High-performance/Low noise
General-purpose Inverter
Complete Digital Features for
Advanced Performance
The continuing demands for flexible production
and advanced factory automation have created
the need for greater functionality in machine tools,
conveyors, and other on-site production
equipment.To meet this need, OMRON offers the
SYSDRIVE 3G3IV Series of Inverters.
Developed through the latest custom LSI and
control technologies, these General-purpose
models represent a new generation in Inverters.
All models feature insulated gate bipolar
transistors (IGBT) for greater performance, higher
torque, and lower noise. And a large selection of
software applications and special features ensures
ease of operation.
If advanced machine performance and digital
functionality is what you are looking for, the
SYSDRIVE 3G3IV is waiting for you.
Innovation
IGBT Employed as the Switching
Element for Higher Torque, Lower
Noise, and Smoother Operation.
SYSDRIVE
3Is Concept
Table of Contents
Standard Specifications . . . . . . . . . . . 14
Dimensions: Inch (mm) . . . . . . . . . . . 17
Intelligence Digital Operator Functions . . . . . . . . 23
Special Features and Software Capa-
Operation Menu
bilities to Suit a Wide Array of Needs. System Constants Sn-jj . . . . . . . . . . . . . . . . 25
Control Constants Cn-jj . . . . . . . . . . . . . . . . 27
Frequency References An-jj . . . . . . . . . . . . 28
Constants To Change During Running Bn-jj 28
Interface
Network Capability Made Possible
via SYSMAC Programmable Con-
trollers: Complete Compatibility
INNOVATION
Optimum Machine Operation for Today’s Diverse Needs
All SYSDRIVE 3G3IV series models
As Quiet as Running with High Torque at Low Speeds
employ IGBT for switching. The high- Commercial Power Ensures Tripless Operation
speed switching of the IGBT has Employing our original asynch- The full-automatic torque boost
changed the very concept of inverter ronous high-carrier technique feature based on our unique
control. Precise waveform control for sine wave PWM control, we torque control operation and ex-
coupled with the high performance of have succeeded in eliminating act sine wave drive achieves
the IGBT provides numerous advan- the motor noises that plagued 150% or greater torque even at
tages such as quiet operation, high conventional PWM inverters. 1/20 speed. This ensures maxi-
starting torque, smoother shaft rota- Running noise has been re- mum performance whenever it
tion and improved reliability. duced by approximately 20 dB is needed. This tough, no-stall
Current Wave Example at 10 Hz as compared to conventional inverter won’t trip even if over-
PWM inverters. This quiet oper- loaded.
ation assures a more comfort-
High Torque Assured Even
able working environment. at Low Speeds
Motor Noise Comparison TORQUE (%)
NOISE LEVEL (dB) 150
3G3IV 3G3IV
6 Hz
PREVIOUS PWM INVERTER
3 Hz 4.5 Hz
100
1.5 Hz
ntlp:photo
CONVENTIONAL PWM INVERTER 1 Hz
50
PREVIOUS
3G3IV MODEL
ntlp:photo PREVIOUS
MODEL
3G3IV
1 (0.75)
Compact, Highly Reliable
Control Board with SMT 2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
3G3IV 10 (7.5)
ntlp:photo
15 (11)
20 (15)
25 (18.5)
30 (22)
50 (37)
60 (45)
INTELLIGENCE
The versatility of the new Advanced Functions through a Wide Range of
fully-digital software invert- Consolidated Monitoring Simple Multi-step Operation
er satisfies numerous Functions for Operating State Operation speed can be set by up to
In addition to the conventional moni- nine steps by switching four-contact
needs and enables you to toring items, frequency input, output input signals. Various sequence op-
up-grade your machines. frequency, output current, output volt-
erations can also be easily set.
age, DC voltage, output power, and
A broad function selection I/O terminal state are also indicated
FREQUENCY REFERENCE
FREQUENCY REF. 8
digitally to facilitate monitoring of ma-
allows rapid and significant chine operation. Alarm contents are
FREQUENCY REF. 7
FREQUENCY REF. 6
FREQUENCY REF. 5
(An-07)
(An-06)
(An-08)
changes in your machine’s retained in memory even at power off. FREQUENCY REF. 4 (An-05)
FREQUENCY REF. 3
SUPPLEMENT (An-04) JOG
Output Frequency Motor Current FREQUENCY (An-03) FREQUENCY
MAIN
(An-09)
performance. Indication Example Indication Example
FREQUENCY (An-02)
(An-01)
TIME
ntlp:photo ntlp:photo
High-grade I/O Functions
Digital indication of operat- Direct indication of motor
The advanced multi-function I/O ter-
ing frequency makes current allows easy verifi- minals adapt the inverter to each ma-
checking of operating cation of loads.
state easy.
chine. Just set system constants with
the digital operator to customize the
DC Voltage Indication Alarm Message
Example Indication Example
I/O terminals.
Input Signal
ntlp:photo ntlp:photo
8 8
EXTERNAL COASTING
STOP 11 11
ANA- ANA-
Over 200 intelligent functions includ- LOG
OUT-
22
– +
LOG
OUT-
22
– +
ntlp:photo
TORQUE
quency Meter
ntlp:photo ntlp:photo
CV500 CV1000
SYSMAC
ntlp:photo
ntlp:photo ntlp:photo
RS-232C
ntlp:photo
ntlp:photo
IBM PC/AT RS-232C
ntlp:photo NSU
NSB
SYSMAC NET
ntlp:photo ntlp:photo
ntlp:photo C2000H
C1000H CV1000
CV1000 C200H
ntlp:photo
G7TC
SYSDRIVE FEATURES SOLVE ON-SITE PRODUCTION PROBLEMS
Solving Customer Problems via the 3I Concept
Conventional Inverter SYSDRIVE 3G3IV Solutions
Shortcomings
Low starting torque 150% torque established at 1/20 of the
Inverter of the next higher rated speed. 3G3IV 6 Hz
capacity must be employed for Motor torque increases up to 150% over
3 Hz 4.5 Hz
applications requiring high starting full-speed range due current waveform
TORQUE (%)
torque. correction by asynchronous PWM method 1.5 Hz
and automatic torque compensation.
1 Hz PREVIOUS
MODEL
SPEED (rpm)
IM
VOLTAGE
SETTING
0
OPERATION RANGE F
MR
RESONANT FREQUENCY
LOCK-OUT CIRCUIT
The brake trip voltage can be
controlled externally.
Difficult to vary speeds of the Automatic torque boost effectively solves
vibrating type URAS motor. the eccentric torque problem.
Inverter of one or two classes Inverter of the same capacity as the motor
greater capacity is applied for the can be used for cost-savings.
eccentric-weight-incorporating
type motor.
ntlp:photo
ECCENTRIC-WEIGHT
10
SYSDRIVE FEATURES SOLVE ON-SITE PRODUCTION PROBLEMS
Conventional Inverter SYSDRIVE 3G3IV Solutions
Shortcomings
ntlp:photo
11
SOFTWARE FEATURES THAT MATCH APPLICATION REQUIREMENTS
OPTION
13 CARD 9
ANALOG
14 10 MULTI–FUNCTION
INPUT 16 25 SIGNAL OUTPUT
17 26
27
INPUT OUTPUT
OPTION OPTION
Speed search Inertia load Synchronize Starts the inverter at the specified frequency, automatically detects the synchro- YES Sn-15 to 18
operation drive such as with the coast- nization point, and leads the operation to the operation frequency. No speed
blower, winder, ing motor detector is required. It is no longer necessary to stop the motor before starting,
etc. the operation efficiency for the customer is greatly improved.
DC injection Blower, pump, Starting the When the direction of the free running motor is unfixed, the above speed search YES Cn-11
braking before etc. which free running operation function is difficult to use. In these, the motor can be stopped by DC Cn-13
operation have wind-mill motor injection braking, and be restarted by the inverter. The operation is completely
effects automatic.
Commercial Blower, pump, Automatic Switching of commercial power source to inverter or inverter to commercial YES Sn-15 to 18
power source/ mixer, extruder, switching be- power source is done without stopping the motor. The operation efficiency for
inverter switch- etc. tween com- the customer is improved. When the inverter size is decided by the starting
over operation mercial power capacity (as in the extruder), this function can be used to reduce the inverter
source and in- capacity.
verter
Energy saving Precision ma- Energy saving, Full power is output during accel/decel. When it reaches a constant speed, the YES Sn-15 to 18
operation chine tool Low vibration output voltage is automatically reduced to the preset value. Mainly applied to bn-09
reduce the vibration in precision machine tools.
Multi-step Transportation Schedule op- Multi-stop operation can be set by setting the contact combinations, so the YES Sn-15 to 18
speed opera- machine, etc. eration under connection with PC becomes very easy. When combined with jog speed can An-01 to 09
tion fixed speed also allow simple positioning.
command and
positioning
stop
Accel/decel Machine tool, The accel/de- The two kinds of accel/decel times are switched by an external contact signal. YES Sn-15 to 18
time change- etc. cel time Necessary for switching operation of 2 machines with different functions by a bn-01, 02
over operation changeover single inverter. Also used in emergency stopping applications. bn-03, 04
with an exter-
nal signal
3-wire se- General Simple config- Operation can be accomplished using a momentary push-button switch. YES Sn-15 to 18
quence uration of con-
trol circuit STOP RUN
1
RUN
2
STOP
5
FWD/REV
11
Operating site General Operability Operation and settings can be selected while the inverter is online. (digital YES Sn-04
selection operator/external instruction, signal input/output). Sn-15 to 18
Fault trip retry Air conditioner, Improvement When the inverter trips, it first begins to coast, and then it immediately is diag- Sn-04
operation etc. of operation nosed by computer, resets automatically, and returns to the original operation Sn-15 to 18
reliability speed by speed search operation. Up to 10 retry counts can be selected.
Quick stop High-speed DC injection DC injection braking is performed from top speed. The duty is 5% or less. Can Sn-04
without braking router, etc. braking of in- generate 50% to 70% of the braking torque. Economic, because a braking Cn-11
resistor (DC in- duction motor resistor is not necessary. Has advantage of mounting in completely closed Cn-12
jection braking cabinets.
stop)
12
SOFTWARE FEATURES THAT MATCH APPLICATION REQUIREMENTS
SYSDRIVE 3G3IV setting
F nction
Function Target
Application Operation, advantages Contact Analog Signal Control constant
name market
input I/O output setting
Excess torque Blower, cutter, Protection of The inverter can be switched to coasting or motor speed reducing mode as YES Sn-07, 10
detect setting extruder, etc. machine soon as it reaches a certain preset torque level. Machine (especially cutter) Cn-26, 27
operation Improvement protection can be done without using special peripheral devices. When used in Cn-30
of continuous a blower application the operation frequency can be automatically reduced to
operation reli- the load balancing point, according to the overload condition, and prevent
ability overload tripping.
Torque limit
Upper/lower Pump, blower Motor speed The upper and lower limits of the motor speed can be set independently. No Cn-14, 15
frequency limit limit peripheral operation units. The command signal bias and gain can also be set
operation independently.
Prohibit setting General ma- Prevent me- The motor simply passes through the preset speed, and continuous running Cn-16, Cn-19
of specific fre- chines chanical vibra- cannot be done at this speed. This function is used to avoid the mechanical
quency (fre- tion in the resonance point of the equipment.
quency jump equipment
control)
Carrier fre- General ma- Lower noise, The carrier frequency can be set to reduce the acoustic noise from the motor Cn-23 to 25
quency setting chines eliminates res- and machine system.
onance
Load speed General Monitor func- Can indicates motor speed (rpm), machine speed loaded (rpm), line speed Cn-20
display tion enhance- (m/min), etc.
ment
Run signal General Motor with me- “Closed” during operation. “Open”during coasting to a stop. Can be used as YES Sn-20 to 22
chanical brake interlock contact point during stop.
operation
Zero-speed Machine tools Zero-frequen- Can be used as tool exchange signal. YES Sn-20 to 22
signal cy interlock
Speed agreed Machine tools Command The contact closes when inverter output frequency reaches the set value. Can YES Sn-20 to 22
signal speed reach be used as an interlock for lathes, etc.
interlock
Excess torque Blower, cutter, Protection of Works when “overtorque setting operation” is accomplished. Can be used as a YES Sn-07
signal extruder, etc. machine, im- torque limiter. Sn-20 to 22
provement of Cn-26, 27
operation con-
tinuation reli-
ability
Low voltage General System protec- This contact is “closed” only when tripped by low voltage. Can be used as YES Sn-20 to 22
signal tion for under- power loss detection relay for the system power loss countermeasure.
voltage
Free uninten- General Command The contact closes when the speed agrees at arbitrary frequency command. YES Cn-21, 22
tionally speed speed agreed
agreed signal interlock
Output fre- General Gear change The contact closes at an arbitrary output frequency and above. YES Sn-20 to 22
quency detec- interlock etc. Cn-21, 22
tion 1
Output fre- General Gear change The contact closes at an arbitrary output frequency and below. YES Sn-20 to 22
quency detec- interlock etc. Cn-21, 22
tion 2
Base block sig- General Operation in- Always “close” when the inverter output is off. YES Sn-20 to 22
nal terlock, etc.
Damping resis- General Preventive “Close” when an overheat of a built-in braking resistor or a braking transistor YES Sn-11
tor protection maintenance error is detected.
Analog input General Operability Functions as supplementary frequency reference. Also used for fine control of YES Sn-19
signal input reference, external control of accel/decel time.
Analog output General Monitor func- Either a frequency meter or ammeter can be used. YES Sn-05
signal tion enhance-
ment
Analog input General Operability Enables external operation with high resolution instructions. Also enables Option card is used. Sn-25
normal and reverse operation using positive or negative voltage signals.
Digital input General Operability Enables operation with 8-bit digital signals. (Two digit BCD or eight binary bits. Sn-26
Easily connects to NC or PC.)
Analog output General Monitor func- Monitors the output frequency, motor current, output voltage, and DC voltage. Sn-28
tion enhance-
ment
Digital output General Operation en- Indicates output frequency using a pulse counter. Indicates error through dis- Sn-27
hancement crete output.
13
STANDARD SPECIFICATIONS
Standard Specifications
Inverter Model 200 to 230 V
3G3IV A2004 A2007 A2015 A2002 A2037 A2055 A2075 B2110 B2150 B2180 B2220 B2300 B2370 B2450 B2550 B2750
Inverter Capacity KVA 1.4 2.1 2.7 4.1 6.9 10.3 13.7 20.6 27.4 34 41 54 68 78 95 130
Rated Output Current 3.2 4.8 6.4 9.6 16 24 32 48 64 80 96 130 160 183 224 300
A
Output Max. Continuous Out- 3.6 5.4 7.2 10.8 18 27 36 54 72 90 108 146 180 205 252 337
Characteristics put Current *2 A
Max. Output Voltage 3-Phase, 200/208/220/230 V (Proportional to input voltage)
Rated Output Fre- 50, 60, 72, 90, 120, 180 Hz (up to 400 Hz available)
quency
Control Overload Capacity 150% rated output current for one minute 150% rated output current for one minute/
Characteristics 110% max. continuous output current for 1
minute
Frequency Setting 0 to 10 VDC (20 kΩ), 4 to 20 mA (250 Ω) 0 to ±10 V (OPTIONAL)
Signal
Accel/Decel Time 0.1 to 6000 sec (Accel/Decel time setting independently)
Braking Torque Approx. 20%
No. of V-f Patterns 4: For general purpose 4: For high starting torque 1: For adjustable pattern 4: For fans and pumps 4: For general purpose 4: For high starting
(Total of 16) 3: For machine tools. torque 4: For fans and pumps 3: For ma-
chine tools.
Overload Motor coasts to a stop after 1 minute at 150% rated output current. Motor coasts to a stop for 1 minute at 150%
rated output current/motor coasts to a stop
for 1 minute at 110% max. continuous out-
put current.
Protective Overvoltage Motor coasts to a stop if converter output voltage exceeds 400 V.
Functions
Undervoltage Motor coasts to a stop if converter output voltage drops to 210 V or below.
Momentary Power Immediately stop by 15 ms and above longer power loss. (Continuous system operation during power loss less than 2 sec is equipped as stan-
Loss dard.)*3 Setting mode before shipment.
Fin Overheat Thermostat
Stall Prevention Stall prevention at acceleration/deceleration and constant speed operation
Ground Fault Provided by electronic circuit
Power Charge Indica- Charge lamp stays ON until bus voltage drops below 50 V.
tion
*3 For Models of 4.1 kVA or less, continuous system operation during power loss less than 1 sec. Two seconds ride-thru available as option.
14
STANDARD SPECIFICATIONS
Inverter Model 380 to 460 V
3G3IV A4004 A4007 A4015 A4022 A4037 A4055 A4075 B4110 B4150 B4180 B4220 B4300 B4370 B4450 B4550 B4750 B411K B416K B418K B422K B430K
Max. Applica- Rated output 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 150 200 250 300 400
ble Motor Out-
Out (0.4) (0.75) (1.5) (2.2) (3.7) (5.5) (7.5) (11) (15) (18.5) (22) (30) (37) (45) (55) (75) (110) (160) (185) (220) (300)
putt HP (kW)*
Max. continuous --- --- --- --- --- --- --- --- --- --- --- --- --- --- 100 150 200 250 300 400 500
output (75) (110) (160) (185) (220) (300) (355)
Inverter Capacity 1.4 2.2 3.4 4.1 6.9 10.3 13.7 20.6 27.4 34 41 54 68 82 110 140 200 250 290 380 510
KVA
Rated Output 1.6 2.6 4.0 4.8 8 12 16 24 32 40 48 64 80 96 128 165 224 300 340 450 600
Current A
Max. Continuous 1.8 2.9 4.5 5.4 9 13.5 18 27 36 45 54 72 90 108 144 180 252 337 380 506 675
Output Output Current
Characteristics *2 A
Max. Output Volt- 3-Phase, 380/400/415/440/460 V (Proportional to input voltage)
age
Rated Output 50, 60, 72, 90, 120, 180 Hz (up to 400 Hz available)
Frequency
Rated Input Volt- 3-Phase, 380/400/415/440/460 V, 50/60 Hz
age and Frequen-
cy
Allowable Voltage ±10%
Power Supply Fluctuation
Allowable Fre- ±5%
quency Fluctua-
tion
Control Method Sine wave PWM
Frequency Con- 0.1 to 400 Hz
trol Range
Frequency Accu- Digital command: 0.01% (+14° to 104°F/–10° to 40°C) Analog command: 0.1% (77° ±18°F/25° ±10°C)
racy
Frequency Reso- Digital operator reference: 0.1 Hz. Analog reference: 0.06 Hz/60 Hz
lution
Output Frequen- 0.01 Hz (1/30000)
Control cy Resolution
Characteristics
Overload Capac- 150% rated output current for one minute 150% rated output current for one minute/110%
ity max. continuous output current for one minute
Frequency Set- 0 to 10 VDC (20 kΩ), 4 to 20 mA (250 Ω) 0 to ±10 V (OPTIONAL)
ting Signal
Accel/Decel Time 0.1 to 6000 sec (Accel/Decel time setting independently)
Braking Torque Approx. 20%
No. of V-f Pat- 4: For general purpose 4: For high starting torque 1: For adjustable pattern 4: For fans and pumps 3: 4: For general purpose 4: For high starting torque
terns (Total of 16) For machine tools. 4: For fans and pumps 3: For machine tools.
Motor Overload Electronic thermal overload relay
Protection
Instantaneous Motor coasts to stop at approx. 200% rated current.
Overcurrent
Blown Fuse Pro- Motor coasts to a stop by blown-fuse.
tection
Overload Motor coasts to a stop after 1 minute at 150% rated output current. Motor coasts to a stop for 1 minute at 150% rated
output current/motor coasts to a stop for 1 minute
at 110% max. continuous output current.
Protective Overvoltage Motor coasts to a stop if converter output voltage exceeds 800 V (700 V).*3
Functions
Undervoltage Motor coasts to a stop if converter output voltage drops to 420 V or below.
Momentary Pow- Immediately stop by 15 ms and above momentary power loss. (Continuous system operation during power loss less than 2 sec is equipped as stan-
er Loss dard.)*4 Setting made before shipment.
Fin Overheat Thermostat
Stall Prevention Stall prevention at acceleration/deceleration and constant speed operation
Ground Fault Provided by electronic circuit
Power Charge In- Charge lamp stays ON until bus voltage drops below 50 V.
dication
Location Indoor (protected from corrosive gases and dust)
Ambient Temper- +14° to 104°F (–10° to +40°C) (not frozen) Enclosed type, totally-enclosed type: +14° to
ature 104°F (–10° to +40°C) Open chassis type: +14°
to 122°F (–10° to +50°C) (not frozen)
Environmental
Conditions Storage Temper- –4° to 140°F (–20 to +60°C)
ature *5
Humidity 90% RH (non-condensing)
Vibration 9.81 m/s2 (1 G) less than 20 Hz, up to 0.2 G at 20 to 50 Hz
*3 800 V for input voltage (Cn-01) more than 400 V and 700 V for less than 400 V.
*4 For Models of 4.1 kVA or less, continuous system operation during power loss less than 1 sec. Two seconds ride-thru available as option.
15
STANDARD SPECIFICATIONS
Protective Enclosures
SYSDRIVE 3G3IV Enclosures (Specify the enclosure type when ordering.)
Max. Applicable Motor
Max
Voltage Inverter Capacity Model Open Chassis Type (IEC IP00) Enclosed Type (NEMA 1)
Output HP (kW)
kVA
0.5 (0.4) 1.4 3G3IV-A2004-j Available by removing the upper
u er Conform to NEMA 1.
1 (0.75) 2.1 3G3IV-A2007-j andd llower cover off enclosed
l d
type.
2 (1.5) 2.7 3G3IV-A2015-j
3 (2.2) 4.1 3G3IV-A2022-j
5 (3.7) 6.9 3G3IV-A2037-j
7.5 (5.5) 10.3 3G3IV-A2055-j
10 (7.5) 13.7 3G3IV-A2075-j
15 (11) 20.6 3G3IV-B2110-j Conform to IEC IP00. ---
200 to 230 V
20 (15) 27.4 3G3IV-B2150-j
25 (18.5) 34 3G3IV-B2185-j
30 (22) 41 3G3IV-B2220-j
40 (30) 54 3G3IV-B2300-j
50 (37) 68 3G3IV-B2370-j
60 (45) 78 3G3IV-B2450-j
75 (55) 95 3G3IV-B2550-j
100 (75) 130 3G3IV-B2750-j
0.5 (0.4) 1.4 3G3IV-A4004-j Available by removing the upper
u er Conform to NEMA 1.
1 (0.75) 2.2 3G3IV-A4007-j andd llower cover off enclosed
l d
type.
2 (1.5) 3.4 3G3IV-A4015-j
3 (2.2) 4.1 3G3IV-A4022-j
5 (3.7) 6.9 3G3IV-A4037-j
7.5 (5.5) 10.3 3G3IV-A4055-j
10 (7.5) 13.7 3G3IV-A4075-j
15 (11) 20.6 3G3IV-B4110-j Conform to IEC IP00. ---
20 (15) 27.4 3G3IV-B4150-j
25 (18.5) 34 3G3IV-B4185-j
380 to 460 V 30 (22) 41 3G3IV-B4220-j
40 (30) 54 3G3IV-B4330-j
50 (37) 68 3G3IV-B4370-j
60 (45) 82 3G3IV-B4450-j
75 (55) 110 3G3IV-B4550-j
100 (75) 140 3G3IV-B4750-j
150 (110) 200 3G3IV-B411K-j
200 (160) 250 3G3IV-B416K-j
250 (185) 290 3G3IV-B418K-j
300 (220) 380 3G3IV-B422K-j
400 (300) 510 3G3IV-B430K-j
ENCLOSURES
Open Chassis Type (IEC IP00) Enclosed Type (NEMA 1)
Mounted in a customer’s enclosure. Constructed so that Provides a clean, and ventilated environment within the en-
openings do not permit direct or inadvertent access to live closure. Front and rear panels are firmly secured (e.g.
parts by personnel. front, rear, right, left, top, bottom). Openings provided for
ventilation, etc. are small enough to prevent inadvertent ac-
cess by personnel
MODEL DESIGNATION
3G3IV-A2004-EV1
V2: Version capable of communicating with PC
Inverter E: European specifications (optional card required)
blank: Japanese specifications
Specifications
A: Enclosed wall- Applicable maximum motor output
mounting 004: 0.4 kW
B: Panel-mounting 007: 0.75 kW
Voltage
P: Option to
2: 200 V
30K: 300 kW
4: 400 V
16
DIMENSIONS: INCH (mm)
200 to 230 V
0.5 to 2 HP (0.4 to 1.5 kW) (Model 3G3IV-A2004-j to 15 HP (11 kW) (Model 3G3IV-B2110-j)
A2015-j) Enclosed Wall-mounted Type Open Chassis Type
4-0.236(M6) DIA 4-0. 236(M6) DIA
MTG. HOLES FACE PLATE MTG. HOLES
UPPER FACE PLATE
COVER
Approx. CONTROL
CIRCUIT
GROUNDING Weight MAIN CIRCUIT GROUND- TERMINAL
TERMINAL M4 TERMINAL M6 ING TER- M4
9 lb (4 kg) MINAL M8
3-35 dia: CABLE ENTRY KNOCK OUT
Note: To use the unit in
the panel, remove
Approx. Weight:
the upper and 42 lb (19 kg)
lower covers.
3 to 5 HP (2.2 to 3.7 kW) (Model 3G3IV-A2022-j to 20 HP (15 kW) (Model 3G3IV-A2150-j)
A2037-j) Enclosed Wall-mounted Type Open Chassis Type
4-0. 236(M6) DIA
MTG. HOLES
4-0.236(M6) DIA MTG. HOLES
COOLING
FAN
Approx.
GROUNDING TERMINAL M5 Weight: MAIN CIR-
LOWER COVER GROUNDING MAIN CIR- CUIT TERMI-
3-44 dia. CABLE ENTRY KNOCK OUT 22 lb (10 kg) TERMINAL M8 CUIT TERMI- NAL M4
NAL M4
17
DIMENSIONS: INCH (mm)
200 to 230 V
60/75 HP (45/55 kW) (Model 3G3IV-B2450-E to 100 HP (75 kW) (Model 3G3IV-B2750-E)
B2550-E) Open Chassis Type Open Chassis Type
Four, M10 dia. mtg. holes
150 min.
65 min.
(20)
65 min.
Front cover AIR
Four, M10 dia. mtg. holes Front cover
150 min.
100 min. 30 min. AIR
10
Digital
Control Operator Cooling fan
1245
1280
terminal
M3.5
Control
terminal
M4
780
800
Control
terminal
Cooling fan
M3.5 4 59 Digital
113
Operator 58.5 133.5
Control
terminal
M4
152 113
455
10
150 min.
375
186
150 min.
50 50
475 550
15.0
90 25 25
Grounding terminal M8 Main terminal M10
90° 600
open 150.5
480 max. Main terminal M12 Grounding terminal M8
695 max.
280 max.
90°
Approx. Weight: 65 kg open
70 906 max. 537.6 max.
297.0
453 max.
150.5
40 HP (30 kW) (Model 3G3IV-B2300-E) 50 HP (37 kW) (Model 3G3IV-B2370-E)
Open Chassis Type Open Chassis Type
150 min.
30 min. 30 min. AIR 100 min. 30 min.
10
AIR
Front cover
10
Control Digital
terminal Operator
M3.5 Digital
59 Control Operator Cooling fan
Control Cooling fan terminal
780
800
655
675
terminal M3.5
81.5 59
M4 83
Control
113
terminal
M4
152 113
211.5
150 min.
150 min.
10
55 55 50 50
90 Grounding terminal M8 475 186
425 90
Grounding terminal M8 Main terminal M10 90°
Main terminal M10
430 max. open
480 max.
695 max.
280 max.
280 max.
Approx. Weight: 51 kg
Approx. Weight: 59 kg
70
18
DIMENSIONS: INCH (mm)
380 to 460 V
0.5 to 3 HP (0.4 to 2.2 kW) (Model 3G3IV-A4004-j to 25 to 30 HP (18.5 to 22 kW) (Model 3G3IV-B4185-j to
A4022-j) Enclosed Wall-mounted Type B4220-j) Open Chassis Type
4-0.236(M6) DIA FACE PLATE 4-0.236(M6) DIA
MTG. HOLES MTG. HOLES
UPPER COVER FACE PLATE
COOLING
FAN
COOLING
FAN
GROUNDING CONTROL
CIRCUIT TIR-
MAIN CIRCUIT TERMINAL
MINAL M4
TERMINAL M5 M8
90° OPEN
GROUNDING TERMINAL M8 CONTROL CIRCUIT TERMINAL M4
MAIN CIRCUIT TERMINAL M8
MODEL WEIGHT
Approx. Weight:
3G3IV-B4110-j 46 lb (21 kg) 165 lb (75 kg)
3G3IV-B4150-j 48 lb (22 kg)
19
DIMENSIONS: INCH (mm)
380 to 460 V
75 to 100 HP (55 to 75 kW) (Model 3G3IV-B4550-E to 150 HP (110 kW) (Model 3G3IV-B411K-E)
B4750-E) Open Chassis Type Open Chassis Type
Four, M10 dia. mtg. holes
(12.5)
Front cover
Four, M10 dia. mtg. holes Front cover
105 min.
(12.5)
100 min. 30 min.
105 min.
30 min. AIR
100 min. AIR
Control
Cooling fan terminal Cooling fan
Control Digital
circuit 20 58.5 Operator
circuit 58.5 Digital M3.5
termi- 28
900
925
Operator
900
925
113
nal
113
M3.5
349
349
M8 M8
150 min.
150 min.
475
50 475 50 50
50 575
12.5
575 167 109
12.5
580 max.
840 max.
Model Approx. weight
Approx. Weight: 104 kg
280
3G3IV-B4550 88 kg.
330
70
3G3IV-B4750 92 kg.
200 HP (160 kW) (Model 3G3IV-B416K-E) 250/300 HP (185/220 kW) (Model 3G3IV-B418K-E to
Open Chassis Type B422K-E) Open Chassis Type
Four, M12 dia. mtg. holes Front cover Six, M12 dia. mtg. holes
150 min.
150min.
50 285 565 50
25
AIR
circuit Operator
311.5
1360
1400
1450
113
terminal M4 M3.5 Control circuit
113
terminal M3.5
Main circuit
717.5
Grounding terminal M16
terminal M8
50
305-500 min.
150 min.
600 25 space
Main circuit terminal M12 Grounding terminal 139 150.7
90° Control circuit
M8
open terminal M4
537.6 956
906 max.
297.0
103
150 max.
298 575 32
55 AIR
Digital
Operator
70 70
58.5
Control circuit 342
1600
terminal M3.5
113
1550
Cooling fan
Main circuit
terminal M16
Grounding
terminal M8
855
410 min.
960 space
20
LIST OF MAIN DIMENSIONS
Dimensions: Inch (mm)
21
LIST OF MAIN DIMENSIONS
Dimensions in mm (inch) Approx.
Voltage Enclos re
Enclosure Model 3G3IV
3G3IV-jjjj-j
jjjj j weight
W H D W1 H1 d kg (lb)
A2004, A2007, A2015 205 305 130 180 285 M6 4 (9)
(8.07) (12.01) (5.12) (7.09) (11.22)
A2022, A2037 205 305 165 180 285 M6 7 (15)
(8.07) (12.01) (6.50) (7.09) (11.22)
A2055, A2075 205 355 200 180 335 M6 10 (22)
(8.07) (14.00) (7.87) (7.09) (13.19)
B2110 250 500 240 200 485 M6 19 (42)
(9.84) (19.69) (9.45) (7.87) (19.09)
B2150 325 550 245 275 535 M6 24 (53)
Open (12.79) (21.65) (9.65) (10.83) (21.06)
chassis
type B2185, B2220 325 550 255 275 535 M6 32 (70)
(12.79) (21.65) (10.04) (10.83) (21.06)
200 to B2300 425 675 280 315 655 M8 51 (112)
230 V (16.73) (26.57) (11.02) (12.40) (25.79)
B2370 475 800 280 375 780 M10 59 (130)
(18.70) (31.50) (11.02) (14.76) (30.71)
B2450, B2550 475 800 280 375 780 M10 65 (143)
(18.70) (31.50) (11.02) (14.76) (30.71)
B2750 600 1,280 453 550 1,245 M12 153 (337)
(23.62) (50.39) (17.83) (21.65) (49.02)
A2004, A2007, A2015 205 305 130 180 285 M6 4 (9)
(8.07) (12.01) (5.12) (7.09) (11.22)
Enclosed A2022, A2037 205 305 165 180 285 M6 7 (15)
type (8.07) (12.01) (6.50) (7.09) (11.22)
(NEMA 1)
A2055, A2075 205 355 200 180 335 M6 10 (22)
(8.07) (14.00) (7.87) (7.09) (13.19)
A4004, A4007, A4015, A4022 205 355 165 180 335 M6 7 (15)
(8.07) (14.00) (6.50) (7.09) (13.19)
A4037, A4055, A4075 205 355 200 180 335 M6 10 (22)
(8.07) (14.00) (7.87) (7.09) (13.19)
B4110, B4150 250 500 255 200 485 M6 22 (48)
(9.84) (19.69) (10.04) (7.87) (19.09)
B4180, B4220 325 550 255 265 535 M6 32 (70)
(12.79) (21.65) (10.04) (10.43) (21.06)
B4300, B4370 350 725 280 250 705 M8 45 (99)
(13.78) (28.54) (11.02) (9.84) (27.76)
B4450 500 925 280 400 900 M10 75 (165)
Open (19.69) (36.42) (11.02) (15.75) (35.43)
chassis
type B4550 575 925 280 475 900 M10 88 (194)
380 to (22.64) (36.42) (11.02) (18.70) (35.43)
460 V B4750 575 925 280 475 900 M10 92 (203)
(22.64) (36.42) (11.02) (18.70) (35.43)
B411K 575 925 330 475 900 M10 104 (229)
(22.64) (36.42) (12.99) (18.70) (35.43)
B416K 600 1,360 453 550 1,325 M12 170 (374)
(23.62) (53.54) (17.83) (21.65) (52.17)
B418K, B422K 950 1,450 435 --- 1,400 M12 360 (793)
(37.40) (57.09) (17.13) (55.12)
B430K 960 1,600 455 --- 1,550 M12 420 (925)
(37.97) (62.99) (17.91) (61.02)
A4004, A4007, A4015, A4022 205 355 165 180 335 M6 7 (15)
Enclosed (8.07) (14.00) (6.50) (7.09) (13.19)
type
(NEMA 1) A4037, A4055, A4075 205 355 200 180 335 M6 10 (22)
(8.07) (14.00) (7.87) (7.09) (13.19)
22
LIST OF MAIN DIMENSIONS
Easy Modification to Gasketed Cabinet Inverter Unit Cooling
Open chassis cabinet incorporating heat sink can be easily changed to Fin Dimensions
or more
PANEL
or more
INVERTER INLET L L
TEMPERATURE +14
113°F TO 113°F, –10 TO 45°C
+45°C
PERIPHERAL TEMPER-
ATURE +40°C 104°F
LOWER COVER 0.5 to 2 HP 25 to 400 HP
0.4 to 15 kW 18.5 to 300 kW
200 to 230 V
Model 3G3IV-jjjj-j A2004 A2015 A2022 A2055 B2110 B2150 to B2030 to B2075
A2007 A2037 A2075 B2220 B2055
Cooling fin Dimensions L 31 (1.22) 31 (1.22) 40 (1.57) 65 (2.56) 105 (4.13) 86 (3.39) 90 (3.54) 150.7
max. mm (inch) (5.93)
Number of rubber bushings --- 4 6 2 --- --- --- ---
200 to 230 V
Model 3G3IV-jjjj-j A4004 A4037 B4110 B4185 B4300 B4450 B4550 B416 B418K
to to B4150 B4220 B4370 to to
A4022 A4075 B411K B430K
Cooling fin Dimensions L 40 (1.57) 65 (2.56) 66 (2.60) 86 (3.39) 106 109 109 150.7 103
max. mm (inch) (4.17) (4.29) (4.29) (5.93) (4.06)
Number of rubber bushings --- 2 --- --- --- --- --- --- ---
Note: For installation on a totally-enclosed type control panel, rubber bushing may be required depending on the model.
Procure necessary rubber bushings separately.
23
DIGITAL OPERATOR FUNCTIONS
Mode Display LED
Red lamp lights in DRIVE mode and goes out in
PRGM mode.
Display
Displays set value of each function or monitoring values
such as frequency and output current. (5 digits)
Read/Write Key
Depressing this key recalls and displays indicated data from memory.
Depressing the second time enters displayed data into memory.
24
DIGITAL OPERATOR FUNCTIONS
(Un-03)
07 Status of Input Terminal (11111111
DSPL Indication of fault that occurred
08 Status of Output Terminal % 111 before power was turned off
FREQUENCY
REFERENCE
VALUE DISPLAY Depress DSPL key to display frequency reference
• Switching between the DRIVE/PRGM (pro-
value. gram) Mode (The mode can be switched only
FREQUENCY
when the machine is stopped.)
REFERENCE Select a digit by RESET key and set by or key.
VALUE SET
KEY OPERATION
SET VALUE
Depressing DATA key to set values.
WRITE-IN PRGM
ENTER (Stops for 2 sec.) PRGM mode PRGM mode
DRIVE
(The numbers stop blinking for approx. 2 sec.)
DRIVE lamp DRIVE lamp
goes off. goes on.
Normal operation
(Blinks again.)
Frequency reference
DSPL
(An-jj)
ROTATING FWD FWD REV
DIRECTION SET Select motor rotating direction by key.
REV
(Typical FWD run) Control parameter
(Rotating direction selected here is displayed on the digital DSPL Frequency reference (An-jj)
(bn-jj)
operator.) and control parameter (bn-jj)
can be changed even in the drive
mode (during operation).
System parameter
DSPL
(Sn-jj)
OUTPUT
FREQUEN- Change to output frequency display by DSPL key.
CY DISPLAY
Control parameter
DSPL
(Cn-jj)
OPERATION
CHECK Check motor operation by JOG key.
FREQUENCY SET
DATA
RUN ENTER
LAMP
STOP
LAMP
RESET
: LIGHT : BLINK : LIGHT OFF
The RUN and STOP lamps goes on/off and blinks according to DATA
ENTER
operation state.
25
OPERATION MENU
SYSTEM CONSTANTS Sn-jj
Function Factory Setting
Function Sn
Sn- Data Name
jj 4th 3rd 2nd 1st 4th- 3rd- 2nd- 1st-
digit digit digit digit digit digit digit digit
Operation
O eration Method Select Master frequency reference from keypad --- --- --- 1
External terminal operation effective (start/stop, etc) --- --- 0 ---
Run Mode 04 Keypad operation effective --- --- 1 ---
Selection 1
RAMP stop 0 0 --- ---
Coasting to stop 0 1 --- ---
Stopping Method select
Full-range DC injection braking stop 1 0 --- ---
Coasting stop (timer function provided) 1 1 --- ---
Keypad STOP key effective during operation. --- --- --- 0 0 0 0 0
Priority of stopping
Keypad STOP key not effective during operation. --- --- --- 1
REV run enabled --- --- 0 ---
Run Mode 05 Prohibition of REV run
Selection 2 REV run disabled --- --- 1 ---
Analog output at terminals 21, 22 is proportional to output frequen- 0 --- --- ---
Analog Monitor Output
Out ut cy.
Analog output at terminals 21, 22 is proportional to output current. 1 --- --- ---
0.2 sec. S-curve --- --- 0 0 0 0 0 0
Protection Section Stall prevention during deceleration enabled --- --- 0 ---
10 Stall Prevention
1 (stall prevention) Stall prevention during deceleration disabled --- --- 1 ---
Stall prevention during running enabled --- 0 --- ---
Stall prevention during running disabled --- 1 --- ---
26
OPERATION MENU
Function Factory Setting
Function Sn
Sn– Data Name
jj 4th 3rd 2nd 1st 4th- 3rd- 2nd- 1st-
digit digit digit digit digit digit digit digit
No DB protection calculated or provided by inverter --- --- --- 0 0 0 0 0
DB resistor Protection provided for OMRON internal DB resistor only, if in- --- --- --- 1
stalled
Fault Contact during Auto Fault contact is not energized during auto reset/restart operation --- --- 0 ---
Protection
Section 2 11 Reset/Restart Operation Fault contact is energized during auto reset/restart operation --- --- 1 ---
Momentary Power Loss Operation stopped by momentary power loss detection --- 0 --- ---
Protection Operation continues during momentary power loss --- 1 --- ---
--- Not used 0 --- --- ---
External Fault Signal External fault input; Normal open-contact input --- --- --- 0 0 1 0 0
Level External fault input; Normal close-contact input --- --- --- 1
Receiving External Fault External fault signal; always detected --- --- 0 ---
Signal External fault signal; detected while running only --- --- 1 ---
Protection 12
Section 3 Ramp stop (major fault) 0 0 --- ---
Coasting to stop (major fault) 0 1 --- ---
Processing at External
Fault Detection Emergency stop (major fault): decelerates to stop by emergency 1 0 --- ---
stop time (bn-04 set value)
Operation to continue (minor fault) 1 1 --- ---
--- 13 --- Not used --- --- --- --- 0 0 0 0
Electronic thermal motor protection effective --- --- --- 0 0 0 0 0
Protection Motor Protection Electronic thermal motor protection ineffective --- --- --- 1
Section 5 14 (Electronic Thermal) Electronic thermal characteristics are in accordance with standard motor --- --- 0 ---
Electronic thermal characteristics are in accordance with constant torque motor --- --- 1 ---
Set Data
15 Terminal 5 Function 00-FF Selects terminal 5 function (factory set for multi-step speed reference 1) 0 3
Input 16 Terminal 6 Function 00-FF Selects terminal 6 function (factory set for multi-step speed reference 2) 0 4
Signal
17 Terminal 7 Function 00-FF Selects terminal 7 function (factory set for jog frequency reference) 0 6
Multi- 18 Terminal 8 Function 00-FF Selects terminal 8 function (factory set for internal base block by NO contact input) 0 8
function
Section Analog 19 Multi-function Analog Input 00-FF Selects multi-function analog input (terminal 16) function 0 F
Input
20 Multi-function Output 1 00-FF Selects multi-function contact output (terminals 9, 10) function (factory set for during running) 0 0
Output 21 Multi-function Output 2 00-FF Selects multi-function open collector (terminal 25) function (factory set for zero speed) 0 1
Signal
22 Multi-function Output 3 00-FF Selects multi-function open collector (terminal 26) function (factory set for speed agreed setting) 0 2
Positive/negative values of frequency reference determine FWD/ --- --- --- 0 0 0 0 0
REV operation
25 Analog Reference Card Positive frequency reference value determine forward operation: --- --- --- 1
(PAI14B) negative = 0 output
Not used 0 0 0 ---
BCD input 1% Resolution 0 0 0 0 0 0 0 0
BCD input 0.1% Resolution 0 0 0 1
BCD input 0.01% Resolution 0 0 1 0
Digital
g Reference Card BCD input 1 Hz Resolution 0 0 1 1
26 refer
(PDI08) (Frequency refer-
ence set mode) BCD input 0.1 Hz Resolution 0 1 0 0
BCD input 0.01 Hz Resolution 0 1 0 1
BINARY input 255/100% 0 1 1 1
BINARY input (input value displayed in decimal on operator) 1 0 0 0
O tion Card
Option 1F 0 0 0 0 0 0 1 0
Function Section 6F 0 0 1 0
Pulse Monitor Card
27 (PPO36F) (No. of out ut
output 10 F 0 1 0 0
pulses)
l )
12 F 0 1 1 0
36 F 1 0 0 0
Output frequency (max. frequency/100%) --- --- 0 0 0 1 0 0
Output current (rated current/ 100%) --- --- 0 1
Channel
1 output
out ut Output voltage ref. (Input voltage/ 100%) --- --- 1 0
DC voltage (400 V/100% for 200 V class, 800 V/100% --- --- 1 1
Analog Monitor Card for 400 V class)
28
(PAO08, PAO12) Output frequency (max. frequency/100%) 0 0 --- ---
Output current (rated current/ 100%) 0 1 --- ---
Channel
2 output
out ut Output voltage ref. (Input voltage/ 100%) 1 0 --- ---
DC voltage (400 V/100% for 200 V class, 800 V/100% 1 1 --- ---
for 400 V class)
27
OPERATION MENU
CONTROL CONSTANTS Cn-jj
Function Cn-jj Data Name Set Unit Set Range Factory Setting
01 Input voltage 0.1 V 0.0 to 255.0 V (200 V) 200.0 V (200 V)
0.0 to 510.0 V (400 V) 400.0 V (400 V)
02 Max. frequency 0.1 Hz 50.0 to 400.0 Hz 60.0 Hz*2
03 Max. voltage 0.1 V 0.0 to 255.0 V (200 V) 200.0 V*2
0.0 to 510.0 V (400 V)
04 Max. voltage frequency 0.1 Hz 0.0 to 400.0 Hz 60.0 Hz*2
V/f pattern Setting
05 Mid. output frequency 0.1 Hz 0.0 to 400.0 Hz 3.0 Hz*2
06 Mid. output frequency voltage 0.1 V 0.0 to 255.0 V (200 V) 15.0 Hz*2
0.0 to 510.0 V (400 V)
07 Min. output frequency 0.1 Hz 0.0 to 400.0 Hz 1.5 Hz*2
08 Min. output frequency voltage 0.1 V 0.0 to 255.0 V (200 V) 10.0 V*2
0.0 to 510.0 V (400 V)
Electronic thermal 09 Motor rated current 0.1 A *4 *1
Over-load relay ref.
Current
10 DC injection braking start frequency 0.1 Hz 0.0 to 10.0 Hz 1.5 Hz
11 DC injection braking current 1% 0 to 100%*6 50%
DC Injection Braking
12 DC injection braking time at stopping 0.1 sec 0.0 to 25.5 sec 0.5 sec
13 DC injection braking time at starting 0.1 sec 0.0 to 25.5 sec 0.0 sec
Frequency Limit Con-
Con 14 Frequency (speed) reference upper limit 1% 0 to 109% 100%
trol 15 Frequency (speed) reference lower limit 1% 0 to 109% 0%
16 Setting prohibit frequency 1 0.1 Hz 0.0 to 400.0 Hz 0.0 Hz
Frequency Jump
19 Setting prohibit frequency range 0.1 Hz 0.0 to 25.5 Hz 1.0 Hz
Operator Display 20 Operator display mode 1 0 to 39999 0
Change
S eed Agreed Detec-
Speed Detec 21 Up-to desired frequency setting 0.1 Hz 0.0 to 400.0 Hz 0.0 Hz
tion 22 Up-to frequency setting detection width/2 0.1 Hz 0.0 to 25.5 Hz 2.0 Hz
23 Carrier frequency upper limit 0.1 kHz 0.4 to 15.0 kHz *3
Carrier
C i F Frequency
24 Carrier frequency lower limit 0.1 kHz 0.4 to 15.0 kHz *3
Adjustment
25 Carrier frequency proportional gain 1 0 to 99 *3
26 Overtorque detection level 1% 30 to 200% 160%
Overtorque Detection
27 Overtorque detection time 0.1 sec 0.0 to 25.5 sec 0.1 sec
28 Stall prevention level during acceleration 1% 30 to 200% 170%
Stall Prevention 29 Constant HP area stall prevention limiter 1% 30 to 200% 50%
30 Stall prevention level during running 1% 30 to 200% 160%
Automatic reset & re- 36 No. of auto restart attempt 1 0 to 10 0
start operation
Momentary Power 37 Momentary power loss ride through time 0.1 sec 0.0 to 2.0 sec *1
Loss
38 Speed search deactivation current level 1% 0 to 200% 150%
Speed Search Control
39 Speed search decel time*7 0.1 sec 0.0 to 25.5 sec 2.0 sec
*1 Factory setting differs depending on inverter capacity (Sn-01 set value).
*2 Initial value differs depending on V/f (Sn-02 set value).
*3 Factory setting differs depending on main circuit transistors.
*4 Set in a range of 10 to 200% of inverter rated current.
*5 Motor rated current (Cn-09) is set as 100% level.
*6 For set value ≤ 50%: carrier frequency = 8 kHz For set value > 50%: carrier frequency = 1 kHz
*7 If set to zero, speed search will be disabled.
All items shaded must be set before starting operation.
28
OPERATION MENU
FREQUENCY REFERENCES An-jj
These references are used during multi-speed operation. Set values of An-jj can be changed or read during running in
DRIVE mode.
List of An-jj
An-jj Data Name Unit Setting Range Factory Setting
01 Frequency reference 1 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
02 Frequency reference 2 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
03 Frequency reference 3 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
04 Frequency reference 4 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
05 Frequency reference 5 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
06 Frequency reference 6 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
07 Frequency reference 7 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
08 Frequency reference 8 0.01 Hz 0.00 Hz to 400.00 Hz 0.00 Hz
09 Jog frequency reference 0.01 Hz 0.00 Hz to 400.00 Hz 6.00 Hz
Note: An-jj setting/reading units can be changed according to operator display mode (Cn-20) set values. The set unit at
factory setting is 0.01 Hz.
29
SELECTING AND SETTING FUNCTIONS
FREQUENCY
[Example] Sn-18 = 7
OUTPUT
Sn-04 = xx00
0: Frequency command from ex- • Open: bn-01 and bn-02 are selected.
ternal terminal * * TIME
• Closed: bn-03 and bn-04 are selected.
bn-01 bn-02
1: Frequency command from the bn-03 bn-04
operator
0: Start/stop control from exter- • S curve non-linear accel/decel is possible.
nal terminal Sn-06 = xx00
1: Start/stop control by the oper- 00: 0.2 sec of non-linear accel/decel
ator 01: 0 sec of non-linear accel/decel
• Stop procedure 10: 0.5 sec of non-linear accel/decel
Stopping mode can be selected according to the 11: 1.0 sec of non-linear accel/decel
application. FORWARD ROTATION COMMAND
REVERSE ROTATION COMMAND
Sn-04 = 00xx ACCELERATION
DECELERATION
00:
Ramp to stop MINIMUM OUTPUT
FREQUENCY (Cn–07)
DC INJECTION BRAKING
AT STOP (Cn–12)
01:
Coasting to a stop OUTPUT FREQUENCY
DC INJECTION BRAKING
MINIMUM OUTPUT FREQUENCY
10:
Full-range DB stop (Cn–07) START FREQUENCY
(Cn–10)
11:
Coasting stop with timer (Re- S–curve characteristics are
indicated by circled points
startable after the deceleration
time set in bn-02 elapses.) Note: S-curve characteristics are not enabled at comple-
• Reverse rotation prevention tion of deceleration when the first and second digits
are 00.
Prevents accidental selection of reverse rotation.
Sn-05 = xx1x
100%
Cn–14
Cn–15
Cn–07
0 100%
FREQUENCY COMMAND
30
SELECTING AND SETTING FUNCTIONS
100%
TORQUE nect terminals 11-7) and in- NORMAL
ROTATION 1
INCREASE
put the start signal. Inching
REVERSE
starts. Depressing the JOG ROTATION
key on the digital operator FREQUENCY TIME
performs the same opera- JOG SIGNAL
ON
tion. FORWARD RUN
TORQUE ROTATION SIGNAL ON
DECREASE REVERSE RUN ON
ROTATION SIGNAL
NORMAL FREQUENCY
31
SELECTING AND SETTING FUNCTIONS
TERMINAL
Sn-04 = xxx1 Sn-10 = xx0x
NORMAL AND REVERSE
ROTATION COMMAND
Sn-15 = 03 0: Stall prevention during deceleration
MULTI SPEED Sn-16 = 04 enabled
COMMAND 1
MULTI SPEED
Sn-17 = 05 1: Stall prevention during deceleration
COMMAND 2
MULTI SPEED
Sn-18 = 06 disabled
COMMAND 3
JOG Sn-19 = 0F
FREQUENCY
FREQUEN-
FREQUEN- CY
CY
Cn-07
Cn-10 SETTING FREQUENCY REF.
TIME
TIME
CURRENT
Cn-11
CURRENT
Cn-11
Built-in Braking Resistor Protection
TIME TIME
Cn-12 Cn-13
Item name Parameter Factory
to be set Preset
Regenerative braking resis- Sn-11 0000
tor protection
Built-in braking resistors are protected by thermal simu-
lation. When a built-in braking resistor is used, select
xxx1 (protection effective). When an external braking re-
sistor unit is used, set xxxx0, and protect the resistor unit
with the built-in thermal relay. The thermal relay should
be wired in series with the inverter run command or the
external fault circuit.
Sn-11 = xxx0
0: Not protected
1: Protected
32
SELECTING AND SETTING FUNCTIONS
OUTPUT FREQUENCY
OUTPUT FREQUENCY
CLOSED Operation During Momentary Power Loss
ARBITRARY FREQUEN-
CY (SPEED) AGREED CLOSED FREQUENCY (SPEED)
CONTACT OUTPUT
SIGNAL
SIGNAL Item name Parameter Factory
to be set Preset
Frequency/CurrentMeterCalibration Function enabled/disabled Sn-11 0000
Compensating time for mo- Cn-37 0.7 s*
Item name Parameter Factory mentary power loss
to be set Preset Operation can be continued even when a momentary
Analog output gain bn-11 1.00 power loss occurs.
Analog output selection Sn-05 0000 *3G3IV-A2004-E
Frequency/current meter connected to the inverter can be Sn-11 = x0xx
calibrated without using a resistor for calibration. 0: Continuation function disabled
1: Continuation function enabled
FREQUENCY/CURRENT METER (1 mA full scale)
21 Set a compensation time (up to 2 sec) for Cn-37. For mo-
+ –
bn-11 FM tors of 2.2 kW capacity or below (of 200 V or 400 V class),
the compensating time is 0.5 sec to 1 sec.
22 If longer momentary power loss ride-thru is required, in-
stall back-up capacitor unit (option for small unit).
Sn-05 = 0xxx
0: Output frequency meter
1: Output current meter Speed Search Function
OutputFrequencyControl (Gain/Bias) Item name Parameter Factory
to be set Preset
Item name Parameter Factory Speed search function Sn-15 to 18 See p. 27
to be set Preset
The speed search function is used to start a free spinning
Frequency command gain bn-05 100% motor without tripping the inverter. Set “61” into any con-
Frequency command bias bn-06 0% stant from Sn-15 to Sn-18.
61: Search function from max. frequency
Output frequency
(gain/bias) can be set bn-05
freely according to 100%
frequency setting (0
to 10 V or 4 to 20 mA)
BIAS
GAIN
bn-06
FREQUENCY
0 10 V SETTING
(4 mA) (20 mA)
33
SELECTING AND SETTING FUNCTIONS
0%
Set value Function Set value Function 0V 5V 10 V
10 V 0V
00 FWD/REV RUN select 0B Not used MULTI-FUNCTION ANALOG INPUT MULTI-FUNCTION ANALOG INPUT
01 Operation signal select Local/ 0C Multi-function analog input en-
Remote abled (AUX) • FIG. (3) Sn-19 = 2 • FIG. (4) Sn-19 = 3
02 Option/inverter reference se- 0D to 1F Not used
lect 20 to 2F External fault 1
10%
03 Multi-step speed command 1 30 to 3F External fault 2 10%
04 Multi-step speed command 2 40 to 4F External fault 3 F BIAS1
F BIAS2 0%
05 Multi-step speed command 3 50 to 5F External fault 4 0V 5V 10 V
06 Jog frequency reference select 60 DC injection braking command 0%
–10% MULTI-FUNCTION ANALOG INPUT
07 Accel/decel time select (JOG with priority) 0V 10 V 0V
08 External base block (NO-con- 61 Search 1 MULTI-FUNCTION ANALOG INPUT
•
tact input) 62 Search 2
09 External base block (NC-con- 63 Energy-saving operation • FIG. (5) Sn-19 = 4 FIG. (6) Sn-19 = 5
tact input) 64 to 6F Not used 200%
10 UP command OVERTORQUE 100 V
DETECTION
11 DOWN command LEVEL
V BIAS
12 FJOG command
13 RJOG command
0%
0A Not used 0V 10 V 0V 10 V
MULTI-FUNCTION ANALOG INPUT MULTI-FUNCTION ANALOG INPUT
REDUCTION 100%
Item name Parameter Factory COEFFICIENT DC INJECTION
BRAKING
to be set Preset 1
CURRENT
0%
Multi-function output function Sn-20 to 22 See p. 27 0V 1V 10 V 0V 10 V
MULTI-FUNCTION ANALOG INPUT
MULTI-FUNCTION ANALOG INPUT
Functions of external output terminals 9-1, 25-27, and
26-27 can be switched
Function of terminal 9 and 10: set into Sn-20 Actual accel/decel time = Actual accel/decel time (bn-01 to bn-04)
Reduction coefficient
Function of terminal 25 and 27: set into Sn-21
Function of terminal 26 and 27: set into Sn22
Set value
00
Function
In operation*
Set value
07
Function
Low voltage detected
Energy Saving Operation Function
01 Zero speed* 08 Base blocked
02 Speed agreed* 0B Over torque detected Item name Parameter Factory
03 Free speed agreed 0D
0E
Braking resistor failure
Fault
to be set Preset
04 Speed agreed detection (less
than set value) Energy saving level gain bn-09 80%
05 Speed agreed detection (more
than set value)
06 Inverter operation ready
If reduced output voltage is required after acceleration,
the energy-saving function can be used to reduce it.
(*: Factory setting prior to shipment) This function helps to eliminate motor/system vibration.
Set “63” for any constant from Sn-15 to Sn-18.
Multi-functionAnalogOutputMonitor
NORMAL ROTATION
OPERATION COMMAND
Item name Parameter Factory
ENERGY-SAVING
to be set Preset OPERATION COMMAND
Operation signal selection 2 Sn-05 0000
Output frequency or motor current can be monitored.
OUTPUT
(Standard function) VOLTAGE ACCEL- (Cn-02 to 08 V/f) x bn-09 DECEL-
ERATION ERATION
Sn-05 = 0xxx
0: Output frequency is monitored.
1: Motor current is monitored.
34
SELECTING AND SETTING FUNCTIONS
er frequency
Slip Compensation Speed Control Cn-25 0
For the change of speed bn-08 0.0%
Item name Parameter Factory control characteristics Cn-34 30%
to be set Preset
Cn-35 2.0 s
Motor rated slip bn-08 0.0%
Motor rated current Cn-09 See p. 28
Motor no-load current Cn-34 30%
Slip compensation primary Cn-35 0.0 s*
delay time
Simple speed control (slip compensation) is available
without motor speed detection (PG or TG). Frequency
command from f1 to f2 eliminates speed fluctuations
caused by varying load.
TORQUE
f1 f2
LOAD TORQUE
SLIP
35
STANDARD CONNECTIONS AND TERMINAL FUNCTIONS
P 3 4
OVERLOAD 1 2
RELAY
TRIP
PO
CONTACT
P B
B
BRAKING RESISTOR LEVEL
UNIT (OPTIONAL) DETECTOR
N
MCCB MC
BRAKING UNIT
THREE-PHASE,
L1(R) L1(R) B0/ (OPTIONAL)
200/208/220 V B1/
50 Hz L2(S) L2(S)
200/208/220/ SYSDRIVE 3G3IV MOTOR
230 V, 60 Hz L3(T) L3(T) T1(U)
r T2(V) IM
THRX OFF ON MC M COOLING
s FAN T3(W)
NOTE6
MC SA
G(E)
THRX
0V
P
Notes: 1. indicates shielded leads and twisted-pair shielded leads.
36
STANDARD CONNECTIONS AND TERMINAL FUNCTIONS
MAIN CIRCUIT
200 to 230 V 380 to 460 V
Termi-
Termi 20P4 to 27P5 2011 to 2022 2030 to 2075 40P4 to 47P5 4011, 4015 4018 to 4045 4055 to 4300
nall
0.5 to 10 HP 15 to 30 HP 40 to 100 HP 0.5 to 10 HP 15 HP (11 kW), 25 to 60 HP 75 to 400 HP
(0.4 to 7.5 kW) (11 to 22 kW) (30 to 75 kW) (0.4 to 7.5 kW) 20 HP (15 kW) (18.5 to 45 kW) (55 to 300 kW)
L1 (R) Main circuit power
ower unit
L2 (S)
L3 (T)
T1 (U) Inverter output
out ut
T2 (V)
T3 (W)
B0/ --- Braking
g unit connector --- --- Braking
g unit connector ---
(B1/ – B0) (B1/ – B0)
B1/ Braking
g resistor unit DC bus (B1/ – B0/) Braking
g resistor unit Braking
g resistor unit DC bus (B1/ – B0/)
connector (B1/ – B2) connector (B1/ – B2) connector (B1/ – B2)
B2 DC bus (B1/ – ) --- DC bus (B1/ – ) DC bus (B1/ – B0/) ---
Braking unit connector Braking unit connector
(1 – ) (1 – )
3 (P3) --- DC bus (1 – ) --- DC bus (1 – )
M i circuit
Main i it capacitor
it M i circuit
Main i it capacitor
it
1 (P1)
(3 – ) (3 – )
I1 (r) --- Cooling fan power
ower Cooling fan power
ower --- Cooling fan power input ---
i
input
t i
input
t
I2 (s) Cooling fan power input
ower in ut
é1 – é2 200:
200 200 to
t
é2 200 --- --- --- 230 VAC
(s 200)
é1 – é2 400: 380 to
é2 400 460 VAC
(s 400)
x --- External power
ower su
supply
ly --- External power
ower su
supply
ly
(220 VAC,
VAC 10 VA) (220 VAC,
VAC 10 VA)
y
G (E) Grounding (class 3 grounding, 100 Ω or less)
CONTROL CIRCUIT
Classification Terminal Signal Function Description Signal Level
1 Forward operation-stop signal Forward run at closed, stop at open Photo-coupler insula-
tion Input +24 VDC
2 Reverse operation-stop signal Reverse run at closed, stop at open 8 mA
3 External fault input Fault at closed, normal state at open
4 Fault reset input Reset at closed
Sequence 5 Master/Aux. change (Multi-step speed Aux. freq. ref. at “closed” Multi-function contact input: the following sig-
Output
Out ut Sig-
Sig ref. 1) nals available to select. Forward/reverse se-
lect, run mode select, multi-speed select, jog
nall 6 Multi-step speed ref. 2 Effective at “closed” frequency select, accel/decel time select,
external fault,
fault external base block stop,
stop hold
7 Jog command Jog run at “closed” command,, inverter overheat prediction,, DB
command aux
command, aux. input effective
effective, speed search
search,
8 External coasting stop Inv. output stop at “closed” energy-saving operation
11 Sequence control input common termi- ---
nal
15 Power supply terminal for speed ref. Speed ref. power supply +15 V (Allowable cur-
rent 20 mA max.)
13 Master speed frequency ref. 0 to +10 V/100% freq. 0 to +10 V (10 kΩ)
14 4 to 20 mA/100% freq. 4 to 20 mA (250 Ω)
16 Aux. frequency ref. 0 to 10 V/100% Multi-function contact input: one of the follow- 0 to +10 V (10 kΩ)
Analog In- ing signals available to select, speed com-
put Signal mand, speed gain, speed bias, overtorque,
overvoltage bias, rate of accel/decel DB cur-
rent
17 Common terminal for control circuit 0 ---
12 Connection to shield sheath of signal --- ---
lead
9 During running (NO) Run at “closed” Multi-function contact output: one of the Dry contact
following signals available to output.
out ut. Contact ca acity:
capacity:
10 Output during running, zero speed, syn- 250 VAC 1 A or less
chronized sspeed,
eed, arbitrary sspeed
eed 30 VDC 1 A or less
25 Zero speed detection Makes at min, freq. (Cn-07) agreed,
d ffrequency ddetection,
t ti overtorque,
t Open collector output
or less undervoltage, run mode, coasting stop, +48 V 50 mA or less
Sequence
S braking resistor overheat
26 Speed agreed detection Makes when the freq. reach-
Input Signal es to ±1% of set freq.
27 Open collector output common ---
18 Fault contact output (NONC) Fault at closed between terminals 18 and 20 Dryy contact
F lt att open between
Fault b t t i l 19 and
terminals d 20 Contact capacity: 250 VAC
19 1 A or less 30 VDC 1 A or
l
less
20
Analog 21 Frequency meter output 0 to 10 V/100% freq. Ammeter output selection available 0 to 11 V max. 2 mA or
Output Sig-
Sig less
nal 22 Common
37
TROUBLESHOOTING
Protection Functions
Fault
Monitor
Protection function Explanation contact
display
output
Main circuit When the inverter power voltage drops, torque becomes insufficient and mo- uu1 (UV1) Operation
voltage low tor is overheated. Inverter output is stopped when the main circuit DC voltage
becomes lower than the low voltage detection level for 15 ms or longer
longer, or
Momentary about 2 seconds or longer if the momentary power loss rede-thru function is
power loss used. Detection level: Approximately 210 V or less for 200 V class and 420 V
Low protection
voltage or less for 400 V class
protec- Control circuit The inverter output is shut-off when the control circuit voltage drops below the uu2 (UV2) Operation
o
tion low voltage low voltage level.
Main circuit The inverter output is shut-off when no answer back received from the main uu3 (UV3) Operation
soft charge circuit soft-start contactor.
contactor de-
fective
Overcurrent protection The inverter output is shut-off when the inverter output current becomes ap- %c (OC) Operation
prox. 200% and above of inverter rated current..
Ground-fault protection The inverter output is shut-off when a ground-fault occurs at the inverter out- Operation
put side and the ground-fault current exceeds approx. 50% of the inverter
rated current.
Overvoltage protection The inverter output is shut-off when the main circuit DC voltage becomes %u (OV) Operation
excessive because of regeneration energy caused by motor deceleration and
negative load. Detection level: Approx. 800 V for input voltage set 400 V and
above Approx. 700 V for input voltage set 400 V or less and approx. 400 V
for 200 V class
Fuse blown The inverter output is shut-off when the main circuit transistor fails. The fuse fu (FU) Operation
clears to prevent wiring from being damaged by the short-circuit current.
Cooling fin overheat The inverter output is shut-off when the ambient temperature rises and the %h (OH) Operation
heat sink fin reaches 90°C. Please check for a defective cooling fan or
clogged filter.
Motor Inverter output is stopped when motor overload is detected by the electronic %l1 Operation
thermal overload in the inverter. Either a inverter duty constant-torque spe- (OL1)
cialized motor or general-purpose motor can be selected. If more than one
motor is drive, overload protection should be disabled. Use a thermal relay or
Over- thermal protector for each motor.
load
l d
Inverter The inverter output is shut-off when the electronic thermal overload reaches %l2 Operation
protec-
or exceeds the inverse time limit of 112% of the inverter’s rated current oc- (OL2)
tion
curs. Maximum rated overload: 150%, 1 min.
Overtorque The motor operates according to a preset mode when the inverter output cur- %l3 Operation
detection rent exceeds the overtorque detection level. This function is used to protect (OL3)
the machine or to monitor the output torque.
Braking transistor fault Inverter output is shut-off when an error occurs in the braking transistor. rr (rr) Operation
Braking resistor over- For 5 HP (3.7 kW) or less (200 V), 3 HP (2.2 kW) or less (400 V), an optional rh (rH) Operation
heat dedicated resistor can be installed. The resistor is monitored by the electronic
thermal switch for overheating. The inverter output is shut-off when a speci-
fied temperature is reached.
External fault signal in- When an external alarm signal is input, the inverter operates according to a efj EF3 Operation
put preset stop method (coasting to a stop, or ramp to stop) to EF8
Control circuit fault, The inverter output is shut-off when a transmission error occurs in the control cpf00 to Operation
communication option circuit or a component fails. The inverter output is also shut-off when a spe- cpf05
fault, option fault cialized option such as the digital operator is not properly connected. cpf06
cpf20 err
38
TROUBLESHOOTING
39
TROUBLESHOOTING
40
TROUBLESHOOTING
41
APPLICATION PRECAUTIONS
Selection
WITH AC REACTOR
When the inverter is connected directly to a large-capacity power transformer 4000
FOR POWER SUPPLY
(1000 kVA or greater with 10 m or less cable length) or when a phase advance POWER
COORDINATION
capacitor is switched, excess peak current may occur in the power feed circuit CAPACITY
(kVA)
600 WITHOUT
and the converter section may be damaged. To avoid this, use an AC reactor AC REACTOR
(option) on the inverter input side. An AC reactor is also required when a thyris-
0 60 400
tor converter such as a DC drive is connected to the same power system. INVERTER CAPACITY (kVA)
When a special motor is used or more than one motor is driven in parallel with a single inverter, select the inverter capacity
so that 1.1 times of the total motor rated current does not exceed the inverter rated output current.
The motor starting and accelerating characteristics of the motor driven by an inverter are restricted by the overload current
ratings of the inverter. Compared to running with commercial power supply, lower torque output should be expected. If high
starting torque is required, use an inverter of higher capacity or increase the capacities of both the motor and the inverter.
When an error occurs, a protective circuit is activated and the inverter output is turned off. However, the motor cannot be
stopped immediately. Use a mechanical brake and hold the equipment for an emergency stop if necessary.
Terminals B1/P, B0/N, B2, and N are for Omron options. Do not connect other equipment.
Installation
Avoid oil mist or dust. Place the inverter in a clean area or house it in a totally enclosed case so that no contamination enters.
To use the totally enclosed case, select the cooling method and panel dimensions so the inverter ambient temperature will
be within the allowable range.
Do not install the inverter on flammable material, such as wood.
Install the inverter on a wall with the longer side in the vertical position.
Setting
The inverter can be driven at an output frequency of up to 400 Hz with the digital operator. Setting errors may create a
dangerous situation. Set the upper limit with the upper limit frequency setting function. (Maximum output frequency in ex-
ternal input signal operation is preset to 60 Hz at the factory.)
Large Dc injection braking operating voltages and times may cause motor overheating.
Motor accel/decel time is determined by the motor generating torque, load torque, and load inertia WK2 (GD2). If the stall
prevention function is activated during accel/decel, set the accel/decel time longer. After the stall prevention function is
activated, accel/decel time is extended to a length that the inverter can handle. To shorten the accel/decel time, increase
the capacity of the inverter and possibly the motor.
Operation
Applying power to inverter output terminals T1 (U), T2 (V), or T3 (W) will damage the inverter. Double check wiring and
sequence before turning the power on.
If magnetic contactor (MC) is used on the primary side of the inverter, do not use the MC for starting and stopping the invert-
er. Otherwise, the inverter life may be reduced.
After turning power to the inverter off, electric charges in the internal capacitors are retained temporarily. Wait until the
charge lamp goes off before touching the inside of the inverter.
42
APPLICATION PRECAUTIONS
Installation and selection of molded-case circuit breaker
On the input power side, a molded case circuit breaker (MCCB) to protect inverter primary wiring should be installed. The
inverter power-factor (depending on power voltage, output frequency, and load) must be taken into account for selecting
MCCB. If a full electromagnetic MCCB is to be used, select a larger capacity because the operating characteristics are
altered by harmonic current. A leakage current breaker threshold of 200 mA and above, or of inverter use is recommended.
If the inverter is connected to a distant motor, (especially when low frequency is output,) motor torque decreases because
of voltage drop in the cable. Use sufficiently heavy wire.
When a digital operator is to be installed separately from the inverter, use the Omron connection cable (option). For remote
control with analog signals, connect the operating pot or operating signal terminal and the inverter within 30 m of the invert-
er. The cable must be routed separately from power circuits (main circuit and relay sequence circuit) so that it is not sub-
jected to inductive interference by other equipment. If fre-
quencies are set not only from the digital operator but also 12 SHIELDED INSULATED WIRE
with external frequency controller, use twisted pair shielded CONNECTION TERMINAL
TWISTED PAIR 0V
SHIELD WIRE
43
OPTIONS
ntlp:photo
ntlp:photo
ntlp:photo ntlp:photo
PSIG PSIF
SYSMAC BUS (wire) SYSMAC BUS II (optical)
Interface Card Interface Card
OPTIONAL CARDS
L1(R)
3-PHASE
POWER L2(S) IM
SUPPLY L3(T)
ntlp:photo
ntlp:photo
ntlp:photo
ntlp:photo ntlp:photo ntlp:photo
44
OPTIONS
OPTIONAL UNITS
Type Name Model (Code No.) Function Pag
e
Analog reference 3G3IV-PAI14U Allows high precision, high resolution analog speed reference setting. 45
card Input signal level: 0 to +10 VDC (20 KΩ) 1 channel 4 to 20 mA DC
(250 Ω) 1 channel
S eed
Speed Input resolution: 14 bits (1/16384)
(Fre- 3G3IV-PAI14B Allows bipolar high precision, high resolution analog speed reference 45
quen- setting.
cy) Input signal level: 0 to ±10 VDC (20 KΩ) 4 to 20 mA DC (250 Ω) 3
Refer- channels
ence Input resolution: 13 bits (1/8192)
Option
Card Digital reference 3G3IV-PDI08 Allows 8 bits digital speed reference set. 45
card Input signal: binary 8 bits/BCD 2 digits + code
Built-in Input voltage: +24 V (insulation)
Type
Ty e Input current: 8 mA
(Connec- Analog monitor 3G3IV-PAO08 Outputs analog signal for monitoring inverter output state (output freq., 45
tor card output current etc.).
Mounted) Output resolution: 8 bits (1/256)
Output voltage: 0 to +10 V (non isolated)
Output channel: 2 channels
3G3IV-PAO12 Outputs analog signal for monitoring inverter output state (output freq., 45
Monitor output current etc.).
Option Output resolution: 11 bits (1/2048)
Card Output voltage: 0 to +10 V (non isolated)
Output channel: 2 channels
Pulse output card 3G3IV-PPO36F Outputs pulse train signal corresponding to the inverter frequency 45
Output pulse: 1F, 6F, 10F, 12F, 36F (F: output freq.)
Output voltage: ±12 V ±10 % (Insulation)
Output current: 20 mA max.
Digital monitor 3G3IV-PJVOP101 Allows freq. or current digital monitor displays and fault indications. 46
Run/stop operation and constant settings are protected against tam-
pering on site.
Adapter panel for 3G3IV-PJVOP109 Adapter panel is capable of mounting on the front of inverter unit with 46
digital operator/ its special cable. Use the adapter panel special cable.
digital monitor
Mounted
on the In- Adapter panel 3G3IV-PCN122 (1 m) Used for the remote operation of digital operator or monitor with adapt- 46
verter special cable er panel (PJVOP109)
( )
Unit 1m 3m
Cable length: 1m,
3G3IV-PCN322 (3 m)
Special cable for 3G3IV-PCN121 (1 m) Used for the operation of digital operator or monitor when removed 46
digital operator/ from the front of inverter unit
Option Cable length; 1 mm, 3 m
Unit digital monitor 3G3IV-PCN321 (3 m)
(with blank cov-
er)
Braking unit 3G3IV-PCDBRjjjj For motor decel tie reduction, use this with braking resistor unit. 47
48
Braking resistor 3G3IV-PLKEBjjjj Motor regenerative energy dissipation by the resistor reduces the decel 47
Separate- unit time. (duty cycle 10% ED) 48
ly
mounted Braking resistor 3G3IV- Motor regenerative energy dissipation by the resistor reduces the decel 47
Type
Ty e (built-in type) PERF150WJj01 time. (duty cycle 3% ED) 48
Backup capacitor 3G3IV-PP0010 For power loss of less than 2 sec. 48
for momentary 3G3IV-PP0020
power loss
PERIPHERAL UNITS
Name Model (Code No.) Function Page
45
OPTIONS
ANALOG REFERENCE CARD ANALOG MONITOR CARD
Unidirectional-type
ntlp:photo
ntlp:photo
MCCB INVERT ER
L1(R) T1(U) MOTOR MCCB INVERTER
L2(S) T2(V) MOTOR
L3(T) T3(W)
3G3IV
0-10 V 3G3IV
2CN
4-20 mA
0V G(E)
0-±10 V TC1
(4-20 m)
BIAS TC2
MASTER 0-±10 V
(4-20 m) 2CN
GAIN
0-±10 V TC3 2CN
(4-20 m)
TC4
G(E)
0V
ntlp:photo
2CN
OPERATOR ntlp:photo
CONTROL EXTERNAL OPTION CARD 3G3IV-PJVOP100
BOARD TERMINALS OPTICAL
CV500-RM211
MTG. HOLE (2) CONNECTOR
Remote I/O
Master Unit
46
OPTIONS
DIGITAL OPERATOR/ADAPTER DIGITAL OPERATOR/SPECIAL
PANEL FOR DIGITAL MONITOR CABLE FOR DIGITAL MONITOR
CABLE CONNECTOR
TO INVERTER
RUBBER BUSHING
ADAPTER PANEL
CABLE CONNECTOR
TO OPERATOR/MONITOR
ntlp:photo
BLANK COVER
ntlp:photo Weight: 0.66 lb (0.3 kg)
DIGITAL
MONITOR
DIGITAL MONITOR
MODEL 3G3IV-PJVOP101
0.73
0.07 (18.5) 0.02
(1.8) 0.64 (0.5)
(16.2)
0.45
(11.5)
0.09 1.97(50)
(2.25) 2.30(58.5) 0.09
(2.25)
0.39
(10)
47
OPTIONS
STANDARD SPECIFICATIONS AND APPLICATION
Built-in Type Separate Installation Type
Inverter
Braking Resistor Braking Unit Braking Resistor Unit
MODEL MODEL 1 (0.75) A2007 201 200 Ω 1 125 --- --- 20P7 70 W 200 Ω 1 4 125
OF 3G3IV- OF 2 (1.5) A2015 101 100 Ω 1 125 --- --- 21P5 260 W 100 Ω 1 5 125
70 Ω 260 W 70 Ω
PERF150WJ 3G3IV- 3 (2.2) A2022 700 1 120 --- --- 22P2 1 4 120
10 (7.5) A2075 --- --- --- --- --- --- 27P5 780 W 20 Ω 1 2 125
15 (11) B2110 --- --- --- --- 2015 1 2011 2400 W 13.6 Ω 1 1 125
200 V to
ntlp: ntlp: 230 V 20 (15) B2150 --- --- --- --- 2015 1 2015 3000 W 10 Ω 1 1 125
photo photo 25 (18.5) B2180 --- --- --- --- 2022 1 2018 4800 W 8 Ω 1 1 125
30 (22) B2220 --- --- --- --- 2022 1 2022 4800 W 6.8 Ω 1 1 125
40 (30) B2300 --- --- --- --- 2015 2 2015 3000 W 10 Ω 2 1 125
50 (37) B2370 --- --- --- --- 2015 2 2015 3000 W 10 Ω 2 1 100
60 (45) B2450 --- --- --- --- 2022 2 2022 4800 W 6.8 Ω 2 1 120
75 (55) B2550 --- --- --- --- 2022 2 2022 4800 W 6.8 Ω 2 1 100
100 (75) B2750 --- --- --- --- 2022 3 2022 4800 W 6.8 Ω 3 1 110
0.5 (0.4) A4004 751 750 Ω 1 230 --- --- 40P7 70 W 750 Ω 1 7 230
BRAKING RESIS- 1 (0.75) A4007 751 750 Ω 1 130 --- --- 40P7 70 W 750 Ω 1 7 130
TOR UNIT MODEL 2 (1.5) A4015 401 400 Ω 1 125 --- --- 41P5 260 W 400 Ω 1 6 125
5 (3.7) A4037 --- --- --- --- --- --- 43P7 390 W 150 Ω 1 4 135
7.5 (5.5) A4055 --- --- --- --- --- --- 45P5 520 W 100 Ω 1 3 135
10 (7.5) A4075 --- --- --- --- --- --- 47P5 780 W 75 Ω 1 2 130
15 (11) B4110 --- --- --- --- --- --- 4011 1040 W 50 Ω 1 2 135
20 (15) B4150 --- --- --- --- --- --- 4015 1560 W 40 Ω 1 2 125
ntlp:
25 (18.5) B4180 --- --- --- --- 4030 1 4018 4800 W 32 Ω 1 1 125
photo 380 V to 30 (22) B4220 --- --- --- --- 4030 1 4022 4800 W 27.2 Ω 1 1 125
460 V
40 (30) B4300 --- --- --- --- 4030 1 4030 600 W 20 Ω 1 1 125
50 (37) B4370 --- --- --- --- 4045 1 4037 9600 W 16 Ω 1 1 125
60 (45) B4450 --- --- --- --- 4045 1 4045 9600 W 13.6 Ω 1 1 125
75 (55) B4550 --- --- --- --- 4030 2 4030 6000 W 20 Ω 2 1 135
100 (75) B4750 --- --- --- --- 4045 2 4045 9600 W 13.6 Ω 2 1 145
150 (110) B411K --- --- --- --- 4030 3 4030 6000 W 20 Ω 3 1 100
200 (160) B416K --- --- --- --- 4045 4 4045 9600 W 13.6 Ω 4 1 140
250 (185) B418K --- --- --- --- 4045 4 4045 9600 W 13.6 Ω 4 1 120
300 (220) B422K --- --- --- --- 4045 5 4045 9600 W 13.6 Ω 5 1 125
400 (300) B430K --- --- --- --- 4045 6 4045 9600 W 13.6 Ω 6 1 110
INTERCONNECTIONS
• Built-in Type • Separate Installation Type
(200 to 230 V 0.5 to 5 HP (0.4 to 3.7 kW) (380 to 460 V 15 HP (11 kW) 20 HP (15 kW))
380 to 460 V 0.5 to 3 HP (0.4 to 2.2 kW)) OVERLOAD RELAY TRIP
CONTACT
Used sequencer to break power supply
side on overload relay trip contact. BRAKING RE-
SISTOR UNIT
BRAKING RESISTOR
MCCB MC
MCCB
MC L1(R) 3G3IV MOTOR
POWER SUPPLY
POWER SUPPLY MOTOR 3-PHASE L2(S) T1(U)
3-PHASE 3G3IV L3(T) T2(V)
T3(W)
FAULT CONTACT
FAULT CONTACT
48
OPTIONS
MOUNTING OF BRAKING BRAKING UNIT DIMENSIONS: Inch (mm)
RESISTOR
(52) MIN.
4-0.236 (6) DIA. MTG. HOLES
2.44 1.81
2.05
(62) (46)
3.94 (100) MIN.
10
AIR
0.59
(15)
10.24 (260)
11.02 (280)
9.84 (250)
ntlp:photo
BRAKING UNIT
0.59
(15)
AIR
3.94 (100)
3.94(100)
2.56 (65) 12 0.59 1.6
3.04 (100) (15) 2.91 (74)
MIN.
1.18 (30) MIN. 5.51 (140) 1.18 (30) MIN. 6.30 (160) Model PCDBR2015
2-LEAD INLET CONVER MTG. SCREW
Weight: 33 lb (15 kg)
5.91 (150)
Braking Resis- Dimensions: Inch (mm)
Voltage tor Unit Model DWG A B C D MTG. Approx.
MIN.
3G3IV- Screw Weight
PLKEBjjjj 1b (kg)
20P7 1 4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260) M5 x 3 6.62 (3.0)
B
D
21P5 1 5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5 x 4 9.93 (4.5)
22P2 1 5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5 x 4 9.93 (4.5) Drawing 1
23P7 1 5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5 x 4 11.0 (5.0)
1
5.91 (150)
200 to 25P5 9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6 x 4 16.6 (7.5)
230 V 27P5 1 9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6 x 4 18.8 (8.5) 1.18 C 1.18
MIN.
2011 2 10.47 (266) 21.38 (543) 9.69 (246) 13.39 (340) M8 x 4 22.1 (10) (30) (30)
MIN. A MIN.
2015 2 14.02 (356) 21.38 (543) 13.23 (336) 13.39 (340) M8 x 4 33.1 (15) 5.91(150)
2018 2 17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8 x 4 41.9 (19)
2022 2 17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8 x 4 41.9 (19)
7.87 (200)
40P7 1 4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260) M5 x 3 6.62 (3.0) MTG. SCREW
41P5 1 5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5 x 4 9.93 (4.5)
MIN.
42P2 1 5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5 x 4 9.93 (4.5)
43P7 1 5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5 x 4 11.0 (5.0)
380 to 45P5 1 9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6 x 4 16.6 (7.5)
460 V 47P5 1 9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6 x 4 18.8 (8.5)
B
D
4011 2 13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6 x 4 35.3 (16) Drawing 2
4015 2 13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6 x 4 39.7 (18)
4018 2 17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8 x 4 41.9 (19)
7.87 (200)
4022 2 17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8 x 4 41.9 (19)
4030 2 14.20 (356) 37.64 (956) 13.23 (336) 29.13 (740) M8 x 4 55.2 (25) 1.97 C 1.97
MIN.
4037 2 17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8 x 4 72.8 (33) (50) (50)
MIN. A MIN. 10.24 (260)
4045 2 17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8 x 4 72.8 (33)
Use this unit for 3 HP (2.2 kW) and below • Connection with Inverter • Dimensions: Inch (mm)
and to extend the inverter’s power loss ride-
thru ability to 2 seconds. (Not required BACK UP
CAPACITOR 3.54(90) 3.78 (96)
above 3 HP 2.2 kW) G(E) UNIT
B1P 9.84(250)
200 to 230 V Model 3G3IV-PP0010 MCCB
380 to 460 V Model 3G3IV-PP0020 L1(R)
B1/ B2
L1(R) L1(U) MOTOR
POWER
11.81 (300)
11.02 (280)
ntlp:photo
BACKUP CAPACITOR UNIT
FOR MOMENTARY POWER G (E)
LOSS
Weight: 4-0.236 (6) DIA MTG. SCREW
4.4 lb (2 kg)
49
OPTIONS
AC REACTOR (Model 3G3IV-PUZBAB, for Input, 50/60 Hz)
(Example of Connection)
AC REACTOR
MCCB
L1(R) T1(U) MOTOR
L1(R)
L2(S) L2(S) 3G3IV T2(V) IM
ntlp:photo
L3(T) L3(T) T3(W)
WITH AC REACTOR
When power capacity is significantly large compared FOR POWER SUPPLY
POWER COORDINATION
to inverter capacity, or when the power-factor needs SUPPLY
CAPACITY
to be improved, connect the AC reactor. Select an AC (kVA) WITHOUT
AC REACTOR
reactor according to the motor capacity.
200 to 230 V
Max. Applicable Motor Output Current Induc- Draw- Dimensions: Inch (mm) Approx. Loss
HP (kW) Value A tance mH Weight lb (kg) Watt
ing A B B1 C D E F H J K L M
0.5 (0.4) 2.5 4.2 1 4.72 (120) 2.80 (71) --- 4.72 (120) 1.57 (40) 1.97 (50) 4.13 (105) 0.79 (20) M6 0.41 (10.5) 0.28 (7) M4 5.51 (2.5) 15
1 (0.75) 5 2.1 4.72 (120) 2.80 (71) --- 4.72 (120) 1.57 (40) 1.97 (50) 4.13 (105) 0.79 (20) M6 0.41 (10.5) 0.28 (7) M4 5.51 (2.5) 15
2 (1.5) 10 1.1 5.12 (230) 3.46 (88) --- 5.12 (130) 1.97 (50) 2.56 (65) 5.12 (130) 0.87 (22) M6 0.45 (11.5) 0.28 (7) M4 6.62 (3) 25
3 (2.2) 15 0.71 5.12 (230) 3.46 (88) --- 5.12 (130) 1.97 (50) 2.56 (65) 5.12 (130) 0.87 (22) M6 0.45 (11.5) 0.28 (7) M4 6.62 (3) 30
5 (3.7) 20 0.53 2 5.12 (230) 3.46 (88) 4.49 (114) 4.13 (105) 1.97 (50) 2.56 (65) 5.12 (130) 0.87 (22) M6 0.45 (11.5) 0.28 (7) M4 6.62 (3) 35
7.5 (5.5) 30 0.35 5.12 (130) 3.46 (88) 4.69 (119) 4.13 (105) 1.97 (50) 2.76 (70) 5.12 (130) 0.87 (22) M6 0.35 (9) 0.28 (7) M4 6.62 (3) 45
10 (7.5) 40 0.265 5.12 (130) 3.86 (98) 5.47 (139) 4.13 (105) 2.95 (75) 2.95 (75) 5.12 (130) 0.87 (22) M6 0.45 (11.5) 0.28 (7) M4 8.82 (4) 50
15 (11) 60 0.18 6.30 (160) 4.13 (105) 5.81 (147.5) 5.12 (130) 2.95 (75) 3.15 (80) 6.30 (160) 0.98 (25) M6 0.39 (10) 0.28 (7) M4 13.23 (6) 65
20 (15) 80 0.13 7.09 (180) 3.94 (100) 6.10 (155) 5.91 (150) 2.95 (75) 3.35 (85) 7.09 (180) 0.98 (25) M6 0.39 (10) 0.28 (7) M4 17.64 (8) 75
25 (18.5) 90 0.12 7.09 (180) 3.94 (100) 5.91 (150) 5.91 (150) 2.95 (75) 3.15 (80) 7.09 (180) 0.98 (25) M6 0.39 (10) 0.28 (7) M4 17.64 (8) 90
30 (22) 120 0.09 7.09 (180) 3.94 (100) 6.10 (110) 5.91 (150) 2.95 (75) 3.15 (80) 7.09 (180) 0.98 (25) M6 0.39 (10) 0.28 (7) M4 17.64 (8) 90
40 (30) 160 0.07 8.27 (210) 3.94 (100) 6.69 (170) 6.89 (175) 2.95 (75) 3.15 (80) 8.07 (205) 0.98 (25) M6 0.39 (10) 0.28 (7) M10 26.46 (12) 100
50 (37) 200 0.05 8.27 (210) 4.53 (115) 7.20 (182.8) 6.89 (175) 2.95 (75) 3.74 (95) 8.07 (205) 0.98 (25) M6 0.39 (10) 0.28 (7) M10 33.07 (15) 110
60 (45) 240 0.044 9.45 (240) 4.96 (126) 8.58 (218) 8.47+0.2 5.91 4.33 9.45 (240) 0.98 (25) M6 0.32 (8) 0.28 (7) M10 50.71 (23) 125
(215+5) (150) (110)
75 (55) 280 0.038 9.45 (240) 4.96 (126) 8.58 (218) 8.47+0.2 5.91 4.33 9.45 (240) 0.98 (25) M8 0.32 (8) 0.39 M12 50.71 (23) 130
(215+5) (150) (110) (10)
380 to 460 V
Max. Applicable Motor Out- Current Indu- Draw- Dimensions: Inch (mm) Approx. Loss
put HP (kW) Value A tance mH ing Weight lb (kg) Watt
A B B1 C D E F H J K L M
0.5 (0.4) 1.3 18.0 1 4.72 (120) 2.80 (71) --- 4.72 (120) 1.57 (40) 1.97 (50) 4.13 (105) 0.79 (20) M6 0.41 (10.5) 0.28 (7) M4 5.51 (2.5) 15
1 (0.75) 2.5 8.4 4.72 (120) 2.80 (71) --- 4.72 (120) 1.57 (40) 1.97 (50) 4.13 (105) 0.79 (20) M6 0.41 (10.5) 0.28 (7) M4 5.51 (2.5) 15
2 (1.5) 5 4.2 5.12 (230) 3.46 (88) --- 5.12 (130) 1.97 (50) 2.76 (70) 5.12 (130) 0.87 (22) M6 0.35 (9) 0.28 (7) M4 5.51 (2.5) 25
3 (2.2) 7.5 3.6 5.12 (230) 3.46 (88) --- 5.12 (130) 1.97 (50) 2.76 (70) 5.12 (130) 0.87 (22) M6 0.35 (9) 0.28 (7) M4 6.62 (3) 35
5 (3.7) 10 2.2 5.12 (230) 3.46 (88) --- 5.12 (130) 1.97 (50) 2.56 (65) 5.12 (130) 0.87 (22) M6 0.45 (11.5) 0.28 (7) M4 6.62 (3) 43
7.5 (5.5) 15 14.2 5.12 (130) 3.46 (98) --- 5.12 (130) 1.97 (50) 2.95 (75) 5.12 (130) 0.87 (22) M6 0.45 (11.5) 0.28 (7) M4 6.62 (3) 50
10 (7.5) 20 1.06 2 6.30 (160) 3.54 (90) 4.53 (115) 5.12 (130) 2.95 (75) 2.76 (70) 6.30 (160) 0.98 (25) M6 0.39 (10) 0.28 (7) M5 8.82 (4) 50
15 (11) 30 0.7 6.30 (160) 4.13 (105) 5.22 (132.5) 5.12 (130) 2.95 (75) 3.35 (85) 6.30 (160) 0.98 (25) M6 0.39 (10) 0.28 (7) M5 11.03 (5) 65
20 (15) 40 0.53 7.09 (180) 3.94 (100) 5.51 (140) 5.91 (150) 2.95 (75) 3.15 (80) 7.09 (180) 0.98 (25) M6 0.39 (10) 0.28 (7) M6 13.23 (6) 90
25 (18.5) 50 0.42 7.09 (180) 3.94 (100) 5.71 (145) 5.91 (150) 2.95 (75) 3.15 (80) 7.09 (180) 0.98 (25) M6 0.39 (10) 0.28 (7) M6 17.64 (8) 90
30 (22) 60 0.36 7.09 (180) 3.94 (100) 5.91 (150) 5.91 (150) 2.95 (75) 2.95 (75) 7.09 (180) 0.98 (25) M6 0.39 (10) 0.28 (7) M6 17.64 (8) 90
40 (30) 80 0.26 8.27 (210) 3.94 (100) 5.91 (150) 6.89 (175) 2.95 (75) 3.15 (80) 8.07 (205) 0.98 (25) M6 0.39 (10) 0.28 (7) M8 18.74 (8.5) 95
50 (37) 90 0.24 8.27 (210) 4.53 (115) 6.99 (177.5) 6.89 (175) 2.95 (75) 3.75 (95) 8.07 (205) 0.98 (25) M6 0.39 (10) 0.28 (7) M8 26.46 (12) 110
60 (45) 120 0.18 9.45 (240) 4.96 (126) 7.66 (193) 8.07±0.2 5.91 (150) 4.33 (110) 9.45 (240) 0.98 (250) M8 0.31 (8) 0.39 (10) M10 33.07 (15) 130
(20.5±5)
75 (55) 150 0.15 9.45 (240) 4.96 (126) 7.80 (198) 8.07±0.2 5.91 (150) 4.33 (110) 9.45 (240) 0.98 (250) M8 0.31 (8) 0.39 (10) M10 50.71 (23) 150
(20.5±5)
50
OPTIONS
NAME PLATE
U V W
C
X Y Z
D H
D H F E
F E B
A
A B B1
L DETAIL IN
DETAIL IN 4-J: MTG.BOLT MTG. HOLE
MTG. HOLE K 4-J: MTG. BOLT
Drawing 1 Drawing 2
51
OPTIONS
DIMENSIONS: Inch (mm)
Weight
Model DWG A B C D E F G H J K L M N P Q lb (kg)
3G3IV- 1 8.66 8.19 7.68 6.69 3.74 (95) 2.76 (70) 1.97 (50) 1.97 (50) 0.98 (25) 0.39 (10) R0.09, 0.24 Length (R2.25, 6 φ0.18 M4 M4 --- 2.213
PHF3005AZ (1.0)
(220) (208) (195) (170) Length) (φ4.5)
3G3IV- 2.65 (1.2)
PHF3010AZ
3G3IV- 4.86 (2.4)
PHF3015AZ
3G3IV- 1 10.79 10.16 9.06 8.27 4.33 3.15 (80) 2.36 (60) 2.76 (70) 1.38 (35) 0.47 (12) R0.11, 0.28 Length (R2.75, 7 φ0.22 M5 M4 --- 5.29 (2.4)
PHF3030AZ (274) (258) (230) (210) (110) Length) (φ5.5)
3G3IV- 2 13.98 12.99 12.06 11.22 4.72 3.54 (90) 2.76 (70) 3.15 (80) 1.57 (40) 0.47 (12) R0.15, 0.3 Length (R3.75, 8 φ0.26 M5 M4 1.18 (30) 10.58
PHF3040AZ (355) (330) (320) (285) (120) Length) (φ6.5) (4.8)
3G3IV- 13.99 M6 12.35
PHF3050AZ (340) (5.6)
3G3IV- 16.54 16.14 14.96 13.39 6.30 5.12 3.54 (90) 3.94 1.97 (50) 0.59 (15) M8 M6 1.97 (50) 24.25
PHF3080AZ (420) (410) (380) (340) (160) (130) (100) (11.0)
3G3IV- 3 11.81 10.24 9.45 8.66 16.54 4.13 3.82 (97) 4.13 0.98 (25) 3.94 2.17 (55) 0.79 (20) φ0.26 M12 M6 40.78
PHF3100AZ (300) (260) (240) (220) (420) (105) (105) (100) (φ6.5) (18.5)
3G3IV- 12.80 10.63 9.84 9.06 17.72 4.65 (118) 3.90 (99) 4.33 (110) 4.74 2.36 (60) 60.03
PHF3150AZ (325) (270) (250) (230) (450) (120) (27.5)
3G3IV- 13.58 11.42 10.63 9.84 18.90 4.53 (115) 4.53 (115) 5.91 2.95 (75) 77.16
PHF3200AZ (345) (290) (270) (250) (480) (150) (35)
3G3IV- 1 8.66 8.19 7.68 6.69 3.74 2.76 (70) 1.97 (50) 1.97 (50) 0.98 (25) 0.39 (10) R0.09, 0.24 Length (R2.25, 6 φ0.18 M4 M4 --- 2.65 (1.2)
PHF3005CZ (220) (208) (195) (170) (195) Length) (φ4.5)
3G3IV- 10.79 9.78 9.06 8.27 4.33 3.15 (80) 2.36 (60) 2.76 (70) 1.38 (35) 0.47 (12) R0.11, 0.128 Length (R2.75, 7 φ0.22 3.97 (1.8)
PHF3010CZ (274) (248.5) (230) (210) (110) Length) (φ5.5)
3G3IV- 4.4 (2.0)
PHF3015CZ
3G3IV- 4.41 (2.0)
PHF3020CZ
3G3IV- 2 13.98 13.00 12.60 11.22 4.72 3.54 (90) 2.76 (70) 3.15 (80) 1.57 (40) 0.47 (12) R0.13, 0.3 Length (R3.25, 8 φ0.26 M5 30 1.18 (30) 6.83 (3.1)
PHF3030CZ (355) (330) (320) (285) (120) Length) (φ6.5)
3G3IV- 10.58
PHF3040CZ (4.8)
3G3IV- 13.39 M4 13.23
PHF3050CZ (340) (5.6)
3G3IV- 16.54 15.51 14.96 13.39 6.30 5.12 3.54 (90) 3.94 1.97 (50) 0.59 (15) R0.13, 0.3 Length (R3.25, 8 φ0.26 M4 50 1.97 (50) 22.05
PHF3060CZ (420) (394) (380) (340) (160) (130) (100) Length) (φ6.5) (10)
3G3IV- 16.14 M6 50 24.25 (11)
PHF3080CZ (410)
3G3IV- 3 11.81 10.24 9.45 8.66 16.54 4.13 3.82 (97) 4.13 0.98 (25) 3.93 2.17 (55) 0.79 (20) (46.5) M6 M6 40.78
PHF3100CZ (300) (260) (240) (220) (420) (105) (105) (100) (18.5)
3G3IV- 12.80 10.63 9.84 9.06 17.2 4.65 (118) 3.90 (99) 4.33 (110) 4.72 2.36 (60) M12 60.63
PHF3150CZ (325) (270) (250) (230) (450) (120) (27.5)
3G3IV- 13.58 11.42 10.63 9.84 18.90 4.53 (115) 4.53 (115) 5.91 2.95 (75) φ0.26
PHF3200CZ (345) (290) (270) (250) (480) (150) (φ6.5)
A±1.5
A±1.5
B±7.5
B±7.5 H±1.5
H±1.5
C±1
J±1.5 C±1 J±1.5
K±1.5 D±1.5 K±1.5 D±1.5 4-M
2-L 2-M 4-L
E +/– 1.5
Q +/– 1
E +/– 1.5
G +/– 1
G +/– 1
G +/– 1
G +/– 1
2-P: GROUND TERMINAL 3-N: INPUT TERMINAL 3-N: OUTPUT TERMINAL 2-P: GROUND TERMINAL 3-N: INPUT TERMINAL 3-N: OUTPUT TERMINAL
Drawing 1 Drawing 2
M +/– 1.5
E±1.5
L +/– 1.5
K +/– 1.5
C +/– 1
A +/– 7.5
Drawing 3
52
OPTIONS
OUTPUT NOISE FILTER (Tohoku Metal Industries Co., Ltd.)
OUTPUT
NOISE FILTER
MCCB 3G3IV
IN
L1(R) L1(R) T1(U) 1 4
53
OPTIONS
ISOLATOR (TRANSDUCER)
Performance
Accuracy ±0.2% FS
Response time 0.1 s max. for standard type or 500 µs max.
for high-speed type between 0% and 90%
Temperature ±0.015% per °C max.
influence
Control power 100 to 240 VAC ±10%, 50/60 Hz
supply 12 to 24 VDC ±10%, 48 to 110 VDC ±10%
Influence of ±0.1% for 10% change in voltage
power supply
ntlp:photo fluctuations
K3F Power/current AC: 10 VA max.
consumption DC: 6 W max.
Ratings
Input
Ambient Operating: –10% to 55%C
temperature Storage: –20% to 65%C
6 5 4 3
Ambient 35% to 85%
– +
operating
5 4 humidity
6 3 Insulation 100 Ω min. between inputs, outputs, and
resistance power supply (at 500 VDC)
7 2
Dielectric 2,000 VAC for 1 min. between inputs, outputs,
U V 8 1
strength and power supply (at 500 VDC)
+ – + –
7 8 1 2 Vibration 10 to 35 Hz, 1-mm double amplitude for 2
resistance hours each in X, Y, and Z directions
Shock 100 m/s2 (10G) three times each in X, Y, and
Control power Output
supply resistance Z directions
(Front View) Noise 1,500 V on power supply terminals in normal
immunity or common mode ±1µs, 50 ns for
square-wave noise with 1-ns rise time
54
OPTIONS
Note: 1. Replace the box in the model number with one of the following numbers to indicate the power supply voltage.
(1) 100 to 240 VAC
(2) 12 to 24 VDC
(3) 48 to 110 VDC
2. Models with the following output specifications are also provided: 0 to 10 mV, 0 to 1 V, 0 to 5 V, 1 to 5 V, 0 to 50 mV, 0 to 100 mV, 0
to 1 mA, 0 to 5 mA, 0 to 2.5 mA, 0 to 10 mA, and 0 to 20 mA.
Dimensions
50 103
(81) 80
8.5
55 min
K3F
123 40±0.2 40±0.2
5 min
8PFA
55
MOTOR PRECAUTIONS
25% ED (OR 15 MIN.)
Application to Existing Standard Motors 40% ED (OR 20 MIN.)
60% ED (OR 40 MIN.)
A standard motor driven by the inverter generates slightly less power than it
does when it is driven with commercial power supply. Also, the cooling effect
deteriorates in low speed range so that the motor temperature rise in-
CONTINUOUS
creases. Reduce load torque in the low speed range. Allowable load char-
acteristics of the standard motor are shown in the figure. If 100% continuous
FREQUENCY (Hz)
torque is required in the low speed range, use an inverter duty motor. (See
Allowable Load Character-
page 53)
istics of the Standard Motor
High-speed Operation
When the inverter is used above 60 Hz, motor mechanical design should be verified. Contact your motor mfg.
Torque Characteristics
Motor torque characteristics vary when the motor is driven by an inverter instead of commercial power supply. Check the
load torque characteristics of the machine to be connected. (For torque characteristics for inverter operation, see page 57.)
Vibration
Because of the high carrier modulation technique for PWM control, the VS-616G3 series reduces motor vibration to a level
equal to running with a commercial power supply. Larger vibrations may occur under the following conditions:
(1) Response at resonant frequency of the mechanical system.
Special care is required if a machine which has previously been driven at a constant speed, is to be driven at varying
speeds. Installation of anti-vibration rubber padding under the motor base and frequency jump control are
recommended.
(2) Rotator residual imbalance
Special care is required for operation at 60 Hz or higher frequencies.
Noise
Inverter operation is as quiet as operation with commercial power supply. At above rated rpm (60 Hz), noise may increase.
56
MOTOR PRECAUTIONS
60 SEC
60 SEC SHORT TIME
SHORT TIME
CONTINU-
CONTINU-
OUS MAX-
OUS MAX-
IMUM
IMUM TORQUE
TORQUE
(%) (%)
60 SEC 60 SEC
SHORT TIME SHORT TIME
CONTINUOUS
MAXIMUM
TORQUE CONTINU-
OUS MAX- TORQUE
(%) (%)
IMUM
AT LOW
SPEEDS
57
CONNECTION EXAMPLES
P
1. indicates shielded leads and twisted-pair shielded leads.
2. External terminal (15) of +15 V has maximum output current capacity of 20 mA.
3. Either external terminal (13) or (14) can be used.
4. Terminal symbols: shows main circuit; shows control circuit.
B1/ B2
MCCB
POWER SUPPLY L (R) MOTOR
1 L1(R) T1(U)
3-PHASE,
200/208/220 V L2(S) L2(S) T2(V) IM
SYSDRIVE 3G3IV
50 Hz
200/208/220/230 V, L3(T) L3(T) T3(W)
60 Hz
FORWARD OPERATION
1 FWD AT INPUT HOLD
REVERSE OPERATION FREQ. METER CALIBRATION
2 REV AT INPUT HOLD RESISTOR: RV30YN 20SB 20kΩ
3 Eb 21
MULTI-FUNCTION ANALOG
OUTPUT
4 RESET ANALOG
OUTPUT STANDARD OUTPUT
22 – + FREQUENCY SETTING
5 FM 0 TO +10 V
13 MASTER REFERENCE
0-10 V (20 kΩ) MULTI-FUNCTION
9 CONTACT OUTPUT
MASTER REFERENCE
14 4-20 mA (250 Ω) 250 VAC, 1 A and below
30 VDC, 1 A and below
MULTI-FUNCTION 10
16 ANALOG INPUT “SIGNAL DURING RUN”
0-10 V (20 kΩ)
SETTING AT FACTORY
17 AUX. FREQ. REFERENCE SHIPMENT
IS STANDARD SETTING
AT FACTORY
25
0V
MULTI-FUNCTION OUTPUT 1
STANDARD SETTING IS
“ZERO SPEED SIGNAL”
MULTI-FUNCTION OPEN
COLLECTOR
26 OUTPUT
MULTI-FUNCTION OUTPUT 2 48 V 50 mA or less
STANDARD SETTING IS
27 “SPEED AGREED SIGNAL”
MULTI-FUNCTION
OUTPUT COMMON
58
CONNECTION EXAMPLES
G(E)
REVERSE OPERATION
REVERSE OPERATION- 2 REV AT INPUT HOLD
STOP COMMAND
3 Eb
EXTERNAL FAULT
INPUT FREQ. METER CALIBRATION
RESISTOR: RV30YN 20SB 20kΩ
FAULT RESET
4 RESET
21
MULTI-FUNCTION ANALOG
MASTER/AUX 5 OUTPUT
FREQUENCY
REFERENCE ANALOG STANDARD OUTPUT
SELECTOR OUTPUT FREQUENCY SETTING
22 – +
MULTI-STEP SPEED 6 FM O TO +10 V
SETTING COMMAND MULTI-FUNCTION
STANDARD CONTACT INPUT
7 (12)
FUNCTIONS JOG
REFERENCE
PRESET AT FREQ. METER (3 VDC, 1 mA)
FACTORY
COASTING STOP
8
COMMAND
11 18
SEQUENCE FAULT CONTACT OUTPUT
COMMON 19
Transistor Operation TERMINAL (0 V) 250 VAC, 1 A and below
ON (Current sink state) 12 30 VDC, 1 A and below
SHIELD SHEATH 20
at closed contact CONNECTION
2 kΩ TERMINAL
0V
25
MULTI-FUNCTION OUTPUT 1
STANDARD SETTING IS
“ZERO SPEED SIGNAL”
MULTI-FUNCTION
OPEN COLLECTOR OUTPUT
26 48 V 50 mA or less
MULTI-FUNCTION OUTPUT 2
STANDARD SETTING IS
“SPEED AGREED SIGNAL”
27
MULTI-FUNCTION
OUTPUT COMMON
59
CONNECTION EXAMPLES
MCCB B1/ B2
MOTOR
THREE-PHASE, L1(R) L1(R) T1(U)
380/400/415/ L2(S) L2(S) SYSDRIVE 3G3IV T2(V) IM
440/460 V,
50/60 Hz L3(T) L3(T) 460/440/ COOLING T3(W)
r 415/400/380 V FAN
VOLTAGE
s SELECTION M
G(E)
FORWARD
RUN/STOP
1 FORWARD OPERATION AT
REVERSE FWD INPUT HOLD
FREQ. METER CALIBRATION
RUN/STOP RESISTOR: RV30YN 20SB 20kΩ
2 REVERSE OPERATION
REV AT INPUT HOLD
21
MULTI-FUNCTION ANALOG
OUTPUT
ANALOG STANDARD OUTPUT
EXTERNAL OUTPUT – + FREQUENCY SETTING:
FAULT 22
FM O TO +10 V
3 Eb
FAULT
RESET
4 RESET (12)
MASTER/AUX. FREQ. METER
CHANGE (3 VDC, 1 mA) PC (PLC)
5
MULTI-STEP
SPEED SETTING
STANDARD 6 SURGE
FUNCTIONS JOG MULTI-FUNCTION ABSORBER
PRESET AT COMMAND CONTACT INPUT
7 18
FACTORY
EXTERNAL
COASTING STOP FAULT CONTACT
19 OUTPUT 200 VAC
8
250 VAC 1 A OR LESS
11 20 30 VDC 1 A OR LESS
SEQUENCE
COMMON
TERMINAL (0 V)
12 MULTI-FUNCTION
12 VDC
SHIELD SHEATH CONTACT OUTPUT
CONNECTION 250 VAC, 1 A OR LESS
TERMINAL
2 kΩ 30 VDC, 1 A OR LESS FLY WHEEL
POWER SUPPLY FOR (SIGNAL DURING RUN
SPEED SETTING DIODE
15 +15 V, 20 mA SETTING AT FACTORY)
0 to +10 V MASTER REFERENCE 9
2 kΩ 13 0-10 V (20 kΩ)
27 STANDARD SETTING IS
“SPEED AGREED SIGNAL”
60
CONNECTION EXAMPLES
B1 BACKUP CAPACITOR
N /P (OPTIONAL)
B1/ B2
MCCB
MOTOR
L1(R) L1(R) T1(U)
THREE-PHASE
POWER L2(S) L2(S) T2(V) IM
SYSDRIVE 3G3IV
SUPPLY
L3(T) L3(T) T3(W)
FORWARD
RUN/STOP G(E)
1 FORWARD OPERATION
REVERSE FWD AT INPUT HOLD
RUN/STOP REVERSE OPERATION
2 REV AT INPUT HOLD
FREQ. METER CALIBRATION
RESISTOR: RV30YN 20SB 20kΩ
EXTERNAL
FAULT 21
3 Eb MULTI-FUNCTION ANALOG
FAULT OUTPUT
RESET ANALOG
4 OUTPUT STANDARD OUTPUT
RESET 22
MASTER/AUX – + FREQUENCY SETTING:
CHANGE FM O TO +10 V
5
MULTI-STEP
(12)
SPEED SETTING FREQ. METER (3 VDC, 1 mA)
STANDARD 6
FUNCTIONS JOG MULTI-FUNCTION
PRESET AT COMMAND CONTACT INPUT
7 18
FACTORY EXTERNAL
COASTING STOP
19 FAULT CONTACT
8
OUTPUT
250 VAC 1 A OR LESS
11 SEQUENCE
COMMON 20 30 VDC 1 A OR LESS
TERMINAL (0 V)
12 SHIELD SHEATH
CONNECTION TERMINAL
2 kΩ
POWER SUPPLY FOR
15 SPEED SETTING
+15 V, 20 mA
0 to +10 V MULTI-FUNCTION
2 kΩ 13 MASTER REFERENCE 9
0-10 V (20 kΩ) CONTACT OUTPUT
FREQUENCY 4 to 20 mA P MASTER REFERENCE
250 VAC 1 A OR LESS
REFERENCE 14 4-20 mA (250 Ω) 30 VDC 1 A OR LESS
10
P (SIGNAL DURING RUN
0 to +10 V MULTI-FUNCTION
16 SETTING AT FACTORY)
P OUTPUT COMMON
0V 17 AUX. FREQ. REFERENCE
AS STANDARD SETTING
AT FACTORY SHIPMENT
25
0V
MULTI-FUNCTION OUTPUT 1
STANDARD SETTING IS
“ZERO SPEED SIGNAL”
MULTI-FUNCTION OPEN
26 COLLECTOR OUTPUT
48 V 50 mA or less
MULTI-FUNCTION OUTPUT 2
STANDARD SETTING IS
27 “SPEED AGREED SIGNAL”
MULTI-FUNCTION
OUTPUT COMMON
61
CONNECTION EXAMPLES
STANDARD SETTING IS
“ZERO SPEED SIGNAL”
MULTI-FUNCTION
21 MULTI-FUNCTION OUTPUT
ANALOG OUTPUT OPEN
26
OUTPUT FREQ. COLLECTOR
SETTING 48 V 50 mA
22 MULTI-FUNCTION OUTPUT 2
and below
STANDARD SETTING IS
27 “SPEED AGREED SIGNAL”
MULTI-FUNCTION
OUTPUT COMMON
Note 1. Braking is not activated at deceleration stop. It’s coasting to a stop.
2. Use MC or MCX of delay release type for restart operation after momentary power loss.
3. Frequency setting resistor is not required for the use of digital operator’s set value as frequency reference.
62
CONNECTION EXAMPLES
OVERLOAD RELAY
TRIP CONTACT
MCCB MC
L1(R) L1(R) B1/ B2
POWER SUPPLY MOTOR
200 TO 230 V, L2(S) L2(S) T1(U)
50/60 Hz SYSDRIVE 3G3IV T2(V)
L3(T) L3(T) IM
T3(W)
THRX OFF ON MC
G(E)
MC SA
BRAKING
RESISTOR UNIT
OVERLOAD RELAY TRIP CONTACT
THRX FREQ. METER CALIBRATION
RESISTOR: RV30YN 20SB 20kΩ
1 2
SA 21
MC MULTI-FUNCTION ANALOG
TRX
OUTPUT
ANALOG OUTPUT STANDARD OUTPUT
20 18 SA 22 FREQUENCY SETTING
– +
FM O TO +10 V
TRX
(12) FREQ. METER/AMMETER
(3 VDC, 1 mA)
FAULT CONTACT
FORWARD
RUN/STOP FORWARD OPERATION
1 FWD AT INPUT HOLD 18
REVERSE
18
RUN/STOP
2 REV REVERSE FAULT CONTACT
BRAKING UNIT OPERATION 19 OUTPUT
AT INPUT HOLD 250 VAC 1 A OR LESS
30 VDC 1 A OR LESS
EXTERNAL 3 4 20
FAULT 20
3 Eb
FAULT
RESET
4 RESET
MASTER/AUX.
CHANGE
5
MULTI-STEP 9 MULTI-FUNCTION
STANDARD SPEED SETTING
6 CONTACT OUTPUT
FUNCTIONS MULTI-FUNCTION 250 VAC 1 A OR LESS
JOG
PRESET AT CONTACT INPUT 30 VDC 1 A OR LESS
COMMAND 10
FACTORY 7 (SIGNAL DURING RUN
EXTERNAL
SETTING AT FACTORY)
COASTING STOP 8
11 25
SEQUENCE MULTI-FUNCTION OUTPUT 1
COMMON
TERMINAL (0 V)
12 STANDARD SETTING IS
“ZERO SPEED SIGNAL”
SHIELD SHEATH
CONNECTION
2 kΩ TERMINAL
MULTI-FUNCTION OPEN
POWER SUPPLY FOR 26 COLLECTOR OUTPUT
15 SPEED SETTING
48 V 50 mA or less
+15 V, 20 mA
0 to +10 V MASTER REFERENCE
MULTI-FUNCTION OUTPUT 2
2 kΩ 13 0-10 V (20 kΩ) STANDARD SETTING IS
4 to 20 mA P
“SPEED AGREED SIGNAL”
FREQUENCY MASTER REFERENCE
27
14 4-20 mA (250 Ω)
REFERENCE MULTI-FUNCTION
0 to +10 V P MULTI-FUNCTION
16 ANALOG INPUT
OUTPUT COMMON
P 0-10 V (20 kΩ)
0V 17
AUX. FREQ. REFERENCE
IS STANDARD SETTING
AT FACTORY SHIPMENT
0V
63
CONNECTION EXAMPLES
With Isolator
MCCB
L1(R) L1(R) B1/ B2
POWER SUPPLY MOTOR
200 TO 230 V, L2(S) L2(S) T1(U)
50/60 Hz SYSDRIVE 3G3IV T2(V)
L3(T) L3(T) IM
T3(W)
FORWARD
RUN/STOP FORWARD OPERATION
1 FWD G(E)
REVERSE AT INPUT HOLD
RUN/STOP REVERSE OPERATION
2 REV
EXTERNAL AT INPUT HOLD
FAULT
3 Eb
FAULT 18
RESET
4 RESET
MASTER/AUX. FAULT CONTACT
CHANGE 19
5 OUTPUT
MULTI-STEP 250 VAC 1 A OR LESS
STANDARD SPEED SETTING 20 30 VDC 1 A OR LESS
6
FUNCTIONS JOG MULTI-FUNCTION
PRESET AT COMMAND CONTACT INPUT
FACTORY 7
EXTERNAL 9 MULTI-FUNCTION
COASTING STOP 8 CONTACT OUTPUT
250 VAC 1 A OR LESS
11 10 30 VDC 1 A OR LESS
SEQUENCE (SIGNAL DURING RUN
COMMON
TERMINAL (0 V) SETTING AT FACTORY)
12 25
SHIELD SHEATH
CONNECTION TERMINAL MULTI-FUNCTION OUTPUT 1
ISOLATOR
K3F-IA31-V4 POWER SUPPLY FOR STANDARD SETTING IS
15 SPEED SETTING “ZERO SPEED SIGNAL”
+15 V, 20 mA
MULTI-FUNCTION OPEN
3 1 13 MASTER REFERENCE 26 COLLECTOR OUTPUT
0-10 V (20 kΩ)
48 V 50 mA or less
4 to 20 mA MASTER REFERENCE MULTI-FUNCTION OUTPUT 2
14 4-20 mA (250 Ω)
4 STANDARD SETTING IS
P MULTI-FUNCTION 27 “SPEED AGREED SIGNAL”
16 ANALOG INPUT
0-10 V (20 kΩ)
0 to 10 V 17 MULTI-FUNCTION
2 OUTPUT COMMON
7 8 AUX. FREQ. REFERENCE
IS STANDARD SETTING ISOLATOR
0V AT FACTORY SHIPMENT K3F-IV41-A3
21
3 1
ANALOG
OUTPUT
22 4 2
0-10 V
7 8
64
APPLICATIONS
FANS AND BLOWERS
M1
3G3IV
EXAUST
MOTOR
M3 L1(R) T1(U) M2
POWER DAMPER
L2(S) T2(V)
SUPPLY L3(T) T3(W)
FREQUENCY
CONTROL- DUST
LER COLLECTION
DEVICE
4 to 20mA
BLOWER
Example of Using the Inverter with Air Scrubber
M1
220 VAC
r s 3G3IV Function and Parame-
M3 M2 Customer’s Request
L1(R)
DIGITAL
OPERA-
MOTOR ter Setting
L2(S) TOR
Wants to Operate Using Operation signal
POWER L3(T)
SUPPLY External Terminals selection Sn-04 = xx00
RUNX Wants Speed Search Multi-function input
1 RUN/STOP
Function Sn-15 to Sn-18 = 61
SPEED
SEARCH Wants Coast to Stop Stop procedure selection
Sn-04 = 01xx
SIGNAL
DURING
RUNNING
Application
Customer’s Request Applicable 3G3IV Function Function and Parameter Setting
example
Wants to switch commercial poer supply Use the speed search operation Multi-function input Sn-15 to Sn-18 = 61
and inverter drive without stopping the
motor.
Needs inverter start from coasting stop
status. Is it possible without stopping
the motor?
Wants to save energy since the load is Apply the variable load V/f V/f selection Sn-02 = 05
not heavy at low-soeed operation
Wants to avoid operation tripping Apply the stall prevention function du- During-operation stall level change
ring-running Cn-30 = 30 to 200%
Dust-collecting
blower, fan for Wants to continue operation even when Select the instantaneous outage reset Momentary power loss protection Sn-11
boilers momentary power loss not longer than and restart mode = x1xx
Fan for cooling 2 seconds occurs.
towers Wants to monitor output power. Turn the monitor to the output power in- Monitor display Un-06
dication.
Needs r/min lower limit for lubricating Use th frequency command lower limit Frequency command lower limit cn-15 =
the decelerator bearing. 0 to 109%
Wants to avoid mechanical resonance. Use the preset frequency band prohibi- Preset prohibited frequency Cn-16 = 0
((The resonance point will be passed,, tion function (frequency jump control). to 400 Hz
andd continuous
ti operation
ti iis eliminated
li i t d Preset prohibited frequency range
at this point.) Cn-19 = 0 to 25.5 Hz
Wants to prevent machine stop caused Use the retry function. Retry count Cn-36 = 0 to 10 times
by inverter tripping.
65
APPLICATIONS
PUMP
3G3IV
AUTO/MANUAL HYPOCHLOROUS
SWITCH ACID
L1(R) T1(U)
L2(S) T2(V)
L3(T) T3(W)
MAIN/SUB
MANUAL SPEED
COMMAND MOTOR
MACHINE 0 to 10 V
OPERATING AUTO
PANEL COMMAND
4 to 20 mA
RAW WATER
PID
3G3IV
MCCB
DIGTAL MOTOR
L1(R) L1(R) T1(U)
OPER- Function and Parame-
POWER
L2(S) Customer’s Request
SUPPLY L2(S) ATOR T2(M) IM ter Setting
L3(T) L3(T) T3(W)
G
Wants to Operate Using Operation signal
4 to 20 mA
PID
14 (E) External Terminals selection Sn-04 = xx00
17
ANALOG Wants 4 to 20 mA signal Frequency command
2 kΩ
15 MONITER Fine Control gain bn-05 = 0% to
2 kΩ 16
(OP
100%
+15 V
0 to 10 V TION) Frequency command
5
bias bn-06 = –100% to
1SW 11
WALL-
AUTO/MANUAL
100%
MOUNTED
Wants a Meter that Channel 1 output Sn-28
2SW AMME
RUN/STOP
TER
A F Indicates Output = xx00
Frequency Channel 2 output Sn-28
= 01xx
Man/Auto Switch Circuit
Application
Customer’s Request Applicable 3G3IV Function Function and Parameter Setting
example
Wants to save evergy since the load is Use the sensorless slip correction func- Motor rated slip: bn-08 = 0 to 9.9%, Mo-
not heavy at low-speed operation. tion. tor rated current: Cn-09 = 10 to 200 A
Chemical-Feed- Wants to have Manual/Auto switching Use the Master/aux. switching function. Master/Aux. switching: Sn-15 to 18 = 03
ing Pump
Pum function. Two toggle switches do the job.
Needs an ammeter for monitoring load Use an F-I motor (option). Output selection function: Sn-28 = xx00
conditions.
Wants to drive the pump directly using 4 Use external terminals (14) and (17). Run signal selection: Sn-04 = xx00
to 20 mA signal.
Wants a function which can maintain Use the lower-limit of the reference fre- Frequency reference lower limit: Cn-15
minimum speed. quency. = 0 to 109%
Wants to run the system using the com- Use a selector circuit together with the Speed search function selection Sn-15
Warm/Cold Water mercial power supply when an emer- speed search function. to 18 = 61
Circulation Pump gency occurs.
Wants a function which can keep the Use the continuous operation function Momentary power loss protection:
system working without resetting it even which can compensate for a momentary Sn-11 = x1xx
when a momentary power loss occurs. power loss within two seconds. Use a
toggle switch for selecting the start and
stop of operations.
Wants to keep a constant water level Read signals directly sent from the wa- Run signal selection: Sn-04 = xx00
inside a tank using a water gauge. ter-level adjusting unit. (4 to 20 mA)
Discharge Pump Wants to keep the motor rpm above the Use the lower-limit of the frequency ref- Frequency ref. lower limit: Cn-15 = 0 to
minimum because if the rpm is too low, erence. 109%
water flows in the reverse direction.
66
APPLICATIONS
Improves Safety and Enables Optimum Operation Setting
BR BRAKE
3G31V
L1(R) T1(U)
L2(S) T2(V)
PAINTING BOOTH L3(T) T3(W)
RUNNING BR
FWD/STOP BRAKE
RELAY SEQUENCE
REV/STOP
BRAKING
LS1 LS2 2 STEPS SPEED REGISTOR
LS4 LS3 FOR FOR FOR SHOCK REFERENCE UNIT
FOR DECEL- DECEL-STOP ABSORBER
STOP ERATION ERA-
TION
GEARED MOTOR
WITH BRAKE RUN/STOP
20 : 1 DL
40 m/min
LS3 LS4 MECHANICAL BR
HOLDING HOLDING 3G31V
FORWARD 1 m/min TYPE TYPE MCCB
RUN
L1(R) L1(R) DIGITAL
POWER
LS1 LS2 SUPPLY L2(S) L2(S) OPERA- IM MOTOR
HOLDING HOLDING TOR
REVERSE RUN L3(T) L3(T)
TYPE TYPE
Application
Customer’s Request Applicable 3G3IV Function Function and Parameter Setting
example
Wants to increase precision of position- Control the braking motor using contact Operating signal selection Slip preven-
ing stop. output from terminals 9 and 10. tion Sn-20 = 0, Sn-20 = 05, Cn-21 = 0 to
400 Hz
Run at lower speeds. Torque compensation gain bn-07 = 0 to
9.9
Wants to perform two-step speed oper- Use the multi-step speed function. Multi-step operation An-01 to 04 = 0 to
Shuttle Conveyor ation 400 Hz
Wants smooth accel/decel time. Apply non-linear accel/decel. Operating signal selection Sn-06 = xx
jj selection
Wants to vary accel/decel time. Use the accel/decel time setting func- Accel/decel time switching Sn-15 to 18
tion. = 07
Wants to select stop procedure accord- Select stop procedures. External fault Sn-15 to 18 = 20 to 3F
ing to degree of emergency.
Raw Material In- Wants to increase starting torque (with Use the standard-equipped automatic Torque compensation gain bn-07 = 0 to
put Conveyor a constant-torque motor). torque boosting function. 9.9
Steel Pipe Con- Wants to drive more than one motor The function is provided. ---
veyor with a single inverter.
Wnats a simple slip compensation func- Check the motor generation torque by Over torque detection Sn-07 = xxx1
tion the excess torque detection function. Over torque detection level Cn-26 = 30
to 200%
Lifter Over torque detection time Cn-27 = 0 to
25.5 s
Wants to use the non-excitation operat- Use the free V/f setting function to turn V/f selection Sn-02 = 0F
ing type braking motor. the motor without excess excitation. Free V/f setting Cn-02 to 08 = Setting
67
APPLICATIONS
Improves Safety and Enables Optimum Operation Setting
3G3IV
L1 (R( T1 (U)
POWER L2 (S) T2 (V)
SUPPLY L3 (T) T3 (W) MAIN AXIS
MOTOR X–AXIS MOTOR
COUPLING
BALL
SCREW TURRET
CONTROLRE- MAIN AXIS
NC EQUIPMENT SISTOR POSITION Z–AXIS
BALL SCREW MOTOR
BELT
OPERATING SIGNAL CUTTER COUPLING
STATUS SIGNAL SPEED CONTROLLER
ZERO SPEED (MANUAL) TIP
FEEDER
WORKPIECE
SPEED AGREED MAIN AXIS
FREQUENCY TIP PRESSING
OPERATION PER- METER MOTOR
FORMED FM BALL SCREW
Interface Circuit to NC
Application
Customer’s Request Applicable 3G3IV Function Function and Parameter Setting
example
Needs a large constant-output Use the winding selection motor. Option
range.
Wants the cutting loss detection Apply the over torque detection Over torque detection Sn-07 =
function. function. 0001 Over torque detection level
Cn-26 = 30% to 200%
Over torque detection time Cn-27 =
0 to 25.5 s
Multi-function output Sn-20 to
Sn-22 = 0B
CNC Lathe
Wants to turn motor with digital in- Use the digital speed command Connect DI-08. Frequency com-
put equipment mand setting mode Sn-26 = select
Want to interface to NC. Apply the zero-speed function. Multi-function output Sn-20 to
Sn-22 = 01
Apply the speed agreed function. Multi-function output Sn-20 to
Sn-22 = 02
Apply the over torque detection Multi-function output Sn-20 to
function. (Cutting loss) Sn-22 = 0B
Wants to reduce vibration. Apply the energy-saving mode. Energy-saving operation Sn-15 to
Super High-pre-
Sn-18 = 63
cision Lathe
bn-9 = 0% to 200%
68
APPLICATIONS
Inverter Capacity Selection
Inverter Capacity Check Points
Related specification
Cl ifi ti
Classification It
Item Speed and Torque Overload Starting torque
Time Ratings
Characteristics Capacity
Load type Friction load and weight load YES YES
Liquid (viscous) load
Inerita load
Load with poer transmission and
accumulation
Load speed Constant torque YES YES
and torque Constant output
Load
charcteristics Decreasing torque
characteristics
Load Motoring YES YES YES YES
charcteristics Braking or overhauling load
Constant load
Shock load
Repetitive load
High-start torque
Low-start torque
Continuous operation YES YES
Operation Long-time operation at medium or low speeds
Short-time operation
Maximum required output (instantaneous) Constant YES YES
Rated output
output (continuous)
Maximum r/min YES
Rated r/min
Rated r/min
Power supply transformer capacity percentage YES YES
impednace
Power supply Voltage fluctuations
Number of phases, singla phase protection
Frequency
Deterioration of Mechanical friction, losses in wiring YES YES
load capacity due
Duty cycle modification YES
to age
69
APPLICATIONS
Specifications
PM ; Motor shaft output required for the load [kW}
η; Motor efficiency (normally, approx. 0.85)
cos φ; Motor power factor (normally, approx. 0.75)
VM ; Motor voltage [v]
IM ; Motor current [A] (current with commercial power supply)
k; Correction factor calculated from current form factor (1.05 to 1.1, depending on the PWM method.)
PC1 ; Continuous capacity [kVA]
ks; Motor starting current/motor rated current
nT; Number of motors in parallel
ns; Number of simultaneously started motors
(GD 2); Total (GD2) converted into motor shaft (kg-m2)
TL ; Load torque (kg-m)
tA : Motor acceleration time
(d)
WL
h
µML WL
Fig. 1 Fig. 2
Symbol WL: Weight of Load. µ: Coefficient of friction
VL: Linear Velocity of Load. η: Efficiency of mechanism
ta: Acceleration time.
Unit ft, lb kg, m
1. Full Load Power (m)W L x V L (m)W L x V L
PO + [Hp] PO + [kW]
33000 x h 6120 x h
2. Full Load Torque (m)W L x V L (m)W L x V L
TL + [ft·lb] TL + [kg·m]
2p x N M x h 2p x N M x h
3. Acceleration Power WL x VL
2
WL x VL
2
Pa + [Hp] Pa + [kW]
64 x 10 6 x ta 3600 x 10 3 x ta
4. Acceleration Torque ∑ (WK 2) x N M ∑ GD 2 x N M
Ta + Ta +
308 x ta 375 x ta
5. INERTIA (Reflected to Motor)
ÒpNV Ó [lb ft ] ÒpNV Ó [kg·m ]
2 2
L L
WK 2 1 + 0.55 x W L . 2
GD 2 1 + W L 2
M M
Ò + ÒNN Ó ·WK Ó
L
M
2
2
Ò + ÒNN Ó ·GD
L
M
2
2
L Ó
6. INERTIA (LOAD) W LD 2 GD 2 L + W L·D 2