0% found this document useful (0 votes)
178 views69 pages

ASCE 7 10 Wind - Provisons

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 69

S. K. Ghosh Associates Inc.

Changes from ASCE 7-05 to


ASCE 7-10: Wind Provisions

S. K. Ghosh Associates Inc.


Palatine, IL and Aliso Viejo, CA

www.skghoshassociates.com
-1-

ASCE 7-10

-2-

www.skghoshassociates.com
1
S. K. Ghosh Associates Inc.

2012 International Building Code

-3-

CHAPTER 6
(Wind Loads in ASCE 7-05)

Reserved for Future


Provisions

-4-

www.skghoshassociates.com
2
S. K. Ghosh Associates Inc.

Chapters 26 - 31
Wind Loads

-5-

Reorganization of Wind Provisions

 ASCE 7-05: Chapter 6 contained all wind provisions


 New:
• 6 new Chapters (Chapters 26-31)
• User Notes added
• Intent is to clarify the applicability of the wind
provisions

-6-

www.skghoshassociates.com
3
S. K. Ghosh Associates Inc.

Reorganization of Wind Provisions


(ASCE 7-05: Dark Gray; ASCE 7-10: Orange)

Method 1 – Envelope Procedure MWFRS, C&C


(Simplified Method 2 Low-Rise)
Method 2
All-Heights - Directional Procedure MWFRS, C&C
Low-Rise – Envelope Procedure MWFRS, C&C
Method 3 – Wind Tunnel Procedure

-7-

Reorganization of Wind Provisions


ASCE 7-10: Dark Gray; ASCE 7-05: Red)

Chapter 26 – General Requirements


Chapter 27 – MWFRS Directional Procedure
Method 2 All-Heights, new simplified version - MWFRS

Chapter 28 – MWFRS Envelope Procedure


Method 2 Low-Rise, Method 1 - MWFRS

Chapter 29 – MWFRS Other Structures and


Appurtenances
Chapter 30 – C&C Method 2 Low-Rise, Method 1, Method 2 All-
Heights, new simplified version of Method 2 All-Heights – C&C

Chapter 31 – Wind Tunnel Procedure Method 3


-8-

www.skghoshassociates.com
4
S. K. Ghosh Associates Inc.

Wind Loads

Load factor on W is now 1.0 in Strength Design and


1/1.6 or 0.6 in ASD.
Thus, the design wind speed maps in ASCE 7-10
produce strength-level design wind forces. The
mapped design wind speeds are, therefore, higher
than in ASCE 7-05.

W SD

0.6W ASD

-9-

Ch 2 Load Combinations with Wind


Strength Design
2.3.2 Basic Combinations
3. 1.2D + 1.6(Lr or S or R) + (L or 0.8 0.5W )
4. 1.2D + 1.6 1.0W + L + 0.5(Lr or S or R)
6. 0.9D + 1.6 1.0W + 1.6H
Load factor on W in SD load combinations is now 1.0
because mapped design wind speeds will produce
strength-level loads

- 10 -

www.skghoshassociates.com
5
S. K. Ghosh Associates Inc.

Ch 2 Load Combinations with Wind


Allowable Stress Design
2.4.1 Basic Combinations
5. D + H + F + (0.6W or 0.7E)
6a. D + 0.75L + 0.75(0.6W) + 0.75 (Lr or S or R)
7. 0.6D + 0.6W + H
Load factor on W in ASD load combinations is now 0.6
because mapped design wind speeds will produce
strength-level loads

- 11 -

ASCE 7-10
Reorganization of Wind Provisions
Chapter 26 – General Requirements
• Scoping
• Definitions
• Wind speed map
• Directionality factor
• Exposure
• Gust effect factor
• Topographic effect factor
• Enclosure classification
• Internal pressure coefficient
- 12 -

www.skghoshassociates.com
6
S. K. Ghosh Associates Inc.

Wind Loads

No Importance Factor is used in wind design any


more.

I
- 13 -

Wind Importance Factor

 Importance Factor No Longer Used


• ASCE 7-05: qz = 0.00256KzKztKdV2I
• ASCE 7-10: qz = 0.00256KzKztKdV2

 Basic Wind Speeds: 3 Maps replace need for


Importance Factor

- 14 -

www.skghoshassociates.com
7
S. K. Ghosh Associates Inc.

Wind Loads

The Standard includes three design wind speed maps:


 A 300-year return period wind speed map for
design of Risk Category I structures
 A 700-year return period wind speed map for
design of Risk Category II structures
 A 1700-year return period wind speed map for
design of Risk Category III, IV structures

- 15 -

Occupancy/Risk Categories

Occupancy Category (ASCE 7-05) Description


Risk Category (ASCE 7-10)
I Miscellaneous Occupancy
II Standard Occupancy (not I, III, or IV)
III High Occupancy
IV Essential Facility
Hazardous Facility

- 16 -

www.skghoshassociates.com
8
S. K. Ghosh Associates Inc.

NEW WIND SPEED MAPS


 Fig. 26.5-1A: Risk Category II
 Fig. 26.5-1B: Risk Categories III & IV
 Fig. 26.5-1C: Risk Category I

- 17 -

New Wind Speed Maps


ASCE 7-10
Chapter 26
ASCE 7-05
Chapter 6

Risk Category II

Risk Category III+IV

Risk Category I
- 18 -

www.skghoshassociates.com
9
S. K. Ghosh Associates Inc.

ASCE 7-05 Figure 6-1

- 19 -

ASCE 7-10 Figure 26.5-1A

Risk Category II - 7% probability of exceedance in 50 years, MRI of 700 years


- 20 -

www.skghoshassociates.com
10
S. K. Ghosh Associates Inc.

ASCE 7-10: Figure 26.5-1B

Risk Category III and IV - 3% probability of exceedance in 50 years, MRI of 1700 years
- 21 -

ASCE 7-10: Figure 26.5-1C

Risk Category I - 15% probability of exceedance in 50 years, MRI of 300 years


- 22 -

www.skghoshassociates.com
11
S. K. Ghosh Associates Inc.

Wind Speed Website

 Applied Technology Council


• http://www.atcouncil.org/windspeed/

23
- 23 -

Wind Speed Website

- 24 -

www.skghoshassociates.com
12
S. K. Ghosh Associates Inc.

Comparative Wind Pressures for


San Francisco
0.00256KzKKztKKdVV22II
qqzz == 0.00256K OC I OC II OC III, IV
z zt d
V, mph 85 85 85

I 0.87 1.00 1.15


ASCE 7-05
q
 1 .6 25.75 psf 29.59 psf 34.03 psf
K z K zt K d
qz = 0.00256KzKztKdV2 RC I RC II RC III, IV

V, mph 100 110 115


ASCE 7-10 q
25.60 psf 30.98 psf 33.86 psf
K z K zt K d
05  10
-0.58% +4.70% -0.50%
05

- 25 -

Comparative Wind Pressures for


Chicago
0.00256KzKKztKKdVV22II
qqzz == 0.00256K OC I OC II OC III, IV
z zt d
V, mph 90 90 90

I 0.87 1.00 1.15


ASCE 7-05
q
 1 .6 28.86 psf 33.18 psf 38.15 psf
K z K zt K d
qz = 0.00256KzKztKdV2 RC I RC II RC III, IV

V, mph 105 115 120


ASCE 7-10 q
28.22 psf 33.86 psf 36.86 psf
K z K zt K d
05  10
-2.22% +2.05% -3.38%
05

- 26 -

www.skghoshassociates.com
13
S. K. Ghosh Associates Inc.

Risk Category II Comparison

0.80-0.93

0.74-0.86

- 27 -

Risk Category III and IV Comparison

0.79-0.95

0.71-0.95

- 28 -

www.skghoshassociates.com
14
S. K. Ghosh Associates Inc.

Risk Category I Comparison

0.84-1.03

1.06-0.97

- 29 -

Section 26.2 Definitions

Changes in the mapped wind speeds necessitated


recalibration of some definitions and requirements.

1 map referenced 3 maps referenced


Old wind speed New wind speed
Occupancy Category Risk Category

- 30 -

www.skghoshassociates.com
15
S. K. Ghosh Associates Inc.

Section 26.2 Definitions

HURRICANE PRONE REGIONS: Areas vulnerable to


hurricanes; in the United States and its territories
defined as
1. The U.S. Atlantic Ocean and Gulf of Mexico coasts
where basic wind speed for Risk Category II
buildings is greater than 90 115 mph, and
2. Hawaii, Puerto Rico, Guam, Virgin Islands, and
American Samoa.

- 31 -

Section 26.10.3
Protection of Glazed Openings
Glazed openings in Risk
Category II, III or IV
buildings located in
hurricane-prone regions
shall be protected as
specified in this Section.

- 32 -

www.skghoshassociates.com
16
S. K. Ghosh Associates Inc.

Section 26.10.3
Protection of Glazed Openings
26.10.3.1 Wind-borne Debris Regions. Glazed
openings shall be protected in accordance with
26.10.3.2 in the following locations:
1. Within 1 mile of coastal mean high water line where
basic wind speed is equal to or greater than 110
130 mph, or
2. In areas where basic wind speed is equal to or
greater than 120 140 mph.

- 33 -

Section 26.10.3
Protection of Glazed Openings
26.10.3.1 Wind-borne Debris Regions (contd). For
Risk Category II buildings and structures and Risk
Category III buildings and structures, except health
care facilities, wind-borne debris region shall be
based on Fig. 26.5-1A. For Risk Category III health
care facilities and Risk Category IV buildings and
structures, wind-borne debris region shall be based
on Fig. 26.5-1B. Risk Categories shall be
determined in accordance with Section 1.5.

- 34 -

www.skghoshassociates.com
17
S. K. Ghosh Associates Inc.

Section 26.10.3
Protection of Glazed Openings
For Risk Category II buildings and structures and Risk
Category III buildings and structures, except health care
facilities

Fig. 26.5-1A

- 35 -

Section 26.10.3
Protection of Glazed Openings
For Risk Category III health care facilities and Risk
Category IV buildings and structures

Fig. 26.5-1B

- 36 -

www.skghoshassociates.com
18
S. K. Ghosh Associates Inc.

Section 26.10.3.2 Protection


Requirements for Glazed Openings
ASTM E1886 - 05 Standard Test Method for Performance
of Exterior Windows, Curtain Walls, Doors, and Impact
Protective Systems Impacted by Missile(s) and Exposed
to Cyclic Pressure Differentials
ASTM E1996 - 09 Standard Specification for
Performance of Exterior Windows, Curtain Walls, Doors,
and Impact Protective Systems Impacted by Windborne
Debris in Hurricanes
EXCEPTION: Other testing methods and/or performance
criteria are permitted to be used when approved.

- 37 -

Section 26.7.2
Surface Roughness Categories
Surface Roughness C: Open terrain with scattered
obstructions having heights generally less than 30
ft. This category includes flat open country, and
grasslands, and all water surfaces in hurricane
prone regions.
Surface Roughness D: Flat, unobstructed areas and
water surfaces outside hurricane prone regions.
This category includes smooth mud flats, salt flats,
and unbroken ice.

- 38 -

www.skghoshassociates.com
19
S. K. Ghosh Associates Inc.

Section 26.7.2
Surface Roughness Categories

- 39 -

Section 26.7.2
Surface Roughness Categories
 Water surfaces in hurricane-prone regions are
moved from Surface Roughness C to Surface
Roughness D.
 Older research and modeling suggested roughness
of ocean approached Surface Roughness C with
increase in wind speed.
 New research suggests otherwise - roughness of
ocean does not continue to increase with increasing
wind speed.

- 40 -

www.skghoshassociates.com
20
S. K. Ghosh Associates Inc.

Section 26.9.2
Frequency Determination
 In ASCE 7-05, several expressions for computing
approximate fundamental frequency , n1, of a
building were suggested in C6.5.8.
 Some of those expressions are now included within
the body of ASCE 7-10
 Expressions provide conservative lower-bound
estimates of n1, which is needed to distinguish
between rigid and flexible buildings.
 Low-Rise Buildings, as defined in 26.2, are
permitted to be considered rigid.
- 41 -

Section 26.9.2
Frequency Determination
26.9.2.1. As an alternative to performing an analysis to
determine n1, the approximate building natural
frequency, na, shall be permitted to be calculated in
accordance with 26.9.3 for structural steel,
concrete, or masonry buildings meeting the
following requirements:

- 42 -

www.skghoshassociates.com
21
S. K. Ghosh Associates Inc.

Section 26.9.2
Frequency Determination
26.9.2.1 May use na for n1 if
1. Building height is less than or equal to 300 ft, and
2. Building height is less than 4 times its effective
length, Leff. n
 hi Li
i 1
Leff  n (26.9-1)
 hi
i 1
summations are over height of building where
hi is height above grade of level i
Li is building length at level i parallel to wind direction
- 43 -

Section 26.9.3
Approximate Natural Frequency
 Structural steel moment-resisting-frame buildings:
na = 22.2/h0.8 (26.9-2)

 Concrete moment-resisting-frame buildings:


na = 43.5/h0.9 (26.9-3)

 Structural steel and concrete buildings with other


lateral-force-resisting system:
na = 75/h (26.9-4)

- 44 -

www.skghoshassociates.com
22
S. K. Ghosh Associates Inc.

Section 26.9.3
Approximate Natural Frequency
 Concrete or masonry shear wall buildings
na = 385(Cw)0.5/h (26.9-5)

where
2
100 n  h  Ai
Cw   
AB i 1 hi   h 
2
1  0.83 i  
  Di  

- 45 -

Section 26.9.3
Approximate Natural Frequency
h = mean roof height (ft)
n = number of shear walls in building effective in
resisting lateral forces in direction under consideration
AB = base area of structure (ft2)
Ai = horizontal cross-section area of shear wall “i” (ft2)
Di = length of shear wall “i” (ft)
hi = height of shear wall “i” (ft)

- 46 -

www.skghoshassociates.com
23
S. K. Ghosh Associates Inc.

BREAK!
If you have any questions,
please type them in

If you are encountering technical


difficulties, please call (847) 991-2700

- 47 -

Question and Answer Session

If you have any questions,


please type them in

If you are encountering technical difficulties, please call (847) 991-2700

- 48 -

www.skghoshassociates.com
24
S. K. Ghosh Associates Inc.

ASCE 7-10
Reorganization of Wind Provisions
Chapter 27 – MWFRS Directional Procedure

• Part 1 – “Buildings of all heights” method


ASCE 7-05 Method 2 All-Heights

• Part 2 – New simplified method for buildings of


height less than 160 ft.

- 49 -

ASCE 7-10 Sections 27.4.7, 28.4.4, 28.6.4


Minimum Design Wind Loads
ASCE 7-05

ASCE 7-10
- 50 -

www.skghoshassociates.com
25
S. K. Ghosh Associates Inc.

Chapter 27
Directional Procedure for MWFRS
Directional
Procedure

PART 1 PART 2
Applies to enclosed, partially Applies to enclosed simple
enclosed, and open buildings diaphragm buildings with
of all heights h ≤ 160 ft

Same as Analytical
Method of ASCE 7-05 CLASS 1 BUILDINGS CLASS 2 BUILDINGS
h ≤ 60 ft 60 < h ≤ 160 ft
0.2 ≤ L/B ≤ 5.0 0.5 ≤ L/B ≤ 2.0

New simplified procedure in ASCE 7-10

- 51 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
ENCLOSED BUILDING: A building that does not
comply with the requirements for open or partially
enclosed buildings.

Required for the new simplified procedure of


Chapter 27 Part 2

- 52 -

www.skghoshassociates.com
26
S. K. Ghosh Associates Inc.

Enclosed Building Example

- 53 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
SIMPLE DIAPHRAGM BUILDING: A building in
which both windward and leeward wind loads are
transmitted by roof and vertically spanning wall
assemblies, through continuous floor and roof
diaphragms, to the MWFRS.

Required for the new simplified procedure of


Chapter 27 Part 2

- 54 -

www.skghoshassociates.com
27
S. K. Ghosh Associates Inc.

Simple Diaphragm Building

- 55 -

ASCE 7-10 Chapter 27 Directional Procedure


for MWFRS – Part 2 (Both Class 1 & 2)
General Conditions
(same as Part 1) per Section 27.1.2:
PART 2 (Both Class 1 & 2)
Applies to enclosed simple
1. The building is regular-shaped diaphragm buildings with
h ≤ 160 ft
2. The building does not have response characteristics
making it subject to across wind loading, vortex
shedding, instability due to galloping or flutter; or
does not have a site location for which channeling
effects or buffeting in the wake of upwind
obstructions warrant special consideration.
- 56 -

www.skghoshassociates.com
28
S. K. Ghosh Associates Inc.

ASCE 7-10 Chapter 27 Directional


Procedure for MWFRS – Part 2 Class 1
Additional Condition for Part 2 Class 1 Buildings
per Section 27.5.2:
PART 2 CLASS 1 BUILDINGS
h ≤ 60 ft
0.2 ≤ L/B ≤ 5.0

Unless Kzt = 1.0, wind pressures determined from this


section shall be multiplied by:
 Kzt at each height z as determined from 26.8 or
 one value of Kzt for the building calculated at
0.33h.
Alternatively, enter the pressure tables with V√Kzt
where Kzt is determined at 0.33h.
- 57 -

ASCE 7-10 Chapter 27 Directional


Procedure for MWFRS – Part 2 Class 2
Additional Conditions for Part 2 Class 2 Buildings per
Section 27.5.2: PART 2 CLASS 2 BUILDINGS
60 < h ≤ 160 ft
0.5 ≤ L/B ≤ 2.0

1. The fundamental natural frequency of building shall not be


less 75/h where h is in ft.
2. Unless Kzt = 1.0, wind pressures determined from this
section shall be multiplied by:
 Kzt at each height z as determined from 26.8 or
 one value of Kzt for the building calculated at 0.33h.
Alternatively, enter the pressure tables with V√Kzt where Kzt is
determined at 0.33h.
- 58 -

www.skghoshassociates.com
29
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Design Steps Parameter Source
1. Determine Basic Wind Speed for
V (mph) Fig. 26.5-1 Maps
appropriate risk category
2. Determine exposure category Exp B, C or D Section 26.7
3. Enter table to determine net
pressures on walls at top and base ph , p0 (psf) Table 27.6-1
of building respectively
4. Enter table to determine net roof
Pz (psf) Table 27.6-2
pressures
5. Determine topographic factor and
apply factor to wall and roof Kzt Section 26.8
pressures (if applicable)

- 59 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Table 27.6-1 for Exposure Categories B, C, and D
V (mph) 110 115 ………… 200
L/B 0.5 or 2.0 or 0.5 or 2.0 or 0.5 or 2.0 or 0.5 or 2.0 or
1.0 1.0 1.0 1.0
h (ft) less more less more less more less more
ph
160
p0
ph
150
p0
ph
140
p0

ph
15
p0
- 60 -

www.skghoshassociates.com
30
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution in along-wind
direction
ph

p0
- 61 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Pressure (psf) distribution on windward and
leeward walls
ph − pleeward
pleeward =
0.38ph for 0.2 ≤ L/B ≤ 1.0
0.27ph for 2.0 ≤ L/B ≤ 5.0
Interpolate for
1.0 < L/B < 2.0

p0 − pleeward
- 62 -

www.skghoshassociates.com
31
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) on parapet
pp = 2.25  ph
ph calculated from Table 27.6-
1 at top of parapet for L/B =
1.0
Accounts for pressures on
windward and leeward
surfaces of windward and
leeward walls

- 63 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on sidewalls

0.54ph for 0.2 ≤ L/B ≤ 1.0


0.64ph for 2.0 ≤ L/B ≤ 5.0
Interpolate for
1.0 < L/B < 2.0

- 64 -

www.skghoshassociates.com
32
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on roof

4
3 h

0.5h
Wind
0.5h
Flat Roof
(θ < 10 deg)

- 65 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on roof

1
θ

4 5
Wind 5
3
4
3
θ

0.5h
h 0.5h
Wind

Gable Roof

- 66 -

www.skghoshassociates.com
33
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on roof

2
4 5
3
5 4
1 4 0.5h
5 0.5h
3
h 0.5h
2
Wind 0.5h
1
5 3
h
4 Wind
Hip Roof 3

- 67 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on roof
Wind

1 2

h θ
h θ
Wind

5
4
Monoslope Roof 3

h
0.5h
0.5h

Wind

- 68 -

www.skghoshassociates.com
34
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on roof
5

4
3

0.5h
0.5h h Wind 2

θ
Mansard Roof Wind

- 69 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Net pressure (psf) distribution on roof

Roof pressures from Table 27.6-2 for


Exposure C

For Exposures B and D, use


adjustment factors provided in the
footnotes to Table 27.6-2

Where two load cases are shown in the


table, both load cases shall be
investigated

- 70 -

www.skghoshassociates.com
35
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Table 27.6-2 for Exposure Category C
V (mph) 110 - 200
Load Zone
h (ft) Roof Slope
Case 1 2 3 4 5
1
Flat < 2:12 (9.46 deg)
2
1
3:12 (14.0 deg)
2
1
4:12 (18.4 deg)
2
1
15 - 160 5:12 (22.6 deg)
2
1
6:12 (26.6 deg)
2
1
9:12 (36.9 deg)
2
1
12:12 (45.0 deg)
2

- 71 -

Chapter 27 Directional Procedure for


MWFRS – Part 2
Conversion from Exposure C to Exposures B and D

- 72 -

www.skghoshassociates.com
36
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Application of wind load
Pressures on the windward,
leeward and sidewalls, and on
roof and parapet are applied
ph θ simultaneously
L

Wind B
h
Plan

p0

- 73 -

Chapter 27 Directional Procedure


for MWFRS – Part 2
 The MWFRS’s in each direction shall be designed
for the wind load cases defined in Figure 27.4-8.
 The torsional load cases in Figure 27.4-8 (Case 2
and Case 4) need not be considered for buildings
that meet the requirements for spatial distribution
and stiffness of the MWFRS’s provided in new
Appendix D.

- 74 -

www.skghoshassociates.com
37
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
Load Cases

- 75 -

Chapter 27 Directional Procedure


for MWFRS – Part 2
 The MWFRS in each direction needs to be
designed for Fig. 27.4-8 wind load cases.
NEW APPENIDX D! The Fig. 27.4-8 Case 2 and 4
torsional load cases need not be considered for
buildings that meet the requirements for spatial
distribution and stiffness of the MWFRS’s provided in
Appendix D.
What is Appendix D?
BUILDINGS EXEMPTED FROM TORSIONAL
WIND LOAD CASES

- 76 -

www.skghoshassociates.com
38
S. K. Ghosh Associates Inc.

Chapter 27 Directional Procedure for


MWFRS – Part 2
 Requirements for spatial distribution and stiffness
of MWFRS’s in new Appendix D are necessary to
ensure that wind torsion does not control design.

 In general, the designer should place and


proportion vertical elements of the MWFRS in each
direction so that center of pressure from wind
forces at each story is located at or near center of
rigidity of the MWFRS, thereby minimizing inherent
torsion from wind on building.

- 77 -

ASCE 7-10
Reorganization of Wind Provisions
Chapter 28 – MWFRS Envelope Procedure

• Part 1 – Low-rise buildings method


ASCE 7-05 Method 2 Low-Rise

• Part 2 – Simplified method for simple diaphragm


buildings
ASCE 7-05 Method 1

- 78 -

www.skghoshassociates.com
39
S. K. Ghosh Associates Inc.

ASCE 7-10
Reorganization of Wind Provisions
Chapter 29 – MWFRS Other Structures and
Appurtenances
• Signs
• Rooftop structures
• Other structures

- 79 -

29.4 Solid Freestanding Walls &


Solid Signs
The provisions for design wind loads on signs have
been revised to clarify the applicability of the
requirements for solid attached signs.

- 80 -

www.skghoshassociates.com
40
S. K. Ghosh Associates Inc.

29.4 Solid Freestanding Walls &


Solid Signs
29.4 DESIGN WIND LOADS – SOLID
FREESTANDING WALLS AND SOLID SIGNS
29.4.1 6.5.14 Design Wind Loads on Solid
Freestanding Walls and Solid Freestanding
Signs
The design wind force for solid freestanding walls and
solid freestanding signs shall be determined by the
following formula:
F = qhGCfAs (lb) (N) (29.4-1 6-27)

- 81 -

29.4 Solid Freestanding Walls &


Solid Signs
Where:
qh = the velocity pressure evaluated at height h
(defined in Figure 29.4-1 6-20) as determined in
accordance with Section 29.3.2 6.5.6.4.1
G = gust-effect factor from Section 26.9 6.5.8
Cf = net force coefficient from Figure 29.4-1 6-20
As = the gross area of the solid freestanding wall or
freestanding solid sign, in ft2 (m2)

- 82 -

www.skghoshassociates.com
41
S. K. Ghosh Associates Inc.

29.4 Solid Freestanding Walls &


Solid Signs
29.4.2 Solid Attached Signs
The design wind pressure on a solid sign attached to
the wall of a building, where the plane of the sign is
parallel to and in contact with the plane of the wall,
and the sign does not extend beyond the side or
top edges of the wall, shall be determined using
procedures for wind pressures on walls in
accordance with Chapter 30, and setting the
internal pressure coefficient (GCpi) equal to 0.

- 83 -

29.4 Solid Freestanding Walls &


Solid Signs
This procedure shall also be applicable to solid signs
attached to but not in direct contact with the wall,
provided the gap between the sign and wall is no
more than 3 ft and the edge of the sign is at least 3
ft in from free edges of the wall, i.e., side and top
edges and bottom edges of elevated walls.

- 84 -

www.skghoshassociates.com
42
S. K. Ghosh Associates Inc.

29.4 Solid Freestanding Walls &


Solid Signs

Exterior Wall

 3 ft

This is a
SOLID SIGN

Elevation Cross-Section

Solid Attached Sign with Small Gap Showing Limitations on


Use of Component & Cladding Loads for Signs on Walls
- 85 -

29.5.1, 30.11
Rooftop Structures & Equipment
Design wind force for rooftop structures and equipment
for buildings with h ≤ 60 ft has been revised and
now also includes a vertical component.
New section has been added for determining
component and cladding loads on rooftop structures
and equipment for buildings with h ≤ 60 ft.

- 86 -

www.skghoshassociates.com
43
S. K. Ghosh Associates Inc.

29.5.1, 30.11
Rooftop Structures & Equipment
29.5.1 6.5.15.1 Rooftop Structures and Equipment
for Buildings with h ≤ 60 ft
The lateral force Fh, on rooftop structures and
equipment with Af less than (0.1Bh) located on
buildings with a mean roof height, h ≤ 60 ft shall be
determined from Eq. 29.5-2 6-28. increased by a
factor of 1.9. The factor shall be permitted to be
reduced linearly from 1.9 to 1.0 as the value of Af is
increased from (0.1Bh) to (Bh).

- 87 -

29.5.1, 30.11
Rooftop Structures & Equipment
Fh = qh (GCr) Af (lb) (29.5-2)
where:
GCr = 1.9 for rooftop structures and equipment with Af less than
(0.1Bh). GCr shall be permitted to be reduced linearly from 1.9
to 1.0 as the value of Af is increased from (0.1Bh) to (Bh)
qh = velocity pressure evaluated at mean roof height of building
Af = vertical projected area of rooftop structure or equipment on
plane normal to direction of wind, ft2

- 88 -

www.skghoshassociates.com
44
S. K. Ghosh Associates Inc.

Af

ELEVATION
- 89 -

29.5.1, 30.11
Rooftop Structures & Equipment
The vertical uplift force, Fv, on rooftop structures and
equipment shall be determined from Eq. 29.5-3:
Fv = qh (GCr) Ar (29.5-3)
where:
GCr = 1.5 for rooftop structures and equipment with Ar less than
(0.1BL). GCr shall be permitted to be reduced linearly from 1.5
to 1.0 as the value of Ar is increased from (0.1BL) to (BL).
qh = velocity pressure evaluated at mean roof height of building
Ar = horizontal projected area of roof top structure or
equipment, ft2

- 90 -

www.skghoshassociates.com
45
S. K. Ghosh Associates Inc.

L Ar

WIND

PLA
N
- 91 -

29.5.1, 30.11
Rooftop Structures & Equipment

Fv = qh (GCr)Ar
Horizontal Projected
Area of Equipment, Ar

Vertical Projected Area, Af

Fh = qh(GCr)Af

Rooftop Equipment MWFRS Loads

- 92 -

www.skghoshassociates.com
46
S. K. Ghosh Associates Inc.

29.5.1, 30.11
Rooftop Structures & Equipment
30.11 ROOFTOP STRUCTURES AND EQUIPMENT FOR
BUILDINGS WITH h ≤ 60 ft
The components and cladding pressure on each wall of
the rooftop structure shall be equal to the lateral force
determined in accordance with Section 29.5.1 divided
by the respective wall surface area of the rooftop
structure and shall be considered to act inward and
outward.

- 93 -

29.5.1, 30.11
Rooftop Structures & Equipment
The components and cladding pressure on the roof shall
be equal to the vertical uplift force determined in
accordance with Section 29.5.1 divided by the
horizontal projected area of the roof of the rooftop
structure and shall be considered to act in the upward
direction.

- 94 -

www.skghoshassociates.com
47
S. K. Ghosh Associates Inc.

29.5.1, 30.11
Rooftop Structures & Equipment

p = Fv /Ar

(Design for Positive & (Design for Positive &


Negative Pressures) Negative Pressures)

p = Fh /Af Rooftop Equipment


p = Fh /Af

Rooftop Equipment Component & Cladding Loads

- 95 -

BREAK!
If you have any questions,
please type them in

If you are encountering technical


difficulties, please call (847) 991-2700

- 96 -

www.skghoshassociates.com
48
S. K. Ghosh Associates Inc.

Question and Answer Session

If you have any questions,


please type them in

If you are encountering technical difficulties, please call (847) 991-2700

- 97 -

ASCE 7-10
Reorganization of Wind Provisions
Chapter 30 – C&C
• Part 1 – Analytical method for h ≤ 60 ft
ASCE 7-05 Method 2 Low-Rise C&C

• Part 2 – Simplified method for h ≤ 60 ft


ASCE 7-05 Method 1 C&C

• Part 3 – Analytical method for h > 60 ft


ASCE 7-05 Method 2 All-Heights C&C

• Part 4 – New Simplified method for h ≤ 160 ft


• Part 5 – Analytical method for free roofs
• Part 6 – Building appurtenances
- 98 -

www.skghoshassociates.com
49
S. K. Ghosh Associates Inc.

Chapter 30 Components and Cladding

Part 4 applies to enclosed buildings having a mean


roof height h ≤ 160 ft having flat roofs, gable roofs,
hip roofs, monoslope roofs and mansard roofs. Wind
pressures are determined directly from a table.

- 99 -

Chapter 30 Components and Cladding

General Requirements:
30.2.2 Minimum Design Wind Pressures. The
design wind pressure for C&C of buildings shall not
be less than a net pressure of 16 lb/ft2 acting in
either direction normal to surface.

- 100 -

www.skghoshassociates.com
50
S. K. Ghosh Associates Inc.

Chapter 30 Components and


Cladding– Part 4
Design Step Parameter Source
1. Determine Basic Wind Speed for
V (mph) Fig. 26.5-1 Maps
appropriate risk category
2. Determine exposure category Exp B, C or D Section 26.7
3. Enter table to determine net
pressures on walls and roof for ptable (psf) Table 30.7-2
Exposure C
4. For Exposures B and D, use Notes to Table
ptable (psf)
adjustment factors 30.7-2
5. Determine topographic factor and
apply factor to wall and roof Kzt Section 26.8
pressures (if applicable)

- 101 -

Chapter 30 Components and


Cladding– Part 4
Table 30.7-2 for Exposure Category C
V (mph) 110 - 200

Load Zone
h (ft) Roof Form
Case
1 2 3 4 5
1
Flat Roof
2

Gable Roof 1
Mansard Roof 2
15 - 160
1
Hip Roof
2
1
Monoslope Roof
2

- 102 -

www.skghoshassociates.com
51
S. K. Ghosh Associates Inc.

Chapter 30 Components and


Cladding– Part 4
Conversion from Exposure C to Exposures B and D

- 103 -

Chapter 30 Components and


Cladding– Part 4
Flat roof (θ < 10)
2
2
3 3 3
1
2
3 a 

a  2

2a  2a 

5

4  4

- 104 -

www.skghoshassociates.com
52
S. K. Ghosh Associates Inc.

Chapter 30 Components and


Cladding– Part 4
Monoslope roof

3 2a

3
4a
2 2
2a

2 a
5
4 4
3
a
2a
5

- 105 -

Chapter 30 Components and


Cladding– Part 4
Gable roof
  
3 3

2 3
a 2
1

3 1
2
5

2
3  4
4

a  a 
5

- 106 -

www.skghoshassociates.com
53
S. K. Ghosh Associates Inc.

Chapter 30 Components and


Cladding– Part 4
Hip roof
  
3
2 2
1

3  a 

1
a  3

4  2 4 

5  a  a 

- 107 -

Chapter 30 Components and


Cladding– Part 4
Mansard roof

3
2

3  1

1

3  5

4  2  a 
  a  4

- 108 -

www.skghoshassociates.com
54
S. K. Ghosh Associates Inc.

Chapter 30 Components and


Cladding– Part 4
Pressures shown in Table 30.7-2 are based on an
effective wind area of 10 ft2. Reductions in wind
pressure for larger effective wind areas may be taken
based on reduction multipliers shown in notes to table.

- 109 -

Chapter 30 Components and


Cladding– Part 4
Reduction Factor Based on Effective Wind Area
1.1

A
1 1.0

0.9 0.9
C
Reduction Factor

D
0.8 0.8

0.7 0.7

0.6 0.6

0.5
1 10 20 50 100 200 500 1000
Effective Wind Area (sf)

- 110 -

www.skghoshassociates.com
55
S. K. Ghosh Associates Inc.

Chapter 30 Components and


Cladding– Part 4
Pressure (psf) on parapet:

p1 = Positive wall pressure for


Zone 4 or 5, as applicable,
p1 p2
computed at top of parapet

p2 = Negative roof pressure for


Zone 2 or 3, as applicable

- 111 -

Chapter 30 Components and


Cladding– Part 4
Pressure (psf) on parapet:

p3 = Positive wall pressure for


Zone 4 or 5, as applicable,
p4 p3 computed at top of parapet

p4 = Negative wall pressure for


Zone 4 or 5, as applicable,
computed at top of parapet

- 112 -

www.skghoshassociates.com
56
S. K. Ghosh Associates Inc.

SKGA Wind Simple Computer Program

 Uses the new simplified directional (all-heights)


procedure in ASCE 7-10.
 Calculates MWFRS and C&C design pressures
on walls, roofs, roof overhangs, and parapets.
 Applies the effective area reduction factor for C&C
pressures.
 Provides the design wind pressures for each applicable
zone of the building in clear and concise tables.
 Documents the calculations in clear and attractive reports.
 And more…..
http://skghoshassociates.com/wind-simple
- 113 -

30.10.1 Roof Overhangs

The determination and application of wind loads on


roof overhangs has been revised to provide a more
accurate description of how the loads are to be
applied.

- 114 -

www.skghoshassociates.com
57
S. K. Ghosh Associates Inc.

30.10.1 Roof Overhangs

6.5.11.4.2 Components and Cladding. For all


buildings, roof overhangs shall be designed for
pressures determined from pressure coefficients
given in Figs. 6-11B,C,D.

- 115 -

30.10.1 Roof Overhangs

30.10 ROOF OVERHANGS


The design wind pressure for roof overhangs of enclosed
and partially enclosed buildings of all heights, except
enclosed buildings with h ≤ 160 ft. for which the
provisions of Part 4 are used, shall be determined from
the following equation:

p = qh[(GCp) – (GCpi)] (lb/ft2) (30.10-1)

- 116 -

www.skghoshassociates.com
58
S. K. Ghosh Associates Inc.

30.10.1 Roof Overhangs

where
qh = velocity pressure from Section 30.3.2 evaluated at mean roof
height h using exposure defined in Section 26.7.3
(GCp) = external pressure coefficients for overhangs given in Figures
30.4-2A to 30.4-2C (flat roofs, gable roofs, and hip roofs), including
contributions from top and bottom surfaces of overhang. The external
pressure coefficient for the covering on the underside of the roof
overhang is the same as the external pressure coefficient on the
adjacent wall surface, adjusted for effective wind area, determined
from Figure 30.4-1 or Figure 30.6-1 as applicable
(GCpi) = internal pressure coefficient given in Table 26.11-1

- 117 -

30.10.1 Roof Overhangs

The steps required for the determination of wind loads on


components and cladding of roof overhangs is shown
in Table 30.10-1.

- 118 -

www.skghoshassociates.com
59
S. K. Ghosh Associates Inc.

30.10.1 Roof Overhangs

Top Surface Pressure = Pressure Calculated


using GCp for overhangs in Figures 30.4-2A to
30.4-2C minus bottom surface pressure
calculated below

Bottom Surface Pressure = Pressure Calculated


using GCp for walls from Figures 30.4-1 or 30.6-1
as applicable based on the effective wind area of
the soffit

Roof Overhang C & C


- 119 -

ASCE 7-10
Reorganization of Wind Provisions
Chapter 31 – Wind Tunnel Procedure

- 120 -

www.skghoshassociates.com
60
S. K. Ghosh Associates Inc.

31.4.3 Limitations on Loads

Lower limits on loads determined from wind tunnel


testing are relocated from the Commentary directly
into the standard.

- 121 -

31.4.3 Limitations on Loads

Loads for the MWFRS determined by wind tunnel


testing shall be limited such that the overall
principal loads in the x and y directions are not less
than 80 percent of those that would be obtained
from Part 1 of Chapter 27 or Part 1 of Chapter 28.
The overall principal load shall be based on
overturning moment for flexible buildings and base
shear for other buildings.

- 122 -

www.skghoshassociates.com
61
S. K. Ghosh Associates Inc.

31.4.3 Limitations on Loads

Pressures for C&C determined by wind tunnel testing


shall be limited to not less than 80 percent of those
calculated for Zone 4 for
walls and Zone 1 for roofs
using the procedure of
Chapter 30.

- 123 -

31.4.3 Limitations on Loads

The limiting values of 80 percent may be reduced to


50 percent for the MWFRS and 65 percent for C&C
if either of the following conditions applies:

1. There were no specific influential buildings or


objects within the detailed proximity model.

- 124 -

www.skghoshassociates.com
62
S. K. Ghosh Associates Inc.

31.4.3 Limitations on Loads

2010 Standard (contd.)


2. Loads and pressures from supplemental tests for
all significant wind directions in which specific
influential buildings or objects are replaced by
the roughness representative of the adjacent
roughness condition, but not rougher than
exposure B, are included in the test results.

- 125 -

ASCE 7-10
Reorganization of Wind Provisions
Appendix C – Serviceability Considerations
C. SERVICEABILITY CONSIDERATIONS
This appendix is not a mandatory part of the Standard
but provides guidance for design for serviceability. .
..
C.1.2 Drift of Walls and Frames. Lateral deflection
or drift of structures and deformation of horizontal
diaphragms and bracing systems due to wind
effects shall not impair serviceability of structure.
- 126 -

www.skghoshassociates.com
63
S. K. Ghosh Associates Inc.

ASCE 7-10
Reorganization of Wind Provisions
Commentary to Appendix C – Serviceability
Considerations

- 127 -

Commentary to Appendix C

Use of the nominal (700-year mean recurrence


interval (MRI) or 1,700-year MRI) wind load in
checking serviceability is excessively conservative.
The following load combination can be used to
check short-term effects:

D + 0.5L + 0.7Wa (CC-3)


in which Wa is wind load based on serviceability
wind speeds in Figs. CC-1 through CC-4.

- 128 -

www.skghoshassociates.com
64
S. K. Ghosh Associates Inc.

Figure CC-1 10-Year MRI 3-sec Gust Wind Speed in


mph (m/s) at 33 ft (10m) above Ground in Exposure C

- 129 -

Figure CC-2 25-Year MRI 3-sec Gust Wind Speed in


mph (m/s) at 33 ft (10m) above Ground in Exposure C

- 130 -

www.skghoshassociates.com
65
S. K. Ghosh Associates Inc.

Figure CC-3 50-Year MRI 3-sec Gust Wind Speed in


mph (m/s) at 33 ft (10m) above Ground in Exposure C

- 131 -

Figure CC-4 100-Year MRI 3-sec Gust Wind Speed in


mph (m/s) at 33 ft (10m) above Ground in Exposure C

- 132 -

www.skghoshassociates.com
66
S. K. Ghosh Associates Inc.

ASCE 7-10
New Appendix
Appendix D – Buildings Exempted from Torsional
Wind Load Cases

- 133 -

- 134 -

www.skghoshassociates.com
67
S. K. Ghosh Associates Inc.

- 135 -

Closing Comments

 Impact of Changes
 Need for Changes

- 136 -

www.skghoshassociates.com
68
S. K. Ghosh Associates Inc.

Question and Answer Session

If you have any questions,


please type them in

If you are encountering technical difficulties, please call (847) 991-2700

- 137 -

Thank You!!
For more information…
www.skghoshassociates.com
Chicago Main Office Southern California Office
334 East Colfax Street, Unit E 43 Vantis Drive
Palatine, IL 60067 Aliso Viejo, CA 92656
Phone: (847) 991-2700 Phone: (949) 215-6560
Fax: (847) 991-2702 Fax: (847) 991-2702
Email: [email protected] Email: [email protected]

Follow us on:

- 138 -

www.skghoshassociates.com
69

You might also like