0% found this document useful (0 votes)
94 views3 pages

Ir3 HD

The FlameSpec-IR3-HD flame detector can detect fires and explosions extremely reliably and fast, allowing preventative action to be initiated rapidly and minimize consequences. It uses improved triple IR technology to address slow and fast growing fires both visible and non-visible. Key benefits include detection within 40 milliseconds of fireballs or explosions, and standard fire detection in only 1.2 seconds from 50 feet. It also provides high definition video output and automatic video recording of fire events.

Uploaded by

Vincent Gabriel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views3 pages

Ir3 HD

The FlameSpec-IR3-HD flame detector can detect fires and explosions extremely reliably and fast, allowing preventative action to be initiated rapidly and minimize consequences. It uses improved triple IR technology to address slow and fast growing fires both visible and non-visible. Key benefits include detection within 40 milliseconds of fireballs or explosions, and standard fire detection in only 1.2 seconds from 50 feet. It also provides high definition video output and automatic video recording of fire events.

Uploaded by

Vincent Gabriel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

FlameSpec

IR3-HD
Triple IR Flame Detector

Introduction
The FlameSpec-IR3-HD flame detector provides ultra-fast
response, high performance and reliable detection of all types
of hydrocarbon fires (visible and non-visible). The detector
addresses slow growing fires as well as fast eruption of fire using
improved triple IR (IR3) technology. It operates in all weather and
light conditions with highest immunity to false alarms.
• Detection within 40 milliseconds of fireballs or explosions
• Standard fire in only 1.2 second from 50 ft. (15m) and
4.1 seconds from 230 ft. (70m).
The detector provides high-definition video output with clear
imaging of fire event at up to 100 ft. (30m), allowing rescuers to
know the exact situation before entering the hazardous area. It
will automatically record a video of a fire event (1 min pre-alarm /
up to 3 min post-alarm).
Add to that, the integral HD quality video, with event recording,
on top of the proven superior capabilities of Triple IR (IR3) flame
detection and you have a very powerful safety tool to protect your
personnel, plant and process.

Key Benefits
• High Immunity to False Alarm
The FlameSpec • Extreme sensitivity – up to 260 ft. (80m) for a 1 ft2 (0.1m2)
n-heptane pan fire
IR3-HD will detect fires
• Ultra-fast detection mode – detection within 40 milliseconds
and explosions extremely for fireballs or explosions
• 1.2 second detection time – for 1 ft2 (0.1m2) n-heptane pan fire
reliable and fast allowing at up to 50 ft. (15m) distance
preventative action to be • HD video output with Automatic HD video recording of fire
events. Data/Event logger: Alarms, faults and other relevant
initiated rapidly and events are logged to non-volatile memory

minimize the • Built-in-Test (BIT) – Automatic and manual self-test of window


cleanliness and the overall operation of the detector
consequences! • Window heater to avoid condensation and icing
• Tilt mounting bracket can be connected either above or below
the detector

Version: F100V0010.02 October 2018

FIRE & GAS DETECTION Fire and Gas Detection Technologies Inc. | 590 W. Central Ave. Suite K, Brea, CA 92821 USA
TECHNOLOGIES INC. Tel: (+1) 714-671-8500 | [email protected]
FlameSpec-IR3-HD Model: FLS-IR3-HD

Triple IR Flame Detector

Immunity to False Alarm


False Alarm Source Modulated Unmodulated
Distance ft.   m Response Distance ft.   m Response
Sunlight, Direct, Reflected No Alarm No Alarm
Incandescent frosted glass light, 300W 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Fluorescent, 70W (3x23.3W) 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Electric arc 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Arc welding 13.1 4.0 No Alarm 13.1 4.0 No Alarm
Radiation heater, 1850W 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Quartz lamp (1000W) shielded 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Quartz lamp (500W) non-shielded 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Mercury vapor lamp 160Wx3 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Exhausts 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Projector led 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Solenoid bell 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Soldering Iron 2.0 0.5 No Alarm 2.0 0.5 No Alarm
Electric Drill 2.0 0.5 No Alarm 2.0 0.5 No Alarm

Response Characteristics
Fuel Pan Size Distance ft. m Avrg Response Time (Sec)
N-Heptane 1 x 1 ft. 262 80 9.0
N-Heptane 1 x 1 ft. 230 70 4.1
N-Heptane 1 x 1 ft. 197 60 3.2
N-Heptane 1 x 1 ft. 98 30 1.5
N-Heptane 1 x 1 ft. 49 15 1.2
Gasoline 2 x 2 ft. 328 100 5.3
Gasoline 1 x 1 ft. 230 70 3.6
Gasoline 1 x 1 ft. 98 30 1.5
Methane 32-in Plume 148 45 3.3
Methane 32-in Plume 82 25 0.8
LPG 32-in Plume 180 55 4.8
LPG 32-in Plume 148 45 2.9
LPG 32-in Plume 98 30 1.4
LPG 32-in Plume 49 15 1.4
Diesel 1 x 1 ft. 164 50 2.9
Diesel 1 x 1 ft. 79 24 3.9
JP5 2 x 2 ft. 295 90 9.2
JP5 1 x 1 ft. 164 50 5.8
JP5 1 x 1 ft. 148 45 4.9
JP5 1 x 1 ft. 79 24 1.9
Kerosene 1 x 1 ft. 164 50 4.1
Kerosene 1 x 1 ft. 79 24 2.5
Methanol 1 x 1 ft. 131 40 4.1
Methanol 1 x 1 ft. 59 18 3.9
Methanol 1 x 1 ft. 75 23 1.2
Methanol 1 x 1 ft. 39 12 1.2
Ethanol 1 x 1 ft. 125 38 4.2
Ethanol 1 x 1 ft. 75 23 1.6
Isopropanol 1 x 1 ft. 180 55 3.5
Isopropanol 1 x 1 ft. 75 23 1.0
Polypropylene 1 x 1 ft. 115 35 10.1
Polypropylene 1 x 1 ft. 66 20 2.6
Paper 1 x 1 ft. 79 24 0.9
Paper 1 x 1 ft. 39 12 0.8

FIRE & GAS DETECTION Fire and Gas Detection Technologies Inc. | 590 W. Central Ave. Suite K, Brea, CA 92821 USA
TECHNOLOGIES INC. Tel: (+1) 714-671-8500 | [email protected]
FlameSpec-IR3-HD Model: FLS-IR3-HD

Triple IR Flame Detector

FIRE DETECTION Detection time and distance 40ms for fast fire burst or explosion
1.5s for 1 ft2 (0.1m2) pan fire at 0–100 ft. (0–30m)
4.1s for 1 ft2 (0.1m2) pan fire at 100–230 ft. (30–70m)
Field of view (IR detection) 90° Horizontal, 75° Vertical
Time Delay 0-30 seconds
Built in Test Automatic and Manual

VIDEO HD Video Allows clear imaging of fire and people at 100 ft. (30m) distance
FUNCTIONALITY Video recording of alarm events 1 minute pre-event and up to 3 minutes post-event
System integration protocol ONVIF (Open Network Video Interface Forum) Profile S

ELECTRICAL Operating Voltage 24 VDC nominal (18-32 VDC)


SPECIFICATIONS Current Consumption Standby: 180mA
Maximum: 250mA all systems in operation (including window heater)
Conduit Entries 2x conduit entries 3/4″ 14NPT or M25x1.5
Wiring 12-20AWG (2.5-0.35mm2)

OUTPUTS Relays Volt-free contacts rated 2A at 30 VDC


Alarm – normally open
Fault – normally closed
0-20mA (stepped) current output 3 wire and 4 wire configurations (sink and source)
Indication Tri-color LED
Modbus RTU compatible on RS-485
Digital (for video) IP network IEEE 802.3 10Base-t
Composite video NTSC or PAL

MECHANICAL Size 7.87 x 5.12 x 5.12″ (200x130x130mm)


SPECIFICATIONS Weight Detector (Stainless Steel 316): 9.8 lbs. (4.4 kg)
Tilt mount (Stainless Steel 316): 5.4 lbs. (2.4 kg)

ENVIRONMENTAL Temperature Range Operating: -67°F to +167°F (-55°C to +75°C)


SPECIFICATIONS Option: -67°F to +185°F (-55°C to +85°C)
Storage: -67°F to +185°F (-55°C to +85°C)
Humidity Up to 99% (RH), non-condensing
Ingress Protection IP66 & 67; NEMA 250 4X & 6P

APPROVALS* Explosion proof ATEX: II 2 G D


Ex db eb IIC T5 Gb -55°C<Ta<75°C or Ex db eb IIC T4 Gb -55°C<Ta<85°C
Ex tb IIIC T95°C Db -55°C<Ta<75°C Ex tb IIIC T105°C Db -55°C<Ta<85°C
IECEx (pending)
Ex db eb IIC T5 Gb -55°C<Ta<75°C or Ex db eb IIC T4 Gb -55°C<Ta<85°C
Ex tb IIIC T95°C Db -55°C<Ta<75°C Ex tb IIIC T105°C Db -55°C<Ta<85°C
FMU & FMC (pending)
Class I, Div. 1, Groups B, C & D;
Class II, Div. 1, Groups E, F & G;
Class III
Performance (pending) ANSI FM 3260
EN 54-10
Functional safety (pending) SIL2, per IEC 61508
DNV GL (pending) Standard DNVGL-CG-0339 for open deck locations
Temperature class D; Vibration Class A, B and C
EAC CU TR (pending)

ACCESSORIES Weather shield


Adapters for connecting different mounts

WARRANTY 5 years
*All products designed and tested to relevant approval standards

FIRE & GAS DETECTION Fire and Gas Detection Technologies Inc. | 590 W. Central Ave. Suite K, Brea, CA 92821 USA
TECHNOLOGIES INC. Tel: (+1) 714-671-8500 | [email protected]

You might also like