R-FIR-DIOMM INEREX-GB-2015 02 UL 2015 05 17 Komprimiert
R-FIR-DIOMM INEREX-GB-2015 02 UL 2015 05 17 Komprimiert
R-FIR-DIOMM INEREX-GB-2015 02 UL 2015 05 17 Komprimiert
INEREX ®
INERT GAS EXTINGUISHING SYSTEMS. CONSTANT FLOW TECHNOLOGY.
In addition, all CEODEUX Extinguisher Valves Technology S.A. manufacturing sites comply with ISO 9001
quality standards.
π EN 12094-4
Certificate No. 724a
INEREX® System
3
Record of revisions
Record of revisions
Rev. Document Number Document Title Date Description of changes
No.
01 R-FIR-DIOMM INEREX®- Design, Installation, Operation 2015/04/17 Initial release
GB-2015 04 and Maintenance Manual for
INEREX® Systems
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
4 Record of revisions
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System
5
Contents
Contents
1 Notes on the documentation ........................................................................................................ 11
1.1 Other applicable documents ............................................................................................................ 11
1.2 Storage of the documents ............................................................................................................... 11
1.3 Symbols used ................................................................................................................................. 11
1.4 Applicability of this manual ............................................................................................................. 11
1.5 Subject to change ........................................................................................................................... 11
1.6 List of abbreviations ........................................................................................................................ 12
1.7 Glossary - technical definitions ....................................................................................................... 13
1.8 Metric conversion factors ................................................................................................................ 16
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
6 Contents
4 Design ........................................................................................................................................... 38
4.1 Determine the volume of the hazard ................................................................................................ 39
4.1.1 Rectangular enclosures .................................................................................................................. 39
4.1.2 Non-rectangular irregular enclosures ............................................................................................... 39
4.1.3 Integrity test of the enclosure ......................................................................................................... 39
4.1.4 Limitations - enclosure .................................................................................................................... 39
4.2 Calculation of the extinguishing agent ............................................................................................ 40
4.2.1 Formula for the calculation of the minimum design quantity ........................................................... 40
4.2.2 Calculation of the design concentration .......................................................................................... 40
4.2.3 Alternative quick calculation ........................................................................................................... 41
4.2.4 Adjustments .................................................................................................................................... 46
4.2.4.1 Altitude and temperature adjustments ............................................................................................ 46
4.2.4.2 Reserve quantity ............................................................................................................................. 46
4.2.4.3 Unclosable openings ...................................................................................................................... 46
4.2.4.4 Relief device to avoid overpressure ................................................................................................ 46
4.3 Selection of cylinders ...................................................................................................................... 47
4.3.1 Dependency of the pressure inside the cylinder and the ambient temperature .............................. 47
4.3.2 Define the number of cylinders ....................................................................................................... 49
4.3.3 Check of the final oxygen concentration ......................................................................................... 49
4.4 Limitations ....................................................................................................................................... 49
4.4.1 Limitations cylinders ........................................................................................................................ 49
4.4.2 Define the pipework and the location of the pipework .................................................................... 50
4.4.3 Define the nozzles and the location of the nozzles ......................................................................... 50
4.4.3.1 Limitations nozzles and location of the nozzles .............................................................................. 50
4.4.4 Limitations according to UL certification (UL 2127) ........................................................................ 51
4.5 VdS calculation software for gas extinguishing systems ................................................................ 53
4.5.1 Quick start guide of the VdS calculation software ........................................................................... 54
4.5.1.1 Project - input screen ...................................................................................................................... 54
4.5.1.2 Sections graphic - input screen ...................................................................................................... 55
4.5.1.3 Calculations zones - input screen .................................................................................................... 56
4.5.1.4 Storage - input screen ..................................................................................................................... 57
4.5.1.5 Hydraulic calculation report ............................................................................................................ 58
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System
7
Contents
6 Operation ....................................................................................................................................... 86
6.1 Operating procedure ....................................................................................................................... 86
6.2 Personnel safety ............................................................................................................................. 86
6.3 INEREX® System 1 zone ................................................................................................................ 87
6.4 INEREX® System multi-sector distribution ..................................................................................... 88
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
8 Contents
9 Malfunctioning ............................................................................................................................... 98
Appendix
IG01 Material Safety Data Sheet .................................................................................................................. 100
IG100 Material Safety Data Sheet ................................................................................................................. 105
IG55 Material Safety Data Sheet .................................................................................................................. 110
IG541 Material Safety Data Sheet ................................................................................................................ 115
Tapered Thread Port Assembly .................................................................................................................... 120
Pressure and flow detector switch, part number 028250050 ........................................................................ 122
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System
9
List of figures
List of figures
Title Figure Page
Temperature/pressure graph for IG01 4-1 47
Temperature/pressure graph for IG100 4-2 48
Temperature/pressure graph for IG55 4-3 48
Temperature/pressure graph for IG541 4-4 48
Nozzle placement in a non-rectangular enclosure 4-5 50
Limitations tee splits 4-6 52
Project input screen VdS calculation software 4-7 55
Sections graphic input screen VdS calculation software 4-8 55
Calculation zones input screen VdS calculation software 4-9 56
Storage input screen VdS calculation software 4-10 57
Overpressure VdS calculation software 4-11 58
Installation height of the cylinder wall mounting rail 5-1 71
Distance between the discharge port of the valve and the centre of the manifold 5-2 72
Manifold assembly steps 5-3 73
End cap attached to the manifold mounting rail 5-4 74
Securely fixed cylinder 5-5 74
Cylinder double row 5-6 75
System assembly 5-7 76
Removal of the protection cap and outlet safety plug 5-8 77
Connecting the pressure regulator to the valve 5-9 78
Connecting the discharge hoses 5-10 78
Connecting the pressure gauge 5-11 79
Connecting the pneumatic release devices 5-12 79
Resetting the electromagnetic release device 5-13 80
Connecting the electromagnetic release device 5-14 80
Connecting the electromagnetic release device to power supply 5-15 81
Installation of a manual/pneumatic release device on top of the electromagnetic release device 5-16 81
Connecting adapters and pilot hoses to the pneumatic release devices on the slave valves 5-17 82
Connecting the bleed valve 5-18 82
Installation of the pilot line 5-19 82
Test unit 5-20 83
Pilot line test 5-21 84
Typical view of an INEREX System for the protection of one hazard area
®
6-1 87
Typical view of an INEREX System for the protection of two hazard areas
®
6-2 88
Valve performance test 7-1 91
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
10 List of tables
List of tables
Title Table Page
Metric conversion factors 1-1 16
Inert gas extinguishing agent quality requirements 2-1 18
Physical properties of inert gas extinguishing agents (SI Units) 2-2 18
Relative hazards to people from reduced oxygen levels (hypoxia) 2-3 19
NOAEL and LOAEL values 2-4 19
IG01 concentrations according to UL 2127 4-1 41
IG100 concentrations according to UL 2127 4-2 41
IG55 concentrations according to UL 2127 4-3 41
IG541 concentrations according to UL 2127 4-4 41
Total flooding quantity for IG01 (SI Units) 4-5 42
Total flooding quantity for IG100 (SI Units) 4-6 43
Total flooding quantity for IG55 (SI Units) 4-7 44
Total flooding quantity for IG541 (SI Units) 4-8 45
Altitude correction factors according to ISO 14250-1 (2000) and NFPA 2001 (2000) 4-9 46
Filling mass of INEREX cylinders at 15°C
®
4-10 47
Storage floor loading capacity for 67 litres cylinders per metre 4-11 49
Storage floor loading capacity for 80 litres cylinders per metre 4-12 49
Storage floor loading capacity for 140 litres cylinders per metre 4-13 49
Minimum and maximum pipeline flow rates 4-14 51
Bullhead tee split limits and side/through split limits 4-15 51
Minimum design nozzle pressure 4-16 52
NPT threads according to ANSI/ASME B1.20.1 5-1 65
R threads according to ISO 7-1 5-2 65
Maximum distance between two pipe supports 5-3 66
Part numbers for cylinder labels depending on extinguishing agent 5-4 68
Distance between two manifold mounting rails 5-5 72
Components for system assembly 5-6 77
Restriction conditions specified in NFPA 2001 and recommended by EPA 6-1 87
Inspection and maintenance intervals 7-1 90
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System
11
Notes on the documentation
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
12 Notes on the documentation
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System
13
Notes on the documentation
Ampere: the unit of measurement of electrical current produced in a circuit by 1 volt acting through a resistance
of 1 ohm.
ASME: the registered trademark of The American Society of Mechanical Engineers, formerly the American
Society of Mechanical Engineers. ASME is a professional association, an engineering society, a standards
organisation, a research and development organisation, a lobbying organisation, a provider of training and
education, and a non-profit organisation.
ASTM: known until 2001 as the American Society for Testing and Materials (ASTM), is an international stand-
ards organisation that develops and publishes technical standards.
Atmospheric pressure: the force per unit area exerted on a surface by the weight of air above that surface in
the atmosphere of the earth.
Authority Having Jurisdiction: organisation, office, surveyor or individual responsible for approving equipment,
installations or procedures.
Boundary surface: the sum of any area of walls, ceilings and floors in an enclosure.
Class A fire: fire in ordinary combustible materials, e.g. fires involving solid materials normally of organic nature,
such as rubbers, wood, paper, data processing equipment etc. These fires typically produce deep-seated
fires that may require higher design concentrations for extended holding times.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
14 Notes on the documentation
Class A polymeric fire: fire in plastic materials such as polypropylene or PVC. These fires typically produce
deep-seated fires that may require extended holding times.
Class B fire: fire in combustible liquids, mainly hydrocarbons, solvents, glycols, methanol, oils, tars and other
additives. These fires produce surface fires.
Class C fire: NFPA 2001, fire that involves energised electrical equipment where the electrical resistivity of the
extinguishing agent is of importance.
Clean agent: electrically non-conductive, volatile, or gaseous extinguishing agent that does not leave a residue
upon evaporation.
Commissioning: process by which an equipment, facility, or plant (which is installed, or is complete) is tested to
verify if it functions according to its design objectives or specifications.
Deep-seated fire: fire involving a flammable, which due to the way of storage contains oxygen. The flammable
e.g. bulk paper, rolls of paper, furs, dust collectors, vaults etc. will when on fire create a layer of more or less
solid ash preventing the extinguishing agent to reach the flame. The fire will continue until the oxygen within
the material is reduced to below the level sustaining the fire.
Design concentration: the required minimum concentration of extinguishing agent in percent which has to be
achieved inside the protected enclosure including safety factors.
Design quantity (DQ): the quantity of extinguishing agent to be discharged into the enclosure.
Design factor (DF): a fraction of the extinguishing agent minimum design quantity added thereto deemed appro-
priate due to a specific feature of the protection application or design of the suppression system.
Discharge rate: the ratio of the quantity of agent discharged from a nozzle to the discharge time measured
within ±1 second. When a minimum discharge rate is indicated, reference is made to the minimum quantity of
agent discharged and the time measured within ±1 second.
Discharge time: the time it takes to achieve a release of the required specific design quantity. ISO and NFPA
specify that 95% of the extinguishing agent including the allocated safety factor shall be discharged within 60
seconds.
Document: a form of information, a record or the capturing of some event or thing so that the information will
not be lost. Normally, a document is written, but a document can also be made with pictures and sounds. A
document can be put into an electronic form and saved and stored in a computer as a uniquely named file.
Product labels and stickers on products containing product specifications are also considered as documents.
Enclosure: the casing, housing, partitions or walls which surround the protected hazard and substantially will
contain the extinguishing agent for a sufficient length of time to achieve the fire extinguishing objectives.
Engineered system: a system that requires individual design and calculation to determine the flow rates, pipe
size, nozzles, nozzle pressures, area protected by each nozzle, quantity of extinguishing agent, and the num-
ber and types of nozzles and their placement in a specific system.
Extinguishing agent concentration: the portion of extinguishing agent in a mixture of extinguishing agent and
air expressed in volume percent.
Final design quantity (FDQ): the quantity of extinguishing agent determined from extinguishing agent minimum
design quantity as adjusted to account for design factors and pressure adjustment.
Fire alarm: an audible and/or visual device that alerts occupants that a fire occurs. Fire alarms usually signal
occupants to evacuate.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System
15
Notes on the documentation
Hold time: period where the design concentration is higher than the cup burner extinguishing agent concentra-
tion in the protected enclosure. The general definition is that the hold time starts when design concentration
throughout the enclosure is reached and lasts until the concentration at the tallest hazard in the enclosure has
dropped to less than the extinguishing agent concentration. The minimum hold time is normally 15 minutes
unless specified otherwise by the Authority Having Jurisdiction. The determination of the required hold time,
may depend on:
1. Response time of trained personnel
2. Arrival time of fire department
3. Sources of persistent ignition
4. Excessive enclosure leakage
5. System enclosure venting requirements
6. Inertion and re-flash hazards
7. Cool-down time of hot equipment
8. Run-down time of rotating equipment
Inert gas extinguishing agent: an extinguishing agent that contains as primary components one or more of the
gases argon or nitrogen. Inert gases that are blends of gases can also contain carbon dioxide as a secondary
component.
INEREX® battery: several inert gas cylinders combined in one unit.
Inspection: a visual examination of the system or portion thereof to verify that it appears to be in operating con-
dition and is free of physical damage.
Listed: equipment, materials, or services included in a list published by an organisation acceptable to the Au-
thority Having Jurisdiction and concerned with evaluation of products or services, that maintains periodic
inspection of production of listed equipment or materials or periodic evaluation of services, and whose
listing states that either the equipment, material, or service meets appropriate designated standards or
has been tested and found suitable for a specified purpose.
LPCB: the Loss Prevention Certification Board (LPCB) is the leading international Certification Body in the fields
of security and fire protection.
LOAEL: Lowest Observable Adverse Effect Level. The lowest concentration at which an adverse toxicological
or physiological effect has been observed in humans.
Maintenance: a “thorough check” to give maximum assurance that the extinguishing system will operate as
intended. Design parameters should be closely examined for hazard changes since the last inspection, parts
and components should be closely examined and tested or replaced if necessary.
Maximum concentration: concentration achieved from the actual extinguishing agent quantity at the maximum
ambient temperature in the protected enclosure.
Minimum Design Quantity (MDQ): the minimum quantity of extinguishing agent to be discharged into the en-
closure.
NOAEL: No Observable Adverse Effect Level. The highest concentration at which no adverse toxicological or
physiological effect has been observed in humans.
Net volume: gross volume minus the volume of permanent impermeable building elements in the enclosure.
Normally occupied area: area that is intended for occupancy, where people are present most of the time.
Normally unoccupied area: area that is normally not occupied by people, but which may be entered occasion-
ally for brief periods. Examples: transformer bays, switch-houses, pump rooms, vaults, engine test stands,
cable trays, tunnels, microwave relay stations, flammable liquid storage areas, enclosed energy systems.
Nozzle: a device that is used to distribute the extinguishing agent within a specific volume or over a specific area
or both.
Nozzle coverage: maximum area or volume protected by one nozzle. The nozzle coverage is normally defined
on the basis of location or projection distance and the discharge rate. A sufficient number of nozzles must
always be installed to adequately cover the volume of the entire hazard.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System
16 Notes on the documentation
Protected area: all areas, rooms, enclosures that are connected to a fire extinguishing system.
PTFE tape: PolyTetraFluoroEthylene tape (EN 751-3) is a thin tape that is used as a sealant for threads.
Reserve quantity: quantity of extinguishing agent available for further discharge in addition to storage quantity.
Safety Factor (SF): a multiplier of the extinguishing agent concentration to determine the extinguishing agent
minimum design concentration.
Sea level equivalent of extinguishing agent: the extinguishing agent concentration in volume percent at sea
level for which the partial pressure of extinguishing agent matches the ambient partial pressure of extin-
guishing agent at a given altitude.
Sea level equivalent of oxygen: the oxygen concentration in volume percent at sea level for which the partial
pressure of oxygen matches the ambient partial pressure of oxygen at a given altitude.
Storage quantity: the total quantity of extinguishing agent kept available for use within a flooding area, compris-
ing the design quantity and any supplementary quantity.
Time delay: time between the release of the inert gas and the discharge through the nozzles.
Total flooding: the act and manner of discharging an extinguishing agent to achieve a specified minimum extin-
guishing agent concentration throughout a hazard volume.
Total flooding system: a system consisting of a supply of extinguishing agent and of a distribution network,
arranged to discharge the extinguishing agent into the hazard volume and to fill that hazard volume to an
effective extinguishing agent concentration to achieve a total flooding condition in a hazard volume.
Units: metric units of measurements are in accordance with the modernised metric system, known as the In-
ternational System of Units (SI). Three units - inch, litre and bar - outside of but recognised by SI, are
commonly used in fire protection. These units are listed in Table 1-1 in chapter 1.8.
VdS: an independent German institution ensuring safety and trust in the fields of fire protection and security.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
17
General information
2 General information
2.1 Introduction
The INEREX® System is a fire suppression system, that is particularly useful for suppressing fires in hazards
where an electrically non-conductive medium is required; where clean-up of other extinguishing agents is a
problem; or where the hazard is normally occupied and requires a non-toxic extinguishing agent and where an
extinguishing capability with low weight is required.
The following examples are typical hazards protected by an INEREX® System:
• Computer rooms
• Telecommunication switch gear
• Storages
• Vaults
• Process equipment
• Machinery spaces
• Historic buildings and museums
• All normally occupied or non-occupied electronic areas where equipment is either very sensitive or
irreplaceable
The INEREX® System is designed for fires of class A, class B and class C.
• Class A fire: fire in ordinary combustible materials, e.g. fires involving solid materials normally of organic na-
ture, such as rubbers, wood, paper, data processing equipment etc. These fires typically produce deep-seat-
ed fires that may require higher design concentrations for extended holding times.
• Class A polymeric fire: fire in plastic materials such as polypropylene or PVC. These fires typically produce
deep-seated fires that may require extended holding times.
• Class B fire: fire in combustible liquids, mainly hydrocarbons, solvents, glycols, methanol, oils, tars and
other additives. These fires produce surface fires.
• Class C fire: NFPA 2001, fire that involves energised electrical equipment where the electrical resistivity of
the extinguishing agent is of importance.
The INEREX® System uses inert gas as extinguishing agent. The inert gas is stored in steel cylinders located in
a safe and accessible location. The inert gas is distributed and discharged into the area affected by fire through
a network of pipes and nozzles. Each nozzle is drilled with a specific fixed opening designed to deliver a uniform
amount of extinguishing agent into the protected area. The cylinders are connected to the pipework or the
manifold by means of flexible discharge hoses and discharge pressure regulators. Various types of actuators are
available for the release of the inert gas into the protected area in case of fire.
The INEREX® System can be actuated by detection and control equipment for automatic system operation along
with providing local and remote manual operation as needed. Accessories are used to provide alarms, ventilation
control, door closures, or other auxiliary shutdown functions.
The INEREX® System combines an environmentally safe extinguishing agent and specially developed
components for a fast extinguishing agent discharge. The resulting rapid fire suppression reduces property
damage to the lowest possible level.
The INEREX® System is designed for total flooding in accordance with NFPA 2001 Standard on Clean Agent Fire
Extinguishing Systems, ISO14520-1 Gaseous fire-extinguishing systems and the U.S. Environmental Protection
Agency.
The complexity of the INEREX® System does not allow for any simple method of manual calculation. Therefore,
the flow calculations and design criteria described in this manual have been incorporated into a VdS calculation
software. The calculations are based on conserving mass, energy and momentum in the pipework. The routine
calculates the flow in quasi-steady state steps from the initiation of the discharge to the final gas distribution.
The system designer must become thoroughly familiar with this manual in order to learn the proper procedures
for applying the input parameters to the INEREX® System flow calculation software. There are a number of
limitations to these input parameters which must be observed if accurate results are to be obtained.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
18 General information
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
19
General information
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
20 General information
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
21
Component descriptions
3 Component descriptions
This chapter provides a functional description of the components in the INEREX® System designed for use with
inert gases. CEODEUX Extinguisher Valves Technology S.A. offers all components to configure a complete 200
or 300 bar system.
DANGER!
For your own safety, do not allow anyone other than fire protection personnel - qualified and
trained by CEODEUX Extinguisher Valves Technology S.A. - to install, service or repair this
INEREX® System. Any improper use is forbidden.
NOTE:
The INEREX® System must not be combined with components produced by other manufacturers
than CEODEUX Extinguisher Valves Technology S.A. The use of non-genuine CEODEUX
Extinguisher Valves Technology S.A. components shall be considered as improper use. We
accept no liability. The limited warranty does not apply to malfunction, failure or damage of the
INEREX® System if non-genuine components are used.
NOTE:
The INEREX® System is built according to the state-of-the-art and recognised safety rules
and regulations. The INEREX® System must be installed, inspected, maintained, tested and
recharged only by fire protection personnel - qualified and trained by CEODEUX Extinguisher
Valves Technology S.A. - in accordance with existing regulations, rules and guidelines including
requirements of the Governmental and/or Local Authority and other regulatory authorities, e.g.:
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems.
NOTE:
CEODEUX Extinguisher Valves Technology S.A. cannot be held responsible for eventual
damage caused by inappropriate, improper or irresponsible use and/or for repairs made to the
product by unauthorised personnel. Intended use includes observance of this manual and all
other applicable documents, as well as adherence to maintenance and inspection conditions.
NOTE:
Due to continuous improvement of our products, CEODEUX Extinguisher Valves Technology
S.A reserves the right to modify products without prior notice. Therefore, the delivered compo-
nents may differ from the components pictured in this chapter, without any change in the use
and the characteristics of the components.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
22 Component descriptions
12
16
13
11 8
7
16
6 14 15
4
5
10
17
9
18
3
2
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
23
Component descriptions
3.1 Cylinder
The cylinder for vertical installation only is a red-coated steel construction. The cylinders are constructed, tested
and marked in accordance with DOT and/or CE regulations. Each cylinder is delivered with a protection cap.
Technical data
Part number 028800020 028800017 028800021
Water volume 80 litres 80 litres 67 litres 140 litres
External diameter 267 ± 1 mm 267 ± 1 mm 267 ± 1 mm
Height 1760 ± 10 mm 1680 ± 10 mm 1470 ± 10 mm
Working pressure 200 bar 300 bar 200 bar 300 bar
Test pressure 300 bar 450 bar 300 bar 450 bar
Material CrMo-steel CrMo-steel CrMo-steel CrMo-steel
Protection cap thread W80 x 1/11“ W80 x 1/11“ W80 x 1/11“ W80 x 1/11“
Conformity 2010/35/EU - TPED 2010/35/EU - TPED 2010/35/EU -TPED 2010/35/EU - TPED
Cylinder/valve assembly
Part number (empty) B04807002 B04808003 B04807001
Part number (filled IG01) B04807102 B04808103 B04807101
Part number (filled IG100) B04807202 B04808203 B04807201
Part number (filled IG55) B04807302 B04808303 B04807301
Part number (filled IG541) B04807402 B04808403 B04807401
3.1.1 Cylinder mounting parts single row for 67l and 80l cylinder
Galvanised steel wall mounting rails and clamps are used to mount the cylinders in a vertical position to the wall.
The wall mounting rail is available for 1 to 10 cylinders.
End cap
Cylinder wall mounting rail
Clamp for
cylinder
End cap
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
24 Component descriptions
3.1.2 Cylinder mounting parts double row for 67l and 80l cylinder
Galvanised steel wall mounting rails, bolts and nuts are used to mount the cylinders with wooden brackets in a
vertical position to the wall. The cylinder mounting parts are available in two sizes for 4 or 6 cylinders.
End cap
rail
ll mounting
Cylinder wa
acket
Nuts Rail br
et
brack
Middle
et
brack
Outer
Bolts
Washer Nuts
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
25
Component descriptions
Discharge port
Port for pilot hose
W21.8 x 1/14 DIN 477
Monitoring port
(for pressure switch or
pressure gauge)
Burst disc
300 bar (200 bar version)
450 bar (300 bar version)
Cylinder connection
Outlet safety plug
25 E EN 629-1
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
26 Component descriptions
3.2.2 Gasket
Technical data
Part number 024100104
Working pressure 360 bar at 20°C
Material PA 6
The gasket is used in between the connection of the pressure regulator to
the discharge port of the valve.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
27
Component descriptions
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
28 Component descriptions
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
29
Component descriptions
3.3.3.3 Adapter
Technical data
Part number 029510006
Connection G1/8” / M12 x 1.5
Material Brass
The adapter is used for the connection of pilot hoses to the manual/pneumatic
release device or to the pneumatic release device.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
30 Component descriptions
The pilot hose is used to build up the pilot line, e.g. for the connection of
several release devices and/or for the connection of the valve to the release
device.
The pilot hose may only be used in accordance with component approv-
al in stationary inert gases fire extinguishing systems. Several cylinders,
equipped with valves, can be connected with pilot hoses.
DKOL - DN 6 form N DIN 20078 connection with O-Ring fit to flare (24°) DIN EN ISO 8434-1 light series.
M12 x 1.5
M12 x 1.5
Marking: Part number, approval sign, working pressure, type 3, date of manufac-
ture (week/year)
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
31
Component descriptions
Marking: Part number, approval sign, working pressure, type 1, date of manufacture (week/year)
Length 400 mm
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
32 Component descriptions
Marking: Part number, approval sign, working pressure, type 1, date of manufacture (week/year)
Length 400 mm
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
33
Component descriptions
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
34 Component descriptions
3.8 Manifolds
Manifolds are used to connect several cylinders at 100 bar pressure. They can only be used with valves with pressure
regulators.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
35
Component descriptions
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
36 Component descriptions
3.9 Nozzles
Technical data
Connection thread R1/2” DIN EN 10226-1
R3/4” DIN EN 10226-1
R1” DIN EN 10226-1
R1 1/2” DIN EN 10226-1
Working pressure 60 bar at 20°C
Material nozzle body Brass
Conformity VdS
The nozzle distributes the extinguishing agent evenly in the extinguishing zone in the calculated flooding time.
Nozzles are designed to direct the discharge of inert gas using the stored pressure from the cylinders. Nozzles
are available in 360° discharge patterns.
The nozzle selection depends on the hazard and location to be protected.
Nozzles are available with a connection thread R1 1/2“, R1“, R1/2“ and R3/4“ and can be screwed into every
fitting corresponding to the pressure stage and the thread. The nozzle outlet must point downwards to distribute
the extinguishing agent effectively and to prevent pollution.
Connection thread Part number Orifice Diameter Part number Orifice Diameter
B04611100 3 mm B04611108 3.5 mm
B04611101 4 mm B04611109 4.5 mm
B04611102 5 mm B04611110 5.5 mm
R1/2” DIN EN 10226-1 B04611103 6 mm B04611111 6.5 mm
B04611104 7 mm B04611112 7.5 mm
B04611105 8 mm B04611113 8.5 mm
B04611106 9 mm B04611114 9.5 mm
B04611200 7 mm B04611208 7.5 mm
B04611201 8 mm B04611209 8.5 mm
B04611202 9 mm B04611210 9.5 mm
R3/4” DIN EN 10226-1 B04611203 10 mm B04611211 10.5 mm
B04611204 11 mm B04611212 11.5 mm
B04611205 12 mm B04611213 12.5 mm
B04611206 13 mm B04611214 13.5 mm
B04611300 10 mm B04611309 10.5 mm
B04611301 11 mm B04611310 11.5 mm
B04611302 12 mm B04611311 12.5 mm
B04611303 13 mm B04611312 13.5 mm
R1” DIN EN 10226-1
B04611304 14 mm B04611313 14.5 mm
B04611305 15 mm B04611314 15.5 mm
B04611306 16 mm B04611315 16.5 mm
B04611307 17 mm B04611316 17.5 mm
B04611400 15 mm B04611412 15.5 mm
B04611401 16 mm B04611413 16.5 mm
B04611402 17 mm B04611414 17.5 mm
B04611403 18 mm B04611415 18.5 mm
B04611404 19 mm B04611416 19.5 mm
R1 1/2” DIN EN 10226-1 B04611405 20 mm B04611417 20.5 mm
B04611406 21 mm B04611418 21.5 mm
B04611407 22 mm B04611419 22.5 mm
B04611408 23 mm B04611420 23.5 mm
B04611409 24 mm B04611421 24.5 mm
B04611410 25 mm B04611422 25.5 mm
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
37
Component descriptions
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
38 Design
4 Design
The design of the INEREX® System must be in accordance with, but not necessarily limited to, the
recommendations of CEODEUX Extinguisher Valves Technology S.A. and the applicable requirements set forth
in the latest editions of the following standards:
• NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems
• ISO 14520-1 Gaseous fire-extinguishing systems
The standards and requirements listed, as well as all other applicable codes and standards, must be used as
“minimum” design standards. Also, compliance with the Authority Having Jurisdiction is required and good engi-
neering practices must be implemented.
The INEREX® System is designed for total flooding in accordance with the standards mentioned above.
The designer must be trained and certified by CEODEUX Extinguisher Valves Technology S.A. The designer
must consider and address possible fire hazards within the protected enclosure at the design stage.
The designer must consider the effect of extinguishing agent distribution through the hazard when the INEREX®
System is operational and in use. The design must be based on a detailed knowledge of the protected area, its
use and the necessity of personnel protection.
It is important to consider the fire precautions of the premises as a whole. An INEREX® System can only be part
of a fire protection concept in combination with other fire protection measures, e.g. a fire detection system.
The design engineer must become thoroughly familiar with this design manual in order to define the proper pro-
cedures for applying the input parameters to the VdS calculation software. There are a number of limitations to
these input parameters which must be observed if accurate results are to be obtained. Most of these limitations
are in the VdS calculation software.
NOTE:
For a sample calculation with the VdS calculation software, refer to chapter 4.5.
Before you start to design an INEREX® System, the following data must be known:
• Kind and use of enclosure to be protected (e.g. computer room, storage room, museum etc.)
• Volume of the enclosure including false ceilings and/or subfloors and special characteristics of the enclo-
sure (e.g. closable and unclosable openings, ventilation systems, unclosable leakages at cables entries,
windows)
• Minimum and maximum temperatures in the enclosure
• Altitude of the enclosure above or below sea level
• Structural strength of the enclosure
• Storage conditions of the cylinders
• Distance between the protected enclosure and the storage room of cylinders
The INEREX® System is designed for fires of class A, B, C (refer also to chapter 2). The INEREX® System is not
designed for local application.
The extinguishing agents IG01, IG100, IG55 and IG541 must not be used on fires involving the following
materials:
• Materials that contain their own oxygen supply and liberate oxygen when burning, such as cellulose
nitrate, gunpowder
IG55, IG541 and IG100 are not effective for fires of:
• Metal hydrides
• Reactive metals such as sodium, potassium, magnesium, titanium, zirconium, uranium and plutoni-
um.
For fires involving metal hydrides or reactive metals IG01 can be used.
However, there are certain restrictions that must be addressed by the design engineer before applying the input
data. The following chapters describe the essential design parameters and design limitations which must be
considered.
CAUTION!
For hazards beyond the scope described in this manual, the designer must consult CEODEUX
Extinguisher Valves Technology S.A., NFPA 2001 and ISO14520-1 on the suitability of inert gas
as extinguishing agent for the protection, necessary design concentration and personnel expo-
sure effects from that concentration.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
39
Design
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
40 Design
NOTE:
To avoid loss of extinguishing agent through openings to adjacent areas, openings must either
be permanently sealed or equipped with automatic closures.
CAUTION!
Forced-air ventilating systems using additional air must shut down or close automatically be-
fore or simultaneously with the discharge of the extinguishing agent, because their continued
operation can adversely affect the performance of the INEREX® System or result in propagation
of the fire.
NOTE:
A temperature adjustment is already integrated in this formula. It is universally valid for designs
according to NFPA 2001 (2000) and ISO 14520-1 (2000).
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
41
Design
NOTE:
If there are flammable liquids in one calculation area, the maximum design concentration must
be applied.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
42 Design
Tempera- Specific Volume requirements of IG01 per unit volume of Hazard Vagent/VEnclosure
ture °C vapour Design Concentration (Percent by Volume)
volume
m3/kg C
T S 34 38 42 46 50 54 58 62
-40 0.479 0 0.522 0.601 0.685 0.775 0.872 0.976 1.091 1.217
-35 0.489 3 0.511 0.588 0.671 0.758 0.853 0.956 1.068 1.191
-30 0.499 6 0.501 0.576 0.657 0.743 0.836 0.936 1.046 1.167
-25 0.509 8 0.491 0.565 0.644 0.728 0.819 0.917 1.025 1.143
-20 0.520 1 0.481 0.554 0.631 0.714 0.803 0.899 1.005 1.120
-15 0.530 4 0.472 0.543 0.619 0.700 0.787 0.882 0.985 1.009
-10 0.540 6 0.463 0.533 0.607 0.686 0.772 0.865 0.966 1.078
-5 0.550 9 0.454 0.523 0.596 0.674 0.758 0.849 0.948 1.058
0 0.561 2 0.446 0.513 0.585 0.661 0.744 0.833 0.931 1.038
5 0.571 5 0.438 0.504 0.574 0.649 0.731 0.818 0.914 1.020
10 0.581 7 0.430 0.495 0.564 0.638 0.718 0.804 0.898 1.002
15 0.592 0 0.423 0.486 0.554 0.627 0.705 0.790 0.883 0.984
20 0.602 3 0.416 0.478 0.545 0.616 0.693 0.777 0.868 0.968
25 0.612 6 0.409 0.470 0.536 0.606 0.682 0.764 0.853 0.951
30 0.622 8 0.402 0.462 0.527 0.596 0.670 0.751 0.839 0.936
35 0.633 1 0.395 0.455 0.518 0.586 0.659 0.739 0.825 0.920
40 0.643 4 0.389 0.448 0.510 0.577 0.649 0.727 0.812 0.906
45 0.653 6 0.383 0.440 0.502 0.568 0.639 0.716 0.799 0.892
50 0.663 9 0.377 0.434 0.494 0.559 0.629 0.704 0.787 0.878
55 0.674 2 0.371 0.427 0.487 0.550 0.619 0.694 0.775 0.864
60 0.684 5 0.366 0.421 0.479 0.542 0.610 0.683 0.763 0.851
65 0.694 7 0.360 0.414 0.472 0.534 0.601 0.673 0.752 0.839
70 0.705 0 0.355 0.408 0.465 0.526 0.592 0.663 0.741 0.827
75 0.715 3 0.350 0.403 0.459 0.519 0.584 0.654 0.730 0.815
80 0.725 6 0.345 0.397 0.452 0.511 0.575 0.645 0.720 0.803
85 0.735 8 0.340 0.391 0.446 0.504 0.567 0.636 0.710 0.792
90 0.746 1 0.335 0.386 0.440 0.497 0.560 0.627 0.700 0.781
95 0.756 4 0.331 0.381 0.434 0.491 0.552 0.618 0.691 0.770
100 0.766 6 0.326 0.376 0.428 0.484 0.545 0.610 0.682 0.760
Table 4-5 Total flooding quantity for IG01 (SI Units)
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
43
Design
Tempera- Specific Volume requirements of IG100 per unit volume of Hazard Vagent/VEnclosure
ture °C vapour Design Concentration (Percent by Volume)
volume
m3/kg C
T S 34 38 42 46 50 54 58 62
-40 0.682 5 0.523 0.601 0.685 0.775 0.872 0.977 1.091 1.217
-35 0.697 1 0.512 0.589 0.671 0.759 0.853 0.956 1.068 1.191
-30 0.711 8 0.501 0.576 0.657 0.743 0.836 0.936 1.046 1.167
-25 0.726 4 0.491 0.565 0.644 0.728 0.819 0.917 1.025 1.143
-20 0.741 1 0.481 0.554 0.631 0.714 0.803 0.899 1.005 1.120
-15 0.755 7 0.472 0.543 0.619 0.700 0.787 0.882 0.985 1.009
-10 0.770 4 0.463 0.533 0.607 0.686 0.772 0.865 0.966 1.078
-5 0.785 0 0.454 0.523 0.596 0.674 0.758 0.849 0.948 1.058
0 0.799 7 0.446 0.513 0.585 0.661 0.744 0.833 0.931 1.038
5 0.814 3 0.438 0.504 0.574 0.649 0.731 0.818 0.914 1.020
10 0.829 0 0.430 0.495 0.564 0.638 0.718 0.804 0.898 1.002
15 0.843 6 0.423 0.486 0.554 0.627 0.705 0.790 0.883 0.984
20 0.858 3 0.416 0.478 0.545 0.616 0.693 0.777 0.868 0.968
25 0.872 9 0.409 0.470 0.536 0.606 0.682 0.764 0.853 0.951
30 0.887 6 0.402 0.462 0.527 0.596 0.670 0.751 0.839 0.936
35 0.902 2 0.395 0.455 0.518 0.586 0.659 0.739 0.825 0.920
40 0.916 9 0.389 0.448 0.510 0.577 0.649 0.727 0.812 0.906
45 0.931 5 0.383 0.440 0.502 0.568 0.639 0.715 0.799 0.892
50 0.946 2 0.377 0.434 0.494 0.559 0.629 0.704 0.787 0.878
55 0.960 8 0.371 0.427 0.487 0.550 0.619 0.694 0.775 0.864
60 0.975 5 0.366 0.421 0.479 0.542 0.610 0.683 0.763 0.851
65 0.990 1 0.360 0.414 0.472 0.534 0.601 0.673 0.752 0.839
70 1.004 8 0.355 0.408 0.465 0.526 0.592 0.663 0.741 0.827
75 1.019 4 0.350 0.402 0.459 0.519 0.584 0.654 0.730 0.815
80 1.034 1 0.345 0.397 0.452 0.511 0.575 0.645 0.720 0.803
85 1.048 7 0.340 0.391 0.446 0.504 0.567 0.636 0.710 0.792
90 1.063 4 0.335 0.386 0.440 0.497 0.559 0.627 0.700 0.781
95 1.078 0 0.331 0.381 0.434 0.491 0.552 0.618 0.691 0.770
100 1.092 7 0.326 0.375 0.428 0.484 0.544 0.610 0.681 0.760
Table 4-6 Total flooding quantity for IG100 (SI Units)
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
44 Design
Tempera- Specific Volume requirements of IG55 per unit volume of Hazard Vagent/VEnclosure
ture °C vapour Design Concentration (Percent by Volume)
volume
m3/kg C
T S 34 38 42 46 50 54 58 62
-40 0.568 17 0.524 0.603 0.688 0.778 0.875 0.980 1.095 1.221
-35 0.563 24 0.513 0.591 0.673 0.761 0.856 0.959 1.072 1.196
-30 0.587 32 0.503 0.579 0.659 0.746 0.839 0.940 1.050 1.171
-25 0.599 40 0.493 0.567 0.646 0.731 0.822 0.921 1.029 1.147
-20 0.611 48 0.483 0.556 0.633 0.716 0.806 0.903 1.008 1.125
-15 0.623 55 0.474 0.545 0.621 0.702 0.790 0.885 0.989 1.103
-10 0.635 63 0.465 0.535 0.609 0.689 0.775 0.868 0.970 1.082
-5 0.647 71 0.456 0.525 0.598 0.676 0.761 0.852 0.952 1.062
0 0.659 79 0.448 0.515 0.587 0.664 0.747 0.837 0.935 1.042
5 0.671 86 0.440 0.506 0.576 0.652 0.733 0.822 0.918 1.024
10 0.683 94 0.432 0.497 0.566 0.640 0.720 0.807 0.902 1.006
15 0.696 02 0.424 0.488 0.556 0.629 0.708 0.793 0.886 0.988
20 0.708 10 0.417 0.480 0.547 0.619 0.696 0.779 0.871 0.971
25 0.720 17 0.410 0.472 0.538 0.608 0.684 0.766 0.856 0.955
30 0.732 25 0.403 0.464 0.529 0.598 0.673 0.754 0.842 0.939
35 0.744 33 0.397 0.456 0.520 0.588 0.662 0.742 0.828 0.924
40 0.756 41 0.390 0.449 0.512 0.579 0.651 0.730 0.815 0.909
45 0.768 48 0.384 0.442 0.504 0.570 0.641 0.718 0.802 0.895
50 0.780 56 0.378 0.435 0.496 0.561 0.631 0.707 0.790 0.881
55 0.792 64 0.373 0.429 0.488 0.553 0.622 0.696 0.778 0.868
60 0.804 71 0.367 0.422 0.481 0.544 0.612 0.686 0.766 0.855
65 0.816 79 0.362 0.416 0.474 0.536 0.603 0.676 0.755 0.842
70 0.828 87 0.356 0.410 0.467 0.528 0.594 0.666 0.744 0.830
75 0.840 95 0.351 0.404 0.460 0.521 0.586 0.656 0.733 0.818
80 0.853 02 0.346 0.398 0.454 0.513 0.578 0.647 0.723 0.806
85 0.865 10 0.341 0.393 0.448 0.506 0.569 0.638 0.713 0.795
90 0.877 18 0.337 0.387 0.441 0.499 0.562 0.629 0.703 0.784
95 0.889 26 0.332 0.382 0.435 0.493 0.554 0.621 0.693 0.773
100 0.901 33 0.328 0.377 0.430 0.486 0.547 0.612 0.684 0.763
Table 4-7 Total flooding quantity for IG55 (SI Units)
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
45
Design
Tempera- Specific Volume requirements of IG541 per unit volume of Hazard Vagent/VEnclosure
ture °C vapour Design Concentration (Percent by Volume)
volume
m3/kg C
T S 34 38 42 46 50 54 58 62
-40 0.562 4 0.521 0.600 0.684 0.773 0.870 0.975 1.089 1.214
-35 0.574 3 0.511 0.587 0.669 0.757 0.852 0.954 1.066 1.189
-30 0.586 3 0.500 0.575 0.656 0.742 0.834 0.935 1.044 1.165
-25 0.598 2 0.490 0.564 0.643 0.727 0.818 0.916 1.023 1.142
-20 0.610 2 0.481 0.553 0.630 0.713 0.802 0.898 1.003 1.119
-15 0.622 1 0.471 0.542 0.618 0.699 0.786 0.881 0.984 1.098
-10 0.634 1 0.463 0.532 0.606 0.686 0.772 0.864 0.966 1.077
-5 0.646 0 0.454 0.522 0.595 0.673 0.757 0.848 0.948 1.067
0 0.658 0 0.446 0.513 0.584 0.661 0.744 0.833 0.931 1.038
5 0.669 9 0.438 0.504 0.574 0.649 0.730 0.818 0.914 1.019
10 0.681 9 0.430 0.495 0.564 0.638 0.717 0.804 0.898 1.001
15 0.693 8 0.423 0.486 0.554 0.627 0.705 0.790 0.882 0.984
20 0.705 8 0.416 0.478 0.545 0.616 0.693 0.777 0.868 0.968
25 0.717 7 0.409 0.470 0.536 0.606 0.682 0.764 0.853 0.951
30 0.729 7 0.402 0.462 0.527 0.596 0.670 0.751 0.839 0.936
35 0.741 6 0.395 0.455 0.518 0.586 0.660 0.739 0.826 0.921
40 0.753 6 0.389 0.448 0.510 0.577 0.649 0.727 0.812 0.906
45 0.765 5 0.383 0.441 0.502 0.568 0.639 0.716 0.800 0.892
50 0.777 5 0.377 0.434 0.494 0.559 0.629 0.705 0.787 0.878
55 0.789 4 0.371 0.427 0.487 0.551 0.620 0.694 0.776 0.865
60 0.801 4 0.366 0.421 0.480 0.543 0.610 0.684 0.764 0.852
65 0.813 3 0.361 0.415 0.473 0.535 0.601 0.674 0.753 0.840
70 0.825 3 0.355 0.409 0.466 0.527 0.593 0.664 0.742 0.827
75 0.837 2 0.350 0.403 0.459 0.519 0.584 0.655 0.731 0.816
80 0.849 2 0.345 0.397 0.453 0.512 0.576 0.645 0.721 0.804
85 0.861 1 0.341 0.392 0.446 0.505 0.568 0.636 0.711 0.793
90 0.873 1 0.336 0.386 0.440 0.498 0.560 0.628 0.701 0.782
95 0.885 0 0.331 0.381 0.434 0.491 0.553 0.619 0.692 0.772
100 0.897 0 0.327 0.376 0.429 0.485 0.545 0.611 0.683 0.761
Table 4-8 Total flooding quantity for IG541 (SI Units)
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
46 Design
4.2.4 Adjustments
4.2.4.1 Altitude and temperature adjustments
According to NFPA 2001 (2000) and ISO 14520-1 (2000), the design quantity of the extinguishing agent must
be adjusted to compensate only for ambient pressures that vary by more than 11% (equivalent to approximately
1000 metres of elevation change) from standard sea level pressure (1.013 mbar). The ambient pressure is af-
fected by changes in altitude, pressurisation or de-pressurisation of the protected enclosure, and weather-relat-
ed barometric pressure changes. The quantity of extinguishing agent is determined by multiplying the quantity
determined in chapter 4.2.1 by the ratio of the average ambient enclosure pressure to the standard sea level
pressure. Correction factors for gaseous agents are shown in table 4-9.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
47
Design
The filling tolerance for each cylinder is +0/-2.5 % of the nominal filling pressure.
4.3.1 Dependency of the pressure inside the cylinder and the ambient temperature
The filling pressure of 200 bar or 300 bar is measured at 15°C according to international standards. The pressure
inside the cylinder depends on the ambient temperature.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
48 Design
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
49
Design
4.4 Limitations
4.4.1 Limitations cylinders
• The floor of the storage room must be able to carry the weight of the filled cylinders.
Weight per metre of 67 litres cylinders 200 bar cylinders
Single row 310 kg
Double row 620 kg
Table 4-11 Storage floor loading capacity for 67 litres cylinders per metre
Weight per metre of 80 litres cylinders 200 bar cylinders 300 bar cylinders
Single row 360 kg 530 kg
Double row 720 kg 1060 kg
Table 4-12 Storage floor loading capacity for 80 litres cylinders per metre
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
50 Design
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
51
Design
• Obstructions located near the nozzle could impede the discharge of extinguishing agent and can affect the
distribution of the extinguishing agent within the enclosure. Obstructions, e.g. ducts, cables, trays, large con-
duits, and light fixtures can disrupt the flow pattern of the extinguishing agent from the nozzles. If the flow of
the extinguishing agent is forced down to the floor, for example, it is unlikely that required concentration will be
achieved at the mid or upper elevations. Certainly a uniform dispersion and concentration will not be achieved.
NOTE:
The number, placement and type of the nozzles must ensure that the design concentration will
be distributed in all parts of the protected area. The extinguishing agent must not splash flam-
mable liquids or create dust clouds that could extend the fire, create an explosion, or otherwise
adversely affect the contents or integrity of the protected area.
4 Limitations regarding the types of tee splits (for example: bullhead or side outlet) and attached fittings
The intended range of flow splits and information on the orientation, installation, and critical length for each
type of split.
The type of splits covered here are side/through and bullhead orientations. Since this is for inert gas, the tee
orientation can be in any direction.
Bullhead tee split limits Side/through split limits
Minimum split 50% / 50% 20% / 80%
Maximum split 13% / 87% 60% / 40%
Since bullhead tee outlets are symmetrical, either of For side tees the side split is referenced first with the
them can be the major/minor flow. through split referenced second. So the side can han-
dle between 20% and 60% of the extinguishing agent
split, while the through can handle between 80% and
40% of the extinguishing agent split.
Table 4-15 Bullhead tee split limits and side/through split limits
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
52 Design
OUT OUT OUT -50% OUT -50% OUT -87% OUT -13%
5 Limitations due to conditions that result in an extinguishing agent time imbalance at each nozzle, for example
limits on the variance for extinguishing agent arrival time and run-out time between nozzles
Use the VdS calculation software limitations for the maximum difference in transport time as limitation that
addresses both arrival and run-out imbalances. For the testing conducted, the limit would be 14.05 seconds.
7 Method for determining nozzle orifice area and selection of nozzles, as well as nozzle flow information, limits
for minimum and maximum nozzle orifice area in relation to the attached pipe area
The method to determine the nozzle orifice area is usually done by the VdS calculation software, so this part
of the UL requirements will be taken care of in your calculation examples.
• minimum area ratio: 0.01733 or 1.7%
• maximum area ratio: 0.25641 or 25.6%
8 Nozzle area coverage limitations and information on location of nozzles in the protected area
Refer to chapter 4.4.3 and chapter 4.4.3.1.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
53
Design
12 Description of the design of an INEREX® System including a sample calculation including all VdS calculation
software input screens and the resulting hydraulic calculation report
Refer to chapter 4.5
13 Equivalent length values of all fittings and all system equipment through which the extinguishing agent flows
The resistance coefficient is integrated automatically into the VdS calculation software.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
54 Design
Number of cylinders
Storage temperature
• Component, pipe, and nozzle data:
Resistance coefficients of combinations of valves, discharge hoses and check valves
Nozzle coefficients
• Nozzles
Nozzle type
Number of nozzle orifices for each nozzle
• Pipes
Pipe type
Length
• Fittings: straight unions, elbow unions, tee unions, cross unions, blanking and adaptors
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
55
Design
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
56 Design
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
57
Design
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
58 Design
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design manual
59
Design
Project:
Project-No:
Building:
Object: COMPUTER ROOM - 140 m3
Contractor:
Owner:
Project engineer:
Date: 17/02/2015
Regulation rule for calculation of IG55 quantities: NFPA 2001
Altitude above sealevel: 0m
Atmospheric correction factor: 1,000
Error messages:
No error detected
10
11
11002
8
9
6
11001 4
7
5
2
3
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
60 Design
Calculation results:
Discharge time:
Discharge time : 55,0 s
System information:
Pipe system working pressure: 33,0 bar abs
Container working pressure: 216,9 bar abs
Total network volume: 7,5 l
Pipe system pressures during the controlled phase of the discharge 24,1 seconds after start
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
61
Design
Nozzle data:
Max. transport time difference between nozzles 11002 and 11001 is 0,05 s
Concentrations:
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Design Manual
62 Design
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Design Manual
63
Design
125
100
100
75
75
50
50
25
25
0 0
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90
Time [s] Time [s]
1,8 300
1,5
250
1,3
200
1,0
150
0,8
100
0,5
0,3 50
0,0 0
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90
Time [s] Time [s]
40 35
35
30
30
25
25
20
20
15
15
10
10
5 5
0 0
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90
Time [s] Time [s]
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
64 Installation
5 Installation
The installation of the INEREX® System must be in accordance with, but not necessarily limited to, the
recommendations of CEODEUX Extinguisher Valves Technology S.A., plus the applicable requirements set
forth in the latest editions of the following standards:
• NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems
• ISO 14520-1 Gaseous fire-extinguishing systems
The standards and requirements listed, as well as all other applicable codes and standards, must be used as
“minimum” installation standards. Also, compliance with the Authority Having Jurisdiction is required and good
engineering practices must be implemented.
The INEREX® System must be installed in such a way as to facilitate proper inspection, testing, manual operation,
recharging and any other required maintenance as may be necessary. The INEREX® System must not be subject to
severe weather conditions or mechanical, chemical or other damage that could render the equipment inoperative.
5.1 Scope
The following installation procedures should, as a minimum, be carried out as described. The procedures togeth-
er with commissioning checks are intended to ensure the required designed properties and the correct function/
operation of the installed INEREX® System. The installer of an INEREX® System must be familiar with these
procedures. The intentions of the procedures are also to minimise risk to personnel during and after installation.
5.2 Responsibilities
5.2.1 Responsibilities – design engineer
It is the responsibility of the design engineer of an INEREX® System to ensure that the requirements listed herein
are incorporated in the project documentation and that detailed information and procedures are made available
to the installer.
5.3 Pipework
5.3.1 Selection of pipework
The correct type and size of pipes and fittings must be selected individually for each system. Temperatures,
operating pressures and ambient conditions must be considered.
According to NFPA 2001 and ISO 14520-1, pipes and fittings must be of non-combustible material with physical
and chemical characteristics such that its integrity under stress can be predicted with reliability. Pipes and fittings
must be able to withstand the anticipated pressures and low temperatures.
CAUTION!
Do not use non-metallic pipes and class 150-lb or cast-iron fittings!
CAUTION!
The identification number of each pipe must not be painted over, concealed, or removed!
CAUTION!
Any deviations in the routing of the pipework or in the number of fittings must be approved by
the design engineer before installation!
CAUTION!
The pipework must not be subjected to mechanical, chemical, vibration or other damages.
The selected piping schedule must always be in accordance with the requirements of the Authority Having Ju-
risdiction.
Pressure rated pipes like standard carbon steel pipes, low temperature carbon steel pipes, stainless steel pipes,
pipes according to AISI 304 or AISI 316 can be used for the pipework.
Recommended pipe qualities and fittings are specified below. Fittings must withstand a test pressure of 1.5 times
of the maximum pressure in the pipework.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
65
Installation
The wall thickness of alternative pipe qualities shall be calculated in accordance with ASME B31.1. The following
pipes and fittings can be used, for example:
Example 1:
• Pipes: Galvanised welded steel pipes according to DIN 2458, steel 37-2.
• Fittings: Malleable Iron ½” to and including 3” according to DIN 2950/EN 10242 pressure tested at mill
to 100 bar.
Seamless steel fittings to according to EN 10241 pressure tested at mill to 150 bar.
Example 2:
• Pipes: Schedule 40, ANSI B 36.10 - 1979, ASTM A 53, Grade B / A 106 Grade B.
Fittings: Malleable Class 300 Iron or Class 3000 (up to and including 3” above 3”).
• Other pipe and fitting qualities depending on local regulations.
The pipework must be installed so that it cannot be damaged by its own weight, temperature, fluctuations, vibra-
tion, release of the extinguishing agent or other installation inherent or factory influences. All pipework must be
easily accessible and must additionally be secured by pipe supports.
All threads of the pipes and pipe components like fittings, nozzles must be sealed with PTFE tape. PTFE tape
must be applied according to EN 751-3 or other applicable standards.
Pipe diameters must be determined with the VdS calculation software. Ensure that the type and size of the se-
lected pipes in the VdS calculation software are identical to the pipes installed on-site.
Pipe size Outside diameter of pipe OD Hand tight engagement Nominal useful length
(inch) (mm) (inch) (mm) (inch) (mm) (inch)
1/2 21.34 0.840 8.13 0.320 13.56 0.5337
3/4 26.67 1.050 8.61 0.339 13.86 0.5457
1 33.40 1.315 10.16 0.400 17.34 0.6828
1 1/4 42.16 1.660 10.67 0.420 17.95 0.7068
1 1/2 48.26 1.900 10.67 0.420 18.38 0.7235
2 60.32 2.375 11.07 0.436 19.22 0.7565
2 1/2 73.02 2.875 17.32 0.682 28.89 1.1375
3 88.90 3.500 19.46 0.766 30.48 1.2000
Table 5-1 NPT threads according to ANSI/ASME B1.20.1
Pipe size Outside diameter of pipe OD Hand tight engagement Nominal useful length
(not defined in ISO 7-1)
(inch) (mm) (inch) (mm) (inch) (mm) (inch)
1/2 21.34 0.840 8.2 0.3228 13.2 0.5197
3/4 26.67 1.050 9.5 0.3740 14.5 0.5709
1 33.40 1.315 10.4 0.4094 16.8 0.6614
1 1/4 42.16 1.660 12.7 0.5000 19.1 0.7520
1 1/2 48.26 1.900 12.7 0.5000 19.1 0.7520
2 60.32 2.375 15.9 0.6260 23.4 0.9213
2 1/2 73.02 2.875 17.5 0.6890 26.7 1.0512
3 88.90 3.500 20.6 0.8110 29.8 1.1732
Table 5-2 R threads according to ISO 7-1
Although the pipework is not subjected to continuous pressurisation, care must be taken that the type of pipes
installed can withstand the maximum stress at maximum storage temperatures. According to NPFA 2001 the
maximum allowable stress levels must be established at values of 67% of the minimum yield strength or 25% of
the minimum tensile strength, whichever is less.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
66 Installation
chanical, chemical, vibration, or other damage. Combustible materials must not be used. Obey also the standard
ASME B31.1, Power Piping Code.
Pipe supports must be connected directly to the structure of the building and must not be used as supports for
other objects. The structure of the building to which the pipe supports are attached must be strong enough to
take the load.
The low temperature generated during discharge must be taken into account when designing pipe supports. The
pipe supports and their anchors must also be able to withstand static and dynamic loads.
Pipes longer than 1m must be fixed with pipe supports. The maximum distance between two pipe supports along
the pipework must not exceed the values given in table 5-3.
Nominal diameter (mm) Maximum distance between two pipe supports (m)
< DN25 2
DN25 to DN50 3
> DN50 4
Table 5-3 Maximum distance between two pipe supports
The distance between a pipe support and the last nozzle must be as short as possible and must not exceed:
• 0.1m for pipes of a nominal diameter less than or equal to DN25
• 0.25m for pipes of a nominal diameter greater than or equal to DN25
NOTE:
When selecting pipe supports, consider the galvanic corrosion potential between the selected
materials.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
67
Installation
CAUTION!
The nozzles must be installed such that they will not cause injury to personnel. The extinguish-
ing agent must not be discharged at head height or below where people in a normally occupied
area could be injured by the discharge. The extinguishing agent must not directly be discharged
on any loose objects or shelves, cabinet tops or similar surfaces where loose objects could be
propelled by the discharge.
NOTE:
Nozzles must be installed in strict accordance with the system drawings. Any deviations in the
location of the nozzles or in the number of nozzles must be approved by the design engineer
before installation.
NOTE:
We recommend to mark each nozzle with a special sealing paint, so that it is possible to find out
if the pipework or the nozzles were manipulated.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
68 Installation
5.4 Cylinders
5.4.1 Labels
Cylinders are filled with the extinguishing agent at a CEODEUX Extinguisher Valves Technology S.A. manufac-
turing facility and labelled with filling, safety, transport, maintenance and warning information.
DANGER: Pressurized
cylinder capable of violent
discharge! Never handle or
IG 01 (Argon) - 80 L - 300 bar Maintenance:
Mimimum Annually:
transport without safety
INEREX Clean Agent Fire Suppression System • Check Pressure gauge. If
pressure loss exceeds
devices installed. The
pressurized cylinder can be WARNING: THE DISCHARGE OF CLEAN AGENT 10% (adjusted for
extremely dangerous and temperature) replace
can cause property SYSTEMS TO EXTINGUISH A FIRE CAN RESULT IN A unit.
damage, severe injury or POTENTIAL HAZARD TO PERSONNEL FROM THE • Check that all parts are
death. Safety plugs must
be installed in the NATURAL FORM OF THE CLEAN AGENT OR FROM THE free from damage,
cylinders are held in
discharge outlets at all PRODUCTS OF COMBUSTION THAT RESULT FROM place, tubing pipe and
times unless mounted in
the bracket or otherwise EXPOSURE OF THE AGENT TO THE FIRE OR HOT nozzles are secure
safely secured. SURFACES. UNNECESSARY EXPOSURE OF and free from damage
and nozzles are
Argon compressed
PERSONNEL EITHER TO THE NATURAL AGENT OR TO free from obstructions.
UN 1006 THE PRODUCTS OF DECOMPOSITION SHALL BE • Record date and service
AVOIDED. performed on
record tag provided.
FACTORY FILLED
SPECIFICATIONS FOR Prior to installation, read and comply with all the INEREX Clean Agent Fire • Safely restore system to
MODEL B04808103 Suppression Systems Design, Installation and Maintenance Manual and this label. Only operating condition.
TARE WEIGHT trained personnel shall store, handle, transport, install, inspect, maintain, and test cylinder
and components in accordance with:
• National Fire Protection Association Standard 2001 Titled: Standard for Clean Agent
Fire Extinguishing Systems.
AGENT WEIGHT
• INEREX Clean Agent Fire Suppression Systems Design Installation and
40,8 kg Maintenance Manual.
PRESSURE • Systems designed and installed in accordance with the INEREX Design Installation and
Maintenance Manual Part nr: 027650013
300 bar • Suitable for use between 0°F and 130°F (-17.8°C to +54.4°C).
• System cylinder has been factory tested to 450 bar (6500 psi)
Year of manufacturing RECYCLING PROTECTS THE ENVIRONMENT.
DO NOT DISPOSE. DISCHARGE ONLY IN CASE OF FIRE.
IF CONTAINER CONTENTS MUST BE REMOVED FOR SERVICE, MAINTENANCE
OR DISMANTLING OF THE CLEAN AGENT SYSTEM - PRIOR TO REMOVAL,
Filling location CONTACT YOUR LOCAL INSTALLER OR MANUFACTURER FOR INSTRUCTIONS
ON HANDLING EQUIPMENT AND RECLAIMING OR RECYCLING CLEAN AGENT.
DO NOT COVER, REMOVE OR DEFACE THIS LABEL.
Label Pt.# 028000311
Manufactured by:
ROTAREX 80 L
ARGON FIRETEC
Rotarex Firetec
24 rue de Diekirch, B.P. 15, L7505 Lintgen, Luxembourg
www.rotarex.com 300 bar
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
69
Installation
5.4.2 Additional safety precautions for storage rooms and protected enclosures
CAUTION!
Attach warning signs to all entrance doors of the gas storage room. The warning sign in national
language and in English (part number 02800318) must contain the following information:
DANGER!
GAS STORAGE AREA!
FIRE PROTECTION SYSTEM INEREX®
AUTHORISED PERSONNEL ONLY!
DANGER
Gas storage area!
Fire protection system INEREX
Authorised personnel only!
ROTAREX
FIRETEC
24 rue de Diekirch
B.P.19, L-7505 Lintgen
Luxembourg, Europe
CAUTION!
Attach warning signs to all entrance doors of the protected enclosures. The warning sign in na-
tional language and in English (part number 02800319) must contain the following information:
THIS ROOM IS PROTECTED BY A FIRE PROTECTION SYSTEM!
LEAVE THE ROOM IMMEDIATELY WHEN ALARM SOUNDS!
WARNING
This room is protected by a Fire protection system!
Leave the room immediately when alarm sounds.
ROTAREX
FIRETEC
24 rue de Diekirch
B.P.19, L-7505 Lintgen
Luxembourg, Europe
CAUTION!
Attach warning signs to all exit doors of the protected enclosures. The warning sign in national
language and in English (part number 02800320) must contain the following information:
THIS ROOM IS PROTECTED BY A FIRE PROTECTION SYSTEM!
LEAVE THE ROOM IMMEDIATELY WHEN ALARM SOUNDS!
TAKE THE EMERGENCY EXITS!
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
70 Installation
WARNING
This room is protected by a Fire protection system!
Leave the room immediately when alarm sounds
Take emergency exits!
ROTAREX
FIRETEC
24 rue de Diekirch
B.P.19, L-7505 Lintgen
Luxembourg, Europe
NOTE:
Operating instructions must be permanently fixed inside the storage room in a visually unob-
structed position.
NOTE:
The name of the installer, and the name of the company responsible for maintenance of the
system must be available. Record the year of installation and the date of an essential change.
Instructions for use, maintenance and relevant data of the installation must always be available,
including a plan of the pipework and plans of the protected areas.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
71
Installation
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
72 Installation
2. Calculate the position of the upper borehole of the manifold mounting rail.
NOTE:
If necessary, make a pre-assembly with the pressure regulator, the discharge hose, the
manifold and the manifold mounting rail. Remove the protection cap for pre-assembly and
immediately reinstall it after pre-assembly.
3. Hold the manifold on the wall or solid structure to mark the boreholes.
NOTE:
The open side of the manifold mounting rail must face upwards.
4. Drill the holes at the marked height.
5. Fix the manifold mounting rail to the wall or solid structure using suitable dowels and bolts.
6. Tighten the bolts. The manifold mounting rails must be firmly attached to the wall or solid structure and not
be able to move.
7. When mounting the second manifold mounting rail, take care of the correct distance between two manifold
mounting rails. The distance between two manifold mounting rails depends on the length of the manifold.
Refer to table 5-5.
Figure 5-2 Distance between the discharge port of the valve and the centre of the manifold
Distance between two manifold mounting rails
Manifold for 100 bar inert gas - 1 row
Part number B05800013 B05800014 B05800015
Connection for 2 cylinders 3 cylinders 5 cylinders
Length L 580 mm 885 mm 1495 mm
Distance between two manifold mounting rails +/- 450 mm +/- 730 mm +/- 1350 mm
Manifold for 100 bar inert gas - 2 rows
Part number B05800016 B05800017 B05800018
Connection for 4 cylinders 6 cylinders 10 cylinders
Length L 580 mm 885 mm 1495 mm
Distance between two manifold mounting rails +/- 450 mm +/- 730 mm +/- 1350 mm
Table 5-5 Distance between two manifold mounting rails
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
73
Installation
1 Check valve
a. Wrap self-adhesive PTFE tape around the R1” thread of the check valve according to EN 751-3 or any ap-
plicable standard. Stretch the PTFE t ape easily while wrapping it around the thread in order to avoid bulges
and to improve adherence.
b. Cut off the PTFE tape cleanly and press it carefully by hand against the thread.
c. Screw a check valve in each manifold inlet connection Rc1” and tighten it according to the Tapered Thread
Port Assembly, appendix pages 120 - 121.
NOTE:
According to NFPA 2001, each manifold inlet must be equipped with a check valve to pre-
vent loss of extinguishing agent and to ensure personnel safety if the system is operated
when any cylinders are removed for maintenance.
2 Manifold connector
A manifold connector is used for the connection of two manifolds.
a. Wrap self-adhesive PTFE tape around each R2” thread of the manifold according to EN 751-3 or any applica-
ble standard. Stretch the PTFE tape easily while wrapping it around the thread in order to avoid bulges and
to improve adherence.
b. Cut off the PTFE tape cleanly and press it carefully by hand against the thread.
c. Screw the manifold connector to the R2” thread of the first manifold and tighten it according to the Tapered
Thread Port Assembly, appendix pages 120 - 121.
d. Screw the second manifold into the manifold connector and tighten it according to the Tapered Thread Port
Assembly, appendix pages 120 - 121.
NOTE:
Make sure, that all check valves attached to the two manifolds, face in the same direction
and that they are correctly aligned.
3 End cap
a. Screw a manifold end cap on the one end of the manifold (R2” thread), that will not be connected to the pipework.
b. Tighten it according to the Tapered Thread Port Assembly, appendix pages 120 - 121.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
74 Installation
NOTE:
An adjustment of the manifolds may be necessary when all cylinders are in place.
NOTE:
A special kind of manifolds is equipped with an accessory port, where optional components
like a pressure gauge for manifold, a pressure relief device for manifold or a pressure and flow
detector switch can be connected to the pipework by using a fitting (refer to chapter 3.10).
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
75
Installation
4. Close the clamp for cylinder with the screw and the nut. Tighten the screw with a torque of 50-55 Nm.
NOTE:
For cylinders with a diameter of 267mm, the distance between each cylinder is 305mm.
bolt
outer bracket
rail bracket
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
76 Installation
Position Part
1a / 1b Valve 200 bar or 300 bar
2a / 2b Cylinder with valve 200 bar or 300 bar
3 Discharge pressure regulator
4 Electromagnetic release device
5 Manual/pneumatic release device
6 Pneumatic release device
7 Adapter M12x1.5 - G1/8”
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
77
Installation
Position Part
8a / 8b Pressure gauge 200 bar or 300 bar
9 Bleed valve
10 Discharge hose
11 Pilot hose
12 Manifold
13 Check valve
14 Manifold connector
15 Manifold end cap
16 Manifold mounting rail
17 Clamp for manifold
18 End cap
19 Cylinder wall mounting rail
20 Clamp for cylinder
Table 5-6 Components for system assembly
1. When all cylinders are securely fastened, remove the protection cap from the cylinder and store it near the
cylinder. Refer to figure 5-8.
DANGER!
The protection cap and the outlet safety plug must be installed on the cylinder at all times,
except when the cylinder is connected to the pipework or when the cylinder is filled or
refilled.
2. Remove the red protection cap from the valve. Refer to figure 5-8.
3. Remove the outlet safety plug from the discharge port. Refer to figure 5-8.
4. Make sure, that the discharge port W21.8 x 1/4 DIN 477 of each valve is facing to the right. Refer to figure
5-8.
Figure 5-8 Removal of the protection cap and outlet safety plug
5. Mount the pressure regulator to the discharge port of the valve. Put a gasket between valve and pressure reg-
ulator when assembling. Tighten the pressure regulator with a torque of 50 +0/-5 Nm.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
78 Installation
NOTE:
The pressure regulator is equipped with a connection port for the discharge hose.
The connection port must face upwards. Refer to figure 5-9.
6. Connect the discharge hose to the pressure regulator and to the check valve at the manifold. Tighten the
swivel nuts of the discharge hose with a torque of 30 - 40 Nm. Refer to figure 5-10.
7. Before assembling the pressure gauge, make sure that the O-ring seal back-up ring is not damaged.
Mount a pressure gauge (200 bar or 300 bar depending on your system) to the monitoring port of the valve.
The pressure gauge can be turned 360 degrees. Screw in pressure gauge to the monitoring port up to the
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
Installation
79
stop and turn back a maximum of one turn for correct orientation. The pressure gauge can be mounted and
removed even if the valve is pressurised.
If no pressure gauge is mounted the monitoring port of the valve must be sealed with the screw plug. Refer
to figure 5-11.
8. Mount a pneumatic release device on all slave cylinders and tighten the pneumatic release devices with a
torque of 50 Nm +0/-15 Nm. Refer to figure 5-12.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
80 Installation
9. Reset the electromagnetic release device with the reset tool. For resetting, screw the reset tool into the
bottom of the electromagnetic release device. Refer to figure 5-13.
DANGER!
Before mounting the electromagnetic release device on top of the master valve, check if the
red marking on the actuating pin is visible! The electromagnetic release device is activated,
if the actuating pin is visible. Reset the electromagnetic release device with the reset tool
before mounting. Failure to reset the electromagnetic release device will result in accidental
discharge when the electromagnetic release device is installed on the valve. Personal injury
and/or property damage could occur.
10. Mount the electromagnetic release device on top of the master valve and tighten it with a torque of 50 Nm
+0/-15 Nm. Refer to figure 5-14.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
81
Installation
The electromagnetic release device is operated by an electrical signal from a fire detection system. In order
to actuate the electromagnetic release device a constant DC voltage of 24V is required.
Conduit Conduit
connection connection
cover cover
Screw Screw
Gasket
Insert screw driver
in this location
1. 2. 3.
Remove the screw from the When the screw is removed from Carefully remove the inner
conduit connection cover. the conduit connection cover, casing with a small flat head
remove the gasket from the body. screw driver.
FRONT BACK
4. 5. 6.
Turn the casing around to make Connect the positive con- Reassemble the electro-
your connections. ductor to terminal (1). magnetic release device
Connect the negative feeding the connected
conductor to terminal (2). conductors through the
conduit connection.
Figure 5-15 Connecting the electromagnetic release device to power supply
11. Mount a manual/pneumatic release device on top of the electromagnetic release device and tighten it with a
torque of 50 Nm +0/-15Nm. Refer to figure 5-16.
Figure 5-16 Installation of a manual/pneumatic release device on top of the electromagnetic release device
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
82 Installation
12. Mount an adapter with the G1/8” thread to all connections of the pneumatic release devices on the slave
valves, except for the last connection on the last pneumatic release device. Tighten the adapters with a
torque of 8 -10 Nm. Refer to figure 5-17.
Figure 5-17 Connecting adapters and pilot hoses to the pneumatic release devices on the slave valves
13. Connect the pilot hoses between the adapters at the M12 x 1.5 thread and tighten the pilot hoses with a
torque of 8 - 10 Nm.
14. Screw a bleed valve with the G1/8” DIN ISO 228-1 thread into the connection of the last pneumatic release
device on the last slave valve and tighten it with a torque of 8 - 10 Nm. Refer to figure 5-18.
CAUTION!
A bleed valve must always be installed at the end of each pilot line! The bleed valve vents an
overpressure in the pilot line and therefore prevents an accidental system release.
NOTE:
The bleed valve is installed at the end of the pilot line or at the last pneumatic release device.
In case of leakage (malfunction) on the master valve, the bleed valve prevents a slow pres-
sure build-up in the pilot line and therefore prevents an accidental system release. In case
of a normal discharge, the bleed valve closes and allows the pressure to increase in the pilot
line and a release of the slave valves.
15. Remove the safety plug from the port for pilot hose on the master valve and mount an adapter with the G1/8”
thread to the port for pilot hose and tighten it with a torque of 8 - 10 Nm. Refer to figure 5-19.
16. Connect a pilot hose between the adapter at the port for pilot hose on the master valve and the adapter at the
pneumatic release device on the first slave valve. Tighten the pilot hoses with a torque of 8 - 10 Nm. Refer
to figure 5-19.
bleed valve
CAUTION!
Do not remove the safety plug from the port for pilot hose on the slave valve!
17. Connect the manifold to the pipework according to the Tapered Thread Port Assembly, appendix pages 120
- 121.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
83
Installation
1. Disconnect the pilot hose from the port for pilot hose on the master valve. Refer to figure 5-21.
2. Connect the end of the pilot hose, which was disconnected in step 1, to the high pressure flexible hose of the
test unit and tighten it carefully. Refer to figure 5-21.
3. Open the hand wheel valve of the high pressure cylinder of the test unit and pressurise the pilot line to 3 bar
maximum.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
84 Installation
4. When the pilot line is pressurised to 3 bar maximum, close the hand wheel valve of the test unit and the tap
of the pressure reducing unit.
5. Wait for 10 minutes and then check the pressure in the pilot line. If the pressure in the pilot line has not
dropped, the pilot line is free from leakage.
CAUTION!
If the pressure in the pilot line has dropped, there is one or more leakage in the pilot line. In
this case, check all pilot line connections for tightness. Additionally test all pilot line con-
nections with leak spray. Repeat steps 3 - 5 until the pilot line is free from leakage.
6. If the pilot line is free from leakage or if all leakage is eliminated, disconnect the high pressure flexible hose
of the test unit from the pilot line.
7. Connect the pilot hose to the port for pilot hose of the master valve and tighten it with a torque of 8 -10 Nm.
NOTE:
We strictly recommend to test all connections of the cylinder/valve assembly with leak spray.
NOTE:
A certificate, that the pilot line test was performed successfully, must be issued at the end.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
85
Installation
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
86 Operation
6 Operation
The INEREX® System is a fire suppression system based on a constant flow technology, that uses inert gas
IG01, IG100, IG55 or IG541 as extinguishing agent. The INEREX® System operates safe at temperatures from
-17.8°C to 54.4°C (0°F to 130°F) according to ISO 14520-1/EN12094 and NFPA 2001. Inert gas fire suppression
systems are based in the principle of reducing the oxygen concentration inside the protected area.
The required quantity of inert gas is held in high-pressure (200 or 300 bar) cylinders by valves with pressure
regulators. In case of fire, the valves are actuated by release devices.
An electromagnetic release device is mounted on top of the master valve and is operated by an electrical sig-
nal from a fire detection system in the protected enclosure. Additionally a manual/pneumatic release device is
mounted on top of the electromagnetic release device, in order to provide additionally a manual actuation.
As soon as a fire is detected by the fire detection system a signal is sent to the electromagnetic release device of
the master valve. The electromagnetic release device then actuates the master valve. Alternatively the system
can be manually actuated. Slave valves are connected to the master valve by pilot hoses. When the master valve
opens, pressure is built up in the pilot line and is passed on to the pneumatic release devices on the slave valves.
Each pneumatic release device then automatically opens the slave valves.
The inert gas is released almost simultaneously from all cylinder valve assemblies across the pressure regulators
into the discharge hoses and then into the manifold. The gas from all the cylinders is collected in the manifold and
then discharged across the pipework to the nozzles. The nozzles distribute the inert gas into the hazard area.
As soon as the hazard area is flooded with inert gas, the oxygen concentration in the air decreases quickly and
uniformly until it reaches a level where combustion is no longer supported. The fire suffocates as a result.
Automatic actuation:
For an automatic actuation the INEREX® System must be connected to a fire detection system. In case of fire the
fire detection systems sends a signal to the INEREX® System and actuates the system automatically.
Manual actuation:
1. Proceed to the appropriate INEREX® System master valve/cylinder for the hazard in the gas storage room.
2. Remove the safety pin from the manual/pneumatic release device.
3. Press the hand lever of the manual/pneumatic release device down.
DANGER!
When the INEREX® System is actuated, everyone must evacuate the hazard area immediately.
Make sure no one enters the hazard area. Call the fire department immediately.
DANGER!
Do not intentionally remain in the area during a discharge because the release of gas will create
considerable turbulence in the enclosure and may be dangerous to life.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
87
Operation
NOTE:
The operator is responsible for the appropriate safety precautions and any measures to be tak-
en for the protection of life.
NOTE:
We recommend to inform the local fire department that an inert gas extinguishing system has
been installed.
Figure 6-1 Typical view of an INEREX® System for the protection of one hazard area
Figure 6-1 shows a typical INEREX® System installed for the protection of one hazard area. The hazard area is
a server room with a subfloor. According to NFPA 2001 the INEREX® cylinders are stored close to the protected
area. The server room is protected by four nozzles - two nozzles for the server room and two nozzles for the
subfloor.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
88 Operation
Figure 6-2 Typical view of an INEREX® System for the protection of two hazard areas
Figure 6-2 shows a typical INEREX® System installed for the protection of two hazard areas. The hazard areas
are server rooms with subfloors and a difference in elevation. According to NFPA 2001 the INEREX® cylinders
are stored close to the protected area. Each server room is protected by four nozzles - two nozzles for the server
room and two nozzles for the subfloor.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
89
Inspection and maintenance
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
90 Inspection and maintenance
CAUTION!
If any changes are made to the INEREX® System or its components which could have an adverse
influence on the effectiveness of the INEREX® System (characteristics of fire risk, enclosure,
ventilation etc.), the insurer (if applicable) must be informed and the INEREX® System must be
modified as appropriate. Any change or extension of the INEREX® System must be performed by
qualified personnel approved for the INEREX® System.
CAUTION!
After a discharge of the INEREX® System, the INEREX® System must be controlled and commis-
sioned by approved and qualified personnel.
7.3.1.2 Valve
Check the operating position of the valves (visual inspection). Check the burst disc for damage. If the burst disc
is damaged, consult CEODEUX Extinguisher Valves Technology S.A. for replacement.
Test the performance of the valve. A performance test of the valve can be executed with filled cylinders. During
the performance test, the correct opening and closing of the valve are checked.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
91
Inspection and maintenance
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
92 Inspection and maintenance
3. Connect the discharge hose to the pressure regulator. Tighten the swivel nuts of the discharge hose with a
torque of 30 - 40 Nm.
4. Mount a pneumatic release device on all slave cylinders and tighten the pneumatic release devices with a
torque of 50 Nm +0/-15 Nm.
5. Check the electromagnetic release device. If the red marking on the actuating pin is visible, reset the elec-
tromagnetic release device before mounting. Refer to chapter 5.8 step 9.
6. Mount the electromagnetic release device on top of the master valve and tighten it with a torque of 50 Nm
0/-15 Nm.
7. Mount a manual/pneumatic release device on top of the electromagnetic release device and tighten it with a
torque of 50 Nm +0/-15Nm.
8. Connect the adapters to all connections of the pneumatic release devices on the slave valves.
9. Connect the pilot hoses between the adapters at the M12 x 1.5 thread and tighten the pilot hoses with a
torque of 8 - 10 Nm.
10. Mount an adapter with the G1/8” thread to the port for pilot hose on the master valve and tighten it with a
torque of 8 - 10 Nm.
11. Connect a pilot hose between the adapter at the port for pilot hose on the master valve and the adapter at
the pneumatic release device on the first slave valve. Tighten the pilot hoses with a torque of 8 - 10 Nm.
7.3.1.4 Components
Check all INEREX® System components for physical damage, deterioration or corrosion (visual inspection). If
any deterioration or corrosion is evident replace the damaged parts.
7.3.1.6 Nozzles
Check the nozzles for physical damage, deterioration or corrosion (visual inspection). If any physical damage,
deterioration or corrosion is evident replace the nozzle. Nozzles must be replaced by nozzles with the same part
number.
CAUTION!
Do not interchange nozzles, since interchanging can adversely affect the proper extinguishing
agent distribution and concentration within the protected enclosure!
Make sure that the nozzles are not obstructed. If there are any obstructions, remove these obstructions. Remove
dirt and dust from the nozzles.
CAUTION!
Do not use corrosive cleaning solutions, high alkaline cleaners or chlorine for cleaning, be-
cause they could cause corrosion.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
93
Inspection and maintenance
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
94 Inspection and maintenance
DANGER!
If there are changes in the volume of the enclosure and/or changes in the type of hazard, the
INEREX® System must be re-designed with the VdS calculation software to ensure that the re-
quired extinguishing agent concentration can be achieved and maintained.
7.4 Maintenance
Maintenance work shall be conducted in such a manner as to keep the shut-down period to a minimum, both in
time and extent. In multi-area INEREX® System installations, the protected areas can be shut down sequentially
so as to disable only a small part of the INEREX® System installation at any one time.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
95
Inspection and maintenance
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
96 Post discharge maintenance
8.2 Disassembly
DANGER!
Before disassembling the INEREX® System shut-down the power supply of the system.
DANGER!
Make sure, that all pressure has been relieved from the INEREX® System before disassembling.
Pressurised cylinders are extremely hazardous. The valve is capable of producing high dis-
charge thrusts if not handled properly.
CAUTION!
Handle all dismantled parts carefully in order to avoid damage.
The following steps must be repeated until all cylinders are ready for transportation.
1. Disconnect all wiring from the electromagnetic release device.
2. Unscrew the discharge hoses from the pressure regulators.
3. Unscrew the pilot hoses from the release devices (either the manual/pneumatic or the pneumatic release
device) and the port for pilot hose on the master valve.
4. Unscrew the manual/pneumatic release device from the electromagnetic release device of the master valve.
5. Unscrew the electromagnetic release device of the master valve.
6. Unscrew the pneumatic releases device of the slave valves.
7. Unscrew the pressure gauges from the monitoring port of the valves.
8. Dispose of all gaskets, which were installed between the discharge port of the valve and the pressure regu-
lators.
9. Screw an outlet safety plug on the discharge port of each valve.
10. Screw a protection cap on each cylinder.
DANGER!
Always fit the protection cap on the cylinder before moving the cylinder. Failure can result
in serious bodily injury, death, or property damage.
DANGER!
Do not grab the protective cap to move or lift the cylinder.
11. Unfasten the clamps for cylinder: remove the screw, the nut and the washer from the middle of the clamp for
cylinder and keep them in a safe place.
12. Take the cylinder out of the clamps for cylinder.
13. Put the cylinder on a cylinder carrier and fix it securely.
14. Move the cylinder to an transportation vehicle and fasten it securely.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
97
Post discharge maintenance
DANGER!
Cylinders must be transported properly secured. Cylinders must not be rolled, dragged or
slid, nor allowed to be slid from tailgates of vehicles. Cylinders next to the driver’s cabin
must be parallel with vehicle axles or standing up.
DANGER!
Cylinders must not be dropped or permitted to strike against other surfaces or each other.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
98 Malfunctioning
Recycling and disposal
Limited warranty
9 Malfunctioning
Malfunctioning of the INEREX® System can only be caused by improper installation or the use of non-genuine
CEODEUX Extinguisher Valves Technology S.A. components, which is considered as improper use.
NOTE:
Strictly obey this “Design, Installation, Operation and Maintenance Manual for INEREX® Sys-
tems” to avoid malfunctioning of the INEREX® System.
NOTE:
If the INEREX® System is not designed, installed, operated and maintained correctly, CEODEUX
Extinguisher Valves Technology S.A. cannot be held responsible for any possible breakage,
damage and malfunctions.
11 Limited warranty
CEODEUX Extinguisher Valves Technology S.A. warrants to the original purchasers that the products manu-
factured by it shall be free from defects in materials and workmanship under normal use for a period of one (1)
year from the date of manufacture. Provided the product is supplied and installed by an authorised CEODEUX
Extinguisher Valves Technology S.A. distributor, in accordance with the written instructions contained in the
instruction manuals or other data supplied with CEODEUX Extinguisher Valves Technology S.A. products, and
when the CEODEUX Extinguisher Valves Technology S.A. products have not been altered or modified and as
long as the following conditions are met:
1. The original purchaser must maintain a semi-annual maintenance agreement with an authorised Rotarex
distributor, commencing with the date the Rotarex product was accepted by the purchaser and placed into
service. The service agreement must remain in effect for the duration of the warranty.
2. The CEODEUX Extinguisher Valves Technology S.A. warranty registration card must be completed and
returned to:
CEODEUX Extinguisher Valves Technology S.A.
24, route de Diekirch
B.P.19 L-7505 Lintgen
Luxembourg
If within thirty (30) days after the buyer’s discovery of what buyer believes is a defect, buyer notifies in writing
and ships the product to CEODEUX Extinguisher Valves Technology S.A, 24 route de Diekirch, B.P.19 L-7505
Lintgen, Luxembourg. CEODEUX Extinguisher Valves Technology S.A at its option, and within forty-five (45)
days of receipt, will repair, replace or refund the purchase price of that part or product found by CEODEUX Ex-
tinguisher Valves Technology S.A to be defective. Failure of the buyer to give such written notice and ship the
product within thirty (30) days shall be deemed obsolete and unconditional waiver of any and all claims of buyer
arising out of such defect.
This warranty does not extend to any product or parts that is not installed and used continuously after installation
in accordance with CEODEUX Extinguisher Valves Technology S.A instructions, all applicable state and local
regulations, and all applicable national standards. This warranty does not extend to any product or part that has
been damaged by accident, misuse, abuse, failure to maintain, or neglect, nor does it extend to any product or
party which has been modified, altered, dissembled, or repaired in the field.
This warranty does not cover any cosmetic issues, such as scratches, dents, marring, fading of colours or discol-
ouration. In no event shall CEODEUX Extinguisher Valves Technology S.A be liable for consequential or inciden-
tal damages arising from the purchase and or use of CEODEUX Extinguisher Valves Technology S.A products,
including but not limited to: damages resulting from loss of use of CEODEUX Extinguisher Valves Technology
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
99
Limited warranty
S.A products, the costs of replacing discharge suppression agent, damages for lost profits or income, or damag-
es for resulting harm to property other than the CEODEUX Extinguisher Valves Technology S.A products.
Furthermore, CEODEUX Extinguisher Valves Technology S.A is not liable for defects in product compliance due
to normal wear of those parts, which by their nature, are subject to continuous wear.
Except as expressly set forth above, and subject to the limitation of liability below, CEODEUX Extinguisher
Valves Technology S.A MAKES NO OTHER WARRANTY,EXPRESS OR IMPLIED, INCLUDING, BUT NOT
LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, with respect to its products and parts, whether used alone or in combination with others. CEODEUX
Extinguisher Valves Technology S.A disclaims all warranties not stated herein.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
100 Appendix
IG01 Material safety data sheet
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
101
Appendix
IG01 Material safety data sheet
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
102 Appendix
IG01 Material safety data sheet
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
103
Appendix
IG01 Material safety data sheet
“Refer to CFR 49 (or Authority Having Jurisdiction) to determine the information required for shipment of the product.”
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
104 Appendix
IG01 Material safety data sheet
SARA Title III Sect. 311/312 Catego- Immediate (Acute) Health Hazard - Pressure Hazard
rization
SARA Title III Sect. 313 This product does not contain a chemical which is listed in Section 313 at or above the
minimum concentrations.
Special
National Fire Protection Flammability
Association (U.S.A.)
Liquid: 0
Health 3 0 Instability
SA
Special
Notice to reader
To the best of our knowledge, the information contained herein is accurate. However, neither the above-named
supplier, nor any of its subsidiaries, assumes any liability whatsoever for the accuracy or completeness of the
information contained herein.
Final determination of suitability of any material is the sole responsibility of the user. All materials may present
unknown hazards and should be used with caution. Although certain hazards are described herein, we cannot
guarantee that these are the only hazards that exist.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
105
Appendix
IG100 Material safety data sheet
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
106 Appendix
IG100 Material safety data sheet
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
107
Appendix
IG100 Material safety data sheet
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
108 Appendix
IG100 Material safety data sheet
“Refer to CFR 49 (or Authority Having Jurisdiction) to determine the information required for shipment of the product.”
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
109
Appendix
IG100 Material safety data sheet
California Proposition 65 This product does not contain materials which the State of California has found to cause
cancer, birth defects or other reproductive harm.
SARA Title III Sect. 302 (EHS) This product does not contain any chemicals subject to SARA Title III Section 302.
SARA Title III Sect. 304 This product does not contain any chemicals subject to SARA Title III Section 304.
SARA Title III Sect. 311/312 Catego- Immediate (Acute) Health Hazard - Pressure Hazard
rization
SARA Title III Sect. 313 This product does not contain a chemical which is listed in Section 313 at or above the
minimum concentrations.
Special
National Fire Protection Flammability
Association (U.S.A.)
Liquid: 0
Health 3 0 Instability
SA
Special
Notice to reader
To the best of our knowledge, the information contained herein is accurate. However, neither the above-named
supplier, nor any of its subsidiaries, assumes any liability whatsoever for the accuracy or completeness of the
information contained herein.
Final determination of suitability of any material is the sole responsibility of the user. All materials may present
unknown hazards and should be used with caution. Although certain hazards are described herein, we cannot
guarantee that these are the only hazards that exist.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
110 Appendix
IG55 Material safety data sheet
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
111
Appendix
IG55 Material safety data sheet
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
112 Appendix
IG55 Material safety data sheet
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
113
Appendix
IG55 Material safety data sheet
“Refer to CFR 49 (or Authority Having Jurisdiction) to determine the information required for shipment of the product.”
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
114 Appendix
IG55 Material safety data sheet
NJ Right To Know Law This product contains the following chemicals found on the New Jersey Right To Know
Hazardous Substance List: Nitrogen - Argon
California Proposition 65 This product does not contain materials which the State of California has found to cause
cancer, birth defects or other reproductive harm.
SARA Title III Sect. 302 (EHS) This product does not contain any chemicals subject to SARA Title III Section 302.
SARA Title III Sect. 304 This product does not contain any chemicals subject to SARA Title III Section 304.
SARA Title III Sect. 311/312 Catego- Immediate (Acute) Health Hazard - Pressure Hazard
rization
SARA Title III Sect. 313 This product does not contain a chemical which is listed in Section 313 at or above the
minimum concentrations.
Special
National Fire Protection Flammability
Association (U.S.A.)
Liquid: 0
Health 3 0 Instability
SA
Special
Notice to reader
To the best of our knowledge, the information contained herein is accurate. However, neither the above-named
supplier, nor any of its subsidiaries, assumes any liability whatsoever for the accuracy or completeness of the
information contained herein.
Final determination of suitability of any material is the sole responsibility of the user. All materials may present
unknown hazards and should be used with caution. Although certain hazards are described herein, we cannot
guarantee that these are the only hazards that exist.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
115
Appendix
IG541 Material safety data sheet
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
116 Appendix
IG541 Material safety data sheet
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
117
Appendix
IG541 Material safety data sheet
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
118 Appendix
IG541 Material safety data sheet
“Refer to CFR 49 (or Authority Having Jurisdiction) to determine the information required for shipment of the product.”
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
119
Appendix
IG541 Material safety data sheet
SARA Title III Sect. 311/312 Catego- Immediate (Acute) Health Hazard - Pressure Hazard
rization
SARA Title III Sect. 313 This product does not contain a chemical which is listed in Section 313 at or above the
minimum concentrations.
Special
National Fire Protection Flammability
Association (U.S.A.)
Liquid: 0
Health 3 0 Instability
SA
Special
Notice to reader
To the best of our knowledge, the information contained herein is accurate. However, neither the above-named
supplier, nor any of its subsidiaries, assumes any liability whatsoever for the accuracy or completeness of the
information contained herein.
Final determination of suitability of any material is the sole responsibility of the user. All materials may present
unknown hazards and should be used with caution. Although certain hazards are described herein, we cannot
guarantee that these are the only hazards that exist.
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
120 Appendix
Tapered thread port assembly
Types of sealant/lubricant
Sealant/lubricants assist in sealing and provide lubrication during assembly, reducing the potential for galling.
Pipe thread sealants are available in various forms such as dry pre-applied, tape, paste and anaerobic liquid.
Pre-applied sealants, such as powdered PTFE are usually applied to connectors by the manufacturer. Connec-
tors with some of these sealants may be remade a few times without needing additional sealant.
PTFE tape, if not applied properly, can contribute to system contamination during assembly and installation. In
addition, because of PTFE’s high lubricity, fittings can be more easily over tightened; and it does not offer much
resistance to loosening due to vibration.
Paste sealants can also contribute to system contamination, if not applied properly. They are also messy to work
with; and some types require a cure period after component installation, prior to system start up.
Anaerobic liquids are available from several manufacturers and perform sealing as well as thread locking func-
tions. They are applied to the connectors by the user and require a cure period prior to system start up. Some
are soluble in common hydraulic fluids and will not contaminate the system. For proper performance they need
to be applied to clean and dry components, carefully following the manufacturer’s directions.
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX® System - Installation, operation and maintenance manual
121
Appendix
Tapered thread port assembly
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
INEREX® System - Installation, operation and maintenance manual
122 Appendix
Pressure and flow detector switch, part number 028250050
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
Commissioning Test for
123
INEREX® System
Page 1 of 4
GENERAL CUSTOMER INFORMATION
Address:
Name Signature
Telephone:
Name Signature
Protected hazard:
Date of test:
Please send the filled out and signed form back to CEODEUX Extinguisher Valves Technology S.A., Fax: +352 32 78 32-326
Name Signature
Location of INEREX ®
System:
Comments:
Make sure that the protection caps of the cylinders are available. □ □ passed □ failed
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
Commissioning Test for
124
INEREX® System
Page 2 of 4
Please send the filled out and signed form back to CEODEUX Extinguisher Valves Technology S.A., Fax: +352 32 78 32-326
DISCHARGE HOSE Result of test Comments
Check if the discharge hoses correspond with the project specification. □ passed □ failed
Make sure that the discharge hoses are fixed and tightened securely to the
connection port of the pressure regulator and to the check valve. □ passed □ failed
Refer to chapter 5.8.
Make sure that the swivel nuts are tightened with a torque of 30 - 40 Nm.
Refer to chapter 5.8. □ passed □ failed
Check if the discharge hoses have a smooth bending. Minimum bending
radius 160 mm. Refer to chapter 5.8. □ □ passed □ failed
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
Commissioning Test for
125
INEREX® System
Page 3 of 4
Make sure that the pipework has been flushed. Refer to chapter 5.3.4.□ □ passed □ failed
Check if the pipe supports are fastened securely to a solid and stable
structure. Refer to chapter 5.3.2.□ □ □ passed □ failed
Make sure that the distance between the pipe supports does not exceed
the maximum recommended distance. Refer to chapter 5.3.2 □ passed □ failed
Check if the correct pipe schedule and the correct fittings are used. □ passed □ failed
Make sure that the pipework has been leak and pressure tested.
Refer to chapter 5.3.7.
□ passed □ failed
Please send the filled out and signed form back to CEODEUX Extinguisher Valves Technology S.A., Fax: +352 32 78 32-326
R-FIR-DIOMM INEREX®-GB-2015 04_01 Design, Installation, Operation and Maintenance Manual for
PART NUMBER 027650013 INEREX® Systems
Commissioning Test for
126
INEREX® System
Page 4 of 4
COMMENTS
Please send the filled out and signed form back to CEODEUX Extinguisher Valves Technology S.A., Fax: +352 32 78 32-326
Cut the Commissioning Test for INEREX® System off from the manual and fax or mail the filled out document to
CEODEUX Extinguisher Valves Technology S.A.
Fax: +352 32 78 32-326
email: [email protected]
Design, Installation, Operation and Maintenance Manual for R-FIR-DIOMM INEREX®-GB-2015 04_01
INEREX® Systems PART NUMBER 027650013
INEREX
INERT GAS EXTINGUISHING SYSTEMS. CONSTANT FLOW TECHNOLOGY.
®