Honeywell Pressure Transmitter STG
Honeywell Pressure Transmitter STG
Honeywell Pressure Transmitter STG
Introduction
In 1983, Honeywell introduced the first Smart Pressure
Transmitter― the ST 3000®. In 1989, Honeywell launched
the first all digital, bi-directional protocol for smart field
devices. Today, its ST 3000 Series 100 In-line Pressure
Transmitters continue to bring proven “smart” technology
to a wide spectrum of measurement applications. These
transmitters are screwed directly onto a ½” male NPT
nipple. Typical applications include high-pressure
measurement in boilers, fuel feeds, and high-pressure
reaction vessels in the petrochemical and hydrocarbon
recovery industries – any location where accuracy and
reliability are crucial to safe, economical operation.
Honeywell In-line Transmitters offer the ability to be
installed in a wide variety of hazardous environments for
accurate repeatable pressure measurement.
Figure 1 - On the right is Model STG140, STG170 and STG180
Models and on the left is STG14L, STG17L and STG18L.
All Series 100 Gauge Pressure Transmitters feature proven
STG140/STG14L 0 to 500 psi 0 to 35 bar piezoresistive sensor technology.
Description Features
The ST 3000 transmitter can replace any 4 to 20 mA Choice of linear or square root output conformity is a
output transmitter in use today and operates over a simple configuration selection.
standard two-wire system. The measuring means is a Direct digital integration with Experion PKS and other
piezoresistive sensor, which actually contains three control systems provides local measurement
sensors in one. It contains a differential pressure sensor, accuracy to the system level without adding typical
a temperature sensor, and a static pressure sensor. A/D and D/A converter inaccuracies.
Microprocessor-based electronics provide higher span-
Unique piezoresistive sensor automatically
turndown ratio, improved temperature and pressure
compensates input for temperature and static
compensation, and improved accuracy.
pressure. Added “smart” features include configuring
lower and upper range values, simulating accurate
The transmitter’s meter body and electronics housing
analog output, and selecting preprogrammed
resist shock, vibration, corrosion, and moisture. The
engineering units for display.
electronics housing contains a compartment for the single-
board electronics, which is isolated from an integral Smart transmitter capabilities with local or remote
junction box. The single-board electronics is replaceable interfacing means significant manpower efficiency
and interchangeable with any other ST 3000 Series 100 or improvements in commissioning, start-up, and
Series 900 model transmitters. ongoing maintenance functions.
The SCT 3000 Smartline® Configuration Toolkit provides Comprehensive list of on-board diagnostics (Ref. ST
an easy way to configure instruments using a personal 3000 User manual with HART® 6, 34-ST-25-17 Rev:
computer. The toolkit enables configuration of devices June 09 and FoundationTM Fieldbus option manual
before shipping or installation. The SCT 3000 can operate 34-ST-25-15 Rev: June 09)
in the offline mode to configure an unlimited number of
devices. The database can then be loaded down-line
during commissioning.
ST 3000 Smart Pressure Transmitter 3
1440
1200
250
= Operating Area
Performance under Rated Conditions* - Models STG140 & 14L (0 to 500 psi)
Parameter Description
Upper Range Limit psi: 500 bar: 35
Minimum Span psi: 5 bar: 0.35
Turndown Ratio 100 to 1
Zero Elevation and No limit except minimum span from absolute 0 (zero) to +100% URL. Specifications
Suppression valid over this range.
Accuracy (Reference – Includes In Analog Mode: ±0.075% of calibrated span or upper range value (URV), whichever is
combined effects of linearity, greater, terminal based.
hysteresis, and repeatability) For URV calibrated below reference point (20 psi), accuracy equals:
• Accuracy includes residual error
after averaging successive 20 psi or 1.4 bar in % of span
0.025 0.05
0.025 0.05
readings.
span psi span bar
• For FoundationTM Fieldbus use
Digital Mode specifications. For For High Accuracy (HA) option: +/- 0.0375% of calibrated span or upper range value
HART use Analog Mode (URV), whichever is greater, terminal based.
specifications.
In Digital Mode: ±0.0625% of calibrated span or upper range value (URV), whichever
is greater, terminal based.
For URV calibrated below reference point (20 psi), accuracy equals:
20 psi or 1.4 bar in % of span
0.0125 0.05
0.0125 0.05
span psi span bar
* For High Accuracy (HA) option: +/- 0.035% of calibrated span or upper range value
(URV), whichever is greater, terminal based
Zero Temperature Effect per In Analog Mode: ±0.0625% of span.
28C (50F) For URV below reference point of 50 psi for model STG140 or 75 psi for model
STG14L, effect equals:
50 psi or 3.5 bar in % of span
0.0125 0.05
0.0125 0.05
span psi span bar
OR
75 psi or 5.25 bar in % of span
0.0125 0.05
0.0125 0.05
span psi span bar
OR
Parameter Description
For URV below reference point of 50 psi for model STG140 or 75 psi for model
STG14L, effect equals:
50 psi or 3.5 bar in % of span
0.025 0.05
0.025 0.05
span psi span bar
OR
Performance under Rated Conditions* - Models STG170 & 17L (0 to 3,000 psi)
Parameter Description
Upper Range Limit psi: 3,000 bar: 210
Minimum Span psi: 30 bar: 2.1
Turndown Ratio 100 to 1
Zero Elevation and No limit except minimum span from absolute 0 (zero) to +100% URL. Specifications
Suppression valid over this range.
Accuracy (Reference – Includes In Analog Mode: ±0.075% of calibrated span or upper range value (URV), whichever is
combined effects of linearity, greater, terminal based.
hysteresis, and repeatability) For URV calibrated below reference point (750 psi), accuracy equals:
• Accuracy includes residual error
750 psi or 52 bar in % of span
after averaging successive 0.025 0.05
0.025 0.05
readings. span psi span bar
• For FoundationTM Fieldbus use
In Digital Mode: ±0.0625% of calibrated span or upper range value (URV), whichever
Digital Mode specifications. For
is greater, terminal based.
HART use Analog Mode
specifications. For URV calibrated below reference point (750 psi), accuracy equals:
750 psi or 52 bar in % of span
0.0125 0.05
0.0125 0.05
span psi span bar
Performance under Rated Conditions* - Models STG180 & 18L (0 to 6,000 psi)
Parameter Description
Upper Range Limit psi: 6,000 bar: 415
Minimum Span psi: 60 bar: 4.1
Turndown Ratio 100 to 1
Zero Elevation and No limit except minimum span from absolute 0 (zero) to +100% URL. Specifications
Suppression valid over this range.
Accuracy (Reference – Includes In Analog Mode: ±0.075% of calibrated span or upper range value (URV), whichever is
combined effects of linearity, greater, terminal based.
hysteresis, and repeatability) For URV calibrated below reference point (1,500 psi), accuracy equals:
1500 psi 104 bar in % of span
• Accuracy includes residual error 0.025 0.05
or 0.025 0.05
after averaging successive span psi span bar
readings. In Digital Mode: ±0.0625% of calibrated span or upper range value (URV), whichever
is greater, terminal based.
• For FoundationTM Fieldbus use For URV calibrated below reference point (1,000 psi), accuracy equals:
Digital Mode specifications. For
HART use Analog Mode 1500 psi 104 bar in % of span
0.0125 0.05
or 0.0125 0.05
specifications.
span psi span bar
(1000 psi
) 70 bar
(
±0.10 span psi or ±0.10 span bar in % of span )
Combined Zero and Span In Analog Mode: ±0.175% of span. For URV below reference point (1,000 psi), effect
Temperature Effect per 28C equals:
(50F) 1000 psi 70 bar in % of span
0.075 0.10
or 0.075 0.10
span psi span bar
In Digital Mode: ±0.15% of span. .
For URV below reference point (1,000 psi), effect equals:
1000 psi 70 bar in % of span
0.05 0.10
or 0.05 0.10
span psi span bar
Stability ±0.03% of per year
* Performance specifications are based on reference conditions of 25C (77F), 10 to 55% RH, and 316 Stainless Steel barrier diaphragm.
ST 3000 Smart Pressure Transmitter 7
±0.10 ( 2500
span psi) or ±0.10 ( span bar) in % of span
psi 172 bar
Certifications
This certificate defines the certifications covered for the ST 3000 Pressure Transmitter family of
products, including the SMV 3000 Smart Multivariable Transmitter. It represents the compilation
of the five certificates Honeywell currently has covering the certification of these products into
marine applications.
For ST 3000 Smart Pressure Transmitter and SMV 3000 Smart Multivarible Transmitter
ST 3000 Pressure American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 &
Transmitter Marine 13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA
Certificate
Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV
(MT Option)
Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B,
Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316
SST bolts to be applied. Certificate number: A-11476
Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001
Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2)
ST 3000 Smart Pressure Transmitter 14
The ST 3000 Smart Pressure Transmitters are in conformity with the essential requirements of the
Pressure Equipment Directive.
Honeywell ST 3000 Smart Pressure Transmitters are designed and manufactured in accordance
with the applicable portions of Annex I, Essential Safety Requirements, and sound engineering
practices. These transmitters have no pressurized internal volume, or have a pressurized internal
volume rated less than 200 bar (2,900 psig), and/or have a maximum volume of less than 0.1 liter
(Article 3, 1.1.(a) first indent, Group 1 fluids). Therefore, these transmitters are not subject to the
essential requirements of the directive 97/23/EC (PED, Annex I) and shall not have the CE mark
European applied.
Pressure
Equipment
For transmitters rated > 200 bar (2,900 psig) < 1,000 bar (14,500 psig) Honeywell maintains a
Directive (PED)
technical file in accordance with Annex III, Module A, (internal production control) when the CE
(97/23/EC)
mark is required. Transmitter Attachments: Diaphragm Seals, Process Flanges and Manifolds
comply with Sound Engineering Practice.
NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems)
or vessel(s) from exceeding allowable pressure limits, (equipment with safety functions in
accordance with Pressure Equipment Directive 97/23/EC article 1, 2.1.3), require separate
examination.
A formal statement from TÜV Industry Service Group of TÜV America, Inc., a division of TÜV
Süddeutschland, a Notified Body regarding the Pressure Equipment Directive, can be found at
www.honeywell.com. A hard copy may be obtained by contacting a Honeywell representative.
Dual Seal Dual Seal Certification based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.01 requirements without
Certification the use of additional seal protection elements.
Recommended
Frequency of Honeywell recommends verifying the calibration of these devices once every four years.
Calibration
TM
Foundation Fieldbus is a trademark of the Fieldbus Foundation.
®
Viton is a registered trademark of DuPont
®
HART is a registered trademark of HART Communications Foundation.
®
Teflon is a registered trademark of DuPont.
®
Hastelloy C-276 is a registered trademark of Haynes International.
®
DC 200 is a registered trademark of Dow Corning.
®
Monel 400 is a registered trademark of Special Metals Corporation.
SM
FM Approvals is a service mark of FM Global
ST 3000 and Experion are registered trademarks of Honeywell International Inc.
ST 3000 Smart Pressure Transmitter 15
Mounting
24267
Figure 3 - Examples of typical mounting positions for single-head models STG140, STG170, and STG180.
24268
Figure 4 - Examples of typical mounting positions for in-line models STG14L, STG17L, STG18L, and STG19L.
Note that a mounting bracket is not required for in-line models.
ST 3000 Smart Pressure Transmitter 16
Reference Dimensions
millimeters
inches
55.3
2.18
Optional
meters
23.5
.925
1/2" NPT
Optional
Rotational
external
lock
252.8 / 262.1* ground
9.95 / 10.32
162 / 171.3*
6.38 / 6.74
6
0.24
71.1
2.80
SQ. 21.2
0.83
1/2" NPT
Pressure
Connection Mounting Holes
M8 x 1.25 (2)
50
1.97
53.6
2.11
74.4
2.93
24269
*Dimensions vary due to slight differences in electronics housing designs.
Figure 5 - Typical mounting dimensions for single-head models STG140, STG170, and STG180 for reference.
ST 3000 Smart Pressure Transmitter 17
Reference Dimensions
millimeters
inches
With With
Smart 82.9 94.9 Analog
meter 3.26 3.74 meter
55.3
2.18
Optional
meters
23.5
.925
1/2"
NPT
Other Connectors
1/2" NPT ½” NPT male DIN19213
Pressure
38.1
44.5 Connection
1.5
1.75 or
9/16 Aminco
38.1 Pressure Connection
1.5
24270
*Dimensions vary due to slight differences in electronics housing designs.
Figure 6 - Typical mounting dimensions for in-line models STG14L, STG17L, STG18L, and STG19L for reference.
ST 3000 Smart Pressure Transmitter 18
Options
High Accuracy (Option HA) Indicator Configuration (Option CI)
Extends applicable ST 3000 S100 models to Provides custom configuration of Smart Meters.
±0.0375% reference accuracy (analog). NAMUR NE43 Compliance (Option NE)
The mounting bracket is available in either zinc- This option provides software the meets the
plated carbon steel or stainless steel. NAMUR NE43 requirements for failsafe
Mounting Bracket (Options MB, MX, SB, SX, FB) software. Transmitter failure information is
The angle mounting bracket is available in either generated when the measuring information is no
zinc-plated carbon steel or stainless steel and is longer valid.
suitable for horizontal or vertical mounting on a Transmitter failure values are:
two inch (50 millimeter) pipe, as well as wall ≤ 3.6 mA and ≥ 21.0 mA. The normal ST 3000
mounting. An optional flat mounting bracket is ranges are ≤ 3.8 mA and
also available in carbon steel for two inch (50 ≥ 20.5 mA.
millimeter) pipe mounting. Lightning Protection (Option LP)
Indicating Meter (Options ME and SM) A terminal block is available with circuitry that
Two integral meter options are available. An protects the transmitter from transient surges
analog meter (option ME) is available with a 0 to induced by nearby lightning strikes
100% linear scale. The Smart Meter (option SM) Tagging (Option TG)
provides an LCD display for both analog and Up to 30 characters can be added on the
digital output and can be configured to display stainless steel nameplate mounted on the
pressure in pre-selected engineering units. transmitter’s electronics housing at no extra
HART® Protocol Compatibility cost. Note that a separate nameplate on the
(Options HC and H6) meter body contains the serial number and
Optional electronics modules for the ST 3000 body-related data. A stainless steel wired on tag
provides HART Protocol compatibility in either with additional data of up to 4 lines of 28
HART 5.x or 6.x formats. Transmitters with a characters is also available. The number of
HART Option are compatible with any HART characters for tagging includes spaces.
enabled system that provides 5.x or 6.x format Transmitter Configuration (Option TC)
support. The factory can configure the transmitter
FOUNDATION Fieldbus (Option FF) linear/square root extraction, damping time,
Equips transmitter with FF protocol for use in LRV, URV and mode (analog/digital) and enter
31.25 kbit/s FF networks. See document 34-ST- an ID tag of up to eight characters and
03-72 for additional information on ST 3000 scratchpad information as specified.
Fieldbus transmitters. Custom Calibration and ID in Memory (Option CC)
SIL2/SIL3 Certification (Option SL) The factory can calibrate any range within the
This ST 3000 product is available for use with scope of the transmitter’s range and enter an ID
safety systems. With the SL option, we are fully tag of up to eight characters in the transmitter’s
certified to SIL 2 capability for single transmitters memory.
and SIL 3 capability for multiple transmitter use Lifetime Warranty (Option WL)
through TÜV Nord Sys Tec GmbH & Co. KG. Extends limited 1-year warranty policy to 15
We are in compliance with the following SIL years for ST 3000 S100 pressure transmitters.
standards: See Honeywell Terms and Conditions.
IEC 61508-1: 1998
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at:
http://hpsweb.honeywell.com/Cultures/en-US/Products/Instrumentation/ProductModelSelectionGuides/default.htm
Model Selection Guide
34-ST-16U-03
Issue 57
Page 1 of 4
Instructions
● Select the desired Key Number. The arrow to the right marks the selection available.
● Make one selection from each Table (I, II and IV) using the column below the proper arrow.
● Select as many Table III options as desired plus a required communications option selection.
● A (●) denotes unrestricted availability. A letter denotes restricted availability.
● Restrictions follow Table IV.
Key Number I II III (Optional) IV
______ - ___ - 00000 - _ _, _ _ + XXXX
KEY NUMBER
Design Span Selection Availability
0-5 to 0-500 psi / 0-0.34 to 0-35 bar STG140
Single
0-30 to 0-3,000 psi / 0-2.1 to 0-210 bar STG170
Head
0-60 to 0-6,000 psi / 0-4.1 to 0-420 bar STG180
Gage
0-5 to 0-500 psi / 0-0.34 to 0-35 bar STG14L
Pressure
0-30 to 0-3,000 psi / 0-2.1 to 0-210 bar STG17L
In-Line
0-60 to 0-6,000 psi / 0-4.1 to 0-420 bar STG18L
0-100 to 0-10,000 psi / 0-7 to 0-690 bar STG19L
Single 0-50 to 0-780 mm HgA / 0-67 to 0-1,040 mbarA STA122
Head 0-5 to 0-500 psi/0-0.34 to 0-35 bar absolute STA140
Absolute
0-50 to 0-780 mm HgA / 0-67 to 0-1,040 mbarA STA12L
Pressure
In-Line 0-5 to 0-500 psia / 0-0.34 to 0-35 barA STA14L
0-30 to 0-3,000 psia / 0-2.1 to 0-210 barA STA17L
Base STG and STA models no longer include a default communications option. All units now require the
Important Note:
selection of a communication option from Table III (AN, DE, HC, H6 or FF).
34-ST-16U-03
Issue 57
Page 2 of 4 STG180 STG14L
STG170 STA14L/17L, STG17L/18L
STG140 STG19L
STA140 STA12L
STA122
TABLE II Selection
No Selection 00000 ● ● ● ● ● ● ● ● ●
34-ST-16U-03
Issue 57
Page 3 of 4
STG180 STG14L
STG170 STA14L/17L, STG17L/18L
STG140 STG19L
STA140 STA12L
TABLE III - OPTIONS (continued) STA122
Warranty Options Selection
Additional Warranty - 1 year W1 ● ● ● ● ● ● ● ● ●
Additional Warranty - 2 years W2 ● ● ● ● ● ● ● ● ●
Additional Warranty - 3 years W3 ● ● ● ● ● ● ● ● ● b
Additional Warranty - 4 years W4 ● ● ● ● ● ● ● ● ●
Lifetime Warranty - 15 years WL ● ● ● ● ● ● ● ● ●
Approval
Approval Type Location or Classification Selection
Body
No hazardous location approvals 9X ● ● ● ● ● ● ● ● ●
Explosion Proof Class I, Div. 1, Groups A,B,C,D
FM Dust-Ignitionproof Class II, III Div. 1, Groups E,F,G
SM 1C ● ● ● ● ● ● ● ● ●
Approvals Non-Incendive Class I, Div. 2, Groups A,B,C,D
Intrinsically Safe Class I, II, III, Div. 1, Groups A,B,C,D,E,F,G
Ex ia IIC
T4 (Ta = –50°C to +93°C);
Intrinsically Safe,
T5 (Ta = –50°C to +85°C);
Zone 0 T6 (Ta = –50°C to +70°C)
Enclosure IP 66/67
3S ● ● ● ● ● ● ● ● ●
Ex ia IIC
T4 (Ta = –50°C to +93°C);
Intrinsically Safe,
T5 (Ta = –50°C to +85°C);
Zone 1
T6 (Ta = –50°C to +70°C)
Enclosure IP 66/67
Ex tD A20 IP6X
Dust-tight Enclosure, T95°C (at Ta = 93°C) or
Zone 0 T80°C (at Ta = 78°C)
Enclosure IP 66/67
Ex d IIC
T5 (Ta = –40°C to +93°C), 33 24 24 24 24 24 24 24 24 24
T6 (Ta = –40°C to +78°C)
Flameproof and Dust-
Supply 11- 42Vdc
tight Enclosure,
Ex tD A21 IP6X
Zone 1 T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C)
Enclosure IP 66/67
Ex nA, IIC
T5 (Ta = –40°C to +93°C),
T6 (Ta = –40°C to +78°C);
Non-Sparking, Zone 2 Supply < 42Vdc, 23mA
ATEX 10 3N ● ● ● ● ● ● ● ● ●
Zone 2 Ex tD A22 IP6X
(LCIE) T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C) (Honeywell).
Enclosure IP 66/67
Ex ia IIC
T4 (Ta = –50°C to +93°C);
T5 (Ta = –50°C to +85°C);
T6 (Ta = –50°C to +70°C);
Ui = 30V; Ii = 100mA
11 Ex tD A20 IP6X
Multiple Marking T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C)
Int. Safe, Zone 0/1
and Dust-tight Enclosure, Ex d IIC
T5 (Ta = –40°C to +93°C),
or T6 (Ta = –40°C to +78°C)
Supply 11- 42Vdc 3C 24 24 24 24 24 24 24 24 24
Flameproof, Zone 1 and Ex tD A21 IP6X
Dust-tight Enclosure, T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C)
or
Ex nA, IIC
Non-Sparking, Zone 2 T5 (Ta = –40°C to +93°C),
T6 (Ta = –40°C to +78°C);
Zone 2 Supply < 42Vdc, 23mA
Ex tD A22 IP6X
T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C) (Honeywell)
Enclosure IP 66/67
34-ST-16U-03
Issue 57
Page 4 of 4 STG180 STG14L
STG170 STA14L/17L, STG17L/18L
STG140 STG19L
STA140 STA12L
TABLE III - OPTIONS (continued) STA122
Approval
Approval Type Location or Classification Selection
Body
Canadian Explosion Proof Class I, Div. 1, Groups B,C,D
Standards
Dust-Ignitionproof Class II, III, Div. 1, Groups E,F,G 2J 24 24 24 24 24 24 24 4 24
Association
(CSA) Intrinsically Safe Class I, II, III, Div. 1, Groups A,B,C,D,E,F,G
Ex d IIC;
Flameproof, Zone 1 T5 (Ta = -40 to +93ºC),
T6 (Ta = -40 to +78ºC)
IECEx CA 24 24 24 24 24 24 24 24 24
Ex ia IIC; T3, T4, T5 , T6
Intrinsically Safe,
See Spec for detailed temperature codes by
Zone 0/1
Communications option
Intrinsically Safe,
Ex ia IIC T4, T5, T6 Z2 ● ● ● ● ● ● ● ● ●
Zone 0/1 b
SAEx Flameproof, Zone 1 EX d IIC T5, T6 Enclosure IP 66/67 ZD ● ● ● ● ● ● ● ● ●
(South Africa) Multiple Marking 11
Int. Safe, Zone 0/1, or Ex ia IIC T4, T5, T6 ZA ● ● ● ● ● ● ● ● ●
Flameproof, Zone 1 Ex d IIC T5, T6 Enclosure IP 66/67
CERTUSP
Flameproof, Zone 1 BR- Ex d IIC T5, T6 6D ● ● ● ● ● ● ● ● ●
INMETRO Intrinsically Safe, BR- Ex ia IIC; T4, T5, T6
(Brazil) (See CERTUSP certificate for detailed temperature codes by 6S ● ● ● ● ● ● ● ● ●
Zone 0/1 Communications option)
10
See ATEX installation requirements in the ST 3000 User's Manual
11 The user must determine the type of protection required for installation of the equipment. The user shall then check the box [√] adjacent to the type of
protection used on the equipment certification nameplate. Once a type of protection has been checked on the nameplate, subsequently the equipment
shall not be reinstalled using any of the other certification types.
TABLE IV Selection
Factory Identification XXXX ● ● ● ● ● ● ● ● ●
RESTRICTIONS
Restriction Available Only With Not Available With
Letter Table Selection Table Selection
b Select only one option from this group
d I A _ _, E _ _
e III SM
f III 2J
g III SL
h I _2_
i III 1C or 2J
m III STA12L, STA14L, ME, FF
n III 1C, 2J
o III CR
p III HC or H6 and WP III FF, WX
TC, ME, or FISCO/FNICO
FISCO/FNICO compliance available only with
r III III compliance not available 2J, 3C, 3N,
1C
33, 3S, CA, Z2, ZD, ZA, 6D & 6S
w I E _ G, F _ G, G _ G
x III FF, SM Key # STA12L, STA14L
z I B _ _, F _ _, J _ _
2 III MX, SX III FB, MB, SB
This approval code requires the selection of a
4 III III No CRN Number available
certified conduit plug: A5, A6 or A7
15 III FF
19 III F7, FG
21 III FF
22 III SL
This approval code requires the selection of a
24 III
certified conduit plug: A5, A6 or A7