Critical Power
8 SPECIFICATIONS
VH Series : 700 1000 1500 2000 3000
Ratings
Voltage Amperes (VA) with computer type load : 700 1000 1500 1920 3000
Watts (W) with resistive load : 630 900 1350 1740 2700
Input thermal circuit breaker (A) : 8 12 18 20 30
Internal input fuse 250V, slow (A) : 15 15 30 30 30
Input converter
AC input voltage : 60 - 140 V
Input current waveform : sinusoidal, EN 61000 -3-2 (IEC 555-2) compliant
Input current (A) at nominal input voltage : 6.6 9.1 13.9 16 24
Input power factor : 1
Input frequency range : 45 - 66 Hz
Inrush current : none
Output converter
AC output voltage : 100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance : ± 2%
Output frequency : auto selectable or 50 / 60 Hz, front selectable
Output frequency range : nominal ± 0.05% unless synchronized to the mains
Output waveform : sine wave
Harmonic distortion : < 1% with linear load
Power factor : 0.9
Crest factor (peak to RMS current) : suitable for loads with c.f. up to 3:1
Capacity appliance outlets : max. 20A per outlet (+ 1 high power outlet max. 20A, on 2000VA model only)
(+ 1 high power outlet max. 30A, on 3000VA model only)
Bypass
AC input voltage range : selected output voltage -15% to +10%
Frequency tracking rate : 2 Hz/sec.
Frequency tracking range : nominal ± 10% / ± 2% selectable
Phase difference : < 1º typical (max. 7º during tracking frequency range)
Typical transfer time, msec : 1
Battery pack
Nominal voltage (Vdc) : 36 36 72 72 72
Max. Number / Ah battery extension pack : 3/14 3/14 3/14 3/14 3/14
Weight (lbs/kg) : 60/27 101/46
Dimensions (HxWxD) : 3.4x17.2x18.5inch 3.4x17.2x21.3 inch
: 87x438x470 mm 87x438x540 mm
Environment
Safety : UL 1778, 5th Edition
Electromagnetic compatibility : EN 62040-2
Ambient temperature : 32 to 104ºF (0 to +40ºC)
Audible noise at 1 meter : < 45 dB(A), load and temperature dependent
Max. relative humidity : 95% (non-condensing)
QUITO: Elia Liut N45-26 y Edmundo Chiriboga Telf: 02 3936 400 CELULAR: 09 9610 8549