NFPA Diamond
NFPA Diamond
NFPA Diamond
"NFPA 704: Standard System for the Identification of the Hazards of Materials for
Emergency Response" is a standard maintained by the U.S.-based National Fire
Protection Association. First "tentatively adopted as a guide" in 1960, [1] and revised
several times since then, it defines the colloquial "Safety Square" or "Fire Diamond"
which is used by emergency personnel to quickly and easily identify the risks posed by
hazardous materials. This helps determine what, if any, special equipment should be
used, procedures followed, or precautions taken during the initial stages of an emergency
response. It is an internationally accepted safety standard, and is crucial while
transporting chemicals.
Contents
1Codes
2History
3See also
4References
5External links
Codes[edit]
Flammability (red)
Materials that will not burn under typical fire conditions (e.g. carbon tetrachloride), including intrinsically noncombustible materials such as concrete, stone, and sand.
0 in air unless exposed to a temperature of 820 °C (1,500 °F) for more than 5 minutes.
Materials that require considerable preheating, under all ambient temperature conditions, before ignition and combustion can occur (e.g. mineral oil, ammonia). Includ
1 suspended solids that do not require heating before ignition can occur. Flash point at or above 93.3 °C (200 °F).
Must be moderately heated or exposed to relatively high ambient temperature before ignition can occur (e.g. diesel fuel, paper, sulfur and multiple finely divided suspe
2 require heating before ignition can occur). Flash point between 37.8 and 93.3 °C (100 and 200 °F).
Liquids and solids (including finely divided suspended solids) that can be ignited under almost all ambient temperature conditions (e.g. gasoline, acetone). Liquids hav
3 22.8 °C (73 °F) and having a boiling point at or above 37.8 °C (100 °F) or having a flash point between 22.8 and 37.8 °C (73 and 100 °F).
Will rapidly or completely vaporize at normal atmospheric pressure and temperature, or is readily dispersed in air and will burn readily (e.g. acetylene, propane, hydrog
4 Includes pyrophoric substances. Flash point below room temperature at 22.8 °C (73 °F).
Health (blue)
0 Poses no health hazard, no precautions necessary and would offer no hazard beyond that of ordinary combustible materials (e.g. wood, paper)
1 Exposure would cause irritation with only minor residual injury (e.g. acetone, sodium bromate, potassium chloride)
2 Intense or continued but not chronic exposure could cause temporary incapacitation or possible residual injury (e.g. diethyl ether, ammonium phosphate, carbon dioxid
Short exposure could cause serious temporary or moderate residual injury (e.g. liquid hydrogen, sulfuric acid, calcium hypochlorite, carbon monoxide, hexafluorosilici
3 chloride, sodium hydroxide)
4 Very short exposure could cause death or major residual injury (e.g. hydrogen cyanide, phosgene, diborane, methyl isocyanate, hydrofluoric acid)
Instability–reactivity (yellow)
0 Normally stable, even under fire exposure conditions, and is not reactive with water (e.g. helium, N2)
1 Normally stable, but can become unstable at elevated temperatures and pressures (e.g. propene)
2 Undergoes violent chemical change at elevated temperatures and pressures, reacts violently with water, or may form explosive mixtures with water (e.g. white phospho
Capable of detonation or explosive decomposition but requires a strong initiating source, must be heated under confinement before initiation, reacts explosively with w
3 severely shocked (e.g. ammonium nitrate, caesium, hydrogen peroxide)
4 Readily capable of detonation or explosive decomposition at normal temperatures and pressures (e.g. nitroglycerin, chlorine dioxide, nitrogen triiodide, manganese hep
The white "special notice" area can contain several symbols. The following symbols are defined by the NFPA 704 standard.
O
Oxidizer, allows chemicals to burn without an air supply (e.g. potassium perchlorate, ammonium nitrate, hydrogen peroxide).
X
Simple asphyxiant gas (specifically helium, nitrogen, neon, argon, krypton, xenon). The SA symbol shall also be used for liquefied carbon dioxide vapor withdrawa
SA quantities of dry ice are used in confined areas.[2]
These hazard codes are not part of the NFPA 704 standard, but are occasionally used in an unofficial manner. The use of non-standard codes may be permitted, required or
authority having jurisdiction (e.g. fire department).
ACID
Acid or alkaline, to be more specific
ALK
BIO
Biological hazard (e.g. flu virus, rabies virus)
POI Poisonous (e.g. strychnine, alpha-amanitin)
RA
Radioactive (e.g. plutonium, cobalt-60, carbon-14)
RAD
CRYO
History[edit]
The development of NFPA 704 is credited to the Charlotte Fire Department after a fire at the Charlotte Chemical
Company in 1959 led to severe injuries to many of the firefighters. [3][4] Upon arrival, the fire crew found a fire burning inside
a vat that firefighters assumed to be burning kerosene. The crew tried to suppress the fire, which resulted in the vat
exploding due to metallic sodium being stored in the kerosene. Thirteen firefighters were injured, including several of
whom had critical injuries and one who lost both ears and most of his face from the incident.
At the time, such vats were not labelled with the materials they contained, so firefighters didn't have the necessary
information to recognize that hazardous materials were present, which required a specific response. In this case, sodium
was able to react with water to release hydrogen gas and large amounts of heat, which has the potential to explode.
The Charlotte Fire Department developed training to respond to fires involving hazardous materials, ensured that
protective clothing was available to those responding, and expanded the fire prevention inspection program. Fire Marshal
J. F. Morris developed the diamond shaped placard as a marking system to indicate when a building contained hazardous
materials, with their levels of flammability, reactivity and health effects. [5]