Sepam Series 80 Configuration: Electrical Network Protection
Sepam Series 80 Configuration: Electrical Network Protection
Sepam series 80
Configuration
Sepam label: ......................................................................................................................................................................................... DG-1 SGPL Application type: G87 Model: Integrated UMI
MES120 (14 input + 6 output module) n°1 .......................................................................................................................................... Present
MES120 (14 input + 6 output module) n°2 .......................................................................................................................................... Absent
MES120 (14 input + 6 output module) n°3 .......................................................................................................................................... Absent
MSA141 (1 analog output module) ...................................................................................................................................................... Absent
MET148 (8 temperature sensors module) n°1 .................................................................................................................................... Absent
MET148 (8 temperature sensors module) n°2 .................................................................................................................................... Absent
ACE 949/959/937 (communication network interface) n°1 ................................................................................................................. Present Communication protocol Modbus Sepam address 6
Speed 9600 Bauds Parity None
Unsecured
COM2 module ....................................................................................................................................................................................... Absent
ACE 850 (communication network interface) (Ethernet) ................................................................................................................... Absent
Memory Cartridge Type: ...................................................................................................................................................................... MMS
MCS025 (Synchro-check module) ....................................................................................................................................................... Absent
Generator speed
Rated speed (Rpm) 1500 rpm Zero speed threshold 5%
Pulses per rotation 1 Rated active Power 17.819 MW
Total inertia
Moment (J) 10000 kg.m2
Constant (H) 51.802 sec
Reactance
Synchronous reactance (Xd) 200 %
Synchronous reactance (Xq) 120 %
Transient react ance (X'd) 20 %
Description Setting
Switchgear control Circuit breaker
Closing with synchro-check No
Closing request time 200 ms
Synchro confirmation time 0 ms
Logic discrimination No
Logic discrimination Acceleration No
Automatic transfer No
Voltage return time 3s
Normal coupling position Normally open
Genset shutdown No
Time delay 0 ms
De-excitation No
Time delay 0 ms
Unlock logic discrimination time 200 ms
On Latching Trip C.B . On Latching Trip C.B . On Latching Trip C.B. On Latching Trip C.B.
50/51 - 1 X X X 46 - 2 X X X 32Q - 1 X X X 59 - 1 X X X
50/51 - 2 X X X 49RMS - 1 X X X 50V/51V - 1 X X X 59N - 1 X X X
50N/51N - 1 X X X 87M - 1 X X X 21B - 1 X X 47 - 1 X X X
50N/51N - 2 X X X 67N - 1 X X X 27R - 1 X X 81H - 1 X X X
46 - 1 X X X 32P - 1 X X X 27 - 1 X X X 81L - 1 X X X
1 2
I/Is 1.00 10.00
T(s) 1.00 1.00
Measurement Settings
Unit Activity Latching Trip C.B. Confirmation Group
origin Tripping curve Threshold Delay Icc min. H2 Timer hold curve Timer hold
A Standard inverse time 121 A 100 ms 6.3 kA Off Definite time 0 ms
1 On X X I1,I2,I3 No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 150 A 1s 6.3 kA Off Definite time 0 ms
2 On X X I1,I2,I3 No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
3 Off I1,I2,I3 No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
4 Off I1,I2,I3 No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
Restraint H2 threshold : 17
Restraint H2 threshold : 17
Measurement Settings
Unit Activity Latching Trip C.B. Group
origin Tripping curve Threshold Delay Timer hold curve Timer hold H2 rest.
A Standard inverse time 40 A 3s Definite time 0 ms
1 On X X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 120 A 1s Definite time 0 ms
2 On X X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Standard inverse time 40 A 3s Definite time 0 ms
3 Off Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
4 Off Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
5 Off Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
6 Off Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
7 Off Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
8 Off Io sum
B Definite time 630 A 100 ms Definite time 0 ms
Settings
Unit Activity Latching Use closed
Is threshold Delay position of CB
Settings
Unit Activity Latching Trip C.B. Trip C.B.
Tripping curve Threshold Delay
1 On X X I1,I2,I3 Definite time 30 %Ib 3s
2 On X X I1,I2,I3 Definite time 35 %Ib 4s
Measurement
Unit Activity Latching Trip C.B.
origin
1 On X X I1,I2,I3
Settings
Unit Activity Latching Trip C.B. Restraint on
Is threshold sensor loss
1 On X X 25 A X
Settings
Unit Activity Latching Trip C.B. Group Curve Delay
Tripping curve Is threshold Delay Angle Direction hold hold Tripping logic
A Definite time 1.26 kA 100 ms 45° Line Definite time 0 ms One out of three
1 Off
B Definite time 1.26 kA 100 ms 45° Line Definite time 0 ms One out of three
A Definite time 1.26 kA 100 ms 45° Line Definite time 0 ms One out of three
2 Off
B Definite time 1.26 kA 100 ms 45° Line Definite time 0 ms One out of three
Settings
Measurement
Unit Activity Latching Trip C.B. Type Group Curve Delay
origin Tripping curve Iso threshold Delay Angle Voltage Threshold Direction hold hold
A Definite time 40 A 100 ms 0° 2 %Unp Line Definite time 0 ms
1 On X X Io sum Type2
B Definite time 1.26 kA 100 ms 0° 2 %Unp Line Definite time 0 ms
A Definite time 50 A 100 ms 0° 2 %Unp Line Definite time 0 ms
2 Off Io sum Type2
B Definite time 1.26 kA 100 ms 0° 2 %Unp Line Definite time 0 ms
Settings
Unit Activity Latching Trip C.B.
Type Power threshold Delay
1 On X X Reverse power 160 kW 10 s
2 Off Reverse power 160 kW 3s
Settings
Unit Activity Latching Trip C.B.
Type Power threshold Delay
1 On X X Reverse power 200 kVAR 10 s
Settings
Unit Activity Latching Trip C.B.
Xa (Common point of the 2 circles) Xb (Circle1 definition point) Xc (Circle2 definition point) Circle1 time delay Circle2 time delay
1 Off 2.5 Ohm 20.8 Ohm 42.8 Ohm 70 ms 500 ms
Settings
Unit Activity Latching Trip C.B.
Protection principle(s) Delay Nb. of rotations Max. time between 2 swings
1 Off Areas and power swings 700 ms 2 rotation(s) 10 seconds
Settings
Unit Activity Latch Trip C.B .
Speed threshold Time delay T
1 Off 106 %rated speed 3s
2 Off 110 %rated speed 1s
Settings
Unit Activity Latch Trip C.B .
Speed threshold Time delay T
1 Off 95 %rated speed 3s
2 Off 20 %rated speed 1s
Measurement Settings
Unit Activity Latching Trip C.B.
origin Tripping curve Threshold Delay Timer hold curve Timer hold
1 On X X I1,I2,I3 Standard inverse time 175 A 3s Definite time 0 ms
2 Off I1,I2,I3 Definite time 1.26 kA 100 ms Definite time 0 ms
Settings
Unit Activity Latching Trip C.B.
Zs Delay
1 On X 6 Ohm 750 ms
Settings
Unit Activity Latching Trip C.B.
Current threshold Voltage threshold Time delay T1 Time delay T2 C.B. position
1 Off X 63 A 80 %Unp 5s 250 ms
Settings
Unit Activity Latching Trip C.B.
Threshold type K Delay
1 Off Adaptive 0.15 5s
2 Off Adaptive 0.15 5s
Settings
Unit Activity Latching Trip C.B.
Machine coupling Tripping curve Threshold Delay
1 Off Delta Definite time 1.1 pu 60 s
2 Off Delta Definite time 1.1 pu 60 s
Measurement Settings
Unit Activity Latching Trip C.B.
origin Voltage threshold Delay
1 Off V1,V2,V3 / U21,U32 30 %Unp 100 ms
2 Off X V1,V2,V3 / U21,U32 30 %Unp 100 ms
Measurement Settings
Unit Activity Latching
origin Voltage threshold Delay
1 On X V1,V2,V3 / U21,U32 30 %Unp 100 ms
2 Off V1,V2,V3 / U21,U32 20 %Unp 100 ms
Measurement Settings
Unit Activity Latching Trip C.B.
origin Tripping curve mode Voltage threshold Delay
1 On X X V1,V2,V3 / U21,U32 IDMT Phase-to-phase 95 %Unp 3s
2 Off V1,V2,V3 / U21,U32 Definite time Phase-to-phase 10 %Unp 100 ms
3 Off V1,V2,V3 / U21,U32 Definite time Phase-to-phase 10 %Unp 100 ms
4 Off V1,V2,V3 / U21,U32 Definite time Phase-to-phase 10 %Unp 100 ms
Measurement Settings
Unit Activity Latching Trip C.B.
origin Mode Voltage threshold Delay
1 On X X V1,V2,V3 / U21,U32 Phase-to-phase 110 %Unp 3s
2 Off V1,V2,V3 / U21,U32 Phase-to-phase 110 %Unp 100 ms
3 Off V1,V2,V3 / U21,U32 Phase-to-phase 110 %Unp 100 ms
4 Off V1,V2,V3 / U21,U32 Phase-to-phase 110 %Unp 100 ms
Measurement Settings
Unit Activity Latching Trip C.B.
origin Tripping curve Voltage threshold Delay
1 On X X Vo IDMT 10 %Unp 4s
2 Off Vo Definite time 10 %Unp 100 ms
Measurement Settings
Unit Activity Latching Trip C.B.
origin Voltage threshold Delay
1 On X X V1,V2,V3 / U21,U32 10 %Unp 100 ms
2 Off V1,V2,V3 / U21,U32 10 %Unp 100 ms
Measurement Settings
Unit Activity Latch Trip C.B .
origin Fs threshold Delay Vs threshold
1 On X X V1,V2,V3/U21,U32 55 Hz 9s 20 %Un
2 Off V1,V2,V3/U21,U32 53 Hz 100 ms 20 %Un
Settings
Measurement
Unit Activity Latch Trip C.B . df/dt
origin Fs threshold Delay Vs threshold restraint
1 On X X V1,V2,V3/U21,U32 45 Hz 9s 20 %Un No
2 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No
3 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No
4 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No
Settings Settings
Unit Activity Latch Trip C.B . Unit Activity Latch Trip C.B.
Alarm Trip Alarm Trip
1 Off X 180 C 180 C 9 Off X 180 C 180 C
2 Off X 180 C 180 C 10 Off X 180 C 180 C
3 Off X 180 C 180 C 11 Off X 180 C 180 C
4 Off X 180 C 180 C 12 Off X 180 C 180 C
5 Off X 180 C 180 C 13 Off X 180 C 180 C
6 Off X 180 C 180 C 14 Off X 180 C 180 C
7 Off X 180 C 180 C 15 Off X 180 C 180 C
8 Off X 180 C 180 C 16 Off X 180 C 180 C
3.1. Logipam
Author: ................
Customer: ...........
Project: ...............
Switchboard: ......
Cubicle: ...............
1. P27_1_113 = I102
2. P81L_1_113 = I102
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
50/51 - 1 X X
50/51 - 2 X X
50/51 - 3 X
50/51 - 4 X
50/51 - 5 X
50/51 - 6 X
50/51 - 7 X
50/51 - 8 X
50N/51N - 1 X X
50N/51N - 2 X X
50N/51N - 3 X
50N/51N - 4 X
50N/51N - 5 X
50N/51N - 6 X
50N/51N - 7 X
50N/51N - 8 X
50BF - 1
46 - 1 X
46 - 2 X
49RMS - 1
49RMS - inhibit
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
Closing
Tripping X
Inhibit closing
Pick-up X
Drop-out
TCS fault
TC/breaker position discrepancy
Breaker monitoring
Reverse phase rotation
Disturbance recording inhibited
Low battery fault
Cumulative breaking current monitoring
Rotation Discordance Command
Watchdog
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
I101 (Breaker closed) X
I102 (Breaker open) X
I103 (------- (Not used) -----------)
I104 (------- (Not used) -----------)
I105 (------- (Not used) -----------)
I106 (------- (Not used) -----------)
I107 (------- (Not used) -----------)
I108 (------- (Not used) -----------)
I109 (------- (Not used) -----------)
I110 (--- ---- (Not used) - ---- ---- --)
I111 (------- (Not used) -----------)
I112 (--- ---- (Not used) - ---- ---- --)
I113 (--- ---- (Not used) - ---- ---- --)
I114 (--- ---- (Not used) - ---- ---- --)
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
V15
V16
V17
V18
V19
V20
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
Description Setting
Activity On
Total recording time: 21 s
Memory used: 93 %
Number of recordings: 6
Duration of a recording: 3
Number of samples stored per period: 12
Number of Pretrig. periods: 36
Description Setting
Memory used: 25.0 %
Number of recordings: 1
Start/Stop Choice by SFT2841
Recording mode: Circular
Duration recordance: 0h:25m:0s
Sample interval: 0h:0m:1s