized
tion remote-control mechanism:
2 1
AUTOMATIC MANUAL
3 2
5 (4 x)
8 9
7
9
3RV1921-1M
MANUAL AUTOM.
RESET RESET
12 14
21
(22)
19
21 22
Warning
Do not set the "Automatic" position or operate the remote-control mecha-
nism when open! There is a risk of injury!
Manual RESET Remove the screw from the RESET lever (step 12)
3RV1928-1A
3RV1.2
5
4
1
6 8
7
Disconnecting and The disconnecting module can be locked and sealed or secured with two
locking padlocks if the connector is removed during maintenance work, for example.
The circuit breaker itself can also be secured with a third padlock.
3
5
2
1
4 5
Terminal cover A terminal cover (3RT1936-4EA2) is available for the disconnecting module
(frame size S2) in frame size S2 (3RV1938-1A) that protects the contacts from dirt and pro-
vides additional shock protection.
3RV1938-1A 3 3RT1936-4EA2
3RV1.3 4
2
1
Figure 2-14: Locking the disconnecting module and mounting the cover (frame size S2)
Rotary switch extensions for doors are available for frame sizes S0, S2, and
S3. They consist of a lockable rotary switch with a detachable door coupling,
a 150 mm long extension shaft, and a connector for the switch drive. The
door handle complies with IP 65.
Installation
1
4
3
2
0.7 to 0.9 Nm 5
Min. 16 mm
Max. 20 mm
6
7
Figure 2-15: Mounting the rotary switch extension for the door (frame size S2)
Opening the door The following table shows you how the cubicle door can be opened using
the rotary switch extension for the door:
Drawing Procedure
To open the cubicle door, set the
circuit breaker to O (OFF). This
releases the extension shaft from
the rotary switch and allows the
door to be opened.
2
If you want to open the cubicle
door during operation, you can
override the procedure by press-
ing the button at the side of the
rotary knob (step 1).
1 To close it during operation, press
the button again so that the exten-
sion shaft snaps into place again.
2
Table 2-10: Opening a cubicle door using the rotary switch extension
Approx. 150
to 200 N
Figure 2-16: Operating the rotary switch extension for the door
The extension shaft must then be remounted on the circuit breaker and the
rotary switch extension for the door as follows:
Drawing Procedure
Security When the rotary switch is in the OFF position, it can be secured with up to 3
padlocks (e.g. during maintenance work on the system).
Max.
ø 8 mm
1
Figure 2-17: Locking the rotary switch extension for the door
2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
Since July 16, 2001, 1 inch air clearance and 2 inch creepage distance is
required for "Combination Motor Controller Type E" on the input side in acc.
with UL 508. Use terminal blocks 3RV1928-1H and 3RT1946-4GA07 for the
3RV10 circuit breakers in frame sizes S0 and S3. The 3RV10 circuit breaker
in frame size S2 complies with the required air clearance and creepage dis-
tance without a terminal block. Terminal blocks are not required for use in
acc. with CSA. These terminal blocks cannot be used in the S0 frame size at
the same time as the 3RV19.5 3-phase busbars or in the S3 frame size at
the same time as a transverse auxiliary switch.
S0 Self-Protected
S3
3RT1946-4GA07
Combination
Controller Type E
3RV1928-1H
2
1
Molded-plastic housings (IP 55) are available if you want to install circuit
breakers as single units. All the housings are equipped with neutral and
ground terminals. Above and below are two openings that can be knocked
out for cable glands. On the back of the housing there are 2 precut open-
ings. All the cable bushings have metric dimensions. The surface casings
can be sealed. There is space in the housing on the rail for additional modu-
lar terminal blocks.
Molded-plastic
Model Width Frame size
...
Housing with actuator membrane for toggle switch Surface casing 54 mm, 72 mm S00
Bay 72 mm S00
Bay 72 mm S0
Lockable housing with emergency stop rotary switch (red/ Surface casing 54 mm, 72 mm S0
yellow) 82 mm S2
Bay 72 mm S0
Table 2-12: Housings for circuit breakers
Widths The widths of the housing depend on whether auxiliary releases are used:
• 54 mm: circuit breaker + lateral auxiliary switch
• 72, 82 mm: circuit breaker + lateral auxiliary switch + auxiliary release
Mounting the
surface casing
2
3
Neutral/ground terminals
4
1
1 1
2 2
3
3
4
5
4
Figure 2-20: Molded-plastic bay (frame size S00)
Front plates Molded-plastic front plates that have IP 55 protection are suitable for any
housing:
Front plates
Frame
and Model
size
accessories
Front plates With actuator membrane and support for switch S00
VU-01015
M3 5
M3 5 1 6
6 e.g.
cubicle door M6
M6 3
3 4
4
5 5
2 2
Figure 2-21: Mounting the front plate (frame size S00)
Frame size S0
3RV1923-4. + 3RV1923-4G 3RV1923-4.
M3
4 M3 a
e.g. cubicle door 3RV1.2 86,5
3RV1.3 139,0
2
3RV1.4 164,5
2
3RV1923-4G
1
1
Figure 2-22: Mounting the front plate (frame size S0)
The following accessories are available for the housings and front plates of
the circuit breakers in frame size S00:
• Replacement actuator membrane
• Locking device for 3 padlocks
• Emergency-stop button (red/yellow)
• Emergency-stop button (red/yellow) with safety lock
3RV1913-7D
3RV1913-7F
1
2
3RV1913-7E
3RV1913-6B
Figure 2-23: Accessories for the housings and front plates (frame size S00)
Locking device
The locking device can be used on the inside of the housings or front plates.
To do this, remove the frame of the actuator membrane. The locking device
can be secured with up to 3 padlocks that can prevent the circuit breaker
from being switched on during maintenance work, for example.
Emergency-stop button
Indicator lights
Indicator lights are available for the housings and front plates of circuit
breakers in frame sizes S00, S0, and S2. They contain a glow lamp and red,
green, yellow, orange, and transparent lenses. Indicator lights are available
for the following voltage ranges: 110-120 V, 220-240 V, 380-415 V and
480-500 V.
Installation There is a precut opening on the front of the housing that can be knocked
out to install an indicator light:
2
For 3RV 1913-4
16 mm
1
3RV 1903-5
Busbar systems The adapters are suitable for the following systems:
60 mm systems 12 mm to 30 mm 5 mm and 10 mm
Table 2-14: Busbar systems
Measurements The following table lists the dimensions of the busbar adapters and accesso-
ries.
For circuit
Busbar adapter and
System Length Width breakers in frame
accessories
size
40 mm Circuit breaker 121 mm 45 mm S00, S0
+ lateral auxiliary switch 55 mm
Circuit breaker
139 mm 55 mm S2
Link module for Link modules are needed to make electrical and mechanical connections
circuit breaker and between the circuit breaker and contactor to form a load feeder. Link mod-
contactor ules are available for the following combinations:
S00 S0
S0 S0
S2 S2
S3 S3
Table 2-16: Link modules for connecting circuit breakers to contactors
You can find additional information about load feeders on busbar systems in
Chapter 5, "Fuseless load feeders".
Mounting circuit The following illustrations show you how to mount circuit breakers in frame
breakers on busbars sizes S00 and S0 onto busbar adapters (8US1..1-5D) and how to remove
them again, using frame size S00 as an example:
8US1..1-5D
10 mm
Connection
module
Figure 2-25: Mounting circuit breakers on busbar adapters (frame sizes S00 and S0)
Mounting circuit The following illustrations show you how to mount circuit breakers in frame
breakers on a busbar sizes S2 and S3 onto a busbar adapter:
system
S2 S3
8US1.61-5FP08 8US1111-4SM00
3
6 to 9 Nm
6
8 (3x)
7
Figure 2-26: Mounting circuit breakers on busbar adapters (frame sizes S2 and S3)
Mounting The following illustration shows you how to mount accessories for busbar
accessories adapters for frame sizes S00 to S2:
• Side module
• Device holder
• Extension piece
• Outgoing terminal rail (for frame sizes S00 and S0 only)
40 mm
Device holder
Side module
1
2
Figure 2-27: Accessories for busbar adapters (frame sizes S00 to S2)
3-phase busbars are used to snap circuit breakers of frame sizes S00, S0,
and S2 quickly and easily in a row onto a rail. There is only one power supply,
via a feed-in terminal.
The 3-phase busbar systems are safe from fingers and are shock protected.
They are rated for the short-circuit stress that can occur on the output side
of the connected circuit breakers.
Spacer
Protective cap
3RV1915-6AB
Models The 3-phase busbars take 2 to 5 circuit breakers, depending on the model.
There are busbars with more generous spacing for circuit breakers with
accessories attached on the side.
Frame size
of the
Spacing Models
circuit
breaker
Combination of Circuit breakers in frame sizes S00 and S0 vary in height and depth and
frame sizes S00 therefore cannot be combined on one busbar. You can combine two busbars
and S0 for circuit breakers in frame sizes S0 and S00 using an extension piece.
Extending the It is possible to extend the busbars by clamping the connecting lugs of a fur-
bus ther bus (turned 180°) under the terminals of the last circuit breaker (see the
section on mounting).
Attention
Note the current-carrying capacity of the busbars when you extend them.
Accessories The following accessories are available for the isolated 3-phase busbar sys-
tem:
• Feed-in terminal from above (3RV1915-5A for S00, 3RV1925-5AB for S0,
3RV1935-5A for S2)
• Feed-in terminal from below (3RV1915-5B for S00, S0)
• Connector
A connector links two 3-phase busbars over a space of 45 mm for circuit
breakers in frame sizes S00 and S0.
• Protective cap for connecting lugs (3RV19 15-6AB)
Protective caps provide shock protection for spare slots. To extend the
bus, remove the protective caps.
• Spacer
Feed-in terminal 3-phase feed-in terminals make it possible to have greater conductor cross-
sections than on the circuit breaker itself.
Tightening torque: 2 to 4 Nm (17.6 to 35.2 LB.IN).
Frame size of
Connec- Conductor
the circuit Conductors
tion cross-section
breaker
3RV1915-6AB
3RV1915-5B
S00:
Cage Clamp 1
1
2
8WA2011-1DG30
3b
3a
3c
S0
3RV1915-.AB
3RV1925-5AB Turned
180°
3RV1915-6AB
3RV1915-5B
Figure 2-29: Mounting the isolated 3-phase busbar system (frame sizes S00 to S0)
S2 3RV1935-1./3.
3RV1935-5A
3RV1935-6A
Figure 2-30: Mounting the isolated 3-phase busbar system (frame size S2)
2.5.1 Mounting
Mounting position You can install the 3RV1 circuit breakers anywhere.
Snap-on mounting The circuit breakers are mounted by snapping them onto 35 mm rails that
comply with DIN EN 50 022. The circuit breakers with a frame size of S3
require a rail with an installation height of 15 mm. Alternatively, they can also
be snapped onto 75 mm rails.
S00 S3
DIN EN 5022
RV-00298
DIN EN 5022
1
2
1
1
Figure 2-31: Mounting the circuit breakers onto the rail
Screw-on mounting The circuit breakers are attached to a flat surface with 2 screws. For circuit
breakers in frame sizes S00 and S0, two push-in lugs (3RB1900-0B) (pack of
10) are also required.
Circuit breakers in frame sizes S2 and S3 can be screwed directly onto a
base plate.
3RB1900-0B
Figure 2-32: Screw-on mounting of the 3RV1 (example: frame size S00)
2.5.2 Connection
Conductor cross-sec- The typical SIRIUS conductor cross-sections apply (see Section 1.5.2 "Con-
tions ductor cross-sections").
Screw-type terminals 3RV1 circuit breakers with frame sizes S00 and S0 have terminals with cap-
tive screws and terminal washers that enable you to connect 2 conductors,
even if they have different cross-sections.
The box terminals of the circuit breakers of frame sizes S2 and S3 can also
take 2 conductors with different cross-sections. With the exception of circuit
breakers of frame size S3, which have terminal screws with a 4 mm Allen
screw, all the terminal screws can be tightened using a standard screwdriver
or a Pozidriv screwdriver (size 2).
You can remove the box terminals from circuit breakers with a frame size of
S3 to connect conductors with lugs or connecting bars. A terminal cover is
available as shock protection and to ensure that you comply with the
required creepages and clearances when the box terminals are removed.
Soldering pin connec- Circuit breakers in frame size S00 can be soldered onto printed circuit
tor boards by means of a soldering pin connector. A soldering pin connector is
available for the main contacts and the transverse auxiliary switch.
Mounting the solder- The soldering pin adapters are clamped above and below in the screw-type
ing pin adapters terminals of the circuit breakers. Alternatively, the power supply can be
taken to the printed circuit boards via cables.
1 3
2
4
1
1
Figure 2-33: Circuit breaker, soldering pin connector (frame size S00)
13 23
Frame size S00 3RV1901-1F
14 24
13 21 3RV1902-.D..
C1
3RV1901-1E
C2
14 22
11 3RV1902-.A..
3RV1901-1G D1
3RV1901-1D
U
D2
14 12
3RV1901-.J 3RV1901-.A 3RV1901-.B 3RV1901-.C
13 21 31 43 33 41 33 43 31 41 L1 1 L2 3 L3 5
14 22 32 44 34 42 34 44 32 42
I >> I >> I >>
3RV1912-.C..
T1 2 T2 4 T3 6
D1 07
max. 10 A
U
D2 08
13 23
Frame sizes S0 to S3
3RV1901-1F
14 24
13 21 3RV1902-.D..
C1
3RV1901-1E
C2
14 22
11 3RV1902-.A..
3RV1901-1G D1
3RV1901-1D U
D2
14 12 3RV1921-1M
3RV1901-.J 3RV1901-.A 3RV1901-.B 3RV1901-.C
57 65
13 21 31 43 33 41 33 43 31 41 L1 1 L2 3 L3 5
58 66
14 22 32 44 34 42 34 44 32 42
77 85
I >> I >> I >>
T1 2 T2 4 T3 6
max. 10 A
78 86
3RV1922-.C..
D1 07
U
D2 08
13 23
Circuit breaker with
3RV1901-1F
overload relay func-
tion 14 24
13 21
14 22
11
3RV1901-1G
3RV1901-1D
14 12
3RV1901-.J 3RV1901-.A 3RV1901-.B 3RV1901-.C
13 21 31 43 33 41 33 43 31 41 L1 1 L2 3 L3 5
97 95
14 22 32 44 34 42 34 44 32 42
I >> I >> I >>
T1 2 T2 4 T3 6 98 96
max. 10 A
Figure 2-36: Circuit breaker with relay function, device circuit diagrams (frame sizes S0 to S3)
2) 1) 11) 5) 3) 4) 1) 2) 11) 5) 3) 4)
14 72 25
25
5
5
12
12
45
45
106
105
45
90
45
90
97
7)
7)
3,5
NSB00027b
8) 8)
NSB 00026c
9 45 18 18 45 18 5 56
18 5 62 9 69
70 80
6) 76 91
Figure 2-37: 3RV10 11, 3RV16 (frame size S00) 3RV10 21 (frame size S0)
1) 2) 11) 20 121 30
3) 4)
5
130
125
140
89
45
85
7)
8)
8
NSB00028a
18 55 18 5 109
9 127
132
144
Figure 2-38: 3RV10 31 (frame size S2)
146
11) 10) 8 4) 30
3)
1) 2) 5
165
116
150
155
45
7)
9)
7
18 70 18 132
NSB00029b
9 5 153
157
169
Figure 2-39: 3RV10 4 (frame size S3)
45
106
125
90
97
45
130
140
90
45
7) 7)
NSB00030b
8) 8)
18 45 20 5 55 18 55 20 8
NSB00031c
9 69 9 5 109
80 127
132
91 144
Figure 2-40: 3RV11 21 (frame size S0) 3RV11 31 (frame size S2)
146 4)
11) 10) 3) 8 30
1) 2)
5
165
116
150
155
45
90
7)
9)
18 70 20 7
NSB00032c
9 5 132
153
157
169
Figure 2-41: 3RV11 42 (frame size S3)
Disconnecting module
55 149
45 94
57
51
121
96
NSB00033a
NSB00034a
144
190
Figure 2-42: 3RV19 28-1A (for frame size S0) 3RV19 38-1A (for frame size S2)
45 19
55 105
3)
4) 11 13 c)
7)
NSB 00035c
4.5
6)
5)
145 - 148
8)
77.5
9)
b) 99 b)
b) 100.5 d) 190
a) 88 b) 143
32 29 25
1) 2)
4)
45 19
7
1)
4)
2)
3)
4.5
3)
145 - 148
235
250
155
NSB 00036c
18
a) 126
NSB 00037c
18
150 181
Figure 2-44: 3RV19 23-1. (for frame size S0) 3RV19 33-1. (for frame size S2)
a) 3RV19 23-1CA00 85 mm 1) Knockout opening for M32 (left) and M40 (right)
3RV1923-1DA00 105 mm 2) Knockout opening for rear M32 cable entry
1) Knockout opening for M25 3) Opening for padlock with a max. shackle diameter of 8 mm
2) Knockout opening for rear M20 cable entry 4) Indicator light 3RV19 03-5.
3) Opening for padlock with a max. shackle diameter of 8 mm
4) Indicator light 3RV19 03-5.
Molded-plastic bay
3) 2) max. 7 1) 3) 2) max. 6 1)
87.5
87.5
105 95 12 87 105 95 12 87
1) Leuchtmelder
1) Indicator light 3RV19
3RV19 03-5.
03-5. 1) Indicator light 3RV19 03-5.
1) Leuchtmelder 3RV19 03-5.
2) Ausbrechöffnungen
2) Knockout opening forfürM25
M25 2)2) Knockout opening für
Ausbrechöffnungen for M25
M25
3) Ausbrechöffnungen
3) Knockout opening forfürM20
M20 3)3) Knockout opening für
Ausbrechöffnungen for M20
M20
Figure 2-45: 3RV19 13-2DA00 (frame size S00) 3RV19 23-2DA00/-2GA00 (frame size S0)
40
12
NSB 00039a 1) ø7 4.5
4,5
85 56.5
56,5 10 62
70
1)1)Leuchtmelder
Indicator light 3RV19
3RV19 03-5.
03-5.
Figure 2-46: 3RV19 13-4C (frame size S00)
12 18 40
NSB 00042a 1) ø 3.5
3,5 7.4
7,4
37.5
85 56.5
56,5 10 62
70
1) Leuchtmelder
1) Indicator light 3RV19
3RV19 03-5.
03-5.
Figure 2-47: 3RV19 23-4. (frame sizes S0, S2, S3)
13.4 13.1
12
45 5 59 5
9
9
2
8.4
14.4 14.4
103
97.4
NSB00041
8.4
49
14.4 14.4
Figure 2-48: 3RV19 18-5A/-5B (frame size S00)
5
2)
max. 327
5) 33 17
min. 55
Terminals for "Combination Motor Controller Type E" in acc. with UL 508
70
10
45 74
84
27
72
168
121
NSB 01228
NSB 01229
Figure 2-50: 3RV19 28-1H (frame size S0) and 3RT19 46-4GA07 (frame size S3)
NSB00044
SI EMENS
RESET I>
I
182
224
MANUAL
AUTOMATIC REVISION
87 a)
148
Busbar adapter
68
1
40
139
142
40
NSK-8186
NSK-8187
13,5 55 32
50
Figure 2-52: 8US10.1-5DJ07 8US1061-5FK08
2 6 .5 2 0
4 0
68
1
60
6 0
3 )
185
182
1 8 5
2 2 0
2 0 0
60
6 0
NSK-8188
N S K -9 4 0 3 a
NSK-8189
13,5 55
32
60 2 0 5 1
NSB 00055b
13 NSB 00056b
13
21
21
64
64
45 55
108
108
83 93
128
173 148
218 203
258
3RV19 15-1A for 2 circuit breakers (length 83 mm) 3RV19 15-3A for 2 circuit breakers with accessories (length 93 mm)
3RV19 15-1B for 3 circuit breakers (length 128 mm) 3RV19 15-3B for 3 circuit breakers with accessories (length 148 mm)
3RV19 15-1C for 4 circuit breakers (length 173 mm) 3RV19 15-3C for 4 circuit breakers with accessories (length 203 mm)
3RV19 15-1D for 5 circuit breakers (length 218 mm) 3RV19 15-3D for 5 circuit breakers with accessories (length 258 mm)
15
31
96
55
NSB00057b
111
166
165
221
Figure 2-55: 3RV19 35-1 (for circuit breakers in frame size S2)
15
31
96
75
NSB00058b
121
166
196
271
Figure 2-56: 3RV19 35-3 (for circuit breakers in frame size S2)
3RV19 35-3A for 2 circuit breakers with accessories (length 121 mm)
3RV19 35-3B for 3 circuit breakers with accessories (length 196 mm)
3RV19 35-3C for 4 circuit breakers with accessories (length 271 mm)
44
14 14 54
NSB01093a
25
44 24
92
NSB00059a
73
71
NSB00060b
25
114
14 14 a
44 31
a) 3RV1.1 19 mm
a) 3RV1.2 23 mm
Connector
112 13
55
NSB 00062c
NSB00061b
21
34
64
91
108
42,5
81
161
1) After the box terminals have been removed, lug or busbar connections are possible.
2) For notes on the Cage Clamp system, see pages 1-19.
3) Use an insulation stop for a conductor cross-section ≤ 1 mm2.
5) Associated opening tool 8WA28 03/8WA28 04
The circuit breakers in the SIRIUS 3RV1 series are approved for u/s and can also be used in acc. with UL 508 and C22.2 No.14 with a
contactor as a load feeder. You can use these circuit breakers as a "Manual Motor Starter" for "Group Fusing" or for "Group Installation" or as a
"Combination Motor Controller Type E".
Circuit breaker Hp rating Rated current To 240 VAC To AC 480 Y/277 V To AC 600 Y/347 V
1 1 1
For FLA max. In Icu ) Icu ) Icu )
Type V 1-phase 3-phase A kA kA kA
0.11 to 2 50 50 10
3RV10 11 2.5 50 50 10
3RV16 11-0BD10 115 ½ - 3.2 50 50 10
200 1½ 3 4 50 50 10
Frame size S00 230 2 3 5 50 50 10
460 - 7½ 6.3 50 50 10
FLA max. 12 A, 600 V 575/600 - 10 8 50 50 10
NEMA Size 00 10 50 50 10
12 50 50 10
0.11 to 3.2 50 50 30
3RV10 21/3RV11 21 4 50 50 30
3RV13 21 5 50 50 30
115 2 - 6.3 50 50 30
Frame size S0 200 3 7½ 8 50 50 30
230 5 7½ 10 50 50 30
FLA max. 25 A, 600 V 460 - 15 12.5 50 50 30
NEMA Size 1 575/600 - 20 16 50 50 30
20 50 50 30
22 50 50 30
25 50 50 30
3RV10 31/3RV11 31 11 to 16 50 50 25
3RV13 31 20 50 50 25
115 3 - 25 50 50 25
Frame size S2 200 7½ 15 32 50 50 25
230 10 20 40 50 50 25
FLA max. 50 A, 600 V 460 - 40 45 50 50 25
NEMA Size 2 575/600 - 50 50 50 50 25
11 to 16 50 50 30
3RV10 41/3RV10 42 20 50 50 30
3RV11 42 115 10 - 25 50 50 30
3RV13 41/3RV13 42 200 20 30 32 50 50 30
230 20 40 40 50 50 30
Frame size S3 460 - 75 50 50 50 30
575/600 - 100 63 50 50 30
FLA max. 99 A, 600 V 75 50 50 30
NEMA Size 3 90 50 50 30
100 (99) 50 50 30
Circuit breaker Hp rating Rated current To 240 VAC To AC 480 Y/277 V To AC 600 Y/347 V
1
Icu )
1 1
For FLA max. In Icu ) Icu )
Type V 1-phase 3-phase A kA kA kA
0.11 to 1.6 50 50 30
3RV10 21 2 50 50 30
+ 3RV19 28-1H 115 2 - 2.5 50 50 30
200 3 7½ 3.2 50 50 30
Frame size S0 230 3 7½ 4 50 50 30
460 - 15 5 50 50 30
FLA max. 22 A, 480 V 575/600 - 10 6.3 50 50 30
12.5 A, 600 V 8 50 50 30
NEMA Size 1 10 50 50 30
12.5 50 50 30
16 50 50 -
20 50 50 -
22 50 50 -
0.9 to 16 50 50 25
3RV10 31 20 50 50 25
115 3 - 25 50 50 25
Frame size S2 200 7½ 15 32 50 50 25
230 10 20 40 50 50 25
FLA max. 50 A, 600 V 460 - 40 45 50 50 25
NEMA Size 1 575/600 - 50 50 50 50 30
3RV10 31/3RV11 31 11 to 16 50 50 25
3RV13 31 20 50 50 25
115 3 - 25 50 50 25
Frame size S2 200 7½ 15 32 50 50 25
230 10 20 40 50 50 25
FLA max. 50 A, 600 V 460 - 40 45 50 50 25
575/600 - 50 50 50 50 25
NEMA Size 2
11 to 16 50 50 30
3RV10 41 20 50 50 30
+ 3RT19 46-4GA07 115 10 - 25 50 50 30
200 20 30 32 50 50 30
Frame size S3 230 20 40 40 50 50 30
460 - 75 50 50 50 30
FLA max. 100 A, 480 V 575/600 - 75 63 50 50 30
75 A, 600 V 75 50 50 30
90 50 50 -
NEMA Size 3 100 50 50 -
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) Corresponds to "short circuit breaking capacity" in acc. with UL
2.7.2 Rated short-circuit breaking capacity Icn in acc. with IEC 60 947-2
The table lists the rated limit short-circuit breaking capacity Icu and the rated service short-circuit breaking capacity Ics of 3RV1 circuit
breakers with different inception voltages and related to the rated current In of the circuit breakers.
The incoming supply of the circuit breakers is permissible at the upper or lower terminals irrespective of the rating.
If the short-circuit current at the installation location exceeds the rated short-circuit breaking capacity of the circuit breaker specified in
the table, a backup fuse is required. You can also use an upstream circuit breaker with a limiter function.
The maximum rated current of this backup fuse is specified in the tables. The rated short-circuit breaking capacity specified for the
fuse then applies.
Circuit breaker/contactor combinations for short-circuit currents of up to 50 kA can be used as fuseless load feeders in acc. with Part 5.
Circuit Rated To 240 VAC 2) To 400 VAC 2)/415 V 3) To 440 VAC 2)/460 V3) To 500 VAC 2)/525 V3) To 690 VAC 2)
breaker current In Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max.
Fuse Fuse Fuse Fuse Fuse
Type A kA kA A kA kA A kA kA A kA kA A kA kA A
3RV10, 0.16 to 0.8 100 100 100 100 100 100 100 100 100 100
3RV16 11-
1 100 100 100 100 100 100 100 100 100 100
0BD10
frame size S00
1.25 100 100 100 100 100 100 100 100 2 2 20
1.6 100 100 100 100 100 100 100 100 2 2 20
2 100 100 100 100 100 100 10 10 35 2 2 35
2.5 100 100 100 100 100 100 10 10 35 2 2 35
3.2 100 100 100 100 50 10 40 1) 3 3 40 2 2 40
4 100 100 100 100 50 10 40 1) 3 3 40 2 2 40
5 100 100 100 100 50 10 50 1) 3 3 50 2 2 50
6.3 100 100 100 100 50 10 50 1) 3 3 50 2 2 50
8 100 100 50 12.5 80 1) 50 10 63 1) 3 3 63 2 2 63
10 100 100 50 12.5 80 1) 10 10 63 3 3 63 2 2 63
12 100 100 50 12.5 80 1) 10 10 80 3 3 80 2 2 80
3RV1. 2 0.16 to 1.25 100 100 100 100 100 100 100 100 100 100
Frame size S0 1.6 100 100 100 100 100 100 100 100 100 100
2 100 100 100 100 100 100 100 100 8 8 25
2.5 100 100 100 100 100 100 100 100 8 8 25
3.2 100 100 100 100 100 100 100 100 8 8 32
4 100 100 100 100 100 100 100 100 6 3 32
5 100 100 100 100 100 100 100 100 6 3 32
6.3 100 100 100 100 100 100 100 100 6 3 50
8 100 100 100 100 50 25 63 1) 42 21 63 6 3 50
10 100 100 100 100 50 25 80 1) 42 21 63 6 3 50
12.5 100 100 100 100 50 25 80 1) 42 21 80 6 3 63
16 100 100 50 25 100 1) 20 10 80 1) 10 5 80 4 2 63
20 100 100 50 25 125 1) 50 10 80 1) 10 5 80 4 2 63
22 100 100 50 25 125 1) 50 10 100 1) 10 5 80 4 2 63
25 100 100 50 25 125 1) 50 10 100 1) 10 5 80 4 2 63
3RV1. 3 16 100 100 50 25 100 1) 50 25 100 1) 12 6 63 5 3 63
Frame size S2 20 100 100 50 25 125 1) 50 25 100 1) 12 6 80 5 3 63
25 100 100 50 25 125 1) 50 15 100 1) 12 6 80 5 3 63
32 100 100 50 25 125 1) 50 15 125 1) 10 5 100 4 2 63
40 100 100 50 25 160 1) 50 15 125 1) 10 5 100 4 2 63
45 100 100 50 25 160 1) 50 15 125 1) 10 5 100 4 2 63
50 100 100 50 25 160 1) 50 15 125 1) 10 5 100 4 2 80
Circuit Rated To 240 VAC 2) To 400 VAC 2)/415 V 3) To 440 VAC 2)/460 V 3) To 500 VAC 2)/525 V 3) To 690 VAC 2)
breaker current In Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max.
Fuse Fuse Fuse Fuse Fuse
Type A kA kA A kA kA A kA kA A kA kA A kA kA A
3RV1. 41 40 100 100 50 25 125 1) 50 20 125 1) 12 6 100 6 3 63
Frame size S3 50 100 100 50 25 125 1) 50 20 125 1) 12 6 100 6 3 80
63 100 100 50 25 160 1) 50 20 160 1) 12 6 100 6 3 80
75 100 100 50 25 160 1) 50 20 160 1) 8 4 125 5 3 100
90 100 100 50 25 160 1) 50 20 160 1) 8 4 125 5 3 125
100 100 100 50 25 160 1) 50 20 160 1) 8 4 125 5 3 125
3RV1.42 16 100 100 100 50 100 50 30 15 80 12 7 63
Frame size S3 20 100 100 100 50 100 50 30 15 80 12 7 63
With increased
switching 25 100 100 100 50 100 50 30 15 80 12 7 63
capacity 32 100 100 100 50 100 50 22 11 100 12 7 63
40 100 100 100 50 100 50 18 9 160 12 6 80
50 100 100 100 50 100 50 15 7.5 160 10 5 100
63 100 100 100 50 70 50 200 1) 15 7.5 160 7.5 4 100
75 100 100 100 50 70 50 200 1) 10 5 160 6 3 125
90 100 100 100 50 70 50 200 1) 10 5 160 6 3 160
100 100 100 100 50 70 50 200 1) 10 5 160 6 3 160
No backup fuse required because it is short circuit-proof up to 100 kA.
1 A backup fuse is only required if the short-circuit current at the installation location is > Icu.
2 10% overvoltage
3 5% overvoltage
2.7.3 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
The table lists the rated limit short-circuit breaking capacity Icu and the rated service short-circuit breaking capacity Ics with an
upstream standard circuit breaker that fulfills the limiter function at 500 VAC and 690 VAC.
The short-circuit breaking capacity can be significantly increased using the upstream standard circuit breaker with a limiter function.
The circuit-breaker connected downstream, should be set to the rated current of the load. Be sure when you set up circuit breaker
combinations to note to the distances between the grounded parts and the distances between the circuit breakers.
Make sure that the cabling between the circuit breakers is short circuit-proof. You can set up the circuit breakers side by side.
Standard circuit breaker Standard circuit breaker To 500 VAC 1)/ 525 V 2) To 690 VAC 1)
with limiter function
Characteristics You can obtain the characteristics for all the setting ranges from our Techni-
cal Assistance team by e-mail: ([email protected]).
3.3.7 3RT10 contactor relays for switching motors (interface) and 3-30
3RH11 contactor relays for switching auxiliary circuits
3.4.7.2 Auxiliary connecting lead terminal, 3 pole (for frame size S3) 3-79
3.1 Specifications/regulations/approvals
Regulations The following regulations apply to contactors:
• IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100), which includes the gen-
eral specifications for low- voltage switching devices.
• IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102), which contains, in
particular, the requirements for contactors and motor starters.
The following regulations apply to auxiliary contactors:
• IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100), which includes the gen-
eral specifications for low-voltage switching devices.
• IEC 60 947-5-1, EN 60 947-5-1 (VDE 0660 Part 200) which includes, in par-
ticular, the requirements for control equipment and switching elements
for the control, signaling, locking, etc. of switchgear and controlgear.
Standards The following standards apply to the terminal markings of the contactors:
• EN 50 012: terminal markings and identification numbers for auxiliary con-
tact elements of particular contactors (also applies to contactors with a
built-on auxiliary switch block)
• EN 50 011: terminal markings, identification numbers, and identification
letters for particular auxiliary contactors (also applies to auxiliary contac-
tors with a built-on auxiliary switch block)
• EN 50 005: terminal markings and identification numbers, general rules
Shock protection The shock protection provided is in acc. with DIN VDE 0106 Part 100.
In acc. with EN 60 947-4-1, the purpose of the contactors and the stress
placed on them is indicated by the utilization category together with details
of the rated operational current or motor output and the rated voltage.
The following tables list the definitions of the utilization categories for low-
voltage switching devices and contactors from IEC 60 947 (VDE 0660) an.
The rated operational voltages for the various utilization categories are listed
in the low-voltage switching devices catalog.
Definition of AC-1 to The definitions of the utilization categories AC-1 to AC-4 for main circuits
AC-4 can be found in the relevant regulations.
The main areas of application for contactors are:
• AC-3 operation: switching of squirrel-cage motors
• AC-1 operation: switching of resistive loads
• AC-4 operation: plugging, reversing, inching
Utilization category for DC Utilization category for Switching capacity I/Ie Switching capacity
DC voltages DC voltages Make/break Time constant L/R (ms)
DC-1 Not an inductive load or 1.5 1.0
a slightly inductive load,
resistance furnaces
DC-3 Shunt motors: 4.0 2.5
switching on, plugging,
reversing, inching
DC-5 Series motors: 4.0 15
switching on, plugging,
reversing, inching
DC-6 Switching of incandescent 1.5 (Incandescent lamp
lamps test)
Table 3-2: Utilization categories, test conditions for DC voltages
Definition of DC-1 to The definitions of the utilization categories DC-1 to DC-6 apply to main cir-
DC-6 cuits for switching DC voltage.
The main areas of application for contactors are:
• DC-3/DC-5 operation: switching of shunt or series motors
• DC-1 operation: switching of resistive loads, resistance furnaces
Note:
In the information on DC switching capacity in previous documents, the uti-
lization categories DC-2 and DC-4 correspond to the current utilization cate-
gories DC-3 and DC-5.
Definition of AC-12 to IEC 60 947-5-1/EN 60 947-5-1 (VDE 0660 Part 200) contains the definitions
AC-15 of the utilization categories AC-12 to AC-15 for switching elements for the
control, signaling, locking, etc. of switchgear and controlgear.
The main areas of application for auxiliary contactors are:
• AC-14/AC-15 operation: switching of contactor coils, solenoid valves, for
example
• AC-14/AC-12 operation: switching of resistive loads, for example
Rated operational cur- The rated operational currents for the various utilization categories are listed
rents in the low-voltage switching devices catalog. The test specifications given in
the table for each utilization category represent the scale for the making and
breaking capacity of the auxiliary contacts.
Definition of DC-12 to The DC voltage switching capacity of auxiliary contacts is defined in utiliza-
DC-14 tion categories DC-12 to DC-14.
The main areas of application for contactors are:
• DC-12: switching of resistive loads (typical application)
• DC-13: switching of inductive loads, such as contactor coils and solenoid
valves
In DC operation, the difference in stress is also determined by the L/R time
constant. This must be specified by the user.
Definition: positively Positively driven contacts are contacts that are mechanically connected with
driven contacts one another in such a way that the NC contacts and NO contacts can never
be closed at the same time. This means ensuring that there is a distance
between the contacts of at least 0.5 mm throughout the entire service life
of the contactor, even when there is a defect, such as when the contact has
been wrongly welded (ZH 1/457).
Definition Circuits are safely isolated when a single fault does not result in a transfer of
voltage from one circuit to another. Faults to be taken into account are, for
example, a bent or loose conductive part, a bent soldering pin, broken win-
ding wire, a screw that has fallen out, or a broken partition wall in a device.
Regulations IEC 61 140 (replacing VDE 0106 Part 101/IEC 536) lists basic requirements
that can be met using safe isolation between circuits in electrical equip-
ment.
Basic requirements are, for example:
• Double or reinforced insulation
• Protective screening
• Combination of double or reinforced insulation and protective screening
The insulation must be resistant to aging throughout the expected service
life.
Circuits without protective extra-low voltage or functional extra-low voltage
do not require safe isolation.
Safe isolation in the If the conducting paths of a contactor are operated with different voltages,
case of 3RT1 and 3RH1 the requirements for safe isolation must be met.
contactors In the case of the 3RT1 and 3RH1 contactors, safe isolation is ensured up to
the following voltage:
• Safe isolation between the different main conducting paths is always
400 V.
• Safe isolation between the different main conducting paths and the coil
connection is always 400 V.
• The following table lists the values for safe isolation between the main
and auxiliary conducting paths and the coil connection:
Aux. switch
at front 690 (*) 500 500 500
at side - 690 500 690
Coil connection 400 400 400 400
Table 3-5: Safe isolation
Attention
In the table, the voltage that can cause electric shock and that must be
safely isolated is critical. If the voltages 400 V and 24 V are to be safely iso-
lated from one another, contactors with safe isolation up to 400 V must be
used between the two points of connection used.
Safety extra-low volt- Safety extra-low voltage (SELV) allows circuits with a rated voltage of up to
age 50 VAC or 120 VDC to be operated ungrounded. The higher voltage is safely
isolated from the SELV circuits.
Safety extra-low voltage helps protect people.
Functional Functional extra-low voltage (FELV) allows circuits with a rated voltage of up
extra-low voltage to 50 VAC or 120 VDC can be operated. It does not, however, meet the
requirements of safety extra-low voltage and is therefore subject to additio-
nal conditions. FELV is implemented using a ground terminal.
Functional extra-low voltage helps protect devices (e.g. programmable con-
trollers).
PELV PELV (protective extra-low voltage) has the same requirements as safety
extra-low voltage, except for the fact that the circuit and/or exposed conduc-
tive part is/are grounded (so it is basically grounded SELV).
S00 S0 S2 S3
Performance ranges The following table specifies the performance ranges for the frame sizes of
the 3RT10 contactors:
15 16 17 23 24 25 26 34 35 36 44 45 46
At 400 V:
Ie/AC-3 A 7 9 12 9 12 17 25 32 40 50 65 80 95
Width 45 mm 45 mm 55 mm 70 mm
Table 3-6: Performance ranges of the 3RT10 contactors
The following table provides an overview of the existing variants of the 3RT and 3RH contactors:
3RH/3RT contactors DC operation with an extended operating range: 0.7 to 1.25 x U S S00 to S3
3RT: to switch motors up to 45 kW/400 V
Ie/AC-3 up to °C: 95 A to 400 V
3RH: to switch auxiliary circuits
Ie/AC-15/AC-14 up to 70 °C: 6 A/230 V
3RT contactor relays DC operation with an extended operating range: 0.7 to 1.25 x U S S00 and S0
(interface) To switch motors, 3-pole, up to 11 kW/400 V
Ie/AC-3 up to 60 °C: 25 A to 400 V
3RH11 contactor relays DC operation with an extended operating range (0.7 to 1.25 x U S) S00
(interface) to switch auxiliary circuits, 4-pole
Ie/AC-15/AC-14 up to 60 °C: 6 A/230 V
Unwelded contactors The unwelded contactors are put together using a circuit breaker to S0, S2
3RT11 24, 3RT11 35 make an unwelded feeder. The features are:
• Standard: IEC 947-6-2 (for feeders with increased requirements)
• Compact
• Extremely high reliability in the entire current range up to 50 kA
Table 3-7: Types of 3RT/3RH contactors
Auxiliary contacts and • A uniform and diverse range of auxiliary switches and accessories that
built-on accessories can be quickly upgraded and replaced is available for 3RT1 contactors up
to 45 kW for various applications.
• The 3RH auxiliary contactors can be extended to form variants with a
maximum of 8 poles using attachable 2 or 4-pole auxiliary switch blocks.
• Wiring kits with and without mechanical interlocking are available for put-
ting together 3RA contactor combinations for reversing and for star-delta
starting.
The accessories are described in detail in Section 3.4, "Accessories".
Coordination types Two types of assignment are defined in the standards that correspond to
two different levels of damage.
The following applies to both types of assignment:
In the event of a short-circuit, the short-circuit protective device used must
be able to disconnect the overcurrent that occurs both safely and success-
fully. Persons or other parts of the system must not be put at risk.
Coordination type 1 The load feeder (e.g. motor starter) can be inoperable after each short-circuit
disconnection. Damage to the contactor and the overload relay is permissi-
ble, but it is only possible to continue operation after defective devices have
been repaired or replaced.
Coordination type 2 After short-circuit disconnections, there must be no damage to the load
feeder devices. The only exception is if the contactor contacts have been
welded and can be easily separated again without distorting the contact
pieces.
Contactors with over- If contactors are combined with an overload relay, a smaller fuse as speci-
load relay fied in the NSK catalog on permissible short-circuit protection fuses for
motor starters should be used.
3.2.3 Operation
Ambient temperature The 3RT10 contactors are designed for use in ambient temperatures of
-25 °C to +60 °C. Some variants can be used in temperatures of -35 °C to
+70 °C.
Warning
When the supply voltage and load are present, the contactor must not be
actuated by pressing the contact support. It is permissible, however, to
carry out tests with an extra-low test voltage (e.g. ≤ 24 V).
Mechanical life A significant criterion for the economical use of contactors is their mechani-
cal endurance. This is expressed in the number of operations that are possi-
ble without placing a load on the conducting path. You cannot expect too
much in terms of mechanical endurance from switches that have to work
with a relatively high contact load, such as isolators and circuit breakers
without neglecting their cost-efficiency. Contactors, on the other hand, are
switching devices designed specifically for very high numbers of operations
and switching frequency.
The following table shows you the mechanical endurance of 3RT1 contac-
tors:
Basic unit, frame size S00 with built- 10 mill. operating cycles
on auxiliary switch block
The mechanical endurance can be increased if low current is used (for exam-
ple, 17 V 5 mA) but only if there is no arcing during switching.
Display of the contactor The 3RT1926 LED indicator block can be connected to the coil connections
function of the contactors in frame sizes S00 to S3. It indicates the status of the con-
tactors by means of the yellow LED. The indicator block can be snapped
onto the front in the opening intended for the inscription plate.
The advantage is that the LED indicator block can be used for AC/DC volt-
ages of 24 V to 240 V and that it is protected against polarity reversal.
Switching with auxil- The following applies to the contactors of the SIRIUS range:
iary contacts (≤ 110 V If voltages ≤ 110 V and currents ≤ 100 mA are to be switched, the auxiliary
and ≤ 100 mA) contacts of the 3RT1 contactors or the 3RH1 auxiliary contactors should be
used instead of the main contacts because of their contact reliability. This
comes from their high contact stability due, in particular, to the shape of the
contact pieces (cross-ribbing).
This ensures that the points of contact remain conductive in spite of surface
contamination and the effect of dust.
These auxiliary contacts are suitable for electronic circuits (programmable
controllers) with voltages > 17 V and currents in the milliampere range (test
circuit: 17 V, 5 mA).
Cross-ribbing Surface contamination is the most common cause of contact faults. Cross-
ribbing the contact areas is an extremely effective way of increasing contact
reliability. All the auxiliary contacts of the SIRIUS contactors have this fea-
ture.
The following illustration show you how cross-ribbing is particularly effective
against surface contamination due to the high number of contact areas and
high surface pressure:
Accumulated surface
contamination
Depression
Lip
Contact reliability of The contact areas of the SIRIUS auxiliary contacts display a high degree of
the auxiliary contacts contact reliability. Fault frequency rates of HF ≤ 10-8 (i. e. < 1 fault per
100 mill. operating cycles at 17 V, 1 mA) have been registered.
These values apply to auxiliary contacts that are either integrated in the con-
tactor housing or can be snapped on as auxiliary switch blocks.
In the case of built-on auxiliary switch blocks at the side, fault frequency
rates are between 10-6 and 10-8.
The tests are based on the requirements placed on signal generators by
electronic controllers.
This means that with the auxiliary contacts of the SIRIUS contactors or aux-
iliary contactors, the permissible contact resistance is only exceeded once
during a total of 108 (100 million) switching operations. During a long period
of operation, therefore, a fault is not expected to occur, irrespective of the
number of switching operations.
A restriction applies in the case of auxiliary switch blocks built on at the
side.
Definition of switch The fault frequency HF is defined as the number of contact faults that occur
fault frequency HF during a certain number of switching operations.
Electrical service life of The rated operational current Ie is defined in acc. with utilization category
the main AC-4 (switching off 6 times the rated operational current) for a contact ser-
contacts vice life of approximately 200 000 operating cycles.
If mixed modes are used - in other words, if normal switching mode (the
rated operational current is switched off in acc. with utilization category AC-
3) is mixed with occasional inching mode (several times the rated opera-
tional current is switched in acc. with utilization category AC-4) - the service
life of the contact pieces can be roughly calculated with the following for-
mula:
A
X = -----------------------------------------
1 + --------- ⋅ --- – 1
C A
100 B
Key to the formula:
X Contact service life in mixed mode in operating cycles
A Contact service life in normal operation (Ia=Ie) in operating cycles
B Contact service life in inching mode (Ia = a multiple of Ie) in operating
cycles
C Percentage of the total number of switching operations accounted for
by inching operations
The following characteristic curves illustrate the contact service life of con-
tactors when switching inductive three-phase loads (AC-3), irrespective of
the breaking current and rated operational voltage. The prerequisites are
arbitrary (i.e. not synchronous with the phase relation of the control station
operating the network).
Characteristic curve: The characteristic curves illustrate the contact service life of the main con-
contact service life of tacts of contactors when switching inductive three-phase loads (AC-3).
the main contacts Ia = breaking current
Ie = rated operational current
PN = rated output of three-phase induction motors with squirrel cage at
400 V
500 V
690 V
400 V
Contactor type 3RT1015 3RT1016, 3RT1017
(3 kW) (4 kW, 5,5 kW)
10 7
10 7 8 6 8 NSB0 0473a
8 6 6
4
6 4 4
4 2
2 2
2 10 6
10 6 8 10 6
10 6 8 6 8
8 6 6
4
6 4 4
4 2
2 2
2 10 5
5
10 8 10 5
10 5 8 6 8
8 6 6
4
6 4 4
4 2
2 2
2 10 4
4
10 8 10 4
2 3 4 5 6 8 10 20 I a (A) 40 50 60 80
7 9 12 I e (A)
3 4 5,5 PN (kW)
Figure 3-3: Characteristic curve of the electrical service life of the main contacts (frame size S00)
Frame size S0
Operating cycles at
230 V
500 V
690 V
400 V
Frame size S2
Operating cycles at
230 V
500 V
690 V
400 V
Contactor type 3RT1034 3RT1035 3RT1036
(15 kW) (18,5 kW) (22 kW)
10 7
10 7 8 6 8 NSB00475a
8 6 4 6
6 4 4
4 2
22
2 6
10
10 6 8 10 6
10 6 8 6 8
8 6 4 6
6 4 4
4 2
2 2
2 10 5
10 5 8 10 5
10 5 8 6 8
8 6 4 6
6 4 4
4 2
2 2
2 10 4
4
10 8 10 4
10 20 30 40 50 60 80 100 Ia(A) 200 300 400
32 40 50 Ie (A)
15 18,5 22 PN (kW)
Figure 3-5: Characteristic curve of the electrical service life of the main contacts (frame size S2)
Frame size S3
Operating cycles at
230 V
500 V
690 V
400 V
30 37 45 PN (kW)
Figure 3-6: Characteristic curve of the electrical service life of the main contacts (frame size S3)
Characteristic curve: The contact service life depends on the breaking current. The prerequisites
contact service life of are arbitrary (i.e. not synchronous with the phase relation of the control sta-
the auxiliary contacts tion operating the network).
The characteristic curves apply to:
• Integrated 3RT10 auxiliary contacts
• 3RH1911 auxiliary switch blocks for contactors in frame size S00
• 3RH1921 auxiliary switch blocks for contactors in frame sizes S0 to S3
30
NSB00472
Basic unit
Operating cycles in millions (10 6 )
10
5 Basic unit with
4 attachable
3 contact block
2
DC-13 DC-13
1 220 V 110 V
AC-15/AC-14
0,5
DC-13
24 V
0,1
0,05
1)
0,01
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 5 6 7 10 I a (A) I a = breaking current
I e DC-13 I e DC-13 I e AC-15 I e DC-13 I e = rated operational current
220 V 110 V < 230 V 24 V
Figure 3-7: Characteristic curve of the electrical service life of the auxiliary contacts
Field of application The 3-pole 3RT10 contactors use 3 NO contacts as main contacts. They are
mainly used to switch three-phase induction motors.
Frame sizes The full performance range from 3 to 45 kW/400 V (utilization categories AC-
2 and AC-3) is covered by 4 frame sizes.
The frame sizes cover the following levels of standard motor output:
• Frame sizes S00, S2, S3: three standard levels of motor output each
• Frame size S0: 4 standard levels of motor output
Dimensions The contactors are provided with alternating or direct current magnetic sys-
tems. The required floor areas of the devices of the two operating mecha-
nism types are the same. As of frame size S0, the installation depth for con-
tactors with the DC magnet system is between 10 mm and 15 mm greater
than for the variants with the AC magnet system.
Power ratings All the specified power and current ratings apply to an ambient temperature
of 60 °C without derating.
Increasing the power The ease of expansion is an advantage for configuration. In many applica-
tions there is enough space to insert the contactor with the next higher rat-
ing class and thus increase motor output.
3.3.2 3RT1446 contactors with 3 main contacts for switching resistive loads (AC-1)
Field of application The 3RT14 46 contactors with 3 main contacts for switching resistive loads
are used for applications in the AC-1 utilization category:
• Switching of resistive loads such as heating systems or resistance fur-
naces
• Applications in which a low switching capacity is sufficient
• Applications in which high continuous currents occur without peaks (e.g.
as a generator contactor or in the case of variable-speed drives.
Switching capacity 1.5 times the Ie/AC-1 can be switched on and off. Switching off higher cur-
rents, with the emergency stop, for example, is possible up to 8 times the
Ie/AC-3 current.
Comparison: 3RT1046/ The following table shows you the difference between the 3RT1446 and
3RT1446 3RT1046 contactors for normal AC-3 applications:
Note on configuration The 3RT10 range of contactors for switching motors also has a specific AC-1
switching capacity. It is much less costly, however, to use the AC-1 contac-
tor 3RT14 for this specific purpose.
Accessories You can use the same accessories for the 3RT14 contactors as you can for
the 3RT104 contactors in frame size S3.
Model There are two variants of the contactors with 4 main contacts :
• 3RT13 with 4 NO contacts
• 3RT15 with 2 NO and 2 NC contacts
You can use the accessories for both the 3-pole SIRIUS contactors and the
4-pole variants.
Field of application The following table gives the fields of application for the 3RT13 and 3RT15
contactors:
Auxiliary contacts The following table specifies the maximum number of auxiliary contacts
that can be attached:
Contactor combination The 4-pole 3RT13 contactors with 4 NO contacts as main contacts in frame
with mechanical inter- sizes S0 to S3 are suitable for putting together contactor combinations with
locking mechanical locking for use, for example, in supply switchovers.
The following tables show how the contactor combinations are put together
in different frame sizes:
1
3/4 Attach the pole to the left side
of the same contactor.
3
4
3RA1922-2C
7
9
Table 3-13: 4-pole reversing contactor combination with front interlock (frame size S0)
3RA1924-2B
Table 3-14: 4-pole reversing contactor combination with lateral interlock (frame size S0)
Table 3-15: 4-pole reversing contactor combination (frame sizes S2 and S3)
Attention
The mechanical interlock at the front cannot be used in contactors in frame
sizes S2 and S3.
Field of application 3RT16 capacitor-switching contactors are used to switch power capacitors
that are used in reactive-current compensation.
Frame sizes The capacitor-switching contactors are available in frame sizes S00 to S3
with the rating levels 12.5, 15 kvar, 25 kvar, and 50 kvar at 400 V.
S00 S3
RT-01023
RT-01022
Auxiliary switch The auxiliary switch block snapped onto the capacitor-switching contactor
contains three leading NO contacts and a normal NO contact that can be
assigned as you wish. A 2-pole auxiliary switch block can also be attached at
the side of the capacitor-switching contactors (variants: 2 NO contacts, 2 NC
contacts, or 1 NO + 1 NC contact).
Switching capacitors/ A single capacitor can normally be switched on because the current is lim-
banks of capacitors ited by the inductance of the upstream transformer and the cables. It is
more difficult to switch banks of capacitors (parallel connection of a capaci-
tor to capacitors already present) because the current is now only limited by
the low inductance of the connecting leads and the capacitors.
This problem is solved in the case of capacitor-switching contactors using
precharging resistors.
Precharging resistors The precharging resistors are an integral part of the contactor in 3RT16
capacitor-switching contactors. They are switched on via leading auxiliary
contacts before the main contacts close. This results in damping down to
approximately 10 % of the undamped peak currents. Damping of peaks in
the making current prevents disturbances to the network.
Important
Make sure when switching banks of capacitors that you adhere to the speci-
fied minimum inductance between the capacitors connected in parallel that
are to be provided in addition.
3RT10. capacitor The normal 3RT10 contactors for switching motors also have a certain
switching capacity capacitor switching capacity. Details of this can be found in
Section 3.7, Technical specifications: Utilization category AC-6b, switching of
individual capacitors and switching of low-inductance three-phase capaci-
tors. The tables contain information on the switching of individual capacitors
and the switching of banks of capacitors.
Operation Caution
Only switch to discharged capacitors! Do not carry out a function test by
hand.
The precharging resistors must not be removed as this will damage the con-
tact pieces in circuits with a load.
Circuit diagram
L1 L2 L3
F0
A1 1 3 5 43
A2 2 4 6 44
C1
Field of application The contactors with an extended operating range are used in systems with
strong fluctuations in the control supply voltage and at the same time high
ambient temperatures, such as railway applications in extreme climatic con-
ditions, rolling mills, etc.
Standards Contactors with an extended operating range comply with the following
standards:
• IEC 60 947-4-1
• EN 60 947-4-1 (VDE 0660 Part 102)
• The requirements of IEC 60 077
They are shockproof in acc. with DIN VDE 0106 Part 100.
Exception: the series resistor in frame sizes S0 to S3
Control current circuits The magnet coils of the contactors have an extended operating range of 0.7
and auxiliary current to 1.25 x Us and are wired with varistors as standard to provide protection
circuits against overvoltage. This increases the time to contact parting compared
with standard contactors by 2 ms to 5 ms.
With/without a series The 3RH11 and 3RT10 contactors with the suffix -0LA0 at digits 13 to 16 in
resistor the order number are used particularly where, in addition to a wide operat-
ing range and a high ambient temperature of 70 °C, several auxiliary con-
tacts are required. Up to 4 auxiliary contacts can be used in these variants.
To ensure that the magnetic system can produce the required amount of
power at power-up, the contactors initially require a certain amount of over-
excitation. By means of the series resistor, the contactors are switched to
the normal hold-in coil level after power-up.
If fewer auxiliary contacts are required, contactors with the same extended
operating range that work without a series resistor are available up to frame
size S0.
The two ranges are described in more detail below.
Arrangement of compo- Auxiliary contactors and contactors of frame size S00 are available with the
nents in frame size S00 following:
• A built-on block that contains the series resistor (the NC contact required
for the switchover in the basic unit is already wired).
• Integrated varistor
• A 4-pole auxiliary switch block (in acc. with EN 50 005) can also be built
on.
Arrangement of compo- Contactors of frame sizes S0 to S3 are fitted on the front with an auxiliary
nents in frame sizes S0 switch block with 2 NO contacts + 2 NC contacts. The separate series resis-
to S3 tor that is attached at the side next to the contactor on the 35 mm rail has
connecting leads for contactor attachment. An NC contact of the auxiliary
switch block is required for the switchover to hold-in coil level. A circuit dia-
gram with the terminal points is stuck onto each contactor.
Auxiliary contacts One NC contact of the auxiliary contacts is required for the series resistor.
The number of auxiliary contacts that are available beyond this is listed in
the selection and order data. With frame size S00, the auxiliary switch block
that you may need must be ordered separately.
Installation The following types of installation are permissible for contactors and auxil-
iary contactors in ambient temperatures of up to 70 °C:
Frame size S00: installation in series
Frame sizes S0 to S3: The resistor block must be installed on the right next
to the contactor because of the connecting leads there.
E1+
E1+ RV K1
RV K1
K1 13 23 31
K1 1 3 5
NSB00560a
A2-
14 24 32
NSB00559a
A2-
2 4 6
Frame sizes S0 to S3
Terminal markings in acc. with EN 50 012
Contactors 3RT102.-, 3RT103.-, 3RT104.-3K.44-0LA0
With front-mounted 4-pole auxiliary switch block 3RH1921-1HA22
(+)
A1 1 3 5 13 21 31 43
NSB00561a
A2( ) 2 4 6 14 22 32 44
2 NO + 2 NC contacts
Identification number 22
Figure 3-11: Contactors with an extended operating range, terminal markings
RV
A1
21 A2
22
(+) (-)
Figure 3-12: Contactors with an extended operating range, circuit diagram
Ambient temperature The permissible ambient temperature for operating the contactors at the full
operating range of the magnet coils is -35 °C to +70 °C. During continuous
operation with temperatures > +55 °C, the mechanical service life, the cur-
rent-carrying capacity of the conducting paths, and the switching frequency
are reduced.
Auxiliary contactors are switching devices for auxiliary circuits for control-
ling, reporting, and interlocking. Auxiliary contactors have to meet specific
requirements in terms of clear terminal markings and a time- and cost-sav-
ing terminal system.
The SIRIUS 3RH1 auxiliary contactors (frame size S00) meet these require-
ments
Terminal markings The terminal markings comply with EN 50 011 and EN 50 005 (for a more
detailed explanation, see Section 3.4.1, Auxiliary switches).
Frame size and features 3RH1 auxiliary contactors are available with the following:
• Frame size S00
• With AC and DC operation
• Format as for motor contactor of frame size S00
• 4-pole basic version
• Can be extended to 8 poles with snap-on auxiliary switch blocks
• Screw-type or Cage Clamp terminals
Screw-type terminals The 3RH1 auxiliary contactors have captive screws (cross-tip Pozidriv,
size 2), with all the terminal points open on delivery. The screwdriver guides
allow screwdriving machines to be used.
Cage Clamp terminals The 3RH11 auxiliary contactors are also available with Cage Clamp terminals
- a screwless terminal system. This type of terminal is particularly suitable if
strong shaking or vibrations can be expected at the installation location.
These terminals are also suitable for two-conductor connections. All the ter-
minals are accessible from the front and are easily visible.
Soldering pin Both the 4-pole basic version as well as the auxiliary contactors that have an
connections auxiliary switch block attached at the front (see Section 3.4, Accessories)
can be soldered onto printed circuit boards using a soldering pin adapter.
Contact reliability All the switching elements of the 3RH1 auxiliary contactors are equipped
with contact pieces that have particularly high contact stability, ensuring
high contact reliability even at low voltages and currents. This subject is dis-
cussed in detail in Section 3.2.3.2, "Contact reliability".
3RH14 latched If there is a short circuit in the low-voltage network, or when large drive
auxiliary contactors motors are switched on directly, the control supply voltage for the auxiliary
contactors may fail briefly or fall under the permissible tolerance level. To
ensure continuous operation, the variant with mechanical latching (3RH14)
can be used with the auxiliary contactors.
These auxiliary contactors latch mechanically after power-up and remain in
an energized state even in the event of a power failure. The auxiliary contac-
tor can be unlocked electrically using an interlock release magnet or manu-
ally using a button on the front of the attached latched block. When the volt-
age returns, the production program can be resumed immediately without
resetting times due to the storage feature of the auxiliary contactors. The
contactor coil and the coil of the release magnet are both designed for con-
tinuous operation.
The power input is the same for the contactor coil and the release coil. The
mechanical service life is 1 million operating cycles.
3.3.7 3RT10 contactor relays for switching motors (interface) and 3RH11 contactor relays for
switching auxiliary circuits
Contactor relays are available in the SIRIUS modular system for switching
motors and auxiliary circuits for the purpose of smooth interaction with elec-
tronic controllers. These are variants of the 3RT10/3RH11 contactor series
with the following features:
• Low power input
• Wide operating range of the magnet coil 0.7 to 1.25 x Us
• High contact reliability of the auxiliary contacts
• Integrated or attachable overvoltage damping
Contact reliability The high contact reliability of the auxiliary contacts ensures that false sig-
nals do not occur even at low switching capacities. With a voltage of 17 V
and a current of 1 mA, there is on average less than one contact fault per
100 million switching operations.
Overvoltage damping Overvoltage damping protects sensitive output levels of electronic control-
lers against switching overvoltages of the coil.
Extended operating The operating range of the coil of the contactor relays covers a voltage
range range from 0.7 to 1.25 x Us (Us= rated control supply voltage). This wide
operating range is required for the supply voltage of electronic controllers
with the required voltage tolerances.
The supply voltage of electronic controllers with 24 VDC covers the range
20.4 V to 28.8 V in acc. with DIN 19 240. If you take into consideration an
additional loss of voltage of up to 3 V during the output phases, the contac-
tor drive must be able to operate perfectly with voltages between 17.4 V and
28.8 V. The 3RT10 and 3RH11 contactor relays for electronic controllers
operate safely from 17 V to 30 V, which corresponds to a voltage range of
0.7 x Us to 1.25 x Us. This is a considerably wider operating range than that
of 0.85 to 1.1 x Us for contactors and auxiliary contactors in acc. with
IEC 60 947, DIN EN 60 947 (VDE 0660).
Voltage ranges The following graphic shows you the voltage ranges for electronic control-
lers and drives of contactors and contactor relays with a rated control supply
voltage of Us = 24 VDC:
Power consumption Variant 1: The power input of the magnet coils for contactor relays in frame
size S00 is 2.3 W at 24 VDC (operating range: 0.7 to 1.25 x US).
Variant 2: Contactor relays with reduced coil performance in frame size
S00, P = 1.4 W at 24 VDC (operating range: 0.85 to 1.85 US).
The power input of magnet coils for contactor relays in frame size S0 is
4.2 W at 24 VDC (operating range: 0.7 to 1.25 x US).
Contactor combinations are available for reversing (3RA1) in frame sizes S00
to S3:
• Installed in the factory
Frame sizes S2 and S3 are delivered already mounted on a base plate.
• As a kit for self-assembly
The same accessories can be used as for the basic units of the correspond-
ing frame size (see Section 3.4).
For motor protection an overload relay must be attached.
4-pole contactor combinations for reversing can be put together in frame
sizes S0 and S2.
S00 S0
3RU1.1
1
2 3RU1.2
Figure 3-14: Fully assembled contactor combination for reversing (frame sizes S00 and S0)
Approvals The s and u approvals only apply to complete contactor combinations and
not to combinations you have assembled from separate parts.
Switchover time If the contactors are interlocked by means of their auxiliary switches (electri-
cal interlocking) or by mechanical interlocking, there is no overlapping of the
contacting and the arcing time between the contactors at switchover.
The switching times of the contactors are not affected by the mechanical
interlock.
Auxiliary contact Different auxiliary switches can be attached (at the front or the side) to the
elements 3RA1 reversing combination. An integrated auxiliary switch contact is avail-
able in frame size S00.
Accessories The following accessories for the basic units can also be used for contactor
combinations for reversing:
• Auxiliary switch blocks (at the front/side)
• Surge suppressors
• Soldering pin adapters (frame size S00)
The following accessory is designed specifically for contactor combinations
for reversing:
• Locking devices for mechanical interlocking
• Locking devices for mechanical and electrical interlocking (at the front/
side)
• Terminals for contactor coils (for frame sizes S0 to S3)
• Mechanical connectors
• Wiring modules
Terminals for To reach the coil terminals A1 and A2 of the contactor combinations for
contactor coils reversing more easily from contactors of frame sizes S2 and S3, you can
use terminals for contactor coils.
For each combination, 2 x A1 and 1 x A2 are required.
Wiring module Wiring modules are available to enable you to carry out different types of
wiring (Dahlander wiring, for example).
You can find out how to mount the wiring modules in the diagrams of the
self-assembly kits.
Note
If you want NC contact interlocking, you must use contactors with 1 NC
contact in the basic unit with the 3RT1 contactors of frame size S00.
The following graphics show you how to mount the locking devices at the
front for mechanical interlocking in frame size S0:
➀
3RA1923-2A
1
6
3
2
RESET
5
1 ➁
Figure 3-15: Star-delta combination, locking device at the front (frame size S0)
The following graphics show you how to mount the locking devices at the
front for mechanical interlocking with frame sizes S2 and S3:
3RA1932-2C
1 3
2
4
5
RESET
Figure 3-16: Star-delta combination, locking devices at the front (frame sizes S2/S3)
Kits The following table shows you the components of the kit for the contactor
combination for reversing in frame size S00 and explains how to put it
together:
1
4
Table 3-16: Assembling the contactor combination for reversing (frame size S00)
The following table shows you the components of the kit for the contactor
combination for reversing in frame size S0 and explains how to put it
together:
3
4/5 Attach the wiring modules (4)
in order to connect the main
4 conducting paths and tighten
the terminals (5).
Table 3-17: Assembling the contactor combination for reversing (frame size S0)
The following table shows you the components of the kits for the contactor
combination for reversing in frame size S2 and S3 and explains how to put it
together:
5 À
Table 3-18: Assembling the contactor combination for reversing (frame sizes S2/S3)
4-pole contactor combi- 4-pole contactor combinations for reversing are available in frame sizes S0
nation for reversing and S2. You will require the following to mount these combinations:
• Frame size S0: locking device for mechanical interlock
• Frame size S2: locking device for mechanical interlock and 2 connecting
clips
The following table shows you how to set up the 4-pole contactor combina-
tion for reversing in frame size S0:
1
3/4 Put the 4th pole on the
other side of the same con-
3 tactor by placing the cat-
ches on the pole into the
4
openings shown on the con-
tactor and snapping the pole
3 onto the contactor.
4
Figure 3-17: 4-pole contactor combination for reversing (frame size S0)
The following table shows you how to set up the 4-pole contactor combina-
tion for reversing in frame size S2:
3RA1924-2B
Figure 3-18: 4-pole contactor combination for reversing (frame size S2)
NO contact function If contactors are used with 1 NO contact that is intended for an auxiliary
not locked function (e.g. as a signaling device), the wiring module must be separated.
The illustration below shows you the wiring for this function:
Mounting and connec- The contactor combinations for reversing have screw-type connections that
tion are suitable for both screw-on and snap-on mounting on a 35 mm rail.
Conductor cross-sec- The permissible conductor cross-sections of the contactor combinations for
tions reversing correspond to those of the basic units for the corresponding frame
size.
L1
L2
L3
F1
K1
K2
NSB00634
F2
UV W
M
3~
Figure 3-20: Contactor combination for reversing, main circuit (frame sizes S00 to S3)
L1/L+ L1/L+
F3 F3
95 95
F2 F2
96 96
S0
10 2
S2 S1 S
53 53
S1 K1 S2 K2
54 54
22 22 22 22
K2 K1 K2 K1
21 21 21 21
NSB00636
NSB00635
A1 A1 A1 A1
K1 K2 K1 K2
N/L A2 A2 N/L A2 A2
Figure 3-21: Contactor combination for reversing, control circuit (frame size S00)
S0 "Off" button
S1 "Clockwise rotation on" button
S2 "Counterclockwise rotation on" button
S "Right/off/left" selector switch
Control circuit: S0 to S3
L1/L+ L1/L+
F3 F3
95 95
F2 F2
96 96
S0
10 2
S2 S1 S
.3 .3
S1 K1 S2 K2
.4 .4
NSB00639
NSB00638
A1 A1 A1 A1
K1 K2 K1 K2
N/L A2 A2 N/L A2 A2
Figure 3-22: Contactor combination for reversing, control circuit (frame sizes S0 to S3)
Technical specifications The technical specifications of the contactor combinations for reversing cor-
respond to those of the basic units for the corresponding frame size.
The following graphics show you the fully assembled star-delta combina-
tions in frame sizes S00 to S2:
Auxiliary switch
Auxiliary switch block, at front
block Time-delay auxiliary
At the front switch block, at
front
Time-delay auxiliary
switch block, at
front
Frame size S2
Auxiliary switch
block, at front Time-delay auxiliary switch
block, at front
Frame size S2
Time-delay auxiliary
switch block, at side
Field of application The star-delta combination is used to start three-phase induction motors
which require a low load torque during startup.
Starting current ratio Star-delta starting can only be used when the motor is switched to delta
mode, starts with no load, or if the load torque during the star startup is
small and does not increase rapidly.
In the star stage, the motors can be loaded with approximately 50 %
(torque class KL16) and 30 % (KL10) of its rated torque.
The tightening torque is reduced to approximately 1/3 of the value at direct
power-up.
The starting current is approximately 2 to 2.7 times the rated current for the
motor.
Switchover Switching from the star to the delta stage can only be carried out once the
motor has completed startup to the rated speed.
The required switchover pause and interlock is included in the contactor
combination.
Important
Drives that require an early switchover are not suitable for star-delta star-
ting.
Overload protection The fully assembled combinations are not equipped with overload protec-
tion. Overload relay (3RU11) and tripping devices for thermistor motor pro-
tection must be ordered separately.
The overload relays can be attached to the contactor directly or set up sepa-
rately. The overload relay is set to 0.58 times the set current Ie. See
Chapter 4 on overload relays for further information.
Features of the star- The following table shows you the features of the fully assembled star-delta
delta combinations combinations with time-delay auxiliary switch blocks with the star-delta
function (3RT19.6-2B...) and solid-state time relays with semiconductor out-
put and the possible configuration if you use the self-assembly kit:
Important
If a time-delay auxiliary switch block is mounted on the front of K3, an auxili-
ary switch block can only be mounted on the side of K3.
Accessories The following basic unit accessories can also be used for star-delta combina-
tions:
• Auxiliary switch blocks (front, side)
• Surge suppressors
• Time-delay auxiliary switch blocks with star-delta function
In addition, there are special accessories available for the star-delta combi-
nations:
• 3-phase feed-in terminals
• Star-point links (parallel links)
• Terminals for contactor coils (S2/S3)
• Mechanical connectors
• Wiring modules
Terminal for In order to reach coil terminals A1 and A2 in the star-delta combination bet-
contactor coils ter from contactors in frame sizes S2 and S3, terminals for contactor coils
can be used.
For each combination, 2 x A1 and 1 x A2 are required.
Infeed With conductor cross-sections > 2 x 2.5 mm2 and 1 x > 4 mm2 , a feed-in
terminal block must be used for the star-delta combination in frame size
S00. This makes the following conductor cross-sections possible:
• Frame size S00: up to 6 mm2
• Frame size S0: up to 25 mm2
• Frame size S2: up to 50 mm2
Kits The following table shows you the components of the kit for the star-delta
combination in frame size S00 and explains how to put it together:
8 7
The following table shows you the components of the kits for the star-delta
combinations in frame sizes S0 to S3 and explains how to put it together:
Compensating for dif- In star-delta combinations with contactors of different frame sizes, it is nec-
ferent depths essary to compensate for the mounting depth of the smaller contactor.
One frame size is the maximum difference possible.
The following depth compensation must be made for a mechanical interlock
attached at the side:
• S2-S2-S0: K3: 1.5 mm; K2: 0 mm
• S3-S3-S2: K3: 0 mm; K2: 27.5 mm
Mounting and connec- The star-delta combinations have screw-type connections that are suitable
tion for both screw-on and snap-on mounting on the 35 mm rail.
Conductor cross-sec- The permissible conductor cross-sections of the star-delta combinations cor-
tions respond to those of the basic units for the corresponding frame size.
F0 F0
K1 1 3 5 K3 1 3 5 K2 K1 1 3 5 K3 1 3 5 K2
2 4 6 2 4 6 2 4 6 2 4 6
NSB00642 NSB00645
F1 F1
U1 W2 U1 W2
V1 M U2 V1 M U2
W1 3 ~ V2 W1 3 ~ V2
U1 W2 U1 W2
V1 M U2 V1 M U2
W1 3 ~ V2 W1 3 ~ V2
S00 S0
F0 F0
K1 1 3 5 K3 1 3 5 K2
2 4 6 2 4 6
NSB00648
F1
U1 W2
V1 M U2
W1 3 ~ V2
U1 W2
V1 M U2
W1 3 ~ V2
S2 and S3
Figure 3-25: Star-delta combination, main circuit (frame sizes S00 to S3)
S0
S1 S
13 13
K1 K1
14 14
27 37 27 37
K4 K4
28 38 28 38
22 22 22 22
K3 K2 K3 K2
21 21 21 21
K4 K1 K2 K3 K4 K1 K2 K3
N(L ) N(L )
NSB00643 NSB00644
Control circuit: S0 to S3
S0
S1 S
44 44
K1 K1
43 43
33 13 33 13
27 38 K1 K2 27 38 K1 K2
K4 34 14 K4 34 14
28 37 28 37
12 22 12 22
K3 K2 K3 K2
11 21 11 21
K4 K2 K3 K1 K4 K2 K3 K1
N(L ) N(L )
Accessories for frame The accessories for contactors that switch motors and for auxiliary contac-
size S00 tors are of the same type. The accessories are attached at the front.
Accessories for frame The accessories are (with few exceptions) the same for frame sizes S0 to
sizes S0 to S3 S3. They can be attached in different ways:
• Auxiliary switches can be attached at the front or the side.
• Surge suppressors can be attached at the top or the bottom.
The following graphic shows you the accessories for the contactors that switch motors and for the
contactor relays of frame size S00:
3 17
18
4
5
12
1
6 19 13
20
7
2
8
10
11
14
15
16
NSB00448
The following graphic shows you the accessories for the auxiliary contactors and contactor relays for
auxiliary circuits of frame size S00:
3
12
5
7 13
8 2
14
10
11
15
16 NSB00066a
Figure 3-29: Accessories for auxiliary contactors/contactor relays of frame size S00
1 Auxiliary contactor
2 Contactor relay for auxiliary circuits
3 Solid-state time relay block, on-delay
4 Solid-state time relay block, off-delay
5 Auxiliary switch block, time-delay (types: on-delay or off-delay)
6 1-pole auxiliary switch block, infeed from above
7 2-pole auxiliary switch block, infeed from above
8 1-pole auxiliary switch block, infeed from below
9 2-pole auxiliary switch block, infeed from below
10 4-pole auxiliary switch block (terminal markings in acc. with EN 50 011 or EN 50 005)
11 2-pole auxiliary switch block, standard or electronic type
(terminal markings in acc. with EN 50 005)
12 Soldering pin adapter for auxiliary contactors with 4-pole auxiliary switch block
13 Soldering pin adapter for auxiliary contactors and contactor relays
14 Additional load module to increase the permissible residual current
15 Surge suppressor with LED
16 Surge suppressor without LED
The following graphic shows you the accessories for the contactors of frame sizes S0 to S3:
4
5
17 20
11
18
10 21
16 2
12
1
14
1
6
9
15
7
19
8
16
20
13
21
22 3
23
NSB00449
Frame size S0 to S3
The contactors of frame sizes S0 to S3 do not have an integrated auxiliary
conducting path in the basic unit.
Auxiliary switch blocks Auxiliary switch blocks for extending the auxiliary contacts are available with
Formats screw-type or Cage Clamp terminals to attach to contactors to switch
motors. They are available in the following formats:
• At the front 1 to 4-pole for frame sizes S00 to S3
• At the side: 2-pole for frame sizes S0 to S3
Different auxiliary switch blocks can be added to the 3RT1 basic units,
depending on the application:
The following can be snapped onto the front of the contactors:
• Frame sizes S00 to S3: a 4-pole auxiliary switch block
or
• Frame sizes S0 to S3: up to four 1-pole auxiliary switch blocks
Frame sizes S0 to S3
If the depth of the installation space is limited, 2-pole auxiliary switches can
be attached on the right and left side in frame sizes S0 to S3.
If 1-pole auxiliary switch blocks are used, note the location ID on the contac-
tor.
1-pole/2-pole auxiliary 1 or 2-pole auxiliary switch blocks that can be connected from above or
switch blocks below make the wiring simple and straightforward when setting up feeders.
These auxiliary switch blocks are only available with a screw-type terminal.
We recommend with the circuit breaker/contactor combination that you use
auxiliary switch blocks that are connected from below. In the case of the
contactor/overload relay combination, an auxiliary switch connected from
above is more suitable.
Electronically opti- The electronically optimized auxiliary switch blocks contain enclosed switch-
mized auxiliary switch ing elements that are particularly suitable for switching low voltages and
blocks currents (hard gold-plated contacts) as well as for use in dusty atmospheres.
The rated operational current is Ie/AC-14 and DC-13: 1 to 300 mA, voltage: 3
to 60 V.
The electronically optimized auxiliary switch blocks are available as screw-
type or Cage Clamp terminal types:
• Frame size S00 (3RH1911-.NF..): Has two enclosed auxiliary contacts (1
NO contact + 1 NC contact, 2 NO or 2 NC contacts
• Frame sizes S0 to S3 (3RH1921-.FE22): Has two enclosed auxiliary con-
tacts and two standard auxiliary contacts, each 1 NO contact + 1 NC con-
tact
• The switched current is in acc. with the VDE 0435 regulation for relays.
Auxiliary contacts The following table gives you an overview of all the available auxiliary con-
tacts:
Auxiliary contacts and atta-
Frame size S00 Frame sizes S0 to S3
chable accessories
2-pole auxiliary switch (infeed Attachable at the front Attachable at the front
from 1 side)
Adding to the auxiliary • The 3RT10 basic units of frame size S00 with an integrated auxiliary con-
contacts tact can be supplemented with up to 4 contacts using attachable auxiliary
switches.
• The basic units of frame sizes S0 to S3 do not have any auxiliary switches,
but auxiliary switches can be attached at the front or the side.
The following table shows you the expansion options for the different frame
sizes:
Frame size Auxiliary switch block Connection
Auxiliary switch at front Auxiliary switches that can be attached at the front are hooked into the
opening of the contactors and pulled down until they snap into place. They
can be removed using the release lever in the middle.
Auxiliary switches at The auxiliary switches are hooked onto the left or right side of the contactor
side (S0 to S3) and snapped onto it. They are removed again by pressing the ribbed sur-
faces.
1 1
2
1
2
2
1
Figure 3-32: Auxiliary switch at side
Note
When you use two 2-pole, auxiliary switches at the side, you must attach an
auxiliary switch block on the left and right in the interests of symmetry.
Maximum number of The following table shows you the maximum number of auxiliary switches and their
auxiliary switches combination options:
Frame size S0 and S2 (3RT102./3RT103.)
1 auxiliary 4 auxiliary 2 auxiliary A maximum of 4 auxiliary contacts can
contact contact contact be attached, and you can use any type
element elements elements of auxiliary switch. When you use two
2-pole, auxiliary switch blocks at the
side, you must attach a block on the
left and right in the interests of sym-
metry. In some situations, it is permis-
Max. 4 0 0
sible to have more auxiliary contacts
Max. 2 0 1 in frame size S2 (for more details,
0 1 0 please contact Technical Assistance).
0 0 1+1
Table 3-24: Possible auxiliary switch combinations (frame size S0/S2)
Switching of the auxil- With the standard type of auxiliary switch, when the contactors are
iary contact elements switched on, first the NC contacts are opened and then the NO contacts are
closed.
On
Contactor Off
N On
Standard Off
auxiliary On
switch S Off
In contactors of frame size S00 with an integrated auxiliary contact, the ter-
minal marking complies with EN 50 012. This also applies to contactors of
frame sizes S0 to S3 with an attached auxiliary switch block (2 NO + 2 NC
contacts) that are available as complete systems.
Expanding the contac- All the contactors of frame size S00 (3 and 4-pole) can be expanded with
tors of frame size S00 auxiliary switch blocks with the identification numbers 40 to 02 in acc. with
EN 50 005 as follows:
• Frame size S00 with an integrated auxiliary contact (identification number
10E or 01) for contactors with 3 or 5 auxiliary contacts
• Frame size S00 with 4 main contacts for contactors with 2 or 4 auxiliary
contacts
Note
The identification numbers on the auxiliary switch blocks only apply to the
attached auxiliary switches.
Expanding the contac- Contactors with one NO contact as an auxiliary contact with screw-type or
tors with 1 integrated Cage Clamp terminals, identification number 10E, can be expanded with
NO contact, S00 auxiliary switch blocks with terminal markings in acc. with DIN EN 50 012
(3RT101.-...01) for contactors with 2, 4, and 5 auxiliary contacts. The terminal markings of
the complete contactors comply with EN 50 012. The identification numbers
11E, 22E, 23E, and 32E on the auxiliary switch blocks apply to the complete
contactors.
Important
Auxiliary switch blocks in acc. with EN 50 012 can only be combined with
contactors of frame size S00 that have 1 NO contact in the basic unit
because they are coded. These auxiliary switch blocks cannot be combined
with contactors that have an NC contact in the basic unit (identification num-
ber 01).
Auxiliary contacts S00 The following graphic shows you the auxiliary contacts that can be used to
expand the contactors of frame size S00 (terminal marking in acc. with
EN 50 012 or EN 50 005):
contactors, contactors,
Hilfsschütze
DIN EN 50 012 DIN
DINEN 50 005,
EN50 005,
5, 4 or 2 58oroder
3 6 Kontakte
auxiliary contacts auxiliary contacts
NSB00450
Figure 3-34: Auxiliary contacts, contactors for switching motors (frame size S00)
Expanding the contac- With contactors of frame sizes S0 to S3, you can also attach 1-pole auxiliary
tors of frame sizes S0 to switch blocks instead of 4-pole auxiliary switch blocks.
S3 The terminal markings of the 1-pole auxiliary switch blocks consist of
sequence numbers (location ID) on the basic unit and function numbers on
the auxiliary switch blocks.
Auxiliary contacts S0 to The following graphic shows you the auxiliary contacts that can be used to
S3 expand the contactors of frame sizes S0 to S3 (terminal marking in acc. with
EN 50 005 or EN 50 012):
4-pole auxiliary switch blocks 1-pole aux. switch blocks
contactors
3RT10 2. contactors
3RT10 3. 3RT10 2.
3RT10 4. 3RT10 3.
without auxiliary 3RT10 4.
contact without
auxiliary contact
NSB00451a
03, 30
identification no. 40, 31, 22, 02 identification no. 31, 22, 13 04, 40
Figure 3-35: Auxiliary contacts, contactors for switching motors (frame sizes S0 to S3)
3.4.1.2 Terminal markings of the contactors and auxiliary contactors combined with auxiliary
switch blocks
Terminal markings in The terminal markings for contactors are defined in EN 50 005 that contains
acc. with EN 50 005 general directives. The following summarizes the basic rules that apply to
switching elements of auxiliary circuits:
• The terminals of auxiliary contact elements are designated by two-digit
numbers.
• The digit in the unit place is a function number (NC contact: 1 and 2,
NO contact: 3 and 4).
• The digit in the tens place is a sequence number (all the switching ele-
ments of the same function must have different sequence numbers).
Identification numbers The identification numbers mean:
(DIN EN 50 005) Switching devices with a fixed number of auxiliary contact elements (NO
contacts or NC contacts) can be assigned a two-digit identification number.
The first digit represents the number of NO contacts and the second one
the number of NC contacts.
There is no information on the sequence of NO contacts and NC contacts in
the contactor/auxiliary contactor.
Note
The identification numbers on the auxiliary switch blocks only apply to the
attached auxiliary switches.
EN 50 012/ For certain equipment such as auxiliary contact elements of contactors and
EN 50 011 auxiliary contactors, the EN 50 012 and EN 50 011 standards also apply.
The EN 50 012 defines the terminal markings and identification numbers for
auxiliary contact elements of particular contactors.
The terminal markings of the auxiliary contact elements match the terminal
markings of corresponding auxiliary contactors with the ID letter E (in acc.
with EN 50 011). For auxiliary contact elements of contactors with the same
identification number, the terminal marking must correspond to the
sequence defined in the standard.
Graphical symbols for Below are some examples of graphical symbols for auxiliary contact ele-
auxiliary contact ele- ments of contactors that comply with EN 50 012:
ments
ID ID ID
Coil Main contact elem. Auxiliary contact elements Auxiliary contact elements Auxiliary contact elements
no. no. no.
13 21 33 43 13 21 31 43 13 21 31 41
31 22 13
14 22 34 44 14 22 32 44 14 22 32 42
13 21 33 43 53 13 21 31 43 53 13 21 31 41 53
41 32 23
14 22 34 44 54 14 22 32 44 54 14 22 32 42 54
Figure 3-36: Graphical symbols for auxiliary contact elements in acc. with EN 50 012 (excerpt)
Device circuit diagrams The following device circuit diagrams of the auxiliary switch blocks for con-
tactors that switch motors contain the terminal markings in acc. with
EN 50 012:
3RT101 contactors
2 NO + 2 NC contacts 2 NO + 3 NC contacts 3 NO + 2 NC contacts
Identification number: 22E Identification number: 23E Identification number: 32E
A1(+) 1 3 5 13 21 31 43 A1(+) 1 3 5 13 21 31 41 53 A1(+) 1 3 5 13 21 31 43 53
A1(+) 1 3 5 13 21 31 43
NSK-1321
A2( ) 2 4 6 14 22 32 44
14 22 34 44 14 22 32 44 14 22 32 42
Figure 3-37: Device circuit diagrams of the auxiliary switch blocks (DIN EN 50 012)
Definition: The main standard for the designation of switching elements for the auxiliary
EN 50 011 contactors is EN 50 011, which defines the terminal markings, identification
numbers, and identification letters of certain auxiliary contactors using a spe-
cific sequence of the switching elements. The number, type, and position of
the switching elements must be specified using an identification number fol-
lowed by an identification letter.
In the case of 8-pole auxiliary contactors, the letter "E" means that four NO
contacts have to be arranged on the lower (rear) contact level.
Expansion using auxil- The following example of an auxiliary contactor with 4 NO contacts (contact
iary switch blocks designation in acc. with EN 50 011 and EN 50 005) explains how auxiliary
switch blocks are added on:
auxiliary contactors,
DIN EN 50 011, 4 contacts
identification no.
identification no. 40E 31E, 22E
Graphical symbols of Below are some examples of graphical symbols for auxiliary contactors with
the auxiliary contactors the identification letter E that comply with EN 50 011:
14 24 34 44 14 24 34 44 54 64 74 84
13 21 33 43 13 23 33 43 53 61 73 83
31 E 71 E
14 22 34 44 14 24 34 44 54 62 74 84
13 21 31 43 13 23 33 43 53 61 71 83
22 E 62 E
14 22 32 44 14 24 34 44 54 62 72 84
13 21 31 41 13 23 33 43 53 61 71 81
13 E 53 E
14 22 32 42 14 24 34 44 54 62 72 82
11 21 31 41 13 23 33 43 51 61 71 81
04 E 44 E
12 22 32 42 14 24 34 44 52 62 72 82
Figure 3-39: Graphical symbols for auxiliary contactors in acc. with EN 50 011 (excerpt)
Device circuit diagrams The following device circuit diagrams of the auxiliary contactors contain ter-
minal markings in acc. with EN 50 011:
NS2-5552
NS2-5553
NS2-5554
A2( ) 14 24 34 44 A2( ) 14 22 34 44 A2( ) 14 22 32 44
NS2-5558
NS2-5559
NS2-5560
A2( ) 14 24 34 44 54 64 74 84 A2( ) 14 24 34 44 54 62 74 84 A2( ) 14 24 34 44 54 62 72 84
5 NO + 3 NC contacts 4 NO + 4 NC contacts
Identification number: 53 E Identification number: 44 E
A1(+) 13 23 33 43 53 61 71 81 A1(+) 13 23 33 43 51 61 71 81
NS2-5561
NS2-5562
A2( ) 14 24 34 44 54 62 72 82 A2( ) 14 24 34 44 52 62 72 82
Position diagrams The following position diagrams of the auxiliary switches of frame sizes S00
to S3 also apply to leading and lagging contacts:
N On
Standard Off
auxiliary On
switch S Off
N On
Off
Overlapping
auxiliary On
switches S Off
Figure 3-41: Position diagrams of the auxiliary switches (frame sizes S0 to S3)
Variants The following variants of the time-delay auxiliary switch are available:
• On-delay
• Off-delay without auxiliary supply
• Star-delta function
On-delay and off-delay The time-delay auxiliary switch in the on-delay or off-delay variants has the
functions following features:
• It facilitates time-delayed functions up to 100 s
• 3 single time areas
• Contains a relay with 1 NO contact and 1 NC contact that switches the
on-delay or off-delay depending on the version.
Star-delta function The time-delay auxiliary switch with star-delta function has the following fea-
tures:
• Equipped with a delayed and an instantaneous NO contact between
which there is an idle time of 50 ms.
• The delay time of the NO contact can be set at between 1.5 s to
30 seconds.
• The contactor on which the time-delay auxiliary switch block is mounted
functions instantaneously.
Conductor cross-sec- The permissible conductor cross-sections correspond to the auxiliary con-
tions ductor terminals of the corresponding frame size.
Description The time-delay auxiliary switch of frame size S00 has the following features:
• The power supply is provided using plug-in contacts directly via the coil
connections of the contactors, parallel to A1/A2.
• The time function is activated when the contactor that has the auxiliary
switch block mounted on it is switched on.
• The off-delay version functions without an auxiliary supply.
• The minimum on-time is 200 ms.
• To dampen switching overvoltages of the contactor coil, a varistor is inte-
grated in the time-delay auxiliary switch of frame size S00.
Information on mount- Note about the off-delay without auxiliary supply function:
ing The position of the output contacts is not defined at shipment (bistable
relay). Apply the control supply voltage once, and then switch it off again to
set up the initial state of the contacts.
Important
The time-delay auxiliary switch cannot be built onto contactor relays.
Installation/removal Caution
Switch off the supply voltage to A1/A2 before you install or remove the time-
delay auxiliary switch block.
Connection When they are attached, the connections for the rated control supply volt-
age are connected to the contactor below by the integrated spring contacts
of the time-delay auxiliary switch.
Function 3RT1916-2E
diagrams A1/A2
On-delay
NSK-7932
27/28
3RT1916-2F
> 200 ms
A1/A2 Off-delay
27/28 Without auxiliary supply
35/36 1 NO and 1 NC contact
t
3RT1916-2G
A1/A2
Star-delta function
NSK-7955
Y 27/28
1 NO contact, instantaneous
D 37/38
t 50 ms 1 NO contact, delayed
t
Figure 3-43: Function diagrams of the time-delay auxiliary switches (frame size S00)
Description The time-delay auxiliary switch for frame sizes S0 to S3 has the following
features:
• The power supply of the time-delay auxiliary switch is via 2 terminals (A1/
A2).
• The time delay for the time-delay auxiliary switch can be activated by par-
allel connection to any contactor coil, or by any source of voltage.
• The off-delay version works without an auxiliary supply.
• The minimum on-time is 200 ms.
• In addition to the time-delay auxiliary switch, a 1-pole auxiliary switch
block can be snapped onto the front of the contactor.
• The time-delay auxiliary switch does not have any integrated overvoltage
damping for the contacted contactor.
Information on mount- Note about the off-delay without auxiliary supply function:
ing The position of the output contacts is not defined at shipment (bistable
relay). Apply the control supply voltage once, and then switch it off again to
set up the initial state of the contacts.
.
Installation/removal
3RT1.2 The time-delay auxiliary switch
3RT1.3 is attached to the front of the
3RT1.4 contactor.
1 2
Connection The A1 and A2 terminals for the rated control supply voltage of the time-
delay auxiliary switch are connected to the respective contactor with cables.
Terminal markings Because an additional auxiliary switch block can be snapped onto the con-
tactor, the terminals of the delayed contacts have been
designated as -5/-6 (NC contact) and -7/-8 (NO contact).
Function
diagrams A1/A2 On-delay
NSK-7932
27/28 1 NO and 1 NC contact
35/36
t
> 200 ms
A1/A2
Off-delay without auxiliary supply
NSK-7933a
27/28
1 NO and 1 NC contact
35/36
t
A1/A2
Star-delta function
NSK-7955
Y 27/28
D 37/38
1 NO contact, instantaneous
t 50 ms 1 NO contact, delayed
Figure 3-45: Time-delay auxiliary switches, function diagrams (frame sizes S0 to S3)
The solid-state time relay blocks are suitable for AC and DC operation. To
dampen switching overvoltages of the contactor coil, a varistor is inte-
grated.
Variants The following variants of the time-delay auxiliary switch are available:
• On-delay (integrated varistor)
• Off-delay with auxiliary supply (integrated varistor)
On-delay and off-delay The time-delay auxiliary switch in the on-delay or off-delay with an auxiliary
functions supply variants has the following features:
• It facilitates time-delayed functions up to 100 seconds.
• 3 individual time ranges
• Contactors with a solid-state time relay block close and open with a delay
according to the time set.
Connection: on-delay The on-delay time relay block is connected in series to the contactor coil;
time relay block the A1 terminal of the contactor coil must not be connected.
Connection: off-delay When an off-delay time relay block is attached, the contactor coil is con-
time relay block tacted via the time relay block; the A1 and A2 terminals of the contactor coil
must not be connected.
Conductor cross-sec- The permissible conductor cross-sections correspond to the auxiliary con-
tions ductor terminals of the corresponding frame size.
Notes on configuration The control of loads parallel to the start input is not permissible in AC opera-
tion. See the relevant circuit diagram ¿ below.
The off-delay solid-state time relay blocks (3RT1916-2D.../3RT1926-2D...)
have a live start input (B1). With AC voltage, this can imitate the control of a
parallel load on the B1 terminal. In this case, an additional load (contactor
K3, for example) should be wired as shown in circuit diagram À.
¿ À
L1 L1
S1 K3 S1
A1 B1 A2 K3 A1 B1 A2 K3
K1 K1
A1 A2 A1 A2
K2 K2
N N
Caution
Switch off the supply voltage to A1/A2 before you install or remove the
solid-state time relay block.
Installation/removal Important
The time-delay auxiliary switch cannot be attached to contactor relays.
The solid-state time relay block of frame size S00 is attached to the front of
the contactor and latched into place with a pushing movement.
Installation Removal
2
1
1 2
Figure 3-47: Solid-state time relay block with semiconductor output, installation (frame size S00)
Connection When the solid-state time relay block is installed, it is connected at the
same time with the A1 and A2 coil connections of the contactor by the plug-
in contacts. Coil connections of the contactor that are not required are cov-
ered by covers on the housing of the time relay block, thus preventing inad-
vertent connection.
NSK-7937a
NSK-7938a
B1/A2
t > 35 ms
A1/A2 A1/A2
Contactor Contactor
t
Figure 3-48: Solid-state time relay block with semiconductor output, function diagrams (frame size
S00)
S1
A1 A1 B1 A2
K1 K1
A1 A2
K2 A1 A2
K2
A1 A2
A1 A2
N/L
Figure 3-49: Solid-state time relay with semiconductor output, circuit diagrams (frame size S00)
Installation/removal
The solid-state time relay block
for the contactors of frame sizes
S0 to S3 is attached at the top on
1 the A1 and A2 coil connections
of each contactor, connecting the
2 time relay electrically and mecha-
nically with pins.
Figure 3-50: Solid-state time relay with a semiconductor output, installation (frame size S00)
✘ Connection prohibited!
Can be connected if required
Figure 3-51: Solid-state time relay with semiconductor output, circuit diagrams
NSK-7938a
B1/A2
NSK-7937a
t > 35 ms
A1/A2 A1/A2
Contactor Contactor
t
Figure 3-52: Solid-state time relay with semiconductor output, function diagrams
Field of application The additional load module for the contactors of frame size S00 is used to
increase the permissible residual current and to limit the residual voltage of
SIMATIC semiconductor outputs.
Mode of operation Malfunctions can sometimes occur when SIRIUS contactors and auxiliary
contactors of frame size S00 work together with SIMATIC output modules
whose residual current at signal "0" is higher than is permissible for the con-
tactors of frame size S00. The maximum permissible residual current of the
electronic components is 3 mA for contactors of frame size S00 with a
230 VAC drive, and in the case of higher residual currents, the contactors no
longer drop down.
The additional load module is used to ensure the safe switching off of S00
contactors in the case of direct control by programmable controllers via
230 VAC semiconductor outputs.
The additional load module takes on the function of overvoltage damping at
the same time.
Installation The additional load is connected in parallel to the contactor coil. It has the
same construction as the surge suppressor and is attached on the front of
the contactors with or without an auxiliary switch block.
Field of application The 3RH1924-1GP11 coupling link is intended for contactors of frame sizes
S0 to S3. It can be controlled by a programmable controller output because
the operating range of 17 to 30 VDC is permissible.
Mode of operation A contactor of frame size S0 to S3 can be controlled, for example, at 24 VDC
with a low control level (< 0.5 W) from a programmable controller output.
The control voltage for the coupling link and the rated control supply voltage
for the contactor are electrically isolated. An LED indicates the switching
state of the coupling link.
To dampen switching overvoltages of the contactor coil, a varistor is inte-
grated in the coupling link.
Installation Caution
Switch off the supply voltage applied to L1 and N before installation.
Conductor cross-sec- The permissible conductor cross-sections correspond to the auxiliary con-
tions ductor terminals of the corresponding frame size.
Circuit diagram
L1 B1+ B2- N
K1
U
U
K1 Coupling link
A1
K2 K2 Contactor
A2
Technical specifications You can find the technical specifications of the coupling link in Section 3.6,
Technical specifications.
Unused coil
Disconnection of an unused contactor coil
U Sp [V ]
U Sp
3000
1000
50 100 t[µs]
Varistor
Circuit with a varistor
(AC/DC operation)
U Sp [V ]
U Sp
200
0 20 t[µs]
RC element
Circuit with an RC element
(AC/DC operation)
U Sp [V ]
U Sp
200
0 5 t[m s]
Diode
Circuit with diode
(DC operation)
U Sp [V ]
U Sp
20
0 = 0,6 V ^
= U SP
derD iode
0 200 t[µs]
Surge suppressors The following surge suppressors are available for the 3RT1 contactors:
Without
Surge suppressor With LED
LED
Suppression diode x x -- --
Diode combination: -- x x x
suppression diode and Zener
diode
Varistor x x x x
RC element -- x x x
Selection aid The following table gives you a comparison of the effects of the different
surge suppressors:
Suitable for
Overvoltage
Surge suppressor control supply Effect
is limited
voltage
1) The rate of drop is reduced once or twice to zero for a few ms:
• A safe drop is always ensured in the case of switching without current.
• The contact pieces are subjected to a greater thermal load when switch-
ing with current. When switching at the upper current limit, this can result
in overload.
Frame sizes S0 to S3
1
2
2 To remove them, press the varis-
1 tors, RC elements, and diode
combinations forwards, and
remove them from the recess.
U
R_L2 C_L2 V_L2
U
R_L3 C_L3 V_L3
U
2T1 4T2 6T3 2T1 4T2 6T3
M M
3~ 3~
Figure 3-60: RC element/varistor, circuit diagrams
Description The LED module can be connected to the coil terminals of the contactors of
frame sizes S0 to S3. It indicates the status of the contactors by means of
yellow LEDs.
Mode of operation The LED module can be used for AC/DC voltages of 24 V to 240 V.
The LEDs are connected bidirectionally to protect against polarity reversal.
Both LEDs light up in AC control, and one lights up in DC control, depending
on the polarity.
Connection The LED module is connected to the A1 and A2 coil terminals of the contac-
tor.
Installation The LED module is snapped onto the front in the openings intended for the
inscription plate.
3.4.7.2 Auxiliary connecting lead terminal, 3-pole (for frame size S3)
Using the 3-pole auxiliary lead terminal, auxiliary and control cables can be
connected to the main cable terminals.
Conductor cross-sections of auxiliary connecting leads that can be con-
nected:
Screw-type terminals (1 or 2 conductors can be connected)
Single-core mm2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) in acc. with IEC 60 947;
Max. 2 x (0.75 to 4)
Finely stranded with wire end ferrule mm2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5)
AWG cables, single- or multi-core AWG 2 x (20 to 16); 2 x (18 to 4); 1 x 12
Terminal screws M3
Tightening torque Nm 0.8 to 1.2 (7 to 10.3 lb.in)
Table 3-30: Conductor cross-sections of 3-pole auxiliary connecting lead terminals (for frame size S3)
Description The connection of the main conducting path to the EMC suppression mod-
ule reduces the contact sparking that is responsible for contact erosion and
many of the clicks, which in turn supports an EMC-compatible configuration.
Mode of operation The EMV suppression module reduces through 3 phases the radio-fre-
quency parts and the voltage peaks. The advantages of this are as follows:
• Longer service life of the contact pieces
• Higher operational reliability and high system availability
A fine grading within the performance class is not required because smaller
motors have greater inductance due to their construction, and one EMC sup-
pression module is thus sufficient for all non-stabilized drives up to 5.5 kW.
Installation
The EMC suppression module is
attached to the underside of the
contactor. To do this, hook the
EMC suppression module with
both hooks onto the contactor,
and push it upward until the con-
1 nection pins of the EMC module
are firmly in place in the terminal
2 3RT1916-1P.. openings of the contactor.
Varistor circuit A varistor circuit can absorb a high level of energy and can be used for fre-
quencies from 10 to 400 Hz (stabilized drives). There is no limit below the
buckling stress.
Description The standard contactors of frame size S00 in the SIRIUS range can be sol-
dered onto printed circuit boards by means of the soldering pin adapter.
Soldering pin connection is possible:
• For contactors with an integrated auxiliary contact
• For contactors with an attached 4-pole auxiliary switch block
• For the reversing wiring of the S00 contactors. This involves carrying out
the reversing wiring before soldering it on the printed circuit board
3
Figure 3-63: Soldering pin connection, mounting
Mounting on 4-pole
auxiliary switch block
1
3
Figure 3-64: Mounting the soldering pin connection on a 4-pole auxiliary switch block
Removing the spring If necessary, the spring for attachment to the rail can be removed before the
soldering pin connection is mounted.
Figure 3-65: Removing the spring from the soldering pin connection
Permanent load in The following applies to permanent loads in the case of parallel connection
parallel connection unless specified otherwise in the catalogs:
• When three conducting paths are connected in parallel, 2.5 times the
amount of continuous current can be applied, and when two conducting
paths are connected in parallel, 1.8 times the continuous current can be
applied. Make sure, however, that the making and breaking capacity do
not increase because the contact pieces do not close and open at the
same time, and therefore the contact pieces in a conducting path have to
switch the entire making and breaking current.
• The wiring must be routed in such a way that each conducting path has
the same line length.
• Any short-circuit current is distributed in proportion to the conducting
path resistances.
Important: The operating current of electromagnetic, instantaneous
short-circuit releases is not reached.
Making/breaking You can find out the making and breaking capacity of contactors in relation
capacity to the load currents in the parallel connection of two or three conducting
paths from the following table:
Ie Ie Ie I’e I’’e I’’e
1 3 5 1 3 5 1 3 5 1 3 5 7
2 4 6 2 4 6 2 4 6 2 4 6 8
Ie Ie Ie Ie Ie Ie
1) 2 conducting paths 3 conducting paths 4 conducting paths
3-pole switching
in parallel1) in parallel1) in parallel1)
Ue
U = -------
3
Terminal cover Offers additional shock protection 2 covers per contactor are
for box terminals required (for the upper
3RT19.6-4EA2 and lower main terminals)
Terminal cover Ensures that voltage intervals are adhered to
for lug and Provides shock protection when the box termi-
bar connection nal is removed
3RT1946-4EA1
Table 3-33: Covers
Installation The following diagrams show you how to mount the covers:
Snapped onto a
S00, S0 35 mm rail (in acc. with Removed without a tool
EN 50 022)
Snapped onto a
S2, S3 35 mm rail (in acc. with
EN 50 022) The snap-on spring can be opened with a
screwdriver
Snapped onto a
S3
75 mm rail
Table 3-34: Attachment
Screw-on attachment
The 3RT1 contactors can be screwed
M4 onto a flat surface.
• With 2 M4 screws, diagonal
• Maximum tightening torque 2 Nm
• Washers and spring lock washers must
always be used
• The distance to grounded parts at the
side must be more than 6 mm
Installation positions The contactors are designed for use on vertical surfaces. The following
installation positions are permissible for AC and DC operation:
22,5° 22,5°
360° Without overload relay
22,5° 22,5°
225° 315°
Vertical installation The following table indicates usage in a vertical installation position:
position
No. Size AC/DC Output power Measure
5 S0 DC 4 to 11 kW Special variant
6 S0 AC 4 to 11 kW Without restriction
8 S2 AC 15 to 22 kW Special variant
10 S3 AC 30 to 45 kW Special variant
Motor and auxiliary contacts (including the contactor relay variants) are
included in frame size S00.
3.5.2 Connection
The SIRIUS contactors are available with the following terminal types:
• Frame sizes S00 to S3: screw-type terminals
• Contactors and auxiliary contactors of frame size S00: All the terminals
are also available as Cage Clamp terminals
• Contactors of frame sizes S0 to S3: The auxiliary switches and coil con-
nections are also available with Cage Clamp terminals.
• Accessories: screw-type and (for most of the range) Cage Clamp termi-
nals
• The contactors of frame size S3 have removable box terminals for the
main conductor terminals. This enables the connection of ring lugs or bus-
bars.
Screw-type terminals The devices with screw-type terminals have the following features:
• All the connections have captive screws.
• All the terminal points are delivered in the open position.
• The screwdriver guides allow screwdriving machines to be used.
• In frame size S00, all the terminal screws for the main and auxiliary cir-
cuits have a uniform screw size (cross-tip Pozidriv 2 screws) and therefore
all require the same torque.
• In all the frame sizes (S00 to S3), the terminal screws are identical for the
auxiliary conductor terminals (no bit change and uniform torque).
Cage Clamp terminals In the variant with Cage Clamp terminals, the devices have the following
features:
• The contactors are recommended if strong shaking or vibrations can be
expected at the installation location.
• The terminals are also suitable for two-conductor connections
• All the terminals are accessible from the front and are easily visible.
• A maximum of two conductors with a cross-section of 0.25 mm2 up to a
maximum 2.5 mm2 can be used for each terminal point.
Cage Clamp terminals: The following illustration shows you how to use the Cage Clamp terminals:
Procedure
Insert the screwdriver straight
into the opening up until the
stop (1) to open the clamping
unit. Insert the conductor in
the oval terminal opening (2),
and remove the screwdriver
(3).
2
1.5 to 2.5 mm²
1
3
Figure 3-70: Cage Clamp terminals
3RT1916-4JA02
≤ 1 mm²
Figure 3-71: Insulation stop with Cage Clamp terminals
Two-conductor connec- It is possible with all the main, auxiliary, and control cable connections to
tion connect two conductor ends. They can also be used to connect untreated
conductors with different cross-sections. Box terminals each with 2 terminal
points are provided for the main conductor connection in contactors of
frame sizes S2 and S3.
This connection method also promises problem-free looping and parallel
connection without intermediate terminals.
Conductor cross-sec- Permissible conductor cross-sections for main and auxiliary connections:
tions S00
Main and auxiliary conductors
0.8 to 1.2 Nm
Cage Clamp
∅ 5 to 6 mm / PZ2 7 to 10.3 lb.in
10 2 x (0.5 to 1.5 mm²)
2 x (0.25 to 2.5 mm²)
2 x (0.75 to 2.5 mm²)
10 2 x (0.5 to 1.5 mm²)
2 x (0.25 to 1.5 mm²)
2 x (0.75 to 2.5 mm²)
10
---- 2 x (0.25 to 2.5 mm²)
S0
Control conductor: A1/A2 Main conductor
Auxiliary conductor: NO/NC
Screw-type termi- Cage Clamp termi- L1 L2 L3
nal nal T1 T2 T3
0.8 to 1.2 Nm 2 to 2.5 Nm
----
∅ 5 to 6 mm / PZ2 7 to 10.3 lb.in 18 to 22 lb.in
10 2 x (0.5 to 1.5 mm²) 2 x (1 to 2.5 mm²)
2 x (0.25 to 2.5 mm²)
2 x (0.75 to 2.5 mm²) 2 x (2.5 to 6 mm²)
10 2 x (0.5 to 1.5 mm²) 2 x (1 to 2.5 mm²)
2 x (0.25 to 1.5 mm²)
2 x (0.75 to 2.5 mm²) 2 x (2.5 to 6 mm²)
10
---- 2 x (0.25 to 2.5 mm²) ----
S2
Control conductor: A1/A2 Main conductor
Auxiliary conductor: NO/NC
Screw-type termi- Cage Clamp termi- L1 L2 L3
nal nal T1 T2 T3
S3
Control conductor: A1/A2 Main conductor
Auxiliary conductor: NO/NC
Screw-type termi- Cage Clamp termi- L1 L2 L3
nal nal T1 T2 T3
0.8 to 1.2 Nm min
22 4 to 6 Nm
---- 4
∅ 5 to 6 mm / PZ2 7 to 10.3 lb.in 35 to 53 lb.in
10 2 x (0.5 to 1.5 mm²) 17
2 x (0.25 to 2.5 mm²) 2 x (2.5 to 16 mm²)
2 x (0.75 to 2.5 mm²)
10 2 x (0.5 to 1.5 mm²) 17 2 x (2.5 to 35 mm²)
2 x (0.25 to 1.5 mm²)
2 x (0.75 to 2.5 mm²) 1 x (2.5 to 50 mm²)
10 17 2 x (10 to 50 mm²)
---- ----
1 x (10 to 70 mm²)
2 x (10 to 1/0)
AWG 2 x (18 to 14) 2 x (24 to 14) AWG
1 x (10 to 2/0)
Table 3-36: Conductor cross-sections (frame sizes S00 to S3)
Changing the magnet The magnet coils can be replaced in the case of contactors of frame sizes
coils S0 to S3.
S0 - AC operation The following illustration shows the replacement of the magnet coil in frame
size S0 in AC operation:
4a
Figure 3-72: Replacing the magnet coil (frame size S0/AC)
S2 - AC operation
3
1
S2 - DC operation
6
Figure 3-74: Replacing the magnet coil (frame size S2/DC)
S3 - AC operation
3
1
S3 - DC operation
6
3
Replace the front half of the
contactor, and tighten the 2
7
screws again.
Make sure the springs are in
8 their correct position.
Frame size S2
Remove the left identification
label, loosen the 2 screws on
the frontplate of the contactor,
and remove the top section of
3
the contactor (1, 2, 3).
Remove the movable contact
2 piece by gently tipping it
upward and then pulling it out
(4, 5). Loosen the screws that
2 attach the two immovable con-
1
tact pieces (6).
4 6
9
Replace the top section of the
contactor, and tighten the 2
screws on the frontplate.
Replace the identification label.
10
11
11
12
Figure 3-77: Replacing the contact piece (frame size S2)
Frame size S3
Loosen the 2 screws on the
frontplate of the contactor, and
remove the top section of the
2 contactor (1, 2).
Remove the movable contact
piece by gently tipping it
1 upward and then pulling it out
(3, 4). Loosen the screws that
attach the two immovable con-
tact pieces (5).
1
3 5
10
10
Contact pieces The following contact pieces can be used for frame sizes S2 and S3 for the
different performance classes:
S2 S3
3RT1034 3RT1035 3RT1036 3RT1044 3RT1045 3RT1046 3RT1446
15 kW 18.5 kW 22 kW 30 kW 37 kW 45 kW 140 A (AC-1)
34 35 36
106
45 99
5.3
5,3 8.6
8,6 5 67
5
3)
50
57,5
57.5
4)
51
118
2) 35
NSB00752a
15.5
15,5 67 5
10 135
1) 10 45 b) 86
5 3)
35
a
5
85
80
4)
60
2)
143
63
NSB00753c
15.5
15,5 86 5
Figure 3-81: 3RT10 2 contactors, 3RT10 2 contactor relays (frame size S0)
with surge suppressor, auxiliary switch block, and attached overload relay
a = 3 mm at < 240 V
a = 7 mm at > 240 V
b = DC 10 mm deeper than AC
1) Auxiliary switch block, attachable at the side
2) Auxiliary switch block, attachable at the front, 1-, 2-, and 4-pole (also electronically optimized variant 3RH1921-.FE22)
3) Surge suppressor
4) Drilling pattern
Distance to grounded parts at the side 6 mm
15 159
55 10 110
a
b) 5 3)
45
1)
5
112
4)
80
95
2)
171
75
NSB00754b
20.5
20,5 107 5
13 183
70 10 10 134
a
b) 5 3)
60
1)
5
4)
130
146
80
2)
221
5)
100
NSB00755b
6)
28 7 132 5
Figure 3-83: 3RT10 4, 3RT14 46 (frame size S3)
with surge suppressor, auxiliary switch block, and attached overload relay
a = 0 mm with varistor, diode combination and < 240 V
a = 3.5 mm with varistor and > 240 V
a = 17 mm with RC element
b = DC 13 mm deeper than AC
3)
5
57,5
57.5
50
4)
NSB00258a
5.3
5,3 8.6
8,6 5 67 35
45 99
45 106
8.6
8,6 99
5,3
5.3 5 67
2)
5
57.5
50
57,5
3)
NSB00757a 1) 35
b)
135
10 61 10 5 86
a
35
2)
60
80
85
4)
NSB 00758e
NSB00759c
b)
183
10 93 13 5 134
3)
a
60
1) 5
SIEMENS
4)
130
80
146
2)
5)
6)
NSB 00760b
121
67
44
100
72
60
85
48
18
ø5
5
45 NSB00761b 130
145
94
68
42
45x75
130
38
64
18
NSB00762a
55 5
8
159
Figure 3-90: 3RT1636 (frame size S2)
116
90
22,5 22,5 51
60x130
104
124
150
167
18
38
NSB00763a
70 5
7
8
183
45 5 118
50
60
28
NSB00764a
35
Figure 3-92: 3RT10 17, 3RH 11 (frame size S00)
70
45 5 148
35 x 60
86
47
NSB00765a
80
55 5 162
45 x 95
110
47
NSB00766a
95
70 5 186
60 x 130
145
47
NSB00767a
46
46
25
38
NSB00772
NSB00254
5 9 127
45 143 5 73
33
Figure 3-96: 3RT1916-2E.., -2F.., -2G.. (frame size S00) 3RT19 26-2E.., -2F.., -2G.. (frame sizes S0 to S3)
45 41
6 4 50
66
38
40
NSB00256
45 92
105
NSB00773
Figure 3-97: 3RT19 16-2 (frame size S00) 3RT19 26-2 (frame sizes S0 to S3)
For attachment to the front of the contactor Attachable on the top of the contactor
(dimensions also apply to off-delay time relay blocks) (dimensions also apply to off-delay time relay blocks and
to coupling links (3RH19 24-1GP11))
13.6
13,6
27,5
27.5
NSB00255
24 27
45 55
67.5
11.6
5
5
∅ 1.4
A1
50
5.2 8.6 8.6 8.6 8.6 5.2 57.5
67 50 57.5 71.5
71.5
18 x ∅ 2.0 A2
45
110
5
∅ 1.4
50
67
38.5 33.5
90
45 45
67.5
A1 A1
50 57.5
5
5 20 x ∅ 2.0 A2 20 x ∅ 2.0 A2
∅ 1.4
50
5.2 8.6 8.6 8.6 8.6 10.4 8.6 8.6 8.6 8.6 5.2 57.5 5.2 8.6 8.6 8.6 8.6 10.4 8.6 8.6 8.6 8.6 5.2
NSB00774
5
67
50
5 8.6
8,6 35 7.5
7,5
90 5 51
67
NSB00776
60
86
29
36
NSB00775
8 14 10 28 7.5
7,5
40 5 39
100 61 45 16
86 90 44
DC 95
NSB00777
120
95
13
10
10 17.5
17,5 50 8
120 5 36
52
110
DC 125
NSB00778
5
157
130
12
10
12 22 65 8
150 5 46
85
134
DC147
2.5
111
NC
112 34 29 36
25 55 80.5
121
122
45 16
48.5 44
10
Figure 3-103: 3RA1924-2B (frame sizes S0 to S3) 3RA1924-1A (frame sizes S0 to S3)
K4
K3 K2
NSB00779
135 5 67
143
(AC+DC)
Figure 3-104: Contactor combinations for star/delta (frame sizes S00 - S00 - S00)
88
K1 K3 K2
K4
K2
K1 K3 K4
7 10
150 169 (AC)
178 184 (DC)
NSB00781
125
140
K1 K3 K2 K4
7 10
150 169 (AC)
198 184 (DC)
NSB00782
K1 K3 K2 K4
7
10
150 194 (AC)
218 207 (DC)
NSB00783
Auxiliary circuit
Rating of the auxiliary contacts in acc. with IEC 60 947-5-1/DIN EN 60 947-5-1 (VDE 0660 Part 200)
Data apply to integrated auxiliary contacts and contacts in the auxiliary switch blocks for contactors in frame sizes S00 to S12
Contactor Frame sizes S00 to S12
Rated insulation voltage Ui (pollution degree 3) V 690
With laterally attachable auxiliary switch blocks
3RH19 21-.EA . . and 3RH19 21-.KA . . V Max. 500
Conventional free air thermal current Ith =
Rated operational current Ie/AC-12 A 10
AC loading
Rated operational current Ie/AC-15/AC-14
With rated operational voltage Ue 24 V A 6
110 V A 6
125 V A 6
220 V A 6
230 V A 6
380 V A 3
400 V A 3
500 V A 2
660 V2) A 1
690 V2) A 1
DC loading
Rated operational current Ie/DC-12
With rated operational voltage Ue 24 V A 10
60 V A 6
110 V A 3
125 V A 2
220 V A 1
440 V2) A 0.3
600 V2) A 0.15
Rated operational current Ie/DC-13
At rated operational voltage Ue 24 V A 101)
60 V A 2
110 V A 1
125 V A 0.9
220 V A 0.3
440 V A 0.14
600 V2) A 0.1
Contact reliability at 17 V, 1 mA Contact fault frequency < 10–8
in acc. with DIN EN 60 947-5-4 i. e. < 1 fault in 100 mill. operating cycles
Short-circuit protection for contactors without overload relay Short-circuit protection for contactors with overload relay, see Part 4.
Short-circuit protection for fuseless load feeders, see Part 5.
Main circuit
Fuse-links, performance class gL/gG
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE
– In acc. with IEC 60 947-4/DIN EN 60 947-4 (VDE 0660 Coordination type "1" 1) A 35
Part 102)
1
Coordination type "2" ) A 20
Unwelded 2) A 10
Or miniature circuit breaker (up to 230 V) with C characteristic A 10
3) Resistance-heated industrial furnaces and electric heating appliances, etc. (increased current consumption at startup of heating taken into account).
Short-circuit protection for contactors without overload relay Short-circuit protection for contactors with overload relay, see Chapter 4.
Short-circuit protection for unwelded contactors, see Chapter 5
(overload and short-circuit protection only with the 3RV10 circuit breaker).
Short-circuit protection for fuseless load feeders, see Chapter 5.
Contactor Frame size S0 S0 S0
Type 3RT10 23, 3RT10 24 3RT10 25 3RT10 26
Main circuit
Fuse-links, performance class gL/gG
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE
With fuse-links
– In acc. with IEC 60 947-4/DIN EN 60 947-4 Coord. type "1" 1) A 63 63 100
(VDE 0660 Part 102)
Coord. type "2" 1) A 25 25 35
Unwelded2) A 10 10 16
Or miniature circuit breaker with C characteristic A 25 25 32
(Short-circuit current 3 kA, coordination type 1) 1)
Auxiliary circuit
Fuse-links, performance class gL/gG A 10 10 10
DIAZED type 5SB, NEOZED type 5SE
(unwelded fuse at Ik ≥ 1 kA)
Or miniature circuit breaker with C characteristic (short-circuit current Ik < 400 A) A 10 10 10
1) Corresponds to section from IEC 60 947-4 (VDE 0660 Part 102):
Coordination type "1":
The destruction of the contactor and the overload relay is permissible. The contactor and/or overload relay must be replaced, if necessary.
Coordination type "2":
The overload relay must not be damaged. Contact welding on the contactor is permissible, if it can be easily
separated again from the contactor.
2)Test conditions in acc. with IEC 60 947-4-1.
Unwelded 3RT11 contactors, see Chapter 5 (overload and short-circuit protection only with the 3RV10 circuit breaker).
1) In acc. with VDE 0660 Part 102, rated value for different startup conditions, see Chapter 4.
2) Resistance-heated industrial furnaces and electric heating appliances, etc. (increased current consumption at startup of heating taken into account).
Short-circuit protection for contactors without overload relay Short-circuit protection for contactors with overload relay, see Part 4.
Short-circuit protection for fuseless load feeders, see Chapter 5.
Contactor Frame size S3 S3 S3
Type 3RT10 44 3RT10 45 3RT10 46
Main circuit
Fuse applications, performance class gL/gG
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE
– In acc. with IEC 60 947-4/DIN EN 60 947-4 Coordin. type "1" 1) A 250 250 250
(VDE 0660 Part 102)
Coordin. type "2" 1) A 125 160 160
Unwelded 2) A 63 100 100
Auxiliary circuit
Fuse applications, performance class gL/gG A 10 10 10
(unwelded fuse at Ik ≥ 1 kA)
DIAZED type 5SB, NEOZED type 5SE
Or miniature circuit breaker with C characteristic (short-circuit current Ik < 400 A) A 10 10 10
Drive
Shock resistance
Rectangular impulse With AC and DC operation g/ms 6.8/5 and 4/10
Sine pulse With AC and DC operation g/ms 10.6/5 and 6.2/10
z’ = z ⋅ ----- ⋅ --------------
Ie 400 V 1.5
1/h
I ′ U′
Technical specifications
Contactor Frame size S00 S0 S2 S3 S3
Type 3RT13 16/17 3RT13 25/26 3RT13 36 3RT13 44 3RT13 46
General specifications
Mechanical life Opera- 30 mill. 10 mill.
ting
cycles
Electrical service life with Ie/AC-1 Opera- Approx. 0.5
ting mill.
cycles
Rated insulation voltage Ui (pollution degree 3) V 690
Permissible ambient temperature For operation °C –25 to +60
During storage °C –55 to +80
Degree of protection in acc. with IEC 60 947-1 and IP20 IP 20
DIN 40 050 Terminal housing IP 00
Short-circuit protection for contactors without overload relay
Main circuit
Fuse-links, performance class gL/gG
NH type 3NA,
DIAZED type 5SB,
NEOZED type 5SE
– In acc. with IEC 60 947-4/
DIN EN 60 947-4 (VDE 0660 Part 102) Coord. type "1" 1) A 35 63 160 250 250
Coord. type "2" 1) A 20 25/35 63 125 160
Unwelded 2) A 10 16 50 63 100
Drive
Operating range of the magnet coils AC At 50 Hz: 0.8 - 1.1 x Us AC/DC: 0.8 - 1.1 x Us
At 60 Hz: 0.85 - 1.1 x Us
DC At +50 °C: 0.8 - 1.1 x Us
At +60 °C: 0.85 - 1.1 x Us
Power input of the magnet coils (cold coil and at 1.0 x Us)
AC operation Hz 50/60 50 50/60 50 50/60 50 50/60
Making capacity VA 26.5/24.3 61 64/ 145 170/ 270 298/
63 155 274
cos ϕ 0.79/0.75 0.82 0.82 0.79 0.76/ 0.68 0.72/
0.74 0.72 0.62
Holding power VA 4.4/3.4 7.8 8.4/ 12.5 15/ 22 27/
6.8 11.8 20
cos ϕ 0.27/0.27 0.24 0.24/ 0.36 0.35/ 0.27 0.29/
0.28 0.38 0.31
DC operation Making capacity = holding power W 3.3 5.6 13.3 15
The technical specifications for frame size S0 correspond, unless listed below, to those of the 3RT10 26 contactors,
for frame size 2 to those of the 3RT10 36 contactors, and for frame size S3 to those of the 3RT10 45 contactors.
Contactor Frame size S0 S2 S3
Type 3RT16 26 3RT16 36 3RT16 46
Capacitor power at 230 V 50/60 Hz kvar 8.5 14 29
operating voltage 400 V 50/60 Hz kvar 15 25 50
525 V 50/60 Hz kvar 20 32 65
690 V 50/60 Hz kvar 25 32 65
Auxiliary contacts attached (freely avai- 1 NO contact
lable)
Additional auxiliary contacts that can be attached (lateral) 2 NC contacts, 2 NO con-
tacts, or 1 NO + 1 NC
Operating range of the magnet coil 0.85 to 1.1 x Us
Max. switching frequency 1/h 180 100 100
Electrical life Operat- > 100,000
ing
cycles
Ambient temperature °C 60 55 55
Regulations IEC 60 947/DIN EN 60 947 (VDE 0660)
The technical specifications correspond to those of the 3RT10 contactors used to switch motors, unless listed below.
Auxiliary switch blocks cannot be added to 3RT10 1. contactor relays.
Two, 1-pole auxiliary switch blocks can be built on to the 3RT10 2. contactor relays.
Contactor Frame size S00 S00 S00 S0
Type 3RT10 1.-1HB4. 3RT10 1.-1JB4. 3RT10 1.-1KB4. 3RT10 2.-1KB40
Mechanical life Opera- 30 mill. 30 mill. 30 mill. 10 mill.
ting
cycles
Operating range of the magnet coils 0.7 to 1.25 x Us q (17 V to 30 V)
Power input of the magnet coil
(with a cold coil) With Us 17 V W 1.2 1.2 1.2 2.1
24V W 2.3 2.3 2.3 4.2
Making capacity = holding power 30V W 3.6 3.6 3.6 6.6
Permissible residual current
< 10 mA x ------------ < 10 mA x ------------ < 10 mA x ------------ < 6 mA x ------------
24 V 24 V 24 V 24 V
of the electronic components mA
(at 0 signal) Us Us Us Us
Suppressor circuit of the magnet coil Without overvoltage With diode With varistor With varistor
damping
U U
Switching times of the contactor
relays
Making At 17 V On delay NO ms 40 to 120 40 to 120 40 to 120 93 to 270
Off delay NC ms 30 to 70 30 to 70 30 to 70 83 to 250
At 24 V On delay NO ms 30 to 60 30 to 60 30 to 60 64 to 87
Off delay NC ms 20 to 40 20 to 40 20 to 40 55 to 78
At 30 V On delay NO ms 20 to 50 20 to 50 20 to 50 53 to 64
Off delay NC ms 15 to 30 15 to 30 15 to 30 45 to 56
Breaking At 17 V to 30 V On delay NO ms 7 to 17 40 to 60 7 to 17 18 to 19
Off delay NC ms 22 to 30 60 to 70 22 to 30 24 to 25
Protective separation between coil and contacts V 400 400 400 400
(in acc. with DIN VDE 0106 Part 101 A1 [Draft 02/89])
The technical specifications correspond to those of the 3RT individual contactor and the 3RU time relay, unless listed below.
starter Frame sizes S . . - S . . - S . . 00-00-00 00-00-00 0-0-0 0-0-0 2-2-0 2-2-2 2-2-2 3-3-2 3-3-2
Type 3RA . . . . 14 15 14 16 14 23 14 25 14 34 14 35 14 36 14 44 14 45
Mechanical life Operating 3 mill.
cycles
Short-circuit protection without overload Short-circuit protection with overload relay, see Part 4
relay
Highest rated current of the fuse
Main circuit1)
Fuse-links, performance class gL/gG
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE
Single or double incoming supply
– In acc. with IEC 60 947-4-1/ Coordination type "1" 1) A 35 35 63 100 125 125 160 250 250
DIN VDE 0660 Part 102 Coordination type "2" 1) A 20 20 25 35 63 63 80 125 160
Control circuit
Fuse-links, performance class gL/gG A 10,
DIAZED type 5SB, NEOZED type 5SE A
(Short-circuit current Ik ≥ 1 kA) 62), if the auxiliary contact of the overload relay is in the circuit of the contactor coil.
Circuit breaker with C characteristic A 10,
A
62), if the auxiliary contact of the overload relay is in the circuit of the contactor coil.
Size of the individual contac- Line contactor K1 Type 3RT 10 15 10 17 10 24 10 26 10 34 10 35 10 36 10 44 10 45
tors Delta contactor K3 Type 3RT 10 15 10 17 10 24 10 26 10 34 10 35 10 36 10 44 10 45
Star contactor K2 Type 3RT 10 15 10 15 10 24 10 24 10 26 10 34 10 34 10 35 10 36
Unassigned auxiliary con- See circuit diagram for the control circuit, page 3/93.
tacts of the individual contac-
tors
Current carrying capacity for the AC-3 utili-
zation category
Switchover time up to 10 s
Rated operational current At 400 V A 12 17 25 40 65 80 86 115 150
500 V A 8.7 11.3 20.8 31.2 55.4 69.3 86 112.6 138.6
690 V A 6.9 9 20.8 22.5 53.7 69.3 69.3 98.7 138.6
Rated power At 230 V kW 3.3 4.7 7.2 12 20.4 25.5 27.8 37 49
of three-phase induction motors 400 V kW 5.8 8.2 12.5 21 35 44 48 65 85
at 50 Hz and 500 V kW 5.3 6.9 13 20.5 38 48 60 80 98
690 V kW 5.8 7.5 18 20.4 51 66 67 97 136
1000 V kW – – – – – – – – –
Switching frequency with overload relay 1/h 15 15 15 15 15 15 15 15 15
Current carrying capacity for utilization cate-
gory AC-3
Switchover time to 15 s
Rated operational current At 400 V A 12 17 25 31 44 57 67 97 106
500 V A 8.7 11.3 20.8 31 44 57 67 97 106
690 V A 6.9 9 20.8 22.5 44 57 67 97 106
Rated power At 230 V kW 3.3 4.7 7.2 9.4 13.8 18.2 21.6 32 35
400 V kW 5.8 8.2 12.5 16.3 24 31.6 38 55 60
of three-phase induction motors
500 V kW 5.3 6.9 13 20.4 30 40 47 69 75
At 50 Hz and 690 V kW 5.8 7.5 18 20.4 42 55 65 95 104
1000 V kW – – – – – – – – –
Switching frequency with overload relay 1/h 15 15 15 15 15 15 15 15 15
4.1 Specifications/regulations/approvals
Standards • The 3RU11 thermal overload relays and the 3RB10 and 3RB12 electronic
overload relays comply with the following standards:
IEC 60947-1/DIN VDE 0660 Part 100
IEC 60947-4-1/DIN VDE 0660 Part 102
IEC 60947-5-1/DIN VDE 0660 Part 200
IEC 60801-2, -3, -4, -5; UL 508/CSA C 22.2.
• The 3RB10 and 3RB12 electronic overload relays also comply with the
EMC standards.
Tripping classes The tripping classes describe time intervals within which the overload relays
have to trip from a cold state with 7.2 times the set current in the case of a
symmetrical, three-pole load. You will find the tripping classes in which the
3RU11, 3RB10, and 3RB12 overload relays are available in Section 4.2. The
following table indicates the tripping classes and tripping times in acc. with
the IEC 60947-4-1 standard:
10A 2 < TA ≤ 10
10 4 < TA ≤ 10
20 6 < TA ≤ 20
30 9 < TA ≤ 30
Time-delayed overload The following table contains the operating limits of time-delayed overload
release releases in the case of an all-pole load:
Ambient tem-
perature-com- 1.05 1.2 1.5 7.2 + 20 °C
pensated
CLASS 10
CLASS 20
Table 4-2: Operating limits of time-delayed overload releases in the case of an all-pole load
Resistance to extreme The 3RU11, 3RB10, and 3RB12 overload relays are climate-proof in acc. with
climates IEC 721.
Shock protection The 3RU11, 3RB10, and 3RB12 overload relays are shockproof in acc. with
DIN VDE 0106 Part 100.
Depending on assignment to other devices, extended terminal covers are to
be attached to the connecting bars.
Ships' systems The 3RU11, 3RB10, and 3RB12 overload relays are suitable for use in ships'
systems.
The overload relays have been submitted to:
• GL (Germany)
• LRS (Great Britain)
• DNV (Norway)
Explosion-proof motors The 3RU11 thermal overload relays and the 3RB10 and 3RB12 electronic
overload relays comply with the regulations for the overload protection of
explosion-proof motors of "increased safety" protection types (EEx d and
EEx e) in acc. with EN 50 019/DIN VDE 0165 and DIN VDE 0170/0171:
• 3RU11: KEMA test certificate no. Ex-97.Y.3235
DMT certificate in acc. with directive 94/9/EC: DMT 98 ATEX G001
• 3RB10: PTB test rules: PTB test report no. 3 43-8803/98
• 3RB12: PTB test rules: PTB test report no. 3 53-3907/96
EC special test certificate in acc. with directive 94/9/EC:
PTB 01 ATEX 3220
When the 3RB12..-....1 electronic overload relays (no change to the switch-
ing state of the auxiliary contact elements in the event of the failure of the
control supply voltage) are used to protect EEx d and EEx e motors, sepa-
rate monitoring of the control supply voltage is recommended.
Fused motor feeders Fused motor feeders consist of combinations of contactors and overload
relays, often referred to as starter combinations, with upstream short-circuit
protection (e.g. fuses, circuit breakers for starter protection).
The 3RU11 and 3RB10 overload relays are electrically and mechanically com-
patible with the 3RT10 contactors and 3RW30/31 soft starters in the corre-
sponding frame size.
Frame sizes The 3RU11 thermal overload relays and the 3RB10 electronic overload relays
are available in 4 frame sizes:
• Frame size S00: width 45 mm; up to 12 A
• Frame size S0: width 45 mm; up to 25 A
• Frame size S2: width 55 mm; up to 50 A
• Frame size S3: width 70 mm; up to 100 A
The 3RB12 electronic overload relay is available with the following dimen-
sions:
• 3RB12 46: width 70 mm; up to 100 A
• 3RB12 53: width 120 mm; up to 205 A
• 3RB12 57: width 145 mm; up to 500 A
• 3RB12 62: width 230 mm; up to 820 A
3RU11 S00 S0 S2
95
96 95
96
979
8 979
8
S3
3RB10 The construction of the 3RB10 is the same as that of the 3RU11.
3RB12
3RB12 46 3RB12 53
Stand-alone installation
with bar-type transformer
3RB12 57 3RB12 62
Overload relay: compar- The following table compares the thermal and electronic overload relays in
ison terms of their configuration and functionality:
Overview: Performance The following table provides an overview of the assignment of the overload
ranges relays to the contactors together with their ratings:
X = direct attachment
¿ = stand-alone installation (device with bar-type transformer)
Snapped onto a 35 mm rail
Fuses The maximum permissible fuse values for overload relays are dependent on:
• The selected setting range (the smaller the setting range, the lower the
fuse value).
• The maximum permissible fusing of the contactor or other devices in the
circuit (e.g. soft starter or even the motor supply lead).
In the case of fuse values in acc. with coordination type 2, the contactor and
overload relay can be reused after a short circuit.
The type plates on the devices provide information on the permissible fuse
values. In addition, you will find detailed information in part 4 of the low-volt-
age switching technology (NSK) catalog.
Starter protection The operating current of the instantaneous short-circuit release should be
switch 12 times the value of the rated motor current (the current set on the over-
load relay). The corresponding 3RV13 starter circuit breakers can be
selected from part 2 of the low-voltage switching technology (NSK) catalog.
Heavy starting Heavy starting is when the motor requires longer than 10 seconds to reach
the nominal speed. Given such long starting times, the switching devices
and capacities have to be configured appropriately because the thermal load
increases. The permissible AC-3 currents of motor contactors only take into
account 10-second starts. In the case of longer starting times, derating
must be carried out or a larger contactor used. You can determine the corre-
sponding configuration on the basis of the tables of different starting times
and motor currents in part 4 of the low-voltage switching technology (NSK)
catalog.
Setting ranges with The setting ranges can be used up to the maximum value when there are
thermal overload relays temperatures of up to 60 °C inside the cubicle. At temperatures of 60 °C to
70 °C, derating is required. In other words, the maximum permissible set
value must be reduced. The reduction at 70 °C is 13 % and thus so negligi-
ble that due to the overlapping of the different current setting ranges no
gaps occur between the setting ranges. A uniform current range of 0.11 to
87 A can thus also be used at 70 °C.
Overload relays in star- When overload relays are used in star-delta combinations, it must be taken
delta combinations into consideration that only 1 ⁄ 3 of the motor current flows through the
line contactor. An overload relay built onto the line contactor must be set to
this level (i.e. 0.58 of the motor current). A second overload relay must be
built onto the star contactor if your load is to receive optimal protection in
star operation as well. The star current is 1 ⁄ 3 of the rated current of the
motor. The corresponding overload relay must be set to this current. The
3RB12 electronic overload relays with internal ground fault detection are not
suitable for use in star-delta combinations, since transient current spikes
occur at switchover from star to delta operation. These can result in the trig-
gering of ground fault detection.
Thermal, time-delayed overload relays are the usual way of providing motor
protection with overload relays. The technology has been tried and tested
and continuously improved over a period of decades. They are reasonably
priced and provide reliable protection, particularly in the case of normal
starting times (class 10) and motor ratings of up to 45 kW (100 A).
Thermal overload relays work with bimetals and heater coils through which
the motor current flows. Thermal overload relays record true root-mean-
square values and direct currents as a result of their current measuring
method (Joule heat). Compatible heating coils and bimetals are used for the
different setting ranges. Single-phase and direct-current motors can also be
protected against overload by looping the motor line. Thermally time-
delayed overload relays can also be used after frequency converters.
Description The 3RB12 electronic overload relays are suitable when there are high
motor protection requirements on account of the following features:
• Tripping classes 5/10/15/20/25/30 settable
• For motor currents of up to 820 A
• Evaluation of PTC thermistors
• Analog output signal of 4 mA to 20 mA for current detection (insensitive
to harmonics)
• High accuracy of the tripping characteristic with a tolerance of < ± 10 %
• Ground fault detection internally and externally through summation cur-
rent transformer
• Insensitive to external influences such as vibrations, different cable cross-
sections, temperature fluctuations, corrosive environments or aging
The 3RB12 electronic overload relay can be used for everything from easy
starting (CLASS 5) to very heavy starting (CLASS 30). The tripping class can
be set in steps to the relevant motor starting time. In addition, the 3RB12 is
equipped with inputs for PTC thermistors, which make it a fully protected
motor device. Additional functions such as ground fault detection and an
analog output signal are also possible. It is available in 4 sizes from 1.25 to
820 A.
It is triggered in the event of an overload, current imbalance, phase loss, or
a blocked rotor.
Variants The 3RB12 electronic overload relays are available in the following variants:
• Output relay with monostable behavior
• Output relay with bistable behavior
• For the following control supply voltages: 24 VDC
110 VAC to 120 VAC
220 VAC to 240 VAC
Auxiliary contact ele- The 3RB12 electronic overload relays have electrically isolated auxiliary con-
ments tact elements with the following functions (depending on the variant):
• 1 NO contact/1 NC contact for overload tripping through current and/or
thermistor
1 NO contact/1 NC contact for ground fault tripping
• 1 NO contact/1 NC contact for overload tripping through current and/or
thermistor and ground fault; 1 NO contact/1 NC contact for overload
warning
Overload protection The currently flowing motor current is detected in each motor supply line by
current transformers and constantly monitored by a microprocessor.
An overload warning occurs as of:
• 1.15 x Ie in the case of a symmetric load
• 0.85 x Ie in the case of an asymmetric load
The overload warning is indicated by the flashing "Overload" LED on the
overload relay or externally by means of 1 NO contact/1 NC contact.
Thermistor motor pro- The continuous evaluation of a PTC thermistor detector ensures thermistor
tection motor protection.
Additional thermistor motor protection (full motor protection) is imple-
mented by connecting a PTC thermistor detector (PTC sensor circuit in the
motor winding). This is important for stator-critical motors, motors with long
starting and braking, and motors with cooling systems problems or with
high ambient temperatures.
No additional equipment is required for evaluation purposes.
Full motor protection is deactivated on delivery by means of a wire jumper.
The monitoring of the thermistor is secure against a wire break. In other
words, tripping occurs in the event of a wire break.
4.2.3 Operation
Use with external cur- If external current transformers are to be used to operate the 3RB12, the
rent transformers following things should be taken into consideration. The 3RB12 with the cur-
rent setting range from 1.25 to 6.3 A must be selected.
The secondary current of the 1 A or 5 A current transformer becomes the
primary current of the 3RB12. In the case of 5 A current transformers, the
3RB12 can be set from 1.25 to 5 A (i.e. from 1/4 of to 1 times the trans-
former's rated current). In the case of 1 A current transformers, a signal
> 1.25 A must be generated by looping the line. If the line is looped five
times, a 5 A signal is generated for the 3RB12.
3RB10
A special coating on the PCB and the electronic components ensures reli-
able operation even in corrosive and tropical environmental conditions.
Auxiliary contact ele- The 3RU11 and 3RB10 overload relays are equipped with a normally closed
ments contact for switching off the contactor and a normally open contact for the
tripped signal.
The switching contacts have a high switching capacity so that they can
switch contactor coils directly. The overload relays are therefore suitable for
use with a PLC (17 V, 5 mA).
Frame sizes S0 - S3
The contactors of these frame sizes are equipped with 4 coil connections. It
is therefore not necessary to pass through the auxiliary switch and coil ter-
minals (A2) of the contactor.
3RB10
The 3RB10 electronic overload relays are available in 2 tripping classes:
Tripping class 10 for normal starting
Tripping class 20 for heavy starting
3RB12
The 3RB12 electronic overload relays can be set to different tripping classes
(5/10/15/20/25/30) on the device.
Phase loss sensitivity The 3RU11/3RB10/3RB12 overload relays are sensitive to phase imbalance.
3RB10 The 3RB10 electronic overload relays are developed for use in sinusoidal 50/
60 Hz voltage networks. No additional supply voltage is required for opera-
tion. The current transformers are integrated in the devices for the purpose
of current detection. An ASIC checks the current values of each phase and
causes tripping in the event of an overload or phase loss.
4
TEST
8 M A 7
2
3 1
STOP RESET
9
6 95 96 97 98 A2
9
5
2T2 4T2 6T3 14/22
Auxiliary contacts The following table shows the behavior of the auxiliary contacts when the
TEST/STOP and RESET buttons are pressed:
NC 95/96
NO 97/98
Setting the rated cur- The following figure shows how the rated current is set, using the example
rent of the 3RU11, frame size S00.
A
Max. + 60 °C
Max. + 70 °C
Ie
Important
When the sealing cover (transparent sliding window) is closed (3RU11) or
mounted (3RB10), it is not possible to use the blue reset button for a
switchover between M (manual reset) and A (automatic reset).
1
2
Figure 4-6: Sealing the adjustment scale (frame size S00)
The following figure shows how to switch between manual and automatic
for the 3RU11 and 3R10 using the example of the 3RU11, frame size S00:
Manual-automatic
MANUAL
AUTO
Figure 4-7: Manual/automatic switchover
Resetting The 3RU11 thermal overload relay can also be reset manually after the
bimetals have cooled down (after approx. 3 to 5 minutes), or it can reset
itself automatically after this time when the AUTO position is set.
The 3RB10 electronic overload relay can be reset at any time by pressing the
RESET button. The recovery time for the automatic reset is 4 minutes.
3RU11
Tripping characteristics The time-current characteristics show the dependency of the tripping time
from a cold state on the multiple of the set current Ie.
When the relay is at operating temperature, preloaded with 1x Ie, the trip-
ping times are reduced to around 25 %. In the case of a single-pole load, the
tripping characteristics lie between the characteristics. In normal operation,
all three bimetal strips of the overload relay must be heated.
The 3RU overload relays are suitable for protecting motors with phase con-
trol.
To protect single-phase or direct current loads, all three main conducting
paths must be connected in series. The minimum tripping current in the
case of a three-pole symmetric load lies between 105 % and 120 % of the
set current.
Tripping time
10 000
100 5000
min
60
s
40
2000
1000
10 500
5
200
2 100
three-pole
1 load
50
20
two-pole
load
10
1
0,6 0,8 1 2 3 4 6 8 10 15 20 30 40 A 60 80 x I n
Current
3RB10
Tripping characteristic The time-current characteristics show the behavior at starting, with a three-
pole load
¿ from a cold state
À from a warm state
Á in the event of phase loss or current imbalance (the phase loss protection
function triggers the overload relay after 3 seconds)
10 NSB00293 10 NSB00294
6 6
Tripping time min
4 4
2 2
1 1 1
50 1 50
40 40
20 20 2
2
10 10
8 3 8 3
s
6 6
4 4
2 2
1 1
0,6 1 2 4 6 10x I e 0,6 1 2 4 6 10x I e
Tripping current (mean values) Tripping current (mean values)
CLASS 10 CLASS 20
Figure 4-9: Time-current characteristics for class 10 and class 20, chart for the 3RB10
SIEMENS 70 80 90 3RB12
2 Ready 60
100
50
3 Gnd Fault
40 A
10
4 Overload 30
25
20 25
15 30
TEST/
5 RESET 10 11
5 CLASS
NC NC
6 12
95 96 97 98 05 06 07 08
NSB00297
Overload In the event of an overload > 110 % of the current Ie set using the rotary
switch on the front of the device, of current imbalance of 40 % Ie, or of
phase loss, tripping occurs through the switchover of two auxiliary contact
elements (1 NO contact: 97/98 / 1 NC contact: 95/96) after the tripping time
set by means of the six-step rotary switch (CLASS 5/10/15/20/25/30).
After overload tripping, the overload relay can be reset either by pressing
the test/reset button on the device or by remote or automatic reset after the
recovery time of 5 minutes elapses.
Thermistor detector A tripping operation as a result of the thermistor detector responding takes
place via the same auxiliary contact elements as for overload tripping (1 NO
contact: 97/98 / 1 NC contact: 95/96), except that it is instantaneous.
The overload relay cannot be reset until the temperature in the motor wind-
ing 5 K has sunk to under the operating temperature of the thermistor.
Ground fault In the event of a ground fault, the device trips instantaneously; depending
on the device variant, this may occur via a separate output (1 NO contact/1
NC contact).
Important
In the case of ground fault tripping, an automatic reset is not possible.
Test The device functions of current detection, thermistor input, and ground fault
input and the tripping functions of the auxiliary contact elements can be
tested by pressing the test/reset button.
The device functions can also be tested during operation. The LEDs indicate
the status.
Internal failure Self-monitoring causes the device to trip in the event of an internal fault. In
this case, the overload relay cannot be reset.
Failure of the control In the event of the failure of the control supply voltage for any length of time
supply voltage (> 0.2 seconds), the output relays respond in either a monostable or
bistable manner, depending on the variant involved.
The following table shows the behavior of the output relays in the event of
the failure of the control supply voltage:
Tripping characteristics The time-current characteristic for three-pole symmetric loading shows the
dependency of the tripping time from a cold state on the multiple of the set
current.
When the overload relay is preloaded with 100 % of the set current, the trip-
ping times are reduced.
In the case of two-pole loading (loss of a phase) or current imbalance
> 40 % of the set current, the corresponding characteristic applies.
120 120
100 100
50 50
20 20
min
min
10 10
CLASS 30 CLASS 30
5 25 5
25
Tripping time
Tripping time
20 20
2 2
1 1
50 50
20 20
15 15
10 10 10 10
s
s
5 CLASS 5 5 CLASS 5
2 2
Field of application The electronic overload relay with analog output is used for measuring
instruments and analog modules with 4 to 20 mA input.
A
A1 A2 T1 T2/C1 C2 + - Y1 Y2
95 96 97 98 05 06 07 08
B
Figure 4-12: Electronic overload relay with analog output, front view
Analog output 4 mA to 20 mA
1 % x Ie = 0.128 mA
0 No connection,
wire break!
4.000 Device in operation
4.128
5.280 0
7.200 1
10.40 10
15.52 25
16.80 50
18.08 90
20.00 100
110
125
4.4 Accessories
4.4.1 Electromechanical remote reset
Installation/removal The following figure shows how the electrical remote reset is installed and
removed, using the example of the 3RU11 in frame size S00.
2
Figure 4-13: Electrical remote reset, installation/removal
Operating range The operating range of the coil is: 0.85 to 1.1 x US
Power consumption The power consumption of the electromagnetic remote reset is:
80 VA AC, 70 W DC
Manual reset A manual reset is possible by means of the blue repeat button on the
remote reset module.
Connection cross-sec- The values for the screw-type terminals of terminals E1 and E2 correspond
tions to the cross-sections of the auxiliary connecting leads of the 3RU11/3RB10
overload relays.
Resetting plunger
Installation The following graphics show how to install and remove the resetting plunger
or the wire release for the 3RU11, frame size S00.
Example 3RU11, frame size S00:
1
3SB1
Cubicle door
Removal
1
2
Figure 4-15: Mechanical remote reset: resetting plunger, removal
Wire release
2
5
Ø 6.5 mm 6
1 4
3
≤ 8 mm 4
Removal
1
2
Figure 4-17: Mechanical remote reset: wire release, removal
Sealable cover A sealable cover is available as an accessory for the 3RB10 electronic over-
load relay.
In the case of the 3RU11 thermal overload relay, the cover is integrated in
the device.
4.5.1 Mounting
3RU11/3RB10 The 3RU11 and 3RB10 overload relays can be attached directly to the 3RT
contactors and 3RW30/31 soft starters in the corresponding frame size.
In stand-alone installation they are suitable for being snapped onto a 35 mm
rail in acc. with DIN EN 50 022 or for screw-on mounting.
The overload relay in the frame size S3 is suitable for 35 mm and 75 mm
rails.
3RB12 70 mm width
The 3RB12 electronic overload relays are either snapped onto a
35 mm rail in acc. with DIN EN 50 022 or screwed onto a mounting plate by
means of push-in lugs, which are available as accessories.
The devices with current setting ranges < 100 A are designed for stand-
alone installation on account of the bar-type system of the primary current
lines.
Mounting onto contac- The following illustration shows how overload relays (in this case the 3RU11)
tors/soft starters in frame size S00 are attached to the 3RT contactor and the 3RW30/31 soft
starter:
3
1
1
2
2
Stand-alone installa- The following illustrations show how the holder for stand-alone installation
tion is mounted.
Frame size S00/S0:
3RU1916-3AA01
3RU1926-3AA01 3
1
3
2
Removal
Figure 4-19: Stand-alone holder, example 3RU11 (frame size S00/S0)
2
2
Figure 4-20: Stand-alone holder, example 3RU11 (frame size S2/S3)
Snap-on mounting The 3RU11 and 3RB10 overload relays can either be mounted onto the con-
tactor or snapped onto a 35 mm rail by means of the holder for stand-alone
installation.
The frame size S3 can be snapped onto a 35 mm rail or a 75 mm rail.
S00/S0 S2/S3
RU-00612
RU-00200
1
4
3
2 3
Figure 4-21: Snap-on mounting and removal with the 3RT contactor
Minimum clearance Maintain a minimum clearance from grounded parts at the side of
> 6.5 mm.
135° 135°
135° 135°
I e x 1.1
I e x 1.1
0°
22.5° 22.5° 45° 0° 45°
I e x 1.1 Ie x 1.1
90° 90°
NSB01364
NSB01363
Figure 4-22: Permissible installation positions for the 3RU11
3RB10/3RB12
Any installation position is possible for the 3RB10 and 3RB12.
4.5.2 Connection
3RU11 The 3RU11 overload relays are equipped with the following terminal system:
• S00 to S3: Screw-type terminal for the main and auxiliary connecting
leads
• S00: Cage Clamp terminal for the main and auxiliary connecting leads
(only stand-alone installation possible)
• S0 to S3: Screw-type terminal for main contacts and Cage Clamp terminal
for auxiliary connecting leads (contactor mounting and stand-alone instal-
lation possible)
3RB10/3RB12 The 3RB10 and 3RB12 electronic overload relays have screw-type terminals.
The 3RB1246 electronic overload relays are equipped with a bar-type trans-
former.
Bar-type system In the case of the 3RB1246 electronic overload relays with current setting
ranges < 100 A (70 mm width), the main lines are connected in a bar-type
system. The main lines are connected through the current transformer inte-
grated in the housing at rated currents for the motor of 1.25 A to 100 A.
The advantages are:
• No additional installation costs
• No power loss at the transfer resistors of the clamping units that would
otherwise be necessary
Looping through At motor rated currents IN < 1.25 A, the motor supply leads can be fed
through the loop-through openings several times (n times) in each phase.
The set current Ie of the device is calculated as follows:
Ie = 3 x IN
Example:
IN = 0.5 A
n=3
Ie = 3 x 0.5 A = 1.5 A
n = 5 is recommended as a good upper limit in practice.
The following graphics illustrate the loop-through system:
L1 L2 L3
3
1
2
Figure 4-23: Loop-through system, 3RB1246
Screw-type terminal The screws are captive, and the screwdriver guides allow the use of power
screwdrivers.
Cage Clamp terminal The following illustration shows a Cage Clamp terminal with the 3RU11,
using the example of frame size S2:
Note
The 8WA280 screwdriver is recommended for opening the Cage Clamp ter-
minal.
Caution
When clamping and unclamping, the screwdriver must be inserted in the
rectangular opening until the stop. You must not make any levering or tur-
ning movements, because these might break the cage clamp.
Connection cross-sec- You can obtain the permissible connection cross-sections for the main and
tions auxiliary connections of the overload relays from Section 4.7, "Technical
specifications".
3RU11
NSK-7601
NSK-7600
1 3 5 1 3 5
2 4 6 2 4 6
Single-pole Two-pole
Figure 4-25: 3RU11 circuit diagrams
RESET
RESET
STOP
STOP
TEST
TEST
NSK-7515b
NSK-7599
2T1 4T2 6T3 96 98 A2 14/22 2T1 4T2 6T3 96 98
F1 F3
1 3 5 A2
K1
2 4 6 A1
STOP
1 3 5 95 97 S1
F2 S2
0.2 to 4 sec.
2 4 6 96 98
Test Reset
U V W Remote reset
M1 M E1 E2
3~
In the case of single-pole loads, the 3 main conducting paths must be con-
nected in series.
Warning
In the case of an automatic reset and maintained-contact operation, the
motor restarts automatically.
L1 L2 L3 N L1 N
F1 F3
1 3 5 A2 13
K1
2 4 6 A1 14
STOP
1 3 5 95 97 S1
F2 S2
0.2 to 4 sec.
2 4 6 96 98
Test Reset
A2 14/22
U V W Remote reset
M1 M E1 E2
3~
L1 L2 L3 L1 L2 L3
3RB12 3RB12
T1 T2 T3 T1 T2 T3
1~ 1~
M M
Important
The electronic overload relays with integrated ground fault detection
(3RB12..-....2./3RB12..-....3.) are not suitable for use with single-phase
motors.
4.5
4,5 52
NSB00339a 1)
185
38
NSK-8631
43
148
46
47
3)
118
87
5
75
61
41
1)
2)
24
5
5
10
5 35 33 30
15,5 5 33 45 5 68 41
45 49
68
max. 161 max. 8
3SB1
Figure 4-30: 3RU11 16-..B0, (frame size S00) 3RU11 16, 3RB10 16, (frame size S00)
with accessories with terminal bracket for stand-alone installation with accessories
4,5
4.5 62 5 51
NSK-9303a NSB00341a
44
50
50
54
105
97
85
95
4
4.5
4,5
5.5
5,5
5 35 44 5 40
45 5 86 5 5.5
5,5 44
55 108 5
Figure 4-31: 3RU11 26-.B., 3RB10 26, (frame size S0) 3RU11 36-..B., 3RB10 36, (frame size S2)
with terminal bracket for stand-alone installation with terminal bracket for stand-alone installation
79
5 7
NSK-9307b
57
62
110
5)
5
5 60 5 59
70 130 5
1) Mechanical reset
2) Wire release (400 mm or 600 mm long, mounting on front or side on bracket)
3) Bracket for reset
4) Module for remote reset
5) Attachment to rail (35 mm, 15 mm depth to DIN EN 50 022 or 75 mm to DIN EN 50 023)
The clearance from grounded parts at the side must be at least 6 mm.
g
10
h f p
Ø4.5
4,5
14
12,5
12.5
100
100
85
o
d
b
i
7.2
7,2
50 5 127.5
127,5
70
f a
NSK-7049b
k m j
e l
a n c
b
e
NSK-7048d
c
d
185 4.5
4,5
148
28 4,5
4.5 17,5
17.5 46 1)
42
8
3)
92
5
75
92
75
26
NSB00344a
12
1) 5
NSK-8249
5 35 7.5
7,5 30
2) 45 5 68 41
5
15.5
15,5 7,5
7.5
5 35 5 68
45
4,5
4.5 62 5 51
44
50
50
54
SIEMENS
SIEMENS
TEST
0 1
TEST
H A 0 1
85
6
97
95
105
H A
4
STOP RESET
STO P RESET
4,5
NSK-8265
4.5
NSB00346a
5,5
5.5
5 35 44
45 5 86 5 5,5
5.5 44 40
55 5 108 5
Figure 4-35: 3RU11 26-..D0 (frame size S0) 3RU11 36-..D0 (frame size S2)
5 79
NSK-8267
57
62
SIEMENS
TEST
0 1
120
H A
110
STOP RESET
5)
5
5 60 7
70 59
5 130 5
1) Mechanical reset
2) Wire release (400 mm or 600 mm long, mounted on front or side on bracket)
3) Bracket
4) Remote reset
The clearance from grounded parts at the side must be at least 6 mm.
5) Attached to rail (35 mm, 15 mm depth to DIN EN 50 022 or 75 mm to DIN EN 50 023).
1) Remote reset in conjunction with suitable accessories 4) For screw-on and snap-on attachment to 35 mm rail
2) Terminal compartment: IP 00 degree Frame size S3 also for 75 mm rail
of protection
3) Only stand-alone installation is possible for the 3RU11 16
overload relay with the Cage Clamp terminal system.
1) For the connection cross-sections for the Cage Clamp terminal system, see "Connecting the auxiliary circuit".
2) The box terminal can be removed. After the box terminal has been removed, busbar and cable-lug connections are possible.
Short-circuit protection with fuses for motor feeders with short-circuit currents of up to 70 kA at 50/60 Hz 690 VAC
Permissible short-circuit protection for motor starters consisting of an overload relay and a contactor of the coordination type "2"
Frame size S00 UL Circuit breaker for
fuse starter protection at
Adjustment range 3 kW 3RT10 15 4 kW 3RT10 16 5.5 kW 3RT10 17
Ie max = 7 A Ie max = 9 A Ie max = 12 A RK5 Iq = 50 kA / 400 VAC
(at 50 Hz 400 VAC) (at 50 Hz 400 VAC) (at 50 Hz 400 VAC)
A gL/gG aM BS88T gL/gG aM BS88T gL/gG aM BS88T A
0.11 to 0.16 0.5 – – 0.5 – – 0.5 – – 1 –
0.14 to 0.2 1 – – 1 – – 1 – – 1 3RV1321-0BC10
0.18 to 0.25 1 – – 1 – – 1 – – 1 3RV1321-0CC10
0.22 to 0.32 1.6 – 2 1.6 – 2 1.6 – 2 1 3RV1321-0DC10
0.28 to 0.4 2 – 2 2 – 2 2 – 2 1.6 3RV1321-0EC10
0.35 to 0.5 2 – 2 2 – 2 2 – 2 2 3RV1321-0FC10
0.45 to 0.63 2 – 4 2 – 4 2 – 4 2.5 3RV1321-0GC10
0.55 to 0.8 4 – 4 4 – 4 4 – 4 3 3RV1321-0HC10
0.7 to 1 4 – 6 4 – 6 4 – 6 4 3RV1321-0JC10
0.9 to 1.25 4 – 6 4 – 6 4 – 6 5 3RV1321-0KC10
1.1 to 1.6 6 – 10 6 – 10 6 – 10 6 3RV1321-1AC10
1.4 to 2 6 – 10 6 – 10 6 – 10 8 3RV1321-1BC10
1.8 to 2.5 10 – 10 10 – 10 10 – 10 10 –
2.2 to 3.2 10 – 16 10 – 16 10 – 16 12 –
2.8 to 4 16 – 16 16 – 16 16 – 16 16 –
3.5 to 5 20 6 20 20 6 20 20 6 20 20 –
4.5 to 6.3 20 6 20 20 6 20 20 6 20 25 –
5.5 to 8 20 10 20 20 10 20 20 10 20 30 –
7 to 10 20 16 20 20 16 20 40 –
9 to 12 20 16 25 45 –
Short-circuit protection with fuses for motor feeders with short-circuit currents of up to 70 kA at 50/60 Hz 690 VAC
1) Remote reset in conjunction with suitable accessories 4) For screw-on and snap-on attachment to 35 mm rail
2) Terminal compartment: IP 00 degree Frame size S3 also for 75 mm rail
of protection
3) For the setting ranges 0.1 to 0.4 A, 0.4 to 1.6 A, and 1.5 to 6 A,
it is 3 V/m.
Short-circuit protection with fuses for motor feeders with short-circuit currents of up to 50 kA at 690 VAC
690 V 415 V 600 V
Overload relay Contactor CLASS Fuse links1)
Adjustment range 10 20 NH Type 3NA NH British
Rated operating current Ie DIAZED Type 5SB Type 3ND Standard UL-listed
fuses
AC-3 in A at NEOZED Type 5SE Fuses
Performance class gL/gG aM BS88, CLASS
Coordination type2) Type T
R K5
Type Type 400 500 690 400 500 690 "1" "2" "2" "1" "2"
V V V V V V
Frame size S00
0.1 A to 0.4 A 3RT10 153) 0.4 0.4 0.4 0.4 0.4 0.4 25 2 25 2 1.6
3RB10 16
0.4 A to 1.6 A 3RT10 153) 1.6 1.6 1.6 1.6 1.6 1.6 25 6 35 6 6
3RB10 16
1.5 A to 6 A 3RT10 153) 6 5 4 6 5 4 35 20 35 20 25
3RB10 16 3RT10 173) 6 6 6 6 6 6 35 20 35 20
3 A to 12 A 3RT10 173) 12 9 6.3 10 6 6.3 35 20 35 25 45
3RB10 16
Frame size S0
0.1 A to 0.4 A 3RT10 243) 0.4 0.4 0.4 0.4 0.4 0.4 63 2 63 2 1.6
0.4 A to 1.6 A 3RT10 243) 1.6 1.6 1.6 1.6 1.6 1.6 63 6 63 6 6
1.5 A to 6 A 3RT10 243) 6 6 6 6 6 6 63 25 20 63 25 25
3 A to 12 A 3RT10 243) 12 12 12 12 12 12 63 25 20 63 25 45
3RB10 26
6 A to 25 A 3RT10 243) 12 12 12 12 12 12 63 25 20 63 25 70
3RB10 26 3RT10 253) 17 17 13 16 16 13 63 25 20 63 25 70
3RT10 263) 25 18 13 16 16 13 100 35 20 63 25 100
Frame size S2
6 A to 25 A 3RT10 343) 25 25 25 22 22 22 125 63 50 125 63 100
3RB10 36 3RT10 353) 25 25 25 25 25 25 125 63 50 125 63 100
13 A to 50 A 3RT10 343) 32 32 31 22 22 22 125 63 50 125 63 125
3RB10 36 3RT10 353) 40 40 40 29 29 29 125 63 50 125 80 150
3RT10 363) 50 50 40 32 32 33 160 80 50 125 80 200
Frame size S3
13 A to 50 A 3RT10 443) 50 50 50 49 49 49 250 100 63 250 100 200
3RB10 46 3RT10 453) 50 50 50 50 50 50 250 100 80 250 100 200
25 A to 100 A 3RT10 443) 65 65 57 49 49 49 250 125 63 250 125 250
3RB10 46 3RT10 453) 80 80 80 53 53 53 250 160 80 250 160 350
3RT10 463) 95 95 95 59 59 59 250 160 100 250 160 350
1) Please note the operating voltage.
2) Assignment and short-circuit facilities in acc. with IEC 60 947-4-1/DIN VDE 660 Part 102
Coordination type "1": Contactors or starters must not endanger people or the system in the event of a short circuit. They do not have to be suitable for
further operation without repair and part replacement.
Coordination type "2": Contactors or starters must not endanger people or the system in the event of a short circuit and must be suitable for further use.
There is a danger of contact welding.
3) Mounting on the contactor is possible after removal of the box terminal block.
• 690V A 2)
• 230 V A 3
• 400 V A 1.5
• 600 V A 2)
2
• 690 V A )
NC contact, NO contact with direct cur- Rated operational current Ie at Ue:
rent DC-13
• 24 V A 2
• 60 V A 0.55
• 110 V A 0.25
• 125 V A 0.25
• 220 V A 0.14
Conventional free air thermal current Ith A 6
Contact reliability 2)
(suitable for PLC; 17 V, 5 mA)
Short-circuit protection
With fuse Performance class gL/gG A 6
flink A 10
With miniature circuit breaker (C characteristic) A 1.63)
Safe isolation between auxiliary conducting paths V 300
in acc. with DIN VDE 0106 Part 101
1) The assignment of the auxiliary contact elements depends on the order number suffix
2) On request
3) Up to IK ≤ 1000 A
1) Please note the operating voltage 2) Assignment and short-circuit facilities in acc. with IEC 60947-4-1/DIN VDE 660 Part 102
3) Please ensure that the safety clearance between the max. 3 AC ope- Coordination type "1": The contactor or starter must not endanger people or the system in the event of a short circuit. They do not have
rating current and the fuse rated current is maintained. to be suitable for further operation without repair and part replacement.
4) Mounting onto contactor possible Coordination type "2": The contactor or starter must not endanger people or the system in the event of a short circuit and must be sui-
table for further operation. There is a danger of contact welding.
4-51
3RU11, 3RB10, and 3RB12 overload relays
5
3RA1 fuseless load feeders
Section Subject Page
5.1 Specifications/regulations/approvals
Coordination types
The fuseless load feeders are manufactured and tested in acc. with IEC
60947 Part 1 and Part 2.
An important selection criterion for the fuseless load feeders are the coordi-
nation types.
IEC 60947-4-1/DIN VDE 0660 Part 102 draws a distinction between two
coordination types, known as coordination type 1 and coordination type 2.
They describe what happens at a short circuit and the device status after a
short circuit. In both coordination types, the short circuit to be dealt with is
reliably disconnected. There must be no damage to systems or injury to per-
sons. The differences lie only in the degree to which the device is damaged
after the short circuit.
Coordination type 1 The fuseless load feeder can be inoperable after each short-circuit discon-
nection. Damage to the contactor and the circuit breaker is permissible.
Coordination type 2 After a short-circuit disconnection, there must not be any damage to the
overload release or any other part. The 3RA1 fuseless load feeder can be put
into operation again without the need for replacement. Only welding of the
contactor contacts is permissible if they can be separated easily without any
significant deformation.
Approvals/test reports All the approvals and test certificates of the individual devices used in the
feeders are valid.
Device variants The fuseless load feeders can be set up in 4 frame sizes:
• Frame size S00: width 45 mm; for three-phase induction motors up to
0.75 kW / 400 V, coordination type "2" and 5.5 kW / 400 V, coordination
type "1"
• Frame size S0: width 45 mm; for three-phase induction motors up to
7.5 kW / 400 V, coordination type "2" and 11 kW / 400 V, coordination type
"1"
• Frame size S2: width 55 mm; for three-phase induction motors up to
22 kW / 400 V, coordination type "2" and coordination type "1"
• Frame size S3: width 70 mm; for three-phase induction motors up to
45 kW / 400 V, coordination type "2" and coordination type "1"
Because SIRIUS is a modular system, the standard devices fit together opti-
mally both mechanically and electrically. The fuseless load feeders can
therefore be assembled quickly and easily in all four frame sizes. To this end,
the circuit breaker and the contactor are connected to the corresponding kit.
Kits There are kits for reversing feeders for mounting on:
• Rail, frame sizes S0, S2, S3: mounting kit for reversing operation
frame size S00: wiring kit for reversing operation
• Busbars, frame sizes S00, S0, S2: mounting kit for reversing operation
The following illustration shows how to assemble the fuseless load feeder
of frame size S00 for reversing operation and rail mounting:
7 6
4
5
Adapter
(3RA1911-1A)
1
2
5.4 Accessories
5.4.1 Accessories for the individual devices
The accessories for the individual devices can also be used in the load
feeder.
You will find information on the accessories of the contactors in Chapter 3,
"Contactors" (Section 3.4, "Accessories").
5.4.2 Accessories specifically for the SIRIUS 3RA fuseless load feeder
The following accessories facilitate the setup and wiring of the fuseless load
feeder:
Accessory Description
Assembly The following illustration and the table below it show how to assemble the
fuseless load feeder:
• Rail mounting
• Frame size S00
• Reversing operation
7 6
4
5
3RA1911-1A
1
2
Step Procedure
1 Hook the back of the right contactor of the contactor combi-
nation onto the link module
2 With a tilting movement, insert the connecting pins of the link
module into the upper terminal openings of the contactor
3 Tighten the upper terminal screws of the contactor
4 Hook the link module onto the back of the circuit breaker
5 With a tilting movement, insert the connecting pins of the link
module into the lower terminal openings of the circuit breaker
6 Tighten the lower terminal screws of the circuit breaker
7 Snap the circuit breaker and thus the feeder onto the rail
Table 5-2: Self-assembly of the reversing starter for rail (frame size S00)
The following illustrations show how to assemble the fuseless load feeder:
• Rail mounting
• Frame sizes S00 to S3
• Direct starters
S00 S0
7 7
4 6 4 6
5
5
1 3RA1911-1A 1 3RA1921-1.
2
2
3
3
S2 S3 3RA1942-1A
3RA1932-1A
1 1
3RA1931-1. 1
1
2 2 3RA1941-1.
4
4 3
3 5
5
4 4
Figure 5-4: Self-assembly, rail, direct starter (frame sizes S00 to S3)
The following illustrations show how to assemble the fuseless load feeder:
• Rail mounting
• Frame sizes S00 with Cage Clamp terminal system
Direct starter
6
4
3RA1911-2E 3
5
5b
5a
5c
Figure 5-5: Self-assembly, rail, direct starter (frame size S00, Cage Clamp)
The following illustrations show how to assemble the fuseless load feeder:
• Rail adapter
• Reversing operation
• Frame size S0
3RA1924-2B 3
2
1
Kit
3RA1923-1B
4 3
4
6 (4x)
7
12
8
7 3RA1921-1.
10 11
The following illustrations show how to assemble the fuseless load feeder:
• Rail adapter
• Reversing operation
• Frame size S2 (assembly of frame size S3 is analogous)
3 4
2
1
Kits 3RA1924-2B
S2: 3RA1933-1B
S3: 3RA1943-1B
4
5 S2: 4X
S3: 6X
7
8 9
6
8
11
5 9
10 3RA1931-1.
3RA1941-1.
12
14
13
14
14 14
Figure 5-7: Self-assembly, rail, reversing operation (frame sizes S2 and S3)
There are kits available for reversing operation for frame sizes S00 to S2.
The fuseless load feeders of frame size S3 are not suitable for busbar
mounting.
Direct starters of frame The following illustrations show how to assemble the fuseless load feeder:
sizes S00 to S2 • Busbar adapter
• Direct starters
• Frame sizes S00 to S2
S00 S0
8US1
8US1
5 5
1
1
110
125
3RA1911-1A
3RA1921-1.
3 2 3
3
3 2
4
4
S2
8US1
2
3RA1931-1.
4
3
4 5
Figure 5-8: Self-assembly, busbars, direct starters (frame sizes S00 and S2)
The following illustrations show how to assemble the fuseless load feeder:
• Busbar adapter
• Direct starters
• Frame sizes S00 and S0 with Cage Clamp terminal system
6
1 8
5
4
7
3 3
7b
7a
7c
3 4 5
3RA1911-2E 1
1b
1a
1c
Figure 5-9: Self-assembly, busbars, direct starters (frame size S00/S0, Cage Clamp)
Reversing operation of The following illustrations show how to assemble the fuseless load feeder:
frame sizes S00 to S2 • Busbar adapter
• Reversing operation
• Frame sizes S00 to S2
S00
5
Kit 3RA1913-1.
3RA1911-1A
3 2
3
S0
55
5
Kit 3RA1923-1.
1
3RA1921-1.
3
6
3 2
3 4
3RA1924-2B
Figure 5-10: Self-assembly, busbars, reversing operation (frame sizes S00 and S0)
S2
Kit 3RA1933-1.
2
3RA1931-1.
4
4
3
5
4
3RA1904-2B
Snap-on attachment
The fuseless load feeders can be snapped onto a 35 mm rail in acc. with
DIN EN 50 022.
Rail mounting without The fuseless direct feeders of frame sizes S00 and S0 and reversing feeders
adapter S00 can be snapped onto the rail without an adapter with the circuit breaker.
No tools are required for either mounting or removal.
A rail adapter is available as an accessory for frame sizes S00/S0. The
reversing feeders of frame sizes S2/S3 are mounted with a rail adapter.
Rail mounting with To mount frame sizes S2 and S3 and reversing feeders S0 on a rail, adapters
adapter must be used for stability reasons. These are available as accessories. To
remove them, the rail adapter is unlocked with a screwdriver. You will find
information on this in Section 2.5.1 on how to mount circuit breakers.
All feeders can be mounted with a rail adapter.
Screw-on attachment
4 6
1
2
Figure 5-12: Screw-on attachment, fuseless load feeder (frame size S00)
Important
In the case of screw-on attachment without a rail adapter, the feeder must
not be screwed onto a conductive surface. Insulation is necessary so that, in
the event of a short circuit of the circuit breaker, there is no short circuit to
the base plate.
Busbar mounting
10 mm
8US1.51-5DM07
8US1.61-5FP08
2
1
2
The fuseless load feeders are available with the SIGUT terminal system.
Conductor cross-sections
The following table gives the permissible conductor cross-sections for fuse-
less load feeders. The specifications apply to main and auxiliary connec-
tions.
S00 S0
A1/A2; NO/NC A1/A2; NO/NC L1 L2 L3
L1 L2 L3 T1 T2 T3
T1 T2 T3
0.8 to 1.2 Nm 0.8 to 1.2 Nm 2 to 2.5 Nm
∅ 5 ... 6 mm / PZ2 7 to 10.3 lb.in 7 to 10.3 lb.in 18 to 22 lb.in
10 2 x (0.5 to 1.5 mm²) 2 x (0.5 to 1.5 mm²) 2 x (1 to 2.5 mm²)
2 x (0.75 to 2.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (2.5 to 6 mm²)
10 2 x (1 to 2.5 mm²)
2 x (0.5 to 2.5 mm²) 2 x (0.5 to 2.5 mm²) 2 x (2.5 to 6 mm²)
S2
A1/A2; NO/NC L1 L2 L3
T1 T2 T3
0.8 to 1.2 Nm 3 to 4.5 Nm
∅ 5 ... 6 mm / PZ2 7 to 10.3 lb.in ∅ 5 ... 6 mm / PZ2 27 to 40 lb.in
10 2 x (0.5 to 1.5 mm²) 13
2 x (0.75 to 16 mm²)
2 x (0.75 to 2.5 mm²)
10 13 2 x (0.75 to 16 mm²)
2 x (0.5 to 2.5 mm²)
1 x (0.75 to 25 mm²)
13 2 x (0.75 to 25 mm²)
---- ----
1 x (0.75 to 35 mm²)
2 x (18 to 3)
AWG 2 x (18 to 14) AWG
1 x (18 to 2)
S3
A1/A2; NO/NC L1, L2, L3
T1,T2,T3
Direct starters
S00 S0 to S3
A1 1L1 3L2 5L3 13 NO/21 NC A1 1L1 3L2 5L3
I»I»I» I»I»I»
Figure 5-14: Circuit diagrams, direct starters (frame sizes S00 to S3)
Reversing starters
S00 S0 to S3
1L1 3L2 5L3 1L1 3L2 5L3
I» I» I» I» I» I»
2 4 6 2 4 6
21 NC NC
21 NC NC
A1 1 3 5 A1 1 3 5 A1 1 3 5 122 A1 1 3 5 111
K1 K2 K1 K2
A2 2 4 6 2 4 6 A2 2 4 6 2 4 6
121 110
70
30 10 67.5
67,5 10
6 14 5 27.5
27,5
1)
8
20
5
8
45
SIEMENS
0 I
0 I
163
163
159
SIEMENS SIEMENS
NSK-8165
SIEMENS
NSK-8164
59 40
7.5 6.5
6,5 90
59 7,5
6.5
6,5 45 51
Figure 5-16: 3RA11 10-..A.. for direct-on-line starting 3RA12 10-..A.. for reversing operation
1) Space above the arc chute
Clearance to grounded parts at the side at least 6 mm
1)
13 21
48
SIEMENS SIEMENS
60
0 I 0 I
203
159
203
159
60
59 27 82 59
6.5 6.5
6,5 90
6,5 45 98
101
Figure 5-17: 3RA11 10-..C.., 3RA11 10-..D.. for direct-on-line starting 3RA12 10-..C.., 3RA12 10-..D.. for reversing operation
1) Space above the arc chute
Clearance to grounded parts at the side at least 6 mm
106
14 91 8 14 7 5 49
8 14 10 5 33
1)
5
22
30
1)
5
39
45
SIEMENS SIEMENS
2) 2)
104
185
178
183
199
125
SIEMENS SIEMENS SIEMENS
5
NSK-8168
NSK-8169
6
7.5 3)
6 5 28 7,5
45 39 8 10 6 55
14
61
55 77
86 7.5
DC 96 7,5 100 102
DC 112
Figure 5-18: 3RA11 20-..A.. for direct-on-line starting 3RA12 20-..B.. for reversing operation
1) Space above the arc chute
2) Lockable in zero position with a shackle diameter of 5 mm
3) Attached using two 35 mm rails with a depth of 7.5 mm in acc. with EN 50 022 or one 75 mm rail in acc. with EN 50 023.
Clearance to grounded parts at the side at least 6 mm
1)
26
13
2)
2)
48
SIEMENS
SIEMENS
b)
209
211
183
185
SIEMENS
SIEMENS SIEMENS
NSK 8170b
NSK 8171b
28 27 70
8 10 6
8 6 92
14 117 14
45 100
121
DC 127
Figure 5-19: 3RA11 20-..C.., 3RA11 20-..D.. for direct-on-line starting 3RA1220-..C.., 3RA1120-..D.. for reversing operation
1) Space above the arc chute
2) Lockable in zero position with a shackle diameter of 5 mm
Clearance to grounded parts at the side at least 6 mm
168
79 10 17 77
10 17 5
NSK-8172b
40
1)
39
NSK-8173
40
104
SIEMENS
SIEMENS 2)
2)
125
260
260
270
270
SIEMENS SIEMENS
SIEMENS
3)
10 17.5
17,5
5
78 17 10 60
18 87 8 65
55 134 120
DC 149
Figure 5-20: 3RA1 direct-on-line starting (frame size S2) 3RA1 reversing operation (frame size S2)
1) Space above the arc chute
2) Lockable in zero position with a shackle diameter of 5 mm
3) Attached using two 35 mm rails with a depth of 7.5 mm in acc. with EN 50 022 or one 75 mm rail in acc. with EN 50 023.
Clearance to grounded parts at the side at least 6 mm
1)
1)
34
14
53
SIEMENS
2)
SIEMENS
2)
259
259
309
309
SIEMENS
SIEMENS SIEMENS
NSK-8174
NSK-8175
7 18 18 68
17 28 95 10
10 55 142 10 17.5
17,5
DC 157 120
176
Figure 5-21: 3RA1 direct-on-line starting (frame size S0) 3RA1 reversing operation (frame size S0)
1) Space above the arc chute
2) Lockable in zero position with a shackle diameter of 5 mm
Clearance to grounded parts at the side at least 6 mm
12 23 8
111
12 23
1)
60
60
5
5
40
4)
4)
100
SIEMENS
2)
SIEMENS
2)
125
330
310
320
330
320
3)
SIEMENS
SIEMENS SIEMENS
NSK-8200
NSK-8176
78 23 12 72
23 111
70 160 78 80 55
DC 173 150
195
Figure 5-22: 3RA1 direct-on-line starting (frame size S3) 3RA1 reversing operation (frame size S3)
1) Space above the arc chute
2) Lockable in zero position with a shackle diameter of 5 mm
3) Attached using two 35 mm rails with a depth of 7.5 mm in acc. with EN 50 022 or one 75 mm rail in acc. with EN 50 023.
4) Hexagonal socket 4 mm
Clearance to grounded parts at the side at least 6 mm
Y
combined with contactors live parts 1L1 3L2 5L3
1) Minimum clearance to the contactor at the front. A minimum clearance at the front is not required for a circuit breaker.
3RT1... 3RT1...
NSB01031c
NSB01032b
When installing the combination, the following clearances must be maintained to grounded
parts:
2 circuit breakers combined with contactors Clearance to grounded or live parts
1
1 3-phase busbar 2 In a combination
Z Z involving a circuit breaker
S0: 3RV19 15-1A of frame size S2 and a
Y1
3RT1... 3RT1...
Y3
Y2
General specifications
Specifications IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100)
IEC 60 947-2, EN 60 947-2 (VDE 0660 Part 101)
IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102)
Type 3RA1. 1 3RA1. 2 3RA1. 3 3RA11 4
Frame size S00 S0 S2 S3
Number of poles 3 3 3 3
Max. rated current Inmax A 12 25 50 100
(= max. rated operational current Ie)
Permissible ambient temperature °C –55 to +80 for storage/transportation
°C –20 to +70 for operation (above +60 °C with restrictions)
Rated operating voltage Ue V 690
Rated frequency Hz 50/60
Rated insulation voltage Ui V 690
Rated impulse strength Uimp kV 6
Tripping class (CLASS) In acc. with IEC 60 947-4-1, 10
EN 60 947-4-1
(VDE 0660 Part 102)
Rated short-circuit current Iq at 50/60 Hz 400 VAC kA 50
in acc. with IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102)
1
Coordination types in acc. with IEC 60 947-4-1, EN 60 947-4-1 )
(VDE 0660 Part 102)
Power loss Pv max of all main conducting paths Up to 1.25 A W 6
depending on the rated current In 1.6 to 6.3 A W 7
(upper setting range) 8 to 12 A W 10.5
2 to 6.3 A W 7
8 to 16 A W 9.5
20 to 25 A W 13
25 to 32 A W
40 A W 19
45 to 50 A W 28
63 A W 35
75 to 90 A W 29
100 A W 45
60
Power input of the magnet coils with contactors
(given a cold coil and Us, 50 Hz)
AC operation Making capacity VA 27 61 127 270
cos ϕ 0.8 0.82 0.82 0.68
Holding power VA 4.6 7.8 13.5 22
cos ϕ 0.27 0.24 0.34 0.27
DC operation Making capacity = holding power W 3.2 5.4
11.50 15
Operating range of the magnet coils with contactors 0.8 to 1.1 x Us
Lower limit at 55 °C 0.8 x Us –
at 60 °C 0.85 x Us –
Service life of circuit breakers
Mechanical life Operating cycles 100,000 50,000
Electrical life Operating cycles 100,000 50,000
Max. switching frequency per hour (motor startups) 1/h 15 15
Service life of contactors
Mechanical life Operating cycles 30 million 10 million
Electrical life Operating cycles See the service life characteristic of the contactors (part 3).
Shock resistance (sinus) In acc. with IEC 60 068 Part 2-27 g Up to 9.8 Up to 12.5 Up to 8 Up to 6
Degree of protection In acc. with IEC 60 947-1 IP 20 IP 20
IP 00
terminal housing
Shock protection In acc. with DIN VDE 0106 Part 100 Protected against
touching by fin-
gers
Phase loss sensitivity In acc. with IEC 60 947-4-1, Yes
of the circuit breaker EN 60 947-4-1
(VDE 0660 Part 102)
Disconnector properties In acc. with IEC 60 947-2, Yes
of the circuit breaker EN 60 947-2
Main and emergency-stop (VDE 0660 Part 101)
switch properties of the circuit In acc. with IEC 60 204-1, Yes, with undervoltage release to category 1
breaker and accessories EN 60 204-1 in the case of proper use
(VDE 0113 Part 1)
Safe isolation between the main In acc. with DIN VDE 0160 Part 101 Up to 400 V
and auxiliary circuits
Positively driven operation with contactors Yes Yes, from the main contact to the auxiliary normally
closed contact
Important: NSK-7666
In acc. with DIN 43 602
Start command "I"
right or above
1) After the box terminals have been removed, lug or busbar connections are possible.
6.1 Specifications/regulations
EMC
emission EN 50081
immunity EN 50082
Overview The following table offers an overview of the device groups and their distin-
guishing features:
SIRIUS
contactor relays3RT10
3RH11 For main circuits: switching from motors to 11 kW directly
For main circuits: up to 4 auxiliary switches
Table 6-2: 3RH, 3TX, LZX coupling links - overview of the device groups with their distinguishing
features
Contact material Relay coupling links are offered with AgNi and hard gold-plated contacts.
Hard gold-plated contacts have greater contact reliability at low voltages and
currents. They can be used as of mV or µA. They can be used to switch low
levels of power, such as those involved in measurement and control signals.
In the case of input coupling links, they are to be recommended on account
of the low currents of the input modules of controllers.
Models The 3TX70 coupling links for SIRIUS are available as both input couplers and
output couplers, which have their terminals in different positions:
A1 13
A2 14
13 A1
14 A2
Input coupling links have hard gold-plated contacts for greater contact reli-
ability at low voltages and currents.
Status indication A yellow status LED on the drive circuit side indicates whether there is any
control supply voltage applied to the coupler.
Protective circuit There is an integrated rectifier at the input of each coupler. As a result, they
are protected against polarity reversal. The rectifiers function as flywheeling
diodes at disconnection. Semiconductor outputs are protected by suppres-
sor or Zener diodes.
Manual-0-automatic Some coupling links are equipped with a manual-0-automatic switch that
makes it easier to switch the system on and is used for test purposes.
• Manual: Relay is always on
• O (zero): Relay is always off
• Automatic: Relay follows the control supply voltage
Power consumption Following on from the technical specifications of the electronic systems, the
coupling links have low power consumption. They can be controlled from a
programmable controller and are suitable for continuous duty.
Accessories The following accessories are available for two-tier coupling links:
• 24-pole connecting lead or connection comb
• Screwdriver for Cage Clamp terminal system
• End holder and end plate
The Plug-in relay coupling links are modular coupling links. The plug-in for-
mat means the relays can be easily replaced.
Models There are complete modules for 1 and 2 changeover contacts and individual
modules for 1, 2, 3 or 4 changeover contacts for a rated control supply volt-
age of either 24 VDC or 230 VAC.
Installation The plug-in relay coupling links are plugged into the associated bases, and
these are snapped onto a 35 mm rail in acc. with EN 50 022.
Surge suppression To avoid high breaking voltage peaks, LZX: RT and PT plug-in relay coupling
links are available for a rated control supply voltage of 24 VDC, with 1, 2, or
4 changeover contacts (Ws) and integrated surge suppression (flywheeling
diode). RC elements are available for AC voltages.
Connection The standard polarity must be taken into consideration when connecting up:
• At A1: positive voltage supply (+)
• At A2: negative voltage supply (-)
Test button The LZX: PT and MT variants are equipped with a test button. The plug-in
relay coupling link can thus be brought into the switching state and locked
without the need for electrical triggering. When the test button is protrud-
ing, this indicates the locked switching position.
Power consumption Following on from the technical specifications of the electronic systems, the
coupling links have low power consumption.
Safe isolation The drive circuit and contacts are electrically isolated. Safe isolation can also
be achieved for the print relays (LZX:RT series) by means of a special base.
Contactors S0 to S3 The 3RH1924-1GP11 coupling relay, which is screwed directly onto the coil
terminals, is available for direct attachment to the contactors of frame sizes
S0 to S3.
The 3TX4090-0C/-0D coupling links are suitable for attachment to 3TH42/43
auxiliary contactors.
Contactors of up to In the case of the large contactors of up to 450 kW (size 14), the 3TX7090
450 kW coupling link can be snapped on at the side like an auxiliary switch block,
and the wires are connected to the contactor coil terminals.
Variants There are variants with one normally open contact, 24 VDC, with and with-
out surge suppression.
The operating range is 17 to 30 VDC.
Installation The 3TX 4090 and 3RH1924-1GP11 coupling links are screwed directly onto
the contactor coil terminals, and the 3TX7090 coupling links are snapped on
at the side like the auxiliary switches.
Surge suppression The following coupling links have an integrated surge suppressor (varistor)
for the contactor coil to be switched:
• 3RH1924-1GP11
• 3TX4090-0D
• 3TX7090-0D
Power consumption Following on from the technical specifications of the electronic systems, the
coupling links have low power consumption.
6.2.6 Installation
Contact microwelding When capacitive loads are switched, a short-circuit current briefly occurs
(for a period lasting only microseconds) if the capacitor is not connected in
series with a resistor. This can result in contact microwelding and the con-
tact being unable to open after the control supply voltage is removed. To
prevent this from happening, a resistor can be connected in series, or a cou-
pling link with a semiconductor output and short-circuit protection can be
used.
Switching inductive The contacts are tested in acc. with EN 60947-5-1, utilization category AC-
loads 15 and DC-13. Going beyond the requirements of the standard, a continuous
test was carried out on the contacts with an AC-15 load for 100,000 operat-
ing cycles. The electrical service life of the contacts was thus tested over
100,000 operating cycles at the specified current under normal conditions. A
lower load on the contacts or a protective circuit for the inductive load
increases the service life of the contacts. If this service life is insufficient, a
semiconductor coupler with an unlimited service life must be used.
Max. line length in AC Each wire has a line capacitance that works like a capacitor connected in
operation series to the coupling link. The effect of this in operation with alternating
current is that so much current may flow due to the line capacitance that the
coupling link does not fall in spite of a switch being open. To remedy this, a
parallel resistor can be fitted to A1/A2 of the coupling link, or an RC combi-
nation can be used. Both of these measures change the performance and
switching times of the coupling link.
The following basic circuit diagram shows the line capacitance:
CL= line capacitance
A1
Button/
switch
Relay coupling link
~
A2
The line lengths specified in the NSK catalog were calculated for a line
capacitance of 0.3 nF/m. This depends on the wire used.
Electrical isolation There is no conductive connection between the input circuit and the output
circuit. Electrical isolation is ensured by the in-built relay and, in the case of
semiconductor outputs, by means of optocouplers.
Safe isolation Safe isolation provides protection against shock currents in different circuits.
It is implemented by means of increased creepages and clearances.
Selection table The following table provides an overview of the main criteria for selection
from different device groups:
6.4 Accessories
6.4.1 Accessories for two-tier coupling links
Connecting lead The 24-pole connecting lead 3TX7004-8BA00 can be used for all two-tier
coupling links both with screw-type and Cage Clamp terminals:
Connection comb The 24-pole connection comb 3TX7004-8AA00 can be used for the 6.2 mm
wide two-tier coupling links with screw-type terminals:
End holder The end holder 8WA2808 is snapped onto the rail (EN 50 022) without
screws.
Screwdriver for Cage The screwdriver 8WA2804 is suitable when wiring coupling links with Cage
Clamp terminal system Clamp terminals.
End plate In order to ensure shock protection in the case of the two-tier optocouplers
having a width of 6.2 mm and with a housing opening (e.g. 3TX7 004-
3AB04), the individual module or last module in a series must be fitted with
an end plate 3TX7004-8CE00.
Labeling strip Each coupling link has a labeling strip for the purpose of identification.
LED module An LED can be fitted as an individual plug-in module with the variants LZX:
RT and LZX:PT.
Module with flywheel- A flywheeling diode for surge suppression can be fitted as a module (for DC
ing diode voltages) with the variants LZX:RT and LZX:PT.
RC module For AC voltages, there is a plug-in RC module available with the series
LZX:RT and LZX:PT for surge suppression.
Snap-on attachment The coupling links are snapped onto 35 mm rails in acc. with EN 50 022.
With a vertical rail and tightly packed devices, the permissible ambient tem-
perature TU is 60° C.
Any installation position is possible.
6.5.2 Connection
The coupling links are available with the SIGUT terminal system, with
screw-type terminals, or with Cage Clamp terminals.
Conductor cross-sec- The following table shows the permissible conductor cross-sections for the
tions coupling links. The specifications apply to main and auxiliary connections.
M3 ------ ------ M3
∅ 5 to 6 mm / PZ2
1 x 0.25 to 4 mm² 1 x 0.08 to 2.5 mm² 2 x 2.5 mm² 2 x (0.5 to 2.5) mm²
1 x 0.5 to 2.5 mm² 1 x 0.25 to 2.5 mm² 2 x 1.5 mm² 2 x (0.5 to 1.5) mm²
Table 6-5: Conductor cross-sections for the 3RH, 3TX, and LZX coupling links
U A1 A2
2
A1
2
A2
NSB00184
NSB00182
A1 11
NSB00192
A2 12 14
-2BF02
Semiconductor cou- A1 13 A1 13 A1 13 A1 13
pling modules 3TX7002
NSB00193
NSB00195 NSB00196
NSB00194
A2 14 A2 14 A2 14 A2 14
A2 14
A2
13
NSB00205 A2 13
NSB00206 13
3TX700.-1M.00 3TX700.-1AB10
A1
A1 12
A1 12
14
14
A2
A2
11
A2 11
NSB00208
NSB00207 11
3TX700.-1BB00 3TX700.-1L.0.
A11
A
114
0
M
A1 113
12
A21
A3 14
214
A2
A2
A2 11
213
NSB00209 11
A2 NSB00210
3TX700.-1BB10 3TX700.-1CB00
A11
A11
114 A11 112
114
113
A21
111
214 A21
111
A21 212
213 214
A31
314
A2
A2 A2 211
NSB00212 211
A2 313 A2
NSB00211
A2 A2
3TX700.-1HB00 3TX700.-1GB00
3TX700.-2M.02
Semiconductor cou- A1 A1
pling modules +13 +13 +
A2
3TX7004/3TX7005 A2
14
14
Output coupling links NSB00214
NSB00215 Last
_
Last 0V
3TX700.-3AB04 3TX700.-3PB54
A
A1 0
M
A1 +13 A1
+13
+13 + A3 +13 +
A2
A2
A2 14
A2 14
NSB00216 Last Last
0V _ NSB00217 0V _
3TX700.-3AC04 3TX700.-3AC14
A1
A1 ~13
~13
A2
A2 ~14
NSB00218
~14
Last
3TX700.-3AC03
Semiconductor cou- A1
pling modules +13
3TX7004/7005 A2
14
Input coupling links NSB00219
Last
3TX700.-4AB04
Relay couplers
LZX: RT/PT/MT
A1 12 11 14
A1 12 11 14
A2 22 21 24
NSB00248a
A2 22 21 24
NSB00247a
NSB00249a
NSB00250a
11(7) 21(8) 31(9) 11(9) 21(10) 31(11) 41(12)
(4)12 (8)32
(3)14 (9)34
NSB00251a
NSB00274
79 1)
80 2)
NSB00271
NSB00273
NSB00272
6.2
6,2 12.5
12,5 17.5
17,5 22.5
22,5 84
NSB00270
NSB00269
60
M3 M3 M3 M3
11.5
11,5 12.5
12,5 17.5
17,5 22.5
22,5 62
3TX7 00.-1AB.. 3TX7 002-3AB00 3TX7 00.-1BB00 3TX7 00.-1CB00
3TX7 00.-2A... 3TX7 002-4A... 3TX7 00.-1BF00 3TX7 002-1BF02
3TX7 002-3AB01 3TX7 002-2BF02
NSB00275a
Haltebügel
NSB00276
15,7
15.7
Printrelais
LED-Modul
2.6
2,6 12.7
12,7
3,8
3.8
29
60
Complete device LZX: RT3/RT4 Print relay LZX: RT3/RT4
NSB00278
NSB00277
75,5
75.5
75,5
75.5
15.5
15,5 4,5 22,2
22.2 15.5
15,5 4.5 22.2
4,5 22,2
43
Plug-in base LZX: RT78625 for print relays Plug-in base LZX: RT78626 with safe isolation for print relays
Relais
NSB00279
Haltebügel
29
75
6
LED-
28 2.2
2,2 Modul
22.5
22,5
NSB00280
22.5
22,5 4.5
4,5 22.2
22,2
27 42.5
42,5
73.1
73,1
Industrial relay LZX: PT570 Plug-in base LZX: PT78703 for industrial relays
100°
35.5
62
NSB00281
32,3
32.3
24,2
24.2
NSB00282
35.5
35,5 57
69
38 4 9.3
9,3
26
Industrial relay LZX: MT32 Plug-in base LZX: MR78750 for industrial relays
45 45
NSB00265
6 11 50
45
20
30,1
30.1
NSB00267
28
NSB00283
26
20
30,1
30.1
28
LZX: RT/PT
Relay type Print relay RT, 8-pole Industrial relay PT, 14-pole
(12.7 mm) 1 W/2 W (22.5 mm) 3 W/4 W
Load side
Short-circuit protection –
Fuse links, performance class gL/gG 10 A
DIAZED
Min. contact loading 12 VDC/10 mA –
(reliability: 1 ppm)
Mechanical life 30 x 106 10 x 106 10 x 106
operating cyc-
les
Electrical life 1 x 105 1 x 105 1 x 105
(resistive load at 250 VAC) operating cyc-
les
Table 6-9: Technical specifications, LZX: RT/PT
LZX: MT
Relay type Industrial relay MT, 11-pole
(35.5 mm) 3 W
Load side
3RH1924/3TX7090
Short-circuit protection
(unwelded fuse at Ik W 1 kA)
Fuse links, performance class gL/gG A 6
NH Type 3NA
DIAZED Type 5SB
NEOZED Type 5SE
Load side
7.1 Specifications/regulations/approvals
Standards The time relays comply with the following standards:
• IEC 61812-1/DIN VDE 0435 Part 2021 on electrical relays and time relays
• IEC 61000 on electromagnetic compatibility
• IEC 60947-5-1; DIN VDE 0660 Part 200 on low-voltage switchgear
• IEC 60721-3-1/-3 on environmental conditions
• IEC 60529 on degree of protection
Electromagnetic com- The time relays are tested in acc. with EN 50 081-1 (emission) and
patibility EN 50 082-2 (immunity) and are thus noise-free and surge-proof.
UL/CSA/marine The SIMIREL time relays are approved by UL and CSA for use worldwide
approval and tested by the GL, LRS, DM marine authorities.
Device types The SIMIREL 3RP1 time relays are available in the following forms:
• Single-function devices, such as the on-delay function
• Multifunctional devices
Frame sizes The SIMIREL 3RP1 time relays are available in two widths:
• 3RP10: 45 mm
The width, height, and depth of time relays and contactors of frame size S00
(3RT/3RH10) are identical. The terminals are therefore on the same level,
and the tier spacing in the cubicle can be kept correspondingly low.
• 3RP15: 22.5 mm
Time relays with 1 changeover contact are 82 mm in height and have six
possible terminals
Time relays with 2 changeover contacts are 102 mm in height and have a
possible twelve terminals
A3 B3 21/25/27C
LED indicators
Runtime adjuster
Time-range selector switch
Function selector switch A Function indicator window
Device type plate
22/26NC
24/28NO
16NC A2(-)
18NO
Figure 7-2: 3RP15 solid-state time relay, multifunctional with 2 changeover contacts
3RP15 features The features of the 3RP15 solid-state time relays are:
• 1 changeover contact (8 functions)
• 2 changeover contacts (16 functions)
• Single or up to 15 selectable time ranges
• Contact position and voltage indication by means of LEDs
• Combination voltage 24 VAC/VDC / 200-240 VAC, and 24 VAC/VDC /
100-127 VAC
• Wide-range voltage variant for 24-240 VAC/VDC
• Single-function devices for the following functions:
- On-delay with 1 or 2 changeover contacts
- Off-delay with auxiliary supply and 1 changeover contact
- Off-delay without auxiliary supply and 1 or 2 changeover contacts
- Clock pulse generator with 1 changeover contact
- Star-delta with 2 NO contacts
- 2-wire, on-delay with semiconductor output
• Multifunctional time relay with 8 (1 changeover contact) or 16 functions (2
changeover contacts)
Accessories 3RP10
Coding plug set for the multifunctional time relay with 7 functions
3RP15
• Label sets for the multifunctional time relay with 8 or 16 functions
• Sealable cap
• Push-in lugs for screw-type terminal
7.2.2 Installation
Connection The terminals of the 3RP1 time relays are designed for connections of the
control cables with a maximum stripped length of 10 mm. Cross-sections of
2 x 0.5 to 2.5 mm2 (single-coil) and 2 x 0.5 to 1.5 mm2 (single-coil) can be
clamped with a wire end ferrule.
Screw-type terminal (SIGUT® terminal)
The 3RP10 and 3RP15 time relays are available with plus-minus Pozidriv 2
screw-type connections.
Cage Clamp terminal
The 3RP10 and 3RP15 time relays are available with Cage Clamp terminals.
Operating temperature There are no restrictions on the control supply voltage, switching current, or
duty cycle for operation between -25 °C to +60 °C.
Time ranges There are up to 15 time settings, ranging from 0.05 s to 100 hr. The 3RP15
has additional time settings between the decade scales (1/10/100 s/min/h)
that make high setting accuracy possible.
Wide-range voltage There are multifunctional relays with a wide voltage range of 24 VAC/VDC to
240 VAC/VDC.
Electrical service life The electrical service life with contactor load (e.g. 3RT1016 contactor) is 10
million operating cycles.
The electrical service life at AC voltage of 230 V, utilization category AC-15/
3 A, and at DC voltage, utilization category DC-13/1 A, is 100,000 operating
cycles.
Start contact In the case of functions that require a continuous auxiliary supply to termi-
nals A1/A2 and A3/A2, the time function can be started by a control supply
voltage to terminal B1 or B3.
Identical potential Identical potential must be applied to terminals A1 and B1 or A3 and B3.
Combination voltage In the case of combination voltage types, only one voltage range can be
connected. Never apply the two control supply voltages simultaneously.
Parallel load at the start The start contact is under voltage and rectified. There is a connection in the
contact time relay to the A1 and A2 terminals. The control of loads parallel to the
start input is therefore not permissible at AC 50/60 Hz control supply volt-
age.
Two-wire time relay Two-wire time relays have the following advantages over conventional time
relays in connection with contactors:
– Reduced wiring
– Bounce-free control
– The electronic output increases service life because no mechanical wear
occurs.
– Greater switching frequency
Special functions • Pulsing function: pulse and idle time can be set separately.
• Flashing: the pulse/break ratio is 1:1.
• The timing period starts with the "off-delay without auxiliary supply" func-
tion if the time relay is separated from the supply voltage.
• In the case of the 3RP15 time relay with 15 selectable time settings,
there is a ∞ switch position. This means an endless timing period. If this
setting is chosen for the on-delay function, the output relay never swit-
ches through after the supply voltage has been applied (off function). In
the case of the "making pulse contact" function, the output relay always
remains on (on function). This can be used for test purposes.
• In the case of the "additive on-delay with auxiliary supply" function, the
time is added for as long as the start contact is activated. If the start con-
tact is interrupted, the timing period stops and is then continued once the
start contact is closed again.
This function is not non-volatile and requires a continuous auxiliary power
supply.
• In the case of the "shaping pulse contact with auxiliary supply" function,
an activated start contact triggers a timing period that can be set. The
control signal for this can be shorter or longer than the desired runtime.
Cable ducts If you use cable ducts for wiring, the position and dimensions of the termi-
nal blocks must be taken into consideration (see pages 7-27).
Setting accuracy Setting accuracy is the accuracy in relation to the end value of the scale in
line with the specified tolerance.
Repeatability Repeatability describes the accuracy with which the set value can be repro-
duced with the specified tolerance.
Operating time adjust- Eight time ranges can be set by means of a rotary switch.
ment The desired runtime can be set accurately by means of a potentiometer (ro-
tary switch for fine adjustment).
Important
Changes to the time range are only effective if they are made in a deenergi-
zed state.
Step Procedure
1 1s
10 s
10 h
1 min
Rotate the time range selector switch to 10 s. This means
100 s
100 min
1h 10 min runtimes of up to 10 seconds can be set.
2
60
40 Rotate the potentiometer to 50% for fine adjustment. In
80
20 other words, 50% (= 5 seconds) of the maximum value (10
5 100% seconds) is set.
Table 7-1: 3RP10 00 (multifunctional) operating time adjustment
1s
10 s
1 min
15C B3+ A3+ B1 A1 10 h 100 s
100 min 10 min
1h
3RP 60
1s 5 s: 40
10 s 80
1 min
10 h 100 s
20
100 min
1 h 10 min 5 100%
60 1s
40 10 s
80 1 min
20
10 h 100 s
5 100%
100 min
1.5 min 1 h 10 min
60
16NC 18NO A2- (90 s): 40
80
20
5 100%
Functions You can select 7 different functions with the coding plug set (7PX9904) pro-
vided.
Important
Changes to the function are only effective if they are made in a deenergized
state.
Without the coding plug the multifunctional time relay (3RP10 00) is pro-
grammed for the on-delay.
Function setting The connector with the function you want is removed from the coding plug
set and put on the time relay as shown in the following diagram:
The name of the function and the corresponding circuit diagram are printed
on the coding plugs in German and English.
Function diagrams The coding plug set contains the functions for the 3RP1000 solid-state time
relay listed in the following table:
Flashing, 15 C
A. A./A2
start with break )
A2 16 NC 18 NO
15/18
15/16
Blinker t t
FLASHER
Important
The same potential must be applied to terminals A and B.
Operating time adjust- Fifteen time ranges can be set using a rotary switch, ensuring very precise
ment adjustment. The set time range is displayed in a window next to the rotary
switch.
The desired runtime can be set accurately by means of a potentiometer
(rotary switch for fine adjustment).
In the time range position ∞ the function is executed with an endless time
period. This means, for example, that the output relay never switches
through when "on-delay" is set and the supply voltage is applied or that the
output relay remains continuously on when "making pulse contact" is set.
Important
Changes to the time range are only effective if they are made in a deenergi-
zed state.
Step Procedure
1
100s
Rotate the time range selector switch until 100 s
appears in the adjacent window. This means runt-
imes of up to 100 seconds can be set.
2
60
40 Rotate the potentiometer to 90%. In other words 90% (=
80
20 90 seconds) of the maximum value (= 100 seconds) is set.
5 100%
A1 B1 15/17C
A3 B3 21/25/27C
60
40
80
20
5 s: 100%
5
10 s
60
40
80
20
A 1.5 min 5 100%
(90 s):
100
22/26NC
24/28NO
16NC A2(-)
18NO
Important
Changes to the function are only effective if they are made in a deenergized
state.
Function setting The function is set using a rotary switch and is indicated by an identifying
letter in the adjacent window.
The set function can be labeled distinctly with an identification plate with
the corresponding function diagram. At the same time, a mechanical code
ensures that the correct function is set by ensuring that a label can only be
clipped on if the corresponding function is set using the rotary switch.
A label set with function diagrams of all the functions that can be set for the
time relay is available as an accessory.
Break the label of the set function out of the label set, and snap it firmly
onto the time relay as shown in the following diagram:
1
2
Identifying letters The following table lists the identifying letters for the 8 or 16 functions of
the solid-state multifunctional 3RP15 05 time relay:
The • after the identifying letter indicates that the second changeover con-
tact present reacts as an immediate switching contact (controlled by the
supply voltage or the start contact depending on the function). If this • is not
present, the second changeover contact reacts with a time delay like the
first changeover contact.
Function diagrams The following table explains the 8 or 16 functions of the solid-state multi-
Circuit diagrams functional 3RP15 05 time relay using circuit diagrams and function dia-
grams:
Device circuit
Identifying letter Function diagram
diagrams
A AC/DC24V
On-delay AC100/127V
AC200/240V
A./A2
15/18
15/16
A1 A3 15 25/28
25/26
*
NSB00897
A2 16 18
B
A./A2
Off-delay with auxiliary sup- AC100/127V
AC200/240V
B./A2
ply 15/18
A1 B1 A3 B3 15 15/16
NSB00898
25/28 *
25/26
A2 16 18
C AC/DC24V
A./A2
On-delay and off-delay with AC100/127V
AC200/240V
B./A2
auxiliary supply (t=ton=toff) 15/18
A1 B1 A3 B3 15 15/16
NSB00899
25/28
25/26
*
A2 16 18
D AC/DC24V
Flashing, start with break AC100/127V
AC200/240V
A./A2
A2 16 18
E AC/DC24V
Making pulse contact AC100/127V A./A2
AC200/240V 15/18
15/16
A1 A3 15 25/28 *
25/26
NSB00901
A2 16 18
F AC/DC24V
A./A2
Breaking pulse contact AC100/127V
AC200/240V B./A2
with auxiliary supply 15/18
A1 B1 A3 B3 15 15/16
25/28 *
NSB00902
25/26
A2 16 18
G AC/DC24V
A./A2
Shaping pulse contact with AC100/127V
AC200/240V
B./A2
auxiliary supply 15/18
A1 B1 A3 B3 15 15/16
(creates a pulse at the out- 25/28 *
NSB00903
25/26
put irrespective of the A2 16 18
length of excitation)
H• AC/DC24V
A./A2
Additive on-delay with aux- AC100/127V
AC200/240V
iliary supply and immediate B./A2
15/18
A1 B1 A3 B3 15
switching 15/16
NSB00904
Σ 21/24
21/22
A2 16 18
Device circuit
Identifying letter Function diagram
diagrams
A• AC/DC24V
NSB00917
21/24
21/22
A2 16 18 22 24
B• AC/DC24V
B./A2
ply and immediate switch- 15/18
A1 B1 A3 B3 15 21
ing 15/16
NSB00918
21/24
A2 16 18 22 24 21/22
C• AC/DC24V
On-delay and off-delay with AC100/127V
AC200/240V
A./A2
B./A2
auxiliary supply and imme- 15/18
A1 B1 A3 B3 15 21
diate switching 15/16
NSB00919
21/24
(t=ton=toff) A2 16 18 22 24 21/22
D• AC/DC24V
21/22
A2 16 18 22 24
E• AC/DC24V
Making pulse contact and AC100/127V A./A2
AC200/240V
immediate switching 15/18
15/16
A1 A3 15 21
21/24
NSB00921
21/22
A2 16 18 22 24
F• AC/DC24V
Breaking pulse contact with AC100/127V
A./A2
AC200/240V
auxiliary supply and imme- B./A2
15/18
diate switching A1 B1 A3 B3 15 21 15/16
NSB00922
21/24
A2 16 18 22 24
21/22
G•
AC/DC24V
Shaping pulse contact with AC100/127V
A./A2
AC200/240V
auxiliary supply and imme- B./A2
15/18
diate switching A1 B1 A3 B3 15 21 15/16
NSB00923
A2 Y18 d28
7.3.3 On-delay
Time ranges Eight time ranges can be set by means of a rotary switch.
Important
Changes to the time range are only effective if they are made in a deenergi-
zed state.
Function diagram
On-delay
ON DELAY
A./A2
15/18
15/16
Time ranges Fifteen time ranges can be set by means of a rotary switch.
Important
Changes to the time range are only effective if they are made in a deenergi-
zed state.
The function diagram for the time relay with 1 changeover contact and with
2 changeover contacts:
Function diagrams On-delay On-delay
ON DELAY ON DELAY
A./A2
15/18
A./A2 15/16
15/18 25/28
15/16 25/26
The two-wire time relay is connected in series with the load. The timing
period begins after the control supply voltage has been applied. The semi-
conductor output then becomes live, and voltage is applied to the load.
Time ranges Four time ranges can be set by means of a rotary switch.
Important
Attention must be paid to the rated operational current, residual current with
unswitched output, and voltage drop in the case of a switched output.
A1/A2
7.3.4 Off-delay
B./A2
15/18
15/16
Time ranges Seven time ranges can be set by means of a rotary switch. Times ranging
from 0.05 to 100 s are possible.
Important
Changes to the time range are only effective if they are made in a deenergi-
zed state.
The function diagram for the time relay with 1 changeover contact and with
2 changeover contacts:
Function diagrams Off-delay Off-delay
OFF DELAY OFF DELAY
2
A1/A2
2
15/18
A1/A2 15/16
15/18 25/28
15/16 25/26
Mode of operation When the rated control supply voltage is applied, the time relay switches
over. After the rated control supply voltage has been disconnected, the runt-
ime t starts. After t has finished, the relay switches back to the quiet state.
If the minimum on-time is not adhered to, it is ensured that either the timing
period will not start or that a started timing period will always be properly
completed.
Intermediate states in the function process, such as the relay getting stuck,
are successfully prevented.
Description The idle time and the pulse time of the clock pulse generator and the time
ranges must be set separately.
The pulsing function begins with the break.
Time ranges Fifteen time ranges can be set by means of a rotary switch.
Important
Changes to the time range are only effective if they are made in a deenergi-
zed state. A pulse, for example, can be output cyclically for 1 second after a
break of 1 hour.
Description The instantaneous star contact and the time-delayed delta contact have a
shared contact root.
To avoid phase short circuits, the switchover break from star to delta is
50 ms.
Function diagram
Star/delta
STAR/DELTA
A./A2
17/18
17/28
Description Supply voltage is applied to A./A2 and there is no control signal at B./A2.
This starts the *d timing period. By applying the control signal to B./A2,
the idling time (overtravel time) is started. When the set time tIdling (30 s to
600 s) is completed, the output relays (17/16 and 17/28) are reset. If the con-
trol signal is switched off at B./A2 (minimum off-time 270 ms), a new timing
period is started.
Function diagram
Star-delta with overtravel
STAR/DELTA with idling
A./A2
B./A2
17/18
50 ms
17/28
17/16
t t
* Idling
7.4 Accessories
7.4.1 Accessories for 3RP10
Coding plug set Included with the 3RP10 00 solid-state time relay is a coding plug set for 7
functions. The function is set by clipping on a label with that function on it.
The following diagrams show you how to affix the coding labels:
Label set Two label sets are available to the 3RP15 05 solid-state time relay, multi-
function device for labeling, depending on the version (8 functions with 1
changeover contact, 16 functions with 2 changeover contacts):
• 3RP19 01-0A for the 3RP15 05-1A electronic relay, 1 changeover contact
• 3RP19 01-0B for the 3RP15 05-1B electronic relay, 2 changeover contacts
The following table shows you how to set the function on the time relay and
put on the label:
Illustration Procedure
1 The desired function is set on
the potentiometer of the time
relay using a screwdriver.
1
2
Sealable cover All 3RP15 solid-state time relays can be secured against unauthorized
adjustment by means of a sealable cover (3RP19 02). The following table
and illustration explain how to do this:
Illustration Procedure
1Break off the key for interlocking from
the upper edge of the cover.
2
3RP19 02
Push-in lugs for screw- Push-in lugs (3RP19 03) are available for the screw-type attachment:
type attachment
3RP19 03
3RP10
Snap-on attachment The 3RP10 time relays can be snapped onto the 35 mm rails and removed
without tools in acc. with EN 50 022.
Place the time relay on the upper edge of the rail, and press it downward
until it snaps onto the lower edge of the rail. To remove the time relay, press
it downward to release the tension of the spring, and the time relay can be
removed.
Screw-on attachment The following is required for screw-type attachment of the 3RP10 time relay:
• 2 M4 screws, diagonal
• Maximum tightening torque of 10.5 Nm
• Washers and spring lock washers must always be used
• The distance to grounded parts at the side must be more than 6 mm
3RP15
Snap-on attachment The 3RP15 time relays can be snapped onto the 35 mm rails and removed
without tools in acc. with EN 50 022.
Place the time relay on the upper edge of the rail, and press it downward
until it snaps onto the lower edge of the rail. To remove the time relay, press
it downward to release the tension of the spring, and the time relay can be
removed.
Screw-on attachment Screw-on attachment is possible by means of push-in lugs for M4 screws
(application, see under Section 7.4 Accessories)
7.5.2 Connection
The 3RP10 solid-state time relays are available with SIGUT terminals with
plus/minus Pozidriv 2 screws and also with Cage Clamp terminals.
The 3RP15 solid-state time relays are available:
• With SIGUT terminals with plus/minus Pozidriv 2 screws
• With Cage Clamp terminals
Conductor cross-sec- The following table lists the permissible conductor cross-sections for the
tions 3RP1 solid-state time relays. The specifications apply to control and load
current connections.
2
1
3
3RP10
Us = AC 100/127 V
Us = AC/DC 24 V Us = AC 200/240 V
L1(+) L1
B3 A3 B1 A1 15 B3 A3 B1 A1 15
A2 16 18 A2 16 18
N(-) N
L1 L1
S1 K1 S1
A1 B1 A1 B1
(A3+) (B3+) (A3+) (B3+)
K1 K1
A2 A2
N N
3RP15
Us = AC/DC 60 V
Us = AC 100 ... 127 V
Us = AC/DC 24 V Us = AC 200 ... 240 V
Us = AC/DC 42 ... 48 V Us = AC/DC 24 ... 240 V
L1(+) L1
B3 A3 B1 A1 B3 A3 B1 A1
A2 A2
N(-) N
L1 L1
K1 S1
S1
A1 B1 A1 B1
(A3+) (B3+) (A3+) (B3+)
K1
K1
A2 A2
N N
8.6 67
5.3 5 51 35
5
2)
36
55
58
50
3)
4)
NSB00978
45 7.5
3RP10
1)
73.5
62
90
80
4)
NSB00980
15 5 approx. 65 (terminals)
22.5 86
3RP15, 1 changeover contact without auxiliary supply5) , clock pulse generator, star-delta function
1)
110
73.5
62
82
80
4)
approx. 37
NSB00981
15 (terminals)
22.5 5 approx. 65 (terminals)
8.1 Specifications/regulations/approvals
The 3RW3 semiconductor motor control units, referred to below more suc-
cinctly as soft starters, meet the UL and CSA requirements.
UL/CSA UL 508
Degrees of protection
EN
offered by housings
Electronic
IEC 60947 - 4-2
Motor control units
Normal switching duty The 3RW3 soft starters can be used for normal switching duty in acc. with
DIN VDE 0100 Part 460:
A switch for normal switching duty must be provided for all circuits that are
to be switched independently of other parts. Switches for normal switching
duty do not necessarily all switch active conductors of a circuit.
Isolation The soft starters do not meet the requirements for isolation
in acc. with DIN VDE 0100 Part 460 and EN 60 947-1:
Every circuit must be capable of being isolated from the active conductors
of the power supply.
Circuit groups can be isolated by a common device if this is permitted by the
operating conditions. In the open position, devices with an isolating function
must have a corresponding isolating distance and an indicator showing the
positions of the moving contacts.
Warnings
Caution Important
The devices are all carefully tested at the The 3RW3...-1.B1. soft starter was built as
factory and are not shipped unless they a class A device. Using this product in res-
are found to be in proper working order. idential buildings could cause radio inter-
However, they may be subjected to ference.
stresses during transportation over which
we have no control.
3RW30/31 frame sizes The 3RW30 soft starter is available in four frame sizes: S00, S0, S2, and S3.
The 3RW31 soft starter is available in frame size S0.
The following table contains the power ranges of the various frame sizes (all
specifications apply to UN = 400 V and 40° C ambient temperature):
1.1 - 4 kW 5.5 - 11 kW 15 - 22 kW 30 - 55 kW
Starting current Three-phase current asynchronous motors have a high inrush current I(star-
ting). This inrush current can be between three and fifteen times as high as
the rated operational current, depending on the type of motor. A figure bet-
ween seven and eight times the rated operational current can be postulated
as typical.
I
Istarting
Irated
I0 (no-load)
nrated nsyn n
Mcusp
M
Mmotor
Mstarting
Mload
Msaddle
Maccel
Mrated
Mmotor
Mload
nrated nsyn n
Figure 8-1: Typical current and torque curve of a three-phase asynchronous motor
Important
This starting current must be taken into consideration in the design of the
supply network, among other things by adapting the supply (high heat deve-
lopment) and the fusing (inadvertent tripping of the fuses).
Reducing the starting There are various ways of reducing the starting current:
current • By star-delta starter
• By frequency converter
• By soft starter
Star-delta starter After a delay, the motor windings are switched from a star to a delta config-
uration. The motor current for star starting is only about 1/3 of that required
for delta starting (motor torque, too, is reduced to approximately 1/3 of the
delta torque).
Disadvantages:
• 6 motor cables are necessary
• Switching surges occur (in the current and torque transients)
• The startup cannot be adapted to the system environment
• Installation is relatively complicated and time-consuming
• More space is needed in the cubicle
Mload
Starting current
for */d-start
IA*=
1/3 IA d Mmotor for*
=1/3 MAd MA*
n n
n nsyn n nsyn
*nrated *nrated
Frequency converter A frequency converter converts the AC voltage from the grid to direct volt-
age, which can then be converted to any voltage and frequency.
The illustration below shows how a frequency converter works:
0V
Disadvantages:
• Relatively complicated wiring needed in order to meet radio interference
suppression requirements; filters are often essential
• Line capacitances limit the lengths of motor feeder cables; it may be nec-
essary to use chokes, sinus filters, or even dV/dt filters.
• Expensive
• System startup is complex and time-consuming on account of the multi-
plicity of operating parameters
• It can be necessary to use shielded motor feeder cables
Advantages:
• Motor speed is variable; speed can be accurately pegged at constant lev-
els.
Soft starter With a soft starter, motor voltage is increased from a selectable starting
voltage to the rated voltage by phase firing within a defined starting time.
Motor current is proportional to the motor voltage, so the starting current is
reduced by the factor of the defined starting voltage.
The illustration below shows how the 3RW3 soft starter works:
UL1- L3
α α
α
α ϕ
L1
UL1- L3
M L2
3~
L3
G1
Figure 8-4: Phase firing of the supply voltage by semiconductor elements in the 3RW3 soft starter
Example:
Starting voltage 50% of Ue => starting current equals 50% of the motor
starting current for direct-on-line starting.
A soft starter also reduces motor torque. This is the reason why a soft-
started motor does not jerk into action.
The relationship is as follows: The motor torque is proportional to the square
of the motor voltage.
Example:
Starting voltage 50% of Ue => starting torque 25% of the starting torque for
direct-on-line starting.
Advantages:
• Less space needed in the cubicle
• No protective circuits (e.g. filters) necessary to comply with the radio
interference suppression specifications (class A; in UC 24 V control volt-
age version also class B)
• Lower installation costs
• Straightforward system startup
• Only 3 motor feeder cables, half as many as are needed for a star-delta
starter
• Adjustment options permit adaptation to the system.
Disadvantages:
• Long-term speed settings not possible.
• Lower torque at reduced voltage
I M
100% Ugrid
Istartingf
100% Ugrid
Istarting Mstarting
0.7 x 70% Ugrid
Istartingf 70% Ugrid
0.5 x 50% Ugrid
Mstarting
0.49 x 50% Ugrid
Mstarting
0.25 x
nsyn n nsyn n
Figure 8-5: Current and torque curves for a soft starter
The SIRIUS modular system offers a variety of alternatives for load feeders.
In addition to the star-delta starters (see Chapter 5, "3RA fuseless load feed-
ers"), the SIRIUS 3RW3 soft starters are also available.
The 3RW3 soft starters can be combined with the following SIRIUS devices:
• 3RT contactors
• 3RV circuit breakers
• 3RU thermal overload relays
• 3RB10 electronic overload relays
They are all mounted and connected up in the same way.
Please note the relevant guidelines in Section 8.3.2.
Normal switching Normal switching duty of a circuit can, according to the definitions of isola-
duty tion and normal switching data in DIN VDE 0100 (see Section 8.1), be imple-
mented with a contactor or a soft starter alone.
Isolation According to DIN VDE 0100, isolation from the supplying network cannot be
provided by a semiconductor element (i.e. soft starter, frequency converter,
contactor, or similar).
To implement isolation from the supplying network, a 3RV circuit breaker (or
another isolating device that fulfills the requirements of DIN VDE 0100)
must be used in addition to the contactor or soft starter. A contactor alone
in combination with the soft starter is not enough.
Both isolation and normal switching duty can be implemented quickly and
easily with the 3RW3 soft starter in combination with the modules from the
SIRIUS modular system.
3RW31
By means of 3 potentiometers for setting:
• Starting time 1 in the range from 0 to 20 seconds
• Starting voltage in the range from approx. 30 to 100% of the rated voltage
of the motor
• Starting time 2 in the range from 0 to 20 seconds
A special software program ensures that progressive ramp times are set.
Short times of up to 5 seconds can thus be set very precisely.
3RW31
The 3RW31 does not have any auxiliary contacts.
Soft coasting-down The integrated soft coasting-down function prevents the drive coming to an
function abrupt halt when the motor is switched off.
3RW30 time ramps The following graphics show the time ramp of the 3RW30 and the timing
diagram of the auxiliary contacts:
U
UN
ON 13/14
Us
BYPASSED 23/24
t tR off
tR on tR off tR on
3RW30: Time ramp Timing diagram of the auxiliary
contacts
Figure 8-6: Time ramp/timing diagram, 3RW30
Us
t
tR1 tR2
Figure 8-7: Time ramp, 3RW31
Accessories A fan can be snapped into the soft starter housing of frame sizes S0 to S3
from below. This brings the following benefits:
• Improved range of options for the installation position
• Increase in the switching frequency (see Section 8.3.2, "Installation guide-
lines")
In the case of frame sizes S0 and S2, extended terminal covers can be
mounted on the box covers in order to cover the cable ends and keep them
safe from fingers. These are identical to the extended terminal covers of the
SIRIUS 3RT contactors of the same frame sizes.
In the case of frame size S3, terminal covers are available for lug connection
or bar connection. These, too, are identical to the accessory parts of the cor-
responding SIRIUS contactor size.
See Section 8.4 for details of other accessories.
Mounting The devices are attached to the 3RV circuit breakers by means of a link mod-
ule and are thus connected mechanically and electrically. This link module is
identical to the one that is used for the corresponding contactor/circuit-
breaker combinations. This installation variant offers all the advantages of a
fuseless load feeder.
Link modules The following link modules are used to combine 3RW3 soft starters and
3RV1 circuit breakers:
S00 3RA1911-1A
S0 3RA1921-1A
S2 3RA1931-1A
S3 3RA1941-1A
Table 8-3: Link modules
Connection The 3RW3 electronic soft starters are available with screw-type terminals.
Plus-minus POZIDRIV 2 screws are used.
The SIGUT terminal system is used (captive screws, contacts open on deliv-
ery, etc.).
8.2.3 Comparison of the 3RW3 semiconductor motor control unit (soft starter) with the
SIKOSTART 3RW22 and SIKOSTART 3RW34 motor control units
Functions
High
End SIKOSTART 3RW22
SIKOSTART 3RW22 The SIKOSTART 3RW22 is suitable for drives that place high demands on
the functionality of the starter. It covers a power range from 3 kW to 710 kW
(at 400 V).
SIKOSTART 3RW34 The SIKOSTART 3RW34 is suitable for drives with low demands in terms of
the functionality of the soft starter. The SIKOSTART 3RW34 is very similar to
the SIRIUS 3RW3 soft starter in terms of its operation and configuration. It
covers a power range of up to 1000 kW (400 V).
The functions of the 3RW34 are as follows:
• Soft starting and soft coasting down
• 2 circuit variants: standard and root 3 circuits
• Three-phase control
• Optional AS-i bus control
You will find the technical specifications and a detailed description of the
3RW34 in the document describing SIKOSTART 3RW22/3RW34 solid-state
motor controllers (order no.: E20001-A200-P302).
SIRIUS 3RW3 soft The SIRIUS 3RW3 soft starter covers the power range from 1.5 kW to
starter 45 kW.
Power semiconductors always exhibit power loss. This manifests itself in
heat generation. In order to keep this power loss as low as possible, the
semiconductors are bypassed by relay contacts after the motor has started
up. The device's heat sink and its dimensions can thus be smaller than they
otherwise would be. In addition, it is necessary to use a bypass contactor,
which bypasses the line semiconductors in the conventional configuration.
For further processing in the system controller, the device offers two relay
outputs:
• "ON" contact (terminals 13/14), which can be used, for example, to control
the soft starter by button (locking)
• "BYPASSED" contact (terminals 23/24), which signals the completion of
startup (e.g. in order to switch a solenoid valve after a soft-started pump
has started up)
For drives in this power range, good motor startups can be achieved with a
two-phase controller.
In the case of a two-phase controller, semiconductor elements are only
used in two phases in order to reduce motor current and motor voltage in all
three phases. The third phase is bypassed internally in the soft starter.
8.2.4 Comparison of the 3RW3 semiconductor motor control unit (soft starter)
with the 3RA star-delta combination
The comparison of soft starter and star-delta combinations shows that the
3RW3 has the following advantages (example here 22 kW):
In order for a motor to reach its rated speed, motor torque at any given time
during startup must be greater than the torque needed by the load, since
otherwise a stable operating point would be reached before the motor
achieved its rated speed (the motor would "drag to a stop"). The difference
between motor torque and load torque is the accelerating torque that is
responsible for the increase in the speed of the drive. The lower the acceler-
ating torque, the longer the motor needs to run up to its operating speed.
Example:
Motor = 55 kW, rated current = 100 A, starting current = 7 x rating current,
motor torque = 355 Nm, starting torque = 2.4 x rated torque
Settings for the soft starter: starting voltage 50% of rated voltage for motor
The reductions are thus as follows:
• The starting current is reduced to half the starting current for a direct
start: 50% of (7 x 100 A) = 350 A
• Starting torque is reduced to 0.5 x 0.5 = 25% of the starting torque for a
direct start: 25% of 2.4 x 355 Nm = 213 Nm
Note On account of the fact that the starting voltage is proportional to the square
root of the motor torque, it is important to ensure that the starting voltage is
not too low. This applies particularly for a pronounced saddle torque, the
lowest motor torque that occurs during run-up to rated speed.
Mmotor
M
Mstarting
MB
MB = accelerating torque
of the motor
Mstarting
with
SIRIUS3R
Soft starter n
Ue
US
tR t
Figure 8-9: Load and motor torques and motor terminal voltage for operation with soft starter
The 3 potentiometers on the starter are for setting the starting voltage, the
starting time, and the coasting-down time.
The soft starter is correctly set when the motor starts smoothly and runs up
rapidly to its rated speed.
Ramp times of up to 20 seconds can be set.
The SIRIUS 3RW3 soft starters offer an alternative to star-delta starters (see
Section 8.2.4 for a comparison and the advantages).
The most important advantages are soft starting and soft coasting-down,
interruption-free switching without current spikes that could interfere with
the supply system, and compact dimensions.
Many drives that needed frequency converters in the past can be changed
to soft-start operation with the 3RW3, if the applications do not call for vari-
ations in speed.
Stand-alone installa- Stand-alone installation is when minimum vertical and lateral clearances
tion between the mounted devices are not violated. This applies both to indivi-
dual devices and complete load feeders.
The following minimum clearances must be adhered to in stand-alone instal-
lation (these minimum clearances depend on the frame size):
Minimum clearance on
Frame size
both sides in mm
S00 15
S0 20
3RW30
S2 30
S3 40
Table 8-5: Stand-alone installation, minimum clearances at the side, 3RW3
a
Vertical Vertical
Frame size
clearance a clearance b
S00 50 50
S0 60 40
3RW30
S2 50 30
S3 60 30 b
Line lengths for the The control inputs for starting and stopping are not rated for longer dis-
drive circuit tances. This means:
• In the case of a drive circuit that goes beyond the control cubicle, cou-
pling relays must be used.
• The control cables in the cubicle should not be laid together with main cir-
cuit cables.
When electronic output modules are used in the drive circuit (e.g. Triac out-
puts at 230 VAC), RC elements (e.g. 3TX7462-3T or similar with C > 100 nF)
may be required at the control inputs under certain circumstances.
Correction factors If the minimum clearances are violated, in a combination of a soft starter
with a circuit breaker, fixed correction factors must be used to determine
the rated current for the device and the switching frequency.
The following variables can be modified by means of correction factors:
• Rated current for the device
• Switching frequency
• Current setting of the circuit breaker
• Current setting of the overload relay
Correction factor for the A factor is specified by which the device rated current of the soft starter is
rated current of the reduced.
device Example:
Correction factor for the rated current of the device = 0.9
Selected device = 3RW3014-1CB14 (under normal conditions at 40 °C a
device rated current of 6 A)
This results in an actual device rated current of:
0.9 x 6 A = 5.4 A
Correction factor for The switching frequency is the maximum permissible number of starts per
switching frequency hour. This value must be adjusted by the specified correction factor. The
number of permissible starts per hour is given in Table 8.7.1, Control electro-
nics/power electronics, in Section 8.7, Technical specifications.
The specified correction factors refer to the following operating conditions:
S4 operation, 40 °C ambient temperature, 30% duty cycle
Example:
Correction factor for the switching frequency = 1.5
Selected device = 3RW3014-1CB14 (has a maximum switching frequency of
30 starts per hour under the conditions specified above)
This results in a corrected switching frequency of:
1.5 x 30 = 45 starts per hour
To increase the switching frequency, it is also possible to use a larger
device.
Correction factor for the In combinations of a 3RW30 soft starter and a 3RV1 circuit breaker, the set
current setting of the value of the circuit breaker may have to be corrected appropriately. The cor-
circuit breaker rection factor specifies the extent of the change.
Example:
Correction for the current setting of the circuit breaker: 1.1
Selected device = 3RW3014-1CB14
The connected motor has a motor rated current of 5 A.
The set value of the circuit breaker must be changed to:
1.1 x 5 A = 5.5 A
Correction factor for the In combinations of a 3RW30 soft starter + 3RU1 thermal overload relay or
current setting of the 3RW30 software starter + 3RB10 electronic overload relay, the set value of
overload relay the overload relay must be corrected appropriately. The correction factor
specifies the extent of the change.
Example:
Correction factor for the current setting of the overload relay 0.9
Selected device = 3RW3014-1CB14
The connected motor has a motor rated current of 5 A.
The set value of the overload relay now has to be changed to:
0.9 x 5 A = 4.5 A
The tables below give the correction factors for the circuit-breaker current
setting, the device rated current, and the switching frequency.
The values indicate the difference between use with a fan (accessory) and
use without a fan.
All correction fans apply throughout the entire temperature range (i.e. for
40 °C, 50 °C, and 60 °C).
The various tables specify the values in turn for the following:
3RW30/31 soft starters in a stand-alone installation
3RW30/31 soft starter + 3RV1 circuit breaker
3RW30/31 soft starter + 3RT1 contactor + 3RU1 thermal overload relay
3RW30/31 soft starter + 3RT1 contactor + 3RB10 electronic overload relay
Minimum clearance In the case of frame size S00 (3RW301..), the following applies to stand-
alone, vertical installation without directly attached switching devices:
In order to maintain the required space above the arc chute, clearance of at
least 50 mm must be maintained to grounded parts above and below.
3RW30/31 correction 3RW30/31 soft starters not combined with any other switching devices:
factors
Without fan With fan
Stand-alone installa-
Stand-alone installa- tion
tion Installed side by side or
side by side
Correction factor Correction factor Correction factor
Device Rated cur- Switching Rated cur- Switching Rated cur- Switching
Order number Frame rated cur- rent for frequency rent for frequency rent for frequency
size rent in A at the device the device the device
40 °C
3RW3014-1CB.. S00 6 1 1 1 0,75 - 1) - 1)
3RW3016-1CB.. S00 9 1 1 1 0.75 - 1) - 1)
3RW3.24-1AB.. S0 12.5 1 1 1 0.65 1 1.8
3RW3.25-1AB.. S0 16 1 1 1 0.65 1 1.8
3RW3.26-1AB.. S0 25 1 1 1 0.65 1 1.8
3RW3034-1AB.. S2 32 1 1 1 0.65 1 1.8
3RW3035-1AB.. S2 38 1 1 1 0.65 1 1.8
3RW3036-1AB.. S2 45 1 1 1 0.65 1 1.8
3RW3044-1AB.. S3 63 1 1 1 0.8 1 1.6
3RW3045-1AB.. S3 75 1 1 1 0.75 1 1.6
3RW3046-1AB.. S3 100 1 1 1 0.7 1 1.6
Table 8-7: Correction factors, 3RW30/31
8.3.3.2 3RW30/31 soft starters in combination with the 3RV1 circuit breaker
3RV
Link module
3RW
3k
M
Dimensioning of the The frame size selected for the circuit breaker should be large enough so
circuit breaker that the current value calculated can just be set.
In the event of current values that are lower than can be set for the speci-
fied circuit breaker, the next smaller circuit breaker must be used.
Frame size
Order number
Order number
Circuit breaker
Circuit breaker
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Adjustment range
Switching frequency
Switching frequency
Switching frequency
Switching frequency
at an ambient temperature of 40 °C
Current setting of the circuit breaker
Current setting of the circuit breaker
Current setting of the circuit breaker
Current setting of the circuit breaker
Table 8-8: Correction factors: 3RV1 circuit breaker + 3RW3 soft starter
3RW3036-1AB.. S2 45 3RV1031-4GA10 (36 - 45) A 1 0.85 1 0.9 0.4 1.1 1 1.8 1 1 1.7 1.1
3RW3044-1AB.. S3 63 3RV1041-4JA10 (45 - 63) A 1 0.85 1 0.95 0.6 1.1 1 1.6 1 1 1.3 1.1
3RW3045-1AB.. S3 75 3RV1041-4KA10 (57 - 75) A 1 0.8 1 0.9 0.5 1.1 1 1.6 1 1 1.3 1.1
3RW3046-1AB.. S3 100 3RV1041-4MA10 (80 - 100) A 1 0.75 1 0.85 0.55 1.1 1 1.6 1 1 1.2 1.1
Combination of a 3RV1 circuit breaker + 3RW30/31 soft starter:
8-23
3RW3 semiconductor motor control unit
3RW3 semiconductor motor control unit
8.3.3.3 Combining the 3RT contactor with the 3RU1 thermal overload relay and 3RW3 soft starter
Frame size of the The frame size selected for the overload relay should be large enough so
overload relay that it is just possible to set the current value calculated.
In the event of current values that are lower than can be set for the speci-
fied overload relay, the next smaller overload relay must be used.
Important
It is not permissible to mount the thermal overload relay under the contac-
tor/connecting lead/soft starter combination.
The overload relay must be integrated in the feeder before the contractor/
connecting lead/soft starter combination. The specified correction factors
apply only to this permissible mounting sequence.
Rail 1:
Combination of 3RT1 contac- 3RT 3RT
tor and 3RU1 thermal over-
load relay
3RU1
Connecting 3RW
lead
Rail 2:
3RW3 soft starter 3RW 3RU1
Minimum clearance For thermal reasons, a minimum clearance is necessary between the con-
tactor/overload relay combination and the soft starter, as is a minimum
length of the connecting leads.
The following table specifies the minimum clearances and minimum lengths
of the connecting leads for the various frame sizes:
S0 200 150
S2 240 200
S3 300 250
Table 8-9: 3RW3 installation guidelines, minimum clearances/lengths
Frame size
Order number
Order number
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
Correction factor
at an ambient temperature of 40 °C
Current setting of the circuit breaker
(7 - 10) A
3RW3.24-1AB.. S0 12.5 3RT1024-1A.. 3RU1126-1KBO (9-12.5)A 0.95 0.9 1 0.9 0.55 1 1 1.8 0.95 1 1.7 0.95
3RW3.25-1AB.. S0 16 3RT1025-1A.. 3RU1126-4ABO (11-16)A 0.95 0.9 1 0.9 0.55 1 1 1.8 0.95 1 1.7 0.95
3RW3.26-1AB.. S0 25 3RT1026-1A.. 3RU1126-4DBO (22-25)A 0.9 0.8 1 0.8 0.55 1 1 1.8 0.95 1 1.7 0.95
3RW3034-1AB.. S2 32 3RT1034-1A.. 3RU1136-4EBO (22-32)A 0.95 0.7 1 0.9 0.45 1 1 2.2 0.92 1 1.9 0.92
3RW3035-1AB.. S2 38 3RT1035-1A.. 3RU1136-4FBO (28-40)A 0.95 0.9 1 0.9 0.35 1 1 1.8 0.92 1 1.7 0.92
3RW3036-1AB.. S2 45 3RT1036-1A.. 3RU1136-4HBO (36-45)A 0.9 0.95 1 0.8 0.45 1 1 1.8 0.92 1 1.7 0.92
3RW3044-1AB.. S3 63 3RT1044-1A.. 3RU1146-4JBO (45-63) A 0.95 0.9 1 0.9 0.65 1 1 1.6 0.92 1 1.5 0.92
3RW3045-1AB.. S3 75 3RT1045-1A.. 3RU1146-4KBO (57-75) A 0.95 0.85 1 0.9 0.5 1 1 1.6 0.92 1 1.5 0.92
3RW3046-1AB.. S3 100 3RT1046-1A.. 3RU1146-1MBO (80-100) 0.9 0.8 1 0.8 0.55 1 1 1.6 0.92 1 1.5 0.92
A
Table 8-10: Correction factors, 3RT contactor + 3RU therm. overload relay + 3RW soft starter
1) = SIRIUS 3RW301 .. soft starters cannot be used with a fan.
Combination of the 3RT1 contactor with an attached 3RU1 thermal overload
8-25
3RW3 semiconductor motor control unit
3RW3 semiconductor motor control unit
8.3.3.4 Combining the 3RT contactor with the 3RB10 electronic overload relay and 3RW3 soft
starter
The contactor, electronic overload relay, and soft starter can be connected in
two ways:
• Combining a 3RT1 contactor with an attached 3 RB10 electronic overload
relay, a connecting lead, and a 3RW30/31 soft starter
• Combining a 3RT1 contactor with a connecting lead and a combination of
a 3RW30/01 soft starter with an attached 3RB10 electronic overload relay
3RB10
Connecting
lead
Rail 2:
3RW30/31 soft starter 3RW
Minimum clearance For thermal reasons, a minimum clearance is necessary between the con-
tactor/overload relay combination and the soft starter, as is a minimum
length of the connecting leads.
The following table specifies the minimum clearances and minimum lengths
of the connecting leads for the various frame sizes:
S0 200 150
S2 240 200
S3 300 250
Table 8-11: 3RT + 3RB10 + 3RW3 installation guidelines, minimum clearances/minimum lengths
Rail 2:
3RW
Combination of 3RW30/31 soft
starter and 3RB10 electronic
overload relay 3RB10
S0 140 150
S2 180 200
S3 240 250
Table 8-12: 3RT1 + 3RW30/31 + 3RB10 installation guidelines, minimum clearances/minimum
lengths
Correction factors: 3RT Combining a 3RT1 contactor with an attached 3RB10 electronic overload
+ 3RB10 + 3RW3 relay, a connecting lead, and a 3RW30/31 soft starter
Correction factor
Stand-alone installation Installed side by side Stand-alone installation Installed side by side
1)
1)
1
1
1
1
1
1
1
1
1
Set value of the el. overload relay
-
-
With fan
1.7
1.7
1.7
1.9
1.7
1.7
1.5
1.5
1.5
1)
1)
Correction factor for switching frequency
-
-
Correction factor
1)
1)
1
1
1
1
1
1
1
1
1
Rated current for the device
-
-
Correction factor
1)
1)
1
1
1
1
1
1
1
1
1
Current setting of the circuit breaker
-
-
With fan
2.2
1.8
1.8
1.8
1.8
1.8
1.6
1.6
1.6
1)
1)
Correction factor for switching frequency
-
-
Correction factor
1)
1)
1
1
1
1
1
1
1
1
1
Rated current for the device
-
-
Correction factor
1
1
1
1
1
1
1
1
1
1
1
Set value of the el. overload relay
Without fan
0.45
0.35
0.35
0.55
0.5
0.5
0.4
0.6
0.5
Correction factor for switching frequency
?
?
Correction factor
1
1
1
1
1
1
1
1
1
1
1
Rated current for the device
Correction factor
1
1
1
1
1
1
1
1
1
1
1
Set value of the el. overload relay
Without fan
0.95
0.95
0.85
0.85
0.75
0.65
0.85
0.85
0.85
0.75
0.8
Correction factor for switching frequency
Order number
of electronic overload relay
3RT1024-1A..
3RT1025-1A..
3RT1026-1A..
3RT1034-1A..
3RT1035-1A..
3RT1036-1A..
3RT1015-1A..
3RT1016-1A..
100
25
32
38
45
63
75
16
6
9
at an ambient temperature of 40 °C
S00
S00
Frame size
S0
S0
S0
S2
S2
S2
S3
S3
S3
3RW3034-1AB..
3RW3035-1AB..
3RW3036-1AB..
3RW3044-1AB..
3RW3045-1AB..
3RW3046-1AB..
3RW3014-1CB..
3RW3016-1CB..
3RW3.24-1AB..
3RW3.25-1AB..
3RW3.26-1AB..
Order number
Table 8-13: Correction factors, 3RT contactor + 3RB10 electronic overload relay + 3RW soft starter
L
N
L1 L2 L3 A2 A1
110...230V UC
14/23
T1 T2 T3 13 24
On Off
13
ON G1
14
STO
1
IN A1
A2
8.3.5 Commissioning
Every SIRIUS 3RW soft starter comes with the following warning, which it is
imperative to heed:
Caution
This device has been tested carefully at the factory and found to be in wor-
king order.
During transportation, however, it may have been subject to stresses over
which we have no control. The bypass relays in the main circuit may be in an
undefined state.
In the interests of complete safety, the following procedure should be used
at commissioning or after the replacement of the SIRIUS soft starter:
First, apply the supply voltage to A1/A2 in order to put the impulse series
relays in a defined switching state.
If you do not do this, the motor can be switched on inadvertently and cause
damage to people or parts of the system.
Settings
3RW30 3RW31
t R on t R1
uS uS
t R off t R2
Note
At commissioning, the settings of the potentiometers for the ramp time and
the starting voltage should remain unchanged. These set values must be
obtained in a trial.
Changing settings The potentiometer settings are scanned before each switching operation
("ON" or "OFF").
If, for example, the setting of the potentiometer for starting time is changed
while the motor is running up, the change does not come into effect until
the next start.
Starting voltage The starting voltage should be set to a value at which the motor starts rap-
idly.
Ramp time The ramp time should be set such that the motor can run up within the time
defined in this way.
If the star time for star-delta starting is known, the ramp time can be set to
this value.
Coasting-down time The potentiometer for the coasting-down time is for setting the duration of
the voltage ramp for coasting down. This parameter can be used to make
the motor run-down longer than it would be if the motor were merely to
coast to a stop.
The motor coasts to a stop on its own if this potentiometer is set to a value
of 0.
Switching frequency To prevent thermal overloading of the devices, the maximum permissible
switching frequency must be adhered to and the correction factor tables
must be used (see the installation guidelines in Section 8.3.2).
Starting time In order to obtain optimum operating conditions for the 3RW3 soft starter,
the setting for the starting time should be approx. 1 second longer than the
resultant motor run-up time, in order to ensure that the internal jumpering
contacts do not have to carry the starting current. This protects the internal
jumpering contacts and increases their service life. Longer starting times
increase the thermal load on the devices and the motor unnecessarily and
lead to a reduction in the permissible switching frequency.
1 L1 3 L2 5 L3 IN1 A1
A2 A1 1
3RW
5
5
10
10 0 20s
0 20s
min max
5
10
min max
5
0 20s
10
0 20s 13 14/23 24
2 T1 4 T2 6 T3 A2 2 T1 4 T2 6 T3
Figure 8-16: Position of the terminals and the potentiometers for adjustment
3RW31
The 3RW31 soft starters are available in frame size S0. Outwardly, they dif-
fer from the 3RW30 in the labeling of the contacts and the terminals:
• There is no BYPASSED auxiliary contact. The free contact is used to
enable the necessary drive contact IN2 to switch between the ramp
times tR1 and tR2.
• The 3RW31 does not have a coasting-down ramp. The potentiometer with
which the coasting-down time is adjusted on the 3RW30 is used here to
set the second ramp time tR2.
• There is no ON auxiliary contact.
Line length of the con- To eliminate problems with the cable coupler capacitances, the control cable
trol cable should be shorter than 15 m. (This is based on devices with a rated control
supply voltage of UC 24 V to 50 m.)
To eliminate problems in control cables that are fed out of the cubicle, cou-
pling links must be used.
Event messages
Diagnostics
Starting and coasting- The following timing diagram shows the switchover times when the device
down behavior is switched on/off:
L1-L2-L3
A1-A2
IN
Bypass
T1-T2-T3
UN
US
Switchover
Switchover delay
delay approx.
approx. 30
30 ms
ms
On-delay approx. 80 ms ON OFF
command command
ON
command
Supply interruption in If the load voltage is switched off in the bypassed state while the auxiliary
bypassed state supply continues to be applied at terminals A1/A2, the soft starter performs
a direct start of the motor after the load voltage is switched on again. To pre-
vent this, the "on" command must be removed in the event of the loss of the
main voltage.
The following graphic illustrates what happens when the supply is inter-
rupted in the bypassed state:
L1-L2-L3
A1-A2
IN
Bypass
T1-T2-T3
UN
Direct start
US
8.4 Accessories
The following accessories are available for the 3RW3 soft starters:
Control of the fan The fan is controlled by the control electronics of the soft starter.
It runs at the following times:
• When the fan is switched on: approx. 0.5 seconds after the bypass con-
tacts close (end-of-startup signal)
• When the fan is switched off: approx. 0.5 hours after the soft starter is
switched off
Attachment of the fan The fan is snapped into the recess provided on the underside of the soft
starter, and the plug-in cable is inserted in the corresponding connector. The
direction of installation is indicated on the fan by an arrow.
Additional parameter assignment is not necessary.
These fan modules mean that the starter can be installed in any position.
The only exception to this is when the fan cannot blow against the convec-
tion downward from above.
Terminal covers To provide additional finger protection, for frame sizes S2 and S3 the termi-
nal covers of the 3RT1 contactors of the same frame sizes can be used.
Installation on the soft starter is analogous to that on the contactors.
Link modules The same link modules are available for building fuseless feeders (soft
starter + 3RV circuit breaker) as are used for the 3RT contactor + 3RV circuit
breaker combinations.
Refer to the information and assignment tables in Section 8.3.2, "Installation
guidelines".
RC element If the 3RW30/31 soft starter is to be controlled from a PLC with a Triac or
thyristor output, malfunctioning can be avoided with an RC element. If there
is leakage current of more than 1 mA, without an RC element the soft
starter may interpret the drop in voltage that occurs at the input as an "ON"
command.
RC element
A2 A1 IN1
3RW30/31...
Snap-on attachment
The 3RW30 soft starters are snapped onto 35 mm rails in acc. with
DIN EN 50 022 without a tool.
The starter is placed on the upper edge of the rail and pressed downward
until it snaps onto the lower edge of the rail.
Frame sizes S00 and S0 can be removed just as easily: The starters are
pressed downward so that the tension of the attachment springs is loos-
ened, and the starters can be removed.
In the case of frame sizes S2 and S3, these attachment springs are released
by a lug on the underside of the starter that can be moved using a screw-
driver.
8.5.2 Connection
Screw-type terminals The 3RW3 electronic soft starters are available with the SIGUT‚ terminal sys-
tem and plus-minus POZIDRIV 2 screws.
Conductor cross-sec- The following table shows the permissible conductor cross-sections for the
tions 3RW30 electronic soft starters:
3RW301. 3RW302.
3RW303. 3RW304..
L1 L2 L3 3RW312.
L1 L2 L3 L1 L2 L3
A1/A2; NO/NC L1 L2 L3
min
0.8 to 1.2 Nm 2 to 2.5 Nm 3 to 4.5 Nm 22 4 to 6 Nm
∅ 5 ... 6 mm / 4
∅ 5 ... 6 mm / PZ2 7 to 10.3 lb.in 18 to 22 lb.in 27 to 40 lb.in 35 to 53 lb.in
PZ2
K1
OFF
A2 A1 1 IN1 A1
K1
ON
K1
A2
N (L-)
L3RW30
3RW302.
3RW303./3RW304
N (L-) L1 (L+)
F1
OFF
K1 3RT
A2 A1 1 3RV
3RU/3RB10
I>
3RW30 3RW30
13 14/23 24
ON
M M
3~ 3~
ON/OFF
Ramp 1 K1
ON/OFF
Ramp 2 K2
A2 A1 1 A2 A1 1
2 2
OFF
F1
F2
3RW31
F3
3RT K1 K2 3RT
ON K1 ON K2
Ramp 1 Ramp 2
3RU/3RB10 F2 F3 3RU/3RB10
K2 K1
K1 K2
M
3~
. /.P
Automatic operation Direct starting of the soft starter is possible as long as the auxiliary supply is
applied at terminals A1 and A2. To this end, a jumper is required between
the auxiliary supply contact A1 and the control contact IN.
The following must be taken into consideration:
• An on delay of up to 4 seconds can occur, depending on the frame size.
• Soft coasting down is no longer possible after the auxiliary supply is
switched off.
Control via PLC The 3RW3 soft starter can be controlled by means of a programmable con-
troller (PLC). It is connected up in the same way as for control via switch.
Important
Always ensure that A1 and A2 are connected up correctly. Although polarity
reversal cannot damage the device, it can lead to malfunctioning.
Control of a motor with An electromechanical brake with infeed from the main voltage (L1/L2/L3)
an electromechanical should not be connected directly to the output of the soft starter. An electro-
brake mechanical brake should be controlled by means of a separate contactor (K1
in the circuit diagram below):
L1
L2 Ue
L3
Q1
L+
I>> I>> I>> L- Us
F
K1 STO
L1 L2 L3 A2 A1 IN
G1 ON BYPASSED
3RW30
AN
T1 T2 T3 13 23 24
14
A1
K1 BR BR2 U V W K1
M A2
3k
g
k 5 f 5
i j a e d m
h
b n
c
mm a b c d e f g h i j k l m n
3RW301. 97.5 45 93 95 66 51 -- 7.5 76 -- 86 -- 90 35
3RW302./3RW312. 125 45 119 125 81 63 96 7 101 63 14 7 115 35
3RW303. 160 55 143 141 95 63 115 8 119 77 18 7 150 30
3RW304. 170 70 183 162 108 87 156 8 132 87 22.5 7 160 60
Control electronics
Type 3RW3. ..-1.B0. 3RW3. ..-1.B1.
Rated control supply voltage V UC 24 UC 110 to 230
Rated control supply current mA Approx. 50 Approx. 25 to
20
Rated frequency at AC Hz 50/60 ± 10%
Power electronics
Type 3RW3. ..-1.B.4 3RW3. ..-1.B.5 3RW30 ..-
1AA12
Voltage operating range V 200 AC to 460 AC, three-phase 460 AC to 575 AC, three phase 115 AC to
(± 10%) (± 10% - 15%) 240 AC, single-
phase
(±10%)
Rated frequency Hz 50/60 ± 10%
Permissible site altitude Reduction of IE
Up to 1000 m above sea level 100%
Up to 2000 m above sea level 92%
Up to 3000 m above sea level 85%
Up to 4000 m ab. sea level1) 78%
Installation position Without additional fan The soft starters are designed for operation when mounted in a vertical position.
With additional fan 3) Any installation position (except vertical rotated by 180 °)
Type 3RW30 1. 3RW3. 2. 3RW30 3. 3RW30 4.
Frame size S00 S0 S2 S3
Continuous operation (% of Ie) % 100
Minimum load2) (% of Ie); At 40 °C % 4
Permissible ambient temperature °C –25 to +60 (derating as of 40 °C, see below)
Switching capacity of the auxiliary 230 V/AC-15 A 4) 3 3 3
contacts 230 V/DC-13 A 4) 0.1 0.1 0.1
24 V/DC-13 A 4) 1 1 1
Type 3RW30 14 3RW30 16 3RW30 24 3RW30 25 3RW30 26
Current-carrying capacity
Rated operational current Ie
in acc. with IEC At 40/50/60 °C, AC-53b A 6/5/4 9/8/7 12.5/11/9 16/14/12 25/21/18
Rated operational current Ie
in acc. with UL/CSA At 40/50/60 °C, AC-53b A 4.8/4.8/4 7.8/7.8/7 11/11/9 17.5/14/12 25/21/18
Power loss at continuous rated operational current (40 °C) approx. W 5 7 7 9 13
Power loss when the max. switching frequency is exploited W 5 6 7 8 9
Permissible starts per hour without the use of a fan
Given intermittent duty S4, Tu = 40 °C 1/h 60 40 30 12
Duty cycle = 30%; stand-alone installation % 250 x Ie, 2 s 300 x Ie, 2 s
Permissible starts per hour with the use of a fan
Given intermittent duty S4, Tu = 40 °C 1/h –3) 54 21
Duty cycle = 30%; stand-alone installation
Idle time after continuous opera- s 0 200
tion
With Ie before a new start
Degree of protection In acc. with IEC 60 529 IP 20 (terminal housing IP 00)
Conductor cross-sections
Screw-type terminals Auxiliary conductors:
(1 or 2 conductors connectable) Single-core mm2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) in acc. with IEC 60 947; max. 2 x (0.75 to 4)
for standard screwdrivers Finely stranded with wire end mm2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5)
ferrule
size 2 and Pozidriv 2
AWG cables, AWG 2 x (18 to 14)
single- or multi-core M 3, PZ2
- Terminal screws Nm 0.8 to 1.0 0.8 to 1.0
- Tightening torque lb.in 7.1 to 8.9 7.1 to 8.9
Main conductors:
Single-core mm2 2 x (0.5 to 1.5); 2 x (1 to 2.5)
2 x (0.75 to 2.5) 2 x (2.5 to 6)
Finely stranded with wire end mm2 2 x (0.5 to 2.5) 2 x (1 to 2.5)
ferrule 2 x (2.5 to 6)
Multi-core mm2 – –
Type 3RW30 14 3RW30 16 3RW30 24 3RW30 25 3RW30 26
AWG cables,
single- or multi-core AWG 2 x (18 to 14) 2 x (14 to 10)
- Terminal screws M 3, PZ2 M 4, PZ2
- Tightening torque Nm 0.8 to 1.2 2 to 2.2
lb.in 7 to 10.3 18 to 22
1)Over 4000 m on request
2)The rated current for the motor (specified on the motor's type plate) should amount at least to the specified percentage of the SIRIUS soft
starter's device rated current Ie.
3)In the case of frame size S00, it is not possible to install the fan provided as an accessory.
4)Frame size S00 does not have any auxiliary contacts.
Power electronics
Type 3RW30 34 3RW30 35 3RW30 36 3RW30 44 3RW30 45 3RW30 46
Current-carrying capacity
Rated operational current Ie
in acc. with IEC At 40/50/60 °C, AC-53b A 32/27/23 38/32/27 45/38/32 63/54/46 75/64/54 100/85/72
Rated operational current Ie
in acc. with UL/CSA At 40/50/60 °C, AC-53b A 27/27/23 34/32/27 42/38/32 62/54/46 68/64/54 99/85/72
Power loss at continuous rated operational current (40 °C) approx. W 10 13 17 13 16 26
Permissible starts per hour
Given interm. duty S4, Tu = 40 °C 1/h 20 15 5 20 30 15
Duty cycle = 30% % 300 x Ie, 3 s 300 x Ie, 4s
Permissible starts per hour with the use of a fan
Given interm. duty S4, Tu = 40 °C 1/h 44 27 9 32 48 24
Duty cycle = 30%; stand-alone installation
Idle time after cont. operation s 0 400 0
with Ie before a new start
Degree of protection In acc. with IEC 60 529 IP 20 (terminal housing IP 00) IP 201)
Conductor cross-sections
Screw-type terminals Auxiliary conductors:
(1 or 2 conductors connectable) Single-core mm2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) in acc. with IEC 60 947; max. 2 x (0.75 to 4)
for standard screwdrivers Finely stranded with wire mm2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5)
end ferrule
size 2 and Pozidriv 2 AWG cables,
single- or multi-core AWG 2 x (18 to 14)
- Terminal screws M3
- Tightening torque Nm 0.8 to 1.0
lb.in 7.1 to 8.9
Main conductors:
Single-core mm2 2 x (0.75 to 16)
Finely stranded with wire mm2 2 x (0.75 to 16)
end ferrule 1 x (0.75 to 25)
General specifications
Standard Parameters
EMC noise immunity
Electrostatic discharge (ESD) IEC 1000-4-2, Severity 3: 6/8 kV
El. magn. RF fields IEC 1000-4-3 Frequency range: 80 to 1000 MHz with 80% at 1 kHz
Severity 3, 10 V/m
Conducted RF disturbance IEC 61000-4-6 Frequency range: 80 MHz to 1000 MHz with 80 %
EN 60 947-4-2 at 1 kHz
SN-IACS 10 V at 0.15 MHz to 80 MHz
3 V at 10 kHz to 80 MHz
Burst IEC 1000-4-4 Severity 3: 1/2 kV
Surge IEC 1000-4-5 Severity 3: 1/2 kV
EMC emitted interference
EMC radio interference intensity CISPR 11/09.1990 Limit value of class B at 30 MHz to 1000 MHz
Radio interference voltage CISPR 11/09.1990 (0.15 MHz to 30 MHz): device class A (industry)
EN 60 947-4-2
1) IP 20 only with attached box terminal (delivery state). Without box terminal IP 00.
2) Device class B (public power supply networks) is complied with only in the case of variants 3RW3.-1AB0. with control supply voltage UC
of 24 V. For the 3RW3.-1A.1. variants with a control supply voltage UC of 110 V to 230 V, single-stage filters (e.g. type B84143-A...) must be
connected upstream.
IEC 60947-4-1/DIN VDE 0660 Part 102 draws a distinction between two
coordination types, known as coordination type 1 and coordination type 2. In
both coordination types, the short circuit to be dealt with is reliably discon-
nected. The differences lie only in the degree to which the device is dam-
aged after a short circuit.
Coordination type 1 The motor feeder can be operable after each short-circuit disconnection.
Damage to the soft starter is possible. The circuit breaker itself always
attains coordination type 1.
Coordination type 2 After a short-circuit event there must be no damage to the soft starter or
any other switching device; only the backup fuse may be destroyed. The
actual motor feeder can be put into operation again immediately once the
short circuit fuse has been replaced.
Maximum short-circuit All the specified fuse configurations are designed for a maximum short-cir-
current cuit current of 50 kA. This ensures that short circuits of 50 kA can be dis-
connected without posing a threat to persons or the system.
Motor feeder: To set up a motor feeder of coordination type 2, the feeder must be fused
coordination type 2 (i.e. the motor must be provided with overload protection).
The following can be used:
• The 3NE1 all-range fuse, which unifies line protection and semiconductor
protection
• The 3NE8 semiconductor protection fuse, in which case additional protec-
tion must be provided for the line
Comparison of coordi- The configuration variant on the basis of coordination type 2 is associated
nation types 1 and 2 with higher costs than that of coordination type 1, which is why the fuseless
configuration (coordination type 1) is recommended. The advantages are:
• Fewer components in the cubicle
• Less effort required for wiring
• Less cubicle space required
• Lower price
Fuse configurations The following table specifies the fuse configuration (coordination type 2) for
with SITOR 3NE1..-0 3RW30/31 with SITOR fuses 3NE1..-0 (short-circuit and line protection);
max. short-circuit current 50 kA:
Fuse configurations The following table specifies the fuse configuration (coordination type 2) for
with SITOR 3NE8 3RW30/31 with SITOR fuses 3NE8 (semiconductor protection is provided by
the fuse; line protection and overload protection are provided by the circuit
breaker); max. short-circuit current 50 kA/400 V:
Order
Order Rated cur- Frame
Order number number Link module
number rent of the size of
Soft starter of the circuit 3RW - 3RV
of the fuse fuse the fuse
breaker2)
MLFB MLFB A Size MLFB MLFB3)
3RW3014 3NE8003 35 00 3RV1011 3RA1911-1A
3RW3016 3NE8003 35 00 3RV1011 3RA1911-1A
3RW3024/3RW3124 3NE8003 35 00 3RV1021 3RA1921-1A
3RW3025/3RW3125 3NE8003 35 00 3RV1021 3RA1921-1A
1)
3RW3026/3RW3126 -- -- -- -- --
3RW3034 3NE8022 125 00 3RV1031 3RA1931-1A
3RW3035 3NE8024 160 00 3RV1031 3RA1931-1A
3RW3036 3NE8024 160 00 3RV1031 3RA1931-1A
3RW3044 3NE8024 160 00 3RV1041 3RA1941-1A
3RW3045 3NE8024 160 00 3RV1041 3RA1941-1A
3RW3046 3NE8024 160 00 3RV1041 3RA1941-1A
Table 8-19: Fuse configurations (SITOR)
Fuseless configuration The following table specifies the components of the fuseless configuration
(coordination type 1) for 3RW30/31; short-circuit current of 50 kA/400 V:
Order number
Order number
of the circuit Link module
of the soft starter
breaker1)
MLFB MLFB MLFB3)
3RW3014 3RV10112) 3RA1911-1A
3RW3016 3RV10112) 3RA1911-1A
3RW3024/3RW3124 3RV1021 3RA1921-1A
3RW3025/3RW3125 3RV1021 3RA1921-1A
3RW3026/3RW3126 3RV1021 3RA1921-1A
3RW3034 3RV1031 3RA1931-1A
3RW3035 3RV1031 3RA1931-1A
3RW3036 3RV1031 3RA1931-1A
3RW3044 3RV1041 3RA1941-1A
3RW3045 3RV1041 3RA1941-1A
3RW3046 3RV1041 3RA1941-1A
Table 8-20: Motor feeder: fuseless configuration
1) The selection and setting of the circuit breaker is based on the rated cur-
rent for the motor
2) 50 mm clearance is required above and below between the 3RW and
grounded parts
3) Note the unit of quantity
Fused configuration The following table specifies the components of the fused configuration
(coordination type 1) for 3RW30/31; short-circuit current of 50 kA/400 V:
Order
Order number Order
Order number Order Fuse rated number
of the therm. number
of the soft number current/ of the elec-
overload of the
starter of the fuse frame size 1) tron. over-
relay contactor
load relay1)
MLFB MLFB A / size MLFB MLFB MLFB
3RW3014 3NA3810 25 / 00 3RU1116 2)4) 3RB10162)4) 3RT1015
3RW3016 3NA3810 25 / 00 3RU1116 2)4) 3RB10162)4) 3RT1016
3RW3024/
3NA3822 63 / 00 3RU11263) 3RB10263) 3RT1024
3RW3124
3RW3025/
3NA3822 63 / 00 3RU11263) 3RB10263) 3RT1025
3RW3125
3RW3026/
3NA3824 80 / 00 3RU11263) 3RB10263) 3RT1026
3RW3126
3RW3034 3NA3830 100 / 00 3RU11363) 3RT1034
3)
3RW3035 3NA3830 100 / 00 3RU1136 3RT1035
3RW3036 3NA3830 100 / 00 3RU11363) 3RT1036
3)
3RW3044 3NA3144 250 / 1 3RU1146 3RT1044
3RW3045 3NA3144 250 / 1 3RU11463) 3RT1045
3)
3RW3046 3NA3144 250 / 1 3RU1146 3RT1046
Table 8-21: Motor feeder: fused configuration
1) The selection and setting of the overload relay is based on the rated cur-
rent for the motor
2) Short-circuit current of 50 kA to max. 400 V
3) Short-circuit current of 50 kA to max. 500 V
4) 50 mm clearance is required above and below between the 3RW and
grounded parts
Reductions as a func- The diagram below plots the reductions in rated current and rated operating
tion of site altitude voltage as a function of site altitude:
105
100 Ue reduction
95 Ie reduction
90
85
80
75
70
0 500 1000 1500 2000 2500 3000 3500 4000
Site altitude in m
Figure 8-25: Reductions as a function of site altitude
Ambient temperature = 40 °C
230 V 400 V Ie Order number 500 V Ie Order number
Pe in kW Pe in kW In A MLFB Pe in kW In A MLFB
1.5 3 6 3RW3014-1CB.4 - - -
2.2 4 9 3RW3016-1CB.4 - - -
3 5.5 12.5 3RW3024-1AB.4 7.5 12.5 3RW3024-1AB.5
4 7.5 16 3RW3025-1AB.4 7.5 16 3RW3025-1AB.5
5.5 11 25 3RW3026-1AB.4 15 25 3RW3026-1AB.5
7.5 15 32 3RW3034-1AB.4 18.5 32 3RW3034-1AB.5
11 18.5 38 3RW3035-1AB.4 22 38 3RW3035-1AB.5
11 22 45 3RW3036-1AB.4 30 45 3RW3036-1AB.5
19 30 63 3RW3044-1AB.4 37 63 3RW3044-1AB.5
22 37 75 3RW3045-1AB.4 45 75 3RW3045-1AB.5
30 55 100 3RW3046-1AB.4 70 100 3RW3046-1AB.5
Table 8-22: 3RW3 motor ratings in acc. with IEC at 40° C
Ambient temperature = 50 °C
230 V 400V Ie Order number 500 V Ie Order number
Pe in kW Pe in kW In A MLFB Pe in kW In A MLFB
1.1 2.2 5 3RW3014-1CB.4 - - -
1.5 4 8 3RW3016-1CB.4 - - -
3 5.5 11 3RW3024-1AB.4 5.5 11 3RW3024-1AB.5
4 5-5 14 3RW3025-1AB.4 7.5 14 3RW3025-1AB.5
5.5 11 21 3RW3026-1AB.4 11 21 3RW3026-1AB.5
7.5 11 27 3RW3034-1AB.4 15 27 3RW3034-1AB.5
7.5 15 32 3RW3035-1AB.4 18.5 32 3RW3035-1AB.5
11 18.5 38 3RW3036-1AB.4 22 38 3RW3036-1AB.5
15 22 54 3RW3044-1AB.4 30 54 3RW3044-1AB.5
18.5 30 64 3RW3045-1AB.4 37 64 3RW3045-1AB.5
22 45 85 3RW3046-1AB-4 55 85 3RW3046-1AB.5
Table 8-23: 3RW3 motor ratings in acc. with IEC at 50° C
Ambient temperature = 60 °C
230 V 400 V Ie Order number 500 V Ie Order number
Pe in kW Pe in kW In A MLFB Pe in kW In A MLFB
0.75 1.5 4 3RW3014-1CB.4 - - -
1.5 3 7 3RW3016-1CB.4 - - -
2.2 4 9 3RW3024-1AB.4 5.5 9 3RW3024-1AB.5
3 5.5 12 3RW3025-1AB.4 7.5 12 3RW3025-1AB.5
4 7.5 18 3RW3026-1AB.4 11 18 3RW3026-1AB.5
5.5 11 23 3RW3034-1AB.4 15 23 3RW3034-1AB.5
7.5 11 27 3RW3035-1AB.4 15 27 3RW3035-1AB.5
7.5 15 32 3RW3036-1AB.4 18.45 32 3RW3036-1AB.5
11 22 46 3RW3044-1AB.4 30 46 3RW3044-1AB.5
15 22 54 3RW3045-1AB.4 30 54 3RW3045-1AB.5
18.5 37 72 3RW3046-1AB.4 45 72 3RW3046-1AB.5
Table 8-24: 3RW3 motor ratings in acc. with IEC at 60° C
Ambient temperature = 40 °C
200V 230 V 460V Ie Order number 460V 575V Ie Order number
Pe in hp Pe in hp Pe in hp In A MLFB Pe in hp Pe in hp In A MLFB
1 1 3 4.8 3RW3014-1CB.4 - - - -
2 2 5 7.8 3RW3016-1CB.4 - - - -
3 3 7.5 11 3RW3024-1AB.4 7.5 10 11 3RW3024-1AB.5
5 5 10 17.5 3RW3025-1AB.4 10 15 17.5 3RW3025-1AB.5
7.5 7.5 15 25.3 3RW3026-1AB.4 15 20 25.3 3RW3026-1AB.5
7.5 7.5 20 27 3RW3034-1AB.4 20 25 27 3RW3034-1AB.5
10 10 25 34 3RW3035-1AB.4 25 30 34 3RW3035-1AB.5
10 15 30 42 3RW3036-1AB.4 30 40 42 3RW3036-1AB.5
20 20 40 62.1 3RW3044-1AB.4 40 60 62.1 3RW3044-1AB.5
20 25 50 68 3RW3045-1AB.4 50 60 68 3RW3045-1AB.5
30 30 75 99 3RW3046-1AB.4 75 100 99 3RW3046-1AB.5
Table 8-25: 3RW3 motor ratings in acc. with NEMA at 40° C
Ambient temperature = 50 °C
200V 230 V 460V Ie Order number 460V 575V Ie Order number
Pe in hp Pe in hp Pe in hp In A MLFB Pe in hp Pe in hp In A MLFB
1 1 3 4.8 3RW3014-1CB.4 - - - -
2 2 5 7.8 3RW3016-1CB.4 - - - -
3 3 7.5 11 3RW3024-1AB.4 7.5 10 11 3RW3024-1AB.5
3 3 10 14 3RW3025-1AB.4 10 10 14 3RW3025-1AB.5
5 5 15 21 3RW3026-1AB.4 15 15 21 3RW3026-1AB.5
7.5 7.5 20 27 3RW3034-1AB.4 20 25 27 3RW3034-1AB.5
7.5 10 20 32 3RW3035-1AB.4 20 30 32 3RW3035-1AB.5
10 10 25 38 3RW3036-1AB.4 25 30 38 3RW3036-1AB.5
15 20 40 54 3RW3044-1AB.4 40 50 54 3RW3044-1AB.5
20 20 40 64 3RW3045-1AB.4 40 60 64 3RW3045-1AB.5
25 30 60 85 3RW3046-1AB.4 60 75 85 3RW3046-1AB.5
Table 8-26: 3RW3 motor ratings in acc. with NEMA at 50° C
Ambient temperature = 60 °C
200 V 230 V 460 V Ie Order number 460 V 575 V Ie Order number
Pe in hp Pe in hp Pe in hp In A MLFB Pe in hp Pe in hp In A MLFB
0.75 0.75 2 4 3RW3014-1CB.4 - - - -
1.5 1.5 3 7 3RW3016-1CB.4 - - - -
2 2 5 9 3RW3024-1AB.4 5 7.5 9 3RW3024-1AB.5
3 3 7.5 12 3RW3025-1AB-4 7.5 10 12 3RW3025-1AB.5
5 5 10 18 3RW3026-1AB.4 10 15 18 3RW3026-1AB.5
5 7.5 15 23 3RW3034-1AB.4 15 20 23 3RW3034-1AB.5
7.5 7.5 20 27 3RW3035-1AB.4 20 25 27 3RW3035-1AB.5
7.5 10 20 32 3RW3036-1AB.4 20 30 32 3RW3036-1AB.5
10 15 30 46 3RW3044-1AB.4 30 40 46 3RW3044-1AB.5
15 20 40 54 3RW3045-1AB.4 40 50 54 3RW3045-1AB.5
20 25 50 72 3RW3046-1AB.4 50 60 72 3RW3046-1AB.5
Table 8-27: 3RW3 motor ratings in acc. with NEMA at 60° C
T
Technical specifications 2-58, 4-37, 8-41
Terminal covers 3-84, 8-13
Terminals for contactor coils 3-44
Thermal overload release 2-11, 2-13
Thermistor detector 4-19
Thermistor motor protection 4-12
Three-phase current asynchronous motors 8-6
Three-phase induction motors 2-13
Three-pole load 2-11
Time ranges 7-16
Time-current characteristics 2-3, 4-17, 4-18, 4-21
Time-delayed overload release 4-2
Timing diagram 8-33
Transformer protection 2-13
Tripping characteristic 4-18