Testrano 600

Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

Application Note

A Guide for Using PTM and the TESTRANO 600 to


Test Transformers

Author
Brandon Dupuis | Brandon.Dupuis@omicronenergy.com
Logan Merrill | Logan.Merrill@omicronenergy.com
Fabiana Cirino | Fabiana.Cirino@omicronenergy.com

Date
August 06,2019

Related OMICRON Product


TESTRANO 600

Application Area
Transformer testing with PTM

Keywords
PTM guide

Version
v 1.0

Document ID

Abstract
This application note is a step-by-step guide for users creating a test plan in the PTM software for
electrical diagnostic testing of power transformers. Important settings and tips for obtaining a good
measurement are highlighted in the guide for each major test associated with the TESRANO 600.
General information

OMICRON electronics GmbH, including all international branch offices, is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this Application Note
represent the technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this Application Note is useful, accurate
and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which
may be present.
OMICRON translates this Application Note from the source language English into a number of other
languages. Any translation of this document is undertaken for local requirements, and in the event of
a dispute between the English and a non-English version, the English version of this note shall
govern.

All rights, including translation, reserved. Reproduction of any kind, for example, photocopying,
microfilming, optical character recognition, and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON. Reprinting, wholly or partly, is not permitted.
© OMICRON 2019. All rights reserved. This Application Note is a publication of OMICRON.

© OMICRON 2019 Page 2 of 50


Table of content

1 Safety instructions ......................................................................................................................... 4


2 PTM Test Procedure Document: Introduction ............................................................................. 5
3 Overview .......................................................................................................................................... 7
4 Location ........................................................................................................................................... 8
5 Asset ................................................................................................................................................ 9
5.1 Asset: Transformer ................................................................................................................ 10
5.2 Asset: Bushings ..................................................................................................................... 14
5.3 Asset: Tap Changers ............................................................................................................. 17
5.4 Asset: Surge Arrester ............................................................................................................ 19
5.5 Asset: DGA Trending ............................................................................................................. 20
6 Test Plan Creation ........................................................................................................................ 21
7 Tests .............................................................................................................................................. 22
7.1 Overall PF & Cap Test ........................................................................................................... 22
7.2 Bushing PF & Cap- C1 Test .................................................................................................. 27
7.3 Bushing PF & Cap- C2 Test .................................................................................................. 31
7.4 Bushing Energized Collar Test .............................................................................................. 35
7.5 Exciting Current Test ............................................................................................................. 37
7.6 Turns-Ratio (TTR) Test.......................................................................................................... 39
7.7 DC Winding Resistance Test ................................................................................................. 41
7.8 Demagnetization Test ............................................................................................................ 44
7.9 Leakage Reactance Test ....................................................................................................... 45

© OMICRON 2019 Page 3 of 50


1 Safety instructions
This Application Note may only be used in conjunction with the relevant product manuals which
contain all safety instructions. The user is fully responsible for any application that makes use of
OMICRON products.
Instructions are always characterized by a  symbol, even if they are included in a safety instruction.

DANGER
Death or severe injury caused by high voltage or current if the respective
protective measures are not complied with.

 Carefully read and understand the content of this Application Note as


well as the manuals of the systems involved before taking them into
operation.
 Please contact OMICRON support if you have any questions or
doubts regarding the safety or operating instructions.
 Follow each instruction listed in the manuals, especially the safety
instructions, since this is the only way to avoid the danger that can
occur when working on high voltage or high current systems.
 Only use the equipment involved according to its intended purpose to
guarantee safe operation.
 Existing national safety standards for accident prevention and
environmental protection may supplement the equipment’s manual.

Only experienced and competent professionals that are trained for working in high voltage or high
current environments may implement this Application Note. Additionally, the following qualifications
are required:
• Authorized to work in environments of energy generation, transmission or distribution, and
familiar with the approved operating practices in such environments.
• Familiar with the five safety rules.
• Good knowledge/proficient in working with the TESTRANO 600 and Electrical Diagnostic
Testing of Power Transformers.

© OMICRON 2019 Page 4 of 50


2 PTM Test Procedure Document: Introduction
The purpose of the following document is to provide the user a step-by-step guide for successfully
using PTM. The document closely follows the PTM “workflow” concept. The user will be guided
through the following process,

Identify Nameplate Information

Create a Test Plan

Perform Measurements

Generate Test Report

Figure 1: PTM Workflow Concept

In addition to providing a step-by-step guide for using PTM, the intention of this document is to also
help the user develop good testing practices, which can help increase the accuracy and quality of the
measurements performed, as well as decrease the likelihood of making safety related mistakes.
The home screen of the PTM software is shown in Figure 2, and can be used to complete the
following tasks,
 Connect the OMICRON equipment to the laptop via an Ethernet cable
 Access the PTM Database via the “Manage” option
 Create a new test plan

© OMICRON 2019 Page 5 of 50


To create a test plan The serial number of
The “Manage” area is the from scratch, select the device should
PTM database, which “New guided job” and appear when the laptop
includes location, follow the instructions is hooked up. Then,
nameplate information, shown in the following connect to the device
test results, and test sections. by clicking the
reports. “Connect” option.

Figure 2: PTM Home Screen

A new test plan can be created either by clicking the “New guided job” or “Manage” button; however,
the “New guided job” button is a more direct way of creating a new test plan and allows the user to
bypass the data manager. Therefore, to create a new test plan for a power transformer, select the
“New guided job” button.
Once a new job is created, the user will have access to the five main sections of the PTM software,
which include, the “overview”, “location”, “asset”, “tests”, and “report” section. The five sections can
be found on the left panel of PTM (see Figure 3). The user should complete these sections in order
from top to bottom, as shown in Figure 3.

Start

Finish
Figure 3: PTM Left Panel- Workflow

© OMICRON 2019 Page 6 of 50


3 Overview
Once a new job is created, the first section that will automatically be displayed is the “Overview”
section, as shown in Figure 4. Please enter the information outlined in Figure 4.

Complete these fields

Field available for


additional comments
(not required)

Figure 4: PTM Overview Section

© OMICRON 2019 Page 7 of 50


4 Location
Once the overview section is complete, click on the “Location” tab on the PTM left panel, as shown in
Figure 5. The “Location” is the name of the job site, substation, etc.… The transformer that you will
eventually create within this test plan will be stored at this location within the PTM database.

Please enter the information outlined in Figure 5.

If location is already in the PTM database, then


select this option to import the location.

Location “Name” field is


required. All other location
information is optional and
for documentation
purposes only.

Figure 5: Location Section

© OMICRON 2019 Page 8 of 50


5 Asset
Once the “Location” section is complete, click on the “Asset” tab on the PTM left panel, as shown in
Figure 6. The “Asset” section of the software is where all the nameplate information of the device
under test and its ancillary equipment (i.e. bushings, etc) will be entered.

NOTICE

Complete fields from top-to-bottom

 It is important that the “Asset” section of the software is completed from top-to-bottom. The
“Asset” section may change based on a previous selection so it is important to enter the
information accurately, and in order.

Please complete the sections outlined in Figure 6.

If the transformer is already in the


PTM database, then select this
option to import the asset and all
associated nameplate information.

Complete the “Asset” section


working from top to bottom. It is
recommended that you complete
as many fields as possible,
unless otherwise noted.

Figure 6: Asset Information

© OMICRON 2019 Page 9 of 50


5.1 Asset: Transformer

Once the main transformer nameplate information is complete, notice that the “Asset” section
expands into 5 tabs, including the “Transformer”, “Bushings”, “Tap Changers”, “Surge Arresters”, and
“DGA Trending” sections, as highlighted in Figure 7. It is recommended that the first four sections are
completed from left-to-right, starting with the “Transformer” section. The “DGA Trending” tab
automatically documents results of available oil analysis tests in the PTM database for the associated
asset.

1 2 3 4 5

Figure 7: Transformer- Main information

Remain in the “Transformer” section and scroll down to the “Winding configuration” section. The
winding configuration section is critical to PTM, and will heavily influence the test plan. By entering
the correct winding configuration and vector group of the transformer you would like to test, the PTM
software will provide the correct connection diagrams for the available tests.

© OMICRON 2019 Page 10 of 50


Click on the “Select Winding
Configuration” box to populate the
vector group of the transformer, as
shown in the following example.

This field is ONLY populated if the


winding configuration of the asset
you are testing is not currently
available in PTM. Otherwise,
leave this field empty.

Figure 8: Winding Configuration

For example, if the asset you would like to test is a 3-phase, two-winding, DYn1 transformer, then the
vector group shown in Figure 9 would be selected. If you are unsure of the correct vector group,
visually match the vector group on the nameplate of the transformer to the options provided below.
Once the desired vector group is selected, click the “ok” button in the lower right-hand corner to
confirm.

Figure 9: Vector Group Selection

© OMICRON 2019 Page 11 of 50


NOTICE

Avoiding Incorrect Test Plan: Y vs Yn

 Please note that from the software’s perspective, there is a major difference between a Y-
winding (wye winding with no accessible neutral) and a Yn-winding (wye winding with an
accessible neutral). To prevent the software from populating the incorrect test plan, please
make sure that the vector diagram you select accurately represents the transformer you
would like to test.

Once the “winding configuration” section is complete, scroll down to the “Ratings” section.

The voltage ratings of the transformer are


critical information. They determine the
maximum applied voltage for each test (where
applicable). Also, these values may be used
in various calculations.

Entering the current and


power ratings is
recommended, but not
required to complete the
transformer tests
successfully.

Figure 10: Ratings Section

Once the “Ratings” section is complete, scroll down to the “Impedances” section.

© OMICRON 2019 Page 12 of 50


The leakage reactance fields are only required if the leakage
reactance test is going to be performed. Otherwise, this
information is for documentation purposes only.

The OLTC and DETC position cannot be selected until the


“Tap Changer” section of the Asset page is completed (See
“Asset: Tap Changers” section). After completing the tap
changer section (section 5.3), please return to this section to
select the OLTC and DETC position if applicable.

To compare the measured leakage reactance values to the nameplate (factory) short-circuit impedance, the
following information is required, and can typically be found on the nameplate of the transformer,
*Leakage Reactance Z (%)
*Base Power
*Base Voltage
*OLTC and/or DETC position (when applicable)

Figure 11: Impedances Section

Once the “Impedances” section is complete, scroll down to the “Others” section.

© OMICRON 2019 Page 13 of 50


The insulating medium of the power transformer
is required to perform an automatic assessment
on the overall transformer power factor results.

The “Conductor material” will be


used to temperature correct the
DC Winding Resistance results.

Note, all other information in


the “Others” section is for
documentation purposes only

Figure 12: Others Section

5.2 Asset: Bushings

Once the “Transformer” nameplate information is complete, scroll up to view the tabs located at the
top of the “Asset” section. If the transformer has bushings that you would like to test, please click the
“Bushings” tab (highlighted in Figure 13) to begin populating the nameplate information of the
bushings. Otherwise, proceed to the next section.

Scroll to the top of the Asset page, and select the


“Bushings” tab.
Note, it is only necessary to complete the “Bushings”
section if the user would like to perform a power factor test
on the bushings. Otherwise, entering the bushing
nameplate information is for documentation purposes only.

Figure 13: Asset- Four Main Tabs

© OMICRON 2019 Page 14 of 50


The “Asset type” field is critical. The software will only allow the
user to perform a bushing power factor C1 and C2 test, if the user
specifies that the bushing has a test or potential tap. If the asset
type is not selected, the only bushing test that is available to the
user is an Energized Collar test.

Note, the serial no., manufacturer are required for using


the trending feature for the bushing power factor tests.
The manufacturer type, and manufacturer year fields are
recommended, but not required.

Note, for the “Asset type”, selecting the “With test tap” option will
set the output voltage to 500V for a C2 power factor test for that
particular bushing. If the “With potential tap” option is selected,
the output voltage for the C2 power factor test will be 2000V.

Figure 14: Bushing Nameplate- Part 1

Next, scroll to the right to view more bushing nameplate fields, as shown in Figure 15.

© OMICRON 2019 Page 15 of 50


Bushings rated > 350kV BIL typically have potential taps
Bushings rated ≤ 350kV BIL typically have test taps

The Voltage L-ground field is


critical. It will determine the
maximum output voltage for
the bushing C1 power factor
test. All other fields shown in
Fig.15 are recommended, but
not required.

Figure 15: Bushing Nameplate- Part 2

Finally, scroll to the right to view the final bushing nameplate fields, as shown in Figure 16.

Enter the nameplate power


factor and capacitance values if
available. This allows the PTM
software to perform an automatic To perform an auto-assessment
assessment of the test results by for the bushing power factor
comparing the measured C1 and results, the insulation type must
C2 values to the nameplate be selected.
values.

Figure 16: Bushing Nameplate- Part 3

© OMICRON 2019 Page 16 of 50


5.3 Asset: Tap Changers

If the transformer you would like to test has a de-energized and/or load tap changer, click on the “Tap
changers” tab in the “Asset” section, as shown in Figure 17. If the transformer you would like to test
does not have a tap changer, then please proceed to the next section.

If the transformer has a load tap changer, select the OLTC


option
If the transformer has a no-load/de-energized tap changer,
select the DETC option

Figure 17: Asset- Tap Changer Section

As an example, let’s say that you would like to test a transformer that has the following tap changer
configuration,
> Load Tap Changer (OLTC): 16R-16L located on the low-voltage winding
> No-Load Tap Changer (DETC): 1-5 located on the high-voltage winding

Then, the “Tap Changers” section would be populated as shown in Figure 18.

© OMICRON 2019 Page 17 of 50


It is only required to populate the “Voltage tables” if the
turns-ratio test is going to be performed. Otherwise, it
is for documentation only.

Please see the notice below.

Figure 18: Tap Changer Section - Part 2

NOTICE

For Leakage Reactance Testing Only

 Once the Tap Changer information is complete, click the “Transformer” tab and scroll down
to the leakage reactance section. Then, populate the OLTC and/or DETC position that the
factory short-circuit impedance test was performed on (most likely the nominal tap
positions).

© OMICRON 2019 Page 18 of 50


5.4 Asset: Surge Arrester

If the transformer has surge arresters that you would like to test, click on the “Surge arresters” tab in
the “Asset” section, as shown in Figure 19. Note, the surge arrester nameplate information is only
required if you would like to perform a watts loss test on the surge arresters. Otherwise, entering the
arrester information is for documentation.

Figure 19: Surge Arrester Nameplate

To enter the nameplate information for one or more surge arresters, click the box next to the surge
arrester that you would like to add to the test plan.

 Input the following critical information to correctly perform a watts loss test by using PTM,
 The number of individual units in the surge arrester stack
 The rated line-to-ground voltage of the surge arrester(s)
 The test voltage for the arrester. We recommend that the test voltage does not
exceed 20% of the rated line-to-ground voltage for each arrester.

Enter the rated line-to-ground voltage of the arrester.


PTM uses this value to determine the test voltage.
The test voltage will be 20% of the rated line-to-
Complete the “Units in stack” field ground voltage. If the calculated voltage is larger than
10 kV, the software will automatically default the test
voltage to 10kv.

Figure 20: Surge Arrester Nameplate

© OMICRON 2019 Page 19 of 50


5.5 Asset: DGA Trending

The DGA Trending Tab documents all available “Oil Analysis” tests in PTM associated with the asset.
This tab is only available if the license has been purchased. It is only populated if at least two oil
analyses are available for the asset. It assesses DGA results using interpretation methods such as
Duval’s triangles or gas ratio methods according to IEEE C57.104 and IEC60599.

Figure 21: DGA Trending Example

© OMICRON 2019 Page 20 of 50


6 Test Plan Creation
Once all the nameplate information for the transformer, bushings, tap changers, and surge arresters
have been completed, click on the “Tests” tab located on the left panel of the PTM software. Once
the “Tests” tab is selected, the PTM software will automatically generate the “recommended” test
plan, based on the nameplate information that was entered in the “Asset” section. Please populate
the test plan by following the guidelines provided in Figure 22.

List of all available tests that can be performed on This column is the current “Test Queue” This column
this transformer, based on the nameplate information and corresponds to the tests shown in represents global
entered in the Asset section. The tests shown the left panel of the PTM software. test settings that
depend on the test set selected. can be applied to
To remove a test from the “Test Queue”, specific tests. For
If you would like to add one or more tests to the “Test click the “X” to the right of the name of example, the
Queue”, simply click the plus (“+”) symbol to the right the test you would like to remove. temperatures
of the test you would like to add. entered below
The tests in the “Test Queue” can be
can be used to
Tests that have a yellow star to the left of their name arranged in any order that you would like.
temperature
(e.g. “Surge Arrester Watt Losses H” shown in Figure Simply click and drag the name of the
correct the power
21) are tests that are highly recommended, but not test you would like to move up or down
factor
currently in the “Test Queue”. the “Test Queue”.
measurements.

Figure 22: Tests Section -TESTRANO 600 Example

Once the test plan has been created, you are ready to begin testing! Use the left panel of PTM to
select the test which you would like to perform first. Note, the tests can be performed in any order
that you would like. In addition, you can add more tests to the “Test Queue” at any time by clicking on
the “Tests” tab and populating the desired tests (as shown in Figure 22).

© OMICRON 2019 Page 21 of 50


7 Tests

7.1 Overall PF & Cap Test

Both the TESTRANO 600 and CP TD1 are required. Before beginning the overall power factor test,
please consider the following,
 Properly isolate the bushing terminals from any cable, bus-bar, support insulator, surge
arrester, etc.
 Properly ground the transformer tank, TESTRANO 600, and CP TD1
 Short-circuit all high-voltage bushings, including the neutral (if applicable)
 Short-circuit all low-voltage bushings, including the neutral (if applicable)
 Short-circuit all tertiary bushings, including the neutral (if applicable)
 Remove all in-service grounds from all the neutral bushings
 Place the load tap changer in any off-neutral tap position (Note: when investigating a failure, it
is recommended to leave the LTC in the as-found position)
 Clean and dry the surface of all bushings.
o If the bushings have a porcelain exterior, use Windex or Colonite
o If the bushings have a silicone exterior, use a clean, dry rag
 Do not test under the following conditions to avoid bad test results
o Rain
o High-humidity situations
o Oil temperatures close to or below 5ºC

Once these considerations have been confirmed, connect the test set leads to the transformer by
using the connection diagram.
 Ensure the HV cable is “in the clear”. The last two feet of the HV cable should not touch any
surface of the transformer ( transformer tank, the bushing surfaces, etc.)

Note, the connection diagram may change depending on which block of the power factor test you are
trying to complete (i.e. “Injection at X” vs “Injection at H”). Consider an overall power factor test on a
two-winding transformer. First, the user would perform an “Injection at H” test, as shown in Figure 23.

© OMICRON 2019 Page 22 of 50


Figure 23: Two-Winding Power Factor Test – Injection at H Connection

Once the “Injection at H” test is completed, the user would proceed to the “Injection at X” test and use
the test connections shown in Figure 24.

Figure 24: Two Winding Power Factor Test – Injection at X Connection

Once the test considerations and test connections have been verified for the overall power factor test,
scroll down to the “Settings and conditions” section to verify the proper test settings for the test.

© OMICRON 2019 Page 23 of 50


If you would like to perform the power factor frequency sweep, then click Global test conditions entered in the “Tests”
the dropdown box and select “OMICRON expertise”. section are automatically transferred here.
These global temperatures can be overridden
If you would like to perform the power factor voltage sweep (aka the by selecting the “Custom test conditions”
voltage tip-up test), then select the dropdown box and select “OMICRON option, and manually entering the test
expertise”. conditions.

To temperature correct the measured power factor values to 20°C, select the “Temperature
correction” option. Then, by using the dropdown box, select the temperature type (e.g. top
oil temp., average oil temp, etc…) that you would like to use for the correction. The
temperature correction factors are no longer supported by any standard. We
recommend not to temperature correct, as results may be misleading.
You must click “Calculate” to apply the correction factor to the measured test results.
We recommend that you click the “Use reference voltage” field, which will automatically
correct all power factor measurements to 10kV and unlock a few key features, such as the
cross-check feature.

Figure 25: Overall Power Factor Settings and Condition

Once the desired test settings have been confirmed, scroll down to the “Assessment” section.

NOTICE
Enabling the assessment feature

 Please note that the assessment feature will only be available if the following conditions are met,

1. The insulating medium of the transformer has been selected in the “Asset – Transformer -
Others” section
2. The “Temperature correction” feature has been enabled (as shown in Figure 25)

© OMICRON 2019 Page 24 of 50


Select the standard (IEEE or
IEC) that you would like to
use to auto-assess your
power factor results.
Note, custom limits can be
set by selecting the
“Customer specific limits”
option.

Select the “Assess during


measurements” option if you
would like PTM to assess your
test results in real-time. If this
feature is not enabled, the user
will have to manually select the
“Assess measurements” field,
once the test is complete to
auto-assess the test results.

Figure 26: Assessment – Overall Power Factor

Once the “Assessment” section has been completed, scroll down to the “Measurements” section.

NOTICE
Locked in asset data after performing measurement

 Please note that once a measurement within this job has been performed many of the
fields within the “Asset” section will be locked and inaccessible. Therefore, it is critical that
all the “Asset” (i.e. the nameplate) information is correct before performing the first
measurement. In addition, please verify that the “Settings and conditions” section is correct
before performing the first measurement.

© OMICRON 2019 Page 25 of 50


First, click on the measurement shown in “row No. 1”, as highlighted in Fig.27. Once the proper test
connections are made for the “row No. 1” measurement, select the “Start all” option for the “Injection
at H” test. If the “Start all” option is not green, then the user must connect the TESTRANO 600 to
their laptop before beginning the test.

Once all measurements for the “Injection at H” section are complete, click on the measurement for
“row No. 4”, as highlighted in the following image. Once the proper test connections are made for the
“row No. 4” measurement, select the “Start all” option for the “Injection at X” test. If the “Start all”
option is not green, then the user must connect the TESTRANO 600 to their laptop before beginning
the test.

Cross check #1: Once the measurement is complete, compare


the measured current, watts, power factor, and capacitance from
row(s) No. 3 to the “Cross check: calculated ICHL” row, which
should be approximately equal.

Cross check #1: Once the measurement is complete, compare


the measured current, watts, power factor, and capacitance from
row(s) No. 6 to the “Cross check: calculated ICLH” row, which
should be approximately equal.

Cross check #2: Compare the current, watts, power


factor, and capacitance for the ICHL and ICLH
measurements, which should be approximately
equal.

Figure 27: Overall Power Factor - Measurements

Once the power factor measurements are complete, perform the two “sanity checks” to verify the
validity of the test results. The two “cross check” features are enabled after checking “Use reference
voltage” box in the “Settings and conditions” section to correct the measured values to 10kV. The two
“sanity checks” that must be performed include,
• Cross check #1: calculated ICHL/ICLH vs measured ICHL/ICLH (see comments in Figure 27)
• Cross check #2: measured ICHL vs ICLH (see comments in Figure 27)
If either of the two sanity checks are not valid, then investigate the following possibilities, and repeat
the test,
• Poor test connection, poor ground connection, and/or poor test procedure
• Possible voltage sensitive defect within insulation (please repeat test and perform the voltage
sweep)

© OMICRON 2019 Page 26 of 50


7.2 Bushing PF & Cap- C1 Test

Both the TESTRANO 600 and CP TD1 are required. Before beginning the bushing C1 power factor
test, please consider the following,
 Properly isolate the bushing terminals from any cable, bus-bar, support insulator, surge
arrester, etc.
 Properly ground the transformer tank, TESTRANO 600, and CP TD1
 Ensure the bushings remain short circuited as in the Overall PF test
 Remove all in-service grounds from all the neutral bushings
 Clean and dry the surface of each bushing before testing
o If the bushings have a porcelain exterior, use Windex or Colonite
o If the bushings have a silicone exterior, use a clean, dry rag
 Do not test under the following conditions to avoid bad test results
o Rain
o High-humidity situations
o Oil temperatures close to or below 5ºC
 Confirm the Test Mode is UST-A (automatically configured by PTM)
 Confirm the Test voltage does not exceed line-to-ground voltage rating of bushing
(automatically configured by PTM)
 Remove one bushing tap cap at a time (i.e. only for the bushing currently under test)
Once these considerations have been confirmed, connect the test set leads to the apparatus by using
the connection diagram in PTM,
 Place High-voltage lead on bushing center-conductor and Red-A lead on bushing test or
potential tap
 Ensure the HV cable is “in the clear”. The last two feet of the HV cable should not touch any
surface of the transformer (transformer tank, the bushing surfaces, etc.)

Figure 28 shows the test connections for a C1 power factor test for the H1 bushing. Note, the
connection diagram may change depending on which bushings you are testing. Once the proper test
considerations and test connections have been confirmed, scroll down to the “Settings and
conditions” section.

Figure 28: H1 C1 Power Factor – Test Connections

© OMICRON 2019 Page 27 of 50


If you would like to perform the power factor frequency sweep, then click the
dropdown box and select “OMICRON expertise”.
If you would like to perform the power factor voltage sweep (i.e. the voltage
tip-up test), then click the dropdown box and select “OMICRON expertise”.

Figure 29: Bushing C1 Power Factor – Settings and Conditions

Once the desired test settings have been confirmed, scroll down to the “Assessment” section.

NOTICE
Locked in Asset Data after performing measurement

 Note, once a C1 power factor measurement has been completed, many of the “Settings
and conditions” fields will be locked and cannot be changed, so please verify that the
settings are correct before proceeding.

NOTICE

Enabling the assessment feature

 Please note that the assessment will only be available if the insulation type of the bushing
was selected in the “Asset - Bushings” section of the PTM software (see Figure 16).

© OMICRON 2019 Page 28 of 50


Select the standard (IEEE or IEC)
that you would like to use to auto-
assess your bushing power factor
results.
Note, custom limits can be set by
selecting the “Customer specific
limits” option.

Select the “Assess during measurements”


option if you would like PTM to assess your
test results in real-time. If this feature is not
enabled, then the user will have to manually
select the “Assess measurements” field, once
the test is complete.

Note, if the nameplate C1 power factor and capacitance values are entered in the “Asset - Bushings” section, then the
assessment will be performed by comparing the measured values to the nameplate values. However, if the nameplate values
are not available, the assessment will be performed by comparing the measured values to absolute limits.

Figure 30: Bushing C1 Power Factor – Assessment Section

Once the “Assessment” section is complete, scroll down to the “Measurements” section and select the
“Start” option for the measurement you would like to perform. For example, selecting the “Start”
option highlighted in Figure 31 would begin the H1 C1 power factor test. Note, if the “Start” option is
not green, then the user must connect their laptop to the TESTRANO 600 to begin the test.

© OMICRON 2019 Page 29 of 50


If the nameplate C1 power factor and capacitance
values were entered in the “Asset - Bushings”
section, then they will automatically be transferred
and displayed in the following fields.

Figure 31: Bushing C1 Power Factor – Measurements Section

Once all the bushing C1 Power Factor measurements are complete, the user should verify the validity
of the measurements, before proceeding to the next test. To help confirm the validity of the test
results consider the following,

• Are the capacitance values for each bushing > 200pF? Typically, the measured capacitance
for a bushing C1 power factor test is >200pF.
• Do the measured capacitance values compare well to the nameplate capacitance values?
They should compare well.
• Do the measured capacitance values of each bushing compare well to each other? (assuming
they are the same make, model, etc…) They should compare well.
If the measurements do not appear to be valid, then consider the following possibilities, and repeat
the test,
• Poor test connection, poor grounding, and/or poor test procedure (please see
considerations at the beginning of the section)

© OMICRON 2019 Page 30 of 50


7.3 Bushing PF & Cap- C2 Test

Both the TESTRANO 600 and CP TD1 are required. Before beginning the bushing C2 power factor
test, please consider the following,
 Properly isolate the bushing terminals from any cable, bus-bar, support insulator, surge
arrester, etc.
 Properly ground the transformer tank, TESTRANO 600, and CP TD1
 Ensure the bushings remain short circuited as in the Overall PF test
 Clean and dry the test tap area of each bushing before testing
 Confirm the Test Mode is GSTg-A (automatically configured by PTM)
 Confirm the correct test voltage for the C2 power factor test depending on whether the
bushing has a test (500V) or potential (2000V) tap.
Once these considerations have been confirmed, connect the test set leads to the apparatus
according to the connection diagram in PTM,
 Place the High-voltage lead on test or potential tap of bushing. The high-voltage lead adapter
shown in Figure 32 should be used to help make the test connection to the bushing tap.
 Place the Red-A lead on center-conductor of bushing
 Ensure the HV cable is “in the clear”. The last two feet of the HV cable should not touch any
surface of the transformer (transformer tank, the bushing surfaces, etc.)

Figure 33 shows an example test connection for a C2 power factor test for the H1 bushing. Note, the
connection diagram may change depending on which bushings you are testing. Once the proper test
considerations and test connections have been confirmed, scroll down to the “Settings and
conditions” section.

Figure 32: High-Voltage Lead Adapter for C2 Power Factor

© OMICRON 2019 Page 31 of 50


Figure 33: C2 Power Factor – H1 Test Connections

For the bushing C2 power factor test, only the line


frequency (60Hz) measurement is performed.

Figure 34: C2 Power Factor Test Settings

© OMICRON 2019 Page 32 of 50


Select the standard (IEEE or IEC) that you would like to
use to auto-assess your bushing power factor results.
Note, custom limits can be set by selecting the
“Customer specific limits” option.

Select the “Assess during measurements” option if you


would like PTM to assess your test results in real-time. If
this feature is not enabled, then the user will have to
manually select the “Assess measurements” option, once
the test is complete.

Note, if the nameplate C2 power factor and capacitance values are entered in the “Asset” section, then the assessment will be
performed by comparing the measured values to the nameplate values. However, if the nameplate values are not available, the
assessment will be performed by comparing the measured values to absolute limits.

Figure 35: C2 Power Factor Test – Assessment Section

Once the “Assessment” section is complete, scroll down to the “Measurements” section and select the
“Start” option for the measurement you would like to perform. For example, selecting the “Start”
option highlighted in Figure 36 would begin the H1 C2 power factor test. Note, if the “Start” option is
not green, then the user must connect their laptop to the TESTRANO 600 to begin the test.

In this example, notice that the


Verify the correct test voltage: nameplate C2 power factor and
capacitance values are not shown in
Test Tap ( ≤350kV BIL ) = 500V
the table, because they were not
Potential Tap ( > 350kV BIL ) = 2000V populated in the “Asset - Bushings”
section.

Figure 36: C2 Power Factor – Measurements

© OMICRON 2019 Page 33 of 50


Once all the bushing C2 Power Factor measurements are complete, the user should verify the validity
of the measurements, before proceeding to the next test. To help confirm the validity of the test
results consider the following,

• Are the capacitance values for each bushing > 200pF? Typically, the measured capacitance
for a bushing C2 power factor test is >200pF.
• Do the measured capacitance values compare well to the nameplate capacitance values?
They should compare well.
• Do the measured capacitance values of each bushing compare well to each other? (assuming
they are the same make, model, etc…) They should compare well.
If the measurements do not appear to be valid, then consider the following possibilities, and repeat
the test,
• Poor test connection, poor grounding, and/or poor test procedure (please see
considerations at the beginning of the section)

© OMICRON 2019 Page 34 of 50


7.4 Bushing Energized Collar Test

Both the TESTRANO 600 and CP TD1 are required. Before beginning the bushing energized collar
test, please consider the following,
 Properly isolate the bushing terminals from any cable, bus-bar, support insulator, surge
arrester, etc.
 Properly ground the transformer tank, TESTRANO 600, and CP TD1
 Clean and dry the surface of each bushing before testing
o If the bushings have a porcelain exterior, use Windex or Colonite
o If the bushings have a silicone exterior, use a clean, dry rag
 Confirm the Test Mode is UST-A (automatically configured by PTM)
Once these considerations have been confirmed, connect the test set leads to the apparatus by using
the connection diagram in PTM,
 Place the High-voltage lead on conductive collar. The high-voltage lead adapter shown in
Figure 32 should be used to help make the test connection to the collar.
 Placed the conductive strap tightly around the bushing under test below the top skirt
 Place the Red-A lead on center-conductor of bushing
 Ensure the HV cable is “in the clear”. The last two feet of the HV cable should not touch any
surface of the transformer (transformer tank, the bushing surfaces, etc.)

Figure 37 shows an example test connection for an energized collar test on the H1 bushing.

Note, the connection diagram may change depending on which bushings you are testing. Once the
proper test considerations and test connections have been confirmed, scroll down to the “Settings and
conditions” section.

Figure 37: Energized Collar Test Connections

© OMICRON 2019 Page 35 of 50


Select reference voltage to
determine the watt losses at a
For the bushing energized collar test, only the line different voltage value than what
frequency (60Hz) measurement is performed. was used for the measurement.
Industry practice is to assess
watt losses at 10kV, therefore
the default reference voltage is
10 kV.

Figure 38: Energized Collar Test Settings

Once the correct test settings have been confirmed, scroll down to the “Measurements” section and
select the “Start” option for the measurement you would like to perform. For example, selecting the
“Start” option highlighted in Figure 39 would begin the H1 energized collar test. Note, if the “Start”
option is not green, then the user must connect their laptop to the TESTRANO 600 to begin the test.

Test at 12 kV unless it exceeds the rating of the bushing. If it


exceeds the rating of the bushing, test at the rated voltage of
the bushing.

Figure 39: Energized Collar Test – Measurements Section

NOTICE

Automatic assessment not possible

 Please note the energized collar test does not provide an automatic assessment. The
results of this test can be assessed by the following methods:
 Comparing the measured current and watt losses of each bushing to each other
(assuming they are the same make, model, etc…)
 Comparing the measured current and watt losses to previous test results
 Ensuring the watts losses at 10kV is <100 mW

© OMICRON 2019 Page 36 of 50


7.5 Exciting Current Test

Both the TESTRANO 600 and CP TD1 are required. Before beginning the exciting current test, please
consider the following,
 Remove all the shorting jumpers used previously in the power factor test (the exciting current
test is an “open circuit test” )
 Follow the connection diagram, and pay close attention to the external ground leads that may
be required for certain winding configurations.

Figure 40 shows the test connection for the Phase-A measurement of a DYn1 transformer. Notice that
there are two external ground leads required (H2 and X0) to complete the measurement successfully.
However, keep in mind that these ground connections may change depending on the phase being
tested. Note, the connection diagram may change once another phase is selected.

Figure 40: Exciting Current – Dyn1 Phase A Test Connection

Once the proper test connections have been made, scroll down to the “Settings and conditions”
section.

© OMICRON 2019 Page 37 of 50


If a DETC and/or LTC was entered in the “Asset – Tap Changers” section, then indicate which tap changer you would like to
change during the exciting current measurement. If a tap changer was not entered in the “Asset – Tap Changers” section, then
these fields require no action.
For example, let’s say that we would like to keep the DETC position fixed on position 3, and test from 1L-16R on the LTC, then
the settings highlighted below would be selected.
Note, once the measurement begins, the start and stop tap positions can only be changed “on the fly” if the automatic tap control
box is not selected. For example, let’s say that once I started the test, I decided that I only wanted to test the 1L, N, 1R, and 16R
positions, I can do so without stopping the measurement or altering these fields.

The test voltage is automatically populated and is based on the


voltage rating of the transformer entered in the “Asset” section.

Figure 41: Exciting Current – Settings and Conditions

Once the correct test settings have been confirmed, scroll down to the “Measurements” section.
Select the phase that you would like to test and then click the “Start” option, which is highlighted in
Figure 42. If the “Start” option is not green, then the user must connect the TESTRANO 600 to their
laptop.

The phase that you would like to test can be selected by clicking on the colored
indicator for each phase. Please note, the connection diagram will change once a
particular phase is selected.
To begin the test, click on the phase that you would like to measure, and then select
the “Start” option.

Figure 42: Exciting Current Test – Measurements Section

© OMICRON 2019 Page 38 of 50


7.6 Turns-Ratio (TTR) Test

Only the TESTRANO 600 is required. Before beginning the turns-ratio test, please consider the
following,
 This test utilizes the TESTRANO 600’s “one-time test connection”, so only one connection will
be necessary for the entire test.
 Always run the TTR test before the DC winding resistance test since a magnetized core can
affect the results.
Fig. 43 shows the wiring diagram for a DYn1 transformer using the 3-phase test connection method.

Figure 43: Turns-Ratio Test – One-Time Test Connection

Once the proper test connections have been made, scroll down to the “Settings and conditions”
section.

If a DETC and/or LTC was entered in the “Asset – Tap Changers” section, then
indicate which tap changer you would like to change during the turns-ratio
measurement. If a tap changer was not entered in the “Asset – Tap Changers” section
The default test voltage is 120V, then these fields require no action.
but can be manually changed. For example, let’s say that you would like to keep the DETC position fixed on position
Note, the maximum test voltage is 3, and test the LTC from 16R-16L, then the settings shown in Figure 44 should be
400V if the 3 x 400V Output mode selected.
is selected.
Note, once the measurement begins, the start and stop tap positions can only be
changed “on the fly” if the automatic tap control box is not selected.

Figure 44: Turns-Ratio Test – Settings and Conditions

© OMICRON 2019 Page 39 of 50


Once the correct settings have been confirmed, scroll down to the “Assessment” section.

Select the standard (IEEE or IEC) that you would like to use to
auto-assess your turns-ratio results.
Note, custom limits can be set by selecting the “Customer
specific limits” option.

Select the “Assess during measurements” option if you would like PTM
to assess your test results in real-time. If this feature is not enabled,
then the user will have to manually select the “Assess measurements”
option, once the test is complete.

Figure 45: Turns-Ratio Test - Assessment

Once the “Assessment” section is complete, scroll down to the “Measurements” section and select the
“Start” option. Note, if the “Start” option is not green, then the user must connect their laptop to the
TESTRANO 600 to begin the test.

Figure 46: Turns-Ratio Test – Measurements Section

© OMICRON 2019 Page 40 of 50


7.7 DC Winding Resistance Test

Only the TESTRANO 600 is required. Before beginning the DC Winding Resistance test, please
consider the following,
 This test utilizes the TESTRANO 600’s “one-time test connection”, so only one connection will
be necessary for the entire test. (Unless the single phase injection method is used)
 The DC Winding Resistance Test should always be followed by the Demagnetization test.

NOTICE

Selecting proper test current

 Please note that the DC winding resistance test can be “stubborn” at times due to
difficulties with saturation of the core. The measurement can still be completed in a
reasonable amount of time if the test current is set correctly. A good guideline is to set the
test current between 10% and 15% of the rated winding current. This applies enough
current to easily saturate the core, without heating up the winding. Typically, we
recommend 5A for the H winding and 25A for the X winding, as long as current ratings of
the windings are not exceeded.

The TESTRANO’s “one-time test connection” for a DYn1 transformer is displayed in fig. 47.

Figure 47: DC Winding Resistance – One-Time Test Connection

Once the proper test connections have been made, scroll down to the “Settings and conditions”
section.

© OMICRON 2019 Page 41 of 50


“Automatic result”: The resistance measurement will be automatically recorded
once the resistance has stabilized based on the selected criteria (i.e. based on
the “Tolerance R dev” and “Settling time”).
The “Output mode” will allow you to switch
between the 16A @ 340V, 33A @ 170V, The “Tolerance R dev” is the maximum deviation percentage that the
and 100A @ 56V modes (single phase resistance can change over the given “Settling time”, before the measurement
injection). The test current can then be is recorded. The lower the tolerance deviation, the more accurate the
adjusted depending on the mode selected. measurement, but also the longer the test may take.
The “Settling time” can also be increased to increase the accuracy of the
measurement; however, we recommend keeping the default value of 5s.

Figure 48: DC Winding Resistance – Settings and Conditions

NOTICE
Compromised results possible if measurement not stable

 Please note that it is critical that the resistance measurement stabilizes before the
measurement is recorded, so if the “Automatic result” feature is enabled (see Figure 48),
we recommend not changing the default setting of .01% for the “Tolerance R dev” any
higher than 0.05%.

Once the correct settings have been confirmed, scroll down to the “Assessment” section.

Select the standard (IEEE or IEC) that you would like to use to auto-assess your winding
resistance results. Note, custom limits can be set by selecting the “Customer specific
limits” option.

Select the “Assess during measurements” option if you would like PTM to assess your test
results in real-time. If this feature is not enabled, then the user will have to manually select
the “Assess measurements” option, once the test is complete.

Figure 49: DC Winding Resistance - Assessment

© OMICRON 2019 Page 42 of 50


Once the correct settings, test connections, and assessment have been confirmed, scroll down to the
“Measurements” section and click the “Start” option. If the “Start” option is not green, then the user
must connect the TESTRANO 600 to their laptop.

Figure 50: DC Winding Resistance Test – Measurements Section

© OMICRON 2019 Page 43 of 50


7.8 Demagnetization Test

Only the TESTRANO 600 is required. Before beginning the Demagnetization Test, please consider
the following,
 This test utilizes the TESTRANO 600’s “one-time test connection”, so only one connection will
be necessary for the entire test.
 This test is used to reduce the amount of residual magnetism in the transformer core, not to
analyze the health of the transformer. It is typically performed after events which magnetize
the core (i.e. after a DC Winding resistance test or if transformer taken out of service has
experienced a fault)
The test connection example shown in figure 51 displays the wiring diagram for a DYn1 transformer.

Figure 51: Demagnetization Test – One-Time Test Connection

Once the proper test connections have been made, scroll down to the “Settings and conditions”
section. The demagnetization test should be run at the same
test current as the high-side DC winding resistance
test (below 15% of rated winding current).

Figure 52: Demagnetization Test – Settings and Conditions

Once the correct settings and test connections have been confirmed, scroll down to the
“Measurements” section and click “Start”. If the “Start” option is not green, then the user must connect
the TESTRANO 600 to their laptop.
Remanence: the residual magnetism remaining in the core after the test has been completed.
Initial remanence: the residual magnetism in the core when the test was started.

Figure 53: Demagnetization Test – Measurements Section

© OMICRON 2019 Page 44 of 50


7.9 Leakage Reactance Test

Only the TESTRANO 600 is required. The leakage reactance test consists of two test types, which
include,
• 3-Phase Equivalent Test: The purpose of this test is to reproduce the factory short-circuit
impedance value. Therefore, once the 3-phase equivalent measurement is performed,
the PTM software will automatically calculate and compare the measured field value to
the nameplate value. The factory short-circuit impedance value can typically be found on
the nameplate of the transformer, as shown in the example in Figure 54.

• Per-Phase Equivalent Test: The results from this test may not compare well to the
nameplate short-circuit impedance, but it is valuable because it helps isolate and test one
individual phase at a time, to identify a fault localized to one phase. The PTM software
will automatically compare the results among phases.

NOTICE

Improper shorting jumpers may affect results

 Please note that it is critical that the resistance and reactance of the shorting jumpers used
to short-circuit the secondary (or tertiary) of the transformer is negligible relative to the test
circuit. We recommend using a wire gauge of #4 or less. In addition, the length of the
shorting jumpers should be as short as possible from bushing terminal to bushing terminal.
Finally, the shorting jumpers should be solidly bonded to the bushing terminals, to avoid
creating additional resistance within the test circuit.

NOTICE

Incorrect tap position in asset settings may affect assessment

 Please note that to compare the measured 3-phase equivalent value to the factory short-
circuit impedance, the DETC and/or LTC must be tested on the same tap position(s) as the
factory. Otherwise, the measured field values and nameplate values may not compare
well.

Please follow the connection diagram closely when changing between phases, and the two test types
outlined above.

© OMICRON 2019 Page 45 of 50


Figure 54: Nameplate Short-Circuit Impedance Example

An example wiring diagram for a 3-Phase Equivalent Test on a DYn1 transformer is shown in figure
55.

Figure 55: Leakage Reactance Test – 3-Phase Equivalent Connection

Once the proper test connections have been made, scroll down to the “Settings and conditions”
section.

© OMICRON 2019 Page 46 of 50


The measured resistance values can be temperature corrected by selecting the “Temperature
correction” field. If the winding temperature was previously entered in the global test conditions
section, it will automatically be transferred and applied. However, if the winding temperature
was not entered, the user must select the “Custom test conditions” option and manually enter
the temperature that they would like to correct from.
To enable the leakage reactance auto-assessment, the measurements must be temperature
corrected.

The default “Test current” is 1A, but may need to be


increased depending on the measured impedance (See
notice “Selecting the appropriate test current on pg.48).

Figure 56: Leakage Reactance Test – Settings and Conditions

NOTICE

Enabling the auto-assessment

 Please note that to enable the leakage reactance auto-assessment, the following
conditions must be met,
 The “Temperature correction” setting must be enabled as shown in Figure 56.
 The DETC and/or LTC position(s) selected on the transformer must be identical to
the DETC and/or LTC position(s) entered to the “Asset – Transformer - Leakage
Reactance” section (Figure 11, 57).
 The nameplate short-circuit impedance, base power, and base voltage must be
entered in the “Asset – Transformer - Leakage Reactance” section (shown in
Figure 11, 57).

Figure 57: Leakage Reactance – Asset Information

© OMICRON 2019 Page 47 of 50


Once the test settings have been verified, scroll down to the “Assessment” section.

Select the standard (IEEE or IEC) that you would like to use to auto-assess your leakage reactance results. Note,
custom limits can be set by selecting the “Customer specific limits” option.

Figure 58: Leakage Reactance – Assessment

Select the “Assess during measurements” option if you would like PTM to assess your test results in real-time. If this
feature is not enabled, then the user will have to manually select the “Assess measurements” option, once the test is
complete.

Once the “Assessment” section is complete, scroll down to the “Measurements: 3Ph equiv.” section.
When you are ready to begin the test, click the “Start” option.

NOTICE

Selecting the appropriate test current

Adjust the “Test current” (fig.56) depending on the measured impedance of the transformer. We
recommend performing the first measurement at a “Test current” of 1A, and monitoring the
measured voltage during the line-frequency (60Hz) test. We recommend that the measured
voltage at 60Hz is >50V. If the measured voltage is <50V, then increase the test current and
repeat the test until one of the following occurs,
• The measured test voltage is >50V (at 60Hz)
• The “Test current” has reached 5A

© OMICRON 2019 Page 48 of 50


Choose the current position of the Once the measurement is complete, PTM will automatically calculate the
DETC/LTC which the transformer will measured impedance percentage (“Zk calc”), provided that the base power and
be tested on. The entries are base voltage were entered in the “Asset – Leakage Reactance” section (Fig.57).
automatically populated from the
entered values in the asset section If the transformer was tested on the same tap position(s) as the factory short-
(fig.11,57) circuit impedance test, then PTM will also populate the “Zk” field with the
nameplate value.

Figure 59: Leakage Reactance – Measurements (Three Phase)

Once the 3-phase equivalent measurement is complete, please select the “Measurements: per-
phase” tab. Next, select the Phase-A measurement by clicking on the corresponding colored
indicator in the “Phase selection” menu, and observe the connection diagram to make the correct test
connections. An example of a per-phase equivalent test connection is shown in Figure 61. When you
are ready to begin the test, click the “Start” option next to the “Phase selection” menu as shown in
Figure 60. Repeat this procedure for the remaining phases (i.e. B and C), keeping in mind that the
connection diagram may be different for each measurement.

Once the measurement for all three phases is complete, the software will
calculate the average impedance of each phase, and then compare each phase
to the average. Typically, we recommend that all three phases compare to within
2% of the average, to pass the per-phase leakage reactance test.

Figure 60: Leakage Reactance – Measurements (Per Phase)

Figure 61: Leakage Reactance – Per Phase Connection (Phase A)

© OMICRON 2019 Page 49 of 50


Support
When you are working with our products we want to provide you with the greatest possible
benefits. If you need any support, we are here to assist you.

24/7 Technical Support – Get Support


www.omicronenergy.com/en/support
At our technical support hotline, you can reach competent, well-educated technicians for all
of your questions. Around the clock and free of charge.
Make use of our 24/7 international technical support hotline:
Europe / Middle East / Africa +43 59495 4444
Americas +1 713 830-4660 +1 800-OMICRON
Asia-Pacific +852 3767 5500
Additionally, on our website you can find our Service Center or Sales Partner closest
to you.

Customer Portal – Stay Informed


https://my.omicronenergy.com/
The Customer Portal on our website is an international knowledge exchange platform.
Download the latest software updates for all our products and share your own experiences
in our user forum.
Browse through the knowledge library and find application notes, conference papers,
articles about daily working experiences, user manuals and much more.

OMICRON Academy – Learn More


www.omicron.academy
Learn more about your product in one of the training courses offered by the OMICRON
Academy.

For more information, additional literature, and


detailed contact information of our
offices worldwide please visit our website.

© OMICRON
www.omicronenergy.com Subject to change without notice.

You might also like