CECCATO CPVS D 10-15-20 Manual
CECCATO CPVS D 10-15-20 Manual
CECCATO CPVS D 10-15-20 Manual
Code
9828093035 00
MANUAL USE AND MAINTENANCE Edition 08/2015
HP 10 - 15 - 20 (IVR)
kW 7,5 - 11 - 15 (IVR)
READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE COMPRESSOR UNIT.
WARNING: THE INVERTER REMAINS CHARGED WITH HIGH VOLTAGE FOR 15 MINUTES AFTER THE MASTER
SWITCH HAS BEEN OPENED.
ALWAYS WAIT FOR 15 MINUTES BEFORE REMOVING THE FRONT COVER (INSTRUMENT PANEL) OR
DISCONNECT CONVERTER SUPPLY WIRES OR MOTOR CABLE.
ALWAYS WAIT FOR FIVE MINUTES BEFORE REMOVING THE FRONT COVER (INSTRUMENT PANEL).
USE A SPECIFIC INSTRUMENT TO CHECK THAT THERE ARE NO DANGEROUS VOLTAGES BEFORE
PERFORMING OPERATIONS ON THE INVERTER OR MOTOR.
CONTENTS
PART A: INFORMATION FOR THE USER
1.0 GENERAL CHARACTERISTICS 16.0 PERIODS OF INACTIVITY
2.0 INTENDED USE 17.0 SCRAPPING THE UNIT
3.0 OPERATION 18.0 LIST OF SPARE PARTS FOR ROUTINE MAINTENANCE
4.0 GENERAL SAFETY STANDARDS 19.0 TROUBLE-SHOOTING AND EMERGENCY REMEDIES
5.0 DESCRIPTION OF DANGER SIGNALS PART B: INFORMATION RESERVED FOR TECHNICALLY
SKILLED PERSONNEL
6.0 DANGER ZONES 20.0 STARTING UP
7.0 SAFETY DEVICES 21.0 GENERAL ORDINARY MAINTENANCE
REQUIRES TRAINED PERSONNEL
8.0 POSITION OF PLATES 22.0 CHANGING THE OIL
9.0 COMPRESSOR ROOM 23.0 REPLACE THE DE-OILER FILTER AND THE OIL FILTER
10.0 TRANSPORT AND HANDLING 24.0 GREASING MOTOR BEARINGS
11.0 UNPACKING 25.0 OLEOPNEUMATIC DIAGRAM
12.0 INSTALLATION 26.0 "IVR" VARIABLE SPEED
13.0 DIMENSIONS AND TECHNICAL DATA
14.0 MACHINE ILLUSTRATION IMPORTANT: THERE IS A COPY OF THE WIRING DIAGRAM
INSIDE THE ELECTRIC PANEL
15.0 ORDINARY MAINTENANCE TO BE DONE BY THE USER
In the event of breakdown or malfunction of the machine, switch it off and do not tamper with it.
If repairs are needed, apply only to a technical assistance centre approved by the manufacturer and insist on the use of original spare parts.
Failure to comply with the above may endanger the safety of the machine.
INTRODUCTION
Keep this manual with care for future consultation; the use and maintenance manual is an integral part of the machine.
Read this manual carefully before carrying out any operations on the compressor unit.
The installation of the compressor unit and all operations involving it must be performed in conformity with the regulations in
force concerning electric plants and personal safety.
Lock Out – Tag Out (LOTO): Open the power isolating switch and lock it with a personal lock. Tag the power isolating switch
with the name of the service technician.
BEFORE REMOVING THE PROTECTIVE GUARDS TO CARRY OUT ANY MAINTENANCE ON THE
MACHINE, SWITCH OFF THE ELECTRIC POWER SUPPLY AND DISCHARGE THE RESIDUAL PRESSURE
INSIDE THE UNIT.
ALL WORK ON THE ELECTRIC PLANT, HOWEVER SLIGHT, MUST BE CARRIED OUT BY PROFESSIONALLY
SKILLED PERSONNEL.
THIS MACHINE CORRESPOND TO THE ESSENTIAL SAFETY REQUIREMENTS FORESEEN FROM THE
EUROPEAN STANDARD (2006/42 CE).
THE LUBRICATING LIQUIDS AND OTHER EVENTUAL FLUIDS MUST NOT BE DISCHARGED IN THE
ENVIRONMENT. THESE POLLUTING AND HAZARDOUS PRODUCTS MUST COMPULSORY BE DISPOSED BY
CHARGING AUTHORISED AND SPECIALISED FIRMS ACCORDING TO THE DIFFERENT TYPOLOGY OF
PRODUCT.
The manufacturer does not accept responsibility for damage caused as a result of negligence or failure to abide by the
instructions given above.
- To limit internal corrosion, which could compromise the safety of the compressed air tank, the condensation
that is produced must be discharged at least once a day. If an automatic drain fitted to the air receiver is
present, it is necessary to check that it is working correctly every week and repair it if necessary.
- The thickness of the receiver must be checked every year and also in accordance with legislation
in force in the country where the receiver is installed.
- The tank cannot be used and must be replaced if the thickness falls below the minimum level given
in the instruction documents for the tank.
- The tank can be used within the temperature limits given in the conformity declaration.
- The safety valves of the air receiver and oil receiver must be checked every year and replaced in
accordance with legislation in force.
NOT RESPECTING THE ABOVE MENTIONED PRESCRIPTION CAN RESULT IN AIR RECEIVER
BURSTING HAZARD.
The manufacturer does not accept responsibility for damage caused as a result of negligence or failure to abide by the
instructions given above.
The compressor units use single-stage screw rotary air compressors with oil injection.
The central unit comprises:
compressor; oil separator; oil cooler and output air cooler; fan; electric start; safety and regulation devices; instrument panel.
The system is self-bearing and does not require bolts or other devices to anchor it to the floor.
The unit is completely assembled in the factory; the necessary connections for setting it up are:
connection to the power mains (see installation chapter)
connection to the compressed air network (see installation chapter)
The compressor-motor unit is fitted on the machine chassis by means of flexible supports: this allows the compressor unit to be laid directly
on the floor without any need of further vibration-damping systems.
The compressor has been built to supply compressed air for industrial use.
The machine cannot be used in premises where there is a risk of fire or explosion or where work is carried out which releases substances
into the environment which are dangerous with regard to safety (for example: solvents, inflammable vapours, alcohol, etc.).
In particular the appliance cannot be used to produce air to be breathed by humans or used on direct contact with foodstuffs. These uses
are allowed if the compressed air produced is filtered by means of a suitable filtering system
(Consult the manufacturer for these special uses.)
This appliance must be used only for the purpose for which it was specifically designed.
All other uses are to be considered incorrect and therefore unreasonable.
The Manufacturer cannot be held responsible for any damage resulting from improper, incorrect or unreasonable use.
3.0 OPERATION
3.1 OPERATION FOR COMPRESSOR
The electric motor and the compressor unit are coupled by means of a flexible coupling transmission.
The compressor unit takes in the outside air through the suction valve. The air taken in is filtered by panel pre-filter fitted one the panel of
the external covering and by the filter cartridge fitted upstream from the suction valve. Inside the compressor unit, the air and the lubricating
oil are compressed and sent to the oil separating filter where the oil is separated from the compressed air; the air is then filtered again by the
oil separating cartridge to reduce the amount of suspended oil particles to a minimum. At this point the two flows (of oil and air) are sent to
two separate coolers where they are cooled, using a flow of air taken from the environment by a special fan inside the machine.
The cooled oil returns to the circuit while the compressed air is sent to the using network.
Dryer operation is described below. The gaseous refrigerant coming from the evaporator (4) is sucked by the refrigeration compressor (1)
and it is pumped into the condenser (2). This one allows its condensation, eventually with the help of the fan (3); the condensed refrigerant
passes through the dewatering filter (8) and it expands through the capillary tube (7) and goes back to the evaporator where it produces the
refrigerating effect.
Due to the heat exchange with the compressed air which passes through the evaporator against the stream, the refrigerant evaporates and
goes back to the compressor for a new cycle. The circuit is equipped with a bypass system for the refrigerant; this intervenes to adjust the
available refrigerating capacity to the actual cooling load. This is achieved by injecting hot gas under the control of the valve (9): this valve
keeps constant the pressure of the refrigerant in the evaporator and therefore also the dew point never decreases below 0 °C (32 °F) in
order to prevent the condensate from freezing inside the evaporator.
The drier runs completely automatically; it is calibrated in the factory for a dew point of
3 °C (37,4 °F) and therefore no further calibrations are required.
ALL WORK ON THE ELECTRIC PLANT, HOWERE SLIGHT, MUST BE CARRIED OUT BY
PROFRSSIONALLY SKILLED PERSONEL.
2
1
7
3
FIG. 2
1 2 3 7 8
FIG. 3
5
3
2 8
3
2
2 2
8
5
2
1
1 2 3 5 8
FIG. 4
1 3
3
3
FIG. 5
3
1
2
3 2
1
FIG. 6
2 1
9.1 FLOOR
The floor must be even and of industrial type; the total weight of the machine is about Kg. (See Ch. 13.0).
Remember the total weight of the machine when positioning it.
9.2 VENTILATION
When the machine is operating, the room temperature must not be higher than 46 °C (114,8 °F)or lower than 1 °C (33,8 °F).
The volume of the room must be about 30 m3 The room must be provided with 2 openings for ventilation with a surface area of about 0,3
m2 each. The first opening must be in a high position to evacuate the hot air, the second opening must be low to allow the intake of external
air for ventilation. If the environment is dusty it is advisable to fit a filtering panel on this opening.
The hot air ejected by the compressor may be led outside with a pipe. This pipe must have a minimum section of 0,5 m2 and it must not be
longer than 2 m. For longer pipes an extra fan must be fitted.
9.3 EXAMPLES OF VENTILATION OF THE COMPRESSOR ROOM
FIG. 7
HOT AIR EJECTION FAN AIR OUTPUT HOT AIR PIPE
ATTENTION: REMOVABLE
PIPE TO ALLOW CLEANING
OF THE RADIATOR
CARDBOARD PROTECTION
AVOID DAMAGING THE
BODYWORK
11.0 UNPACKING
CUTTING THE METAL STRAPPING IS A DANGEROUS OPERATION, SEE FIG.9 DO NOT ABANDON THE CUT PIECES IN
THE ENVIRONMENT.
After removing the packing, ensure that the machine is unbroken and that there are no visibly damaged parts. If you are in doubt, do not use
the machine but apply to the manufacturer technical assistance service or to your dealer. The packing material (plastic bags, polystyrene
foam, nails, screws, wood, metal strapping, etc.) must not be left within the reach of children or abandoned in the environment, as they are a
potential source of danger and pollution. Dispose of these materials in the approved collection centres.
FIG. 9
12.0 INSTALLATION
12.1 POSITIONING
After unpacking the equipment and preparing the compressor room, put the machine into position, checking the following items:
ensure that there is sufficient space around the machine to allow maintenance (see Fig. 10).
FIG. 10
2
MINIMUM mt 2
1 (inch 78,7)
1
ENSURE THAT THE OPERATOR CAN SEE THE WHOLE MACHINE FROM THE CONTROL PANEL AND CHECK THE
PRESENCE OF ANY UNAUTHORIZED PERSONS IN THE VICINITY OF THE MACHINE.
ONLY PROFESSIONALLY SKILLED PERSONNEL MAY HAVE ACCESS TO THE ELECTRIC PANEL. SWITCH OFF THE
POWER BEFORE OPENING THE DOOR OF THE ELECTRIC PANEL.
COMPLIANCE WITH THE REGULATIONS IN FORCE CONCERNING ELECTRIC PLANTS IS FUNDAMENTAL FOR
OPERATOR SAFETY AND FOR THE PROTECTION OF THE MACHINE
CABLES, PLUGS AND ALL OTHER TYPE OF ELECTRIC MATERIAL USED FOR THE CONNECTION MUST BE SUITABLE
FOR THE USE AND COMPLYING WITH THE REQUIREMENTS STATED BY THE REGULATIONS IN FORCE.
PIPES, FITTINGS AND CONNECTIONS USED FOR THE CONNECTION OF THE ELECTROCOMPRESSOR TO THE
COMPRESSED AIR NETWORK MUST BE SUITABLE TO THE USE ACCORDING TO THE PRESCRIPTIONS OF THE
REGULATIONS IN FORCE IN THE COUNTRY OF USE.
ALWAYS USE A
FLEXIBLE PIPE
1
1
4
3
ALL DAMAGE DUE TO THE FAILURE TO COMPLY WITH THESE INDICATIONS CANNOT BE ATTRIBUTED TO THE
MANUFACTURER AND MAY CAUSE INVALIDITY OF THE GUARANTEE CONDITIONS.
12.4 STARTING UP
See part B of this manual, Chapter 20.0
Air receiver Air receiver Air receiver Air receiver Air receiver Air receiver
270 LT. (Gal 71,3) 500 LT. (Gal 132) 270 LT. (Gal 71,3) 500 LT. (Gal 132) 270 LT. (Gal 71,3) 500 LT. (Gal 132)
Nominal Nominal
Type dryer Freon Power w
Nominal bar
Power w (HP) Power w (HP)
R 134a Kg. (lb) (HP) MAX.
(psi)
See data plate 60 Hz 60 Hz 60 Hz bar 13
A4 dryer 326 (0,44) 46 (0,06) 372 (0,51) (188)
Nominal Nominal
Type dryer Freon Nominal bar
Power w (HP) Power w Power w (HP)
R 134a Kg. (lb) (HP) MAX.
(psi)
See data plate 60 Hz 60 Hz 60 Hz bar 13
A 4+ dryer 350 (0,48) 46 (0,06) 380 (0,52) (188)
Nominal Nominal
Type dryer Freon Nominal bar
Power w Power w
R 404a Kg. (lb) Power w MAX.
(psi)
See data plate 60 Hz 60 Hz 60 Hz bar 13
A6 dryer 608 (0,83) 60 (0,08) 668 (0,91) (188)
Nominal Nominal
Type dryer Freon Nominal bar
Power w Power w Power w
R 134a Kg. (lb) MAX.
(psi)
See data plate 60 Hz 60 Hz 60 Hz bar 13
A6 dryer 560 (0,76) 60 (0,08) 620 (0,84) (188)
5
9
10 9
6
4
2 8 3
1
1 Refrigerant compressor
2 Condenser
3 Motor fan
4 Evaporator
5 Compressed air tank
6 Hot gas bypass valve
7 Refrigerant filter
8 Expansion capillary tube
9 Safety valve ()
10 Condensate manual drainage
FIG. 12
4 3 8
15
14
17
10
13
1
18
20 11 9
19
12
7
6
16
BEFORE CARRYING OUT THE OPERATION TEST, READ CAREFULLY AND ACQUIRE A GOOD KNOWLEDGE OF THE
COMMAND FUNCTIONS.
FIG. 13
2 1
1) Control card
2) Emergency stop button with mechanical retention and rotation release
14.3 ELECTRONIC CARD MODELS “ ES 4000 “ (Controller version inverter – standard controller)
3 11 13 9 8
FIG. 14
15 12
10
2
6
4
1
5
CAUTION: WAIT AT LEAST 30 SECONDS BEFORE STARTING THE MACHINE AFTER SWITCH OFF.
Introduction:
The ES4000 controller performs the following functions:
- Compressor control
- Compressor protection
- Maintenance monitoring
- Automatic restart after supply interruption (optional).
Tab. A
Ref. Name Description
Emergency stop push button Push the button to stop the compressor immediately in case of an emergency. After
S3 remedying the trouble, unlock the button by rotate it according to the arrow indication
and press the reset key (4).
Stop button Push the button to stop the compressor. The led (10) switches off. The compressor will
stop after running in unloaded conditions (30 seconds).
1
Start button Push the button in order to start the compressor. The led (10) lights up, indicating that
the controller is operating automatically the compressor.
2
3 Display It shows the operating conditions of the compressor, the actual measured values and
the programmed parameters.
Reset button Button to reset the service timer, a shut-down condition, or in order to return to a
previous visualization on the display.
4
Enter key Key to select or to confirm a parameter, or to open a sub display.
5
6 Voltage on led It indicates that the voltage is switched on
Voltage on symbol
7
8 General alarm led It is lit in case of warning condition.
It blinks in case of shut-down or emergency stop condition.
General alarm symbol
9
10 Automatic operation led It indicates that the controller is operating the compressor automatically. The
compressor is loaded, unloaded, stopped and restarted depending on the air demand
and on the limitations programmed in the controller.
The led is lit in during the automatic operations.
It blinks when the unit is remotely controlled.
Automatic operation symbol
11
12 Service warning led It is lit in case of service is needed
Service warning symbol
13
Downward scroll key Key to scroll downward through the screens or to decrease a parameter value.
14
Upward scroll key Key to scroll upwards through the screens or to increase a parameter value.
15
Left scroll key Key to scroll left through the screens.
16
Right scroll key Key to scroll right through the screens.
17
Motor stopped.
3)
Main screen
When the voltage is switched on, the main screen is shown automatically, indicating the operation status of the compressor and the outlet
temperature.
example:
The display is showing that the compressor is running loaded (when the horizontal arrow is blinking) and the outlet pressure is 6.8bar.
Consult the service dept. if <test> appears on the display.
Blinking
The screen shows that the temperature at the compressor element outlet is 107°C (224,6 °F).
Using the keys (14) and (15), it is possible to scroll through other screens to check the actual status of other parameters.
Stop the compressor using the button (1) and wait until the compressor stops.
Open the disconnect switch in the supply line of the compressor.
Dew-point temperature
For compressors with integrated dryer:
If the dew point temperature exceeds the warning level (not programmable), the alarm led (8) will lit up and the related pictograph will appear
blinking.
Main screen with warning dew point temperature
Blinking
Press the arrow key (14) until the actual dew point appears:
The screen shows that the actual dew-point temperature is 22°C (71,6 °F).
Using the keys (14) and (15), it is possible to scroll through other screens to check the actual status of other parameters.
Stop the compressor using the button (1) and wait until the compressor has stopped.
Open the disconnect switch in the supply line of the compressor.
Press the arrow key (14) until the actual compressor element temperature appears:
The screen shows that the temperature at the outlet of the compressor element is 122°C (251,6 °F).
Open the disconnect switch in the supply line of the compressor.
Converter Allarm
In case of converter fault, the compressor will be shut-down, the alarm led (8) will blink, the automatic operation led (10) will switch off and the
following type of screen will appear:
Warning: The symbol of "Motor Overload" appears both in case of an alarm in the event of converter fault or temperature switches
TSHH11-12 have been tripped.
Open the disconnect switch in the supply line of the compressor.
Emergency stop
Compressor can be manually shut down by pressing the emengency stop pushbutton.
NOTE:
5 seconds after the stop command, the controller displays “Motor thermal overload” icon (converter has been shut down).
This icon disappears once the pushbutton is reset.
The screen shows that the reading of the service timer is 4002h.
Using the keys (14) or (15), scroll to the screen <d.01> and the running hours symbol will be shown.
Press the key (5) and the actual running hours will appear in <hrs> (or in <x1000hrs> if the value is higher than 9999).
Press the scroll key (14) until the screen <d.06> appears, then press enter key (5):
This screen shows the unit used is <hrs> (or <x1000 hrs>) and the value 1191: the compressor has run 1191 h since the previous service.
Resetting the service timer
After servicing, see section Service warning, the timer has to be reset:
Scroll to register screen <d.06> and press enter key (5).
The reading (e.g. 4000) will appear.
Press the enter key (5). If a password is set, enter the password.
The icon will flash (indicating that resetting is possible).
Press the enter key (5) to reset the timer to <0.000> or press reset key (4) to cancel the operation.
S c r o l l i n g th r o u g h a l l s c r e e n s
Scroll buttons (14) can be used to scroll through all screens. The screens are divided into register screens, measured data screens, digital input
screens (numbered as <d.in>, <d.1>, ...), parameter screens (numbered as <P.1>, <P.2>, ...), protections screens (numbered as
<Pr.2>,...) and test screens (numbered as <t.1>,...).
During scrolling, the numbers of the screens appear consecutively. For most screens, the unit of measurement and the related pictograph are
shown together with the screen number.
Example
The screen shows the screen number <d.1>, the unit used <hrs> and the related symbol for running hours. Press Enter key (5) to call up the actual
running hours.
<P.2> Setting a node ID for LAN control and the channels for Mk 4
and Mk 5
<P.3> Settings for IP, gateway and Subnet mask
Menu flow
Introduction
The electronic controller has following functions:
Controlling the compressor
Protecting the compressor
Monitoring components subject to service
Automatic restart after voltage failure (option)
Shut-down warning
A shut-down warning level is a programmable level below the shut-down level. If one of the measurements exceeds the programmed shut-
down warning level, this will also be indicated to warn the operator before the shut-down level is reached.The shut-down warning appears in
case of:
Too high temperature at the compressor element outlet
Too high or too low dew-point temperature for dryer equipped units
In chapter “Shut-down warinig visualization” it’s explained how it appears on the display, how to recognize which is the warning and how to
solve it.
Service warning
If the service timer exceeds a programmed value, this will be indicated on the display to warn the operator to carry out some service actions.
Provided the controller is in the automatic operation mode, the compressor will automatically restart when
the supply voltage to the module is restored.
Control panel
2 8 4 FIG. 14a
5
1
9
3
10 7
11 14
13
12 6
Running unloaded
Running loaded
Or
Network control
Shutdown
Warning
Not valid
System icons
Icon Description Icon Description
Compressor element (LP, HP, ...) Motor
Menu icons
Icon Description Icon Description
Inputs Event history (saved data)
Counters Setpoint
Test Information
Service General
Navigation arrows
Up Down
Main screen
Function
The Main screen is the screen that is shown automatically when the voltage is switched on and one of the keys is pushed. It is switched off
automatically after a few minutes when no keys are pushed.
Typically, 5 different main screen views can be chosen:
Two value lines
Four value lines
Chart (High resolution)
Chart (Medium resolution)
Chart (Low resolution)
Typical Main screen (2 value lines) Typical Main screen (4 value lines)
Text on figures
(1) Compressor Outlet
(2) Element outlet
(3) Load, ... (text varies upon the compressors actual condition)
(4) Menu
(5) Running hours
(6) Flow
Section A shows information regarding the compressor operation (e.g. the outlet pressure or the temperature at the compressor outlet). On
compressors with a frequency converter, the load degree (flow) is given in % of the maximum flow.
Section B shows Status icons. Following icon types are shown in this field:
Fixed icons
These icons are always shown in the main screen and cannot be selected by the cursor (e.g. Compressor stopped or running, Compressor
status (running, running unloaded or motor stopped).
Optional icons
These icons are only shown if their corresponding function is activated (e.g. week timer, automatic restart after voltage failure , etc.)
Pop up icons
These icons pop up if an abnormal condition occurs (warnings, shutdowns, service,...)
To call up more information about the icons shown, select the icon concerned using the scroll keys and press the enter key.
Section C is called the Status bar. This bar shows the text that corresponds to the selected icon.
To activate an action button, highlight the button by using the Scroll keys and press the Enter key. To go back to the previous menu, press
the Escape key.
Chart views
Instead of viewing values, it is also possible to view a graph of one of the input signals (see section Inputs menu) in function of the time.
When Chart (High Resolution) is selected, the chart shows the variation of the selected input (in this case the pressure) per minute. Also the
instantaneous value is displayed. The screen shows the last 4 minutes.
The switch button (icon) for selecting other screens is changed into a small Chart and is highlighted (active).
When the Chart (Medium Resolution) is selected, the chart shows the variation of the selected input per hour. The screen shows the last 4
hours.
When the Chart (Low Resolution) is selected, the chart shows the variation of the selected input per day. The screen shows the evolution
over the last 10 days.
Select the layout required and press the Enter key. See also section Inputs menu.
Calling up menus
Description
When the voltage is switched on, the main screen is shown automatically (see section Main screen):
To go to the Menu screen, highlight the Menu button (4), using the Scroll keys. Press the Enter key to select the menu. Following screen
appears:
The screen shows a number of icons. Each icon indicates a menu item. By default, the Pressure Settings (Regulation) icon is selected. The
status bar shows the name of the menu that corresponds with the selected icon.
Use the Scroll keys to select an icon. Press the Escape key to return to the Main screen.
To check which is the warning, highlight the yellow triangle, using the Scroll keys. Press the Enter key and it will appears the Protections
menu as in picture above in the right side. Press Enter key and then in the display will appear the list of the Protection that are active on the
controller. Use Scroll key to check all the protections and the one who is causing the warning will be highlighted as in picture below:
Stop the compressor pressing the button (11) in the Fig. 14a and wait until the compressor stops.
Isolate the compressor from the power supply, and de pressurize / isolate compressed air system..
WARNING: Before carrying out any maintenance the machine must be stopped, cut off the machine from the electrical
mains and from the compressed air distribution circuit, check that the machine is not under pressure.
Inspect the compressor and remedy.
To check which is the shutdown, highlight the red icon, using the Scroll keys. Press the Enter key and it will appears the Protections menu
as in picture above in the right side. Press Enter key and then in the display will appear the list of the Protection that are active on the
controller. Use Scroll key to check all the protections and the one THAT is causing the shutdown will be highlighted as in picture below:
Take care that the shut-down “Overload motor” appears in case of main motor fan motor OVERLOAD or overtemperature detected by
temperature switch.
Isolate the compressor from the power supply.
WARNING: Before carrying out any maintenance isolate the compressor from the power supply, and de pressurize / isolate
compressed air system., cut off the machine from the electrical mains and from the compressed air distribution circuit, check that the machine
is not under pressure.
Inspect the compressor and remedy.
After remedying and when the shut-down condition has disappear, switch on the voltage and restart the compressor.
WARNING: CONVERTER FAULT
If FREQUENCY CONVERTER ALARM RESET does not work:
- Disconnect the unit from power supply for 15 minutes.
- After power supply is restored, RESET frequency converter alarm on Elektronikon controller.
If the problem is not solved, please contact the manufacturer’s technical support.
Inputs menu
Function: to display the actual value of the measured data (analog inputs) and the status of the digital inputs (e.g. emergency stop contact,
motor overload relay, etc.) and to select the digital input to be shown on the chart in the main screen.
Procedure
Starting from the main screen (see Main screen),m ove the cursor to the action button Menu and press the Enter key.
Using the Scroll keys, move the cursor to the Inputs icon, as shown in the following screen:
Press the Enter key. A screen similar to the one below appears:
(1) Inputs
(2) Compressor outlet
(3) Element outlet
(4) Ambient air
(5) Emergency stop
The screen shows a list of all inputs with their corresponding icons and readings.
If an input is in warning or shutdown, the original icon is replaced by the warning or shutdown icon respectively (i.c. the Stop icon and the
Warning icon in the screen shown above).
A small chart icon, shown below an item in the list means this input signal is shown on the chart at the main screen. Any analog input can be
selected.
Press the Enter key. A screen similar to the one below appears:
(1) Outputs
(2) Fan motor contact
(3) Blow-off contact
(4) General shutdown
(5) Automatic operation
Counters
Function: to call up the running hours, the loaded hours, the number of motor starts, the number of hours that the regulator has been
powered and the number of load cycles.
Procedure: starting from the Main screen (see Main screen), move the cursor to the action button Menu and press the Enter key. Using the
Scroll keys, move the cursor to the Counters icon (see below)
Press the Enter key. A screen similar to the one below appears:
(1) Counters
(2) Running hours
(3) Motor starts
(4) Load relay
VSD 1-20 % rpm in % (the percentage of the time during which the motor speed
(5) was between 1 and 20 %)
The screen shows a list of all counters with their actual readings.
Note: the example above is for a frequency converter driven compressor. For a fixed speed compressor, the actual screen will be somewhat
different.
Next, use the scroll buttons to go to the Status icons (see Main screen) and select the Regulation icon (2). When the icon is active, this icon
is highlighted with a grey background colour.
Press the enter button:
After selecting the required regulation mode, press the enter button on the controller to confirm your selection. The new setting is now visible
on the main screen. See section Used icons for the meaning of the icons.
To activate the remote start/stop please contact the customer centre.
Service menu
Function: to reset the service plans which are carried out, to check when the next service plans are to be carried out, to find out which
service plans were carried out in the past and to modify the programmed service intervals.
Procedure: starting from the Main screen (see Main screen), move the cursor to the action button Menu and press the Enter key.
Using the Scroll keys, move the cursor to the Service icon (see below).
(1) Service
(2) Overview
(3) Service plan
(4) Next service
(5) History
Scroll through the items to select the desired item and press the Enter key to see the details as explained below.
(1) Overview
(2) Running Hours
(3) Real Time hours
(4) Reset
Example for service level (A): the figures at the left are the programmed service intervals. For Service interval A, the programmed number of
running hours is 4000 hours (upper row, green) and the programmed number of real time hours is 8760 hours, which corresponds to one
year (second row, blue). This means that the controller will launch a service warning when either 4000 running hours or 8760 real hours are
reached, whichever comes first. Note that the real time hours counter keeps counting, also when the controller is not powered.
The figures at the end of the bars are the number of hours to go till the next service intervention. In the example above, the compressor was
just started up, which means it still has 4000 running hours or 8299 hours to go before the next Service intervention.
Service plans
A number of service operations are grouped (called Level A, Level B, etc...). Each level stands for a number of service actions to be carried
out at the time intervals programmed in the controller.
When a service plan interval is reached, a message will appear on the screen.
After carrying out the service actions related to the indicated levels, the timers must be reset. From the Service menu above, select Service
plan (3) and press Enter. Following screen appears:
In the example above, the A Service level is programmed at 4000 running hours, of which 0 hours have passed. History
The History screen shows a list of all service actions done in the past, sorted by date. The date at the top is the most recent service action.
To see the details of a completed service action (e.g. Service level, Running hours or Real time hours), use the Scroll keys to select the
desired action and press the Enter key.
Regulation menu
Function: on fixed speed compressors , the operator can program two different pressure bands. This menu is also used to select the active
pressure band.
Procedure: starting from the Main screen (see Main screen), move the cursor to the action button Menu and press the Enter key.
Using the Scroll keys, move the cursor to the Setpoint icon (see below).
(1) Regulation
(2) Unloading pressure 1
(3) Loading pressure 1
(4) Unloading pressure 2
(5) Loading pressure 2
(6) Modify
The screen shows the actual unloading and loading pressure settings for both pressure bands. To modify the settings, move the cursor to
the action button Modify and press the Enter key. Following screen appears:
The first line of the screen is highlighted. Use the Scroll keys to highlight the setting to be modified and press the Enter key. Following
screen appears:
The upper and lower limit of the setting is shown in grey, the actual setting is shown in black. Use the ↑ or ↓ key of the Scroll keys to modify
the settings as required and press the Enter key to accept.
If necessary, change the other settings as required in the same way as described above.
Press the Enter key. The list of last shut-down and emergency stop cases is shown.
This submenu screen shows again a number of icons. By default, the User Password icon is selected. Also the status bar shows the name
of the menu that corresponds with the selected icon.
General menu
Function: this menu covers a list of general settings:
Language
Time
Date
Date Format
Units
Procedure: starting from the submenu screen (see Modifying general settings), using the Scroll keys, move the cursor to the General icon
(see below).
Press the Enter key. A screen similar to the one below appears:
(1) General
(2) Language in use
(3) Time
(4) Date
(5) Date format
(6) Modify
A screen similar to the one above is shown, a selection bar is covering the first item (Language). Use the ↓ key of the Scroll keys to select
the setting to be modified and press the Enter key.
To modify, select the Modify button using the Scroll keys and press the Enter key.
A pop-up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter key to confirm.
Restart delay This parameter allows you to programme the controller so that not all compressors are restarted at the same
time after a power failure (ARAVF active).
Compressor element outlet The regulator does not accept inconsistent settings, e.g. if the warning level is programmed
at 95 ˚C (203 ˚F), the minimum limit for the shut-down level changes to 96 ˚C (204 ˚F). The
recommended difference between the warning level and shut-down level is 10 ˚C (18 ˚F).
Delay at shut- down signal Is the time for which the signal must exist before the compressor is shut down. If it is required to program this
setting to another value, consult your supplier.
Minimum stop time Once the compressor has automatically stopped, it will remain stopped for the minimum stop time, whatever
happens with the net air pressure. Consult your supplier if a setting lower than 20 seconds is required.
Unloading/ Loading The regulator does not accept incorrect settings, e.g. if the unloading pressure is programmed at 7.0 bar(e) (101
pressure psi(g)), the maximum limit for the loading pressure changes to 6.9 bar(e) (100 psi(g)). The recommended
minimum pressure difference between loading and unloading is 0.5 bar (7 psi(g)).
These maintenance intervals are recommended for work environments that are not dusty and are will ventilated.
For particularly dusty environments, double the frequency of controls.
Every 500 hours Clean the air suction filter (see control board LED)
Every 2000 hours Change the oil (see control board LED)
Change the oil filter (see control board LED)
Change the suction filter (see control board LED)
Every 4000 hours Clean the finned surface of the air-oil cooler
Change the oil separating filter (see control board LED)
Greasing motor bearings
Every 8000 hours Visual inspection of motor element elastic coupling
Proceed as follows:
- Switch off the machine with pushbutton Ref. 1 Fig. 15: in this way the machine stops after 50 seconds of idle running.
- Open the differential supply switch, Ref. 2 Fig. 15 (on the screw-compressor) and Ref. 3 Fig. 15 (on the dryer if fitted).
2
FIG. 15
2 3
4
7
USE OIL OF THE SAME TYPE AS THAT ALREADY IN THE MACHINE; DO NOT MIX DIFFERENT TYPES OF OIL
USE OIL OF THE SAME TYPE AS THAT ALREADY IN THE MACHINE; DO NOT MIX DIFFERENT TYPES OF OIL.
BEFORE CARRYING OUT ANY OPERATION ON THE MACHINE, ENSURE THAT THE ELECTRIC POWER SUPPLY HAS
BEEN DISCONNECTED.
- Open the front panel with the special key Ref. 4 Fig. 15.
- Slowly open the oil plug Ref. 7 Fig. 15
- Top up to maximum level Ref. 6 Fig. 15, with oil of the same type in the compressor.
- Turn off the cap of the oil tank Ref. 7 Fig. 15.
- Close the panel Ref. 4 Fig. 15.
BEFORE DRAINING THE CONDENSATE IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS.
- Switch off the machine with pushbutton Ref. 1 Fig. 15: in this way the machine stops after 50 seconds of idle running.
- Open the differential supply switch, Ref. 2 Fig. 15 (on the screw-compressor) and Ref. 4 Fig. 15 (on the dryer if fitted).
- Remove the filter panel Rif. 1 e Rif. 2 Fig. 15a.
- Clean the filtering panel with a jet of air wash it with water, do not use solvents.
- Once the operation has been completed, reassemble the filter panel.
FIG. 15a
1
1
2 2
BEFORE DRAINING THE CONDENSATE IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS.
FIG. 16
2
2
3
HP 10 - 15 HP 20
- Switch off the machine with pushbutton Ref. 1 Fig. 15: in this way the machine stops after 50 seconds of idle running.
- Open the differential supply switch, Ref. 2 Fig. 15 (on the screw-compressor) and Ref. 3 Fig. 15 (on the dryer if fitted).
The automatic and manual condensation drain must be checked every day (Rif. 1 and Ref. 2 Fig. 17).
Proceed as follows:
- Press the "TEST" button, Ref. 1 Fig. 17, for a few seconds to check if the condensation is correctly emptied from the drainage pipe
- Check manual condensation emptying from the tank, to ensure that condensation is correctly emptied from the valve, Ref. 2 Fig. 17
(PURGE EVERY DAY AFTER USE).
FIG. 17
2 1
BEFORE CARRYING OUT ANY MAINTENANCE IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM
THE POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
FIG. 18
3
2
4
10
6
8
8
7 9
9
5
15.9 CLEAN THE DIRT COLLECTOR FILTER (DRYER and AIR TANK)
BEFORE CARRYING OUT ANY MAINTENANCE IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM
THE POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
Proceed as follows:
- Switch off the machine with pushbutton Ref. 1 Fig. 18: in this way the machine stops after 50 seconds of idle running.
- Close the cock Ref. 5 Fig. 18
- Open the differential supply switch, Ref. 2 Fig. 18 (on the screw-compressor).
- Depressurise the dryer by pressing the "TEST" condensation emptying button (for about 10-20 seconds), which is fitted on the timer, Ref. 6
Fig. 18.
- Open the differential supply switch, Ref. 3 Fig. 18 (on the dryer if fitted).
- Close the cock Ref. 10 Fig. 18
- Release pressure from the machine by turning on the cock Ref. 7 Fig. 18.
- Remove the stopper Rif. 8 Fig. 18
- Remove the filter Rif. 9 Fig. 18
- Clean the filter Ref. 9 with a jet of air, working from inside to outside.
- Install the filter, fix the plug. Rif. 8 - 9 Fig. 18.
WARNING: internal corrosion can seriously compromise the safety of installation; check it when changing cartridge.
Proceed as follows:
- Switch off the machine with pushbutton Ref. 2 Fig. 19: in this way the machine stops after 50 seconds of idle running.
- Open the differential supply switch, Ref. 3 Fig. 19 (on the screw-compressor).
- Close the cock Ref. 1 and Ref. 5 Fig. 19.
- Remove the protection Rif. 10 Fig. 19
- Depressurise the filters by pressing the "TEST" condensation emptying button (for about 10-20 seconds), which is fitted on the timer, Ref.
6 Fig. 19.
- Open the differential supply switch, Ref. 4 Fig. 19 (on the dryer if fitted).
- Release pressure from the machine by turning on the cock Ref. 5 Fig. 19.
- Change the filters Ref. 8 – 9 Fig. 19.
- Stick the adhesive label showing the month and year for the next filtering element change (max. one year) on the filter bowl.
FIG. 19
4
3
6
Afterfilter Afterfilter
Pre-filter
10
9
9
8
8
Pre-filter
Type 1
A4 - A4+ Type A6
If the machine is to be scrapped, it must be dismantled into parts of the same material, to be disposed of according to the local regulations in
force.
ALWAYS RESPECT THE REGULATIONS IN FORCE FOR DISPOSING OF OLD OIL AND OTHER POLLUTING MATERIALS
SUCH AS SOUND-DEADENING, FOAM, ETC.
FIG. 20
5
6 4
2
HP 20- kW 15
3
HP 10 – 15 / kW 7,5-11 7
1
Prefilter
9 Option
Afterfilter
2
8
ALL WORK MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL. BEFORE CARRYNG OUT ANY
MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE POWER MAINS.
N.B. OPERATIONS MARKED MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL APPROVED THE
MANUFACTURER
2) The machine does not start 2A – Hight oil temperature protection has -environment temperature too high;
the pilot lamp (Ref. 8 Fig. 13) is flashes. tripped ( oil Temp > 115°C – 239 °F) improve ventilation in the compressor
The pictograpf appears intermittently (Ref. room, Chapter 9.2
7 Tab. B)
3) The machine does not start 3A – Compressor screw temperature - environment temperature too high;
the pilot lamp (Ref. 8 Fig. 13) is flashes. switches have tripped (TSHH11-12) improve ventilation in the compressor
The pictograpf appears intermittently (Ref. 3B - Converter alarm. room, Chapter 9.2
5 Tab. B) 3C – Fan motor overload protection has - Check Converter alarm code: Read alarm
tripped. code on converter display and consult
converter user manual.
5) Excess oil consumption 5A - deteriorated oil separating filter - change the oil separating filter,
- oil level is too high Chapter 23
PART “B”
THIS PART “B” OF THE INSTRUCTIONS MANUAL IS RESERVED FOR PROFESSIONALLY SKILLED PERSONNEL
APPROVED THE MANUFACTURER.
WARNING: THE INVERTER REMAINS CHARGED WITH HIGH VOLTAGE FOR 15 MINUTES AFTER THE MASTER
SWITCH HAS BEEN OPENED.
ALWAYS WAIT FOR 15 MINUTES BEFORE REMOVING THE FRONT COVER (INSTRUMENT PANEL) OR
DISCONNECT CONVERTER SUPPLY WIRES OR MOTOR CABLE.
ALWAYS WAIT FOR FIVE MINUTES BEFORE REMOVING THE FRONT COVER (INSTRUMENT PANEL).
USE A SPECIFIC INSTRUMENT TO CHECK THAT THERE ARE NO DANGEROUS VOLTAGES BEFORE
PERFORMING OPERATIONS ON THE INVERTER OR MOTOR.
20.0 STARTING UP
BEFORE CARRYING OUT ANY OPERATION ON THE MACHINE, ENSURE THAT THE ELECTRIC POWER SUPPLY HAS
BEEN DISCONNECTED.
3 FIG. 21
OIL
1 1
- If the rotation is correct, the paper sheet Ref. 6 is blown up (See Fig. A)
- If the rotation is not correct, the paper sheet Ref. 6 remains flat (See Fig. B)
ALL WORK ON THE ELECTRIC PLANT, HOWEVER SLIGHT, MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED
PERSONNEL.
- Disconnect the energy supply and invert two connections as per Ref. 1 Fig. 22.
IF ALL THE INSTRUCTIONS FOUND IN THIS MANUAL HAVE BEEN OBSERVED THE MACHINE CAN BE STARTED.
FIG. 22
1
4
3
2
WANING: Motor start is ihnibit for a few seconds immediately after the
control card has power up or compressor motor has been stopped.
6
OK 6
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT
FROM THE POWER MAINS.
MAINTENANCE SCHEDULE
These maintenance intervals are recommended for work environments that are not dusty and are will ventilated. For particularly dusty
environments, double the frequency of controls.
Every 500 hours Clean the air suction filter (see control board LED)
Every 2000 hours Change the oil (see control board LED)
Change the oil filter (see control board LED)
Change the suction filter (see control board LED)
Every 4000 hours Clean the finned surface of the air-oil cooler
Change the oil separating filter (see control board LED)
Greasing motor bearings
Every 8000 hours Visual inspection of motor element elastic coupling
N.B.: THE OPERATIONS MARKED ARE DESCRIBED IN PART "A" OF THIS MANUAL ON CHAPTER 15.3
2 FIG. 23
2
OIL
1 3
THE OLD OIL MUST BE DISPOSED OF IN COMPLIANCE WITH THE REGULATIONS IN FORCE.
NOTE ON LUBRICANTS
When delivered the machine is filled with oil.
Extending the use of the oil over the scheduled replacement interval result in the risk of fire. If the compressor is used at high
temperatures or in particularly severe conditions, we advise shorter oil replacement interval.
DO NOT TOP UP WITH DIFFERENT OILS
FIG. 24
BEFORE CARRYING OUT ANY MAINTENANCE THE MACHINE MUST BE STOPPED, CUT OFF THE MACHINE FROM THE
ELECTRICAL MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION CIRCUIT, CHECK THAT THE MACHINE IS NOT
UNDER PRESSURE.
Proceed as follows: (Fig. 25)
- Switch off machine
- Remove machine rear panel Rif. 1.
- Before lubricating, clean the up grease nipple and immediate vicinity thoroughly.
- Lift grease inlet protection
- Remove the grease outlet plug
- Pump in approximately half of the total grease indicated on motor data plate (7grams)
- Close rear panel Rif. 1.
- Press down arrow on controller Ref. 4, till parameter "t. 03 "Regreasing is shown on Display Ref. 5, then press Enter button Ref. 6.
- Insert password (1807), and enable Regreasing procedure changing set from "OFF" to "ON" and press Enter Ref. 6.
- Press start button Ref. 7, the compressor start and will run for 60 seconds at 1560 rpm. When regreasing time will be elapsed controller will
reset automatically to return to standard operative conditions.
- Remove machine rear panel Ref. 1.
- Pump in the remaining grease.
- Lower again the grease inlet protection Ref. 2 and close reinstall the grease outlet protection Ref. 3.
5
FIG. 25
1 7
6
4
BEFORE PERFORMING ANY MAINTENANCE THE MACHINE MUST BE STOPPED, DISCONNECT THE MACHINE FROM
THE ELECTRIC SUPPLY AND FROM THE COMPRESSED AIR DISTRIBUTION CIRCUIT, CHECK THAT THE MACHINE IS
NOT UNDER PRESSURE.
- Insert password (1807), and enable Regreasing procedure changing set from “OFF” to “ON”.
- Come back to manin menù then press Start button, the compressor Start and will run for 60 seconds at 1560 rpm. When Regreasing
time will be elapsed controller will reset automatically to return to standard operative conditions
1 SUCTION FILTER
2 SUCTION REGULATOR
3 SCREW COMPRESSOR
4 OIL DISCHARGE VALVE
5 AIR-OIL PRESEPARATOR
6 OIL FILTER
7 THERMOSTATIC VALVE
8 AIR-OIL COOLER
9 PRESSURE SENSOR
10 MINIMUM PRESSURE VALVE
11 AIR-OIL SEPARATOR
12 PRESSURE GAUGE
13 SAFETY VALVE
14 TEMPERATURE SENSOR
15 ELECTRIC MOTOR
16 NO-LOAD RUNNING SOLENOID VALVE
17 OIL LEVEL
18 BLED VALVE
AIR CIRCUIT
OIL CIRCUIT
CONTROL CIRCUIT