[Automation Server Family] SmartStruxure solution

I/O Modules DO-FA-12 and


DO-FA-12-H
12 channel Form A digital output

Introduction Patented two-piece design


Each module can be separated from its terminal
The DO-FA-12 and DO-FA-12-H are digital output
base to allow the site to be wired prior to the
12 channel I/O modules.
installation of the electronics. The patented locking
mechanism serves as handles for removing the
The digital outputs support digital Form A point module from its base. All critical components have
types. The Form A relays are designed for direct a protective cover that permits convection cooling
load applications. to occur.

Function
Modular and scalable system
The modules are part of a modular system that
© 2014 Schneider Electric. All rights reserved.

delivers power and communications on a common


bus. Connecting modules is a one-step process:
just slide the modules together using the built-in
connectors.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-13004-02-en July 2014
[Automation Server Family] SmartStruxure solution
2

Efficient terminal management


The I/O module terminals are clearly labelled and
protected by transparent covers. The input and
output terminals are at the top and bottom of each
module and are accessible for maintenance without
removing the module. The StruxureWare Building
Operation WorkStation software can generate
custom as-built labels for each module. Pre-
perforated letter and A4 size label sheets are
available as an accessory.

Accommodates multiple row panel installations


The Automation Server module family uses built-in
connectors for single row connectivity, side by side.
If a panel size requires multiple rows, extension
cords are available.

Figure: Two-piece design LED status indicators


The I/O module has a status indicator that denotes
Hot-connect and Hot-swap the health and status of the module.
Because critical applications require 24-hour
operation, Schneider Electric designed the I/O Each digital output channel has a dedicated status
modules for hot-connection of terminal bases and indicator using a green LED.
hot-swapping of the modules to their bases. This
design ensures continuous power and Hand/Off/Auto switches
communication during service operations. The front panel of the DO-FA-12-H includes
Hand/Off/Auto (HOA) switches to provide override
Auto-addressing control of the digital outputs.
The auto-addressing feature eliminates the need for
setting DIP switches or pressing commission The position of the HOA switch is readable through
buttons. With the Automation Server family, each user interfaces, such as the StruxureWare Building
module automatically knows its order in the chain Operation WorkStation software, enabling more
and assigns itself accordingly – significantly precise monitoring and control.
reducing engineering and maintenance time.

Simple DIN-rail installation


Fasteners easily snap into a locked position for
panel installation. The fastener has a quick-release
feature for easy DIN-rail removal.

Specifications
Output channels .....................................................................................................................................12
DC input supply power ......................................................................................................................1.8 W
© 2014 Schneider Electric. All rights reserved.

DC input supply voltage ..................................................................................................................24 VDC


Environment
Ambient temperature, operating .............................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage .........................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity...............................................................................................95 % RH non-condensing
Material
Plastic rating................................................................................................................................UL94-5VB

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-13004-02-en July 2014
[Automation Server Family] SmartStruxure solution
3

Enclosure....................................................................................................................Eco Friendly ABS/PC


Enclosure rating...................................................................................................................................IP 20
Mechanical
Dimensions including terminal base ..............................90 W x 114 H x 64 D mm (3.6 W x 4.5 H x 2.5 D in.)

Weight including terminal base .........................................................................................0.317 kg (0.70 lb)


Weight excluding terminal base ........................................................................................0.194 kg (0.43 lb)
Terminal base .............................................................................................................................TB-IO-W1
Part numbers
DO-FA-12, I/O module
12 Form A digital outputs .............................................................................................SXWDOA12X10001
DO-FA-12-H, I/O module with HOA switches
12 Form A digital outputs with Hand/Off/Auto override switches ..................................SXWDOA12H10001
TB-IO-W1, terminal base for I/O module
(Required for each I/O module)......................................................................................SXWTBIOW110001
Accessory part numbers
DIN-RAIL-CLIP, DIN-rail end clip
package of 25 pieces ....................................................................................................SXWDINEND10001
PRINTOUT-A4-W1, printout sheets for terminal labels
A4 sheet size, 100 sheets, 18 labels per sheet...............................................................SXWTERLBL10011
PRINTOUT-LTR-W1, printout sheets for terminal labels
Letter sheet size, 100 sheets, 16 labels per sheet ..........................................................SXWTERLBL10012
S-CABLE-L, S-cable extension cord for Automation Server I/O bus L shaped connectors
1.5 m............................................................................................................................SXWSCABLE10002
S-CABLE-L, S-cable extension cord for Automation Server I/O bus L shaped connectors
0.75 m..........................................................................................................................SXWSCABLE10003
© 2014 Schneider Electric. All rights reserved.

Digital outputs
The Form A digital outputs of the DO-FA-12 and
DO-FA-12-H I/O modules are closing contacts with
one common terminal (C) and one normally open
terminal (NO). The terminals are isolated from signal
ground.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-13004-02-en July 2014
[Automation Server Family] SmartStruxure solution
4

The I/O bus in the terminal base provides the I/O


module with power and an address.

The address value in the I/O bus is increased by


one for each terminal base. The I/O bus also
enables RS-485 communication between the I/O
module and the Automation Server.

Figure: Form A digital output internal configuration

Specifications
Digital outputs

Contact rating ...........................................................................................................250 VAC/30 VDC, 2 A


Switch type ............................................................................................................................Form A Relay
..............................................................................................................................Single Pole Single Throw
.............................................................................................................................................Normally Open
Isolation contact to system ground ..............................................................................................3000 VAC
Cycle life ..................................................................................................................At least 100,000 cycles
© 2014 Schneider Electric. All rights reserved.

Minimum pulse width .......................................................................................................................100 ms


LED polarity energized relay ....................................................................................................................On
LED polarity non-energized relay .............................................................................................................Off
LED color ...........................................................................................................................................Green

For protection from excess current that could be


produced by field wiring, see Automation Server
Family Hardware Guide.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-13004-02-en July 2014
[Automation Server Family] SmartStruxure solution
5

Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2004/108/EC Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following This equipment complies with the rules, of the Official Journal of the European Union, for
two conditions: (1) This device may not cause harmful interference. (2) This device must governing the Self Declaration of the CE Marking for the European Union as specified in
accept any interference received, including interference that may cause undesired the above directive(s) per the provisions of the following standards: IEC/EN 61326-1
operation. Product Standard, IEC/EN 61010-1 Safety Standard.

Industry Canada
ICES-003 WEEE - Directive of the European Union (EU)
This is a Class B digital device that meets all requirements of the Canadian Interference This equipment and its packaging carry the waste of electrical and electronic equipment
Causing Equipment Regulations. (WEEE) label, in compliance with European Union (EU) Directive 2002/96/EC, governing
the disposal and recycling of electrical and electronic equipment in the European
community.
C-Tick (Australian Communications Authority (ACA))
AS/NZS 3548
This equipment carries the C-Tick label and complies with EMC and radio UL 916 Listed products for the Unites States and Canada, Open Class Energy
communications regulations of the Australian Communications Authority (ACA), governing Management Equipment.
the Australian and New Zealand (AS/NZS) communities.

© 2014 Schneider Electric. All rights reserved.

Schneider Electric | Building Business www.schneider-electric.com/buildings