SOFAR 1.1K~3.3KTL-G3 User manual
Contents
Preface..................................................................................................................................... III
1. Basic safety information................................................................................................... - 1 -
1.1. Safety instructions...............................................................................................- 1 -
1.2. Symbols and signs...............................................................................................- 4 -
2. Product characteristics...................................................................................................... - 6 -
2.1. Product dimensions............................................................................................. - 6 -
2.2. Function characteristics.......................................................................................- 8 -
2.3. Efficiency curve................................................................................................ - 10 -
3. Installation...................................................................................................................... - 11 -
3.1. Installation Process............................................................................................- 11 -
3.2. Checking Before Installation.............................................................................- 11 -
3.3. Product Overview............................................................................................. - 14 -
3.4. Tools..................................................................................................................- 14 -
3.5. Determining the Installation Position............................................................... - 16 -
3.6. Moving the SOFAR 1.1K~3.3KTL-G3............................................................ - 18 -
3.7. Installing SOFAR 1.1K~3.3KTL-G3................................................................- 19 -
4. Electrical Connections.................................................................................................... - 21 -
4.1. Electrical connection.........................................................................................- 22 -
4.2. Connecting PGND Cables................................................................................ - 22 -
4.3. Connecting DC Input Power Cables................................................................. - 24 -
4.4. Connecting AC Output Power Cables...............................................................- 26 -
4.5. RS485,CT,inverter logic interface connection.................................................. - 32 -
4.6. WIFI/GPRS module installation procedure...................................................... - 38 -
4.7. Communication method....................................................................................- 38 -
5. Commissioning of inverter............................................................................................. - 42 -
5.1. Safety inspection before commissioning.......................................................... - 42 -
5.2. Start inverter......................................................................................................- 42 -
6. Operation interface......................................................................................................... - 43 -
6.1. Operation and Display Panel.............................................................................- 43 -
6.2. Standard Interface............................................................................................. - 44 -
6.3. Main Interface................................................................................................... - 46 -
6.4. Update Software online.....................................................................................- 52 -
7. Trouble shooting............................................................................................................. - 53 -
7.1. Trouble shooting............................................................................................... - 53 -
7.2. Maintenance...................................................................................................... - 58 -
8. Technical data................................................................................................................. - 60 -
8.1. Input parameters (DC)...................................................................................... - 60 -
8.2. Output parameters (AC)....................................................................................- 61 -
8.3. Efficiency,Protection and Communication....................................................... - 62 -
8.4. General Date..................................................................................................... - 63 -
9. Quality Assurance...........................................................................................................- 64 -
I
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Notice
This manual contains important safety instructions that must be followed during
installation and maintenance of the equipment.
Save these instructions!
This manual must be considered as an integral part of the equipment. The manual
must always accompany the equipment,even when it is transferred to another user
or field.
Copyright Declaration
The copyright of this manual belongs to Shenzhen SOFARSOLAR Co.,Ltd.Any
corporation or individual should not plagiarize, partially copy or fully copy it
(including software, ect .),and no reproduction or distribution of it in any form or
by any means.All right reserved.
SOFARSOLAR reserves the right of final interpretation.This manual is subject to
change according to user’s or customer’s feedback.Please check our website at
http://www.sofarsolar.com for latest version.
The current Version updated at 20210519.
II
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Preface
Outline
Please read the product manual carefully before installation, operation or
maintenance. This manual contains important safety instructions and installation
instructions that must be followed during installation and maintenance of the
equipment.
Scope
This product manual describes the installation,electrical connections,
commissioning, maintenance and troubleshooting of SOFAR 1.1K~3.3KTL-G3
inverters:
1100TL-G3 1600TL-G3 2200TL-G3
2700TL-G3 3000TL-G3 3300TL-G3
Keep this manual where it will be accessible at all times.
Target Group
This manual is intended for qualified electrical technical personnel who are
responsible for inverter installation and commissioning in the PV power system and
PV plant operator.
Symbols Used
This manual is provides safety operation information and uses the symbol in order
to ensure personal and property security and property security and use inverter
efficiently when operating the inverter. You must understand these emphasized
information to avoid the personal injury and property loss.Please read the following
symbols used in this manual carefully.
III
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
IV
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
If you have any question or problem when you read the following
information, please contact Shenzhen SOFARSOLAR Co., Ltd.
Note
Outlines of this chapter
Safety instruction
It mainly introduce the safety instruction when install and operate the equipment.
Symbols and signs
It mainly introduce the safety symbols on the inverter.
-1-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Transport requirements
If you find packing problems that may cause the damage of the inverter, or find any
visible damage, please immediately notice the responsible transportation company.
You can ask solar equipment installation contractor or Shenzhen SOFARSOLAR
Co.Ltd for help if necessary.
Transport of the equipment, especially by road, must be carried out with by suitable
-2-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
ways and means for protecting the components (in particular, the electronic
components) from violent shocks, humidity, vibration, etc.
Electric connection
Please comply with all the current electrical regulations about accident prevention
in dealing with the solar invert.
Operation
Touching the electrical grid or the terminal of the equipment may
lead to electrocution or fire!
Don’t touch the terminal or conductor connected to the electrical
grid.
Pay attention to any instructions or safety documents related to grid
Danger connection.
Before any repair work, turn OFF the AC circuit breaker between
the inverter and electrical grid first, then turn OFF the DC switch.
After turning OFF the AC circuit breaker and DC switch, wait for 5
minutes at least before carrying out any maintenance or repair work.
Danger
-3-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Inverter should work again after removing any faults. If you need
any repair work, please contact with the local authorized service
center.
Can’t open the internal components of inverter without authorized.
Shenzhen SOFARSOLAR Co., Ltd. does not take any responsibility
Attention for the losses from that.
EMC / noise level of inverter
Electromagnetic compatibility (EMC) refers to that one electrical equipment
functions in a given electromagnetic environment without any trouble or error, and
impose no unacceptable effect upon the environment. Therefore, EMC represents
the quality characters of an electrical equipment. The inherent noise-immune
character: immunity to internal electrical noise.External noise immunity: immunity
to electromagnetic noise of external system. Noise emission level: influence of
electromagnetic emission upon environment.
Electromagnetic radiation from inverter may be harmful to
health!
Please do not continue to stay around the inverter in less than 20 cm
Danger when inverter is working.
-4-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Grounding point.
-5-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
2. Product characteristics
Outlines of this chapter
Product dimensions
It introduces the field of use, and the overall dimensions of SOFAR
1.1K~3.3KTL-G3 inverters.
Function description
It introduces how SOFAR 1.1K~3.3KTL-G3 inverters work and the function
modules inside.
Efficiency curves
It introduces the efficiency curves of in the inverter.
-6-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Only the photovoltaic modules can be connected to the input of the inverter (do not
connect batteries or other sources of power supply) .
The choice of optional parts of inverter should be made by a qualified technician
who knows the installation conditions clearly.
SOFAR 1100TL-G3 SOFAR 1600TL-G3 SOFAR 2200TL-G3:
W×H×D=303mm×260.5mm×118mm
SOFAR 2700TL-G3 SOFAR 3000TL-G3 SOFAR 3300TL-G3:
W×H×D=321mm×260.5mm×131.5mm
Figure 2-2 Front view and left view dimensions of SOFAR 2200TL-G3
Figure 2-3 Front view and left view dimensions of SOFAR 3300TL-G3
-7-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
-8-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Function module
A. Energy management unit
This control can be used to switch the inverter on/off through an external (remote)
control.
B. Feeding reactive power into the grid
The inverter is able to produce reactive power and can therefore feed it into the grid
through the setting of the phase shift factor. Feed-in management can be controlled
directly by the grid company through a dedicated RS485 serial interface.
C. Limiting the active power fed into the grid
The inverter, if enabled can limit the amount of active power fed into the grid by
the inverter to the desired value (Expressed as a percentage) .
D. Self power reduction when grid is over frequency
When the grid frequency is higher than the limited value, inverter will reduce
output power which is necessary for the grid stability.
E. Data transmission
The inverter or a group of inverters may be monitored remotely through an
advanced communication system based on RS-485 serial interface, or remotely via
the WIFI/GPRS.
F. Software update
Support USB flash drive local upgrade software and WIFI/GPRS remote upgrade
software.
-9-
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 10 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
3. Installation
Outlines of this chapter
This topic describes how to install the SOFAR 1.1K~3.3KTL-G3 .
Installation notes
Do NOT install the SOFAR 1.1K~3.3KTL-G3 on flammable
material.
Do NOT install the SOFAR 1.1K~3.3KTL-G3 in an area used to
Danger store Flammable or explosive material.
The enclosure and heat sink are very hot while the inverter is
working, therefore do NOT install the SOFAR 1.1K~3.3KTL-G3 in
places where you might touch them inadvertently.
Caution
Consider the weight of SOFAR 1.1K~3.3KTL-G3 when transporting
and moving the inverters.
Choose an appropriate mounting position and surface.
Attention Assign at least two persons to install the inverter.
Therefore, check the outer packing materials before installing the inverter. Check
the outer packing materials for damage, such as holes and cracks. If any damage is
found, do not unpack the SOFAR 1.1K~3.3KTL-G3 and contact the dealer as soon
as possible. You are advised to remove the packing materials within 24 hours
before installing the SOFAR 1.1K~3.3KTL-G3 inverter.
Checking Deliverables
After unpacking the inverter, check whether deliverables are intact and complete. If
any damage is found or any component is missing, contact the dealer.
Table 3-1 shows the components and mechanical parts that should be delivered.
NO. Picture Description Quantity
1 1.1-3.3KTL-G3 1pcs
- 12 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
12 Manual 1pcs
- 13 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Please check the product package and fittings carefully before installation.
CAUTION
Figure.3-2 SOFAR 1.1K~3.3KTL-G3 inverter overview
- 14 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
twist the DC switch from OFF to ON, or ON to OFF. Remove the screw before
turning the DC switch from OFF to ON or ON to OFF.
3.4. Tools
Prepare tools required for installation and electrical connections.
Table 3-3 shows the tools required for installation and electrical connections.
Hammer drill
1 Recommend drill Used to drill holes on the wall.
dia. 6mm
2 Screwdriver Wiring
- 15 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 16 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 17 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Step 2 Lift the SOFAR 1.1K~3.3KTL-G3 from the packing case and move it to the
- 18 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
installation position.
To prevent device damage and personal injury, keep balance when
moving the inverter because the inverter is heavy.
Do not put the inverter with its wiring terminals contacting the floor
because the power ports and signal ports are not designed to support the
weight of the inverter. Place the inverter horizontally.
When placing the inverter on the floor, put foam or paper under the
Attention
inverter to protect its shell.
Step 4 Hook the inverter to the rear panel. Using an M5 screw to secure the inverter
to the rear panel to ensure safety.
Step 5 You can secure the inverter to the rear panel and protect if from stealing by
installing an anti-theft lock (this action is optional).
- 19 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Figure 3-9
- 20 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
4. Electrical Connections
Outlines of this chapter
This topic describes the SOFAR 1.1K~3.3KTL-G3 inverter electrical connections.
Read this part carefully before connecting cables.
NOTE: Before performing electrical connections, ensure that the DC switch is OFF. Since
the stored electrical charge remains in a capacitor after the DC switch is turned OFF. So it’s
necessary to wait for at least 5 minutes for the capacitor to be electrically discharged.
- 21 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Interface DVC
PV input interface DVCC
AC output interface DVCC
USB interface DVCA
RS485 interface DVCA
CT interface DVCA
Logic interface DVCA
WiFi/GPRS/Ethernet interface DVCA
- 22 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Note 1: L3 is the length between the insulation layer of the ground cable and the crimped
part.L4 is the distance between the crimped part and core wires protruding from the crimped
part.
Note 2: The cavity formed after crimping the conductor crimp strip shall wrap the core wires
completely. The core wires shall contact the terminal closely.
Step 3 Install the crimped OT terminal, flat washer using M5 screw, and tighten the
screw to a torque of 3 N.m using an Allen wrench.
Figure 4-4 Ground terminal composition
- 23 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 24 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
1.Bayonet
- 25 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Follow-up Procedure
To remove the positive and negative connectors from the inverter, insert a removal
wrench into the bayonet and press the wrench with an appropriate strength, as
shown in Figure 4-8.
Context
All the AC output cables used for the inverters are outdoor three-core cables. To
facilitate the installation, use flexible cables. Table 4-2 lists the recommended
specifications for the cables.
Figure 4-9 NOT allowed: connect loads between inverter and circuit breaker
- 26 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 27 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Inverter is equipped with two types of IP66 AC connector (Type Ⅰ connector or Type
Ⅱ connector are randomly equipped with one) , and the AC output cable needs to
be wired by the customer. The appearance of AC connector is shown in figure 4-11.
AC connector type:
Figure 4-11 (1) Figure 4-11 (2)
- 28 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 29 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Removing the AC connector Pull out the AC connector by rotating the knob
counterclockwise.
Figure 4-17
- 30 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 31 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Removing the AC connector Hold the button to unlock and rotate the knob
counterclockwise to the unlock position, then pull out the AC connector.
Figure 4-23
connection
The communication interface location of the SOFAR 1.1K~3.3KTL-G3 is shown in
the figure below.
Figure 4-24
- 32 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Table 4-3 Recommended communication cable size are shown below, The wiring
methods are the same for RS485 and CT, this part describes their wiring methods
and logic interface wiring method.
Communication function RS485 CT
Cable size 0.5~1.5mm² 0.5~1.5mm²
Outside diameter 2.5~6mm 2.5~6mm
Step 1 Remove the communication waterproof cover using a screwdriver;
Figure 4-25
Step 2 Unlock the waterproof cable gland, remove the stopper in the waterproof
connector;
Figure 4-26
- 33 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
A1:Waterproof stopper
Step 3 Select appropriate cable according Table4-2, remove the insulation layer
using a wire stripper, the length of the wire core is about 6mm,insert the cable
through the cable gland and waterproof cover, according to Table4-4, connect the
wires as per the labels, and secure the wire using a slotted screwdriver, as shown in
the figure below:
Table 4-4 Function description of the communication terminals
Type RS485 CT Logic interface
Connector
- 34 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
The logic interface pin definitions and circuit connections are as follows:
The function of logical interface needs to be set on the display screen, please refer
to the operation steps in section 6.3 .
Logic interface pin are defined according to different standard requirements.
(a) Logic interface for AS/NZS 4777.2:2015, also known as inverter demand
response modes (DRMs).
The inverter will detect and initiate a response to all supported demand response
commands within 2 s. The inverter will continue to respond while the mode
remains asserted.
Table 4-5 Function description of the DRMs terminal
Pin NO. Color Function
1 White and orange DRM1/5
2 Orange DRM2/6
3 White and green DRM3/7
4 Blue DRM4/8
5 White and blue RefGen
6 Green DRM0
7 White and brown
Pin7&Pin8 short internal
8 Brown
NOTE: Supported DRM command: DRM0, DRM5, DRM6, DRM7, DRM8.
(b) Logic interface for VDE-AR-N 4105:2018-11, is in order to control and/or
limit the inverter’s output power.
The inverter can be connected to a RRCR (Radio Ripple Control Receiver) in order
to dynamically limit the output power of all the inverters in the installation.
Figure 4-28 Inverter – RRCR Connection
- 35 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 36 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Table 4-9 The inverter is precon figured to the following RRCR power levels.
Relay status: close is 1, open is 0
L1 Active Power Power drop rate Cos(φ)
1 0% <5 seconds 1
0 100% / 1
Step 4 Insert the terminal as per the printed label, and then tighten the screws to fix
the waterproof cover, rotate the cable gland clockwise to fasten it securely.
Figure 4-30
- 37 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Figure 4-31
procedure
Step 1: Remove WiFi/GPRS waterproof cover using screw driver.
Step 2: Install WiFi/GPRS module.
Stpe 3: Fasten WiFi/GPRS module using screws.
2. WI-FI
Refer to the figure shown below: (wireless function required for the PC) . (NOTE4)
Figure 4-33
The operation information (generated energy, alert, operation status) of the inverter
can be transferred to PC or uploaded to the server via Wi-Fi. You can register on the
website. http://www.solarmanpv.com/portal/Register/Regi_Pub.aspx
- 39 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Using the Wi-Fi S/N number (NOTE3), then you can login the website:
http://www.solarmanpv.com/portal/LoginPage.aspx to remote monitors the inverter.
B. Communication between multiple inverters and one PC:
1. RS485
Refer to the following figure: RS485 wires are connected in parallel between
inverters, refer to section 4.5 of this manual for wire connection methods. Connect
the TX+ and TX- of the inverter to the TX+ and TX- of the RS485→USB adapter;
connect the USB port of the adapter to the computer. A maximum of 31 inverters
can be connected in one daisy chain. (NOTE2)
Figure 4-34
2. WI-FI
Refer to the figure shown below: (wireless function required for the PC). (NOTE4)
Figure 4-35
- 40 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
The operation information (generated energy, alert, operation status) of the inverter
can be transferred to PC or uploaded to the server via Wi-Fi. You can register on the
website. http://www.solarmanpv.com/portal/Register/Regi_Pub.aspx
Using the Wi-Fi S/N number (NOTE3) , then you can login the website:
http://www.solarmanpv.com/portal/LoginPage.aspx to remote monitors the inverter.
Note1:
The length of the RS485 communication cable should be less than 1000 m.
Note2:
When multiple inverters are connected via RS485 wires, set mod-bus address to differentiate
the inverters.
Note3:
S/N number of the Wi-Fi module is located on the side.
- 41 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
5. Commissioning of inverter
Ensure that DC and AC voltages are within the acceptable range of the
inverter.
Attention
- 42 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
6. Operation interface
Outlines of this chapter
This section introduces the display, operation, buttons and LED indicator lights of
SOFAR 1.1K~3.3KTL-G3 Inverter.
Button:
Long press the button to enter the next menu or confirm the selection
Short press the button to achieve the next page turning function
Turn down the loop once to exit
Indicator Lights:
RUN (Green)
ON: “ Normal ” state
Flash: “ Wait ” or “ Check ”state
FAULT (Red)
ON: “ Fault ” or “ Permanent ”state
- 43 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 44 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
When control board successfully connected with communication board, the LCD
display the current state of the inverter,display as shown in the figure below.
- 45 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
1.Enter Setting
2.Event List
3.SystemInfo
4.Display Time
5.Software Update
3. Clear Events
Clean up the historical events recorded in the inverter.
4. Set Country
Set up the safety regulation country that meets the current use conditions and
requirements. Before setting this item, ensure that the “Enable Set Country”option
are enabled . Please refer to “7.Enable Set Country” for details.
Table6-1 country code setting
*Mark serial number for temporarily can not set safety regulations country
code country code country code country
Germany VDE
00 20 Korea 40* Thailand PEA
AR-N4105
CEI0-21
01 21 Sweden 41* Thailand MEA
Internal
02 Australia 22 Europe General 42* LV-Range-50HZ
- 48 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
18 EU EN50438 38 Wide-Range-60HZ
5. On-Off Control
Inverter on-off local control.
6. Enable Set Country
Enable this option before setting the country.
Attention: when inverter working for power generation over 24h, country setting is
forbidden, it can only be set after LCD setting. Key in passwords for country
setting through LCD (default: 0001) , country setting can be set in 24h after keying
in the correct passwords, over 24h, set through LCD again.
7. Set Energy
Set the total power generation. You can modify the total power generation through
this option.
8. Set address
Set the address (when you need to monitor multiple inverters simultaneously)
Default 01.
9. Set Input mode
The input modes of the SOFAR inverter are divided into parallel mode and
independent mode (when multi-channel MPPT is input) . Since SOFAR 1.1k ~
3.3KTL-G3 has only one group of MPPT input, the input modes are not
distinguished.
10. Set Language
Set the inverter display language.
11. Set Start Parameter
12. Set Safety Voltage
13. Set Safety Frequency
- 49 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 50 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
interface through main interface to check details of real-time event records, Event
will be listed by the happening time, and recent events will be listed in the front.
Please refer to below picture. Long press the button and short press the button to
turn the page in standard interface, then enter into “2.Event List” interface.
2. Event List
1. Current event 2. History event
001 ID04 06150825
Fault information (Display the event sequence number, event ID
number, and event occurrence time)
(C) “SystemInfo” Interface as below
3.SystemInfo ------Long press the button
1.Inverter Type 8.Power Factor
2.Serial Number 9.Reflux Power
3.Soft Version 10.Safety Paras
4.Hard Version 11.MPPT Scan
5.Country 12.Power Ratio
6.Modbus Address
7.Input Mode
The user enters the main menu by long pressing the button, short press and turns
the page to select menu contents, then long press the button to enter "3.
SystemInfo". Turning the page down can select the system information to view.
(D) Display Time
Long press the button and short press the button to turn the page in the standard
user interface to enter into “4. Display Time”,then long press the button to display
the current system time.
(E) Software Update
User can update software by USB flash drive, SOFARSOLAR will provide the new
update software called firmware for user if it is necessary, The user needs to copy
the upgrade file to the USB flash drive.
- 51 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 52 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
7. Trouble shooting
Outlines of this chapter
This topic describes how to perform daily maintenance and troubleshooting to
ensure long term proper operation of the inverter.
- 53 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
monitoring.
If an Earth Fault Alarm occurs, the fault will be displayed on the LCD screen,
the red light will be on, and the fault can be found in the history of the fault.
For the machine installed with Wi-Fi/GPRS, the alarm information can be seen
on the corresponding monitoring website, and can also be received by the APP
on the mobile phone.
Table 7-1 Event list
Event Event List
Even tList Name solution
List NO. description
The power grid If the alarm occurs occasionally, the possible
ID01 Grid OVP
voltage is too high cause is that the electric grid is abnormal
The power grid occasionally. inverter automatically returns to
ID02 Grid UVP normal operating status when the electric grid’s
voltage is too low
The power grid back to normal.
ID03 Grid OFP frequency is too If the alarm occurs frequently, check whether the
high grid voltage/frequency is within the acceptable
range. If no, contact technical support. If yes,
check the AC circuit breaker and AC wiring of
the inverter.
If the grid voltage/frequency is within the
The power grid acceptable range and AC wiring is correct, while
ID04 Grid UFP the alarm occurs repeatedly, contact technical
frequency is too low
support to change the grid over-voltage,
under-voltage, over frequency, under-frequency
protection points after obtaining approval from
the local electrical grid operator.
Check whether too few PV modules are series
connected in a PV string, thus the voltage (Vmp)
of the PV string is lower than the minimum
operating voltage of inverter. If yes, adjust the
The input voltage is
ID05 PVUVP number of series connected PV modules to
too low
increase the voltage of the PV string to fit the
input voltage range of inverter. inverter
automatically returns to normal operating status
after correct adjustments.
LVRT function is
ID06 Vlvrtlow faulty Check whether the grid voltage fluctuates
OVRT function is greatly.
ID07 Vovrthigh faulty
Check whether too many PV modules are series
connected in a PV string, thus the voltage (Voc)
of the PV string is higher than the maximum
The input voltage is
ID09 PVOVP input voltage of inverter. If yes, adjust the
too high
number of series connected PV modules to
decrease the voltage of the PV string to fit the
input voltage range of inverter. inverter
- 54 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
automatically returns to normal operating status
after correct adjustments.
Input current is not Check the input mode (parallel mode/
ID10 Ipv Unbalance
balanced independent mode) setting of inverter according
to Section 6.3 (C) 6.Input Mode of this user
Pv Config Set Incorrect input manual, If it’s incorrect, change it according to
ID11 Section 6.3 (A) 10.Set Input mode of this
Wrong mode
manual.
If the fault occurs occasionally, the possible
cause is that the external circuits are abnormal
occasionally. inverter automatically returns to
normal operating status after the fault is rectified.
ID12 GFCI Fault GFCI Fault If the fault occurs frequently and lasts a long
time, check whether the insulation resistance
between the PV array and earth (ground) is too
low, then check the insulation conditions of PV
cable.
The input current is Check whether the input current is higher than
too high , and has the maximum input current of inverters, then
ID14 HwBoost OCP
happen hardware check the input wiring, if both are correct, please
protection contact technical support.
The grid current is
too high , and has
ID15 HwAc OCP
happen hardware
protection
The grid current is
ID16 AcRms OCP
too high
HwAD Fault The grid current
ID17
IGrid sampling error
The DCI sampling ID15-ID24 are internal faults of inverter, turn
ID18 HwAD FaultDCI
error OFF the “DC switch”, wait for 5 minutes, then
HwAD Fault The grid voltage turn ON the “DC switch”. Check whether the
ID19
VGrid sampling error fault is rectified. Ifno, please contact technical
GFCI Device The GFCI sampling support.
ID20
Fault error
The master chip
ID21 MChip_Fault
fault
Hw Aux Power The auxiliary
ID22
Fault voltage error
Bus Volt Zero The bus voltage
ID23
Fault sampling error
Iac Rms The Output current
ID24
Unbalance is not balanced
If the PV array configuration is correct (no ID05
fault) , the possible cause is that the solar
The bus voltage Is
ID25 Bus UVP irradiance is too low. inverter automatically
too low
returns to normal operating status after the solar
irradiance returns to normal level.
The bus voltage Is ID26-ID27 are internal faults of inverter, turn
ID26 Bus OVP
too high OFF the “DC switch”, wait for 5 minutes, then
- 55 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
turn ON the “DC switch”. Check whether the
The bus voltage is
ID27 Vbus Unbalan fault is rectified. If no, please contact technical
not balanced
support.
Check the input mode (parallel mode/
independent mode) setting of inverter according
ID28 Dci OCP The Dci is too high to Section 6.3 (C) 6.Input Mode of this user
manual, If it’s incorrect, change it according to
Section 6.3 (A)
Internal faults of inverter, turn OFF the “DC
The grid current is switch”, wait for 5 minutes, then turn ON the
ID29 Sw OCP Instan
too high “DC switch”. Check whether the fault is
rectified. If no, please contact technical support.
Check whether the input current is higher than
SwB OCP The input current is the maximum input current of inverters, then
ID30
Instant too high check the input wiring, if both are correct, please
contact technical support.
Reflux overload Check if the load power is out of range, and if so,
ID33 Overload
time out adjust the power to the correct range.
The grid voltage
sampling value
Consistent
ID49 between the master
Fault_VGrid
DSP and slave DSP
is not consistent
The grid frequency
sampling value
Consistent
ID50 between the master
Fault_FGrid
DSP and slave DSP
is not consistent
The DCI sampling
value between the
Consistent
ID51 master DSP and
Fault_DCI
slave DSP is not
consistent ID49-ID55 are internal faults of inverter, turn
OFF the “DC switch”, wait for 5 minutes, then
The GFCI sampling
turn ON the “DC switch”. Check whether the
value between the
Consistent fault is rectified. If no, please contact technical
ID52 master DSP and
Fault_GFCI support.
slave DSP is not
consistent
The spi
communication
ID53 Spi Comm Lose between the master
DSP and slave DSP
is fault
The Sci
communication
between the control
ID54 Sci Comm Lose
board
communication
board is fault
ID55 Relay Test Fail The relays fault
- 56 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Check the insulation resistance between the PV
The insulation
ID56 Pv Iso Fault array and earth (ground) , if a short circuit
resistance is too low
occurs, rectify the fault.
Over Temp The inverter temp is Ensure the installation position and installation
ID57
Fault_Inv too high method meet the requirements of Section 3.4 of
Over Temp The Boost temp is this user manual.
ID58 Check whether the ambient temperature of the
Fault_Boost too high
installation position exceeds the upper limit. If
Over Temp The environment yes, improve ventilation to decrease the
ID59
Fault_Env temp is too high temperature.
The grid current is
Unrecover too high, and has
ID65
Hw Ac OCP cause unrecoverable
hardware fault
The bus voltage is
Unrecover too high, and has
ID66
Bus OVP cause unrecoverable
fault
The grid current is
Unrecover
unbalance, and has
ID67 Iac Rms ID65-ID70 are internal faults of inverter, turn
cause unrecoverable
Unbalance OFF the “DC switch”, wait for 5 minutes, then
fault
turn ON the “DC switch”. Check whether the
The input current is fault is rectified. If no, please contact technical
Unrecover Ipv unbalance, and has support.
ID68
Unbalance cause unrecoverable
fault
The bus voltage is
Unrecover Vbus unbalance, and has
ID69
Unbalance cause unrecoverable
fault
The grid current is
Unrecover too high, and has
ID70
OCP Instant cause unrecoverable
fault
Check the input mode (parallel mode/
Unrecover PV independent mode) setting of inverter according
Incorrect input
ID71 Config Set to Section 6.3 (C) 6.Input Mode of this user
mode
Wrong manual, If it’s incorrect, change it according to
Section 6.3 (A) 10.Set Input mode of this manual
The input current is
Unrecover too high, and has
ID74
IPV Instant cause unrecoverable
fault ID74-ID77 are internal faults of inverter, turn
OFF the “DC switch”, wait for 5 minutes, then
Unrecover
The EEPROM is turn ON the “DC switch”. Check whether the
ID75 WRITE
unrecoverable fault is rectified. If no, please contact technical
EEPROM
support.
Unrecover The EEPROM is
ID76
READEEPROM unrecoverable
Unrecover Relay has happen
ID77
Relay Fail permanent fault
- 57 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Ensure the installation position and installation
The inverter has method meet the requirements of Section 3.4 of
Over Temp derated because of this user manual. Check whether the ambient
ID81
Derating the temperature is temperature of the installation position exceeds
too high the upper limit. If yes, improve ventilation to
decrease the temperature.
The inverter has Inverter automatically reduce the output power
Over Freq derated because of when the frequency of electrical grid is too
ID82
Derating the grid frequency is high.Please make sure the grid frequency is
too high within the acceptable range.
Inverter records ID83 in case of remote power
The inverter has derating operation. Check the wiring of remote
ID83 Remote Derating derated by the input and output control signal port on the
Remote control communication board according to Section 4.5 of
this user manual.
Inverter records ID84 in case of remote
The inverter has
shutdown operation. Check the wiring of remote
shut down because
ID84 Remote Off input and output control signal port on the
by the Remote
communication board according to Section 4.5 of
control
this user manual.
Inverter automatically reduce the output power
Inverter derated
Under Frequency when the frequency of electrical grid is too low.
ID85 because the grid
Derating Please make sure the grid frequency is within the
frequency is too low
acceptable range.
Under Freq Under frequency up Please make sure the grid frequency is within the
ID89
Up Power power acceptable range.
Lightning Lightning Please check if the machine is damaged and
ID93
protection alarm protection tripped contact the technician for help.
The software in the
control board and
Software version
ID94 the communication Contact technical support to upgrade software.
Isnot consistent
board is not
consistent
Communication The communication ID95~ID96 are internal faults of inverter, turn
ID95 Board EEPROM board EEPROM is OFF the “DC switch”, wait for 5 minutes, then
fault fault turn ON the “DC switch”. Check whether the
RTC clock chip RTC clock chip is fault is rectified. If no, please contact technical
ID96 support.
anomaly fault
Check the country setting according to Section
The country is 6.3 (C) 5.Country of this user manual, If it’s
ID97 Invalid Country
invalid incorrect, change it according to Section 6.3 (A)
4.Set Country Code of this manual.
ID98 SD fault The SD card is fault Please replace the SD card.
7.2. Maintenance
Inverters generally do not need any daily or routine maintenance. Heat sink should
not be blocked by dust, dirt or any other items.Before the cleaning, make sure that
- 58 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
the DC SWITCH is turned OFF and the circuit breaker between inverter and
electrical grid is turned OFF. Wait at least for 5 minutes before the Cleaning.
Inverter cleaning
Please clean the inverter with an air blower, a dry & soft cloth or a soft bristle brush.
Do NOT clean the inverter with water, corrosive chemicals, detergent, etc.
Heat sink cleaning
For the long-term proper operation of inverters, ensure there is enough space
around the heat sink for ventilation, check the heat sink for blockage (dust, snow,
etc.) and clean them if they exist. Please clean the heat sink with an air blower, a
dry & soft cloth or a soft bristle brush. Do NOT clean the heat sink with water,
corrosive chemicals, detergent, etc.
- 59 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
8. Technical data
Outlines of this chapter
This topic lists the technical specifications for all SOFAR 1.1K~3.3KTL-G3
inverters.
G3 G3 G3 G3 G3 G3
Rated Output
4.8A 7A 9.6A 11.8A 13A 14.3A
current
Nominal grid
L/N/PE,220Vac 230Vac 240Vac
voltage
Nominal grid
50Hz/60Hz
frequency
Grid frequency
45~55Hz/54~66Hz (According to local grid standard)
range
THDi <3%
- 61 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
- 62 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
G3 G3 G3 G3 G3 G3
Topology Transformerless
Ambient temperature
-30~60℃
range
Permissible humidity
0~100%
range
DC Switch Optional
Max.Operating
2000m
altitude
Bracket Wall-mounted
Display LCD+LED
Communication
RS485.WiFi/GPRS(optional),USB
mode
Degree of
IP65
protection
- 63 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
9. Quality Assurance
- 64 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Once the extended warranty service is purchased, our company will issue the
extended warranty card to the customer to confirm the extended warranty period.
- 65 -
Copyright © Shenzhen SOFARSOLAR Co., Ltd
SOFAR 1.1K~3.3KTL-G3 User manual
Statement
If you have purchased this product in Australia, you should be aware that this
warranty is provided in addition to other rights and remedies held by a consumer at
law.
Our goods come with guarantees that cannot be excluded under the Australian
Consumer Law. You are entitled to a replacement or refund for a major failure and
compensation for any other reasonably foreseeable loss or damage. You are also
entitled to have the goods repaired or replaced if the goods fail to be of acceptable
quality and the failure does not amount to a major failure.
- 66 -