S1 Series

Vector Inverter
Power range:0.4kW~4.0kW

User Manual

Product introduction 1
Installation 2
Wiring 3
Operating panel 4
Trial operation 5
Parameter list 6
Faults and diagnosis 7
Braking resistor selection 8
MODBUS protocol 9

Version
V1.0
Please carefully read the manual for safe use.
File No.:29900005 Please properly keep the manual and hand over it to its actual user.
Introduction
Thank you for choosing S1 series general vector inverter of Huayuan.

This Manual provides basic information related to the installation, wiring, parameter setting,
run and debug, fault diagnosis and detailed technical specifications of S1 series vector
inverter. Please carefully read this Manual before use. Improper use may cause abnormal
operation, fault, decreased service life and even equipment damage and personal injury.
We have reviewed whether the contents in this Manual are consistent with the said
hardware and software during editing, however, careless omission is inevitable, we will
regularly inspect the contents in this Manual for further modification and supplement. You
are welcome to provide valuable improvement suggestions.

This Manual is an accessory attached with the equipment. Please hand over it to its actual
user and keep it properly for future reference.

Our Company commits itself to continuous product improvement and update, so the
hardware and software will be subject to continuous upgrade, and the information provided
will be changed without notice.

V1.0
Revision date: June 2017
Important information

Unpacking inspection
After unpacking, please confirm whether the machine body and accessories are damaged,
whether parts and components are damaged or loosened, whether there are the machine
your ordered, User Manual, Quality Certificate and Warranty Bill. If you find any missed or
damaged parts or components, please contact with our supplier without any hesitation.

Please confirm the following items before unpacking:


(1) Is the external packing damaged;
(2) Is the model and specifications on the label consistent with your order requirements.

Safety precautions
The safe running of this product depends on proper installation, operation and
maintenance, please carefully read and pay attention to the hints related to
safety in this Manual.

● Please use the product after being familiar with the knowledge,
safety information and all precautions about Vector Inverter.
● This Manual should be kept by its actual user.
● In this Manual, there are two safety classes,“Danger”and“Warning”,
which are marked as follows:
:It indicates death or severe personal injury if
ignored.

: It indicates death or severe personal injury if


ignored.

According to the circumstance, an event at warning class may also cause a


serious consequence. Please always abide by the precautions at two classes
due to their importance to personal safety.
(1) Not used for machines or systems that may put the operator at risk
of life.
(2) Safety devices should be installed if a major accident or loss is
expected due to the fault of this product.

(1) Please install the inverter on a non-combustible object, such as


metal, to avoid the risk of fire.
(2) It is strictly prohibited to install this product in the environment
which contains combustible or explosive gas; otherwise there is the
risk of explosion.

(1) Install the inverter firmly on the object that can bear its weight;
otherwise, there may be the risk of personal injury or equipment
damage.
(2) Do not let metal foreign objects fall into the inverter, or an accident
may occur.
(3) Do not install or operate the damaged inverter, or an accident may
occur.

(1) Install the circuit breaker that matches the capacity of the inverter
at the input side of power supply; otherwise, personal injury or death,
equipment damage or other accidents may occur.
(2) The PE terminal of the inverter must be grounded reliably;
otherwise, there may be the risk of electric shock or fire.
(3) Tighten the screws at the power input terminal and motor output
terminal; otherwise there may be the risk of fire.
(4) Wiring must be carried out by the qualified personnel.
(5) Wiring must be carried out after confirming that the power is off and
the power supply charging indicator is off.

(1) Always ensure that the input power matches the data at the
nameplate, or the inverter may be damaged.
(2) Do not connect the power input wire to the output terminal (U.V.W)
of the inverter, or the inverter may be damaged.
(1) Do not turn on the power until the inverter cover is covered;
otherwise there is the risk of electric shock.
(2) After the inverter is powered on, even if it is in the stop state, do not
touch the main circuit terminal of the inverter; otherwise there is the risk
of electric shock.
(1) Use the “ ” key at the keyboard or the external ON / OFF
terminal to stop the inverter. Do not directly disconnect the main power
supply of the inverter; otherwise the inverter may be damaged.

(1) The inverter should not be inspected and repaired within 10


min after the charging indicator is off or the inverter is powered off;
otherwise, there is the risk of electric shock.
(2) The inverter should be maintained only by trained personnel;
otherwise, there is the risk of electric shock or personal injury.

(1) Do not leave any conductive material such as metal in the inverter
after maintenance; otherwise, the inverter may be damaged.
(2) If the inverter is reused after a long time, it is necessary to charge
the internal capacitors of the inverter. Use the voltage regulator to
slowly increase the input voltage of the inverter (can not be higher than
the rated input voltage of the inverter); otherwise, an accident may
occur.

(1) When disposal, the product should be treated as industrial waste;


otherwise an accident may occur.
Contents

1. Product introduction ..............................................................................1


1.1 Product model description ....................................................................2
1.2 Product nameplate description .............................................................2
1.3 Technical parameters ...........................................................................3
1.4 Technical specifications ........................................................................3

2. Installation ...............................................................................................5
2.1 Installation environment........................................................................6
2.2 Picture of installation space ..................................................................6
2.3 Disassembly and assembly of keypad .................................................8
2.4 Disassembly and assembly of terminal cover ......................................9
2.5 Installation dimension ..........................................................................10

3. Wiring ......................................................................................................13
3.1 Wiring of peripherals............................................................................14
3.2 Wiring of main circuit ...........................................................................15
3.3 Wiring of control circuit .......................................................................16
3.4 System connection ..............................................................................19

4. Keypad ....................................................................................................20
4.1 Introduction ..........................................................................................21
4.2 Keypad operation method ...................................................................22

5. Trail operation ........................................................................................24


5.1 Initial setting.........................................................................................25
5.2 Quick operation instruction ..................................................................25

6. Functional parameter list .....................................................................28


6.1 Functional parameter list .....................................................................29
7. Faults and diagnose .............................................................................66
7.1 Fault phenomenon and countermeasures ...........................................67

7.2 Warning phenomenon and countermeasures ....................................71

Appendix I Braking resistor selection ............................................................73

Appendix II MODBUS protocol .......................................................................74


S1 Series Vector Inverter

1. Product introduction 1

Product introduction
S1 series vector inverter is a kind of general Vector inverter which is researched and
developed at our new platform, it has excellent performance, complete protection functions,
compact, attractive and durable, and can be widely used in textile, food, packaging,
woodworking, carving and other industries.

1
S1 Series Vector Inverter

1.1 Product model description


S1-2S 0 015 - B

Serial number

Voltage class inbuilt braking unit


2 220V
Power level (kW)
4 380V
0004 0.4
Phase number 0007 0.75
S Single 0015 1 .5
T Three …

1.2 Product nameplate description

IP20 Protection class


Model MODEL: S1-2S0015-B
Motor power POWER: 1.5kW
Rated input INPUT: 1PH 220-240V
15A 50/60Hz
Rated output OUTPUT: 3PH 0V-UINPUT
7.5A 0-300Hz

Certification mark

2D code

S/N:

Bar code

Serial number 1002003017030001

HuaYuan Electric Co.,Ltd.

2
S1 Series Vector Inverter

1.3 Technical parameters


Voltage Rated Rated input Rated output Adaptive
Model capacity(kVA) current (A) current (A) motor (kW) 1
class

Product introduction
S1-2S0004(-B) 0.9 6 2.5 0.4
S i n g l e S1-2S0007(-B) 1.5 9.5 4 0.75
phase
220V S1-2S0015(-B) 2.8 15 7 1.5
S1-2S0022(-B) 4.1 25 10 2.2
S1-4T0007(-B) 1.7 3.2 2.5 0.75
Three S1-4T0015(-B) 2.6 5 4 1.5
phase
380V S1-4T0022(-B) 3.4 7 5.2 2.2
S1-4T0040(-B) 5.9 11 9 4.0

Table 1-1 Technical parameters

1.4 Technical specifications


Item Specifications
Adaptive motor (kW) See table 1-1
Rated capacity (kVA) See table 1-1
Rated output current (A) See table 1-1
Output Output voltage (V) 0V~ input voltage
Output frequency 0Hz~300Hz
150% of rated output current -60s (±5%) , 180% of rat
Currentoverload capacity
ed output current -3s

2S:200Vac~240Vac
Rated voltage
4T:380Vac~480Vac
Input
Rated input current (A) See table 1-1
Rated frequency 48Hz~62Hz
Max frequency 300Hz
Basic frequency 0Hz~300Hz
Frequencyof starting 0Hz~50Hz
Contro
lchara Accelerationand deceler 0S~3600S, of which the unit can be set as s (default)
cterist ation time or minute
ic
Analog setting: 0.1% of max frequency
Frequencyresolution
Digital setting: 0.01Hz

Analog setting: 2% of max frequency


Frequency precision
Digital setting: 0.01Hz

3
S1 Series Vector Inverter

Item Specifications
Usage rate: 0.0% ~ 100.0%
Direct voltage:
Dynamicbraking
220V : 350V~390V
380V : 650V~760V

Starting frequency: 0.00 Hz ~ 10.00Hz


DC injection braking Current level of DC injection braking: 0.0% ~ 100.0%
DC injection braking active time: 1.0 S ~ 60.0 S
0: Keypad setting
1: Potentiometer setting
Control
charact 2: UP/DOWN setting
eristic 3: Multi-speed setting
Frequency setting 4: AI1 Analog setting
mode
5: AI2 Analog setting
6: Serial communication setting
7: DI6 terminal pulse setting
8: Custom main and supplement setting

No action
AVR function Continuous action
Act only during deceleration
Relayoutput A programmable FormC relay

Output Programmable DO1 and DO2, of which DO2 is pulse output, up to


signal digital output 50kHz
Analog output AO1, AO2
DI1~DI6 programmable terminals, of which DI6 can also
Input Digital input
be used as the input terminal of 50kHz high-speed pulse
signal
Analog input AI1,AI2
5 bit LED display
8 buttons: RUN, STOP, ∧ , ∨ , PRG, 》, ENT, MF
Display LED 3 green LED lamps, display default unit: A, V, Hz
An additional green LED lamp next RUN button, display
the running status

Commu 232 None


nication 485 Two lines, MODBUS-RTU protocol
Efficiency ≥95%
MTBF No requirement
Other
Protection class IP20
Type of cooling Forcedair cooling

4
S1 Series Vector Inverter

2. Installation

2
This chapter will describe the correct installation method of S1 Series Vector Inverter

Installation
to ensure system safety and normal running of this product. Before installation, please
carefully read this Manual.

5
S1 Series Vector Inverter

2.1 Installation environment


Ambient temperature range: -10 ℃ - 40 ℃ . In case that the ambient temperature is
higher than 40℃ , please select a well-ventilated place. Rated output current must be
de-rated for 10% per 5℃ . Permissible maximum temperature is 55℃ .
The inverter must be de-rated for an installation altitude of above 1000 meters.
Rated output current must be de-rated for 10% per 1000 meters. Maximum altitude is
3000meters.

Please pay attention to the following items when selecting installation location:

Avoid high temperature and much humidity as far as possible. The


humidity should be less than 90%, without condensation;
tips no water drop, vapor, dust and metal dust;
keep away from inflammable, explosive and corrosive gas and liquid;
the mounting platform should be firm with vibration <5.9mm/s² (0.6g);
keep away from electromagnetic interference source.

2.2 Picture of installation space


The inverter is wall-mounted. The requirements on the mounting space and distance
of single inverter is shown in Figure2-1. In case that an inverter is required to be
mounted directly above another one, it is recommended to install an air guide plate as
shown in Figure2-2.

Air
出 风口outlet

Draught direction H Over 100mm


IP20
MODEL: S1-2S0015
POWER: 1.5kW
INPUT: 1PH 220-240V
15A 50/60Hz
OUTPUT: 3PH 0V-UINPUT
7.5A 0-300Hz

S/N:

1 0 0 2 0 0 3 11 6 1 2 0 0 0 1
HuaYuan Electric Co.,Ltd.

Air导guide
流隔 板 plate
L L 30 mm以上

Over
30mm Over
30mm MODEL: S1-2S0015
POWER: 1.5kW
INPUT: 1PH 220-240V
IP20

15A 50/60Hz
OUTPUT: 3PH 0V-UINPUT
7.5A 0-300Hz

S/N:

1 0 0 2 0 0 3 11 6 1 2 0 0 0 1
HuaYuan Electric Co.,Ltd.

H Over 100mm Air


inlet
进 风口

Figure2-1 Mounting space Figure2-2 Vertical installation of two inverters

Dimensional requirement
Power class
L H
0.4kW-4kW ≥30mm ≥100mm

6
S1 Series Vector Inverter

In case that an inverter is mounted at the right or left of another one, it is recommended
that the mounting space should be not less than 20mm, as shown in Figure2-3.

Draught出
direction
风方向 Draught出风
direction
方向 Over
10 100mm
0m m以上 出风 方向

Hz
RPM
A
%
V

2
Hz
RPM
A
%
V

Installation
3 0 mm以 上

Over
30m m以上
Over
3 0m m以上

30mm 30mm

Over 20mm
20mm以 上

Inlet air 进
direction
风 方向 Inlet air direction
进风 方向 Over 100mm
10 0m m以上

Figure2-3 Horizontal installation of two inverters

√ The higher the temperature is, the shorter the service life is
√ If there is any heating device near the inverter, please keep it far away from the
inverter as far as possible. Furthermore, if the inverter is installed in a case, please take
full account of perpendicularity and space to help heat dissipation.

This product is wall-mounted vertically. Please see chapter 2.5 for the hole sizes.

W
W1

Hz
RPM
A
%
V
H1
H

Figure 2-4 Installation diagram

7
S1 Series Vector Inverter

2.3 Disassembly and assembly of keypad

◆ Disassemble the keypad as shown in Figure2-5: Press elastic snap joint in the
direction 1 at first, and then uplift the keypad in the direction 2.

2
1

Figure 2-5 Keypad disassembly

◆ Assemble keypad as shown in Figure2-6: Place the keypad in the groove of keypad,
press the keypad in the direction 1 until you hear “crack” and the keypad is at the
level of the front surface of the inverter.

Figure2-6 Keypad assemble

8
S1 Series Vector Inverter

2.4 Disassembly and assembly of terminal cover

◆ Disassemble the terminal cover as shown in Figure 2-7:Use a cross screwdriver


to rotate the screw anticlockwise in the direction 1, take the screw out and then
disassemble the cover in the direction 2.

Installation
出风方向
1

2 3 0 m m以 上

Figure2-7 Terminal cover disassembly

◆ Assemble terminal cover as shown in Figure 2-8:Place the upper snap joint in the
appropriate juncture in the direction 1, use a cross screwdriver to rotate the screw
clockwise in the direction2.

出风方

2 出风方向

3 0 m m以 上

1
30mm以上

进风

Figure2-8 Terminal cover assembly

9
S1 Series Vector Inverter

2.5 Installation dimension


① Part name

Terminal cover screw


General keypadpanel

Terminal cover
Function indicator

Rs485 interface

Keypad interface
Wiring label of control terminal
Wiring label of main circuit terminal Wiring label of jumper
Main circuit terminal
Nameplate

Cooling air
Control terminal
Fan housing

Figure2-9 Part name

② Mounting dimensions of keypad


23
69 16 77

46 55

Figure2-10 Mounting dimensions of keypad (unit: mm)

According to the actual installation requirements,foot mounting method can be selected for
the keypad, the hole sizes of the foot are as follows:
94.8 104

60.2 69.9

Figure2-11 Mounting dimensions of keypad foot (unit: mm)

Note: For S1 Series Vector Inverter, it is permitted that the connecting cable (RJ45
interface) between keypad control terminal and the inverter is less than 10m. In case that
a larger distance is required, remote keypad should be equipped.
10
S1 Series Vector Inverter

③ Mounting dimensions of inverter


Applicable model of sizeA: S1-2S0004 (-B) ~S1-2S0015 (-B);
S1-4T0007 (-B)~S1-4T0022 (-B), as shown in Figure2-12.

Installation
Hz
RPM
A
%
V

Figure2-12 Mounting dimension of size A

Applicable model of Size B: S1-2S0022 (-B), S1-4T0040 (-B), as shown in Figure2-13.

D W
W1

EKPG101
Hz
RPM
A
%
V
H1
H

Figure2-13 Mounting dimension of size B

11
S1 Series Vector Inverter

④ Mounting dimension of inverter

Model (single Model W1 W H1 H D Applicable


phase 220V) (three phase 380V) (mm) (mm) (mm) (mm) (mm) screw
S1-2S0004(-B) —
S1-2S0007(-B) S1-4T0007(-B)
60 81.5 171.5 182.5 145 M5
S1-2S0015(-B) S1-4T0015(-B)
— S1-4T0022(-B)
S1-2S0022(-B) —
80 100 189 200 145 M5
— S1-4T0040(-B)

12
S1 Series Vector Inverter

3 . Wiring

This chapter describes the correct wiring method of S1 Series Vector Inverter. To ensure
system safety and normal operation of the inverter, please always wire the inverter
according to the wiring method provided in this chapter.

Wiring

13
S1 Series Vector Inverter

3.1 Wiring of peripherals


When S1 Series Inverter is used to drive asynchronous motor, a variety of electrical
devices must be installed on both input and output sides to ensure system safety
and stability.
L1
Input L2
Power L3
PE
Fuse
Air circuit breaker

PE AC reactor on input side

Contactor

L1 L2 L3
+ Braking resistor
PB
PE U V W

PE AC reactor on output side

PE
M Motor

Figure3-1 Wiring of peripherals

◆ Input power
Please supply power for the inverter according to the specifications provided in
this Manual.
◆ Air circuit breaker
(1) Cut off power supply of the inverter;
(2) Cut off power supply when short circuit occurs on power input side or
overcurrent occurs on downstream devices.
◆ AC reactor on input side
Control current surge due to grid voltage jump and switching overvoltage, smooth
spike pulse in supply voltage or voltage defect produced during phase change of
bridge rectifier circuit, effectively protect the inverter and improve power factor, it
can eliminate the interface from the grid and reduce the electric network pollution
caused by harmonic current produced by rectification unit.
◆ Contactor
Switch ON/OFF the inverter, do not use it to directly power on/off or start the
inverter frequently.
◆ Reactor on output side
It mainly can compensate for the impact of distributed capacitance in a long run
(20-200m), decrease earth leakage current of motor, inhibit harmonic current,
improve high-frequency impedance, effectively suppress dv/dt. It decrease high-
frequency leakage current to protect the inverter and reduce the noise.
◆ Braking resistor
Improve the braking capacity of inverter to prevent overvoltage warning.
14
S1 Series Vector Inverter

Do not install a capacitor or surge suppressor on output side, which


may cause the inverter fault or damage to the capacitor or surge
suppressor.
Input or output side of inverter has certain harmonics, which may
disturb the normal running of peripherals.
tips Please install anti-interference filter to minimize the disturbance.
The output of inverter is high-speed impulse voltage, which may
increaseleakage current in the circuit. If aresidual-current circuit
breaker is installed on input side of inverter, the induced current
of residual-current circuit breaker should be more than 100mA,
otherwise high-frequency impulse interference may cause
malfunction of residual-current circuit breaker.
3
Selection of peripheral electrical devices:

Wiring
Model Air circuit breaker (A) Contactor(A) Wire diameter (mm²)
S1-2S0004(-B) 10 9 0.75
S1-2S0007(-B) 16 12 0.75
S1-2S0015(-B) 25 18 1.5
S1-2S0022(-B) 40 32 2.5
S1-4T0007(-B) 6 9 0.75
S1-4T0015(-B) 10 9 0.75
S1-4T0022(-B) 10 9 0.75
S1-4T0040(-B) 16 12 1.5
Table 3-1 Selection of peripheral electrical devices

3.2 Wiring of main circuit


(1)Main circuit terminals class Ⅰ for S1-4T0007 (-B) ~S1-4T0040 (-B)

L 1 L2

Dynamic braking resistor Three-phase supply input Motor Motor ground

(2)Main circuit terminals class II forS1-2S0004 (-B) ~S1-2S0022 (-B)

L N

Dynamic braking resistor Single-phase supply input Motor Motor ground

Symbol description of main circuit terminals


Terminal symbol Function description
L, N L, N, single-phase 220V AC supply input
L1, L2, L3 L1, L2, L3, three-phase 380V AC supply input
U, V, W Connected to three-phase motor
+ Positive terminal on DC side of voltage

15
S1 Series Vector Inverter

- Negativeterminal on DC side of voltage


PB Dynamic braking resistor can be connected between + and PB
Ground terminal

√ No phase sequence is required for power supply wiring on input side of inverter;
√ Main circuit terminals should be wired after copper conductor is properly selected
according to the specifications shown in Table 3-1 and the method should comply with
local regulations and relevant IEC standards;
√ The cable between inverter and motor should not be parallel to power cable as far as
possible and should be at least 30cm;
√ It is prohibited to connect other devices with input side of inverter supply, it is strictly
prohibited to connect output terminals (U, V, W) with power supply, and do not connect
an capacitor or surge absorber on output side.
√ A non-fuse breaker must be installed between input power and inverter to prevent
extension of accident, if any, due to inverter fault, damage to power distribution unit or
fire;
√ There is no braking resistor inside the inverter, so a braking resistor must be installed
in case of large load inertia or frequent start-stop. When external braking module is
selected, the cable should not be more than 10m and the wiring distance should not be
more than 5m;
√ The ground terminal (PE) of inverter must be grounded reliably, the resistance of
ground wire muse be less than 0.4Ω, ground terminal (PE) should not be used as zero
terminal (N);
√ The specifications of ground wire are shown in the table below:

Section area of a phase line (S) Minimum section area of ground wire (S1)
S ≤ 16mm² S
16mm²< S ≤ 35mm² 16mm²
35mm²< S S/2

√ Yellow-green cable should be used as ground wire of inverter.

3.3 Wiring of control circuit


◆ Description of control circuit terminals
Wiring of control circuit must be separated from wiring of main circuit and should
not be placed in the same wiring duct.

16
S1 Series Vector Inverter

◆ Symbol description of control circuit terminals


Terminal
Category Functiondescription Technical specifications
symbol

Positive terminal
A of 485Differential
signal
Serialcommunication Modbus RTUprotocol
Negative terminal
B of 485Differential
signal

Select “sink” or “source” 3


Common multi- with jumper J3, in sink state, input
DI1~DI5 function digital input resistance is 6.8K, the upper and

Wiring
terminal lower logic threshold is 10V, sampling
period is 1ms

Select common digital input terminal


and high-speed pulse input terminal
Digital input and High-speed multi-
with jumper J7, the maximum input
output DI6 function digital input
pulse is 50kHz (only switch off with
terminal
24V switch in sink state).
Sampling period is 1ms

Programmable
DO1 Up to 50mA drive capability
digital output port 1

Programmable Up to 50mA drive capability, can be


DO2
digital output port 2 used as pulse output, up to 50kHz

0V~10V, input resistance 100k


0 mA ~20mA, load resistance 200Ω
(The modes selected with function
Programmable
AI1 code include 20 mA~0mA, 4 mA
analog input 1
~20mA, 20 mA~4mA)
Resolution 0.1%, precision 2%
Sampling period is 5ms

0V~10V, input resistance 100k


Programmable
AI2 Resolution 0.1%, precision
analog input 2
2%Sampling period is 5ms
Analog input and
output Select voltage and current mode with
jumper J4
Output voltage: 0V-10V
AO1 Analog output1
Output current: 0mA-20mA
Resolution 0.1%, precision ±5%
Update rate 5ms

0V~10V, maximum output current


5mA
AO2 Analog output2 Resolution 0.1%
precision ±5%
Update rate 5ms
17
S1 Series Vector Inverter

Terminal
Category Functiondescription Technical specifications
symbol

10V +10V power supply terminal Output 10V, 20mA, precision2%


Power
supply Output 24V, 100mA, precision
24V +24V power supply terminal
±15%

Reference ground shared by


Reference Referenceground of control
GND digital input, analog input and
ground circuit
power supply

FormC
Programmable relay 1 Contact capacity:
Other TA,TB,TC
output 250VAC/3A (cosφ=1) , 250VAC
/1A (cosφ=0.4) , 30VDC/3A

◆ Description of jumper terminals

1 1 1 1 1

2 2 2 2 2

3 3 3 3 3

Jumper selection
Category Function description
1-2 short circuit 2-3 short circuit
AI1 Analog input voltage and current
J2 0-20mA 0-10V
selection
Multi-function digital input sink and
J3 Source input Sink input
source selection
AO1 Analog output voltage and
J4 0-20mA 0-10V
current selection
Not connect
J5 RS485 terminal resistance selection 120Ω
withterminal resistor
DI6 terminal high-speed pulse High-speed Common digital
J7
selection pulse input

√ It is recommended to use 0.3~0.75mm²wire to connect control circuit terminals;


√ The wire should not be longer than 30m;
√ To avoid noise and disturbance, control circuit terminal should be connected with,
shielded wire and must be separated from main circuit and high voltage circuit;
√ It is recommended to useshielded twisted pairs to connect RS485 communication.

18
S1 Series Vector Inverter

3.4 System connection


External braking resistor

Three-phase
input supply
L1 Motor

L2

3
Ground

Wiring
Forward
running
DI1
Backward Multi-function relay output
running DI2 250 VAC, 3A and below
30 VAC, 3A and below
Forward
running DI3
Multi-section
Mult-function command terminal 1
digital input
DI4
Multi-section
command terminal 2 DO1
DI5
Programmable digital
Stop inverter outputAnalog outputIn
DI6
case of ON, DO1 and
DO2 supply
GND 24V/50mA power
DO2

Terminal to shieldedtwisted pairs

AI1 AO1
Analog output
Analog input AO2
AI2

GND

External keypad interface

Figure3-2 System connection of S1 series inverter

19
S1 Series Vector Inverter

4 . Keypad

This chapter describes the operation method and display information of S1 series
EKPG101 keypad in detail. Please always carefully read this chapter before you operate
the inverter.

20
S1 Series Vector Inverter

4.1 Introduction
EKPG101 keypad consists of the following four parts: 5-bit and 8-section LED display
tubes, 4 indicators, 8 keys and 1 rotational potentiometer. Users can use the keypad
to start and stop the inverter, view and change function parameters, monitor state
parameters. Its appearance and function distribution are shown in Figure4-1.

Indicator
LED Rotational
display tube potentiometer
RUN indicator

Confirm Increment
Multifunction Run
Return decrement 4
Shift Stop / Reset

Operating panel
Figure4-1Introduction

Function description

Key Key name Function description

LED display Display output frequency, current, the set value of


tube various parameters and faults

Hz: It keeps on to display output frequency or


Display flashes to display the set frequency
function
A: It keeps on to display current current, the unit is
Indicator
A
V: It keeps on to display output voltage or flashes
to display mains voltage

Rotational
potentiometer
Used to set the set parameters of potentiometer

Used to set auto stop, inching, forward running or


Multifunction
reverse running
Keypad
function Used to exit current menu or operation, the main
Return interface returns to the default display (i.e. the
function of “Escape”)

Used to enter the menu or confirm the changed


Confirm
parameter or return

Used to switch main interface or select the digit to


Shift
be modified when modifying a parameter value

21
S1 Series Vector Inverter

Key Key name Function description

Keypad running command (The inverter starts


Run when the indicator is on and stops when the
indicator is off)

Stop / Reset Keypad stop command or fault reset


Keypad
function
Increment Function code or value increment

Decrement Function code or value increment

4.2 Keypad operation method


① Query and change function parameters
S1 Series Vector Inverter keypad has three levels of menu to set parameters, monitor
state, which are function parameter group (Level I), function code(Level II) and parameter
value(Level III). Function parameters are queried and changed as shown in Figure4-2.

Initial interface

Level I menuFunction
parameter group
Level II menu
Function code

Level III menuParameter


value

Figure4-2Parameter query and change flow chart

Description:
Press “PRG” or “ENT” from a Level III menu to return Level II menu. The difference
between two keys:Press “ENT” to save the parameter value you have set, return to
Level II menu and then automatically go to the next function parameter; while press“PRG”
to directly return to Level II menu without saving the parameter value you have set.

22
S1 Series Vector Inverter

② Lock and unlock keypad


Lock:
Set function parameter P09.06 to lock all or part functions of keypad, if the
parameter value is set as 1 or 2, press “ENT”, the keypad is locked;

Unlock:
f the keypad is locked, press “PRG” and hold for over 5s to unlock it. After that, P09.06
return to 0.

Operating panel

23
S1 Series Vector Inverter

5 . Trail operation

This chapter describes the relevant operations necessary for the starting and trail operation
of S1 Series Vector Inverter, initialization of common parameter groups as well as the
regulating methods and steps of motor parameter during the open loop vector operation of
SVC.

24
S1 Series Vector Inverter

5.1 Initial setting


① Control mode selection of motor, initial value P00.20=1
Two control modes can be set with function code P00.20:
0: Open loop V/F control;
1: Open loop vector control mode.

② Operation command mode selection, initial valueP00.03=0


Three operating command modes can be set with function code P00.03:
0: Keypad control
1: Terminal control
2: Communication control

③ Setting frequency source selection, initial valueP00.04=0


0:Keypad setting 3:Multi-speed setting 6:Serial communication
1:Potentiometer setting 4:AI1 7:DI6
2:UP/DOWN setting 5:AI2 8:Custom main and
5

5.2 Quick operation instruction

Trial operation
It is strictly prohibited to connect input power line to the output
terminal U, V, W of Inverter

L1 U
Three-phase Motor
L2 V
input supply
L3 W

Ground

Figure5-1 Wiring diagram of trail operation

① Keypad operation
Parameters are set as shown in Table 5-2 with parameter group (P00 group) in
shortcut menu as an example.

Parametersetting Description
P00.13 Rated voltage of motor, set according to motor nameplate
P00.14 Rated current of motor, set according to motor nameplate
P00.15 Rated frequency of motor, set according to motor nameplate
P00.16 Rated speed of motor, set according to motor nameplate
P00.19 Power factor of motor, set according to motor nameplate
Table5-2 Parameter setting when the keypad starts

25
S1 Series Vector Inverter

Other parameters can be set according to factory default value.


● Inching
Press“ ” and hold it, the inverter starts within acceleration time set with
parameterP02.20 until it runs with the frequency up to 5.00Hz(P01.03 defaultvalue),
release “ ”, and then it stops in the mode set with parameter P03.12.
● Normal running
Press “ ”, the inverter starts and RUN indicator is on. Press “ ” to
increase output frequency, press “ ” to decrease output frequency. Press
“ ”, the inverter decelerates and stops when the speed is decreased to 0, the
run indicator is off.

②  Terminal operation
Control the inverter with terminals, the relevant parameters are set as shown in Table
5-3, at this time, RUN andMF are invalid. Peripheral wiring of terminals are shown in
Figure5-4
Parametersetting Description
P00.03(P03.01)=1 External terminal control
P00.04(P01.08)=4 Set AI1(0~10V) as frequency source
P00.13 Rated voltage of motor, set according to motor nameplate
P00.14 Rated current of motor, set according to motor nameplate
P00.15 Rated frequency of motor, set according to motor nameplate
P00.16 Rated speed of motor, set according to motor nameplate
P00.19 Power factor of motor, set according to motor nameplate

Table 5-3Parameter setting when the keypad starts


Other parameters can be set according to factory default value.
K1
DI1
K2
DI2
K3
DI3
GND/24V

10V
AI1

GND

Figure5-4 Wiring diagram (default setting)

Switch on K1, Run indicator is on, the motor runs forward, adjust output frequency
with AI1. Switch off K1, the motor decelerates and stops when the speed is decreased
to 0, the run indicator is off;
Switch onK2, Run indicator is on, the motor runsreverse running, adjust output
frequency with AI1. Switch offK2, the motor decelerates and stops when the speed is
decreased to 0, the run indicator is off;

26
S1 Series Vector Inverter

If K1, K2 are switched on at the same time, the inverter stops;


Switch on K3, Run indicator is on, the motor runs forward with the set inching
frequency. Switch off K3 the motor decelerates and stops when the speed is
decreased to 0, the run indicator is off.

③  Open-loop vector parameter identification


Select vector control running mode, during parameter identification, you must ensure
that the parameters are sect according to motor nameplate, otherwise the control
effect will be impacted.
With 2.2kW motor driven byS1-4T0022 as an example, the whole operation procedure
is as follows:

Rated Rated Rated


Frequency Rated speed Power factor
voltage current frequency
2.2 kW 380V 5A 50Hz 1450 0.9

◆ Please refer to motor nameplate to set


P00.13=380 Rated voltage of motor
P00.14=5 Rated current of motor
P00.15=50 Rated frequency of motor
5
P00.16=1450 Rated speed of motor

Trial operation
P00.19=0.9 Power factor of motor

◆ After the following parameters are set, setP00.17(P04.02) =1, press “ ”


to save. Press “ ” to return status display interface, press “ ” to enter
parameter identification state, the keypad display is as shown in Figure5-5.

Figure5-5 Keypad display during parameter identification

◆ After parameter identification, the inverter stops.

27
S1 Series Vector Inverter

6. Functional parameter list

S1 Series Vector Inverter consists of 21 function parameter groups accordingto parameter


property of, of which:
● P00 group is shortcut menu group, built-in function code parameters are mapped by
other parameters, including most of commonly used function code parameters, serves
uses which require simple application;
● P01~P19 groups and P30 group are application function code parameter groups,
including 510 function code parameters, and serves users which require complex
application.

28
S1 Series Vector Inverter

6.1 Functional parameter list


P00 groupshortcut menu
Minimum Change
Parameter Correlation Name Setting range Default
unit method
Recycling 0: Fixed mode
P00.01 P09.02 display 1: Auto switching mode 1 0 Read-write
mode 2: Retain
0: Only display parameters
in shortcut menu
Parameter 1: Display parameters in all
P00.02 P09.03 display menu 1 1 Read-write
selection 2: Only display the
parameters different from
factory default value
Operating 0: Keypad Writable
P00.03 P03.01 mode 1:Terminal 1 0 during
selection 2: Communication downtime
0: Keypad setting
1: Keypad potentiometer
setting
2: UP/DOWNsetting
Frequency 3: Multi-speed setting
source 4: AI1 analog setting
P00.04 P01.08 1 0 Read-write
setting 5: AI2analog setting
selection 6: Serial communication
setting 6
7: DI6 terminalpulse setting
8: Customized main and

Parameter list
auxiliary setting
0: 0 mA - 20mA
1: 20 mA - 0mA
2: 4 mA - 20mA (alarm
in case that current input
breaks)
3: 20 mA - 4mA (alarm
Analog in case that current input Writable
P00.05 P07.02 input breaks) 1 6 during
1 mode 4: 4 mA-20mA (no alarm downtime
in case that current input
breaks)
5: 20 mA -4mA (no alarm
in case that current input
breaks)
6: 0V~10V
Multi-
P00.06 P14.01 -P01.01 ~ +P01.01 0.01Hz 5.00 Read-write
speed1
Maximum Writable
P00.07 P01.01 operating 0.00 ~ 300.0 0.01Hz 50.00 during
frequency downtime
Minimum Writable
P00.08 P01.02 operating 0.00 ~ P01.01 0.01Hz 0.00 during
frequency downtime
Acceleration
P00.09 P02.06 0.0 ~ 3000.0 0.1 10.0 Read-write
time 1

29
S1 Series Vector Inverter

Paramet Correlati Minimum Change me


Name Setting range Default
er on unit thod
P02.07
P00.10 P02.07 Deceleration 0.0 ~ 3000.0 0.1 20.0 Read-write
time 1
0: Decelerate to stop
1: Coast to stop
Writable du
P00.11 P03.12 Stop mode 2: Decelerate to stop+ DC inje 1 0 ring downti
selection ction braking me
3: Decelerate to stop+ Coast
to stop
Initial value 0: 0.00
set in keyp
P09.05 ad control 1: Set parameter of keypad at
P00.12 1Hz 0.00 Read-write
last run
when poweri
2: Multi-speed1
ng on
Motor1 rated 220V:0 ~ 240 Approp Writable du
P00.13 P04.06 1V riate for ring downti
voltage 380V:0 ~ 480 mode me
Approp Writable du
P04.07 Motor1 rated 0.1 ~rated current of invert
P00.14 0.1A riate for ring downti
current er×1.2 model me
Writable du
P00.15 P04.08 Motor1 rated
frequency 1.00 ~ 300.00 0.01Hz 50.00 ring downti
me

Motor1 rated Writable du


P00.16 P04.10 frequency 0 ~ 18000 1RPM 0 ring downti
me
0: No operation
Motor param 1: Static parameter identificati Writable du
identifi on 1 (run once)
P00.17 P04.02 eter 1 0 ring downti
cation functi 2: Static parameter identificati me
on selection on 2 (every run)
3: Retain
Writable du
P04.11 Motor 1 stat
P00.18 or resistance 0.000 ~ 32.000 0.001 ohm 0.000 ring downti
me
Writable du
P04.05 Motor 1 pow 0.00 ~ 1.00
P00.19 0.01 0.85 ring downti
er factor me
0: Open-loop V/F control Writable du
P00.20 P04.01 Motor contr 1: Open-loop vector control 1 0 ring downti
ol mode
mode me

P09.15 Carrier frequ


P00.21 ency setting 1 ~ 15 1kHz 6 Read-write

Motor torque
P06.08 compensati 0.0 ~ 30.0 (relative to rated vo
P00.22 0.1% 3.0 Read-write
ltage of motor)
on
0: Customized V/F curve
MotorV/F cu 1: 2 power curve Writable du
P00.23 P06.01 1 0 ring downti
rve setting 2: 1.7 power curve me
3: 1.2 power curve
Return to fac 0: Do not return to factory par Writable du
ameter setting
P00.24 P09.13 tory paramet 1 0 ring downti
1: Return to factory parameter me
er setting setting
30
S1 Series Vector Inverter

P01 groupSet parameter


Minimum Change
Parameter Name Setting range Default
unit method
Writable
Max running
P01.01 0.00 ~ 300.0 0.01Hz 50.00 during
frequency
downtime
Writable
Min running
P01.02 0.00 ~ P01.01 0.01Hz 0.00 during
frequency
downtime
Inching running
P01.03 0.00 ~ P01.01 0.01Hz 5.00 Read-write
frequency
Writable
P01.04 Hopping frequency 1 0.00 ~ P01.01 0.01Hz 0.00 during
downtime
Writable
P01.05 Hopping frequency 2 0.00 ~ P01.01 0.01Hz 0.00 during
downtime
Writable
Hopping frequency
P01.06 0.00 ~ 30.00 0.01Hz 0.00 during
range
downtime
P01.07 Standby — — — —
0: Keypad setting
1: Keypad potentiometer
setting
2: UP/DOWN setting
3: Multi-speed setting
4: AI1Analog setting
6
Set frequency source
P01.08 5: AI2Analog setting 1 0 Read-write
selection
6: Serial communication

Parameter list
setting
7: DI6 terminal pulse
setting
8: Customized main and
auxiliary setting
P01.09 Set frequency -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
P01.10 Keypad key set value -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
Keypad potentiometer
P01.11 -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
set value
P01.12 UP/DOWNset value -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
P01.13 Multi-speed set value -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
P01.14 AI1Analog setting -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
P01.15 AI2Analog set value -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
Serial communication
P01.16 -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
set value
DI6 terminal pulse set
P01.17 -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
value
Customized main and
P01.18 -P01.01 ~ +P01.01 0.01Hz Displayed value Read only
auxiliary setting
P01.19 Standby — — — —
0: Disabled (output
UP/DOWNnegative
0.0%~100.0%)
P01.20 output value 1 0 Read-write
1: Enabled (output
permission control
-100.0% ~+100.0%)
31
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
UP/DOWN setting
P01.21 0.0 ~ 250.0 0.1s 10.0 Read-write
slope
UP/DOWN
P01.22 outputmagnification 0.000 ~ 4.000 0.001 1.000 Read-write
times
Writable
UP/DOWN output
P01.23 0.00 ~ 30.31 P00.01 0.00 during
function selection
downtime
UP/DOWN output 0: Invalid
P01.24 1 0 Read-write
reset control 1: Valid
UP/DOWN
0: Invalid
P01.25 outputincrement 1 0 Read-write
1: Valid
(UP)
UP/DOWN
0: Invalid
P01.26 output decrement 1 0 Read-write
1: Valid
(DOWN)
UP/DOWN Displayed
P01.27 -100.0 ~ +100.0 0.1% Read only
outputdisplay value
0: 0 after being re-powered on
1: 0 after being re-powered on
and change only during the
inverter running
2: Last set value after being
UP/DOWN initial
powered on
P01.28 value after being 1 0 Read-write
3: last set value after being
re-powered on
powered on and change only
during the inverter running
4:Multi-speed1
5:Multi-speed1, change only
during the inverter running

Stop UP/ DOWN 0: Retain


P01.29 1 0 Read-write
output selection 1: Reset

P01.30 Standby — — — —
Frequency setting 0: Invalid Displayed
P01.31 1 Read only
switched to AI1 1: Valid value
Frequency setting 0: Invalid Displayed
P01.32 1 Read only
switched to AI2 1: Valid value

32
S1 Series Vector Inverter

P02 groupAccelerate/ decelerate parameter


Change
Parameter Name Setting range Minimum unit Default
method
0: Linear accelerate/
Writable
accelerate / decelerate decelerate
P02.01 1 0 during
mode selection 1: S–curve accelerate/
downtime
decelerate
Initial segment time of
P02.02 0.0 ~ 40.0 0.1% 20.0 Read-write
S curve
Initial segment time of
P02.03 0.0 ~ 40.0 0.1% 20.0 Read-write
S curve
Output frequency 0: No
P02.04 1 0 Read-write
retain 1: Yes
Writable
Acceleration, 0:s(s)
P02.05 1 0 during
deceleration time unit 1:m(min)
downtime
P02.06 Acceleration time1 0.0 ~ 3000.0 0.1 10.0 Read-write
P02.07 Deceleration time1 0.0 ~ 3000.0 0.1 20.0 Read-write
P02.08 Acceleration time2 0.0 ~ 3000.0 0.1 30.0 Read-write
P02.09 Deceleration time2 0.0 ~ 3000.0 0.1 30.0 Read-write
P02.10 Acceleration time3 0.0 ~ 3000.0 0.1 30.0 Read-write
P02.11 Deceleration time3 0.0 ~ 3000.0 0.1 30.0 Read-write
P02.12 Acceleration time4 0.0 ~ 3000.0 0.1 30.0 Read-write
P02.13 Deceleration time4 0.0 ~ 3000.0 0.1 30.0 Read-write
Acceleration time 0: Invalid Displayed 6
P02.14 1 Read only
select bit 0 1: Valid value
Acceleration time 0: Invalid Displayed

Parameter list
P02.15 1 Read only
select bit 1 1: Valid value
Deceleration time 0: Invalid Displayed
P02.16 1 Read only
select bit 0 1: Valid value
Deceleration time 0: Invalid Displayed
P02.17 1 Read only
select bit 1 1: Valid value
1: Acceleration time1Valid
Acceleration time 2: Acceleration time2Valid Displayed
P02.18 1 Read only
select value 3: Acceleration time3Valid value
4: Acceleration time4Valid
1: Deceleration time1Valid
Deceleration time 2: Deceleration time2Valid Displayed
P02.19 1 Read only
select value 3: Deceleration time3Valid value
4: Deceleration time4Valid
Inching acceleration
P02.20 0.1 ~ 600.0 0.1s 10.0 Read-write
time
Inching deceleration
P02.21 0.1 ~ 600.0 0.1s 10.0 Read-write
time

33
S1 Series Vector Inverter

P03 group Start/stop control parameter


Minimum Change
Parameter Name Setting range Default
unit method
0: Keypad Writable
Operating mode
P03.01 1: Terminal 1 0 during
selection
2: Communication downtime
0: Enabled Writable
P03.02 Anti-reverse control 1:Disabled 1 0 during
downtime
Forward/reverse
P03.03 0.0 ~ 3000.0 0.1s 0.0 Read-write
dead time
0: Disabled Writable
Restart function after
P03.04 1: Enabled 1 1 0 during
power failure
2: Enabled 2 downtime
Waiting time of
P03.05 restart after power 0.0 ~ 60.0 0.1s 0.0 Read-write
failure
0:Direct starting
Writable
Starting mode 1:Start after braking
P03.06 1 0 during
selection 2:Start after rotate speed
downtime
tracking
P03.07 Start frequency 0.00 ~ P01.01 0.01Hz 0.00 Read-write
Hold time of start
P03.08 0.0 ~ 60.0 0.1s 0.0 Read-write
frequency
Start DC braking 0.0 ~300.0 (relative to rated
P03.09 0.1% 0.00 Read-write
current current of motor)
P03.10 Start DC braking time 0.0 ~ 60.0 0.1s 0.0 Read-write
Interval between
restart and inching
P03.11 0.1 ~ 600.0 0.1s 0.1 Read-write
after rotate speed
tracking
0:Decelerate to stop
1:Coast to stop
Writable
2:Decelerate to stop+DC
P03.12 Stop mode selection 1 0 during
braking
downtime
3:Decelerate to stop+Coast to
stop
P03.13 Stop frequency 0.00 ~ P01.01 0.01Hz 0.10 Read-write
Start frequency of DC 0.0 ~100.0 (relative to max
P03.14 0.1% 0.0 Read-write
braking running frequency)
0.0 ~300.0 (relative to rated
P03.15 DC braking current 0.1% 0.0 Read-write
current of motor)
P03.16 DC braking time 0.00 ~ 60.00 0.01s 0.00 Read-write
P03.17 Standby — — — —
Command switched 0: Invalid Displayed
P03.18 1 Read only
to terminal 1: Valid value
0: Invalid
P03.19 Disable inverter 1 0 Read-write
1: Valid
0: Invalid
P03.20 Running 1 0 Read-write
1: Valid

34
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Three-wire mode 0: Invalid
P03.21 1 0 Read-write
enabled 1: Valid
0: Invalid
P03.22 Forward running 1 0 Read-write
1: Valid
0: Invalid
P03.23 Reverse running 1 0 Read-write
1: Valid
0: Invalid
P03.24 Forward/Reverse 1 0 Read-write
1: Valid
0: Invalid
P03.25 Forward inching 1 0 Read-write
1: Valid
0: Invalid
P03.26 Reverse inching 1 0 Read-write
1: Valid
Serial communication
P03.27 0 ~ 65535 1 0 Read-write
control word
Serial communication 0: Invalid
P03.28 1 0 Read-write
control word enabled 1: Valid
Inching running selecti 0: Invalid Display
P03.29 1 Read only
on 1: Valid ed value

Parameter list

35
S1 Series Vector Inverter

P04 groupMotor parameter


Minimum Change
Parameter Name Setting range Default
unit method
0: Open-loopV/F control
Motor control Writable during
P04.01 1: Open-loop vector control 1 0
mode downtime
mode
0: No operation
Motor parameter 1: Static parameter
Writable during
P04.02 identification identification 1 (run once) 1 0
downtime
function selection 2: Static parameter
identification 2 (every run)
Motor 1/Motor2 0: Select motor1 Writable during
P04.03 1 0
selection 1: Select motor2 downtime
P04.04 Standby — — — —
Motor 1 power Writable during
P04.05 0.00 ~ 1.00 0.01 0.85
factor downtime
Motor 1 rated 220V:0 ~ 240 Appropriate Writable during
P04.06 1V
voltage 380V:0 ~ 480 for model downtime
Motor 1 rated 0.1 ~ rated current of Appropriate Writable during
P04.07 0.1A
current inverter× 1.2 for model downtime
Motor1 rated Writable during
P04.08 1.00 ~ 300.00 0.01Hz 50.00
frequency downtime
Motor1 number of Writable during
P04.09 0~4 1 2
pole-pairs downtime
Motor1 rated Writable during
P04.10 0 ~ 18000 1RPM 0
speed downtime
Motor1 stator 0.001 Writable during
P04.11 0.000 ~ 32.000 0.000
resistance ohm downtime
P04.12 Standby — — — —
P04.13 Standby — — — —
P04.14 Standby — — — —
P04.15 Standby — — — —
P04.16 Standby — — — —
Motor 2 power Writable during
P04.17 0.00 ~ 1.00 0.01 0.85
factor downtime
Motor 2 rated 220V:0 ~ 240 Appropriate Writable during
P04.18 1V
voltage 380V:0 ~ 480 for model downtime
Motor 2 rated 0.1 ~ rated current of Appropriate Writable during
P04.19 0.1A
current inverter× 1.2 for model downtime
Motor2 rated Writable during
P04.20 1.00 ~ 300.00 0.01Hz 50.00
frequency downtime
Motor2 number of Writable during
P04.21 0~4 1 2
pole-pairs downtime
Motor2 rated Writable during
P04.22 0 ~ 18000 1RPM 0
speed downtime
Motor2 stator 0.001 Writable during
P04.23 0.000 ~ 32.000 0.000
resistance ohm downtime

36
S1 Series Vector Inverter

P05 group Vector control parameter


Minimum Change
Parameter Name Setting range Default
unit method
0: Unchangeable during
Speed/Torque control
running
selection
P05.01 1: Changeable during 1 0 Read-write
Changeable/unchangeable
running
during running

Speed /Torque control 0: Speed control mode


P05.02 1 0 Read-write
selection 1: Torque control mode
Max speed limit during
P05.03 0.00 ~ 1.2 * P01.01 0.01Hz 50.00 Read-write
torque control
0: Keypad
1: Keypad potentiometer
2: Analog value AI1 Writable
P05.04 Torque setting selection 3: Analog value AI2 1 0 during
4: Pulse frequency (DI6) downtime
5: Remote communication
6: User PID
P05.05 Torque gain 0.0 ~ 300.0 0.1% 100.0 Read-write
P05.06 Torque offset 0.0 ~ 100.0 0.1% 0.0 Read-write
Displayed
P05.07 Torque setting -300.0 ~ +300.0 0.1% Read only
value
P05.08 Standby — — — —
0: Invalid Displayed
P05.09 Torque limited 1 Read only
1: Torque limited value 6
P05.10 Standby — — — —
P05.11 Standby — — — —

Parameter list
P05.12 Standby — — — —
P05.13 Standby — — — —
P05.14 Standby — — — —
P05.15 Standby — — — —
P05.16 Standby — — — —
P05.17 Standby — — — —
P05.18 Standby — — — —
P05.19 Standby — — — —
P05.20 Standby — — — —
Electriccurrent
P05.21 loopproportionality 0.001 ~ 10.000 0.001 0.07 Read-write
coefficient
Electriccurrent loopintegral
P05.22 0.00 ~ 100.00 0.01s 0.20 Read-write
time
P05.23 Standby — — — —

P05.24 Slip compensation gain 0 ~ 1500 1RPM 0 Read-write


0.0 ~ 300.0 (relative to rated
P05.25 Motor torque limit level 0.1% 200.0 Read-write
current of motor)
Generator torque limit 0.0 ~ 300.0 (relative to rated
P05.26 0.1% 150.0 Read-write
level current of motor)

37
S1 Series Vector Inverter

P06 group V/F control parameter


Minimum Change
Parameter Name Setting range Default
unit method
0: Customized V/F curve
1: 2 power curve
Motor V/Fcurve Writable
P06.01 2: 1.7 power curve 1 0
setting during
3: 1.2 power curve
downtime

Writable
Motor V/F frequency P06.04 ~rated frequency of
P06.02 0.01Hz 0.00 during
value3 motor
downtime
Writable
Motor V/Fvoltage P06.05~100.0 (relative to rated
P06.03 0.1% 0.0 during
value 3 voltage of motor)
downtime
Writable
Motor V/Ffrequency
P06.04 P06.06~P06.02 0.01Hz 0.00 during
value 2
downtime
Writable
Motor V/Fvoltage
P06.05 P06.07~P06.03 0.1% 0.0 during
value 2
downtime
Writable
Motor V/Ffrequency
P06.06 0.00 ~ P06.04 0.01Hz 0.00 during
value 1
downtime
Writable
Motor V/Fvoltage
P06.07 0.0 ~ P06.05 0.1% 0.0 during
value 1
downtime
Motor torque 0.0 ~30.0 (relative to rated
P06.08 0.1% 3.0 Read-write
compensation voltage of motor)
Motor torque
0.0 ~50.0 (relative to rated
P06.09 compensation 0.1% 50.0 Read-write
frequency of motor)
frequency cutoff
Motor oscillation
P06.10 suppression 0~1 1 0 Read-write
enabled
0: Invalid Writable
P06.11 Auto power save 1: Valid 1 0 during
downtime
0: No action
Writable
1: Always be valid
P06.12 AVR selection 1 1 during
2: Be invalid only during
downtime
deceleration

38
S1 Series Vector Inverter

P07 group Analog input and output


Change
Parameter Name Setting range Minimum unit Default
method
0: P07.03 & P07.12
Basic application
Analog input function
P07.01 1: P07.03 & P07.12 1 0 Read-write
level control
Advanced application

0: 0 mA - 20mA
1: 20 mA - 0mA
2: 4 mA - 20mA (alarm
in case that current input
breaks)
3: 20 mA - 4mA (alarm
in case that current input Writable
P07.02 Analog input 1 mode breaks) 1 6 during
4: 4 mA-20mA (no alarm downtime
in case that current input
break)
5: 20 mA -4mA (no alarm
in case that current input
break)
6: 0V~10V
P07.01 = 0 :
0: No function
P07.01 = 0 时: P07.01 = 0
1: Speed limit (torque Writable
Analog input1 1 时:0
P07.03 running mode) during
function selection
2: Torque offset
P07.01 = 1 时: P07.01 = 1
downtime 6
P00.01 时:0.00
P07.01 = 1 :
0.00~30.31

Parameter list
P07.04 Analog input 1 offset -100.0 ~ 100.0 0.1% 0.0 Read-write
Analog input 1
P07.05 0.000 ~20.000 0.001 1.000 Read-write
magnification times
Analog input 1 0: no negation
P07.06 1 0 Read-write
negation 1: negation
Analog input 1 filter
P07.07 0.00 ~ 10.00 0.01s 0.10 Read-write
time factor
Analog input 1 upper
P07.08 0.0 ~ 100.0 0.1% 100.0 Read-write
limit
Analog input 1 lower
P07.09 0.0 ~ P07.08 0.1% 0.0 Read-write
limit
Analog input 1 Displayed
P07.10 0.0 ~ 100.0 0.1% Read only
display value
Analog input 1 break Displayed
P07.11 0~1 1 Read only
indication value
P07.01 = 0: P07.01 = 0 P07.01 =
Writable
Analog input2 0: No function :1 0: 0
P07.12 during
function selection 1: speed limit(torque P07.01 = 1 P07.01 =
downtime
running mode) : P00.01 1: 0.00

39
S1 Series Vector Inverter

Change
Parameter Name Setting range Minimum unit Default
method
P07.01 =0 P07.01 =0
2: Torque offset Writable
Analog input :1 :0
P07.12 P07.01 =1: during
2function selection P07.01 =1 P07.01 =1
0.00~30.31 downtime
: P00.01 : 0.00
P07.13 Analog input 2offset -100.0 ~ 100.0 0.1% 0.0 Read-write
Analog input
P07.14 0.000 ~20.000 0.001 1.000 Read-write
2magnification times
Analog input 2 0: no negation
P07.15 1 0 Read-write
negation 1: negation
Analog input 2 filter
P07.16 0.00 ~ 10.00 0.01s 0.10 Read-write
factor
Analog input 2
P07.17 0.0 ~ 100.0 0.1% 100.0 Read-write
upper limit
Analog input 2 lower
P07.18 0.0 ~ P07.17 0.1% 0.0 Read-write
limit
Analog input
P07.19 0.0 ~ 100.0 0.1% 显示值 Read only
2display
0: P07.21 &
P07.22Basic
Analog output application
P07.20 1 0 Read-write
function level control 1: P07.21 &
P07.22Advanced
application
P07.20 =0:
0: No function
1: Output frequency
2: Set frequency
P07.20 =0
3: Torque current
:
4: Output current
AO1: 1
Analog output 5: Motor speed P07.20 =0
AO2: 2
P07.21 1function selection 6: Mains voltage :1
P07.20 =1 Read-write
P07.22 Analog output 7: Output voltage P07.20 =1
:
2function selection 8: AI1 : P00.01
AO1:
9: AI2
30.01
10: Actual length
AO2: 1.09
11: Specified count
value
P07.20 =1:
0.00~30.31
Analog output
P07.23 0.000 ~ 20.000 0.001 1.000 Read-write
1magnification times
Analog output
P07.24 0.000 ~ 20.000 0.001 1.000 Read-write
2magnification times
Analog output Displayed
P07.25 0.0 ~ 100.0 0.1% Read only
1display value
Analog output Displayed
P07.26 0.0 ~ 100.0 0.1% Read only
2display value

40
S1 Series Vector Inverter

P08 group Digital input and output


Change
Parameter Name Setting range Minimum unit Default
method
0: P08.02~P08.07
Digital input
Basic application
P08.01 function level 1 0 Read-write
1: P08.02~P08.07
control
Advanced application
P08.01 =0:
0: No function
1: Multi-speed select bit 0
2: Multi-speed select bit 1
Digital input
3: Multi-speed select bit 2
1terminal function
4: Multi-speed select bit 3 P08.01 =0
selection
5: Running : DI1: 6
Digital input
6: Forward running DI2: 7
2terminal function
7: Reverse running DI3: 10
selection
8: Three-wire mode DI4: 1
P08.02 Digital input
enabled DI5: 2
P08.03 3terminal function P08.01 =0
9: Forward/Reverse DI6: 13 Writable
P08.04 selection :1
10: Forward inching P08.01 =1 during
P08.05 Digital input P08.01 =1
11: Output increment (UP) : downtime
P08.06 4terminal function : P00.01
12:Output decrement DI1: 3.22
P08.07 selection
(DOWN) DI2: 3.23
Digital input
13: Inverter disabled DI3: 3.25
5terminal function
14: Fault reset DI4: 14.17
selection
15: Command switched to DI5: 14.18
Digital input
terminal DI6: 3.19
6terminal function
selection
16: Length count reset 6
17: Count value reset
18: external fault

Parameter list
P08.01 =1:
0.00 ~30.31
Digital input 1
P08.08 0: Invalid 1: Valid 1 0 Read-write
negation
Digital input 2
P08.09 0: Invalid 1: Valid 1 0 Read-write
negation
Digital input 3
P08.10 0: Invalid 1: Valid 1 0 Read-write
negation
Digital input 4
P08.11 0: Invalid 1: Valid 1 0 Read-write
negation
Digital input 5
P08.12 0: Invalid 1: Valid 1 0 Read-write
negation
Digital input 6
P08.13 0: Invalid 1: Valid 1 0 Read-write
negation
Three-wire 0: Two-wire mode Writable
P08.14 terminal mode 1: Three-wire mode1 1 0 during
control 2: Three-wire mode 2 downtime
Digital input
0: common port +24V Displayed
P08.15 common port 1 Read only
1:common port 0V value
selection

41
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
0: Disconnected with common
Digital input Displayed
P08.16 port 1 Read only
1status display value
1: Connected with common port
0: Disconnected with common
Digital input Displayed
P08.17 port 1 Read only
2status display value
1: Connected with common port
0: Disconnected with common
Digital input Displayed
P08.18 port 1 Read only
3status display value
1: Connected with common port
0: Disconnected with common
Digital input Displayed
P08.19 port 1 Read only
4status display value
1: Connected with common port
0: Disconnected with common
Digital input Displayed
P08.20 port 1 Read only
5status display value
1: Connected with common port
0: Disconnected with common
Displayed
P08.21 port 1 Read only
value
1: Connected with common port
0: Disconnected with common
Digital input
P08.22 port 1 0 Read-write
6status display
1: Connected with common port

P08.23 0.1 ~ 50.0 0.1kHz 10.0 Read-write

0: No central point
1: Central point is (P08.23)/2, the
frequency is negative when it is
Digital input less than center frequency
P08.24 1 0 Read-write
6mode selection 2: Central point is (P08.23)/2,
(P08.23)/2, the frequency is
positive when it is less than center
frequency
Digital input
6Frequency Displayed Read-write
P08.25 -100.0 ~ 100.0 0.1%
percentage of value
input pulse
P08.26 Standby — — — —
0: P08.28basic application
Relay function
P08.27 1: P08.28advanced application 1 0 Read-write
level control

P08.27 =0:
0: no function
1: Normal status of inverter
(relative to ERROR)
P08.27 = P08.27=
2: Inverter alarm (relative to
0: 1 0: 1
Relay function ALARM)
P08.28 P08.27 P08.27 Read-write
selection 3: Inverter is running
=1: =1:
4: Zero-speed running
P00.01 12.01
5: external fault
6: 100% load
7: Overload detection signal
8: Torque limited

42
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
9: Undervoltage lockout
reached
10: brake status
11: Frequency reached
P08.27 = P08.27 =
12: Length reached
0:1 0:1
relay function 13: Time reached
P08.28 P08.27 P08.27 Read-write
selection 14: Simple PLC cycle
=1: =1:
operation
P00.01 12.01
15: Simple PLC completion
indication
P08.27 = 1:
0.00 ~ 30.31
relay output 0: Invalid
P08.29 1 0 Read-write
negation 1: Valid
0: relay break
P08.30 relay status display 1 Displayed Read only
1: relay close
P08.31 Standby — — — —
Digital output 0: P08.33~P08.34 basic
P08.32 function level application 1 0 Read-write
control 1: P08.33~P08.34 advanced
application
P08.32 = 0:
0: No function
1: Inverter status (relative to
ERORR) 6
2: Inverter alarm (relative to
ALARM)

Parameter list
3: Inverter is running
P08.32 =
4: Zero-speed running
0:
5: external fault
DO1: 4
Digital output 1 6: 100% load P08.32 =
DO2: 3
terminal function 7: Overload detection signal 0: 1
P08.32 =
P08.33 selection 8: Torque limited P08.32
1: Read-write
P08.34 Digital output 9: Undervoltage lockout = 1:
DO1:
2terminal function reached P00.01
30.21
selection 10: brake status
DO2:
11: Frequency reached
30.26
12: Length reached
13: Time reached
14: Simple PLC cycle
operation
15: Simple PLC completion
indication
P08.32 = 1:
0.00 ~ 30.31

Digital output1 0: Invalid


P08.35 1 0 Read-write
negation 1: Valid
Digital output2 0: Invalid
P08.36 1 0 Read-write
negation 1: Valid

43
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
0: Common digital signal
Digital output2 mode
P08.37 output 1 0 Read-write
selection
1: Pulse output
Digital output2 Max
P08.38 frequency of output 0.1 ~ 50.0 0.1kHz 10.0 Read-write
frequency
Digital output1 status 0: Output low level0V Displayed
P08.39 1 Read only
display 1: Output high level24V value
0: Output low level 0V or
Digital output2 status Displayed
P08.40 P08.37 ≠ 0 1 Read only
display value
1: Output high level24V

44
S1 Series Vector Inverter

P09 groupSystem configuration parameter


Minimum Change
Parameter Name Setting range Default
unit method
Keypad display
P09.01 1.01 ~ 30.31 P00.01 30.01 Read-write
parameter selection
0: Fixed mode
Keypad cycle display
P09.02 1: Auto switching mode 1 0 Read-write
mode
2: Retain
0: Only display parameters
in shortcut menu
1: Display parameters in all
Parameter display
P09.03 menu 1 1 Read-write
selection
2: Only display the
parameters different from
factory default value
0: No action
1: Upload parameter of Writable
P09.04 Parameter copy inverter to keypad 1 0 during
2: Download parameter of downtime
keypad to inverter
0: 0.00
Initial value set in
1: Set parameter of keypad
P09.05 keypad control when 1Hz 0.00 Read-write
at last run
powering on
2:Multi-speed1
0: Not locked
Key lock function 1: All locked
P09.06
selection 2:Loced except for RUN
1 0 Read-write
6
andSTOP/RESET
0: Inching

Parameter list
Programmable key 1: Forward/reverse
P09.07 1 0 Read-write
function selection 2: Coast to stop
3: Retain
Whether the inverter Writable
0: Continuous running
P09.08 continues running after 1 0 during
1: Stop
the keypad is removed downtime
Whether default
0: Not return to default
parameter is uploaded
parameter
P09.09 if the passwords are 1 0 Read-write
1: Return to default
unlocked after being
parameter
powered on
P09.10 Standby — — — —
P09.11 User password 0~9999 1 0 Read-write
Appropriate
P09.12 Model parameter 0 ~ 255 1 Read only
for model
0: Not return to default
Writable
Return to default parameter
P09.13 1 0 during
parameter 1: Return to default
downtime
parameter
0: Auto running
P09.14 Fan running 1: Continuous running after 1 0 Read-write
being powered on

45
S1 Series Vector Inverter

P09 groupSystem configuration parameter


Minimum Change
Parameter Name Setting range Default
unit method
Carrier frequency
P09.15 1 ~ 15 1kHz 6 Read-write
setting
Carrier frequency auto
P09.16 0: Invalid 1: Valid 1 1 Read-write
adjustment enabled
0:slow mode
Writable
High and low speed (0.00~300.0Hz)
P09.17 1 0 during
switching 1:High-speed mode
downtime
(0.0~3000Hz)

46
S1 Series Vector Inverter

P10 group Auxiliary function


Minimum Change
Parameter Name Setting range Default
unit method
Electricitymeter: Displayed
P10.01 -999.9 to999.9 Mwh 0.1 Mwh Read only
Mwh value
Electricity meter: Displayed
P10.02 -99.9 to99.9 kwh 0.1kwh Read only
Kwh value
0.01(yuan/ 0.00(yuan/
P10.03 Price per Kwh 0.00~9.99(yuan/Mwh) Read-write
Mwh) Mwh)
P10.04 Electricmeter reset 0: Invalid 1 0 Read-write
Displayed
P10.05 Electric cost 1: Valid 1 yuan Read only
value
P10.06 standby 0~10000 — — —
Reset accumulative
P10.07 — 1 0 Read-write
running time
Writable
0: s
P10.08 Set running time unit 1 0 during
1: h
downtime
Writable
Set the upper limit of
P10.09 0 ~ 30000 1 1000 during
running time
downtime
P10.10 Set running time 0 ~ P10.09 1 0 Read-write
Set running time 0: Invalid Displayed
P10.11 1 Read only
reached 1: Valid value
P10.12 standby — — — — 6
Output frequency
P10.13 detection (FDT) 0.00Hz~P01.01 0.01Hz 0.00Hz Read-write

Parameter list
value
Output frequency
P10.14 detection (FDT) 0.00Hz~P10.13 0.01Hz 0.00Hz Read-write
width
Output frequency
P10.15 detection (FDT) 0~1 1 0 Read only
indication

47
S1 Series Vector Inverter

P11 group Fault record


Minimum Change
Parameter Name Setting range Default
unit method
P11.01 Failure record 1
P11.02 Failure record 2
P11.03 Failure record 3
P11.04 Failure record 4
P11.05 Failure record 5 Displayed
0~99 1 Read only
P11.06 Failure record 6 value
P11.07 Failure record 7
P11.08 Failure record 8
P11.09 Failure record 9
P11.10 Last failure record
Displayed
P11.11 Frequency at last failure -P01.01 ~ +P01.01 0.01Hz Read only
value
0.0 ~ 3 * rated current of Displayed
P11.12 Current at last failure 0.1A Read only
motor value
Mains voltage at last 220V:0 ~ 415 Displayed
P11.13 1V Read only
failure 380V:0 ~ 830 value
Input terminal status at Displayed
P11.14 0 ~ 255 1 Read only
last failure value
Output terminal status at Displayed
P11.15 0 ~ 255 1 Read only
last failure value
Displayed
P11.16 Current failure record 0 ~ 99 1 Read only
value

48
S1 Series Vector Inverter

P12 group Protection parameter


Minimum Change
Parameter Name Setting range Default
unit method
Normal inverter 0: With fault Displayed
P12.01 1 Read only
status 1: Without fault value
0: Disabled (when brake Writable
Overvoltage stall
P12.02 resistor is installed) 1 1 during
selection
1: Enabled downtime
220V:
Writable
Overvoltage stall 220V:350 ~ 370 370
P12.03 1V during
point 380V:750 ~ 780 380V:
downtime
750
Undervoltage 0: Invalid Displayed
P12.04 1 Read only
lockout reached 1: Valid value
Undervoltage fault
0: Not disabled
P12.05 at normal power 1 0 Read-write
1: Disabled
failure disabled
0: Coast to stop Writable
Stop mode at
P12.06 1: Decelerate to stop 1 0 during
power failure
downtime
0: Not used Writable
Dynamic braking
P12.07 1: Used 1 1 during
selection
downtime
Usage rate of
P12.08 0.0 ~ 100.0 0.1% 50.0 Read-write
dynamic braking
DC voltage
220V: 350 ~ 390 220V: 360
Writable 6
P12.09 point of dynamic 1V during
380V: 650 ~ 780 380V: 680
braking downtime

Parameter list
0: Invalid overload pre-alarm
Writable
Overload pre- detection
P12.10 1 1 during
alarm selection 1: Valid overload pre-alarm
downtime
detection
Overload pre-
P12.11 alarm detection 80.0 ~ 150.0 0.1% 130.0 Read-write
level
Overload pre-
P12.12 0.0 ~ 60.0 0.1s 5.0 Read-write
alarm detection
Overload 0: Invalid Displayed
P12.13 1 Read only
detection signal 1: Valid value
0: Common motor protection
Overload Writable
mode
P12.14 protection mode 1 1 during
1: Variable frequency motor
selection downtime
protection mode
Overload 0~ (rated current of inverter/
P12.15 1% 100 Read-write
protection factor rated current of motor)* 100
Writable
Set auto reset
P12.16 0 ~100 (auto reset times) 1 0 during
times
downtime
Writable
P12.17 Auto reset delay 2.0 ~ 20.0 0.1s/ 次 5.0 during
downtime

49
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Writable
0: Invalid
P12.18 Fault reset 1 0 during
1: Valid
downtime
Writable
Input phase
P12.19 0.0 ~ 3000.0 0.1s 0.1 during
loss fault delay
downtime
0: No
1: Output phase loss fault(Err05)
masking
Writable
Fault masking 2: 24V short-circuit fault(Err14)
P12.20 1 0 during
selection masking
downtime
3: Short-circuit fault to ground(Err17)
masking
4: External fault(Err18) masking
0: Invalid
P12.21 External fault 1: Valid 1 0 Read-write

Alarm 0: Disabled alarm information


P12.22 information display 1 1 Read-write
display control 1: Enabled alarm information display
0: Invalid Displayed
P12.23 Inverter alarm 1 Read only
1: Valid value
Operation at
Writable
low DC mains 0: Disabled
P12.24 1 0 during
voltage(380V 1: Enabled
downtime
Valid)
Forced DC 0: Invalid
P12.25 1 0 Read only
braking 1: Valid
Current limit 0.0 ~ 300.0 (relative to rated current Appropriate
P12.26 0.1% Read-write
factor of motor) for model
0: Not disabled
1: Stall protection function disabled
Current limit above base frequency Writable
P12.27 protection 2: Current limit protection function 1 0 during
control disabled during fast acceleration/ downtime
deceleration
3: Disabled

50
S1 Series Vector Inverter

P13 group User PID controller and sleep mode


Minimum Change
Parameter Name Setting range Default
unit method
P13.01 PIDreference setting 0.00 ~ 30.31 P00.01 0.00 Read-write
P13.02 PIDfeedback 0.00 ~ 30.31 P00.01 0.00 Read-write
PIDmain setting
P13.03 0.00 ~ 30.31 P00.01 0.00 Read-write
selection
PIDreference setting 0: Invalid
P13.04 1 0 Read-write
negation 1: Valid
PIDfeedback setting 0: Invalid
P13.05 1 0 Read-write
negation 1: Valid
PIDreference
P13.06 0.0 ~ 3000.0 0.1s 0.0 Read-write
conversion time
0: PIDdisabled
P13.07 PIDenabled 1 0 Read-write
1: PIDenabled
P13.08 PID proportional gain 0.000 ~ 32.000 0.001 1.000 Read-write
P13.09 PID integral gain 0.000 ~ 32.000 0.001 0.500 Read-write
P13.10 PID differential gain 0.000 ~ 32.000 0.001 0.000 Read-write
P13.11 PID upper limit 0.0 ~ 100.0 0.1% 100.0 Read-write
P13.12 PID lower limit -100.0 ~ +P13.11 0.1% 0.0 Read-write
PID output
P13.13 0.000 ~ 4.000 0.001 1.000 Read-write
magnification times
PID output target
P13.14 0.00 ~ 30.31 P00.01 0.00 Read-write
parameter
PID integral retain 0: Invalid
6
P13.15 1 0 Read-write
selection 1: Valid

Parameter list
0:P13.12 ≤ P13.22 ≤
P13.11, P13.12
P13.11
P13.16 Actuating range 1 0 Read-write
selection 1:-P13.11 ≤ P13.22 ≤
P13.11
PID output retain 0: Invalid
P13.17 1 0 Read only
selection 1: Valid
PIDmain setting Displayed
P13.18 -100.0 ~ +100.0 0.1% Read only
display value
PIDreference setting Displayed
P13.19 -100.0 ~ +100.0 0.1% Read only
display value
Displayed
P13.20 PIDfeedback display -100.0 ~ +100.0 0.1% Read only
value
Displayed
P13.21 PIDerror display -100.0 ~ +100.0 0.1% Read only
value
Displayed
P13.22 PID output display -100.0 ~ +100.0 0.1% Read only
value
P13.23 Standby — — — —
Writable
0: Disabled
P13.24 Sleep mode enabled 1 0 during
1: Enabled
downtime
Writable
Sleep channel
P13.25 0.00 ~ 30.31 P00.01 30.01 during
selection
downtime

51
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
0.00 ~ P01.01 (P13.25 =
Writable
30.01) 0.01Hz 0.00
P13.26 Sleep threshold value during
0.0 ~ 100.0 (P13.25 = 0.1% 0.0
downtime
other)
Writable
P13.27 Sleep delay time 0.0 ~ 3000.0 0.1s 30.0 during
downtime
Writable
0: Wakeup mode1
P13.28 Wakeup mode 1 0 during
1: Wakeup mode2
downtime
Writable
Wakeup feedback
P13.29 0.00 ~ 30.31 P00.01 13.20 during
channel selection
downtime
Writable
Wakeup threshold
P13.30 0.0 ~ 100.0 0.1% 0.0 during
value
downtime
Writable
P13.31 Wakeup delay time 0.0 ~ 3000.0 0.1s 0.0 during
downtime
P13.32 standby — — — —
P13.33 standby — — — —
P13.34 standby — — — —
Sleep status 0: Invalid Displayed
P13.35 1 Read only
indication 1: Valid value

52
S1 Series Vector Inverter

P14 group Multi-speed and PLC


Minimum Change
Parameter Name Setting range Default
unit method
P14.01 Multi-speed 1 0.01Hz 5.00 Read-write
P14.02 Multi-speed 2 0.01Hz 10.00 Read-write
P14.03 Multi-speed 3 0.01Hz 20.00 Read-write
P14.04 Multi-speed 4 0.01Hz 30.00 Read-write
P14.05 Multi-speed 5 0.01Hz 40.00 Read-write
P14.06 Multi-speed 6 0.01Hz 45.00 Read-write
P14.07 Multi-speed 7 0.01Hz 50.00 Read-write
P14.08 Multi-speed 8 0.01Hz 5.00 Read-write
-P01.01 ~ +P01.01
P14.09 Multi-speed 9 0.01Hz 10.00 Read-write
P14.10 Multi-speed 10 0.01Hz 20.00 Read-write
P14.11 Multi-speed 11 0.01Hz 30.00 Read-write
P14.12 Multi-speed 12 0.01Hz 40.00 Read-write
P14.13 Multi-speed 13 0.01Hz 45.00 Read-write
P14.14 Multi-speed 14 0.01Hz 50.00 Read-write
P14.15 Multi-speed 15 0.01Hz 50.00 Read-write
P14.16 Multi-speed 16 0.01Hz 50.00 Read-write
Multi-speed 0: Invalid Actual
P14.17 1 Read only
select bit 0 1: Valid value
Multi-speed 0: Invalid Actual
P14.18 1 Read only
select bit 1 1: Valid value
Multi-speed 0: Invalid Actual
6
P14.19 1 Read only
select bit 2 1: Valid value

Parameter list
Multi-speed 0: Invalid Actual
P14.20 1 Read only
select bit 3 1: Valid value
Multi-speed Actual
P14.21 1~16 1 Read only
select value value
P14.22 Standby — — — —
P14.23 Standby — — — —
SimplePLC 0: PLC uncompleted or
Displayed
P14.24 completion Not run 1 Read only
value
indication 1: PLC run completed
0: PLC has no cycle run Displayed
P14.25 PLC cycle run 1 Read only
1: PLC has cycle run value
0: No action
1: Stop after running one cycle Writable
PLC running
P14.26 2: keep final value after running a 1 0 during
mode
cycle downtime
3: Repeatafter running a cycle
PLC retentive 0: Not retentive Writable
P14.27 selection at 1: Retentive 1 1 during
stop downtime
0: Start from the frequency of
reference 1
1: Repeat running from the Writable
Repeat mode
P14.28 reference frequency at stop (or 1 0 during
of PLC
fault) downtime
2: Repeat running from the running
frequency at stop (or fault)
53
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Running time unit 0: s(s) Writable
P14.29 1: H (h) 1 0 during
selection of PLC downtime
Running time of
P14.30 0.0 ~ 3000.0 0.1 0.0 Read-write
PLC reference 1
0: Acceleration and deceleration
time1
1: Acceleration and deceleration
Acceleration /
time2
P14.31 deceleration time 1 0 Read-write
2: Acceleration and deceleration
of PLC reference1
time3
3: Acceleration and deceleration
time4
Running time of
P14.32 0.0 ~ 3000.0 0.1 0.0 Read-write
PLC reference 2
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2
P14.33 1 0 Read-write
of PLC reference 2: Acceleration and deceleration
2 time3
3: Acceleration and deceleration
time4
Running time of
P14.34 0.0 ~ 3000.0 0.1 0.0 Read-write
PLC reference 3
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2
P14.35 1 0 Read-write
of PLC reference 2: Acceleration and deceleration
3 time3
3: Acceleration and deceleration
time4
Running time of
P14.36 0.0 ~ 3000.0 0.1 0.0 Read-write
PLC reference 4
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2
P14.37 1 0 Read-write
of PLC reference 2: Acceleration and deceleration
4 time3
3: Acceleration and deceleration
time4
Running time of
P14.38 0.0 ~ 3000.0 0.1 0.0 Read-write
PLC reference 5
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2
P14.39 1 0 Read-write
of PLC reference 2: Acceleration and deceleration
5 time3
3: Acceleration and deceleration
time4

54
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Running time of Read-
P14.40 0.0 ~ 3000.0 0.1 0.0
PLC reference 6 write
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2 Read-
P14.41 1 0
of PLC reference 2: Acceleration and deceleration write
6 time3
3: Acceleration and deceleration
time4
Running time of Read-
P14.42 0.0 ~ 3000.0 0.1 0.0
PLC reference 7 write
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2 Read-
P14.43 1 0
of PLC reference 2: Acceleration and deceleration write
7 time3
3: Acceleration and deceleration
time4
Running time of Read-
P14.44 0.0 ~ 3000.0 0.1 0.0
PLC reference 8 write
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration 6
deceleration time time2 Read-
P14.45 1 0
of PLC reference 2: Acceleration and deceleration write

Parameter list
8 time3
3: Acceleration and deceleration
time4
Running time of Read-
P14.46 0.0 ~ 3000.0 0.1 0.0
PLC reference 9 write
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2 Read-
P14.47 1 0
of PLC reference 2: Acceleration and deceleration write
9 time3
3: Acceleration and deceleration
time4
Running time of Read-
P14.48 0.0 ~ 3000.0 0.1 0.0
PLC reference 10 write
0: Acceleration and deceleration
time1
Acceleration / 1: Acceleration and deceleration
deceleration time time2 Read-
P14.49 1 0
of PLC reference 2: Acceleration and deceleration write
10 time3
3: Acceleration and deceleration
time4
Running time of Read-
P14.50 0.0 ~ 3000.0 0.1 0.0
PLC reference 11 write

55
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Acceleration / 0: Acceleration and deceleration time1
deceleration time 1: Acceleration and deceleration time2 Read-
P14.51 1 0
of PLC reference 2: Acceleration and deceleration time3 write
11 3: Acceleration and deceleration time4
Running time of Read-
P14.52 0.0 ~ 3000.0 0.1 0.0
PLC reference 12 write
Acceleration / 0: Acceleration and deceleration time1
deceleration time 1: Acceleration and deceleration time2 Read-
P14.53 1 0
of PLC reference 2: Acceleration and deceleration time3 write
12 3: Acceleration and deceleration time4
Running time of Read-
P14.54 0.0 ~ 3000.0 0.1 0.0
PLC reference 13 write
Acceleration / 0: Acceleration and deceleration time1
deceleration time 1: Acceleration and deceleration time2 Read-
P14.55 1 0
of PLC reference 2: Acceleration and deceleration time3 write
13 3: Acceleration and deceleration time4
Running time of Read-
P14.56 0.0 ~ 3000.0 0.1 0.0
PLC reference 14 write
Acceleration / 0: Acceleration and deceleration time1
deceleration time 1: Acceleration and deceleration time2 Read-
P14.57 1 0
of PLC reference 2: Acceleration and deceleration time3 write
14 3: Acceleration and deceleration time4
Running time of Read-
P14.58 0.0 ~ 3000.0 0.1 0.0
PLC reference 15 write
Acceleration / 0: Acceleration and deceleration time1
deceleration time 1: Acceleration and deceleration time2 Read-
P14.59 1 0
of PLC reference 2: Acceleration and deceleration time3 write
15 3: Acceleration and deceleration time4
Running time of Read-
P14.60 0.0 ~ 3000.0 0.1 0.0
PLC reference 16 write
Acceleration / 0: Acceleration and deceleration time1
deceleration time 1: Acceleration and deceleration time2 Read-
P14.61 1 0
of PLC reference 2: Acceleration and deceleration time3 write
16 3: Acceleration and deceleration time4

56
S1 Series Vector Inverter

P15 group Wobble frequency, fix length and count


Minimum Change
Parameter Name Setting range Default
unit method
Writable
Wobble frequency 0: Disabled
P15.01 1 0 during
function enabled 1: Enabled
downtime
P15.02 Center frequency 0.00 ~ P01.01 0.01Hz 0.00 Read-write
P15.03 Preset frequency 0.00 ~ P01.01 0.01Hz 0.00 Read-write
Waiting time of
P15.04 0.0 ~ 3000.0 0.1s 0.0 Read-write
preset frequency
0.0 ~50.0 (relative to
P15.05 Set amplitude center frequency of wobble 0.1% 0.0 Read-write
frequency)
Set hopping 0.0 ~50.0(relative to amplitude
P15.06 0.1% 0.0 Read-write
frequency of motor wobble frequency)
P15.07 Period 0.1 ~ 1000.0 0.1s 10.0 Read-write
Triangular wave 0.0 ~100.0 (relative to period
P15.08 0.1% 50.0 Read-write
rising time of wobble frequency)
0: Invalid
P15.09 Suspend 1 0 Read-write
1: Valid
P15.10 Standby — — — —
Writable
Upper limit of set
P15.11 0 ~ 30000 1 1000 during
length
downtime
P15.12 Set length 0 ~ P15.11 1 1000 Read-write 6
Upper limit of Writable
P15.13 number of pulses 0.1 ~ 3000.0 0.1 100.0 during

Parameter list
per unit length downtime
Number of pulses
P15.14 0.1 ~ P15.13 0.1 100.0 Read-write
per unit length
Displayed
P15.15 Actual length 0 ~ 30000 1 Read only
value
Displayed
P15.16 Length reached 0: Not reached 1:Reached 1 Read only
value
Length count 0: Invalid
P15.17 1 0 Read-write
reset 1: Valid
P15.18 Standby — — — —
Writable
Upper limit of set
P15.19 1 ~ 30000 1 1000 during
count value
downtime
P15.20 Set count value 1 ~ P15.19 1 1000 Read-write
Designated count
P15.21 1 ~ P15.20 1 1000 Read-write
value
0: Invalid
P15.22 Count value reset 1 0 Read-write
1: Valid
Set count value 0: Not reached Displayed
P15.23 1 Read only
reached 1: Reached value
Designated count 0: Not reached Displayed
P15.24 1 Read only
value reached 1: Reached value

57
S1 Series Vector Inverter

P16 group Communication configuration


Minimum Change
Parameter Name Setting range Default
unit method
0: Modbus
P16.01 Communicationprotocol 1: Retain 1 0 Read-write

P16.02 Local address 1 ~ 247 1 1 Read-write


0:2.4KBPS
1:4.8KBPS
2:9.6KBPS
P16.03 Baud rate 1 3 Read-write
3:19.2KBPS
4:38.4KBPS
5:57.6KBPS
0: 1-8-1, no check
1: 1-8-2, no check
Communication
P16.04 2: 1-8-1, odd parity check 1 1 Read-write
configuration
3: 1-8-1, even parity
check
P16.05 Response delay 0 ~ 250 1ms 2 Read-write

58
S1 Series Vector Inverter

P17 group Braking logic control module


Minimum Change
Parameter Name Setting range Default
unit method
Writable
0: Disabled
P17.01 Brake logic enabled 1 0 during
1: Enabled
downtime
Current threshold
P17.02 0 ~ 200 1% 50 Read-write
value at brake remove
Currentthresholdat
P17.03 0 ~ 200 1% 10 Read-write
brake application
Frequency threshold
P17.04 0.00 ~ 20.00 0.01Hz 1.00 Read-write
value at brake remove
Frequency threshold
P17.05 value at brake 0.00 ~ 20.00 0.01Hz 2.00 Read-write
application
Hold time of running
P17.06 frequency before 0.0 ~ 25.0 0.1s 1.0 Read-write
brake remove
Hold time of running
P17.07 frequency after brake 0.0 ~ 25.0 0.1s 1.0 Read-write
remove
Brake logic module 0: Application Displayed
P17.08 1 Read only
outputstatus display 1: Remove value

Parameter list

59
S1 Series Vector Inverter

P18 group Programmable logic module and binary operation module


Minimum Change
Parameter Name Setting range Default
unit method
Logic module 1 Input 1 Writable during
P18.01 0.00 ~ 30.31 P00.01 0.00
selection downtime
Logic module 1 Input 1 0: Invalid
P18.02 1 0 Read-write
negationcontrol 1: Valid
Logic module 1 Input 2 Writable during
P18.03 0.00 ~ 30.31 P00.01 0.00
selection downtime
Logic module 1 Input 2 0: Invalid
P18.04 1 0 Read-write
negationcontrol 1: Valid
Logic module 1 output 0: Invalid
P18.05 1 0 Read-write
negation control 1: Valid
Logic module 1 output
P18.06 -3000.0 ~ +3000.0 0.1s 0.0 Read-write
delay
Logic module 1 output Writable during
P18.07 0.00 ~ 30.31 P00.01 0.00
function selection downtime
Logic module 2 Input 1 Writable during
P18.08 0.00 ~ 30.31 P00.01 0.00
selection downtime

Logic module 2 Input 1 0: Invalid


P18.09 1 0 Read-write
negationcontrol 1: Valid

Logic module 2 Input 2 Writable during


P18.10 0.00 ~ 30.31 P00.01 0.00
selection downtime
Logic module 2 Input 2 0: Invalid
P18.11 1 0 Read-write
negationcontrol 1: Valid
Logic module 2 output 0: Invalid
P18.12 1 0 Read-write
negation control 1: Valid
Logic module 2 output
P18.13 -3000.0 ~ +3000.0 0.1s 0.0 Read-write
delay
Logic module 2 output Writable during
P18.14 0.00 ~ 30.31 P00.01 0.00
function selection downtime
Unit’s digit input of binary 0: Invalid
P18.15 1 0 Read-write
system operation module 1: Valid
Ten’s digit input of binary 0: Invalid
P18.16 1 0 Read-write
system operation module 1: Valid
Hundred’s digit input of
0: Invalid
P18.17 binary system operation 1 0 Read-write
1: Valid
module
Result offset of binary
P18.18 0-248 1 0 Read-write
system operation module
Function selection of binary Writable during
P18.19 0.00 ~ 30.31 P00.01 0.00
system operation module downtime
Logic module 1 output 0: Output0 Displayed
P18.20 1 Read only
display 1: Output 1 value
Logic module 2 output 0: Output0 Displayed
P18.21 1 Read only
display 1: Output 1 value
Binary system operation Displayed
P18.22 0~255 1 Read only
module output display value

60
S1 Series Vector Inverter

P19 group Programmable comparison module and operation module


Minimum Change
Parameter Name Setting range Default
unit method
Comparison module1input Writable during
P19.01 0.00 ~ 30.31 P00.01 0.00
selection downtime
Comparison
P19.02 0.0 ~ 100.0 0.1% 0.0 Read-write
module1threshold setting
Comparison
P19.03 0.0 ~ 25.0 0.1% 0.0 Read-write
module1hysteresis setting
Comparison module1output 0: Invalid
P19.04 1 0 Read-write
negation 1: Valid
Comparison module1 output Writable during
P19.05 0.00 ~ 30.31 P00.01 0.00
function selection downtime
Comparison module2input Writable during
P19.06 0.00 ~ 30.31 P00.01 0.00
selection downtime
Comparison
P19.07 0.0 ~ 100.0 0.1% 0.0 Read-write
module2threshold setting
Comparison
P19.08 0.0 ~ 25.0 0.1% 0.0 Read-write
module2hysteresis setting
Comparison module2output 0: Invalid
P19.09 1 0 Read-write
negation 1: Valid
Comparison module2output Writable during
P19.10 0.00 ~ 30.31 P00.01 0.00
function selection downtime
Operation module1input Writable during
P19.11 0.00 ~ 30.31 P00.01 0.00
1selection downtime
6
Operation module1input Writable during
P19.12 0.00 ~ 30.31 P00.01 0.00
2selection downtime

Parameter list
Operation module1input
P19.13 -4.000 ~ +4.000 0.001 1.000 Read-write
1magnification times
Operation module1input
P19.14 -4.000 ~ +4.000 0.001 1.000 Read-write
2magnification times
0: Input selection 1
1: Input selection 2
2: Addition
3: Subtraction
4: Multiplication
Operation module1operation
P19.15 5: Division 1 0 Read-write
mode selection
6: Time constant
7: Linear output
8: Absolute value
9: Exponentiation
operator
Operation module1controls
P19.16 0.00 ~ 99.99 0.01 0.00 Read-write
parameter
Operation module1output Writable during
P19.17 0.00 ~ 30.31 P00.01 0.00
function selection downtime
Operation module2Input 1 Writable during
P19.18 0.00 ~ 30.31 P00.01 0.00
selection downtime
Operation module2Input 2 Writable during
P19.19 0.00 ~ 30.31 P00.01 0.00
selection downtime
Operation module2Input
P19.20 -4.000 ~ +4.000 0.001 1.000 Read-write
1magnification times

61
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Operation module2 Input 2
P19.21 -4.000 ~ +4.000 0.001 1.000 Read-write
magnification times
0: Input selection1
1: Input selection2
2: Addition
3: Subtraction
4: Multiplication
Operation module2 operation
P19.22 5: Division 1 0 Read-write
mode selection
6: Time constant
7: Linear output
8: Absolute value
9: Exponentiation
operator
Operation module2 controls
P19.23 0.00 ~ 99.99 0.01 0.00 Read-write
parameter
Writable
Operation module2 output
P19.24 0.00 ~ 30.31 P00.01 0.00 during
function selection
downtime
Writable
Operation module3 Input 1
P19.25 0.00 ~ 30.31 P00.01 0.00 during
selection
downtime
Writable
Operation module3 Input2
P19.26 0.00 ~ 30.31 P00.01 0.00 during
selection
downtime
Operation module3 Input 1
P19.27 -4.000 ~ +4.000 0.001 1.000 Read-write
magnification times
Operation module3Input 2
P19.28 -4.000 ~ +4.000 0.001 1.000 Read-write
magnification times
0: Input selection 1
1: Input selection 2
2: Addition
3: Subtraction
4: Multiplication
Operation module3 operation
P19.29 5: Division 1 0 Read-write
mode selection
6: Time constant
7: Linear output
8: Absolute value
9: Exponentiation
operator
Operation module3 controls
P19.30 0.00 ~ 99.99 0.01 0.00 Read-write
parameter
Writable
Operation module3 output
P19.31 0.00 ~ 30.31 P00.01 0.00 during
function selection
downtime
Comparison module1 output 0: Output 0 Displayed
P19.32 1 Read only
display 1: Output 1 value
Comparison module2 output 0: Output 0 Displayed
P19.33 1 Read only
display 1: Output 1 value
Operation module1 output Displayed
P19.34 -100.0 ~ +100.0 0.1% Read only
display value

62
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
Operation module2 output Displayed
P19.35 -100.0 ~ +100.0 0.1% Read only
display value
Operation module3 output Displayed
P19.36 -100.0 ~ +100.0 0.1% Read only
display value
P19.37 Customized bit variable1 0~1 1 0 Read-write
P19.38 Customized bit variable2 0~1 1 0 Read-write
P19.39 Customized bit variable3 0~1 1 0 Read-write
P19.40 Customized bit variable4 0~1 1 0 Read-write
P19.41 Customized bit variable5 0~1 1 0 Read-write
P19.42 Customized word variable1 -300.0 ~ +300.0 0.1% 0.0 Read-write
P19.43 Customized word variable2 -300.0 ~ +300.0 0.1% 0.0 Read-write
P19.44 Customized word variable3 -300.0 ~ +300.0 0.1% 0.0 Read-write
P19.45 Customized word variable4 -300.0 ~ +300.0 0.1% 0.0 Read-write
P19.46 Customized word variable5 -300.0 ~ +300.0 0.1% 0.0 Read-write

Parameter list

63
S1 Series Vector Inverter

P30 group Display parameter


Minimum Change
Parameter Name Setting range Default
unit method
Displayed
P30.01 Output frequency -P01.01 ~ +P01.01 0.01Hz Read only
value
Displayed
P30.02 Output voltage 0V ~ rated voltage of inverter 1V Read only
value
220V:0 ~ 415 Displayed
P30.03 Mains voltage 1V Read only
380V:0 ~ 830 value
Displayed
P30.04 Output current 0.0A~3* rated current of motor 0.1A Read only
value
Displayed
P30.05 Torque current ±3 * rated current of motor 0.1A Read only
value
Displayed
P30.06 Flux current 0.0 ~ 3 * rated current of motor 0.1A Read only
value
0.0~300.0(relative to rated Displayed
P30.07 Output power 0.1% Read only
power of motor) value
Displayed
P30.08 Motor speed ± rated speed of motor 1RPM Read only
value
Load speed
P30.09 proportionality 0.1 ~ 1000.0 0.1% 100.0 Read-write
coefficient
Displayed
P30.10 Load speed -180000 ~ +180000 1 Read only
value
Running time record: 0.001 Displayed
P30.11 0.000 ~ 9.364 Read only
y. d 年.天 value
Running time record: 0.01 Displayed
P30.12 0.00 ~ 23.59 Read only
h. m 时.分 value
Displayed
P30.13 Heatsink temperature -25 ~ 127 1℃ Read only
value
IGBT temperature Displayed
P30.14 -25 ~ 200 1℃ Read only
threshold value
Status word of Displayed
P30.15 0 ~ 65535 1 Read only
inverter value
0: Invalid Displayed
P30.16 100% load 1 Read only
1: Valid value
P30.17 Standby — — — —
Frequency
P30.18 reached(FAR) 0.00 ~ P01.01 0.01Hz 2.50 Read-write
Detection width
0: Invalid Displayed
P30.19 Frequency reached 1 Read only
1: Valid value
P30.20 Zero-speed threshold 0.00 ~ P01.01 0.01Hz 0.50 Read-write
0: Invalid Displayed
P30.21 Zero-speed running 1 Read only
1: Valid value
P30.22 Standby — — — —
P30.23 Standby — — — —

P30.24 Standby — — — —

P30.25 Standby — — — —

64
S1 Series Vector Inverter

Minimum Change
Parameter Name Setting range Default
unit method
0: Invalid Displayed
P30.26 The inverter is running 1 Read only
1: Valid value
0: Stop command comes
Start/Stop command into force Displayed
P30.27 1 Read only
comes into force 1: Start command comes value
into force
0: Invalid
Reverse rotation Displayed
P30.28 1: Reverse rotation of 1 Read only
command value
inverter
P30.29 Standby — — — —
Control MCU software Displayed
P30.30 0.00 ~ 327.67 0.01 Read only
version number value
Power MCU software Displayed
P30.31 0.00 ~ 327.67 0.01 Read only
version number value

Parameter list

65
S1 Series Vector Inverter

7. Faults and diagnose

When a fault occurs during running, please see the fault information, alarm type, cause
and countermeasure provided in this chapter. Do not disassemble or modify the inverter
without authorization. Please contract our company or our agent in time if you need any
technical support.

66
S1 Series Vector Inverter

7.1 Fault phenomenon and countermeasures


When a fault occurs during running, LED display tube will show the corresponding fault
code, the inverter will stop output. S1 series inverter may show the fault types as shown in
Table7-1 and its fault codes ranges from Err01 to Err43.
Table7-1 Fault phenomenon and countermeasure
Fault code Fault type and action Possible causes Countermeasure
Output short circuit Inspect motor cable
Too short acceleration/ Properly prolong acceleration/
Overcurrent deceleration time deceleration time
Lock IGBT, reset it within After the inverter stops
10s after overcurrent Start mode P03.06, Start after
suddenly, restart the
fault is solved rotate speed tracking
rotating motor
Internal faults Seek for service
Inspect and properly adjust
Too high grid voltage
grid voltage
Overvoltage The load should not be
Lock IGBT, reset Sudden change in load
removed as far as possible
it within 1s after
overvoltage fault is Properly prolong deceleration
Too short deceleration
solved time or install a braking
time
resistor
Internal faults Seek for service
Undervoltage Inspect and properly adjust
Too low grid voltage
Lock IGBT, it grid voltage
automatically resets The inverter is powered off Normal display, no fault record
after recovery point is
reached Internal faults Seek for service
Phase loss of on input
side
7
Stop the inverter in stop Inspect intput voltage and
Phase loss on input side
mode, lock IGBT, reset wiring
Faults and diagnosis

it within 1s after the fault


is solved

Phase loss on output Inspect output voltage and


Phase loss on input side
side wiring
Stop the inverter in stop
mode, lock IGBT, reset
it within 1s after the fault Internal faults Seek for service
is solved

Short circuit of braking Short circuit of braking Check the wiring of braking
unit resistor resistor
Lock IGBT, reset it
within 10s after the fault
Internal faults Seek for service
is solved

Too high ambient Decrease ambient


Heatsink overheat 1 temperature temperature
LockIGBT, it resets Blocked air duct Clear up air duct
within 1s after recovery
point is reached Damaged fan Replace fan
Internal faults Seek for service
67
S1 Series Vector Inverter

Fault code Fault type and action Possible causes Countermeasure


Heatsink overheat 2 Too high ambient
Decrease ambient temperature
45kW and above temperature
model Blocked air duct Clear up air duct
Lock IGBT, it resets Damaged fan Replace fan
within 1s after recovery
point is reached Internal faults Seek for service
Too high carrier frequency Decrease carrier frequency
IGBT overheat
Frequently accelerate/ Increase the capacity, prolong
Lock IGBT, it resets
decelerate in case of heavy acceleration and deceleration
within 1s after recovery
load time
point is reached
Internal faults Seek for service
Properly set V/F curve and
Improper V/F curve
Motor overload torque compensation
Stop the inverter in Too low grid voltage Inspect grid voltage
stop mode,lock IGBT, Motor stalling or too large
it resets within 1s after Inspect the load
sudden change in load
the fault is solved Improper motor overload Properly set motor overload
protection factor protection factor
AI1break(current
mode)
Stop the inverter in AI1 input current is lower
Inspect AI1 input device
stop mode, lock IGBT, than4mA
it resets within 1s after
the fault is solved
24V overload at user
terminal
Stop the inverter 24V power supply and Inspect the external circuit of
in stop mode,lock DO1 output are greater DO output, inspect whether
IGBT, it resets within than 50mA 24V power supply is short
1s after the fault is
solved
Abnormal copy Abnormal copy of keypad
Power on again
It resets within 1s parameter
after the fault is Keypad EEPROM is Upload parameter once and
solved empty then download
Internal faults Seek for service
Motor capacity does not
Replace the inverter model
match with that of inverter
Parameter
Improper rated parameter Set motor parameter
identification fault
It resets within 1s of motor according to its nameplate
after the fault is Wait until parameter
Press “Stop” before
solved identification automatically
identification completes
completes
Short circuit to ground on Inspect wiring and motor
Short circuit to ground output side insulation
on input side when
being powered on Current detection fault Seek for service

68
S1 Series Vector Inverter

Fault code Fault type and action Possible causes Countermeasure


External fault
Error action is input
Stop the inverter in stop
through DI terminal Inspect external devices
mode, it resets within 1s
externally
after the fault is solved
Valid data cannot be
Watch dog overflow of received within 2s while Inspect communication wire and
remote communication remote communication upstream control unit
is normal
Wrong read and write Press “STOP” to reset, Seek
EEPROMread-write fault control parameter for service
Internal faults Seek for service
Inspect whether the same
function assignment parameter
Parameter assignment
is set. Change it and then press
fault Parameter assignment
“STOP” to reset.
It resets within 1s after fault
Recover default parameter and
the fault is solved
then reset manually.

Current detection fault


LockIGBT, cannot be Internal faults Seek for service
reset
DSP software overflow software overflow Power on again
Lock IGBT, cannot be
reset Internal faults Seek for service

MCUcannot receive Software fault Seek for service


data from DSP
Lock IGBT, cannot be MCU or DSPdamage Seek for service
reset

MCU receives error data External disturbance Inspect wiring 7


fromDSP
Lock IGBT, cannot be
Faults and diagnosis

reset Internal faults Seek for service

Overcurrent during
powering on
Detection circuit fault Seek for service
Lock IGBT, cannot be
reset
Error model
Lock IGBT, cannot be Internal faults Seek for service
reset
Inner thermocouple fails
to work
IGBT module damage Seek for service
Lock IGBT, cannot be
reset
Program fault Software fault Seek for service
Lock IGBT, cannot be
reset MCUorDSPdamage Seek for service
Watch Dog fault Software fault Seek for service
Lock IGBT, cannot be
reset MCUorDSPdamage Seek for service

69
S1 Series Vector Inverter

Fault code Fault type and action Possible causes Countermeasure


EEPROM inner fault MCU orDSP damage Seek for service
Lock IGBT, cannot be
reset EEPROM damage Seek for service

The above faults can be divided into the following categories:

Category Fault information Comment

Err03(undervoltage) cannot be reset manually but


Automatic recovery Err03 automatically recover according to actual voltage
level

Unrecoverable ≥Err30 Theses faults cannot be reset manually

When an EEPROM read and write fault (Err20)


EEPROM read and
Err20 occurs, upload default parameter, and then power
write fault
on to reset.

Common fault1 Err01, Err06 It resets within 10s after the fault is solved

Common fault2 Other faults It resets within 1s after the fault is solved

√ Err03,recoverable, undervoltage point and recovery point vary with voltage level.
√ Err03,start to save power failure parameters
√ Err03,saved as a fault record only during running.
√ Priority of fault:Err03 >unrecoverable faults> Err20 >the faults which may impact
common faults>common faults.
√ The faults which may impact common faultsinclude Err15, Err40, Err41 andErr43.
√ Common faults refer to < Err30 except for Err03, Err20.
√ At the same priority level, the fault triggered earlier is superior to that triggered
latter.

70
S1 Series Vector Inverter

7.2 Warning phenomenon and countermeasures


When the inverter's parameters are within the set alarm range, it does not stop andthe
keypad sends corresponding alarm code at this time. The keypad shows alarm code which
flashes for 3s, and then switches to parameter content selected with function codeP09.01
(output frequency in default) , 3s later, it switches to alarm code, and so on(as long as the
alarm condition is not eliminated). You can select whether to display alarm information with
function code P12.22. S1 series inverter can display the alarm types as shown in Table7-2.

Table7-2 Warning phenomenon and countermeasures

Alarm code Description Possible cause Countermeasures

Inspect motor wiring

Properly prolong
Output current has been
acceleration /deceleration
Current limit function limited: P05.12*P04.07
ALA01 time
enabled (motor 1) P05.12*P04.19
(motor 2) Start mode is selected as
P03.06Start after rotate
speed tracking

Output current excesses


Motor overload is P04.07 Increase the capacity of
ALA02
accumulated (P04.19) until overload inverter and motor
protection of motor

Too high ambient Decrease ambient


temperature temperature
Heatsink overheat
ALA03
pre-alarm Blocked air duct Clear up air duct

Damaged fan Replace fan 7


Adjust parameter setting
Frequently accelerate/
Faults and diagnosis
ALA04 IGBToverheat Increase the capacity of
decelerate
inverter

P12.24 is set as valid,


Operation at low showing
ALA05 —
mains DC voltage 380V machine works at
220Vpower supply

ALA06 Retain — —

The inverter exits or cancels


ALA07 Sleep state The inverter is in sleep state sleep mode, and then the
alarm cancels

ALA08 Retain — —

ALA09 Retain — —

71
S1 Series Vector Inverter

72
S1 Series Vector Inverter

Appendix IBraking resistor selection


When the inverter drives the motor to reverse or decelerate to stop, energy feedback of
motor may cause the mains DC voltage of inverter to increase. To prevent the inverter
from stop due to overvoltage protection, the inverter automatically switches to dynamic
braking circuit before the mains DC voltage reaches to the protection voltage and releases
redundant energy in the form of heat energy through braking resistor, thus control the
continuous increase of voltage and ensure the normal operation of inverter.
① Resistance selection of braking resistor
During braking, almost all recovered energy from motor is consumed by braking
resistor. According to the formula:U×U/R=Pb

U — Braking resistance during stable braking(it varies with system voltage value,
380VAC
System voltage value generally takes 700V)
Pb — braking power

② Power selection of braking resistor


Theoretically, the power of braking resistor is as same as that of braking power while
the power of braking resistor is generally de-rated in fact.
According to the formula: λ×Pr=Pb×ED%

λ— derating factor, generally taking70% Pr — power of braking resistor


ED% — usage rate(the ratio of energy recovering process to the whole working
process) , generally taking 10%.

Please refer to the table below:


Winding Centrifugal Accident braking Common
Load type Elevator
machine machine load occasion
Usage rate 20%~30% 20%~30% 50%~60% 5% 10%
8
③ Braking resistor selection table
Braking resistor selection

Resistance of
Power of braking
Model braking resistor
resistor (kW) (Ω)
S1-2S0004-B ≥ 0.48 ≥ 350
S1-2S0007-B ≥ 0.9 ≥ 192
S1-2S0015-B ≥ 1.8 ≥ 96
S1-2S0022-B ≥ 2.6 ≥ 65
S1-4T0007-B ≥ 0.9 ≥ 556
S1-4T0015-B ≥ 1.3 ≥ 326
S1-4T0022-B ≥ 1.8 ≥ 222
S1-4T0040-B ≥ 2.6 ≥ 155

73
S1 Series Vector Inverter

Appendix II MODBUS protocol


1.Wiring of communication interface
S1 series inverter provides users with RS485 serial communication interface: 485
protocol communication terminal A(RS485 + ) , B(RS485 - ), which can be used
simultaneously. Control system single host/ singe slave or single host /multi slave
can be configured while the inverter can only be used as a slave.
As shown in the figure below

A RS485+

B RS485

PE
S1
Upper
上位机
computer

Wiring diagram of communication interface

2.Communication mode
◆ S1 series inverter uses Modbus protocol andRTU message transmission mode and
support common read and writing of register command. Its frame format is as shown
in the figure below:

MODBUSData frame

start (at least 3.5 idle characters) slave address Command code data check code end (at least 3.5 idle characters)

◆ ModbusRTU uses “big-endian” code to represent address and data item(except


CRC, which belongs to “little- endian”). During transmission, low bytes follow high
bytes.
◆ InRTU mode, the frame is defined by frame header and end through the interval of at
least 3.5 byte time.

2.1 Slave address


S1 series inverter can only be used as a slave during networking. The address can
be set through function code P16.02, the set range is 1~247 and default is 1.

2.2 Command code


Modbus’s functions are mainly reading and writing parameters,operation
requirements vary with the command codes. S1 series inverter’s ModbusRTU
protocol supports the operations shown in the table below.

74
S1 Series Vector Inverter

Command code
(represented Meaning
with 16 system)
03H Read and write message from several registers
06H Change message from single register, unless the inverter is powered off
Change message from several registers, unless the inverter is powered
10H
off
Read, write and change message from several registers, unless the
17H
inverter is powered off

2. 3 D ata
S1 series inverter’s Modbus communication data is divided into three categories,
register address, register number (or byte number) and specific value of register.
Data is in 16 system format(except byte number during writing) and is represented
with two bytes, low bytes following high bytes.
MODBUS addressing
◆ Mapping relationship between parameter function code and inner
Modbus register of S1 series inverter.
S1 series inverter’s parameter function code is mapped into Modbus reading
and writing register. The rules: parameter function code×100 =M×256+N+1,
represented in decimal system, of which0≤N≤255
Register address High byte low byte
For example:
Calculate Modbus register address of parameterP04.01
4.01×100 = 1×256+144+1, and thenM = 1, N = 144, convert to 16 system and
gain high byte 01H and low byte90H, that is, register address is0190H, Modbus
register address of each parameter is shown in each group of menu table.

The decimal point in the number of function code is removed, the


resulting number is subtracted by 1 and then converted to a digital
tips in 16 system to gain register address. For example,function code
P04.01, the decimal point is removed, the result 401 is subtracted by 1
and then the result 400 is converted to 0190H in 16 system.

9
◆ Corresponding relationship between parameter function code
and standard MODBUS address
MODBUS protocol

Some upper controller only supports standard MODBUS addressing, the


relationship between parameter function code and it:
Standard MODBUS address = parameter function code ×100+40000

For example:
Corresponding MODBUS address of parameter P04.01: 4.01×100+40000=40401

75
S1 Series Vector Inverter

2 .4 Check code
CRC-16 is used for data check, content of entire message is checked, the high byte
and low byte of checksum should be sent after exchange.
Please see the following example for specific CRC check.
CRC check
CRC check is 16-bit Cyclic redundancy check, standard CRC-16 multi nominal
x16+x15+x2+1 is used. Add 16-bit CRC to a message and send LSB at first, CRC is
calculated through all bytes in the frame.
//High-Order Byte Table
const unsigned char auchCRCHi[] = {
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1,
0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1,
0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1,
0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1,
0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40
};

//Low-Order Byte Table

76
S1 Series Vector Inverter

const char auchCRCLo[] = {


0x00, 0xC0, 0xC1, 0x01, 0xC3, 0x03, 0x02, 0xC2, 0xC6, 0x06,
0x07, 0xC7, 0x05, 0xC5, 0xC4, 0x04, 0xCC, 0x0C, 0x0D, 0xCD,
0x0F, 0xCF, 0xCE, 0x0E, 0x0A, 0xCA, 0xCB, 0x0B, 0xC9, 0x09,
0x08, 0xC8, 0xD8, 0x18, 0x19, 0xD9, 0x1B, 0xDB, 0xDA, 0x1A,
0x1E, 0xDE, 0xDF, 0x1F, 0xDD, 0x1D, 0x1C, 0xDC, 0x14, 0xD4,
0xD5, 0x15, 0xD7, 0x17, 0x16, 0xD6, 0xD2, 0x12, 0x13, 0xD3,
0x11, 0xD1, 0xD0, 0x10, 0xF0, 0x30, 0x31, 0xF1, 0x33, 0xF3,
0xF2, 0x32, 0x36, 0xF6, 0xF7, 0x37, 0xF5, 0x35, 0x34, 0xF4,
0x3C, 0xFC, 0xFD, 0x3D, 0xFF, 0x3F, 0x3E, 0xFE, 0xFA, 0x3A,
0x3B, 0xFB, 0x39, 0xF9, 0xF8, 0x38, 0x28, 0xE8, 0xE9, 0x29,
0xEB, 0x2B, 0x2A, 0xEA, 0xEE, 0x2E, 0x2F, 0xEF, 0x2D, 0xED,
0xEC, 0x2C, 0xE4, 0x24, 0x25, 0xE5, 0x27, 0xE7, 0xE6, 0x26,
0x22, 0xE2, 0xE3, 0x23, 0xE1, 0x21, 0x20, 0xE0, 0xA0, 0x60,
0x61, 0xA1, 0x63, 0xA3, 0xA2, 0x62, 0x66, 0xA6, 0xA7, 0x67,
0xA5, 0x65, 0x64, 0xA4, 0x6C, 0xAC, 0xAD, 0x6D, 0xAF, 0x6F,
0x6E, 0xAE, 0xAA, 0x6A, 0x6B, 0xAB, 0x69, 0xA9, 0xA8, 0x68,
0x78, 0xB8, 0xB9, 0x79, 0xBB, 0x7B, 0x7A, 0xBA, 0xBE, 0x7E,
0x7F, 0xBF, 0x7D, 0xBD, 0xBC, 0x7C, 0xB4, 0x74, 0x75, 0xB5,
0x77, 0xB7, 0xB6, 0x76, 0x72, 0xB2, 0xB3, 0x73, 0xB1, 0x71,
0x70, 0xB0, 0x50, 0x90, 0x91, 0x51, 0x93, 0x53, 0x52, 0x92,
0x96, 0x56, 0x57, 0x97, 0x55, 0x95, 0x94, 0x54, 0x9C, 0x5C,
0x5D, 0x9D, 0x5F, 0x9F, 0x9E, 0x5E, 0x5A, 0x9A, 0x9B, 0x5B,
0x99, 0x59, 0x58, 0x98, 0x88, 0x48, 0x49, 0x89, 0x4B, 0x8B,
0x8A, 0x4A, 0x4E, 0x8E, 0x8F, 0x4F, 0x8D, 0x4D, 0x4C, 0x8C,
0x44, 0x84, 0x85, 0x45, 0x87, 0x47, 0x46, 0x86, 0x82, 0x42,
0x43, 0x83, 0x41, 0x81, 0x80, 0x40
};
/* CRC Generation for Modbus messages */ 9
// The function returns the CRC as a unsigned short type
MODBUS protocol

unsigned short CCRC_ModbusRTUCRC16 (unsigned char *puchMsg, short


usDataLen)
{
unsigned short ReturnValue;
unsigned char uchCRCHi = 0xFF; // high byte of CRC initialized
unsigned char uchCRCLo = 0xFF; // low byte of CRC initialized
unsigned char uIndex;
// pass through message buffer

77
S1 Series Vector Inverter

while (usDataLen--)
{
// calculate the CRC
uIndex = uchCRCHi ^ *puchMsg++;
uchCRCHi = uchCRCLo ^ auchCRCHi[ uIndex ];
uchCRCLo = auchCRCLo[ uIndex ];
}
ReturnValue = uchCRCHi;
ReturnValue <<= 8;
ReturnValue |= uchCRCLo;
return ReturnValue;
}

3、Communication command interpretation


3 .1 With command code03H as an example
Read successive register arrays to read content of 10 parameters from P14.1 to
P14.10 of inverter 1, as shown in the table below.
● Initial function01 is numbered as 1401 and then converted into 0578H in the same
way above;
● Successively read 10 function codes, the register number is 10, which is
converted into 000AH in 16 system;
● CRC checksum is calculated as above: 45H, 18H

The format of message sent by the host


Address of initial register Number of register read CRC checksum
Inverter Command
address code High byte Low byte High byte Low byte Low byte High byte
(MSB) (LSB) (MSB) (LSB) (LSB) (MSB)
01H 03H 05H 78H 00H 0AH 45H 18H
The format of response message returned by the inverter
CRC
Number Parameter content of P14.01 ~ P14.10
Inverter Command checksum
of bytes of
address code P14.01 …… P14.10
register read LSB MSB
MSB LSB MSB LSB
01H 03H 14H 01H F4H …… 07H D0H B9H 76H

78
S1 Series Vector Inverter

3 .2 With command code06H as an example


Write the value into single 16-bit register, the message will return after the content of
register is written normally. For example, parameter P03.27of inverter 1 is changed
into 8, as shown in the table below.

Analyze:
P03.27’sModbus Register address:
3.27×100 = 1×256+70+1, soM = 1, N = 70, convert to 16 system and gain
high byte 01H and low byte 46H, register address is 0146H, data content 8 is
converted into 0008H in 16 system.

The format of message sent by the host


Inverter Command Register address Register data CRC CHECKSUM
address code MSB LSB MSB LSB LSB MSB
01H 06H 01H 46H 00H 08H 68H 25H
The format of response message returned by
Inverter Command Register address Register data CRC CHECKSUM
address code MSB LSB MSB LSB LSB MSB
01H 06H 01H 46H 00H 08H 68H 25H

3 .3 With command code10H as an example


Successively write register arrays. For example, three parameters P14.01 ~ P14.03
of inverter 1 are successively written in inverter 1(the written values are09C4H,
04E2H, 1077H respectively) , as shown in the table below.

The format of message sent by the host


Initial Inverter
Byte number First register Second register Third register
Inverter Command inverter number
data written data written data written
CRC checksum
address written of written
address code
register
MSB LSB MSB LSB MSB LSB MSB LSB MSB LSB LSB MSB
01H 10H 05H 78H 00H 03H 06H 09H C4H 04H E2H 10H 77H 69H 25H
The format of response message returned by the inverter
Command Initial register address Register number written CRC CHECKSUM
Inverter address
code MSB LSB MSB LSB LSB MSB
9
01H 10H 05H 78H 00H 03H 00H DDH
MODBUS protocol

3 .4 With command code17H as an example


Write and read successive arrays from more than two registers. For example, the
content of three successive function codes starting from P14.01 is read from inverter
1(P14.01 = 0x09C4P14.02 = 0x04E2P14.03 = 0x1077), the value of three function
codes starting from P14.05 is successively written (P14.05 = 0x09A1 P14.06 =
0x00FF P14.07 = 0x105A) , as shown in the table below:

79
S1 Series Vector Inverter

The format of message sent by the host


Initial Initial Byte Third
Register Register Second
register register number First register register data CRC
Inverter Command address number number register data
address of data written checksum
address code read written written written
read written written
MSB LSB MSB LSB MSB LSB MSB LSB data MSB LSB MSB LSB MSB LSB LSB MSB
01H 17H 05H 78H 00H 03H 05H 7CH 00H 03H 06H 09H A1H 00H FFH 10H 5AH 22H 27H
The format of response message returned by the inverter
Byte number First register data Second register data Third register data
Inverter Command CRC CHECKSUM
of register data read read read
address code
read MSB LSB MSB LSB MSB LSB LSB MSB
01H 17H 06H 09H C4H 04H E2H 10H 77H 3CH 22H

3 .5 Error
In case of abnormal communication, the inverter returns a fault message as a
response to the host in the format as shown in the table below:

Inverter address Command code Exceptioncode CRC CHECKSUM


1 byte 1 byte 1 byte LSB MSB

S1 series inverter’s Modbus protocol supports error codes and their meaning as
shown in the table below:
Code Description
81H Do not support function code
82H Register address is over limit or too much registers are requested
83H The value written in register is over limit

4、Communication parameters
During communication between S1 series inverter and the host, relevant parameters
may be set or accessed as shown in the table below:

Change
ID Name Setting range Default Modbus add.
method
0: Keypad
P00.03 Control 0002H
1: Terminal 0 Stop Only
(P03.01) mode (012CH)
2: Communication
0: Keypad
1: Keypad
potentiometer
2: UP/DOWN
3: Multi-speed
P00.04 Setting 4: AI1analog 0003H
0 Run&Stop
(P01.08) channel 5: AI2analog (006BH)
6: Serial
communication
7: DI6terminal pulse
8: Customized main
and auxiliary

80
S1 Series Vector Inverter

Change Modbus
ID Name Setting range Default
method add.
P03.27 Communication
controlword 0 ~ 65535 0 Run&Stop 0146H
Communication
P03.28 controlword 0~1 0 Run&Stop 0147H
enabled
P16.02 Local address 1 ~ 247 1 Run&Stop 0641H
0:2.4KBPS
1:4.8KBPS
2:9.6KBPS
P16.03 Baud rate 3 Run&Stop 0642H
3:19.2KBPS
4:38.4KBPS
5:57.6KBPS
0:1-8-1,RTU,no check
1:1-8-2,RTU,no check
Communication 2:1-8-1,RTU,odd parity
P16.04 1 Run&Stop 0643H
configuration check
3:1-8-1,RTU,even parity
check
Local response
P16.05 0ms ~ 250ms 2 Run&Stop 0644H
delay
Actual
P30.15 Inverter
byte
status 0 ~ 65535 measured Actual 0BC6H
value
In the table above, set:
P00.03(P03.01)= 2 Communication control drive.
P00.04(P01.08)= 6 Serial communication is selected as setting
channel, at this time upper computer adjusts set frequency through changing the
value of parameter P01.16.
P03.27 Communication controlword.
The meaning of each bit in the parameter is shown in the table below:

Bit Bit function Bit Bit function


0 Inverter disabled 8 Fault resetting
1 Running 9 Save parameter
2 Three-mode enabled 10 Fault record cleanup 9
3 Forward running 11 Serial change function enabled
MODBUS protocol

4 Reverse running 12 Retain


5 Forward/reverse 13 Retain
6 Forward inching 14 Retain
7 Reverse inching 15 Retain
The bits shown in the table above are set as follows(only low 8 bits are listed) :
P03.27 = 1, binary digit is00000001B(01H) , inverter disabled
P03.27 = 2, binary digit is00000010B(02H) , inverter running
P03.27 = 8, binary digit is00001000B(08H) , inverter forward running

81
S1 Series Vector Inverter

P03.27 = 16, binary digit is00010000B(10H) , inverter reverse running


P03.27 = 32, binary digit is00100000B(20H) , inverter forward/reverseP03.27 = 64,
binary digit is01000000B(40H) , inverter forward inching
P03.27 = 128, binary digit is10000000B(80H) , inverter reverse inching
P03.28Communication controlword enabled. It is used with P03.27. It must be set as
“1”, and then communication controlword can be used to control the inverter.
P30.15 Status word of inverter, showing status information of inverter. Users can
read the word through serial communication to gain status information of inverter.
The meaning of each bit is shown in the table below.

Status words in P10.14 have the following meanings:


Bit Bit function Bit Bit function
0 No fault 8 Command swiched to terminal
1 Running 9 Undervoltage lockout
2 100% load 10 Overload detection signal
3 Frequency reached 11 Inverter alarm
4 Zero-speed running 12 Length reached
5 Reversed 13 Count value reached
6 Torque limited 14 Simple PLC completion indication
7 Time reached 15 PLC cycle operation

For example, the value of status word read P30.15 = 15(000FH) , binary digit is
00001111B(low8 bits), representing no fault, forward running, set frequency reached,
100% load.

5、Scaling relationship
● Frequency,1:100
The frequency of inverter is set as 50.00Hz, which should be written as1388H(16
system, the same below)
● Time,1:10
Acceleration time is 10.0s, which should be written as0064H
● Current, 1:10
The current is 30.0A, which should be written as 012CH
● Voltage, 1:1
The voltage is 380V, which should be written as 017CH

82
S1 Series Vector Inverter

6、Application example
◆ Start inverter1, forward running, set frequency 50.00Hz
Analyze:
Forward running, write P03.27 = 0008H
P03.27 Register address 为 0146H
Set frequency50.00Hz, write P01.16 = 1388H
P01.16 Register address 为 0073H
Start inverter, forward running:
Data Inverter Command Register address Register data CRC checksum
frame address code MSB LSB MSB LSB LSB MSB
Request 01H 06H 01H 46H 00H 08H 68H 25H
Response 01H 06H 01H 46H 00H 08H 68H 25H

Set frequency 50.00Hz :


Data Inverter Command Register address Register data CRC checksum
frame address code MSB LSB MSB LSB LSB MSB
Request 01H 06H 00H 73H 13H 88H 75H 47H
Response 01H 06H 00H 73H 13H 88H 75H 47H

◆ Inverter 1, output frequency (P30.01) is50.00H(1388H), output voltage(P30.02) is


380V(017CH). The host reads the two parameters.
analyze:
P30.01 Register address 为 0BB8H, P30.02 Register address 为 0BB9H。
Read output frequency and output voltage of inverter:

Initial Second
Register First register
register Byte number data read register data CRC checksum
Data Inverter Command address number read read
of read
frame address code
register
MSB LSB MSB LSB MSB LSB MSB LSB LSB MSB

Request 01H 03H 0BH B8H 00H 02H None None None 46H 0AH
Response 01H 03H None None 04H 13H 88H 01H 7CH 7EH ECH
9
Note:
MODBUS protocol

When users use communication control method to control the running inverter, if
press STOP to stop the inverter, the value ofcommunication control wordP03.27
will not change, suggesting that P03.27 must be reset and then a new control word
should be written to restart the inverter.

83
S1 Series Vector Inverter

84
Warranty clause
Our company solemnly promises that users enjoy the warranty services below since
the date when they purchase this product:
I.This product enjoys free warranty within 18 months since the date when users
purchase this product(except export countries and non-standard products).
II.This product is freely returned, replaced and repaired in case that any quality
problem occurs within one month since the date when this product is purchased.
III.This product is freely replaced in case that any quality problem occurs within three
months since the date when this product is purchased.
IV.Our company provides compensable service for life since the data when this
product is purchased.
V.Exception clause: In case that this product is damaged or fails to work for the
following reasons, this product is not covered by our 18-month free warranty services
1)This product is damage because the user fails to use it according to User’s Manual
or standard specifications;
2)This product is damaged due to earthquake, fire, flood, abnormal voltage and other
force majeure;
3)This product is damaged due to wrong use or disassembly, maintenance and
modification without authorization;
4)This product is damaged because it is used for improper purpose;
5)This product is damaged due to improper storage.
VI. Our company has the right to refuse warranty service under the following
circumstances:
1) Information about this product (nameplate, label, serial number and other markings)
cannot be identified;
2) The user has not pay off the price according to Purcahse Contract signed between
the user and our company;
3) The user intentionally conceal any improper service condition from our after-sale
service provider during installing, wiring, operating and maintaining this product.

HuaYuan Electric Co., Ltd.


Address: 1F No1 Building, Hong Hui Industrial Park, Liu Xian Second
Road , Bao’an District, Shenzhen, Guangdong, China
Post code: 518000
Tel: 0755-23227099
Fax: 0755-23505661
E-mail: [email protected]
Website: www.huayuan-elec.com
Name of working unit:

Address of working unit:


Customer
Information
Contact: Tel.:

Fax: Post code:

Model: Barcode:

Purchase date: Date of fault:


Product
information
Motor power: Application site:

Name of agent:

(Repair time and content)

Fault
information

After-sales personnel: Date:


Huayuan Electric Co., Ltd. S1 Series Vector Inverter File code:29900005
HuaYuan Electric Co.,Ltd.
Address: 1F No1 Building, Hong Hui Industrial Park,
Liu Xian Second Road , Bao’an District, Shenzhen,
Guangdong, China
Post code: 518000
Tel: 0755-23227099
Fax: 0755-23505661
Official website
E-mail: [email protected]

You might also like