DATA SHEET: TEMBREAK 2 H800-NE MCCB

MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
Frame reference Quantity Unit Condition TB2 H/L 800
Max In (A) of Frame 800
Model H800
Number of Poles 3, 4
Type NE

Nominal current ratings


In (A) 50°C 630
800

Electrical characteristics
Rated operational voltage Ue (V) AC 50/60 Hz 690
DC -
Rated insulation voltage Ui (V) 800
Rated impulse withstand voltage U imp (kV) 8
Ultimate breaking capacity I cu (kA) 690V AC 25 3
(IEC, JIS, AS/NZS) 525V AC 40
440V AC 125
400/415V AC 125
220/240V AC 150
250V DC -
Service breaking capacity I cs (kA) 690V AC 20 3
(IEC, JIS, AS/NZS) 525V AC 34
440V AC 94
400/415V AC 94
220/240V AC 150
250V DC -
Rated breaking capacity (NEMA) (kA) 480V AC 40
240V AC 150
Rated short-time withstand current I cw (kA) 0.3 Seconds 10

Protection
Adjustable thermal, adjustable magnetic
Fixed thermal, fixed magnetic
Microprocessor
Utilisation category B

Installation
Front connection (FC) -
Extension bar (FB)
Cable clamp (FW -
Rear connection (RC) •
Plug-in (PM) •
DIN rail mounting (DA) -
Dimensions height (mm) 273
width (mm) 3 pole 210
4 pole 280
depth (mm) 140
3 pole 1
Weight weight (kg)
2
4 pole

Operation
Direct Opening Action
Toggle operation
Door mounted (HS) / Breaker mounted handle (HB) •
Motor operation (MC) •

Endurance Electrical 690V AC


Mechanical cycles 4,000
cycles 10,000

1 13.3kg 630A, 14.8kg 800A


2 16.8kg 630A, 18.8kg 800A
3 MCCB cannot be used in
IT systems at this voltage Standard • Optional - Not Available

Page 1 of 4
DATA SHEET: TEMBREAK 2 H800-NE MCCB
Outline Dimensions H800-NE

ASL: Arrangement Standard Line HL: Handle Frame Centre Line

Front connected

3P Interpole barrier 4P Mounting hole


H ø13 (removable)
H
10 69 Drilling plan (front view)
L L
13 Toggle extension 3P 4P
110

(removable) H H

80
L L

170 170

126
46.5 55.5
273

ASL ASL ASL ASL


90

65 15

117
51 Trip button (red) 51

M8
15 32 25

Mounting screw 70 70 M8
8
80

Tapped hole
40 70 70 70 8 10 L2
140 105 175 Conductor Rated current L2
overlap, max 140
210 280 164.5 630A 73
80.5 182
800A 74

Rear connected
Drilling plan (front view) Panel cutout (front view)
4P Groove for dissipating
Stud can be 3P heat generated by
ø15 for accessory wiring ø48 overcurrent 4P
Toggle extension turned 90° H
L 3P 4P
(removable) when necessary 3P
H
L H
L
HL
10

5
30.5

136
126

126
13 R6
ASL ASL

92
M8 ASL
65 15 Tapped hole
32 25

122
117

117
127
8
42

Conductor 172
20

M8 ø13
70 70 70 overlap, max
5

8 70 70
140 Mounting screw 43 70 70 70 43
43 70 70 43
164.5
80.5 182 Panel cutout dimensions shown give an allowance
Note: Studs are factory installed in horizontal direction both on the line and load sides.
of 1.0mm around the handle escutcheon.

Front connected with Motor Operator

Interpole barrier Drilling plan (front view) Panel cutout (front view)
(removable)
Mounting hole 12.5 237.5
3P 4P
HL HL 10 69 M8
3

Front Panel
ø1

Tapped hole
13 Manual operating handle
110

HL
80

(removable) (18) HL

Pad lock
101.9

101.9
126
156

160
160

ASL ASL ASL ASL ASL


273

117

65 15
(15.5)
overlap, max 15 32 25

M8 70 140
80

Connector plug
8

(19.8) Mounting screw


40 70 70
70 10 L2
140 105 175 136.5
210 280
Conductor

16 174.5 Panel cutout dimensions shown


250 Rated current L2 give an allowance of 1.5mm
630A 73 around motor operator.
800A 74

Rear connected with Motor Operator


Drilling plan (front view)
Groove for dissipating Panel hinge position (hatching area)
ø15 for accessory wiring heat generated (bottom view)
12.5 237.5 140 when necessary by overcurrent
Front Panel Stud can be 136
turned 90° 3P 4P ø48
Manual operating handle HL
H
L H
L
(removable) (18)
5
10

HL
Pad lock 100 100
30.5
101.9

136
126
126

16
156

8
160

ASL ASL M8
140

13
65 15 Tapped hole
117
127
117
(15.5)

237.5
42

32 25

122
8

70 70
Connector plug M8
(19.8) 136.5 43 70 70 43 43 70 70 70 43
Mounting screw
overlap, max 20

16 174.5 70 70 70
250 150 150
Conductor

200 200

Note: Studs are factory installed in horizontal direction both on the line and load sides.

Page 2 of 4
DATA SHEET: TEMBREAK 2 H800-NE MCCB
Outline Dimensions H800-NE Plug-in Versions

ASL: Arrangement Standard Line HL: Handle Frame Centre Line

Outline Dimensions M8
Termination of Busbar
Mounting screw
3P 4P Toggle extension Preperation of conductor
HL
Mounting hole
HL (removable)

170 170
158.5
141

126
46.5 55.5

308
350
ASL ASL ASL
90

25 (max.)

117
149.5
132

51 51

8 17
210 105 175 140
280 164.5 51.6 ø13
Trip button 80.5 182 116
(red)
40 (max.) 10 (max.) Mounting screw M12✕25 max. Hex. sec. head bolt.

Mounting on a support or rails


Detail of connecting part
Oriented for rear access
Mounting base Drilling plan
M8 (rear view) (front view) ø13 R6.5
21
Mounting screw

13

40
Toggle extension 3P 4P 3P 4P
(removable) HL HL HL HL 25
21

44 81

25
17
ø9
66
ø13 30
63

70.5 79.5 15
126

10t
70.5 79.5

10t
100 170
308
350

182

ASL ASL ASL 30 ø13

17
25
66
117

44 81 ø13 R6.5
50 21

15
63

13
8

40
40.5
140
21

70 70 70 70 70 100 170
164.5 51.6 25
80.5 182 116
Terminal bars should be connected alternately
on adjacent poles.

Mounting through the backplate (shown with optional connection bars oriented for rear access)

(rear view) Drilling plan (front view)


Detail of connecting part
Mounting plate Oriented for rear access
Pan head screw Mounting plate
M8✕16 ø13 21 R6.5
163
148
13

Toggle extension 3P 4P 3P 4P
112
40
(removable) HL HL HL HL
10t

25
44 81
25
17

66
ø13 30
169.5

160.5
10t

10t

10t
193
273

308
102

293

ASL ASL ASL


312
330
90

30 ø13
17
151.5

25
160.5

66
44 81 ø13 R6.5
21
13

40.5 40
18 70 70 70 70 35 105
70 70
8 174 65 81 107 177 25

216 214 284


Terminal bars should be connected alternately
on adjacent poles.

Mounting on the backplate (optional connection bars must be oriented for front access)

(rear view) Drilling plan (front view) Detail of connecting part


Oriented for front access
3P 4P
HL HL
280
44 1 210 175 105
Mounting plate ø13
Insulating plate
10t
Toggle extension 3P 4P
M8✕80 HL HL
(removable)
13

R6.5
144

17
272
102

279

279

ASL ASL ASL


90

21
53
68
ø13
135

Mounting plate
10t
40
53
17

10t 70 70 70 105
Insulating plate
15

140 4-ø9
44 1
40
8 257 70 70 70 70 70
299

Page 3 of 4
DATA SHEET: TEMBREAK 2 H800-NE MCCB

Time/Current Characteristic Curves


H800-NE

Percent Rated
Current In Percent Rated Current IR

In = 800A; 630A
IR (A)
LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0

Characteristics No. 1 2 3 4 5 6 7
11 21 21 5 10 19 29
LT tR (s)
at 200% x IR at 600% x IR
Standard xIR 2.5 5 10
ST
Isd
tsd (s) 0.1 0.2
INST Ii xIR 14(Max: 12 x In) Note (1)
xIR 0.8
PTA
Ip
tp (s) 40
gF Ig xIn 0.2
Option Note(3) tg (s) 0.2
xIR 1.0/0.5 Note(2)
NP
IN
tN (s) tN=tR

Note
(1) Ii max. = 12 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic of phase