FIRE PROTECTION
SIL Suitable Final Elements
FUNCTIONAL SAFETY OF
FIRE & GAS SYSTEMS
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR FUNCTIONAL SAFETY
ELECTRIC ACTUATOR
VDD DELUGE VALVE
FUNCTIONAL SAFETY
Safety is the absence of an
•
•
Definition
SIS
unacceptable risk of physical injury to
•
•
Requirements
IEC 61508 people or damage to the properties
• SIL
01/11/2022 SIL Suitable Final Elements 3
SAFETY INSTRUMENTED SYSTEM (SIS)
FUNCTIONAL SAFETY
A Safety Instrumented System (SIS) or
•
•
Definition
SIS
Safety‐related System is an appropriate
•
•
Requirements
IEC 61508 system required to reduce the risk
• SIL
F&G SYSTEM
(shown by a hazard analysis) of the
NIAGARA MONITOR Equipment Under Control (EUC)
ELECTRIC ACTUATOR
VDD DELUGE VALVE
A SIS performs one or more Safety
Functions to reduce the risk
01/11/2022 SIL Suitable Final Elements 4
REQUIREMENTS TO FUNCTIONAL SAFETY
FUNCTIONAL SAFETY
Two types of requirements are necessary
•
•
Definition
SIS
to achieve Functional Safety:
• Requirements
•
•
IEC 61508
SIL
Safety Function Requirements: the
F&G SYSTEM scope of the Safety Function, derived
NIAGARA MONITOR from the hazard analysis
ELECTRIC ACTUATOR
VDD DELUGE VALVE Safety Integrity Requirements: the
probability that the Safety Function will
be performed satisfactorily, derived
from the risk assessment
01/11/2022 SIL Suitable Final Elements 5
THE STANDARD IEC 61508
FUNCTIONAL SAFETY
IEC 61508 “Functional Safety of electrical
•
•
Definition
SIS
/electronic / programmable electronic
•
•
Requirements
IEC 61508 (E/E/PE) safety‐related systems”:
• SIL
FUNCTIONAL SAFETY
Safety Integrity is the probability that
•
•
Definition
SIS
the SIS will perform the required Safety
•
•
Requirements
IEC 61508 Functions satisfactorily
• SIL
01/11/2022 SIL Suitable Final Elements 8
FUNCTIONAL SAFETY
F&G SYSTEM
• Objectives
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
FIRE & GAS SYSTEM
VDD DELUGE VALVE
01/11/2022 SIL Suitable Final Elements 9
TASKS OF F&G SYSTEM
FUNCTIONAL SAFETY
The main tasks of a F&G system are:
F&G SYSTEM
• Tasks
Detect any hazardous fire or gas
•
•
Effectiveness
Components
condition
• Final Elements
01/11/2022 SIL Suitable Final Elements 10
F&G SYSTEM EFFECTIVENESS
FUNCTIONAL SAFETY
The F&G system Effectiveness is the
F&G SYSTEM product of three factors:
• Tasks
•
•
Effectiveness
Components
Detection Coverage: the fraction of the
• Final Elements
NIAGARA MONITOR
monitored area in which an eventual
ELECTRIC ACTUATOR hazard would be detected
VDD DELUGE VALVE
Mitigation Effectiveness: the
probability that the activation of the
Final Elements would reduce the
consequence of a defined hazard
F&G Safety Availability (SA): 1‐PFDavg
01/11/2022 SIL Suitable Final Elements 11
COMPONENTS OF F&G SYSTEM
FUNCTIONAL SAFETY
A F&G system consists of:
F&G SYSTEM
• Tasks
Detectors LOGIC
SOLVER
•
•
Effectiveness
Components Logic Solver
• Final Elements
FUNCTIONAL SAFETY
The F&G Effectiveness is related to the
F&G SYSTEM Safety Availability of all its components
• Tasks
• Effectiveness LOGIC NIAGARA
• SOLVER
•
Components
Final Elements
ELECTRIC
MONITORS
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE DETECTORS
FINAL ELECTRIC
ELEMENTS ACTUATORS
SA has developed VDD
DELUGE
SIL suitable Final Elements VALVES
for the main fire‐fighting systems
01/11/2022 SIL Suitable Final Elements 13
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
ELECTRIC MONITOR
VDD DELUGE VALVE NIAGARA SERIES
01/11/2022 SIL Suitable Final Elements 14
DESCRIPTION
FUNCTIONAL SAFETY
The fire‐fighting monitors
F&G SYSTEM Niagara series are electric
NIAGARA MONITOR
• Description
type remote controlled
•
•
Main features
Advantages
water cannons, intended to
• Application
ELECTRIC ACTUATOR
deliver large amount of water
VDD DELUGE VALVE towards remote targets.
The monitor architecture comprises
of a Logic Controller and one or more
monitor assemblies
01/11/2022 SIL Suitable Final Elements 15
MAIN FEATURES
FUNCTIONAL SAFETY
Automatic self‐diagnostic
F&G SYSTEM analysis
NIAGARA MONITOR
• Description Remote controlled
• Main features
•
•
Advantages
Application
Designed for sea water and
ELECTRIC ACTUATOR water foam solution
VDD DELUGE VALVE
Suitability for SIL2 systems
validated by Bureau Veritas
01/11/2022 SIL Suitable Final Elements 16
ADVANTAGES
FUNCTIONAL SAFETY
Automatic self‐diagnostic analysis: at
F&G SYSTEM regular intervals the self‐diagnostic
NIAGARA MONITOR
• Description
system in the Logic Controller checks the
•
•
Main features
Advantages
correct operation on given commands
• Application
FUNCTIONAL SAFETY
Designed for petrochemical
F&G SYSTEM jetty and marine harbor and
NIAGARA MONITOR
• Description
structure cooling
• Main features
• Advantages Recommended for those systems which
• Application
01/11/2022 SIL Suitable Final Elements 19
DESCRIPTION
FUNCTIONAL SAFETY
The double coil electric actuator has
F&G SYSTEM been developed to sharply reducing
NIAGARA MONITOR the probability of failure of a pilot
ELECTRIC ACTUATOR
• Description cylinder of a gaseous based fire
• Main features
• Application protection system (carbon dioxide,
VDD DELUGE VALVE
inert gases, halocarbons) or a water
mist system
01/11/2022 SIL Suitable Final Elements 20
MAIN FEATURES
FUNCTIONAL SAFETY
Redundancy: the actuator has two coils
F&G SYSTEM which receive two independent signals
NIAGARA MONITOR from the Logic Solver. If one coil should
ELECTRIC ACTUATOR
• Description fail, the other coil is able to open the
• Main features
• Application cylinder valve
VDD DELUGE VALVE
Suitability for SIL2
systems validated
by Bureau Veritas
01/11/2022 SIL Suitable Final Elements 21
APPLICATION
FUNCTIONAL SAFETY
Designed for the protection of gas
F&G SYSTEM turbines and their generators, electronic
NIAGARA MONITOR rooms and general installations on FPSO
ELECTRIC ACTUATOR
• Description
• Main features
Recommended for those systems which
• Application
require:
VDD DELUGE VALVE
A low probability of failure on demand
A fire protection system with a high
Safety Integrity Level
01/11/2022 SIL Suitable Final Elements 22
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
•
•
Description
Principle of operation
DOUBLE CHAMBER DELUGE VALVE
•
•
•
Main features
Advantages
Application
MODEL VDD
01/11/2022 SIL Suitable Final Elements 23
DESCRIPTION
FUNCTIONAL SAFETY
The VDD deluge valve combines all the
F&G SYSTEM functions of a traditional deluge valve
NIAGARA MONITOR with a fully redundant architecture,
ELECTRIC ACTUATOR
VDD DELUGE VALVE
designed to achieve a higher Safety
•
•
Description
Principle of operation
Availability
•
The VDD deluge valve
Main features
• Advantages
• Application
has two priming
chambers, each one
provided with its own
diaphragm and trim
01/11/2022 SIL Suitable Final Elements 24
PRINCIPLE OF OPERATION
FUNCTIONAL SAFETY
In the set position (valve closed)
F&G SYSTEM The pressure of the water trapped in
NIAGARA MONITOR the priming chambers holds the
ELECTRIC ACTUATOR
VDD DELUGE VALVE
diaphragms on the valve seats, keeping
•
•
Description
Principle of operation
the valve closed
•
In fire condition (valve open)
Main features
• Advantages
• Application
The pressure is released from the
priming chambers. The water supply
pressure forces the diaphragm off the
seats, opening the valve
01/11/2022 SIL Suitable Final Elements 25
MAIN FEATURES
FUNCTIONAL SAFETY
Fully redundant system
F&G SYSTEM Built‐in emergency bypass line that
NIAGARA MONITOR
operates on both priming chambers in
ELECTRIC ACTUATOR
VDD DELUGE VALVE
“hot back‐up”
• Description
•
•
Principle of operation
Main features
Continuous fire protection
Designed to overcome a double failure
• Advantages
• Application
Suitability for SIL3 systems validated by
Bureau Veritas
Under UL testing for UL/cUL Listing
FUNCTIONAL SAFETY
Built‐in emergency bypass line
F&G SYSTEM Each priming chamber provides the
NIAGARA MONITOR
nominal design waterway for the fire
ELECTRIC ACTUATOR
VDD DELUGE VALVE
protection system
• Description
•
•
Principle of operation
Main features
The system is fully redundant
The time to respond to a failure is
• Advantages
• Application
reduced to zero
No need of an external bypass line on
the skid: reduction of dimensions,
weight and cost of the skid
01/11/2022 SIL Suitable Final Elements 27
ADVANTAGES
FUNCTIONAL SAFETY
Designed to overcome a double failure
F&G SYSTEM A hydraulic bridge between the trims
NIAGARA MONITOR
allows each trim to control both the
ELECTRIC ACTUATOR
VDD DELUGE VALVE
diaphragms
• Description
•
•
Principle of operation
Main features
In case of failure of one trim, the other
•
•
Advantages
Application
trim can open both the priming
chambers
The VDD deluge valve can overcome a
double failure
FUNCTIONAL SAFETY
Designed to overcome a double failure
F&G SYSTEM Fault Tree of the VDD deluge valve
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
FUNCTIONAL SAFETY
Fire protection system always in service
F&G SYSTEM Two built‐in isolation
NIAGARA MONITOR
valves allow alternate
ELECTRIC ACTUATOR
VDD DELUGE VALVE
in‐line maintenance
•
•
Description
Principle of operation to be performed
• Main features
• Advantages
•
An interlock system prevents
Application
the accidental or incorrect
rotation of the isolation valves
FUNCTIONAL SAFETY
Made of Ni‐Al‐Bronze, a
F&G SYSTEM highly resistant material
NIAGARA MONITOR
Specifically designed for
ELECTRIC ACTUATOR
VDD DELUGE VALVE
harsh environments, such
•
•
Description
Principle of operation as oil & gas onshore and
• Main features
•
•
Advantages
Application
offshore and chemical and
nuclear plants installations
Sea water, foam
concentrate and
water foam solution
01/11/2022 SIL Suitable Final Elements 31
APPLICATION
FUNCTIONAL SAFETY
Recommended for those systems which
F&G SYSTEM require:
NIAGARA MONITOR
A low probability of failure on demand
ELECTRIC ACTUATOR
VDD DELUGE VALVE A fire protection system with a high
• Description
•
•
Principle of operation
Main features
Safety Integrity Level
Continuity of fire protection during
• Advantages
• Application
maintenance or repair
Reduction of weight, dimension and
cost of the skid