PROJECT :
PREPARED BY CHECKED BY APPROVED BY DATE REV
TITLE SINGLE POLE FOUNDATION
SSS SSS SSS - 0
FOUNDATION DESIGN :
A Design Loads at P L (per fdn.) : Normal Condition Short circuit force Condition
Horizontal Shear kg = 148 = 436
Moment kgm = 529 = 2429
Vertical load kg = 414 = 414
B Soil Parameters :
Density of soil kN/m3 18.00 = 18.00
Refer Soil Report
Density of soil kg/cum 1835 = 1835
Depth of foundation below FGL m = 1.5 = 1.5
Filling m = 0.0 = 0
Net SBC at founding level KN/m2 = 250.00 = 250.00
Refer Soil Report
Net SBC at founding level kg/sqm = 25484 = 25484
Hence, Gross SBC at 1.5 m from NGL kg/sqm = 25484 + 1.5 = 25484.2 +
x 1835 1835 x 1.5
= 28236 = 28236
C Concrete & Steel : ( Ref Technical Specifications)
Concrete grade = M25 = M25 Refer Soil Report
Density of Concrete kg/Cum = 2500 = 2500
Rebar yield stress (Fe-500 Grade) N/mm² = 500 = 500 Refer Soil Report
D Other parameters :
1 Pedestal size m = 0.50 x 0.50 = 0.5 x 0.5
2 Bottom pad size m = 0.50 x 0.50 = 0.5 x 0.5
3 Bottom pad thickness m = 1.5 = 1.5
4 Depth of foundation below FGL (Min.) m = 1.5 = 1.5
5 Plinth level m = 0.30 = 0.3
6 FOS against overturning = 1.5 = 1.50
7 FOS against sliding = 1.5 = 1.50
8 Angle of internal friction (φ) = 38 = 38
Refer Soil Report
9 Coefficient of sliding bet. soil & concrete ( tanφ) = 0.68 = 0.68
10 FOS against Strength = 2.2 = 1.65 Refer Soil Report
E Design Calculations : Check for bearing pressure
Weight of Concrete kg (( 0.5 x 0.5 x 1.5 )
+ ( 1.5 x 1.5 x 0.3 ))x 2500
= 2626
Volume of concrete cum = 2626 / 2500
= 1.05
Weight of earth kg = ( 1.5 x 1.5 - 0.5 x 0.5 )
x 1.2 x 1783.893986
= 4282
Vertical load of Equipment / structure kg = 414
Total Vertical Load kg = 2626 + 4282 + 414
= 7322
Normal Condition Short circuit force Condition
Moment about base of fdn. kgm = 148 x 1.8 = 436 x 1.8
+ 529 + 2429
= 796 = 3214
Overturning moment kgm = 796 = 3214
(Ignoring Passive Resistance)
Actual Eccentricity m = 796 / 7322 = 3214 / 7322
= 0.1087 = 0.4390
Maximum Eccentricity ( =b/6 ) m = 0.5 / 6 = 0.5 / 6
0.0833 = 0.083
PROJECT :
PREPARED BY CHECKED BY APPROVED BY DATE REV
TITLE SINGLE POLE FOUNDATION
SSS SSS SSS - 0
Maximum Eccentricity ( =b/3 ) m = 0.08 x 2 = 0.08 x 2
= 0.17 = 0.17
e > b/6 & e < b/3 = e > b/6 & e > b/3
Max . bearing pressure kg/m² = 2P / ( B X ) = 2P / ( B X )
where X=3(0.5L-e) where X=3(0.5L-e)
Dist. of point of zero shear from edge, X m = 0.4239 = -0.567
Max. gross bearing pressure kg/m² = 69092 > 28236 = -51654 < 28236
Unsafe (Gross SBC) Hence safe (Gross SBC)
Min . bearing pressure kg/m² = 0 = 0
= 0 = 0
Contact Area (based on modified pressure) % 0.4239x0.5
= x100/(0.5x0.5) = -0.567x0.5 x100/(0.5x0.5)
= 85 = -113
F1 Check for overturning Normal Condition Short circuit force Condition
Restoring Moment at base kgm = 7322 x 0.5 = 7322 x 0.5
2 2
= 1831 = 1831
F.O.S.against overturning = 1831 / 796 = 1831 / 3214
= 2.3 > 1.5 = 0.57 > 1.5
Hence Safe UNSAFE
F2 Check for sliding
Total horizontal shear kg = 148 gh = 436
Total vertical load kg = 7322 = 7322
Resistance against sliding kg = 0.7 x 7322 = 0.7 x 7322
= 4942.35 = 4942.35
FOS against sliding = 4942.35 / 148 = 4942.35 / 436
= 33.39 > 1.5 = 11.34 > 1.5
Hence safe Hence safe
J. Design of Short column
Member size m = 0.5 x 0.5
Least dimension of member x 3 m = 1.5
Effective height of member m = 0.3 x 2 = 0.6 < 1.5
Height / Least Lateral Dimension = 1.2 < 12
Hence it acts as a pedestal
Refer Design aids SP : 16 Normal Condition Short circuit force Condition
Direct vertical load kg = 414 = 414
Self weight of pedestal kg = 0.5 x 0.5 x 0.3 x 2500
= 188
Total vertical load kg = 602 = 602
Factored vertical load, Pu kg = 602 x 2.2 = 602 x 1.65
= 1325 = 994
Moment at PL kgm = 529 = 2429
Shear at PL kg = 148 = 436
Max. moment at the base of Member kgm = 529 + 148 = 2429 + 436
x 0.3 x 0.3
= 574 = 2560
Factored moment at base, Mu kgm = 574 x 2.2 = 2560 x 1.65
= 1263 = 4225
PROJECT :
PREPARED BY CHECKED BY APPROVED BY DATE REV
TITLE SINGLE POLE FOUNDATION
SSS SSS SSS - 0
b mm = 500 = 500
D mm = 500 = 500
d' mm = 40 + 6 =
= 46 = 46
d' / D = 46 / 500 =
= 0.092 say = 0.1
f ck N/mm² = 25 = 25
pu / f ck b D = 0.002 = 0.002
Mu / f ck b D² = 0.004 = 0.013
1
From chart 48 of SP:16,for d /D=0.1 p / f ck = 0.01 = 0.010
Hence, p reqd. % = 0.01 x M25 = 0.25
L RESULT
1. Depth of foundation from FGL = 1.5 m
2. Plinth level above FGL = 0.30
3. Bottom pad Details
Size of bottom pad in 'm' = 0.5 x 0.5
Thickness of bottom pad = 1.5 m
Clear cover = 50 mm