Lighting requirements
Content:
This guidance covers the following issues which relate to lighting:
Actions:
i. Design internal lighting specification in-line with Hea01.
ii. Design internal lighting zoning and controls in-line with Hea01.
iii. Design external lighting in-line with Hea01, Ene03 and Pol04.
iv. Ensure these measures are achieved so to not impact on additional credits.
Internal lighting
1. Internal lighting in all relevant areas of the building is designed to provide illuminance (lux) levels and colouring
rendering index in accordance with the SLL Code for Lighting 2012 and any other relevant industry standard.
Internal lighting should be appropriate to the tasks undertaken, accounting for building user concentration and
comfort levels.
2. For areas where computer screens are regularly used, the lighting design complies with CIBSE Lighting Guide 7
sections 2.4, 2.13 to 2.15, 2.20, and 6.10 to 6.20. This gives recommendations highlighting:
a. Limits to the luminance of the luminaires to avoid screen reflections. (Manufacturers’ data for the
luminaires should be sought to confirm this.)
b. Any area where a surface is used to reflect light into a space, such as up lighting, the recommendations
refer to the luminance of the lit ceiling rather than the luminaire; a design team calculation is usually
required to demonstrate this.
c. Recommendations for direct lighting, ceiling illuminance, and average wall illuminance.
1. All external lighting located within the construction zone is specified in accordance with BS 5489-1:2013 Code for
the practice for the design of road lighting. Lighting of roads and public amenity areas and BS EN 12464-2:2014
Light and lighting - Lighting of work places - Part 2: Outdoor work places. External lighting should provide illuminance
levels that enable users to perform outdoor visual tasks efficiently and accurately, especially during the night.
Zoning and occupant control
Internal lighting must be appropriately zoned to allow for occupant control. The required level of control will vary,
depending on the building/assessment type. Zoning must be in accordance with the following:
a. In office areas, zones of no more than four workplaces
b. Workstations adjacent to windows or atria are separately zoned and controlled to other areas of the room/building
c. Seminar and lecture rooms: zoned for presentation and audience areas
d. Library spaces: separate zoning of stacks, reading and counter areas
e. Teaching space or demonstration area zoned separately
f. Whiteboard or display screen zoned separately
g. Auditoria: zoning of seating areas, circulation space and lectern area
h. Dining, restaurant, café areas: separate zoning of servery and seating or dining areas
i. Retail: separate zoning of display and counter areas
j. Bar areas: separate zoning of bar and seating areas
k. Wards or bedded areas: zoned lighting control for individual bed spaces and control for staff over groups of bed
spaces
l. Treatment areas, dayrooms, waiting areas: zoning of seating and activity areas and circulation space with controls
accessible to staff
Areas used for teaching, seminar or lecture purposes have lighting controls provided in accordance with CIBSE Lighting
Guide 5.
The following are building specific lighting requirements:
Building type Internal and external lighting requirements
Education Buildings Manual lighting controls are easily accessible for the teacher while teaching and on entering
or leaving the teaching space. Manual lighting controls need only be provided for staff, not
the children.
Court Buildings Separate zoning is also provided for the following areas (as a minimum):
1. Judge's or magistrate's bench
2. Dock
3. Jury area
Note: This document is intended as guidance only. Consult your BREEAM AP or
Assessor to ensure compliance is achieved.
Small spaces (less than Buildings consisting entirely of small rooms or spaces (less than 40m²) which do not require
40m2) any subdivision of lighting zones or control will meet the zoning criteria by default.
Lighting zoning and The controls specified will depend on the size and use of the space but a typical auditorium
control - auditoria or lecture theatre with stepped seating and a formal lectern, demonstration or performance
spaces area would typically be expected to have lighting controls as follows:
1. Full normal lighting (to allow for entry, exit, cleaning etc.)
2. Demonstration area lighting off and audience area lighting reduced to a low level (for
the purpose of line slide projection, but allowing enough light for the audience to take
notes)
3. All lighting off (for the projection of tone slides, colour slides, and for the purposes of
visual demonstrations or performances)
4. Separate localised lectern lighting.
Internal areas excluded The following internal areas are excluded from the lighting zone requirements:
from the lighting zone
1. Media and arts production spaces
requirements
2. Sports facilities (exercise spaces only, including hydrotherapy and physiotherapy
areas).
a. The average initial luminous efficacy is not less than 70 luminaire lumens per circuit Watt
b. Automatic control is used to prevent operation during daylight hours (timer or daylight sensors)
c. Presence detection is used in areas of intermittent pedestrian traffic (i.e. the lighting is not permanently on)
a. The external lighting strategy has been designed in compliance with Table 2 (and its accompanying notes)
of the Institution of Lighting Professionals (ILP) Guidance notes for the reduction of obtrusive light, 2011.
b. All external lighting (except for safety and security lighting) can be automatically switched off between
23:00 and 07:00.
Note: This document is intended as guidance only. Consult your BREEAM AP or
Assessor to ensure compliance is achieved.
Issue Requirement
Hea06 - Security No specific requirement, but lighting should satisfy the Suitably Qualified
Security Specialist (SQSS/ALO) that the security is not compromised by poor
lighting.
Hea07 - Safety ‘Safe cycle lanes’ and ‘safe footpaths’ require adequate external lighting in
accordance with BS 5489-1:2013 Lighting of roads and public amenity areas.
Tra02 – Sustainable transport measures Any cycle storage facility has adequate lighting; demonstrated by meeting the
lighting criteria in BREEAM issue Hea01 Visual comfort.