0% found this document useful (0 votes)
449 views3 pages

Foundation Design For Single Pole

This document provides the design details for a single pole foundation. It includes the design loads, soil parameters, material properties, and calculations to check for bearing pressure, overturning stability, and sliding resistance. The maximum bearing pressure is found to be unsafe under normal conditions but safe under short circuit force conditions. A factor of safety of 1.5 is used to check for overturning and sliding stability.

Uploaded by

Gururaj Kanjiker
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
449 views3 pages

Foundation Design For Single Pole

This document provides the design details for a single pole foundation. It includes the design loads, soil parameters, material properties, and calculations to check for bearing pressure, overturning stability, and sliding resistance. The maximum bearing pressure is found to be unsafe under normal conditions but safe under short circuit force conditions. A factor of safety of 1.5 is used to check for overturning and sliding stability.

Uploaded by

Gururaj Kanjiker
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT :

PREPARED BY CHECKED BY APPROVED BY DATE REV


TITLE SINGLE POLE FOUNDATION
SSS SSS SSS - 0

FOUNDATION DESIGN :

A Design Loads at P L (per fdn.) : Normal Condition Short circuit force Condition
Horizontal Shear kg = 148 = 436
Moment kgm = 529 = 2429
Vertical load kg = 414 = 414

B Soil Parameters :
Density of soil kN/m3 18.00 = 18.00
Refer Soil Report
Density of soil kg/cum 1835 = 1835
Depth of foundation below FGL m = 1.5 = 1.5
Filling m = 0.0 = 0
Net SBC at founding level KN/m2 = 250.00 = 250.00
Refer Soil Report
Net SBC at founding level kg/sqm = 25484 = 25484

Hence, Gross SBC at 1.5 m from NGL kg/sqm = 25484 + 1.5 = 25484.2 +
x 1835 1835 x 1.5
= 28236 = 28236
C Concrete & Steel : ( Ref Technical Specifications)
Concrete grade = M25 = M25 Refer Soil Report
Density of Concrete kg/Cum = 2500 = 2500
Rebar yield stress (Fe-500 Grade) N/mm² = 500 = 500 Refer Soil Report

D Other parameters :
1 Pedestal size m = 0.50 x 0.50 = 0.5 x 0.5

2 Bottom pad size m = 0.50 x 0.50 = 0.5 x 0.5

3 Bottom pad thickness m = 1.5 = 1.5

4 Depth of foundation below FGL (Min.) m = 1.5 = 1.5

5 Plinth level m = 0.30 = 0.3

6 FOS against overturning = 1.5 = 1.50

7 FOS against sliding = 1.5 = 1.50

8 Angle of internal friction (φ) = 38 = 38


Refer Soil Report

9 Coefficient of sliding bet. soil & concrete ( tanφ) = 0.68 = 0.68

10 FOS against Strength = 2.2 = 1.65 Refer Soil Report

E Design Calculations : Check for bearing pressure

Weight of Concrete kg (( 0.5 x 0.5 x 1.5 )


+ ( 1.5 x 1.5 x 0.3 ))x 2500
= 2626
Volume of concrete cum = 2626 / 2500
= 1.05
Weight of earth kg = ( 1.5 x 1.5 - 0.5 x 0.5 )
x 1.2 x 1783.893986
= 4282
Vertical load of Equipment / structure kg = 414
Total Vertical Load kg = 2626 + 4282 + 414
= 7322
Normal Condition Short circuit force Condition
Moment about base of fdn. kgm = 148 x 1.8 = 436 x 1.8
+ 529 + 2429
= 796 = 3214
Overturning moment kgm = 796 = 3214
(Ignoring Passive Resistance)
Actual Eccentricity m = 796 / 7322 = 3214 / 7322
= 0.1087 = 0.4390
Maximum Eccentricity ( =b/6 ) m = 0.5 / 6 = 0.5 / 6
0.0833 = 0.083
PROJECT :

PREPARED BY CHECKED BY APPROVED BY DATE REV


TITLE SINGLE POLE FOUNDATION
SSS SSS SSS - 0

Maximum Eccentricity ( =b/3 ) m = 0.08 x 2 = 0.08 x 2


= 0.17 = 0.17

e > b/6 & e < b/3 = e > b/6 & e > b/3

Max . bearing pressure kg/m² = 2P / ( B X ) = 2P / ( B X )


where X=3(0.5L-e) where X=3(0.5L-e)

Dist. of point of zero shear from edge, X m = 0.4239 = -0.567

Max. gross bearing pressure kg/m² = 69092 > 28236 = -51654 < 28236

Unsafe (Gross SBC) Hence safe (Gross SBC)

Min . bearing pressure kg/m² = 0 = 0


= 0 = 0

Contact Area (based on modified pressure) % 0.4239x0.5


= x100/(0.5x0.5) = -0.567x0.5 x100/(0.5x0.5)
= 85 = -113

F1 Check for overturning Normal Condition Short circuit force Condition


Restoring Moment at base kgm = 7322 x 0.5 = 7322 x 0.5
2 2
= 1831 = 1831

F.O.S.against overturning = 1831 / 796 = 1831 / 3214


= 2.3 > 1.5 = 0.57 > 1.5

Hence Safe UNSAFE


F2 Check for sliding
Total horizontal shear kg = 148 gh = 436

Total vertical load kg = 7322 = 7322

Resistance against sliding kg = 0.7 x 7322 = 0.7 x 7322


= 4942.35 = 4942.35

FOS against sliding = 4942.35 / 148 = 4942.35 / 436


= 33.39 > 1.5 = 11.34 > 1.5

Hence safe Hence safe

J. Design of Short column


Member size m = 0.5 x 0.5

Least dimension of member x 3 m = 1.5

Effective height of member m = 0.3 x 2 = 0.6 < 1.5

Height / Least Lateral Dimension = 1.2 < 12


Hence it acts as a pedestal

Refer Design aids SP : 16 Normal Condition Short circuit force Condition

Direct vertical load kg = 414 = 414


Self weight of pedestal kg = 0.5 x 0.5 x 0.3 x 2500
= 188
Total vertical load kg = 602 = 602

Factored vertical load, Pu kg = 602 x 2.2 = 602 x 1.65


= 1325 = 994
Moment at PL kgm = 529 = 2429
Shear at PL kg = 148 = 436

Max. moment at the base of Member kgm = 529 + 148 = 2429 + 436
x 0.3 x 0.3
= 574 = 2560
Factored moment at base, Mu kgm = 574 x 2.2 = 2560 x 1.65
= 1263 = 4225
PROJECT :

PREPARED BY CHECKED BY APPROVED BY DATE REV


TITLE SINGLE POLE FOUNDATION
SSS SSS SSS - 0

b mm = 500 = 500
D mm = 500 = 500
d' mm = 40 + 6 =
= 46 = 46
d' / D = 46 / 500 =
= 0.092 say = 0.1
f ck N/mm² = 25 = 25

pu / f ck b D = 0.002 = 0.002

Mu / f ck b D² = 0.004 = 0.013
1
From chart 48 of SP:16,for d /D=0.1 p / f ck = 0.01 = 0.010
Hence, p reqd. % = 0.01 x M25 = 0.25

L RESULT

1. Depth of foundation from FGL = 1.5 m

2. Plinth level above FGL = 0.30

3. Bottom pad Details


Size of bottom pad in 'm' = 0.5 x 0.5

Thickness of bottom pad = 1.5 m


Clear cover = 50 mm